SYMBOL
DESCRIPTION
SYMBOL
LIGHT FIXTURES
DESCRIPTION
GENERAL NOTES
SPECIAL SYSTEM SYMBOLS
GENERAL: THESE DRAWINGS REMAIN THE SOLE PROPERTY OF SOL CHAVEZ AND ASSOCIATES AND MAY BE USED ONLY FOR THE PROJECT AS
INDICATED BY NAME AND LOCATION. ANY OTHER USE REQUIRES PRIOR, WRITTEN PERMISSION.
THE CONTRACTOR WILL PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, TOOLS, TRANSPORTATION, LICENSES, FEES, PERMITS, ETC. TO
COMPLETE THE ELECTRICAL WORK DESCRIBED ON THE DRAWINGS. THE CONTRACTOR WILL WARRANT EQUIPMENT, MATERIAL AND
WORKMANSHIP FOR A MINIMUM PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE. WARRANTY SHALL INCLUDE REPLACEMENTS OR
REPAIRS WITHOUT COST TO THE OWNER DURING THE WARRANTY PERIOD.
ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) 2011 AND ALL OTHER APPLICABLE
LOCAL CODES AND ORDINANCES. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS.
PUSHBUTTON OPERATOR.
CEILING MOUNTED SPEAKER
RECESSED FLUORESCENT LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
S
S
WALL MOUNTED SPEAKER
SURFACE FLUORESCENT LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
E
NURSE/EMERGENCY CALL BUTTON
N
NURSE/EMERGENCY CALL BUTTON
1
2/10/16
STATE
COMMENTS
2
2/18/16
STATE
COMMENTS 2
FLUORESCENT STRIP LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
USE OF DRAWINGS: DO NOT SCALE FROM THE ELECTRICAL DRAWINGS. FOR EXACT LOCATIONS USE ARCHITECT'S DIMENSIONED DRAWINGS,
SHOP DRAWINGS AND FIELD MEASUREMENTS. VERIFY ALL LOCATIONS WITH THE ARCHITECT PRIOR TO ELECTRICAL ROUGH-IN.
COMMUNICATION SYSTEM SYMBOLS
WALL BRACKET FLUORESCENT LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
WIRING METHODS: ALL WIRING FOR LIGHTING AND POWER SYSTEMS WILL BE IN CONDUIT OR CABLE ASSEMBLIES APPROVED BY THE GOVERNING
AUTHORITIES. CONDUCTOR SIZES SHOWN ARE BASED ON AMPACITIES FOR COPPER CONDUCTORS, #12 AWG FOR BRANCH CIRCUITS MIN. WHEN
APPROVED BY ENGINEER, FEEDERS MAY BE ALUMINUM CONDUCTORS OF EQUIVALENT AMPACITIES. GROUNDING CONDUCTORS SHALL BE
PROVIDED FOR ALL CIRCUITS SHOWN ON THE DRAWINGS. PROVIDE BLOCKING AND OTHER NECESSARY SUPPORTS IN WALLS AND CEILINGS FOR
MATERIAL AND EQUIPMENT TO BE PROVIDED. BRANCH CIRCUIT NUMBERS SHOWN ON THE DRAWINGS MAY BE REARRANGED WITHIN A GIVEN
PANELBOARD TO SUIT THE NEEDS OF THE INSTALLATION. ELECTRICAL BRANCH CIRCUITS SHALL BE BALANCED BETWEEN LINES AND PHASES.
MULTIWIRE BRANCH CIRCUITS SHALL HAVE A MEANS TO SIMULTANEOUSLY DISCONNECT ALL UNDERGROUNDED CONDUCTORS AT THE POINT
WHERE BRANCH CIRCUITS ORIGINATE (HANDLE TIES ARE AN APPROVED MEANS). THE GROUNDED AND UNDERGROUNDED CONDUCTOR OF EACH
MULTIWIRE BRANCH CIRCUIT SHALL BE GROUPED BY WIRE TIES AT ONE LOCATION IN PANELBOARD.
ALL PATIENT CARE AREAS SHALL COMPLY WITH NEC 517.13(A)(B) TO INCLUDE LUMINAIRES.
TELEPHONE OUTLET. WIRING BY OTHERS, UNO. MOUNT 18" AFF.
WALL MOUNTED LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
TELEPHONE OUTLET. WIRING BY OTHERS, UNO., WALL PHONE, MOUNT 48" AFF.
W
DATA OUTLET. WIRING BY OTHERS, UNO. MOUNT 18" AFF.
RECESSED CEILING MOUNTED DOWNLIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
DATA/TELEPHONE OUTLET, WIRING BY OTHERS UNO. MOUNT 18" AFF.
CABLE TV OUTLET, WIRING BY OTHERS, UNO. MOUNT 18" AFF.
TV
SURFACE MOUNTED CEILING DOWNLIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
T
PENDANT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
TRACK HEAD FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
FIRE ALARM SYMBOLS
UTILITY COORDINATION: PROVIDE ALL COORDINATION WITH THE UTILITY INCLUDING LOAD DATA FORMS AND APPLICATION FOR SERVICE AS
APPLICABLE. INSTALLATION OF SERVICE, PRIMARY OR SECONDARY FEEDERS AND METERING SHALL BE PERFORMED IN ACCORDANCE WITH THE
UTILITIY REQUIREMENTS.
HORN
ONLY THERMOSTAT. PROVIDED BY MECHANICAL., INSTALLED BY ELECTRICIAN.
LINE VOLTAGE
F
HORN AND STROBE
PARKING LOT POLE LIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
STROBE ONLY
F
MANUAL PULL STATION
S
SMOKE DETECTOR
H
HEAT DETECTOR
S
GROUNDING: PROVIDE A COMPLETE GROUNDING SYSTEM AS REQUIRED BY THE NEC AND LOCAL AUTHORITIES HAVING JURISDICTION. ALL
BRANCH CIRCUITS SHALL INCLUDE A GROUND CONDUCTOR. USE OF RACEWAY FOR GROUNDING IS NOT PERMITTED. GALVANIZED GROUND
RODS ARE NOT PERMITTED.
PANELBOARDS: PROVIDE MINIMUM INTEGRATED EQUIPMENT SHORT CIRCUIT RATING AS INDICATED ON PANEL SCHEDULES. PROVIDE BOLT-ON
BREAKERS UNLESS OTHERWISE NOTED. PROVIDE CIRCUIT BREAKERS SHOWN ON THE PANELBOARD SCHEDULES. ALL TERMINATIONS AND
LUGS SHALL BE RATED FOR 75-DEGREE CONDUCTORS.
PROVIDE TYPEWRITTEN CIRCUIT SCHEDULES TO IDENTIFY PANELBOARD AND EACH BRANCH BREAKER.
ACCEPTABLE MANUFACTURERS ARE SQUARE D, SIEMENS AND EATON.
DUCT SMOKE DETECTOR
D
MAGNETIC DOOR HOLD OPEN
LIGHT FIXTURE WITH EMERGENECY BALLAST, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
FIRE/SMOKE DAMPER
WIRING DEVICES: PROVIDE SPECIFICATION GRADE 15 AND 20- AMPERE SWITCH AND RECEPTACLE DEVICES, AS APPLICABLE. OTHER DEVICES
SHALL BE PROVIDED AS INDICATED AND SHALL MATCH PLUG-CONNECTED EQUIPMENT FURNISHED FOR THE PROJECT. DEVICE WALL PLATES
SHALL BE SMOOTH, NYLON TYPE AND SHALL BE OFFICE WHITE IN COLOR OR AS OTHERWISE SPECIFIED. DEVICE COLOR SHALL MATCH WALL
PLATES.
FIRE ALARM CONTROL PANEL
EMERGECY LIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
ANNUNCIATION PANEL
EXIT SIGN, WITH TYPE NOTED IN PLAN, SEE PLAN FOR ARROWS AND FACE OF EXIT NEEDED. SEE FIXTURE SCHEDULE FOR DETAILS.
ONE-LINE SYMBOLS
SWITCHES
CIRCUIT BREAKER, FRAME AND TRIP AS INDICATED.
TOGGLE SWITCH, 20A, SINGLE POLE, VOLTAGE AS REQUIRED. MOUNTED AT 48" ABOVE FINIDHED FLOOR.
POWER TRANSFORMER, RATING AS INDICATED.
DISCONNECT SWITCHES: HEAVY DUTY QUICK-MAKE, QUICK-BREAK TYPE, NON-FUSED UNLESS OTHERWISE NOTED. PROVIDE MEANS TO LOCK
SWITCH IN OFF POSITION WITH PAD-LOCK. ENCLOSURES SHALL BE NEMA TYPE 1 OR NEMA TYPE 3R FOR OUTDOOR INSTALLATION. PROVIDE
PERMANENT LABELS FOR DISCONNECTS TO INDICATE EQUIMENT SERVED.
LIGHTING FIXTURES: SEE LIGHT FIXTURE SCHEDULE. PROVIDE ALL FIXTURES WITH LAMPS AS INDICATED. WHERE REQUIRED, FIXTURES SHALL
BE WET OR DAMP LOCATION LABELED. VERIFY MOUNTING HEIGHTS PRIOR TO ELECTRICAL ROUGH-IN. PROVIDE ALL REQUIRED MOUNTING
ACCESSORIES REQUIRED FOR PROPER MOUNTING TO SURFACES SUCH ACCESSORIES TO INCLUDE BUT NOT LIMITED TO SLOPE ADAPTORS.
CANOPIES, AND VAULTED CEILING CANOPIES, ETC.
PROVIDE DISCONNECTING MEANS FOR LUMINAIRES THAT UTILIZE DOUBLE-ENDED LAMPS AND BALLASTS(S) IN ACCORDANCE WITH NEC 410.130(G)(1).
ALTERNATES NOT ACCEPTABLE UNLESS NOTED AS "OR EQUAL" ON LIGHT FIXTURE SCHEDULE.
S
OCCUPANCY SENSOR, WALL MTD., 48" AFF. SENSOR SWITCH WSD PDT, OR EQUAL
OCCUPANCY SENSOR, CEILING MTD. SENSOR SWITCH CMR PDT OR EQUAL
GROUND ELECTRODE
PHOTOCELL SWITCH, MOUNT ON NORTH FACING EXTERIOR WALL, UNO.
CURRENT TRANSFORMER (CT)
VOICE/DATA: RACEWAY SYSTEM BY CONTRACTOR. ALL RACEWAYS SHALL BE PROVIDED WITH PULLSTRINGS OF MINIMUM OF 400-LB. TEST
STRENGTH. ALL EQUIPMENT, RECEPTACLES AND CABLING BY OTHERS. PROVIDE BLANK COVERS OVER ALL UNUSED OUTLETS. CABLES,
DEVICES AND CABLE TERMINATION IS BY OTHERS.
SUBSCRIPTS FOR SWITCHES
NON-FUSIBLE SWITCH, RATING AS INDICATED.
3
THREE-WAY TOGGLE SWITCH
4
FOUR-WAY TOGGLE SWITCH
D
0 - 10 VOLT ELECTRONIC DIMMER SWITCH, 1000W, 120V LUTRON DIVA OR EQUAL, UNO. COORDINATE COMPATIBLE DIMMER WITH
LIGHTING MANUFACTURER.
M
MANUAL MOTOR STARTER WITH THERMAL OVERLOAD
FIRE ALARM: BY SIMPLEX TO PROVIDE AS REQUIRED PER FIRE AND LOCAL CODES.
FUSIBLE SWITCH, RATING AND FUSE SIZE AS INDICATED.
FEEDER SCHEDULE KEY TAG
UTILITY TRANSFORMER
RECEPTACLES
UTILITY ELECTRIC METER
M
DUPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO., MOUNT 18" AFF.
CRGA
CR2A
Chavez Tiffany & Ayers
Engineering Corporation
UPS2
119 West Cucharras Street
Colorado Springs, Colorado 80903
P (719)636-0021
QUAD RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO., MOUNT 18" AFF.
MOTOR WITH DISCONNECT
SIMPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO. MOUNT 18" AFF.
MCB
SPECIAL RECEPTACLE, 220V, TYPE AS INDICATED OR MATCH EQUIPMENT CAP., MOUNT AT HEIGHT AS REQUIRED PER EQUIPMENT.
MOTOR WITH CONTROLLER AND DISCONNECT
DUPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO., WITH TIE-BAR REMOVED FOR SWITCHING., MOUNT 18" AFF.
SPECIAL PURPOSE RECEPTACLE, NEMA TYPE AS INDICATED., MOUNT AT HEIGHT AS REQUIRED PER EQUIPMENT.
FLOOR BOX DUPLEX RECEPTACLE, FLUSH MOUNTED, PROVIDE COVER AS REQUIRED.
GENERATOR
G
FLOOR BOX QUAD RECEPTACLE, FLUSH MOUNTED, PROVIDE COVER AS REQUIRED.
N
S
L
TRANSFER SWITCH
15KVA 3PH
480V DELTA PRI.
WEATHERHEAD
208Y/120V SEC
SUBSCRIPTS FOR RECEPTACLES
C
CLOCK RECEPTACLE
CE
CEILING FLUSH MOUNTED
IG
ISOLATED GROUND
GFI
GROUND FAULT INTERRUPTER
WR
WEATHER RESISTANT WITH GROUND FAULT INTERRUPTER IN WEATHER PROOF BOX
OC
OVER COUNTER, MOUNT RECEPTACLE MOUNTED 6" ABOVE BACKSPLASH.
UNO
UNLESS NOTED OTHERWISE.
UC
UNDER COUNTER
TVSS
TRANSIENT VOLTAGE SURGE SUPPRESSOR
EWC
ELECTRIC WATER COOLER, PROVIDE GFI PROTECTION
E
EXISTING DEVICE TO REMAIN.
N
NEW DEVICE TO BE INSTALLED
H
MOUNT DEVICE 6" AFF, HORIZONTALLY.
TP
TAMPER-PROOF
SWD
SWITCH RATED BREAKERS
NL
NIGHTLIGHT WIRED FIXTURE
POWER SYMBOLS
J
J
JUNCTION BOX, FLUSH/SURFACE MTD.
POWER POLE WITH COMM AND POWER.
150AF
70AF
200A/3P
100A/3P
ID
PANELBOARD OR LOADCENTER, IDENTIFICATION, AMPERES AND VOLTAGE.
ABBREVIATIONS
TVSS
CLGA
CL1A
UPS
45KVA 3PH
480V DELTA PRI.
208Y/120V SEC
FEEDER SCHEDULE
5(4#400 CU IN 3" PVC)
MAIN BREAKER
GFI
225A/3P
MOTOR
3#3 1#6 CU IN 1-1/2" EMT
30A/3P
100A/3P
100A/3P
70A/3P
40A/3P
NON FUSIBLE DISCONNECT SWITCH, RATING AS INDICATED.
4#250 1#2 CU IN 2-1/2" EMT
FUSIBLE DISCONNECT SWITCH, RATING AS INDICATED.
4#4/0 1#2 CU IN 2-1/2" EMT
PANELBOARD/LOADCENTER.
3#1 1#6 CU IN 1-1/4" EMT
CEILING MOUNTED PAD FAN.
NOTE: NOT ALL SYMBOLS ARE USED. VERIFY ALL CONNECTIONS AND RECEPTACLE TYPES FOR EQUIPMENT
EQUIPMENT FROM APPROVED MECHANICAL AND EQUIPMENT SUBMITTALS PRIOR TO INSTALLATION.
RGA
NOTES:
1.
ALL ELECTRICAL EQUIPMENT, FEEDERS AND PANELBOARDS ARE EXISTING TO REMAIN UNLESS NOTED
OTHER WISE.
2. PROVIDE NEW BREAKERS IN EXISTING PANELS AS NEEDED. CONTRACTOR TO VERIFY NUMBER AND SIZE OF
NEEDED BREAKERS.
3. NEW ADDED BREAKERS TO HAVE AIC RATING AND SAME MANUFACTURER MATCHING EXISTING IN ORDER
TO MAINTAIN SERIES RATING.
4. CONTRACTOR SHALL VERIFY ALL BRANCH CIRCUITS AND PROVIDE TYPE WRITTEN UPDATED PANEL
DIRECTORY FOR ALL PANELS.
5. SECOND FLOOR PANELS ARE CONNECTED WITH FEED THROUGH LUGS FROM FIRST FLOOR PANELS.
R2A
5#10 CU IN 3/4" EMT
GENERATOR
MCB
G
MCB
2(4#4/0 1#2 CU IN 2-1/2" EMT)
4#3 1#6 CU IN 1-1/2" EMT
R1A
ELEVATOR
15KVA 3PH
480V DELTA PRI.
GFI
225A/3P
R1A1
M2A
NOT USED
MCB
3#6 1#6 CU IN 1" EMT
208Y/120V SEC
3#4 1#8 CU IN 1-1/4" EMT
(4#3 1#6 EQUIPMENT GND AND 1#3 INSULATED/ISOLATED GND) IN 1-1/2" EMT
TVSS
LGA
L
N
L1A
M1A
SM
(4#1 1#6 EQUIPMENT GND AND 1#1 INSULATED/ISOLATED GND) IN 1-1/2" EMT
75KVA 3PH
480V DELTA PRI.
SHUNT TRIP
70A/3P
4#2/0 1#4 CU IN 2-1/2" EMT
208Y/120V SEC
ELECTRICAL
LEGEND
NOT USED
4#4 1#6 CU IN 1" EMT
SERVICE MAIN
1600AS/3P
PUBLIC SAFETY BUILDING - UCCS
BOLLARD OR POST LIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
F
MILITARY AND STUDENT VETERAN CENTER REMODEL
SPOTLIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS.
BID SET:
2/01/2016
3#8 1#8 CU IN 3/4" EMT
60A/3P
225A/3P
70A/3P
250A/3P
200A/3P
125A/3P
400A/3P
01/29/16
200A/3P
4#6 1#6 CU IN 1" EMT
EXISTING PAD MOUNT
TRANSFORMER
EXISTING
SERVICE
GROUND
EXISTING
CT CABINET
AND METER
1
EJR
3#3 1#6 CU IN 1-1/4" EMT
JJA
(4#2/0 1#4 EQUIPMENT GND AND 1#2/0 INSULATED/ISOLATED GND) IN 2" EMT
15135
ELECTRICAL ONE-LINE DIAGRAM
E1.0
NONE
0' 1'
5'
10'
20'
1
2/10/16
STATE
COMMENTS
2
2/18/16
STATE
COMMENTS 2
Chavez Tiffany & Ayers
Engineering Corporation
46.1
144.1
PUBLIC SAFETY BUILDING - UCCS
LOAD (AMPS) FROM FEED THRU PANEL R2A
TOTAL (AMPS)
MILITARY AND STUDENT VETERAN CENTER REMODEL
119 West Cucharras Street
Colorado Springs, Colorado 80903
P (719)636-0021
ELECTRICAL
SCHEDULES
BID SET:
2/01/2016
01/29/16
EJR
JJA
15135
E2.0
0' 1'
5'
10'
20'
X
1.
2.
3.
4.
FLAG NOTES:
REMOVE AND RELOCATE EXISTING FIXTURE. RE-LAMP AND RE-BALLAST FIXTURE AS NEEDED.
REMOVE AND RELOCATE EXISTING EXIT SIGN.
DEMOLISH AND REPLACE FIXTURE WITH NEW AS INDICATED ON NEW WORK PLAN. RELOCATE
JUNCTION BOX AND BRANCH CIRCUIT TO NEW FIXTURE LOCATION INDICATED.
REPLACE FIXTURE WITH NEW AS INDICATED ON NEW WORK PLAN.
1
2/10/16
STATE
COMMENTS
2
2/18/16
STATE
COMMENTS 2
GENERAL NOTES:
1.
2.
EXIST.
MENS
GRAY LIGHTWEIGHT ITEMS ARE EXISTING TO REMAIN.
DARK DASHED ITEMS ARE TO BE DEMOLISHED.
EXIST.
WOMENS
S
F
S
S
S
F
S
S
1
S
4
2
S
1
S
F
ENTRY
CORRIDOR
S
S
3
S
S
S
2
S
F
3
4
3
PUBLIC SAFETY BUILDING - UCCS
S
J
119 West Cucharras Street
Colorado Springs, Colorado 80903
P (719)636-0021
MILITARY AND STUDENT VETERAN CENTER REMODEL
3
Chavez Tiffany & Ayers
Engineering Corporation
S
1
S
3
GFI
1
S
1
ELECTRICAL
DEMOLITION
FLOOR PLAN
BID SET:
2/01/2016
01/29/16
EJR
JJA
15135
1
ELECTRICAL DEMOLITION FLOOR PLAN
E3.0
1/4" = 1'-0"
0' 1'
5'
10'
20'
X
1.
2.
3.
4.
5.
6.
7.
C
C
1
2/10/16
STATE
COMMENTS
2
2/18/16
STATE
COMMENTS 2
C
C
C
ALL LIGHTING AND SWITCHING IN THIS AREA IS EXISTING TO REMAIN.
NEW LOCATION OF EXISTING FIXTURE TO BE REINSTALLED. CONNECT TO CIRCUIT SHOWN IN PLAN.
NOT USED.
CONNECT CORRIDOR LIGHTS TO EXISTING LIGHTING CIRCUIT.
EXISTING EXIT SIGN TO BE RE-INSTALLED AND CONNECTED TO LIGHTING CIRCUIT SHOWN IN PLAN.
NEW WALL PACK. RECONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT.
GROUND MOUNTED SPOT LIGHT TO BE LOCATED ON HILL BEHIND RETAINING WALL AND DIRECTED
AT CANOPY. COORDINATE EXACT LOCATION AND INSTALLATION WITH GENERAL CONTRACTOR AND
UCCS PROJECT MANAGER.
EXIST.
WOMENS
EXIST.
WOMENS
SHARED
OFFICE 1
C
C
S
S3
C
SHARED
OFFICE 2
(R)
C
(R)
PRIVATE
OFFICE 2
PRIVATE
OFFICE 1
C
(R)
ELECTRICAL
ROOM
(R)
X
1
2
2
2
2
Chavez Tiffany & Ayers
Engineering Corporation
L1A-5
C
D
D
119 West Cucharras Street
Colorado Springs, Colorado 80903
P (719)636-0021
D
MILITARY AND STUDENT VETERAN CENTER REMODEL
D
D
A
S
3
D
A
A
A
D
A
A
STAFF
SMALL
MEETING
D
ENTRY
CORRIDOR
RECEPTION
AE
A
AE
A
D
D
A
MECHANICAL
ROOM
A
LOUNGE
5
D
D
S S S S
D D D D
A
D
A
S
A
D
D
A
L1A-7
A
A
COMPUTERS
REAR
ENTRY
VESTIBULE
A
A
X
A
D
D
D
D
D
D
AE
D
5
6
11 H
6
H
L1A-11
PUBLIC SAFETY BUILDING - UCCS
EXIST.
MENS
C
FLAG NOTES:
L1A-13
7
NEW WORK
LIGHTING
PLAN
G
BID SET:
2/01/2016
01/29/16
EJR
JJA
15135
1
NEW WORK LIGHTING PLAN
E4.1
1/4" = 1'-0"
0' 1'
5'
10'
20'
X
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
PROVIDE DEDICATED RECEPTACLE AND CIRCUIT FOR PRINTER.
PROVIDE DEDICATED RECEPTACLE AND CIRCUIT FOR COPIER.
PROVIDE JUNCTION BOX ABOVE CEILING FOR CONNECTION TO BUILT-IN DISPLAY CASE WITH LED
PUCK LIGHTS. ELECTRICAL CONTRACTOR TO VERIFY POWER AND CONNECTION REQUIREMENTS
PRIOR TO ROUGH-IN.
PROVIDE GFI DEAD FRONT FOR REFRIGERATOR RECEPTACLE. GFI DEAD FRONT TO BE LOCATED IN
ACCESSIBLE AREA TO COMPLY WITH NEC 210.8.
ALL ELECTRICAL IN THIS AREA IS EXISTING TO REMAIN.
PROVIDE PLUGMOLD WITH DUPLEX RECEPTACLE SPACED EVERY 12" OC. MOUNT PLUGMOLD 6"
BELOW BOTTOM WINDOW SILL, FIELD VERIFY MOUNTING HEIGHT.
EXISTING FIRE SMOKE DAMPER CONNECTED TO EXISTING DUCT WORK. ELECTRICAL CONTRACTOR
TO VERIFY EXISTING ELECTRICAL CONNECTION. IF NEEDED CONNECT TO NEAREST 120V CIRCUIT.
PROVIDE GFI DEAD FRONT FOR DISHWASHER RECEPTACLE. GFI DEAD FRONT TO BE LOCATED IN
ACCESSIBLE AREA TO COMPLY WITH NEC 210.8.
PROVIDE GFI DEAD FRONT FOR MICROWAVE RECEPTACLE. GFI DEAD FRONT TO BE LOCATED IN
ACCESSIBLE AREA TO COMPLY WITH NEC 210.8.
PROVIDE IN-CARPET WIREWAY BY CONNECTRAC FOR POWER AND TELECOM CONNECTIVITY. ROUTE
FROM WALL TO DEAD END UNDER RECEPTION DESK. PROVIDE (2) DUPLEX RECEPTACLES AND
2-PORT TELECOMM DEVICE, TO BE CLEAR ANODIZED ALUMINUM FINISH. COORDINATE INSTALLATION
WITH CARPET INSTALL.
EXISTING ELECTRICAL EQUIPMENT TO REMAIN, NO NEW WORK. FOR REFERENCE ONLY.
1
2/10/16
STATE
COMMENTS
2
2/18/16
STATE
COMMENTS 2
EXIST.
WOMENS
5
SHARED
OFFICE 1
SHARED
OFFICE 2
5
PRIVATE
OFFICE 1
5
PRIVATE
OFFICE 2
7
ELEC.
CLOS.
EXIST.
MENS
FLAG NOTES:
ELECTRICAL
ROOM
11
OC
OC
F
4
GFI /OC
R1A1-52
R1A1-54
GFI/OC
Chavez Tiffany & Ayers
Engineering Corporation
7
119 West Cucharras Street
Colorado Springs, Colorado 80903
P (719)636-0021
GFI
R1A1-64
MILITARY AND STUDENT VETERAN CENTER REMODEL
STAFF
KIT.
72" 46
72"
R1A1-62
J
3
2
OC
R1A1-56
7
7
STAFF
SMALL
MEETING
7
72"
ENTRY
CORRIDOR
R1A1-49
TV
J
RECEPTION
R1A1-45
72"
MECHANICAL
ROOM
72"
10
R1A1-60
3
COMPUTERS
J
R1A1-58
4
72"
7
GFI /OC
7
1
7
LOUNGE
45
72"
R1A1-66
8
R1A1-70,72,74
R1A1-51
R1A1-53
R1A1-43
6
9
REAR
ENTRY
VESTIBULE
R1A1-68
S
GFI /OC
ECUH-1 J
F
PUBLIC SAFETY BUILDING - UCCS
R1A1-48
NEW WORK
POWER PLAN
BID SET:
2/01/2016
01/29/16
EJR
JJA
15135
1
NEW WORK POWER PLAN
E4.2
1/4" = 1'-0"
0' 1'
5'
10'
20'