SYMBOL DESCRIPTION SYMBOL LIGHT FIXTURES DESCRIPTION GENERAL NOTES SPECIAL SYSTEM SYMBOLS GENERAL: THESE DRAWINGS REMAIN THE SOLE PROPERTY OF SOL CHAVEZ AND ASSOCIATES AND MAY BE USED ONLY FOR THE PROJECT AS INDICATED BY NAME AND LOCATION. ANY OTHER USE REQUIRES PRIOR, WRITTEN PERMISSION. THE CONTRACTOR WILL PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, TOOLS, TRANSPORTATION, LICENSES, FEES, PERMITS, ETC. TO COMPLETE THE ELECTRICAL WORK DESCRIBED ON THE DRAWINGS. THE CONTRACTOR WILL WARRANT EQUIPMENT, MATERIAL AND WORKMANSHIP FOR A MINIMUM PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE. WARRANTY SHALL INCLUDE REPLACEMENTS OR REPAIRS WITHOUT COST TO THE OWNER DURING THE WARRANTY PERIOD. ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) 2011 AND ALL OTHER APPLICABLE LOCAL CODES AND ORDINANCES. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS. PUSHBUTTON OPERATOR. CEILING MOUNTED SPEAKER RECESSED FLUORESCENT LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. S S WALL MOUNTED SPEAKER SURFACE FLUORESCENT LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. E NURSE/EMERGENCY CALL BUTTON N NURSE/EMERGENCY CALL BUTTON 1 2/10/16 STATE COMMENTS 2 2/18/16 STATE COMMENTS 2 FLUORESCENT STRIP LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. USE OF DRAWINGS: DO NOT SCALE FROM THE ELECTRICAL DRAWINGS. FOR EXACT LOCATIONS USE ARCHITECT'S DIMENSIONED DRAWINGS, SHOP DRAWINGS AND FIELD MEASUREMENTS. VERIFY ALL LOCATIONS WITH THE ARCHITECT PRIOR TO ELECTRICAL ROUGH-IN. COMMUNICATION SYSTEM SYMBOLS WALL BRACKET FLUORESCENT LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. WIRING METHODS: ALL WIRING FOR LIGHTING AND POWER SYSTEMS WILL BE IN CONDUIT OR CABLE ASSEMBLIES APPROVED BY THE GOVERNING AUTHORITIES. CONDUCTOR SIZES SHOWN ARE BASED ON AMPACITIES FOR COPPER CONDUCTORS, #12 AWG FOR BRANCH CIRCUITS MIN. WHEN APPROVED BY ENGINEER, FEEDERS MAY BE ALUMINUM CONDUCTORS OF EQUIVALENT AMPACITIES. GROUNDING CONDUCTORS SHALL BE PROVIDED FOR ALL CIRCUITS SHOWN ON THE DRAWINGS. PROVIDE BLOCKING AND OTHER NECESSARY SUPPORTS IN WALLS AND CEILINGS FOR MATERIAL AND EQUIPMENT TO BE PROVIDED. BRANCH CIRCUIT NUMBERS SHOWN ON THE DRAWINGS MAY BE REARRANGED WITHIN A GIVEN PANELBOARD TO SUIT THE NEEDS OF THE INSTALLATION. ELECTRICAL BRANCH CIRCUITS SHALL BE BALANCED BETWEEN LINES AND PHASES. MULTIWIRE BRANCH CIRCUITS SHALL HAVE A MEANS TO SIMULTANEOUSLY DISCONNECT ALL UNDERGROUNDED CONDUCTORS AT THE POINT WHERE BRANCH CIRCUITS ORIGINATE (HANDLE TIES ARE AN APPROVED MEANS). THE GROUNDED AND UNDERGROUNDED CONDUCTOR OF EACH MULTIWIRE BRANCH CIRCUIT SHALL BE GROUPED BY WIRE TIES AT ONE LOCATION IN PANELBOARD. ALL PATIENT CARE AREAS SHALL COMPLY WITH NEC 517.13(A)(B) TO INCLUDE LUMINAIRES. TELEPHONE OUTLET. WIRING BY OTHERS, UNO. MOUNT 18" AFF. WALL MOUNTED LIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. TELEPHONE OUTLET. WIRING BY OTHERS, UNO., WALL PHONE, MOUNT 48" AFF. W DATA OUTLET. WIRING BY OTHERS, UNO. MOUNT 18" AFF. RECESSED CEILING MOUNTED DOWNLIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. DATA/TELEPHONE OUTLET, WIRING BY OTHERS UNO. MOUNT 18" AFF. CABLE TV OUTLET, WIRING BY OTHERS, UNO. MOUNT 18" AFF. TV SURFACE MOUNTED CEILING DOWNLIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. T PENDANT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. TRACK HEAD FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. FIRE ALARM SYMBOLS UTILITY COORDINATION: PROVIDE ALL COORDINATION WITH THE UTILITY INCLUDING LOAD DATA FORMS AND APPLICATION FOR SERVICE AS APPLICABLE. INSTALLATION OF SERVICE, PRIMARY OR SECONDARY FEEDERS AND METERING SHALL BE PERFORMED IN ACCORDANCE WITH THE UTILITIY REQUIREMENTS. HORN ONLY THERMOSTAT. PROVIDED BY MECHANICAL., INSTALLED BY ELECTRICIAN. LINE VOLTAGE F HORN AND STROBE PARKING LOT POLE LIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. STROBE ONLY F MANUAL PULL STATION S SMOKE DETECTOR H HEAT DETECTOR S GROUNDING: PROVIDE A COMPLETE GROUNDING SYSTEM AS REQUIRED BY THE NEC AND LOCAL AUTHORITIES HAVING JURISDICTION. ALL BRANCH CIRCUITS SHALL INCLUDE A GROUND CONDUCTOR. USE OF RACEWAY FOR GROUNDING IS NOT PERMITTED. GALVANIZED GROUND RODS ARE NOT PERMITTED. PANELBOARDS: PROVIDE MINIMUM INTEGRATED EQUIPMENT SHORT CIRCUIT RATING AS INDICATED ON PANEL SCHEDULES. PROVIDE BOLT-ON BREAKERS UNLESS OTHERWISE NOTED. PROVIDE CIRCUIT BREAKERS SHOWN ON THE PANELBOARD SCHEDULES. ALL TERMINATIONS AND LUGS SHALL BE RATED FOR 75-DEGREE CONDUCTORS. PROVIDE TYPEWRITTEN CIRCUIT SCHEDULES TO IDENTIFY PANELBOARD AND EACH BRANCH BREAKER. ACCEPTABLE MANUFACTURERS ARE SQUARE D, SIEMENS AND EATON. DUCT SMOKE DETECTOR D MAGNETIC DOOR HOLD OPEN LIGHT FIXTURE WITH EMERGENECY BALLAST, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. FIRE/SMOKE DAMPER WIRING DEVICES: PROVIDE SPECIFICATION GRADE 15 AND 20- AMPERE SWITCH AND RECEPTACLE DEVICES, AS APPLICABLE. OTHER DEVICES SHALL BE PROVIDED AS INDICATED AND SHALL MATCH PLUG-CONNECTED EQUIPMENT FURNISHED FOR THE PROJECT. DEVICE WALL PLATES SHALL BE SMOOTH, NYLON TYPE AND SHALL BE OFFICE WHITE IN COLOR OR AS OTHERWISE SPECIFIED. DEVICE COLOR SHALL MATCH WALL PLATES. FIRE ALARM CONTROL PANEL EMERGECY LIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. ANNUNCIATION PANEL EXIT SIGN, WITH TYPE NOTED IN PLAN, SEE PLAN FOR ARROWS AND FACE OF EXIT NEEDED. SEE FIXTURE SCHEDULE FOR DETAILS. ONE-LINE SYMBOLS SWITCHES CIRCUIT BREAKER, FRAME AND TRIP AS INDICATED. TOGGLE SWITCH, 20A, SINGLE POLE, VOLTAGE AS REQUIRED. MOUNTED AT 48" ABOVE FINIDHED FLOOR. POWER TRANSFORMER, RATING AS INDICATED. DISCONNECT SWITCHES: HEAVY DUTY QUICK-MAKE, QUICK-BREAK TYPE, NON-FUSED UNLESS OTHERWISE NOTED. PROVIDE MEANS TO LOCK SWITCH IN OFF POSITION WITH PAD-LOCK. ENCLOSURES SHALL BE NEMA TYPE 1 OR NEMA TYPE 3R FOR OUTDOOR INSTALLATION. PROVIDE PERMANENT LABELS FOR DISCONNECTS TO INDICATE EQUIMENT SERVED. LIGHTING FIXTURES: SEE LIGHT FIXTURE SCHEDULE. PROVIDE ALL FIXTURES WITH LAMPS AS INDICATED. WHERE REQUIRED, FIXTURES SHALL BE WET OR DAMP LOCATION LABELED. VERIFY MOUNTING HEIGHTS PRIOR TO ELECTRICAL ROUGH-IN. PROVIDE ALL REQUIRED MOUNTING ACCESSORIES REQUIRED FOR PROPER MOUNTING TO SURFACES SUCH ACCESSORIES TO INCLUDE BUT NOT LIMITED TO SLOPE ADAPTORS. CANOPIES, AND VAULTED CEILING CANOPIES, ETC. PROVIDE DISCONNECTING MEANS FOR LUMINAIRES THAT UTILIZE DOUBLE-ENDED LAMPS AND BALLASTS(S) IN ACCORDANCE WITH NEC 410.130(G)(1). ALTERNATES NOT ACCEPTABLE UNLESS NOTED AS "OR EQUAL" ON LIGHT FIXTURE SCHEDULE. S OCCUPANCY SENSOR, WALL MTD., 48" AFF. SENSOR SWITCH WSD PDT, OR EQUAL OCCUPANCY SENSOR, CEILING MTD. SENSOR SWITCH CMR PDT OR EQUAL GROUND ELECTRODE PHOTOCELL SWITCH, MOUNT ON NORTH FACING EXTERIOR WALL, UNO. CURRENT TRANSFORMER (CT) VOICE/DATA: RACEWAY SYSTEM BY CONTRACTOR. ALL RACEWAYS SHALL BE PROVIDED WITH PULLSTRINGS OF MINIMUM OF 400-LB. TEST STRENGTH. ALL EQUIPMENT, RECEPTACLES AND CABLING BY OTHERS. PROVIDE BLANK COVERS OVER ALL UNUSED OUTLETS. CABLES, DEVICES AND CABLE TERMINATION IS BY OTHERS. SUBSCRIPTS FOR SWITCHES NON-FUSIBLE SWITCH, RATING AS INDICATED. 3 THREE-WAY TOGGLE SWITCH 4 FOUR-WAY TOGGLE SWITCH D 0 - 10 VOLT ELECTRONIC DIMMER SWITCH, 1000W, 120V LUTRON DIVA OR EQUAL, UNO. COORDINATE COMPATIBLE DIMMER WITH LIGHTING MANUFACTURER. M MANUAL MOTOR STARTER WITH THERMAL OVERLOAD FIRE ALARM: BY SIMPLEX TO PROVIDE AS REQUIRED PER FIRE AND LOCAL CODES. FUSIBLE SWITCH, RATING AND FUSE SIZE AS INDICATED. FEEDER SCHEDULE KEY TAG UTILITY TRANSFORMER RECEPTACLES UTILITY ELECTRIC METER M DUPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO., MOUNT 18" AFF. CRGA CR2A Chavez Tiffany & Ayers Engineering Corporation UPS2 119 West Cucharras Street Colorado Springs, Colorado 80903 P (719)636-0021 QUAD RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO., MOUNT 18" AFF. MOTOR WITH DISCONNECT SIMPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO. MOUNT 18" AFF. MCB SPECIAL RECEPTACLE, 220V, TYPE AS INDICATED OR MATCH EQUIPMENT CAP., MOUNT AT HEIGHT AS REQUIRED PER EQUIPMENT. MOTOR WITH CONTROLLER AND DISCONNECT DUPLEX RECEPTACLE, 20A, 120V, 3 WIRE GROUNDED, NEMA 5-20R, UNO., WITH TIE-BAR REMOVED FOR SWITCHING., MOUNT 18" AFF. SPECIAL PURPOSE RECEPTACLE, NEMA TYPE AS INDICATED., MOUNT AT HEIGHT AS REQUIRED PER EQUIPMENT. FLOOR BOX DUPLEX RECEPTACLE, FLUSH MOUNTED, PROVIDE COVER AS REQUIRED. GENERATOR G FLOOR BOX QUAD RECEPTACLE, FLUSH MOUNTED, PROVIDE COVER AS REQUIRED. N S L TRANSFER SWITCH 15KVA 3PH 480V DELTA PRI. WEATHERHEAD 208Y/120V SEC SUBSCRIPTS FOR RECEPTACLES C CLOCK RECEPTACLE CE CEILING FLUSH MOUNTED IG ISOLATED GROUND GFI GROUND FAULT INTERRUPTER WR WEATHER RESISTANT WITH GROUND FAULT INTERRUPTER IN WEATHER PROOF BOX OC OVER COUNTER, MOUNT RECEPTACLE MOUNTED 6" ABOVE BACKSPLASH. UNO UNLESS NOTED OTHERWISE. UC UNDER COUNTER TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR EWC ELECTRIC WATER COOLER, PROVIDE GFI PROTECTION E EXISTING DEVICE TO REMAIN. N NEW DEVICE TO BE INSTALLED H MOUNT DEVICE 6" AFF, HORIZONTALLY. TP TAMPER-PROOF SWD SWITCH RATED BREAKERS NL NIGHTLIGHT WIRED FIXTURE POWER SYMBOLS J J JUNCTION BOX, FLUSH/SURFACE MTD. POWER POLE WITH COMM AND POWER. 150AF 70AF 200A/3P 100A/3P ID PANELBOARD OR LOADCENTER, IDENTIFICATION, AMPERES AND VOLTAGE. ABBREVIATIONS TVSS CLGA CL1A UPS 45KVA 3PH 480V DELTA PRI. 208Y/120V SEC FEEDER SCHEDULE 5(4#400 CU IN 3" PVC) MAIN BREAKER GFI 225A/3P MOTOR 3#3 1#6 CU IN 1-1/2" EMT 30A/3P 100A/3P 100A/3P 70A/3P 40A/3P NON FUSIBLE DISCONNECT SWITCH, RATING AS INDICATED. 4#250 1#2 CU IN 2-1/2" EMT FUSIBLE DISCONNECT SWITCH, RATING AS INDICATED. 4#4/0 1#2 CU IN 2-1/2" EMT PANELBOARD/LOADCENTER. 3#1 1#6 CU IN 1-1/4" EMT CEILING MOUNTED PAD FAN. NOTE: NOT ALL SYMBOLS ARE USED. VERIFY ALL CONNECTIONS AND RECEPTACLE TYPES FOR EQUIPMENT EQUIPMENT FROM APPROVED MECHANICAL AND EQUIPMENT SUBMITTALS PRIOR TO INSTALLATION. RGA NOTES: 1. ALL ELECTRICAL EQUIPMENT, FEEDERS AND PANELBOARDS ARE EXISTING TO REMAIN UNLESS NOTED OTHER WISE. 2. PROVIDE NEW BREAKERS IN EXISTING PANELS AS NEEDED. CONTRACTOR TO VERIFY NUMBER AND SIZE OF NEEDED BREAKERS. 3. NEW ADDED BREAKERS TO HAVE AIC RATING AND SAME MANUFACTURER MATCHING EXISTING IN ORDER TO MAINTAIN SERIES RATING. 4. CONTRACTOR SHALL VERIFY ALL BRANCH CIRCUITS AND PROVIDE TYPE WRITTEN UPDATED PANEL DIRECTORY FOR ALL PANELS. 5. SECOND FLOOR PANELS ARE CONNECTED WITH FEED THROUGH LUGS FROM FIRST FLOOR PANELS. R2A 5#10 CU IN 3/4" EMT GENERATOR MCB G MCB 2(4#4/0 1#2 CU IN 2-1/2" EMT) 4#3 1#6 CU IN 1-1/2" EMT R1A ELEVATOR 15KVA 3PH 480V DELTA PRI. GFI 225A/3P R1A1 M2A NOT USED MCB 3#6 1#6 CU IN 1" EMT 208Y/120V SEC 3#4 1#8 CU IN 1-1/4" EMT (4#3 1#6 EQUIPMENT GND AND 1#3 INSULATED/ISOLATED GND) IN 1-1/2" EMT TVSS LGA L N L1A M1A SM (4#1 1#6 EQUIPMENT GND AND 1#1 INSULATED/ISOLATED GND) IN 1-1/2" EMT 75KVA 3PH 480V DELTA PRI. SHUNT TRIP 70A/3P 4#2/0 1#4 CU IN 2-1/2" EMT 208Y/120V SEC ELECTRICAL LEGEND NOT USED 4#4 1#6 CU IN 1" EMT SERVICE MAIN 1600AS/3P PUBLIC SAFETY BUILDING - UCCS BOLLARD OR POST LIGHT, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. F MILITARY AND STUDENT VETERAN CENTER REMODEL SPOTLIGHT FIXTURE, WITH TYPE NOTED IN PLAN. SEE FIXTURE SCHEDULE FOR DETAILS. BID SET: 2/01/2016 3#8 1#8 CU IN 3/4" EMT 60A/3P 225A/3P 70A/3P 250A/3P 200A/3P 125A/3P 400A/3P 01/29/16 200A/3P 4#6 1#6 CU IN 1" EMT EXISTING PAD MOUNT TRANSFORMER EXISTING SERVICE GROUND EXISTING CT CABINET AND METER 1 EJR 3#3 1#6 CU IN 1-1/4" EMT JJA (4#2/0 1#4 EQUIPMENT GND AND 1#2/0 INSULATED/ISOLATED GND) IN 2" EMT 15135 ELECTRICAL ONE-LINE DIAGRAM E1.0 NONE 0' 1' 5' 10' 20' 1 2/10/16 STATE COMMENTS 2 2/18/16 STATE COMMENTS 2 Chavez Tiffany & Ayers Engineering Corporation 46.1 144.1 PUBLIC SAFETY BUILDING - UCCS LOAD (AMPS) FROM FEED THRU PANEL R2A TOTAL (AMPS) MILITARY AND STUDENT VETERAN CENTER REMODEL 119 West Cucharras Street Colorado Springs, Colorado 80903 P (719)636-0021 ELECTRICAL SCHEDULES BID SET: 2/01/2016 01/29/16 EJR JJA 15135 E2.0 0' 1' 5' 10' 20' X 1. 2. 3. 4. FLAG NOTES: REMOVE AND RELOCATE EXISTING FIXTURE. RE-LAMP AND RE-BALLAST FIXTURE AS NEEDED. REMOVE AND RELOCATE EXISTING EXIT SIGN. DEMOLISH AND REPLACE FIXTURE WITH NEW AS INDICATED ON NEW WORK PLAN. RELOCATE JUNCTION BOX AND BRANCH CIRCUIT TO NEW FIXTURE LOCATION INDICATED. REPLACE FIXTURE WITH NEW AS INDICATED ON NEW WORK PLAN. 1 2/10/16 STATE COMMENTS 2 2/18/16 STATE COMMENTS 2 GENERAL NOTES: 1. 2. EXIST. MENS GRAY LIGHTWEIGHT ITEMS ARE EXISTING TO REMAIN. DARK DASHED ITEMS ARE TO BE DEMOLISHED. EXIST. WOMENS S F S S S F S S 1 S 4 2 S 1 S F ENTRY CORRIDOR S S 3 S S S 2 S F 3 4 3 PUBLIC SAFETY BUILDING - UCCS S J 119 West Cucharras Street Colorado Springs, Colorado 80903 P (719)636-0021 MILITARY AND STUDENT VETERAN CENTER REMODEL 3 Chavez Tiffany & Ayers Engineering Corporation S 1 S 3 GFI 1 S 1 ELECTRICAL DEMOLITION FLOOR PLAN BID SET: 2/01/2016 01/29/16 EJR JJA 15135 1 ELECTRICAL DEMOLITION FLOOR PLAN E3.0 1/4" = 1'-0" 0' 1' 5' 10' 20' X 1. 2. 3. 4. 5. 6. 7. C C 1 2/10/16 STATE COMMENTS 2 2/18/16 STATE COMMENTS 2 C C C ALL LIGHTING AND SWITCHING IN THIS AREA IS EXISTING TO REMAIN. NEW LOCATION OF EXISTING FIXTURE TO BE REINSTALLED. CONNECT TO CIRCUIT SHOWN IN PLAN. NOT USED. CONNECT CORRIDOR LIGHTS TO EXISTING LIGHTING CIRCUIT. EXISTING EXIT SIGN TO BE RE-INSTALLED AND CONNECTED TO LIGHTING CIRCUIT SHOWN IN PLAN. NEW WALL PACK. RECONNECT TO EXISTING EXTERIOR LIGHTING CIRCUIT. GROUND MOUNTED SPOT LIGHT TO BE LOCATED ON HILL BEHIND RETAINING WALL AND DIRECTED AT CANOPY. COORDINATE EXACT LOCATION AND INSTALLATION WITH GENERAL CONTRACTOR AND UCCS PROJECT MANAGER. EXIST. WOMENS EXIST. WOMENS SHARED OFFICE 1 C C S S3 C SHARED OFFICE 2 (R) C (R) PRIVATE OFFICE 2 PRIVATE OFFICE 1 C (R) ELECTRICAL ROOM (R) X 1 2 2 2 2 Chavez Tiffany & Ayers Engineering Corporation L1A-5 C D D 119 West Cucharras Street Colorado Springs, Colorado 80903 P (719)636-0021 D MILITARY AND STUDENT VETERAN CENTER REMODEL D D A S 3 D A A A D A A STAFF SMALL MEETING D ENTRY CORRIDOR RECEPTION AE A AE A D D A MECHANICAL ROOM A LOUNGE 5 D D S S S S D D D D A D A S A D D A L1A-7 A A COMPUTERS REAR ENTRY VESTIBULE A A X A D D D D D D AE D 5 6 11 H 6 H L1A-11 PUBLIC SAFETY BUILDING - UCCS EXIST. MENS C FLAG NOTES: L1A-13 7 NEW WORK LIGHTING PLAN G BID SET: 2/01/2016 01/29/16 EJR JJA 15135 1 NEW WORK LIGHTING PLAN E4.1 1/4" = 1'-0" 0' 1' 5' 10' 20' X 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. PROVIDE DEDICATED RECEPTACLE AND CIRCUIT FOR PRINTER. PROVIDE DEDICATED RECEPTACLE AND CIRCUIT FOR COPIER. PROVIDE JUNCTION BOX ABOVE CEILING FOR CONNECTION TO BUILT-IN DISPLAY CASE WITH LED PUCK LIGHTS. ELECTRICAL CONTRACTOR TO VERIFY POWER AND CONNECTION REQUIREMENTS PRIOR TO ROUGH-IN. PROVIDE GFI DEAD FRONT FOR REFRIGERATOR RECEPTACLE. GFI DEAD FRONT TO BE LOCATED IN ACCESSIBLE AREA TO COMPLY WITH NEC 210.8. ALL ELECTRICAL IN THIS AREA IS EXISTING TO REMAIN. PROVIDE PLUGMOLD WITH DUPLEX RECEPTACLE SPACED EVERY 12" OC. MOUNT PLUGMOLD 6" BELOW BOTTOM WINDOW SILL, FIELD VERIFY MOUNTING HEIGHT. EXISTING FIRE SMOKE DAMPER CONNECTED TO EXISTING DUCT WORK. ELECTRICAL CONTRACTOR TO VERIFY EXISTING ELECTRICAL CONNECTION. IF NEEDED CONNECT TO NEAREST 120V CIRCUIT. PROVIDE GFI DEAD FRONT FOR DISHWASHER RECEPTACLE. GFI DEAD FRONT TO BE LOCATED IN ACCESSIBLE AREA TO COMPLY WITH NEC 210.8. PROVIDE GFI DEAD FRONT FOR MICROWAVE RECEPTACLE. GFI DEAD FRONT TO BE LOCATED IN ACCESSIBLE AREA TO COMPLY WITH NEC 210.8. PROVIDE IN-CARPET WIREWAY BY CONNECTRAC FOR POWER AND TELECOM CONNECTIVITY. ROUTE FROM WALL TO DEAD END UNDER RECEPTION DESK. PROVIDE (2) DUPLEX RECEPTACLES AND 2-PORT TELECOMM DEVICE, TO BE CLEAR ANODIZED ALUMINUM FINISH. COORDINATE INSTALLATION WITH CARPET INSTALL. EXISTING ELECTRICAL EQUIPMENT TO REMAIN, NO NEW WORK. FOR REFERENCE ONLY. 1 2/10/16 STATE COMMENTS 2 2/18/16 STATE COMMENTS 2 EXIST. WOMENS 5 SHARED OFFICE 1 SHARED OFFICE 2 5 PRIVATE OFFICE 1 5 PRIVATE OFFICE 2 7 ELEC. CLOS. EXIST. MENS FLAG NOTES: ELECTRICAL ROOM 11 OC OC F 4 GFI /OC R1A1-52 R1A1-54 GFI/OC Chavez Tiffany & Ayers Engineering Corporation 7 119 West Cucharras Street Colorado Springs, Colorado 80903 P (719)636-0021 GFI R1A1-64 MILITARY AND STUDENT VETERAN CENTER REMODEL STAFF KIT. 72" 46 72" R1A1-62 J 3 2 OC R1A1-56 7 7 STAFF SMALL MEETING 7 72" ENTRY CORRIDOR R1A1-49 TV J RECEPTION R1A1-45 72" MECHANICAL ROOM 72" 10 R1A1-60 3 COMPUTERS J R1A1-58 4 72" 7 GFI /OC 7 1 7 LOUNGE 45 72" R1A1-66 8 R1A1-70,72,74 R1A1-51 R1A1-53 R1A1-43 6 9 REAR ENTRY VESTIBULE R1A1-68 S GFI /OC ECUH-1 J F PUBLIC SAFETY BUILDING - UCCS R1A1-48 NEW WORK POWER PLAN BID SET: 2/01/2016 01/29/16 EJR JJA 15135 1 NEW WORK POWER PLAN E4.2 1/4" = 1'-0" 0' 1' 5' 10' 20'