Solutions For Business-Critical Continuity™ Smart Solutions Reference Guide 1100kW Tier 2 With Air Economization Design Reference Guide: 1100kW Tier 2 With Air Economization Intelligent, Integrated Infrastructure for the Data Center The SmartDesign from Emerson Network Power uses a perimeter/room-based approach to deliver efficiency, availability, capacity and control, that allows you to be prepared for what’s next. Our approach helps to create, maintain and grow data centers that meet customer challenges through innovative systems, industry-best practices and local data center specialists who fully understand how to solve these problems. This sample reference scenario, 1100kW Tier 2 With Air Economization, illustrates one possible example of how the SmartDesign approach can be used to create a high-performance IT infrastructure. SmartDesign Approach: Lower energy bills by $112,000/yr Deliver impressive PUE: 1.21 Save 38% in OPEX Save 33% in floor space 1+N Distributed Bypass Architecture Leverage density of 12 kW/rack Improve flexibility and scalability Reduce rack needs by 43% Common Data Center Challenges: Limited availability and capacity SmartDesign Benefits: Insufficient and inefficient cooling capabilities Proven power solutions that deliver efficiency, scalability, and availability Piecemeal infrastructure that is difficult to manage Precision cooling that controls the temperature, humidity and airflow Space constraints Effective monitoring and control Energy inefficiencies Efficient space utilization Budgetary constraints Improved PUEs Complexities that limit growth Lower TCO Flexible and scalable configurations To find out more about the SmartDesign approach and view more Reference Scenarios, visit SmartSolutionsDesigns.com Data Center Design Overview Efficiency. Availability. Capacity. One Approach. This reference scenario shows how the SmartDesign approach can be applied to create a Tier 2 data center that features high capacity, presicion cooling with air economization. In addition to efficiency gains in cooling, this scenario also depicts how the SmartDesign approach can be used to align availability and capex goals through UPSs, PDUs, and infrastructure management from Emerson Network Power. Use this design approach when: Chiller plant with capacity is available Climate allows for economization Raised floor is specified Hot aisle/cold aisle arrangement is desirable Tier 2 availability is required along with enhanced efficiency Benefits of this application: Scalability and efficiency using 500kVA Liebert NXL double conversion UPS Flexibility from Liebert busway electrical distribution system and rack PDUs Cooling efficiency and scalability from industry-best practices and equipment Density of 12kW per rack and a clear plan for future growth Integrated systems operation through Liebert iCOM controls and infrastructure management 2 Design Summary This data center utilizes a Tier 2 power design for 1.1MW data center with free cooling through air economization: (4) Liebert NXL 500 kVA UPS in redundant (3+1) configuration (6) Liebert PPC/FPC isolated distribution units (3) Liebert MB busway distribution systems (90) DCF Optimized Racks (90) Liebert MPX rack PDUs (2) Liebert TVSS, (2) ASCO ATS (4) Liebert CW 400 kW Liebert iCOM Controls Intelligent Cold Aisle Containment This design delivers: Reduced data center footprint for improved construction costs. More efficient rack utilization Improved scalability over air handlers. Variable capacity & improved airflow. High efficiency UPS. Improved change management with scalable busway power distribution. Data Center Overview Total Cost of Ownership Premium Base Minimum Mech. Redundancy 20%, Electrical Tier 4 This SmartDesign Mech. Redundancy at least 35%, Electrical Tier 2 Cost Savings (vs. Base) $6,500,000 $4,900,000 $1,600,000 25% $450,000 $1,600,000 $10,200,000 $250,000 $1,700,000 $7,000,000 $200,000 -$100,000 $3,200,000 44% -6% 31% Total CAPEX $18,750,000 $13,850,000 $4,900,000 26% Infrastructure Energy Costs $269,000 $162,000 $107,000 40% Water Usage $23,500 $18,000 $5,500 23% $292,500 $180,000 $112,500 38% $1,462,500 $900,000 $562,500 38% $20,212,500 $14,750,000 $5,462,500 27% 1.35 1.21 Building Costs Cost Advantage Engineering/Contracting, Building, Ceiling/Floor, Lights, Fire Suppressions Infrastructure Racks & Install Mechanicals & Install Electricals & Install Total Annual Energy Cost 5 Year OPEX 5 Year TCO PUE * Using Columbus, OH weather table , base utilizes (14) Liebert CW 084, (4) Liebert 750kVA without Eco-mode energy optimization. Utility costs of $.08/kw-h electric, $1.99 per k gallon water. Total power efficiency of 89% for base, 93% average for this SmartDesign (1.5% loss of PDU, 1.5% loss for lighting). SmartSolutionsDesigns.com 3 Applied Cooling Approach Free Cooling Through Air Economization and Containment Through the use of free cooling with air economization and aisle This cooling approach includes: containment, the cooling strategy leveraged in this approach provides Water-cooled centrifugal chiller system efficiency, availability and capacity to a 1.1MW data center. Four 400kW Base humidification Liebert CW units provide cooling capacity with fluid-side economization – 36-inch raised floor Space above dropped ceiling utilized as a return-air pathway combined with cold aisle containment for efficient performance. Service, support and data center design expertise from Emerson Network Power Hot Aisle Cold Aisle Hot Aisle Cold Aisle Hot Aisle Cold Aisle Total RF 73x59 Data Center Footprint 3224 ft2 Room Perimeter 227 lf Total Racks 90 kW per Rack 12.2kW Total kW 1100kW Gallery Footprint 1083 ft2 Precision Cooling AC Power Racks and Integrated Cabinets Hot Aisle Cold Aisle Containment (doors only here, full containment available) Liebert iCOM Control 4 Liebert CW 400D EC Fans Applied Cooling Equipment and Best Practices Let’s Compare: Premium Conventional This Smart Design Hot Aisle Cold Aisle Hot Aisle Cold Aisle Hot Aisle Cold Aisle Hot Aisle Capacity 1.1MW 1.1MW Dimensions sq ft Total 6,603 DC 4,819 Total 4,307 DC 3,224 Racks 160 @ 7kW per Rack 90 @ 12kW per Rack Raised Floor 36” 36” Chiller Plant Dual 300T Water cooled centrifugal 48F EWT, 60F LWT, 85F RAT VSD: 25hp CW pumps, 20hp cond pumps, 40 hp tower fans Dual 300T Water cooled centrifugal 48F EWT, 60F LWT, 85F RAT VFD: 25hp cond pumps, 20hp cond pumps, 40 hp tower fans Economizer Series fluid Air side AC Liebert CW 084 kW standard fan/motor Liebert CW 400 kW EC plugs fans in floor Airflow Ceiling return pathway Ceiling return pathway Containment None Cold Aisle Containment doors only * Images not to scale Equipment Overview Technologies Benefits Liebert CW 400 kW High Capacity Models Larger, integrated, scalable precison cooling units maintain the benefits of a redundant and packaged cooling design. Flexible fan locations allow for some variable floor depths. Air Side Economizer Plenum mixer boxes allow efficient use of outside air for cooling (when enthalpy of outside air is less than indoor return air). Liebert iCOM Controls Advanced controls ensure superb efficiency through teamwork, seperate fan and capacity control, unit rotation and more. EC Fans Improved airflow performance and efficiency. Energy savings of 20-30% over traditional designs. Intelligent Cold Aisle Containment Improved air management, energy efficiency and capacity. In this design we deploy partial containment with doors but no roof while leveraging Liebert iCOM control. Best Practices Overview: Maximize the return temperature at the cooling units to improve capacity and efficiency Match cooling capacity and airflow with IT loads Utilize cooling designs that reduce component power Enhance data center operations with management and control systems Raise chiller temperature 2-3F for even greater savings SmartSolutionsDesigns.com 5 Applied Power Approach Tier 2, Transformer-based Power with Busway Distribution The power approach utilized in this scenario supports a Tier 2, 1.1 MW data center. Both the UPS and electrical distribution configurations are optimized for efficiency, availability and capacity. UPS Design: Electrical Distribution Design: Designed to be Tier 2 rated, utilizes one (1) utility transformer, and one (1) main utility switchgear module. The UPS system consists of four (4) 500kVA Liebert NXL UPS modules paralleled into a bypass distribution cabinet in a distributed redundant (1+N or distributed static switch) configuration. Backup power generation is provided by two (2) 2.5MW generators paralleled in (N+1) configuration. The distribution design consists of six (6) 225kVA Liebert PPCs which receive power from a UPS distribution panel board. Each Liebert PPC powers three (3) 225A Liebert MB modular busway systems to provide reliable, flexible power distribution. Final power connections to the servers are performed in the rack using Liebert MPX intelligent rack PDUs. 2500 KW GENERATOR -1 2500 KW GENERATOR -1 4000A 4000A SWBD, 4000A, 480V, 3Ø, 4W+G 3000 KVA 13,200V / 480V 4000A BYPASS ISOLATION TVSS E N LOAD SWBD, 4000A, 480V, 3Ø, 4W+G 4000A 1000A 800A 1000A 800A 1000A 800A 1000A 800A 2000A 1600A UPS BYPASS 500KVA UPS MODULE #4 CB1 500KVA UPS MODULE #3 CB1 CB1 500KVA UPS MODULE #2 CB1 CB1 SWBD, 1600A, 480V, 3Ø, 4W+G 500KVA UPS MODULE #1 CB1 CB1 CB1 1600A SS SS SS CB2 CB2 CB2 ???A ???A ???A ???A UPS PARALLELING, MAINT BYPASS, & DIST SWBD SS CB2 350A 350A BATTERY STRING #B4 BATTERY STRING #B3 BATTERY STRING #B2 MBB 2000A BATTERY STRING #B1 350A 350A 800A 800A 800A 800A 350A MIB 2000A FPC #1 225 KVA FPC #2 225 KVA 350A 225A FPC #3 225 KVA 350A 225A 225A FPC #4 225 KVA 350A 225A 225A FPC #5 225 KVA 350A 225A 225A FPC #6 225 KVA 350A 225A 225A 350A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A 225A MB #1 MB #2 MB #3 MB #4 MB #5 MB #6 MB #7 MB #8 MB #9 MB #10 MB #11 MB #12 MB #13 MB #14 MB #15 MB #16 MB #17 MB #18 6 Applied Power Equipment Equipment Overview Technologies Benefits Liebert NXL with 1+N Distributed Bypass Architecture Robust UPS performance. Resilient stack up performance protects from all electrical conditions. Flexible scalability for capacity or redundancy. Calculated MTBF over 1.5 million hours. Liebert MB Modular Busway Fast, flexible, scalable and cost effective alternative to traditional cabling and PDUs. Liebert PPC Reliable and flexible isolated power conditioning and distribution delivers significant power to numerous circuits. Liebert MPX Rack PDU Intelligent rack power distribution creates a very smart, scalable and flexible system. Hot swappable modules, receptacle level control and management. Single or three phase. Flexible mounting. Liebert TVSS Facility-wide and Panel Mount versions remove electrical surges in the power stream. ASCO ATS Switches for reliable, mission critical performance. Best Practices Overview: Obtain the power system designed to match your needs for availability and efficiency (tiers, redundancy, voltages, distribution) Leverage the optimum design for electrical scalability and modularity to meet current and future needs Enhance data center operations with management and control systems Rely on local service and support to ensure proper designs, maintenance and assessments Alber Battery Monitoring: Identifies issues in batteries and extends lifespan. Infrastructure Management Liebert Nform: Distributed monitoring and alarm management of critical devices. Increase availability. Supporting Data Center PDUs in gallery Batteries Hot Aisle Cold Aisle Hot Aisle Liebert NXL UPS Cold Aisle Liebert CW 114 Cooling Unit Hot Aisle Hot Aisle Equipment Room (1748 s/f) Cold Aisle Avocent DCP: Data center planner manages assets, capacities and room/rack layouts. Switchgear Liebert PDU SmartSolutionsDesigns.com 7 Power Approach Benefits Reduce or eliminate downtime costs of $507,000/event. Energy Efficient UPS Power 100% 100% Liebert NXLNXL 500kVA ECOECO Mode Liebert 500kVA Mode andand Normal Mode Efficiencies Normal Mode Efficiencies 98%98% 96%96% Creating, maintaining and expanding data centers with Emerson Network Power 94%94% 92%92% ECOECO Mode Mode Normal Mode Normal Mode 90%90% 88%88% 20% 20% 30%30% 40%40% 50%50% 60%60% 70%70% 80%80% 90%90%100% 100% PDU Efficiency Curve For more examples of the high-efficiency and high-capacity data centers that the SmartDesign approach can create, maintain and grow, visit our website. 100100 98 98 96 96 94 94 92 92 90 90 88 88 0% 0% Liebert PPC/FPC Liebert PPC/FPC Liebert MB busway Liebert MB busway 20%20% 30%30% With Emerson Network Power and the SmartDesign approach, there’s virtually no limit to what you can solve and how you can design the optimal data center. 40%40% 50%50% 75%75% 100% 100% Efficiency through performance based TCO. The SmartDesign approach helps data centers save money while still ensuring mission-critical availability. Using the innovative equipment and industry-best practices that this approach offers, you can avoid the costly expenses associated with system failures and down times. Did you know? Average data centers experience 5.12 power outages every two years Outage duration averages 106 minutes System recovery is estimated at 3 times the duration of the outage (318 on average) This means that on average, each unplanned outage costs $507,000*. Contact a local data center specialist to discuss your situation. They can assist you with technical advice, configuration development and energy analysis to support your unique design needs. The SmartDesign Approach Efficient Economical Simplified Controllable To see more Reference Scenarios, visit www.SmartSolutionsDesigns.com today. While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. *Read the Ponemon white paper on costs of downtime at www.liebert.com © 2012 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners. ® Liebert is a registered trademark of the Liebert Corporation. SL-11505A (R08-12) Emerson Network Power. The global leader in enabling Business-Critical Continuity™. EmersonNetworkPower.com AC Power Embedded Computing Infrastructure Management & Monitoring Precision Cooling Connectivity DC Power Embedded Power Industrial Power Outside Plant Power Switching & Controls Racks & Integrated Cabinets Services Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2012 Emerson Electric Co.