ADDENDUM No. 01 TO THE BIDDING AND CONTRACT DOCUMENTS FOR

advertisement
ADDENDUM No. 01
TO THE BIDDING AND
CONTRACT DOCUMENTS FOR
THE PROJECT:
UCCS University Hall Remodel, Simulation Lab
LKA PROJECT NO. 09.028
DATE: 05 December 2011
THE ARCHITECT:
THE LKA PARTNERS, INC.
430 NORTH TEJON STREET - SUITE 208
COLORADO SPRINGS, COLORADO 80903
THE FOLLOWING shall become as fully a part of the above named Bidding and Contract Documents
as if included and shall take full and complete precedence over anything stated or shown to the
contrary in them.
ACKNOWLEDGMENT: Each bidder shall indicate in the place provided on the Bid Form
acknowledgement of receipt of this Addendum.
EACH AND EVERY BIDDER, subcontractor and material supplier shall be responsible for reading
each and every item in this Addendum to ascertain the extent and manner it affects the work in which
he is interested.
The Addendum items may not be listed in the same order that they occur on the Drawings or in the
Project Manual.
1
A.
PROJECT MANUAL.BIDDING REQUIREMENTS, CONTRACT FORMS AND
CONDITIONS OF THE CONTRACT
No Changes
B.
PROJECT MANUAL / SPECIFICATIONS
SECTION 08 81 00
Glazing
2.02 GLASS TYPES
Delete existing paragraph 2.02 in its entirety and replace with the following
TYPE
DESCRIPTION
AT
1/4“ clear tempered
BT
1/4“ Viracon “Optigray” monolithic tempered glass with perforated window film.
Film shall be Koroseal Perforated Vinyl Window Film, or equivalent of other
manufacturer.
1.
Thickness: 5.8 mil.
2.
Open area: 30%
3.
Adhesive: Removable acrylic based clear adhesive
4.
Flammability: M1 and B1 certified.
5.
Pattern and Color: patterns shall be from digital image provided by the
Owner. Color of film shall be white on image side, black side applied to
glass
SECTION 23 81 29
VARIABLE REFRIGERANT FLOW AIR-CONDITIONING
Add the following paragraphs:
2.06 E 3. The following operation/settings shall be provided by the Campus EMCS:
Request all Off (Emergency Stop)
Request On/Off
Setpoint
Request Lossnay Mode
Request Fan Speed
Filter sign reset
Request Local Prohibit On/Off, Mode, and Filter Sign
Filter Sign Reset
Request Limit Temperature Setting Range
Ventilation Mode
2
2.06 E 4. The following points shall be measured/monitored by the Campus EMCS:
Emergency state
On/Off run state
Mode state
Setpoint state
Lossnay mode state
Fan Speed state
Filter status
Space Temperature
Alarm state
Error Code
Ventilation Mode
C.
DRAWINGS
SHEET TS1.1
Title Sheet
At the Door Elevation, at the word “glazing” add the words “type AT”
SHEET A2.1
Partial Floor Plan
Add the note:
NOTE: SEE SHEET P1.1 FOR THE LOCATION OF SANITARY SEWER PIPING. IF
PENETRATION OF THE EXISTING LOWER 4” CONCRETE SLAB IS REQUIRED,
PATCH AND REPAIR EXISTING VAPOR BARRIER AND SLAB TO MATCH EXISTING
CONDITIONS, REINSTALL GRAVEL AND INSTALL NEW 4” SLAB ON TOP TO MATCH
EXISTING.
At MED ROOM/170F and at AV ROOM/1S-2 delete the finish schedule remark (2)
SHEET A3.1
Reflected Ceiling Plan
Ceiling Legend: revise the note, “AREAS OF CEILING PANEL REPAIR: PROVIDE (N)
GRID & ACOUSTICAL CLG PANEL TO CMPLETE CLG.” To read,
“AREAS OF CEILING REPAIR: PATCH WITH CEILING WITH
SALVAGED, EXISTING GRID AND ACOUSTICAL TILES.”
SHEET A8.1
Casework and Interior Elevations
At the Equipment Schedule, item <E29>, change the manufacturers name from Metro to
Pocket Nurse and change the item number from 02-25-257W to 02-25-257M
SHEET A9.1
General Building Details
At the Hollow Metal Frame Elevations, at the note “glazing type BT” to frame elevations
HM2 and HM3
Replace detail 18/A9.1 with the attached detail 18/A9.1 on sheet A9.1.1
3
SHEET M1.1
MECHANICAL PLANS
Add General Note 3 as follows:
Tie variable refrigerant flow air-conditioning and ventilation control systems into
existing Setpoint Systems Corporation (303-733-2300) building management
system via BACnet interface.
SHEET E0.1
Electrical Legend
Remove General Note #8. See attached sheet E0.1.1
SHEET E1.1
Lighting & Fire Alarm Plan
Add ceiling mounted occupancy sensors/relays in Simlab control rooms. See sheet E1.1.1
Specify a circuit number on panel L for the new lighting circuit as L-30. See sheet E1.1.1
Edit Keynote #5 to provide a new breaker for the new lighting circuit. See sheet E1.1.1
SHEET E2.1
Power & Signal Plan
Change receptacles in Sim 1 to GFCI near sinks. See sheet E2.1.1
Change receptacles in Sim 3 to GFCI near sinks. See Sheet E2.1.2
Add receptacle for EMS monitor on west wall of control room. See Sheet E2.1.1
Add junction box for automatic sink power in Sim 3. See Sheet E2.1.2
Remove monitor receptacle on southwest wall in Briefing Room 135. See Sheet E2.1.2
Edit Keynote #6 to include specific information regarding transformer size and fusing. See
Sheet E2.1.2
SHEET E4.1
Electrical Schedules
Add the new lighting circuit information into existing Panel L; add note to provide new circuit
breaker. See sheet E4.1.1
SHEET T0.2
TECHNOLOGY SCHEDULES/LEGENDS SHEET
Add the following Project Notes:
X REFER TO SHEET ED.1, PARTIAL ELECTRICAL DEMOLITION PLAN, FOR
LOCATIONS OF EXISTING DATA OUTLETS TO BE REMOVED. REMOVE
EXISTING FACEPLATE, BOX, CONDUIT, AND CABLING. REMOVE CABLING
ALL THE WAY FROM OUTLET BOX BACK TO EXISTING TELECOM ROOM.
REFER ALSO TO SPECIFICATION 27 17 30, COMMUNICATIONS – DEMOLITION.
Y REMOVE ALL UNUSED COMMUNICATIONS HANGERS, CABLE TRAY, AND
SUPPORTS ABOVE EXISTING CEILINGS IN ALL AREAS OF DEMOLITION. DO NOT
REMOVE ANY WHICH MAY BE SUPPORTING EXISTING CABLING THAT WILL
REMAIN TO SERVE ADJOING SPACES THAT ARE OUTSIDE THE AREA OF WORK.
4
D.
APPROVAL OF MATERIALS AND MANUFACTURED ITEMS
SECTION 23 72 00
ENERGY RECOVERY VENTILATORS
Add paragraph 2.02.A.8. Daikin AC (Americas), Inc.
END OF ADDENDUM No. 01
5
Download