Pressure Losses Across Evaporators Chelsea Buxton Abstract: This case study analyzes the evaporator section of a refrigerant system. Fluid dynamics will be used to address the effects of friction on pressure drop through the tubes. The flows within the tubes transition from laminar to turbulent and move through the entrance length and fully developed region. The main question being addressed is how much this friction affects the overall pressure drop and if it needs to be taken into account when doing calculations to determine this pressure drop. Bernoulli’s equation will be used along with the head loss factor. The data collected was the pressure change over the tube length of the evaporator through the use of a differential pressure gage and the volume flow rate from a variable-area flow meter. These two pieces of data will be compared with the experimental data to find the error created from the use and negligence of friction/head loss. The most important results taken from this analysis are that neglecting friction in laminar flows does not result in a large error and the critical Reynolds number in a rectangular tube is slightly lower than the accepted critical Reynolds number for circular tubes. The overall conclusion that can be made from this case study is that friction is important but it can be neglected in the laminar flow region and result in small percent errors but in the turbulent region the friction should be taken into account because the error will get larger and larger at a linear rate. Introduction: An evaporator is a heat exchanger in which a refrigerant liquid enters at low pressure and temperature (relative to atmospheric) and leaves as a vapor. During the vaporization process, the refrigerant "boils,” absorbing energy from the refrigerated space surrounding the evaporator, and everything within. The fluid within the refrigerated space, typically air or water, is forced over the exterior sides of the lateral tubes of the heat exchanger containing a volatile refrigerant (e.g. R134a is used in automobile cooling systems). Heat energy from the air/water flow enters the lateral tubes of the heat exchanger by convection, and then is conducted through the tube walls and into the refrigerant (again by convection.) If the refrigerant is in a saturated state and sufficient latent heat enters the refrigerant, it changes phase (i.e., it “evaporates”). Figure 1 shows the overall geometry and flow directions of the fluids in the evaporator that is the subject of this analysis. The liquid enters through the “top diving header”, flows through the lateral tubes and collects in the “bottom combining header” in its vapor state. Figure 2 shows a cross sectional view of the lateral tubes in which the liquid undergoes vaporization. Each individual lateral tube has 11 channels, also pictured in figure 2 along with their dimensions. If liquid water was placed into the evaporator, no phase change would occur. This would result in a pressure drop between the inlet and outlet of each lateral tube that is dependent upon the Reynolds number of the fluid. This pressure drop is the same as the pressure drop from the inlet of a single tube channel to its exit. Data was collected by Habte [ref 2] as a preliminary analysis of two-phase pressure drop in the full evaporator. Flow transitions from laminar to turbulent when the Reynolds number exceeds a critical value which is quoted to be approximately 2300 in a circular tube. Recrit can vary with the cross-sectional shape of the channel, roughness, flow conditions, and other factors. Pressure drop is affected by this Reynolds number along with inlet and outlet geometries, entrance length, and tube roughness. Pressure drop due to frictional head loss in real tubes of non-circular cross section (in this case, an individual flow channel of the lateral tubes of the evaporator) vary with flow rate. This overall pressure drop is extremely important to the performance of the heat exchanger and has great impact upon the other components that are chosen for the system, such as the compressor. The first part of this case study will focus upon the experimental evaluation of head loss and compare it was standard engineering correlations by approximating the flow as fully developed throughout the lateral tube. The second part will recognize that there exists an entrance length causing for the fully developed flow to be limited to length of the tube after this entrance length. An analysis was carried out to estimate the error introduced by the fully developed approximation that were made in the first part. Setup, Data, and Methods of Analysis: The tests were performed on a single aluminum flat tube with 11 channels as shown in Fig. 2. The channel length was 24 inches, and because the tubes were new and smooth when the tests were performed, roughness effects were negligible. All data were collected at room temperature, about 20C. Test Setup As illustrated in Fig. 3, the two ends of the flat tube were connected to plenum chambers each of which was connected to a flexible hose. The cross section of the plenum is shown in Fig 4. The two plenum chambers were connected to different sides of a differential pressure gage that measures the pressure difference between the inlet and outlet of the flat tube, P1 - P2. A variable-area flow meter was used to measure the flow rate of water Q into the lateral tube. The data that was collected from the differential pressure gage and the variable-area flow meter are shown in table1. Table1. Data collected by Hatbe in his experiment for two-phase flow mal-distribution in a brazed aluminum evaporator. Q volume flow rate [gal/hr] 1.0 2.0 3.0 4.0 5.0 6.0 7.0 9.5 12.5 15.6 18.6 21.6 24.7 P1 - P2 Pressure drop [psi] 0.075 0.08 0.15 0.325 0.4 0.525 0.625 0.85 1.23 1.675 1.8 2.15 2.6 26.2 27.7 30.7 33.8 35.3 36.8 2.9 2.95 3.6 4.2 4.65 5.1 The first objective carried out in this section of the case study was to see how well predicted estimates for pressure drop vs. flow rate and Reynolds number using correlations for major loss (friction factor) and minor loss (pressure loss coefficient) from a circular pipe compare with experimentally measured pressure drops in the channels of rectangular cross section. These data and predictions were then used to determine the Reynolds number below which the flow in the channels in laminar and above which it is turbulent. Finally it was observed that real data of flows are more complex than the basic flow studies displayed in test books. It was assumed in this section that the entire length of the tube exhibits fully developed flow. The data displayed in table 1 was converted into standards units of m3/s for volume flow rate and Pa for pressure drop in order to keep the same units throughout the analysis. The evaporator has a rectangular cross section rather than a circular one so an “effective diameter” needed to be calculated for the analysis. The “effective diameter” that was used is the same as the hydraulic diameter, DH. The calculation of this diameter then permitted the calculation of the Reynolds number for each flow rate Q into the flat tube. Through the approximation of the flow throughout the channels to be fully developed and applying the friction factors for both laminar and turbulent flows, two predictions were made for pressure drop as a function of flow rate Q and Reynolds number Re. From this calculated data two curves were created; one for laminar flow and the other for turbulent flow permitting for the estimation of the critical Reynolds number. The overall pressure drop is a function of pressure losses created by both major and minor losses. After the overall pressure change, the minor pressure changes, the major turbulent flow pressure changes, and the major laminar pressure changes were calculated and plotted, the relative contribution of the theoretical minor loss contribution to the total pressure drop was plotted against the volume flow rate. This was then used to allow for another estimation of the critical Reynolds number. Due to the fact that ΔPminor << ΔP, we were able to neglect the minor loss contribution to the pressure change and just use the pressure change due to the major losses. We used these pressure changes to calculate the friction factor for the given data, turbulent flow, and laminar flow. These were then plotted against Reynolds number on the same graph (in both linear scale and log-log) to allow for one final update of the critical Reynolds number. By assuming in part 1 that the flow in the entire length of the tubes was fully developed, error was created in the measurement of the friction factor. In reality, a boundary layer grows from the inlet of the tube and grows until it has completely filled the tube. The length over which this occurs is called the entrance length and the remaining portion of the tube contains the fully developed flow as show in figure 5. The objective of the second part of this case study was to estimate the percent error associated with treating the flow as fully developed in the entire tube, including the entrance length. The first pressure change occurs across Le and the second occurs across LFD. These two pressure differences were added together to create the overall pressure change between the inlet and outlet of the tube. In this section of the study we modeled the flow in the rectangular channels with the flow through a circular tube with the effective diameter because there is no analytical solution for laminar flow in a rectangular duct. Flow is laminar where Re is less than Recrit and these are the flow rates upon which we focused for this section of the study. The ratio of the entrance length to the overall length was calculated for each flow rate where flow was laminar. Entrance length is a factor of both Reynolds number and effective diameter. Due to the fact that the flow at the inlet is nearly uniform, it can be assumed that the peak velocity at the entrance can be approximated with the average velocity at the entrance. This cannot be assumed at any other location because the peak velocity will exceed the average velocity. A relationship was worked out between the peak velocity and the average velocity in the fully developed region using the integration of the equation for the velocity profile over the radius of the tube. This was then used to prove that average velocity is the same at all axial locations in each channel. The Bernoulli equation is an approximate relation between pressure, velocity, and elevation and is only valid in regions of steady, incompressible flow where net frictional forces are negligible [ref 1]. This means that it cannot be used in regions where friction occurs, or fully developed regions. This allowed for the equation to be used to mathematically estimate the change in pressure over the entrance length as a function of the average velocity. Bernoulli’s equation was also used to estimate the pressure change over the fully developed region and the pressure change if the whole length was fully developed as functions of average velocity also, but in order to do this head loss had to be taken into account. The head loss adds the friction factor into the equation. The percent error between the pressure change of the tube including the entrance length and the fully developed length was then calculated to demonstrate why it cannot be assumed that flow in the tube is always fully developed. The result was plotted linearly vs. the Reynolds number. The percent error was not found to be the same for any two Reynolds numbers. To finalize the second part of the case study, the relative error was considered when flow was turbulent and compared to the relative error that was calculated when the flow was laminar. These two flows will result in different amounts of error. Analysis and Results: -Part1- (a). The tubes that are in the evaporator that was used for the experiment were rectangular, not circular, so an “effective diameter”(1) was needed for the calculations. This diameter is the same as the hydraulic diameter: 2ππ π·π» = (1) π+π This is calculated where a and b are the cross sectional dimensions of each flow channel. This gave a result of a hydraulic diameter of 0.001286 mm. This diameter, along with the volume flow rate was used to calculate the Reynolds (2) number for each individual volume flow rate in the flat tube as shown in table 2. The relationship between flow rate and average velocity was provided to simplify the equations throughout the analysis (3). The volume flow rates that were provided were changed to the correct units (m3/s) and divided by 11 due to the fact that there are 11 channels but for this experiment the focus was only upon 1. π π = Μ π·π» ππ (2) π π πΜ = π΄ (3) Table 2. The volume flow rate in the standard units per individual tube along with the number for each volume flow rate. Q (m^3/s) Per Vent 9.620E-08 1.923E-07 2.884E-07 3.846E-07 4.807E-07 5.768E-07 6.729E-07 9.055E-07 1.195E-06 1.485E-06 1.774E-06 2.064E-06 2.353E-06 2.498E-06 2.643E-06 2.932E-06 3.222E-06 3.366E-06 3.511E-06 calculated Reynolds Reynolds Number 68.28490432 136.5158066 204.7467089 272.9776112 341.2085135 409.4394158 477.6703181 642.7391651 848.2449513 1053.750737 1259.256524 1464.76231 1670.268096 1773.020989 1875.773882 2081.279668 2286.785455 2389.538348 2492.291241 (b). Pressure drop can be calculated as a function of the friction factor, density, and average velocity. Major frictional losses are calculated using different equations for turbulent (5,6) and laminar (4) flow and were found in the text [ref 1]. The equation for the frictional factors due to turbulent flow needed to be restructured to be equivalent to the frictional factor, f: LAMINAR: π 64 π (π π , π·) = π π (4) TURBULENT: 1 √π = −1.8 log [ 6.9 π π +( π π· 3.7 1.11 ) ] (5) 2 π=( −1 1.8 log( 6.9 ) π π ) (6) These frictional factors are the main driving force in the major pressure change that occurs between the inlet and outlet of the tube. Equations (7,8) were obtained to directly calculate both the pressure changes due to major and minor losses. It was taken into account that the roughness of the walls of the tube was negligible: 1 πΏ π βππππ = 2 ππΜ 2 π· π (π π , π·) π» 1 βππππ = 2 ππΜ 2 ∑ πΎ (7) (8) From the text book [ref 1] it was determined that the loss coefficient, K, for the inlet of a straight sharpedged tube is 0.5 and α for the outlet. It can be determined that the correction factor, α, is equal to 1. These loss coefficients are the same for both laminar and turbulent flow which means that the same equation was used for the pressure changes due to minor losses for both laminar and turbulent flow. When the frictional losses were added into the equation for pressure changes (7,8) equations for the major (9,10) pressure changes as functions of flow rate Q, and Reynolds number were found. The loss coefficients were used to create an equation (11) for the minor losses that was independent of the Reynolds number. These calculations values are displayed in table 3. LAMINAR: 1 πΏ 64 βππππ = 2 ππΜ 2 (π· ) π π π» (9) TURBULENT: 2 βππππ 1 πΏ = 2 ππΜ 2 (π· ) ( π» −1 1.8 log( 6.9 ) π π ) (10) LAMINAR + TURBULENT: 1 βππππ = 2 ππΜ 2 (1.5) (11) The pressure changes due to the minor losses were added to the pressure changes due to the major losses to calculate the overall pressure changes vs. flow rate Q and Reynolds number Re. These calculated values are displayed in table 3. Table 3. Calculated values for the change in pressure due to minor and major losses along with total pressure change for both laminar and turbulent flows as functions of Q and Re. [ΔPmajor]lam (Pa) 636.3150092 1272.126799 1907.938589 2543.750379 3179.562168 3815.373958 4451.185748 5989.384943 7904.397017 9819.409091 11734.42116 13649.43324 15564.44531 16521.95135 17479.45739 19394.46946 21309.48153 22266.98757 23224.49361 [ΔPmajor]turb (Pa) 211.4514349 498.373148 869.0078354 1312.549073 1822.836968 2395.617527 3027.691146 4787.608966 7404.721309 10462.5421 13936.31422 17807.15784 22059.98772 24325.67389 26682.3482 31663.70051 36994.95774 39789.27751 42668.16593 ΔPminor (Pa) 2.138322319 8.546526382 19.22461353 34.17258375 53.39043706 76.87817345 104.6357929 189.4494231 329.963822 509.2130694 727.1971655 983.9161102 1279.369903 1441.622368 1613.558545 1986.482036 2398.140375 2618.495113 2848.533562 ΔPlam (Pa) 638.4533 1280.673 1927.163 2577.923 3232.953 3892.252 4555.822 6178.834 8234.361 10328.62 12461.62 14633.35 16843.82 17963.57 19093.02 21380.95 23707.62 24885.48 26073.03 ΔPturb (Pa) 213.5898 506.9197 888.2324 1346.722 1876.227 2472.496 3132.327 4977.058 7734.685 10971.76 14663.51 18791.07 23339.36 25767.3 28295.91 33650.18 39393.1 42407.77 45516.7 (c). These calculations in table 3 were plotted vs. Q and Re to then determine what the critical Reynolds number is. The turbulent and laminar flows were plotted on separate figures along with the data provided from the experiment. By evaluating these plots the critical Reynolds number can be determined from the point on each graph at which the data seems to follow the curve for each type of flow. Figures 6 and 7 pertain to laminar flow, while 8 and 9 pertain to turbulent flow. Pressure [Pa] Pressure Change vs Q Laminar 40000 35000 30000 25000 20000 15000 10000 5000 0 0.000E+001.000E-062.000E-063.000E-064.000E-06 Laminar data Flow Rate (m3/s) Figure 6. Graph of pressure change for laminar flow versus the provided volume flow rates. Pressure [Pa] Pressure Change vs Re Laminar 40000 35000 30000 25000 20000 15000 10000 5000 0 Laminar data 0 500 1000 1500 2000 2500 3000 Reynold's Number Figure 7. Graph of pressure change for laminar flow versus Reynolds number calculated from effective diameter and the provided volume flow rates. Pressure Change vs Q Turbulent 50000 Pressure [Pa] 40000 30000 Turbulent 20000 data 10000 0 0.000E+001.000E-06 2.000E-06 3.000E-06 4.000E-06 Flow Rate (m3/s) Figure 8. Graph of pressure change for turbulent flow versus the provided volume flow rates. Pressure Change vs Re Turbulent 50000 Pressure [Pa] 40000 30000 Turbulent 20000 data 10000 0 0 1000 2000 3000 Reynold's Number Figure 9. Graph of pressure change for turbulent flow versus Reynolds number calculated from effective diameter and the provided volume flow rates. Through analysis of figures 6-9 it can be estimated that Recrit is about 2100. Recrit is the Reynolds number at which the flow transitions from laminar to turbulent. Figure 7 shows that the data points begin to stray from the laminar curve at a Reynolds number of about 2100. Figure 9 can be used to show that at about 2100 the data points begin to follow the same slope as the turbulent curve. Recrit is fairly obvious when using figure 7 because up until Re of 2100 the data points almost perfectly follow the laminar curve, but in figure 9, it is not as obvious because the data points do not lay on the curve they just follow the slope of it. This value of 2100 is fairly close to the quoted value of 2300 this difference is most likely due to the fact that 2300 is the accepted value for circular tubes. This would lead to the assumption that corners lead to the flow becoming turbulent at a lower Reynolds number and volume flow rate. Logically this would make sense because corners create a surface that is much less uniform than a circular tube. This would account for the difference in the critical Reynolds number. (d). The relative contribution of the theoretical minor loss contribution to the total pressure drop can be defined as ΔPminor/ΔP and when plotted vs. the volume flow rate from the theoretical estimates for both laminar and turbulent correlations can be used to estimate the critical Reynolds number. This was the next part of the analysis and is displayed in figure 10. Minor Pressure change/Total Pressure Change ΔPminor/ΔP vs Q 0.12 0.1 0.08 data 0.06 Laminar 0.04 Turbulent 0.02 0 0.000E+005.000E-071.000E-061.500E-062.000E-062.500E-063.000E-063.500E-064.000E-06 Flow Rate (m3/s) Figure 10. The relative contribution of the theoretical minor loss contribution to the total pressure drop can be defined vs. the volume flow rate for the data, laminar flow, and turbulent flow. From figure 10 Recrit can be estimated to occur at a volume flow rate of approximately 3E-6 m3/s. This is the point where the data curve seems to change from follow the laminar curve to the turbulent curve. From looking at table 2 it can be determined that Recrit occurs at about 2100. This is the same estimation that was obtained from the plots used in (c). The laminar curve is linear in all of the plots for (c) and (d). The turbulent curves for sections (c) and (d) are both parabolic. The data curve changes from linear to parabolic showing its transition from laminar to turbulent. (e). ΔP was obtained from the experiment and ΔPminor was obtained through an equation (11) and is much smaller than ΔP. This means that the data can be used to estimate the true friction factors as a function of Reynolds number for this rectangular channel flow. The major losses were used to calculate a measured friction factor for each flow rate using equations obtained from the text [ref 1]. The pressure change for the major losses for the data can be calculated from the difference between the pressure change obtained from the experiment and the calculated change in pressure due to minor losses (12). This is then used to find the frictional factor for the data: βππππ(πππ‘π) = βππππ‘π − βππππππ ππππ‘π = ( (12) π·π» βππππ(πππ‘π) ) 1 Μ 2 πΏ ππ (13) 2 The frictional factors for the laminar flow (4), turbulent flow (6), and data (13) were calculated and then plotted in two forms, linear and log-log versus the Reynolds number to be compared with the accepted curve for fully developed circular pipe flow (moody curves). The curves drawn are figures 11 and 12. Friction Factor f vs Re Linear Scale 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 data Laminar Turbulent 0 500 1000 1500 2000 2500 3000 Reynold's Number Figure 11. Linear plot of the friction factors vs. Reynolds number for laminar flow, turbulent flow, and the data. f vs Re log-log scale 1 Friction Factor 1 10 100 1000 10000 data 0.1 Laminar Turbulent 0.01 Reynold's Number Figure 12. Log-log plot of the friction factors vs. Reynolds number for laminar flow, turbulent flow, and the data. From evaluating figures 11 and 12 it seems to be a little bit more difficult to estimate Recrit. Most people have a difficult time reading log-log plots, and the linear plot in figure 11 has lines that are extremely close together and difficult to read. From these two figures Recrit can be estimated to remain around 2100. The fact that each plot has shown the critical Reynolds number to be 2100 leads to the assumption that this is most likely a value that is fairly close to the true value. Part II (a). Due to the fact that the flow through the entire tube cannot be considered fully developed, there is a section of the tube that is called the entrance length. The entrance length was determined through an equation provided by the text [ref 1] (14): πΏπ = 0.05π ππ·π» (14) This entrance length is the region of the tube in which the boundary layer grows and then when the boundary layer meets the fully developed flow begins. Le/L was tabulated for each flow rate where the flow is laminar (Re<2100) and can be seen in table4. Table 4. Le/L for each volume flow rate that occurs where the flow is laminar. Le/L 0.007169 0.014332 0.021496 0.028659 0.035822 0.042986 0.050149 0.067479 0.089055 0.11063 0.132205 0.153781 0.175356 0.186144 0.196932 0.218507 (b). The flow at the inlet is nearly uniform leading to the assumption that the peak velocity at the entrance is equal to the average velocity at the inlet. Using an equation for the velocity profile (15) from the text [ref 1], a relationship (19) between the peak velocity and the average velocity in the fully developed flow can be derived. Equations (16), (17) ,and (18) show steps of the derivation in order to demonstrate the validity of the final relationship (19): 2 π ππππ₯ (1 − π 2 ) = πΜ π π2 ∫0 ππππ₯ (1 − π 2 ) ππ΄ = π ππ΄ = 2ππππ π π2 ∫0 ππππ₯ (1 − π 2 ) 2ππππ = π ππ = 2πΜ π (15) (16) (17) (18) (19) Due to the fact that the velocity profile is the same at all points in the fully developed region and there is a direction relationship between the peak velocity and the average velocity it can be assumed that the average velocity is the same at all axial locations in the channels. The average velocities for all volume flow rates in laminar flow can be seen in table 5. Table 5. The average velocities for volume flow rates in laminar flow region. Vavg 0.026722 0.053423 0.080123 0.106824 0.133525 0.160226 0.186926 0.251523 0.331943 0.412364 0.492784 0.573205 0.653625 0.693835 0.734045 0.814466 (c). By definition, the Bernoulli equation can only be used when frictional forces are negligible. The frictional forces in the tube do not occur until it has developed into a fully developed flow so head loss can be ignored because in the entrance length the flow is not fully developed. This entrance length occurs between point 1 and point e. The Bernoulli equation (21) for this region can be used to estimate ΔP1(20) as a function of average velocity (22): βπ1 = π1 − ππ π1 π 1 + 2 πΜ 2 + ππ§1 = ππ π (20) 1 + 2 ππ2 + ππ§π 1 βπ1 = 2 π(ππ2 − πΜ 2 ) (21) (22) The z terms in the equation (21) drop out due to the fact that they are both the same leaving just the velocity and pressure terms to be used to calculate the final equation for the change in pressure. (d). ΔP2 (23) and [ΔP]FD (24) can be calculated in much the same manner, but due to the fact that they occur in the fully developed region this means that friction much be taken into account in the form of head loss (26). Taking Bernoulli’s equation and calculating it over the fully developed region can be used to find ΔP2 (25): ππ π βπ2 = ππ − π2 (23) βππΉπ· = βπ1 + βπ2 (24) 1 + 2 ππ2 + ππ§π = βπ = π π2 π Μ 2 πΏπΉπ· π π·π» 2 1 + 2 ππ2 + ππ§2 + ππβπ (25) (26) The head loss equation (26) can be taken directly from its definition and can be found in the text [ref 1]. The addition of this head loss factor to Bernoulli’s equation takes friction into account and with the addition of the friction factor equation for laminar flow (4) can be used to find the pressure changes (27) (28) when placed into (25) and (26). The length used to find the second pressure change is the length of the fully developed region because this is the region across which the pressure change is being calculated. When it is assumed that the entire region is fully developed ([ΔP]FD ) for the whole length is used. All of the pressure changes are displayed in table6. Μ 2 64 πΏπΉπ· π βπ2 = π π π (27) π·π» 2 Μ 2 64 πΏ π βππΉπ· = π π π π· π» (28) 2 Table 6. The pressure changes across the entrance length, the fully developed length, and the entire length when it is assumed that the whole tube is fully developed. delP1 1.069161 4.273263 9.612307 17.08629 26.69522 38.43909 52.3179 94.72471 164.9819 254.6065 363.5986 491.9581 639.685 720.8112 806.7793 993.241 delP2 157.9383 313.4736 466.7315 617.7122 766.4156 912.8418 1056.991 1396.307 1800.119 2183.272 2545.767 2887.603 3208.781 3361.623 3509.3 3789.16 delPfd 159.0788 318.0317 476.9846 635.9376 794.8905 953.8435 1112.796 1497.346 1976.099 2454.852 2933.605 3412.358 3891.111 4130.488 4369.864 4848.617 (e). An equation was provided to calculate percent error (29) in the write up for this analysis: % πππππ = π = βππΉπ· βπ −1 (29) The ΔP can be calculated through the addition of ΔP1 and ΔP2 (30): Μ 2 1 64 πΏ π βπ = 2 π(ππ2 − πΜ 2 ) + π π π π·πΉπ· 2 π» (30) This can then be simplified to (31): % πππππ = Μ 0.1π 32ππΏ Μ −0.1π π·2 π» (100) (31) The percent error calculated for each pressure difference in the laminar flow region was calculated and can be seen in table 7. They were then graphed vs Reynolds number in figure 13. Table 7. The overall pressure difference and percent error calculated for each of these pressure difference in the laminar flow region. delP 159.0075 317.7468 476.3438 634.7985 793.1109 951.2809 1109.309 1491.031 1965.1 2437.879 2909.365 3379.561 3848.466 4082.434 4316.079 4782.401 % error 0.044826 0.089658 0.134529 0.179441 0.224392 0.269385 0.314417 0.423531 0.559706 0.696252 0.833168 0.970457 1.108121 1.177094 1.246161 1.384578 Percent Error vs Re 1.6 Percent Error 1.4 1.2 1 0.8 0.6 Percent Error vs Re 0.4 0.2 0 0 500 1000 1500 2000 2500 Reynold's Number Figure 13. Plot of the Percent Error vs the Reynolds number for each pressure change in the laminar flow region. The percent errors are so small that it does not seem to warrant redoing analysis in part 1 to take entrance length into account. The percents start out extremely small but then get larger as the Reynolds number reaches the critical Reynolds number. The largest percent error calculated is 1.38% which is very small. The percents also grow at a linear rate with Reynolds number. (f). Due to the fact that the error grows linearly with Reynolds number and turbulent flows occur at higher Reynolds numbers, it is to be assumed that the relative error will be larger when the flow is turbulent. Physically, this would be logical due to the fact that turbulent flow is characterized by velocity fluctuations and highly disordered motion [ref 1] creating greater friction between the fluid particles and increasing the head loss. This means that the pressure change calculated from the Bernoulli equation would lead to a higher error because of this larger head loss. Discussion and Summary: The analysis of the data and calculations of this case study created a deeper understanding of head loss due to laminar and turbulent flow through pipes. A multitude of new knowledge was produced: ο· The critical Reynolds number for flow through a rectangular tube is similar to, but a little lower than the critical Reynolds number that is accepted for flow through a circular tube. ο· The critical Reynolds number can be easily computed through the interpretation of graphs for laminar and turbulent flows. ο· The effective diameter used in a rectangular tube is the same as the hydraulic diameter. ο· The minor losses for laminar and turbulent flow are the same. ο· The error that is calculated for pressure change when friction is taken into account and when it is not is greater with regard to turbulent flow than laminar flow. All of these new pieces of knowledge can be used to greater develop ones understanding of fluid dynamics. Relating the equations and assumptions to real life scenarios make them much more concrete and easier to understand. Due to the fact that higher pressure drops lead to more expenses in the overall development of evaporators methods to reduce the pressure drop while maximizing the aspect ratio need to be implemented. Some possible methods of doing this are: ο· Through increasing the overall size of the tubes, this would increase the effective diameter and decrease the pressure drop. To increase the aspect ratio, the width needs to be increased more than the length. ο· The width of the tubes can be increased while the length remains the same to increase the aspect ratio and slightly decrease the pressure drop. The pressure drop can be decreased through the use of shorter tubes. Overall, this case study led to the deepening of knowledge on the subject matter. Fluid dynamics is evident all over the world and further understanding of this can be implemented into different mechanisms, such as evaporators, to create products that work much more efficiently. References: 1. Cengel, Y & Cimbala, J.M. 2006 Fluid Mechanics, McGraw-Hill, New York, NY 2. Habte, M. 2003 Two-Phase Flow Mal-distribution in a Brazed Aluminum Evaporator. M.S. Thesis, The Pennsylvania State University, Department of Mechanical Engineering.