Liebert® XDF Air-Cooled Product Application Guidelines To ensure successful installation and proper operation of the Liebert® XDF air-cooled unit, please adhere to the guidelines below. If questions remain after reviewing these guidelines, please contact Emerson Network Power, at 1-800-222-5877 to speak with an application specialist. Application Question Can the Liebert XDF be installed in any size room? Requirements The air-cooled, self-contained XDF is intended to be used in an open room. If no ducting is used, a minimum room size of 1600 sq ft is required. Comments Additional air exchange to a large space (for example, via an open door) is recommended whenever possible. How much heat will the Liebert XDF exhaust and how should it be removed? The self-contained Liebert XDF produces 2700 CFM of airflow with up to 68,000 BTU of heat load and an air temperature increase of up to 25°F. This heat must be removed by the building system serving the room in which the self-contained XDF is installed. Inadequate exchange of condenser air will cause recirculation and will adversely affect performance. Ducting or a water-cooled Liebert XDF should be considered if adequate airflow and heat removal aren’t available. Should the exhaust air be ducted? In applications where the room volume is small, the condenser exhaust air should be ducted. The Liebert XDF condenser fan is optimized for open discharge, not for ducting, so a booster fan should be used in most applications to ensure adequate exhaust airflow. Please consult a contractor to determine the appropriate booster fan requirements given the ducting that will be installed at your site. Ducted condenser air can significantly increase back-up ventilation time. When ducting the exhaust, the condenser fan power source should be modified to ensure the condenser fan runs during back-up ventilation mode. Please reference the Liebert XDF user manual (SL-17010) available at www.liebert.com for instructions. How much make-up air is required for this unit? If ducting is used, a make-up air source must be provided. 2700 CFM of air, between 35°F and 104°F is required. Insufficient make-up air will reduce condenser airflow and will adversely affect performance. If adequate make-up air is not available, the water-cooled Liebert XDF should be used. In what ambient temperature can the Liebert XDF operate effectively? Can the unit be operated in a highhumidity environment? The ambient temperature should be between 35°F and 104°F. Ambient temperature will affect the capacity of the Liebert XDF. Temperatures above 95°F begin to reduce the XDF’s capacity. The unit can be operated anywhere from 20% RH to 80% RH. High humidity will impact the cooling capacity of the Liebert XDF. Conditions with a dew point above 60°F (31% RH at 95°F, or 60% RH at 75°F) will begin to reduce the XDF’s sensible cooling capacity. Liebert XDF Air-Cooled Product Application Guidelines 1 SL-17007_Rev3_09/08 Liebert® XDF Air-Cooled Product Application Guidelines Application Question How will condensate be removed? Requirements Condensate created via the cooling process should be fed into a gravity drain or pumped away with an optional, factoryinstalled condensate pump. Comments The condensate pump will increase the distance the condensate can be run from the unit to approximately 30 horizontal feet and/or 12 vertical feet. Should cable entrances be sealed? Yes, cables entrances should always be sealed. What is the minimum room size in which the Liebert XDF can be operated? The smallest acceptable room dimensions based solely on 36” service clearances on the side, top, front and rear are: • 10’D x 5’10”W x 9’10”H • 574 cubic feet If cables are not sealed, air infiltration will adversely affect unit performance and allow contaminants inside the cabinet. Without ducting, the minimum room size the XDF should be operated in is 1600 sq ft. If ducting is used, the room size requirement is minimal, but makeup air must be considered (per the guidelines above). The volume of the room will also impact the back-up ventilation time. Refer to the table on page 3 for more information. In what type of environment can the Liebert XDF be operated? Environments containing caustic or explosive vapors are not acceptable for this product. The backup ventilation mode of the XDF will circulate room air through the cabinet. What equipment heat load can this unit accommodate? The equipment load should be between 3 kW and 14 kW. Equipment load will also impact back-up ventilation time. Refer to the table on page 3 for more information. What is the power requirement for this unit? Two power connections are required: • 120/208V 3-ph (NEMA L21-30P), and • 120V 1-ph (NEMA 5-15P) Please ensure 3-ph power (4 wires + ground) is available to the room in which the Liebert XDF will be located. How much sound will the Liebert XDF make? The sound power of the Liebert XDF air-cooled unit is 86 dBA (slightly louder than a fully configured IT rack). The water-cooled Liebert XDF has a lower sound level than the Liebert self-contained, aircooled XDF (79 dBA compared to 86 dBA) and is recommended for applications in which people are working full-time in the same area. How will I be able to control and monitor my Liebert XDF? Liebert XDF comes standard with an iCOM monitor and control module. An optional webcard can be ordered for remote viewing and control via SNMP. What type of backup power is recommended to be used with this unit? A true on-line, doubleconversion UPS is recommended. It is recommended that the Liebert XDF 1-ph power connection be plugged into UPS backup power to ensure the backup ventilation system allows ample time for safe automated shutdown of IT equipment in the event of an outage. Liebert XDF Air-Cooled Product Application Guidelines 2 SL-17007_Rev3_09/08 Liebert® XDF Air-Cooled Product Application Guidelines Backup Ventilation System The back-up ventilation system in the Liebert XDF circulates room air through the cabinet in case of a power failure or interruption of cooling inside the XDF. The size of the room, the temperature of the room, and the heat load inside the XDF all affect the amount of back-up ventilation time available. The table below contains estimates of the time until the internal rack equipment reaches 95°F (with back-up ventilation running and Liebert XDF cooling off). Room Volume (Cubic Feet) 1,200 2,400 5,000 7,500 10,000 6 kW Load 2 minutes 4 minutes 8 minutes 12 minutes 15 minutes 10 kW Load 1 minute 2 minutes 5 minutes 7 minutes 9 minutes 14 kW Load 45 seconds 1.5 minutes 3 minutes 5 minutes 6 minutes NOTE - The following assumptions apply: • Liebert XDF controls and internal fans continue to run during back-up ventilation. This may require that they be powered from a separate back-up power source. This back-up power source must have sufficient run time. • The temperature in the room is 75° F when back-up ventilation begins operating. • No cooling is done by the building system during the back-up ventilation. If the building cooling system continues to run during backup ventilation, the time to reach 95°F will be longer. Additional Information Additional information related to specifying, engineering, and installing a Liebert XDF cooling solution is available in the following documents. The documents can be accessed at www.liebert.com by entering the SL number listed below into the search bar: • Liebert XDF User Manual, SL-17010 • Liebert XDF Guide Specification, SL-17015 Liebert XDF Air-Cooled Product Application Guidelines 3 SL-17007_Rev3_09/08