Design Smart Solutions Reference Guide

advertisement
Solutions
For Business-Critical Continuity™
Smart Solutions Reference Guide
1100kW Tier 3 With High Density
Design
Reference Guide:
1100kW Tier 3 With High Density
Intelligent, Integrated Infrastructure
for the Data Center
The SmartDesign from
Emerson Network Power
uses a perimeter/room-based
approach to deliver efficiency,
availability, capacity and
control, that allows you to be
prepared for what’s next.
Our approach helps to create,
maintain and grow data centers that
meet customer challenges through
innovative systems, industry-best
practices and local data center
specialists who fully understand how
to solve these problems.
This sample reference scenario,
1100kW Tier 3 With High Density,
illustrates one possible example of
how the SmartDesign approach can be
used to create a high-performance
IT infrastructure.
To find out more about the
SmartDesign approach and view
more Reference Scenarios, visit SmartSolutionsDesigns.com
SmartDesign Approach:
Lower energy bills by $122,000/yr
Save 60% in floor space
Generate PUE of 1.19
Provide high Tier 3 availability
Save 38% in OPEX
Obtain over 97% UPS efficiency
Lower TCO by 21% over base
Improve flexibility and scalability
Reduce rack count by 65%
Leverage density of 20kW/rack
Common Data Center
Challenges:
Limited availability and capacity
Insufficient and inefficient
cooling capabilities
Piecemeal infrastructure that
is difficult to manage
SmartDesign
Benefits:
Proven power solutions that deliver
efficiency, scalability and reliability
Precision cooling that controls the
temperature, humidity and airflow
Effective monitoring and control
Space constraints
Efficient space utilization
Energy inefficiencies
Improved PUE
Budgetary constraints
Lower TCO
Complexities that limit growth
Flexible and scalable configurations
Data Center Design Overview
Efficiency. Availability. Capacity.
One Approach.
This innovative reference design uses efficient refrigerantbased rear door heat exchangers and chilled water
economization alongside a highly efficient tier 3 power
configuration to deliver high capacity within a smaller space.
The design blends efficiency, availability and scalability to
deliver an optimized infrastructure.
Use this design approach when:
Climate allows for economization
Data center floor space is to be minimized
Tier 3 availability is desired
Benefits of this application:
Free cooling saves energy
Higher density improves efficiency
Dual bus reduces downtime
Design Summary
This data center integrates power and cooling
in a Tier 2 mechanical and a Tier 3 electrical
configuration to support a 1.1MW load.
(2) Liebert CW 114kW base cooling
(56) Liebert XDR rear door heat exchangers
(56) DCF Optimized Racks
(8) Liebert XDP refrigerant pumping units
(2) Liebert NXL1100kVA/1100kW UPS–
2N Dual Bus configuration
(12) Liebert PPC PDU
(12) Liebert FDC PDU
(2) Liebert TVSS
(2) ASCO ATS
(112) Liebert MPX rack PDU
Liebert Nform, Avocent Data Center Planner
This design delivers:
Operating/energy savings
Lower data center footprint
More efficient rack utilization
Free cooling using fluid economization
Simplified scalability
High capacity, high efficiency UPS
Protected dual bus architecture
Operational DCIM control and factory local service
2
Data Center Overview
Premium Base
Minimum Mech.
Redundancy 20%,
Electrical Tier 4
Building Costs
This SmartDesign
Miniumum Mech.
Redundancy 35%,
Electrical Tier 3
Cost Savings
(vs. Base)
Cost
Advantage
$6,500,000
$5,100,000
$1,400,000
22%
$450,000
$118,000
$332,000
$1,600,000
$2,400,000
-$800,000
$10,200,000
$7,400,000
$2,800,000
74%
-50%
27%
$18,750,000
$15,018,000
$3,732,000
20%
Infrastructure
Energy Costs
$313,000
$147,000
$122,000
45%
Water Usage
$23,500
$23,500
$0
$292,500
$170,500
$122,000
42%
$1,462,500
$852,500
$610,000
42%
$20,212,500
$15,870,500
$4,342,000
21%
Engineering/Contracting, Building, Ceiling/Floor,
Lights, Fire Suppression
Infrastructure
Racks & Install
Mechanicals & Install
Electricals & Install
Total CapEx
Total Annual
Energy Cost
5 Year OpEx
5 Year TCO
0%
* Using Columbus, OH weather table, base utilizes (14) Liebert CW 084, (4) Liebert 750kVA without Eco-mode energy optimization. Utility
costs of $.08/kw-h electric, $1.99 per k gallon water. Total power efficiency of 89% for base, 94% average for this SmartDesign (1.5% loss of
PDU, 1.5% loss for lighting).
SmartSolutionsDesigns.com
3
Applied Cooling Approach
Efficient Refrigerant-Based Heat Exchangers and
Chilled Water Economization
This cooling
approach includes:
Shown below is a sample SmartDesign cooling scenario using our
innovative refrigerant high density systems along with base chilled water
cooling with economization in a 1.1MW data center. This facility uses a
water cooled centrifugal chiller system with series fluid side economizer.
Using this design a customer only needs 56 IT racks at 20 kW per rack. There is a 36 inch raised floor with space above dropped ceiling used as
return air pathway. The precision cooling units use (2) Liebert CW 114
with Liebert iCOM and EC fans, and the Liebert XD system with (56) of the
Water-cooled centrifugal
chiller system
Base humidification
36-inch raised floor
Space above dropped
ceiling utilized as a
return-air pathway
Service, support and
data center design
expertise from Emerson
Network Power
Liebert XDR attached to the racks and (8) Liebert XDP pumping units. Hot
aisle, cold aisle arrangement is optional.
* Liebert systems identified are repeated in the gallery on the left.
Neutral Aisle
Cold Aisle
Total RF
69x39
Data Center
Footprint
1701 ft2
Room Perimeter
166 lf
Total Racks
56
kW per Rack
19.64 kW
Total kW
1100kW
Gallery Footprint
(2) 495 ft2
Precision Cooling
Neutral Aisle
AC Power
Racks and Integrated
Cabinets
Cold Aisle
Neutral Aisle
Liebert XDR
4
EC Fans
Liebert iCOM
Liebert CW 114
Liebert XDP
This innovative data center
packs tremendous computing
power into a very efficient
space for remarkable savings.
The layout shown is one
representation. Another
option when working with
Liebert XDRs is to arrange in a
cascading aisle configuration.
Naturally, air movement is front
to back and returned to the
cooling unit(s) via a pathway.
Applied Cooling Equipment
and Best Practices
Let’s Compare:
Premium Conventional
This SmartDesign
Neutral Aisle
Cold Aisle
Neutral Aisle
Cold Aisle
Neutral Aisle
Capacity
1.1MW
1.1MW
Dimensions sq ft
Total 6,603 DC 4,819
Total 2,691 DC 1,701
Racks
160 @ 7kW per Rack
56 @ 20kW per Rack
Raised Floor
36”
36”
Chiller Plant
Dual 300T Water cooled centrifugal 48F EWT,
60F LWT, 85F RAT SD: 25hp CW pumps, 20hp
cond pumps, 40 hp tower fans
Dual 300T Water cooled centrifugal 48F EWT, 60F
LWT, 85F RAT VFD: 25hp CW pumps, 20hp cond
pumps, 40 hp tower fans
Economizer
Series fluid
Series fluid
AC
Liebert CW 084 kW standard fan/motor
(2) Liebert CW 114 kW, EC plugs fans in floor
(56) Liebert XDR, (8) Liebert XDP
Airflow
Ceiling return pathway
Ceiling return pathway
Containment
None
None
* Images not to scale
Equipment Overview
Technologies
Benefits
Best Practices
Overview:
Liebert CW 114 kW
Chilled water pre-packaged systems. Dedicated systems
allow for easier scalability and redundancy. Proven, reliable
operation provides humidity control and air filtration.
Highly manageable and serviceable. Efficient components.
Maximize the return
temperature at the
cooling units to improve
capacity and efficiency
Liebert iCOM Controls
Advanced controls ensure superb efficiency through
teamwork, seperate fan and capacity control, unit
rotation and more.
Match cooling capacity
and airflow with IT loads
EC Fans
Improved airflow performance and efficiency. Energy
savings of 20-30% over traditional designs.
Liebert XDR
Fanless heat exchanger provides outstanding energy
savings - no added floor space - higher computing
density saves energy and data center space - uses only
server fans to move air over the coils - no cooling fans
required - use with or without hot aisle/cold aisle layout.
Utilize cooling
designs that reduce
component power
Liebert XDP
Intelligent isolating pumping interface between
the building chilled water system and the pumped
refrigerant circuit.
Fluid Economizer
Incorporated into the chiller plant heat rejection loop
to cool the fluid during appropriate times reducing
pump operations.
Enhance data center
operations with
management and
control systems
For even greater
improvements, you
could raise the chiller
temp 2-3°F above 48°F
SmartSolutionsDesigns.com
5
Applied Power Approach
Tier 3, Efficient, 2N Power with Two-Stage Distribution
The power approach utilized in this scenario supports a Tier 3, 1.1 MW data center. Both the UPS and electrical distribution
configurations are optimized for maximum efficiency, availability and capacity.
Electrical Power Design:
Electrical Distribution Design:
Our Tier 3 1100kW operation utilizes (2) separate utility
transformers and (2) separate main utility switchgear modules.
The UPS system consists of (2) Liebert NXL 1100kVA/1100kW
UPS– 2N Dual Bus configuration. Backup power generation
provided by two (2)2.5MW Generators in (2N) configuration.
Design distribution to consist of six (6) pairs of 225kVA Liebert
PPCs in a dual bus configuration. They in turn will receive
power from a UPS distribution panel board. Each Liebert PPC
powers a Liebert FDC, which then deliver power to the racks via
the Liebert MPX PDU.
Close up of Bus “A” of an “A/B Bus” Power
System in a Tier 3 Architecture
3000 KVA
13,200V / 480V
2500 KVA
GENERATOR–1
ISOLATION
BYPASS
N
E
4000A
TVSS
4000A
LOAD
SWBD, 4000A, 480V, 3Ø, 4W+G
2000A
2000A
2000A
1600A
4000A
UPS
BYPASS
SWBD, 1600A, 480V, 3Ø, 4W+G
1600A
1100KVA UPS
MODULE A
150A
DIST SWBD, 2000A
150A
150A
150A
350A
CB1
BFB
350A
350A
SS
MBB
2000A
350A
350A
CB2
BATTERY
STRING #B2
350A
FPC–A1
225 KVA
FPC–A3
225 KVA
350A
FPC–A5
225 KVA
350A
350A
3000 KVA
13,200V / 480V
2500 KVA
GENERATOR–1
ISOLATION
BYPASS
N
E
4000A
TVSS
4000A
E
N
225A
LOAD
SWBD, 4000A, 480V, 3Ø, 4W+G
2000A
2000A
2000A
1600A
225A
225A
225A
225A
225A
225A
225A
225A
4000A
UPS
BYPASS
SWBD, 1600A, 480V, 3Ø, 4W+G
225A
FDC–A1
1600A
1100KVA UPS
MODULE A
150A
DIST SWBD, 2000A
150A
150A
150A
350A
CB1
225A
FDC–A1
225A
FDC–A1
225A
FDC–A1
225A
FDC–A3
225A
FDC–A3
225A
FDC–A3
225A
FDC–A3
225A
FDC–A5
225A
FDC–A5
225A
FDC–A5
225A
FDC–A5
BFB
350A
350A
SS
MBB
2000A
SS
350A
350A
CB2
BATTERY
STRING #B2
350A
FPC–A1
225 KVA
FPC–A3
225 KVA
350A
225A
225A
FDC–A1
FPC–A5
225 KVA
350A
225A
225A
FDC–A1
225A
225A
FDC–A1
225A
225A
FDC–A1
225A
FDC–A3
225A
225A
FDC–A3
225A
225A
FDC–A3
225A
FDC–A2
225A
FDC–A5
350A
225A
225A
FDC–A5
225A
225A
FDC–A2
225A
FDC–A2
225A
225A
FDC–A4
350A
350A
225A
FDC–A5
350A
225A
225A
FDC–A4
225A
225A
FDC–A4
225A
FDC–A4
225A
225A
FDC–A6
225A
225A
FDC–A6
225A
225A
FDC–A6
225A
FDC–A6
225A
One-Line Snapshot of Both”A/B” Buses
6
FPC–A6
225 KVA
FPC–A6
225 KVA
350A
225A
225A
FDC–A2
225A
225A
FDC–A5
FPC–A4
225 KVA
350A
225A
FPC–A4
225 KVA
350A
225A
225A
FDC–A3
FPC–A2
225 KVA
FPC–A2
225 KVA
225A
FDC–A2
225A
225A
FDC–A2
225A
225A
FDC–A2
225A
FDC–A2
225A
225A
FDC–A4
225A
225A
FDC–A4
225A
225A
FDC–A4
225A
FDC–A4
225A
225A
FDC–A6
225A
225A
FDC–A6
225A
225A
FDC–A6
225A
FDC–A6
Applied Power Equipment
Equipment Overview
Technologies
Benefits
Liebert NXL1100kVA/
1100kW UPS – 2N Dual
Bus configuration
Robust and efficient double conversion UPS.
Resilient stack-up performance Protects from all
electrical conditions. Efficiency rivals transformerfree systems. Power factor rated at near unity.
Liebert FPC/PPC
Reliable and flexible isolated power conditioning
and distribution process significant power to
many circuits.
Liebert FDC
Flexible, fast, in row power distribution for high
capacity connections to the racks.
Liebert MPX
Rack PDU
Intelligent rack power distribution creates a
very smart, scalable and flexible system. Hot
swappable modules, receptacle level control and
management. Single or three phase.
Flexible mounting.
Liebert TVSS
Facility-wide and Panel Mount versions remove
electrical surges in the power stream.
ASCO ATS
Reliable switches for critical performance.
Best Practices
Overview:
Obtain the power
system designed to
match your needs for
availability and efficiency
(tiers, redundancy,
voltages, distribution)
Leverage the optimum
design for electrical
scalability and
modularity to meet
current and future needs
Enhance data center
operations with
management and
control systems
Rely on local service and
support to ensure proper
designs, maintenance
and assessments
Albér Battery Monitoring: Identifies issues in
batteries and extends product lifespan.
Infrastructure
Management
Liebert Nform: Distributed monitoring and alarm
management of critical devices.
Increase availability.
Switchgear
Liebert NXL UPS
Neutral Aisle
Liebert CW 114
Cooling Unit
Cold Aisle
Equipment Room (2) 1,446 ft2
Neutral Aisle
Cold Aisle
Neutral Aisle
Avocent DCP: Data center planner manages assets,
capacities and room/rack layouts.
Supporting Data Center PDUs in gallery
Batteries
Liebert PPC/PDU
SmartSolutionsDesigns.com
7
Power Approach Benefits
Reduce or eliminate downtime costs
of $507,000/event.
Energy Efficient UPS Power
100%
Typical Load
96%
92%
88%
Intelligent EcoMode
AC-AC (UPS Dual Conversion)
84%
80%
10%
Creating, maintaining and
expanding data centers with
Emerson Network Power
Liebert NXL
1100kVA/1100kW UPS
20%
30%
40%
50%
60%
70%
80%
90%
100%
For more examples of the high-efficiency and highcapacity data centers that the SmartDesign approach
can create, maintain and grow, visit our website.
PDU Efficiency Curve
100
98
96
94
92
90
88
Contact a local data center specialist to discuss
your situation. They can assist you with technical
advice, configuration development and energy
analysis to support your unique design needs.
Liebert PPC/FPC
0%
20%
30%
With Emerson Network Power and the SmartDesign
approach, there’s virtually no limit to what you can
solve and how you can design the optimal data center.
40%
50%
75%
100%
The SmartDesign Approach
Efficiency through performance based TCO.
The SmartDesign approach helps data centers save money
while still ensuring mission-critical availability. Using the
innovative equipment and industry-best practices that this
approach offers, you can avoid the costly expenses associated
with system failures and down times.
Efficient
Economical
Simplified
Controllable
Did you know?
Average data centers experience 5.12 power outages
every two years
Outage duration averages 106 minutes
To see more Reference Scenarios, visit
www.SmartSolutionsDesigns.com today.
System recovery is estimated at 3 times the duration of
the outage (318 on average)
This means that on average, each unplanned outage
costs $507,000*.
While every precaution has been taken to ensure accuracy and completeness in this
literature, Liebert Corporation assumes no responsibility, and disclaims all liability for
damages resulting from use of this information or for any errors or omissions.
*Read the Ponemon white paper on costs of downtime at www.liebert.com
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Industrial Power
© 2014 Liebert Corporation. All rights reserved throughout the world. Specifications subject
to change without notice. All names referred to are trademarks or registered trademarks
of their respective owners. ® Liebert is a registered trademark of the Liebert Corporation.
SL-11505C (R01-14)