SITE PLANNING DATA—LIEBERT® EXL™ 625-1200KVA SINGLE-MODULE AND 1+N SYSTEMS Table 1 Site planning data—Liebert eXL 625-1200kVA SMS UPS Rating Rectifier AC Input Current Bypass AC Input Current UPS AC Output Current Battery External External External External External External Breaker Breaker Breaker Breaker Breaker Breaker Max. Heat Trip Amp Trip Amp Trip Amp Trip Amp Trip Amp Trip Amp Max. External Dissipation Input (80% (100% (80% (100% (80% (100% Nom, Current Breaker Full Load Voltage Rated) Nom Rated) Rated) Nom Rated) Rated) VDC at EOD Trip Amps BTU/H VAC Nom Max Rated) Dimensions WxDxH in (mm) Approx. Weight Eff. Eff. Unpacked AC-AC DC-AC lb (kg) 100% 100% kVA kW 625 625 480 779 818 1200 900 752 1000 800 752 1000 800 480 1624 2000 77,348 5735(2601) ≥96.5% ≥96.5% 625-750* 625-750* 480 935 981 1400 1000 902 1200 1000 902 1200 1000 480 1949 2000 92,817 5735(2601) ≥96.4% ≥96.4% 625-800* 625-800* 480 995 1044 1400 1200 962 1200 1000 962 1200 1000 480 2079 2500 101,940 750 750 480 935 1400 1000 902 1200 1000 902 1200 1000 480 1949 2000 92,817 125.2x33.5x76.8 (3145x850x1950) 5735(2601) ≥96.5% ≥96.5% 5735(2601) ≥96.5% ≥96.5% 5735(2601) ≥96.4% ≥96.4% 981 800 800 480 995 1044 1400 1200 962 1400 1000 962 1400 1000 480 2079 2500 101,940 1000 1000 480 1244 1308 2000 1600 1203 1600 1400 1203 1600 1400 480 2588 3000 123,756 8050(3651) ≥96.5% ≥96.5% 1000-1100* 1000-1100* 480 1368 1438 2000 1600 1323 2000 1400 1323 2000 1400 480 2847 3000 136,132 8050(3651) ≥96.4% ≥96.4% 1000-1200* 1000-1200* 480 1493 1569 2000 1600 1443 2000 1600 1443 2000 1600 480 3106 4000 152,909 480 1368 1438 2000 1600 1323 2000 1400 1323 2000 1400 480 2847 3000 136,132 171.7x33.5x76.8 8050(3651) ≥96.5% ≥96.5% (4330x850x1950) 8050(3651) ≥96.5% ≥96.5% 480 1493 1569 2000 1600 1443 2000 1600 1443 2000 1600 480 3106 4000 152,909 8050(3651) ≥96.5% ≥96.5% 480 1493 1569 2000 1600 1443 2000 1600 1443 2000 1600 480 3106 4000 152,909 1100 1100 1100-1200* 1100-1200* 1200 1200 See Notes below: 1,2,4,6,7,8 3,4,6,7,8 3,4,6,7,8 * Capacity on Demand Unit. Breakers, cables and other infrastructure must be sized for maximum planned capacity. 5,6,7,8 — 8050(3651) ≥96.4% ≥96.4% 9,10,11 9 — — Specifications are subject to change. Notes for Tables 1, 2 and 3 1. 2. 3. 4. 5. 6. Nominal rectifier AC input current (continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (non-continuous) at 100% rated load. Both nominal and maximum currents are calculated at nominal voltage. The recommended external breakers are based on nominal conditions; 100% load with maximum battery recharge current at nominal voltage. Bypass AC input and AC output current (considered continuous) is based on full rated output load. Feeder protection, (by others) for rectifier AC input and bypass AC input are recommended to be provided by separate overcurrent protection devices. UPS output load cables must be run in separate conduit from input cables. Power cable from module DC bus to battery should be sized for a total maximum 2.0V line drop (power cable drop plus return cable drop as measured at the module) at maximum discharge current. Grounding conductors to be sized per NEC 250-95. 7. Rectifier AC Input: 3-phase, 3-wire, plus ground Bypass AC Input: 3-phase, 3-wire, plus ground AC Output to Load: 3-phase, 3-wire, plus ground Module DC Input from Battery: 2-wire (positive and negative), plus ground 8. All wiring is to be in accordance with national and local electrical codes. 9. Minimum overhead clearance is 2 ft. (0.6m) above the UPS. 10. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size. 11. Control wiring and power cables must be run in separate conduits. 12. The rectifier overload current is controlled by the the input current limit setting, which is adjustable from 25 to 200% (default:125%). If a smaller feed breaker is used, the input current limit can be adjusted lower to limit the maximum input current. See your Emerson representative for more information. For system breaker coordination, See your Emerson representative for information on the overload v. time profile for the rectifier, bypass and output. 1 Figure 1 One-line drawing—Liebert eXL 625-1200kVA single-module system Maintenance Bypass Panelboard/Switchboard Table 2 HRG compatability UPS Modules HRG Current Rating, A 1 5 2 8 3 10 4 12 5 15 6 18 MBB * Bypass AC Input 3-Wire + GND BIB MIB See Note 6 UPS Output 3-Wire + GND UPS Cabinet NOTES 1. UPS rectifier input and bypass input must be fed from a common, securely grounded wye source. Contact the factory if separate sources are required for the rectifier and bypass. 2. Refer to Table 2 for High Resistance Ground (HRG) compatibility. Contact the factory for further infomation. 3. UPS rectifier input, bypass input and AC output cables must be run in separate conduits. 4. All power cables from DC supply should be sized for a total maximum 2V drop at maximum discharge current. 5. Control wiring and power wiring must be run in separate conduits. 6. Grounding conductors are required. 7. Optional interlock shown. AC Output 3-Wire + GND BFB * Rectifier AC Input 3-Wire + GND DC Bus CB1 See Note 3 Battery Cabinet (optional) Battery System 2 MBD CB2 Optional 2-Wire + GND * External overcurrent protection by others Field-Supplied Wiring Table 3 Site planning data—Liebert eXL 625-1200kVA 1+N UPS Rating kVA Rectifier AC Input Current Bypass AC Input UPS AC Output Current Battery External External External External External External Breaker Breaker Breaker Breaker Breaker Breaker Max.Heat Input Trip Amp Trip Amp Trip Amp Trip Amp Trip Amp Trip Amp Max. External Dissipation Voltage (80% (100% (80% (100% (80% (100% Nom Current Breaker Full Load VAC Nom Max Rated) Rated) Nom Rated) Rated) Nom Rated) Rated) VDC at EOD Trip Amps BTU/H kW Dimensions WxDxH in. (mm) Approx. Weight Eff. Eff. Unpacked AC-AC DC-AC lb. (kg) 100% 100% 625 625 480 781 820 1200 900 752 1000 800 752 1000 800 480 1624 2000 81,989 6035 (2597) ≥96.5% ≥96.5% 625- 750* 625- 750* 480 937 983 1400 1000 902 1200 1000 902 1200 1000 480 1949 2000 98,386 6035 (2597) ≥96.4% ≥96.4% 625- 800* 625- 800* 480 997 1046 1400 1200 962 1200 1000 962 1200 1000 480 2079 2500 108,056 125.2x33.5x76.8 (3145x850x1950) 6035 (2597) ≥96.5% ≥96.5% 750 750 480 937 983 1400 1000 902 1200 1000 902 1200 1000 480 1949 2000 98,386 6035 (2597) ≥96.5% ≥96.5% 800 800 480 997 1046 1400 1200 962 1400 1000 962 1400 1000 480 2079 2500 108,056 6035 (2597) ≥96.4% ≥96.4% 1000 1000 480 1246 1311 2000 1600 1203 1600 1400 1203 1600 1400 480 2588 3000 131,181 8250 (3745) ≥96.5% ≥96.5% 1000- 1100* 1000- 1100* 480 1371 1441 2000 1600 1323 2000 1400 1323 2000 1400 480 2847 3000 144,300 8250 (3745) ≥96.4% ≥96.4% 1000- 1200* 1000- 1200* 480 1496 1572 2000 1600 1443 2000 1600 1443 2000 1600 480 3106 4000 162,084 480 1371 1441 2000 1600 1323 2000 1400 1323 2000 1400 480 2847 3000 144,300 480 1496 1572 2000 1600 1443 2000 1600 1443 2000 1600 480 3106 4000 162,084 8250 (3745) ≥96.5% ≥96.5% 480 1496 1572 2000 1600 1443 2000 1600 1443 2000 1600 480 3106 4000 162,084 8250 (3745) ≥96.5% ≥96.5% 1100 1100 1100- 1200* 1100- 1200* 1200 1200 See Notes 1,2,4,6,7,8 3,4,6,7,8 3,4,6,7,8 * Capacity on Demand Unit. Breakers, cables and other infrastructure must be sized for maximum planned capacity. 3 5,6,7,8 Specifications are subject to change. — 171.7x33.5x76.8 (4330x850x1950) 9,10,11 8250 (3745) ≥96.5% ≥96.5% 8250 (3745) ≥96.5% ≥96.5% 9 — — Figure 2 Table 4 One-line drawing—Liebert eXL 625-1200kVA 1+N system PARALLELING CABINET BY OTHERS HRG compatability UPS Modules HRG Current Rating, A 1 5 2 8 3 10 4 12 5 15 6 18 A * Paralleling Cabinet Bypass AC Input MIB UPS CABINET 1 See Note 7 BFB Motor Operated DC Bus A * Module AC Input FBO CB1 NOTES 1. UPS rectifier input and bypass input must be fed from a common, securely grounded wye source. Contact the factory if separate sources are required for the rectifier and bypass. 2. Refer to Table 4 for High Resistance Ground (HRG) compatibility. Contact the factory for further infomation. 3. UPS rectifier input, bypass input and AC output cables must be run in separate conduits. 4. All power cables from DC supply should be sized for a total maximum 2V drop at maximum discharge current. 5. Control wiring and power wiring must be run in separate conduits. 6. Grounding conductors are required. 7. Optional interlock shown. AC Output MBB FBO CB2 A UPS Output MOB See Note 3 2 Wire + GND To DC Supply UPS CABINET 2 See Note 7 BFB Motor Operated DC Bus A * Module FBO AC Input CB1 A 3Ø 3W +G * External Overcurrent Protection By Others FBO - Furnished By Others BFB - Back Feed Breaker MOB - Module Output Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker Field-Supplied Wiring CB2 A UPS Output MOB GND See Note 3 2 Wire + GND To DC Supply Notes: 1. All bypass inputs and rectifier inputs must be from the same source. 2. Grounding conductors are required. 3. All power cables from DC supply (batteries) should be sized for a total maximum 2V drop at maximum discharge current. 4. UPS rectifier, bypass input, and output cables must be run in separate conduits. 5. Control wiring and power wiring must be run in separate conduits. 6. Up to six modules can be paralleled in a system. 7. Cabling between the rectifier and bypass inputs is supplied by others. U46-CA-4201 Rev. 0 © 2014 Liebert Corporation Technical Support / Service United States All rights reserved throughout the world. Specifications subject to change without notice. 1050 Dearborn Drive 800-543-2378 ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. powertech@emersonnetworkpower.com P.O. Box 29186 SL-26020_REV5_02-15 Web site: www.liebert.com 4 Columbus, OH 43229