SOCIALIST REPUBLIC OF VIETNAM Independence - Freedom - Happiness QCVN 09:2013/BXD NATIONAL TECHNICAL REGULATION ON ENERGY EFFICIENCY BUILDINGS Hanoi - 2013 Unofficial translation - QCVN 09: 2013/BXD CONTENTS INTRODUCTION ....................................................................................................................................... 3 I. GENERAL REQUIREMENTS .................................................................................................................... 4 1.1. Scope ................................................................................................................................................ 4 1.2. Coverage ........................................................................................................................................... 4 1.3. Normative references....................................................................................................................... 4 1.4. Terms, definitions and symbols........................................................................................................ 4 II. TECHNICAL REQUIREMENTS ................................................................................................................ 6 2.1.Building envelope .............................................................................................................................. 6 2.2.Ventilation and air conditioning ........................................................................................................ 9 2.3. Lighting ........................................................................................................................................... 15 2.4. Escalators and elevators ................................................................................................................. 18 2.5. Electric power consumption........................................................................................................... 18 2.6.Service water heating system ......................................................................................................... 20 III.MANAGEMENT REGULATIONS .......................................................................................................... 23 IV.IMPLEMENTATION ARRANGMENT ................................................................................................... 23 ANNEXES................................................................................................................................................ 24 2 QCVN 09:2013/BXD INTRODUCTION QCVN 09:2013/BXD - “Energy Efficiency Building Code” was developed by the Vietnam Association of Civil Engineering Environment, put forward by the Department of Science, Technology and Environment Department, and enacted by the Ministry of Construction under Circular 15 /2013/TTBXD, dated on September 26, 2013. The National Energy Efficiency Building Code QCVN 09:2013/BXD shall supersede the Vietnam Energy Efficiency Building Code QCXDVN 09:2005 ratified under the Minister of Construction’s Decision 40/2005/QĐ-BXD of November 17, 2005. The National Energy Efficiency Building Code QCVN 09:2013/BXD was developed with research inputs and contributions of international consultants from various external donors, including the International Finance Corporation (IFC), the United States Agency for International Development (USAID) and the Danish Energy Agency (the Kingdom of Denmark). 3 Unofficial translation - QCVN 09: 2013/BXD National Technical Regulation on Energy Efficiency Buildings (NATIONAL TECHNICAL ENERGY EFFICIENCY BUILDING CODE) I. GENERAL REQUIREMENTS 1.1. Scope 1.1.1 This National Technical Building Energy Efficiency Building Code provides mandatory technical standards to achieve energy efficiency in the design, new construction or retrofit of civil buildings (office buildings, hotels, hospitals, schools, commercial buildings,, services buildings, apartments buildings, among others), with a gross floor area of 2,500 m2 or larger. 1.1.2 The requirements of this Code apply to: 1) The building envelope, except envelopes of non-air conditioned storage space or warehouses; 2) Equipment and systems in the building, including: a) Interior lighting b) Ventilation and air conditioning c) Water heating d) Energy management equipment, and e) Elevators and escalators. 1.2. Coverage This Code provides statutory technical requirements applicable to all entities and individuals involved in activities pertaining to energy efficient buildings. 1.3. Normative references 1) ARI 340/360 – Performance rating of commercial and industrial unitary air-conditioning and heat pump equipment. 2) ARI 365 – Performance rating of commercial and industrial unitary air-conditioning condensing units. 3) ARI 550/590-2003 – Performance rating of water-chilling packages using the vapor compression cycle. 4) ASHRAE 90.1-2001 – Standard 90.1-2001 (I-P Edition) -- Energy Standard for Buildings except Low-Rise Residential Buildings (IESNA cosponsored; ANSI approved; Continuous Maintenance Standard). 5) SHRAE 90.1-2004 – Energy Standard for Buildings except Low-Rise Residential Buildings. 6) DIN 4702-1 – Boilers for central heating; terms, requirements, testing, marking. 7) ISO 6946:2007 – Building components and building element - Thermal resistance and thermal transmittance - Calculation method. 8) TCVN 298:2003 – Building components and parts – Thermal resistance and thermal conductivity – Calculating methods. 9) TCVN 6307:1997 – Cooling systems – Testing methods. 10) TCVN 7830-1:2012 – Air conditioning equipment – Part 1: Energy efficiency. 1.4. Terms, definitions and symbols 1.4.1Terms and definitions 4 QCVN 09:2013/BXD 1) Cooling air saving system: including ducts and automatic controlling system that allow fans to drive cool air from outside into the building in appropriate weather conditions to reduce energy consumption for air cooling or when mechanical air conditioning is not needed. 2) Building energy cost: total annual cost of energy consumption for the building. 3) Coefficient of performance (COP) – cooling: the ratio of the rate of heat removal to the rate of energy input, in consistent units, to be verified based on existing national standards or designated operating conditions. COP is used to rate the efficiency of electricity-powered condenser air conditioner, including the compressor, evaporator coil and condenser coil. COP can also be used to rate the efficiency of water-cooled chiller (not including chiller pumps, condensed cooling water and cooling tower fans). 4) Coefficient of performance (COP) - heat pump: the ratio of the rate of heat output to the rate of energy input, in consistent units, for a complete heat pump system under designated operating conditions. 5) Overall thermal transfer value (OTTV): the total heat gain through the entire surface area of the building envelope, including opaque walls and glazing by every square meter of the building exterior surface area, W/m2. 6) Floor area of a particular space: the horizontal surface area of a specific space, measured from the interior side of the circumference walls or partitions, at the elevation of the working plane (0.8 m). 7) Radiation reduction coefficient of shading structures: the ratio of solar heat gain through windows, in case a window external shading system is installed, to that of windows without shading systems. 8) Overall heat transfer coefficient (Uo): the intensity of a time-constant heat flux going through a surface area unit of the enclosing structure when the temperature difference of the air on both sides of the structure is 1 K, measured in W/m2.K. 9) Total thermal resistance (Ro): the inverse of overall heat transfer coefficient Uo:Ro = 1/Uo, measured in m2.K/W. 10) Lamp efficiency: the ratio of rated light output to power consumption, measured in lumen/W. 11) Efficiency of the ventilation-air conditioning systems: the ratio of output energy (useful energy at the time of use) to input energy, in consistent unit, for a specific length of time, measured in %. 12) Enthalpy recovery: the ability to recover cooling energy of air conditioning equipment, boilers etc., resulting in energy efficiency. 13) Annual energy consumption efficiency: the annual ratio of energy output to energy input of a building or piece of equipment. 14) Indirectly air-conditioned space: an enclosed space in a building that is indirectly cooled (rather than directly cooled) and allows heat transfer therefrom to adjacent air-cooled spaces. 15) Lighting power density (LPD): the ratio of electric lighting output to the illuminated area, measured in W/m2. 16) Daylight relay: a device that automatically turns on or off input energy for electric lighting, located near windows to maintain appropriate working illuminance level when direct or indirect daylight fails to provide the desired illuminance. 17) Temperature control relay: an automatic temperature-sensitive device. 18) Building envelope: building envelope or building enclosure consists of opaque or transparent walls, windows, doors, skylights, among others, that form enclosed spaces within a building. 1.4.2 Symbols, measurement units and acronyms 1) SHGC (Solar Heat Gain Coefficient): heat gain coefficient of glazing, published by manufacturers or determined in accordance with prevailing standards, dimensionless. In case manufacturers avails of the shading coefficient SC, SHGC = SC 0.87. 2) SC: Shading coefficient; 3) T: Absolute temperature, K; 4) RO: Total thermal resistance (inverse of heat transfer ratio Uo) of enclosing assembly – m2 K/W; 5 Unofficial translation - QCVN 09: 2013/BXD 5) Uo: Heat transfer coefficient (including heat transfer through ambient air layers on both sides of the structure), W/m2 K; 6) Uo,M: Overall heat transfer coefficient of the roof assembly, W/m2 K; 7) Uo,T: Overall heat transfer coefficient of walls, W/m2 K; 8) AHU: Air handling unit; 9) ARI: Air-conditioning and Refrigeration Institute; 10) ASHRAE: American Society of Heating, Refrigerating and Air-Conditioning Engineers; 11) BEF: Ballast efficacy factor for fluorescent lamps, %/W; 12) BF: Ballast factor, %; 13) COPcooling: Air conditioner coefficient of performance – ratio of air cooling output to electricity input, kW/kW; 14) COPheating: Heat pump coefficient of performance – ratio of heat gain to electricity input, kW/kW; 15) EER: Energy efficiency ratio of air conditioners – ratio of cooling output and electricity input, kW/kW; 16) FCU: Fan coil unit – thermal exchange system consisting of multiple plain or fanned tubal rows; thermal carriers being cooled or heated water running inside the tubes to provide cooling/heating effects for a space; the FCU is the end-of-the-line component of a water-cooled central air-conditioning system with chillers; 17) IEER: Integrated energy efficiency ratio, kW/kW; 18) IPLV: Integrated part load value, or in full term, integrated energy efficiency part load value; kW/kW; 19) OTTVT: Overall thermal transfer value for walls – the mean intensity of the heat flux transferred through 1 m2 of exterior walls, W/m2; 20) OTTVM: Overall thermal transfer value for roofs – the mean intensity of the heat flux transferred through 1 m2 of roofing, W/m2; 21) PIC: Power input per capacity – the ratio of energy input, in kW, to cooling output, in RT (ton of refrigeration), kW/RT; 22) VLT (Visible Light Transmission): the ratio of light passing through glazing materials, measured in the amount of light energy that passes through glazing as a percentage of the light energy that directs on the glazing surface, %; 23) VRV/VRF: Air conditioning systems with variable refrigerant volume/flow; 24) VSD: Variable speed driver; 25) WWR: Window-to-wall ratio, dimensionless; II. TECHNICAL REQUIREMENTS 2.1.Building envelope 2.1.1 General requirements The building envelope shall be designed and constructed in ways shall guarantee: 1) Natural ventilation whenever exterior climate conditions allow; 2) Sufficient insulation and minimum exposure to cold wind; 3) Sufficient day lighting under normal conditions, while reducing solar heat gain into the building; 4) Choice of appropriate materials to improve energy efficiency for the building. 2.1.2 Requirements for building exterior walls and roofs 1) All ground exterior walls (opaque parts of the walls) shall maintain a maximum overall heat transfer value Uo.max no greater than, or a minimum overall heat transfer value Ro.min no smaller than the values specified in Table 2.1. 6 QCVN 09:2013/BXD Table 2.1. Thermal performance requirements for exterior walls Areas Wall orientation Uo.max, W/m2.K Ro.min, m2.K/W All areas All orientations 1.80 0.56 2) Requirements for flat roofs and roofs with gradient of less than 15 degrees: All roofs, including those with insulation, metal roofs and others shall possess an overall heat transfer value Uo no greater than, or total thermal resistance Ro no smaller than the values specified in Table 2.2. Table 2.2. Thermal performance requirements for flat roofs Uo.max, W/m2.K 1.00 Area All areas Ro.min, m2.K/W 1.00 Notes: 1) Shaded roofs: If more than 90% of the roof is covered with a fixed sunshade with ventilation, there is no need for insulation for such roof. The sunshade must be installed at a minimum clearance of 0.3 m from the roof surface to be recognized as having ventilation between the roof and sunshade (double-layer roof with an air cushion in between). 2) Flat roofs with reflective materials: Thermal resistance values Ro,min provided in Table 2.2 may be multiplied by a coefficient of 0.80 for roofs designed with reflective materials, within a range of 0.70 0.75, to increase heat inflection for the exterior roof surface. 3) Roofs with gradient of 15 degrees or above: The minimum total thermal resistance or maximum overall thermal transfer value for roofs may be identified by multiplying Ro.min and Uo.maxvalues in Table 2.2 with a coefficient of 0.85 and 1.18, respectively. 3) Sizes of windows and skylight a) The gross area of vertical openable and fixed windows shall guarantee good ventilation and day lighting. b) The overall thermal transfer value of walls and roofs shall guarantee: - OTTVT for walls no greater than 60 W/m2; - OTTVM for roofs no greater than 25 W/m2. c) OTTV values are determined using prevailing standards and technical guidelines. 4) Glazed windows shall be designed with applicable SHGC coefficients in lieu of the OTTVT referred to in 2.1.2 – 3) – b) above. SHGC of glazing shall be smaller or equal to the maximum allowed value, and glazing VLT shall not be lower than the VLTmin in Table 2.3. Table 2.3. WWR-related SHGC for glazing SHGCmax on 8 main orientations WWR, % 20 N E or W 0.90 0.80 NE, NW or SE, SW 0.86 S VLTmin 0.90 0.70 7 Unofficial translation - QCVN 09: 2013/BXD 30 0.64 0.58 0.63 0.70 0.70 40 0.50 0.46 0.49 0.56 0.60 50 0.40 0.38 0.40 0.45 0.55 60 0.33 0.32 0.34 0.39 0.50 70 0.27 0.27 0.29 0.33 0.45 80 0.23 0.23 0.25 0.28 0.40 90 0.20 0.20 0.21 0.25 0.35 100 0.17 0.18 0.19 0.22 0.30 Notes: 1) If WWR does not match the values in column 1, Table 2.3, SHGC shall be determined through linear interpolation using the nearest higher and lower WWR values. 2) Glazing materials with SHGC values higher than the reference SHGC providing that sunshades with appropriate A coefficients are used to insure that the selected SHGC is smaller or equal to the reference SHGC multiplied by the A coefficient – see 2.1.2 – 5). 5) In case of building facades being installed with sunshades, SHGC values in Table 2.3 may be adjusted by multiplying them with the A coefficients in Tables 2.4 and 2.5. Table 2.4. A coefficient for consistent horizontal sunshades placed on or above the upper window edge by a clearance d, with d/H < 0.1 R=b/H N 1.23 1.43 1.56 1.64 1.69 1.75 1.79 1.82 1.85 1.85 On walls, facing 8 main orientations NE or NW E or W SE or SW 1.11 1.09 1.14 1.23 1.19 1.28 1.35 1.30 1.45 1.47 1.41 1.59 1.59 1.54 1.75 1.69 1.64 1.89 1.82 1.75 2.00 1.89 1.85 2.13 2.00 1.96 2.22 2.08 2.08 2.27 S 1.20 1.39 1.39 1.39 1.39 1.39 1.39 1.39 1.39 1.39 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 Notes: 1) Dimensions: b – reach of sunshade; H – window height; d – clearance from upper window edge to lower sunshade contact; b, d and H share the same dimension for length. 2) Applicable for sunshades placed above the upper window edge by a clearance d, with d/H ≤ 0.1 – tolerance of less than 10%. Table 2.5. A coefficient for consistent vertical sunshades placed on or next to a window side by a clearance e, with e/B < 0.1 R=b/B 0.10 0.20 0.30 8 N 1.25 1.52 1.75 On walls, facing 8 main orientations NE or NW E or W SE or SW 1.06 1.01 1.09 1.12 1.03 1.19 1.19 1.05 1.32 S 1.11 1.19 1.22 QCVN 09:2013/BXD 0.40 1.82 1.28 1.06 1.45 1.25 0.50 1.85 1.37 1.09 1.64 1.28 0.60 1.85 1.47 1.10 1.82 1.30 0.70 1.89 1.59 1.12 1.96 1.30 0.80 1.89 1.69 1.14 2.13 1.30 0.90 1.89 1.82 1.16 2.22 1.30 1.00 1.89 1.96 1.18 2.33 1.30 Notes: 1) Dimensions: b – reach of vertical sunshade; B – window width; e – clearance from window side to vertical sunshade inner contact; b, e and B share the same dimension for length. 2) Applicable also for vertical sunshades placed by a clearance e from the window side, with e/B ≤ 0.1, tolerance of less than 10%. 2.2.Ventilation and air conditioning 2.2.1 General requirements 1) Natural ventilation and mechanical ventilation For every specific space, natural (passive) ventilation systems or coerced (active – mechanical) ventilation systems may be used. Natural ventilation systems used shall meet the requirements of 2.2.1 – 2). 2) Natural ventilating system Spaces are considered naturally ventilated if the following requirements are met: a) Vent holes and windows may be opened outward with sizes no less than 5% of the floor area. Users may easily get access to these ventilation openings. b) There are vent holes that may be opened on the roofs or walls that face the external oncoming wind sources. The ventilation openings have ventilating sizes of no less than 5% of the floor area. Users may easily get access to these vent holes which connect to the external air through openings with similar or larger sizes. c) The accumulated size of the vent openings is no smaller than the gross area of the wind catchers. 3) Mechanical ventilating system Spaces without natural ventilation shall be installed with mechanical ventilating systems to provide external air to every frequently occupied area through anair distribution piping system. 2.2.2 Requirements for ventilation-air conditioning systems and equipment 1) General requirements a) Equipment performance: air conditioning and water cooling equipment and systems shall ensure the minimum coefficients of performance (COP) in standard rating conditions, and not lower than the values provided in the following tables. - Table 2.6: for electric air conditioners and condenser coils; - Table 2.7: for water cooling equipment; - Table 2.8a: for cooling towers; - Table 2.8b: for condenser units. Notes: Apart from the cooling coefficient of performance (COP), refrigeration equipment is also reviewed for energy efficiency through the integrated part load value (IPLV) and integrated energy efficiency ratio (IEER). 9 Unofficial translation - QCVN 09: 2013/BXD b) Automatic timer: the following equipment must come with a timer or other control devices that may automatically turn the equipment on or off as set up. - Chillers; - Hot air systems; - Cooling tower fans; - Pumps with capacity equal or greater than 5 HPs (3.7 kW). c) Piping insulation of cooling systems: Coolant ducts of air conditioning systems and chilled water piping of central air conditioning systems shall be affixed with a thermal insulating layer with thickness equal or greater than the insulation thickness values specified in Tables 2.9 and 2.10. The insulating thickness (mm) provided in Tables 2.9 and 2.10 apply to thermal insulating materials with heat conductivity of 0.032÷0.04 W/m.K at a mean temperature of 24C. The minimum insulation thickness increases for materials with heat conductivity greater than 0.04 W/m.K or may decrease for materials with thermal conductivity lower than 0.032 W/m.K. For insulating materials with conductivity outside the above mentioned range, the minimum thickness (bmin) is determined using the following formula: b bmin r (1 0 ) / 0.04 1 r where, bmin r b0 λ (2.1) minimum thickness of the insulating layer, mm; actual duct external radius, mm; the thickness of the insulating layer listed in Tables 5.4, 5.5 and 5.6, with applicable piping sizes,mm; thermal conductivity coefficient of replacement materials at the liquid applicable temperatures, W/m.K. d) Inlet and outlet air duct system insulation: inlet and outlet air ducts shall be affixed with an insulating layer with thickness equal or greater than the thickness values specified in Table 2.11. No insulation is required for air exhausts. e) Testing and calibration: fans or pumps with capacity of 5 HPs (3.7kW) or higher shall have their designed flows calibrated in by calibrating speeds using multi-speed drives, twin-speed drives or variable speed drives (VSDs). Adjustment of fan and pump flow using flowregulating valves shall be restricted. f) Cooling tower fan control: heat extraction towers with fan motors of 5 HPs (3.7 kW) or higher shall be equipped with multi-speed drives, twin-speed drives or variable speed drives (VSDs). g) Water cooling chiller system: water-cooled air conditioning systems shall be designed with variable flow rates using pumps with variable speed drives. h) Buildings with central air conditioning must be equipped with enthalpy recovery systems. Equipment energy recovery efficiency shall be no smaller than 50%. 2) Supplementary requirements for mechanical ventilating and air conditioning systems To be qualified, mechanical ventilating and air conditioning systems shall meet the following additional requirements. 10 QCVN 09:2013/BXD a) CO2 sensor: installed to increase the inlet air flow for standard zones with design area of less than 3 m2/occupant. b) Automatic timer: intermittent ventilating fans shall be equipped with timers or automatic controls that are able to set their own on/off and operational timings. c) Piping welding and joining: inlet and circulating air ducts shall meet the requirements for joining air and fluid piping in line with existing regulations. Table 2.6. Coefficient of performance for direct electric air conditioners Type of equipment Unitary air-conditioner Split air-conditioner Cooling output - Min COP of air conditioners. kW/kW 2.30 <4.5 kW 2.60 4.5 kW and < 7.0 kW 7.0 kW and < 14.0 kW 2.50 2.93 19 kW and < 40 kW 40 kW and < 70 kW 70 kW and < 117 kW 117 kW <19 kW 19 kW and <40 kW 40 kW and < 70 kW 3.02 2.84 2.78 2.70 3.35 3.37 3.32 70 kW 2.70 Air-cooled condenser units 40 kW 2.96 Water-cooled or evaporating condenser units 40 kW Water-cooled and evaporating airconditioner TCVN 7830:2012 and TCVN 6307:1997 2.40 14.0 kW and < 19 kW Air-cooled airconditioner Test procedures TCVN 6307:1997 or ARI 210/240 ARI 340/360 ARI 210/240 ARI 340/360 ARI 365 3.84 ARI 365 11 Unofficial translation - QCVN 09: 2013/BXD Notes: 1) Coefficient of performance of air-conditioners: COP = refrigerant output/power input (kW/ kW); 2) Condenser units, including the compressor and condenser coils; 3) Minimum coefficients of performance listed in the Table are calculated at 100% of refrigerant output. To calculate the coefficient of performance for AC units running for one year, ARI 340/360 uses the following equation: IEER = 0.020A + 0.617B + 0.238C + 0.125D (W/W) where, IEER – Integrated energy efficiency ratio: coefficient of performance of AC units running for one year at various loads. A = EER –coefficient of performance of the AC unit (W/W) at full load; B = EER – coefficient of performance of the AC unit (W/W) at 75% load; C = EER – coefficient of performance of the AC unit (W/W) at 50% load; D = EER – coefficient of performance of the AC unit (W/W) at 25% load. Table 2.7. Coefficient of performance for chillers Cooling output (kW) Chiller coefficient of performance. COPMIN. kW/kW Air-cooled chiller, electric Attached or separated condenser All capacities 3.10 1.133 - Reciprocating water-cooled chiller, electric All capacities 4.20 0.836 - < 528 ≥ 528 and < 1055 ≥ 1055 < 528 ≥ 528 and < 1055 ≥ 1055 4.45 4.90 5.50 5.00 5.55 6.10 0.789 0.717 0.639 0.702 0.633 0.576 - Type of equipment Water-cooled rotary screw/scroll chiller, electric Centrifugal water-cooled chiller, electric Input energy consumption PICMAX. kW/RT Electricity Heat Air-cooled absorption chiller, All capacities 0.60 (*) 5.860 single effect Water-cooled absorption All capacities 0.70 (*) 5.022 chiller, double effects Absorber chiller, double All capacities 1.00 (*) 3.516 effects, indirectly fired Absorber chiller, double All capacities 1.00 (*) 3.516 effects, directly fired Notes: 1) Source: ASHRAE Standard 90,1-2001; ASHRAE Standard 90,1-2004; 2) (*) For absorption chillers, COP = Cooling output/Heat input; - Power input consumption: PIC = electricity input/cooling output in RT; - Refrigerant Ton (RT):1RT = 3.516 kW = 12000 Btu/h; 3) To calculate the coefficient of performance for chillers operating in one year, ARI 550/590-2003 provides the following equation: IPLV = 0.01A + 0.42B + 0.45C + 0.12D (kW/kW) where, IEER – Integrated energy efficiency ratio: coefficient of performance of cooling equipment for 12 QCVN 09:2013/BXD the accumulated operational time in one year on various loads. A –COP (kW/kW) at full load; B –COP (kW/kW) at 75% load; C –COP (kW/kW) at 50% load; D –COP (kW/kW) at 25% load. Table 2.8a. Performance specifications for cooling towers Cooling Type of output equipment range Cooling tower with draft fans and centrifugal fans Rated specifications Rating criteria Input water temperature:370C Output water All temperature: capacities 320C Moist air temperature:270C Water flow Supplementary throughput water flow 13 l/minute, Tc Test procedure Fan output 1.0 1.4 % Water flow through condenser 35 40 W/Tc CTI Notes: 1) CTI – Cooling Technology Institute; 2) Tc: condenser ton; Tc = RT 1.25 = 3.516 1.25 = 4.395 Kw. Table 2.8b. Required specifications for condenser units Rated specifications Type of equipment Cooling output range Rating criteria Air-cooled condenser units, with compressor 0.5500 RT Input air temperature: 350C Water-cooled 101600 condenser units RT Input water temperature: 29.40C Output water temperature: 350C Wind flow Fan Compressor 1734 m3/minute RT 75150 W/RT 1.01.3 kW/RT Test procedure CTC Water flow 9.08 11.40 l/minute RT CTC Notes: CTC – Cooling towers and condensers HVAC Equations, Data and Rules of Thumb, 2008, USA. Table 2.9. Thickness of insulation for copper refrigerant conduits Copper conduit diameter, mm 2 Air conditioned space Applicable conditions: t=26 ±2oC, φ= 60% Refrigerant temperature oC -18 -30 13 Unofficial translation - QCVN 09: 2013/BXD 6÷16 19÷25 34÷54 66÷80 105 9 9 9 13 - Copper conduit diameter mm 2 6÷16 19÷25 34÷54 66÷80 105 25 32 32 32 - Insulation thickness, mm 19 19 19 19 Non-air conditioned space Applicable conditions: t =26÷32 oC, φ = 85% Refrigerant temperature oC -18 Insulation thickness, mm 38 50 50 50 Applicable conditions: t = 32÷37 oC, φ = 60% Refrigerant temperature oC -18 Insulation thickness, mm 38 50 50 57 - 19 19 25 25 25 -30 50 50 57 64 70 Copper conduit 2 -30 diameter mm 6÷16 25 50 19÷25 32 50 34÷54 32 64 66÷80 32 70 105 76 Notes: 1) t – Exterior air temperature, oC; 2) The above insulation thickness applies to copper refrigerant (fluid, gas) conduits; 3) The thickness of the insulation (mm) given in the Table apply to insulating materials with thermal conductivity λ within a range of 0.032 ÷ 0.04 W/m.K at an average temperature of 24C. The minimum thickness of the insulating layer shall increase with materials having thermal conductivity higher than 0.04 W/m.K or decrease with materials having thermal conductivity less than 0.032 W/m.K and is adjusted using equation (5.1). Table 2.10. Thickness of insulation for cooled water conduits Steel pipe diameter, mm 20÷50 50÷75 75÷150 150÷250 250÷600 Steel pipe diameter, mm 14 Air conditioned space Applicable conditions: t=26 ±2oC, φ= 60% Cooled water temperature,oC 7÷12 Insulation thickness, mm 16 16 19 19 25 Non-air conditioned space Applicable conditions: t =26÷37oC, φ = 85% Cooled water temperature,oC 7÷12 QCVN 09:2013/BXD Insulation thickness, mm 20÷50 25 50÷75 25 75÷150 30 150÷250 30 250÷600 38 Notes: 1) For steel pipes with diameters listed in the table being rated diameters (IPS - Iron pipe standard); 2) The insulation thickness of steel pipes may apply also to PE, PPR and PN16 plastic pipes. In case of PE and PPR plastic pipes, the diameter values listed in the Table are outside diameters. 3) The thickness of the insulating layer (mm) given in Table 5.5 apply to insulating materials with thermal conductivity λ within a range of 0.032 ÷ 0.04 W/m.K at an average temperature of 24C. The minimum thickness of the insulating layer shall increase with materials having thermal conductivity higher than 0.04 W/m.K or decrease with materials having thermal conductivity less than 0.032 W/m.K and is adjusted using equation (2.1). Table 2.11. Thickness of insulation for air ducts Air conditioned space Applicable conditions: t=26 ±2oC, φ= 60% Cooled air temperature, oC 12÷16 Insulation thickness, mm 15 Non-air conditioned space Applicable conditions: t =26÷37 oC, φ = 85% Cooled air temperature, oC 12÷16 Insulation thickness, mm 20 Notes: The thickness of insulation (mm) given in the Table apply to porous polymer, close-compartment structured insulating materials with thermal conductivity λ within a range of 0.032 ÷ 0.04 W/m.K at a mean temperature of 24C. The minimum thickness of insulation shall increase with materials having thermal conductivity higher than 0.04 W/m.K or decrease with materials having thermal conductivity less than 0.032 W/m.K and is adjusted using equation (2.1). 2.3. Lighting 2.3.1 General provision 1) Scope This section provides limits for the maximum allowable lighting output needed for the building lighting system as well as limits on the acceptable performance of commonly used lighting components (lamps and ballasts) and lighting control systems. The following categories do not fall under the requirements of this section: a) Lighting designed for theatrical performance, television shows, different parts of recreation facilities, including hotel ballrooms, dance clubs, and areas where lighting is a vital technical part of the show functions; b) Specialized medical lighting; c) Special lighting for research laboratories; d) Safety lighting that automatically switches on and off during operation; e) Lighting in special security zones as required by the law or local governments; f) Safety or security zones for humans that need auxiliary lighting. 15 Unofficial translation - QCVN 09: 2013/BXD 2) Minimum illuminance The minimum illuminance (lux) for functional spaces shall meet the requirements of prevailing technical standards. 3) Maximum lighting power density a) The mean lighting power density (LDP) of an entire building shall not exceed the maximum allowed limits listed in Table 2.12. The mean lighting power density of a building equals the total lighting output of the building divided by the total occupied area. Table 2.12. Mandatory requirements for lighting power density (LPD) LPD (W/m2) Type of building Offices 11 Hotels 11 Hospitals 13 Schools 13 Commercial and services buildings 16 Apartments 8 Enclosed, in-house, basement car parks 3 Outdoor or open (roofed only) car parks 1.6 b) Other types of buildings with sizes subject to the restrictions of this Code but not listed in Table 2.12 above may apply maximum values of lighting power density of up to 13 W/m 2. c) For mixed-use buildings with sizes subject to the restrictions of this Code and various different functional areas, the functional use of each area shall be accounted for, with each of the areas complying with the maximum lighting power density values listed in Table 2.12 above. d) The mean lighting power density for parking lots is calculated by dividing the total lighting power by the gross area of the parking lot. 2.3.2 Requirements on lighting equipment performance 1) Minimum lamp performance is defined in Tables 2.13 and 2.14. Table 2.13. Minimum illuminating performance of linear fluorescent lamps Rated lamp power, W 14-20 20-40 Rated illumination efficiency, lm/W 72 78 Table 2.14. Minimum illuminating performance of compact fluorescent lamps Rated lamp power, W 5-8 16 Rated illumination performance, lm/W 55 QCVN 09:2013/BXD 9-14 15-24 25-60 60 65 70 2) Ballast efficacy values are listed in Table 2.15. Table 2.15. Electronic ballast efficacy Nominal output, W 18 20 22 30 32 36 40 Ballast efficacy factor (BEF), %/W 5.518 5.049 4.619 3.281 3.043 2.681 2.473 2.3.3 Lighting controls 1) Lighting controls for different building spaces Every space enclosed with ceiling-height partitions is a separate space that needs at least one lighting control device. Each of these lighting control devices shall be actuated manually or by automatic sensors for occupants in such space. Each control device must: a) Cover a maximum floor area of 100 m2 b) The spaces specified in Table 2.16 shall to be installed with occupancy sensors, which directly connect to and control the lighting system. Occupancy sensors controlling lamps shall not be connected to the exit lighting and security lighting systems. Table 2.16. Buildings for which occupancy sensors are required Type of building Application Offices Mandatory Hotels Mandatory Hospitals Schools Conference rooms and passageways Conference rooms and passageways Optional Mandatory In-house parking lots and passageways Commercial and services buildings Apartments To be used in Optional Mandatory Passageways and in-house parking lots d) For parking lots, at least 70% of the lighting system shall be controlled through occupancy sensors (proportion of the system in terms of lighting consumption power). 2) Controls for day-lit areas Artificial lighting designs for day-lit enclosed spaces need to take into account the following considerations: a) Potentially day-lit areas are spaces parallel to windows/exterior glazing within a distance from the window/exterior glazing of up to 1.5 times the height from the floor to the tip of the window glass area or exterior glazing. 17 Unofficial translation - QCVN 09: 2013/BXD b) All lighting equipment in potentially day-lit areas may be installed with lighting control devices in ways that allow: - Automatic photosensor to be used to control lamp dimming or turn lamps on and off depending on the level of natural illuminance received. Photosensor shall be positioned at half the depth of potentially day-lit areas. When natural light measured by the sensors at beyond the standard preset level for the occupant space (e.g. 300 lux for offices), the sensors should trigger lamp switch-off. - Stand-alone lamps to be turned on at potentially day-lit areas independently from the public lighting system. c) In respect of the design for areas using concurrently occupancy sensors and photosensors, the occupancy sensors shall be prioritized over photosensors for lighting control. d) Hospitals, apartment buildings and hotel rooms are not mandatorily required to apply the requirements of 2.3.3. e) Spaces designed for special uses are exempted from the requirements of 2.3.3 – 2), providing that the designer presents detailed justification. 3) Auxiliary lighting controls Auxiliary controls for light on/off switching installed in fixed positions underneath decks, shelves, cabinets and so on shall be used in the following events: a) Lighting for hotel, guesthouse rooms and luxurious guestrooms; b) Display lighting in shops or for demonstration. 2.4. Escalators and elevators 2.4.1 Escalators Escalators must be fitted with controls to reduce speed or to stop when no traffic is detected. Escalators shall be designed with energy savings features as described below: 1) Reduced speed control: the escalator shall change to a slower speed when no activity has been detected for a period of a maximum of three minutes. Detection shall be by photocell activation at the top and bottom landing areas. 2) Use on demand: the escalator shall shut down when no activity has been detected for a period of a maximum of fifteen minutes. Use on demand escalators must be designed with energy efficient soft start technology. The escalator shall start automatically when required. The activation shall be by photocells installed in the top and bottom landing areas. 2.4.2 Elevators (lifts) Elevators (lifts) must be provided with controls to reduce the energy demand. To meet this requirement, the following features must be incorporated in traction drive elevators: 1) Use of AC Variable-Voltage and Variable-Frequency drives on non-hydraulic elevators. 2) The lift car uses energy-efficient lighting and display lighting i.e. an average lamp efficacy, across all fittings in the car, of >55 lamp lumens/circuit watt and lighting switches off after the lift has been inactive for a maximum period of five minutes. 3) Elevators shall operate in a stand-by condition during off-peak periods. For example, the power side of the lift controller and other operating equipment such as lift car lighting, user displays and ventilation fans switch off when the lift has been inactive for a maximum period of five minutes. 2.5. Electric power consumption 2.5.1 Electrical distribution system 1) Measurement 18 QCVN 09:2013/BXD Building electrical distribution system shall be equipped with attached metering instruments to record energy demand (kVA), power consumption (kWh), and total loads on electricity meters. Electrical distribution systems in buildings shall be designed so that energy consumption at end-use loads can be check-metered. Check-metering is required for load facilities with total installed power consumption of over 100 kVA, including lighting and socket outlets, air conditioning system, ventilation, hot water system and other load centers of over 100 kVA. 2) Submetering Sub-metering for each tenant and a provision to permit check-metering the tenant load shall be in place. Notes: Shared (central) air-conditioning systems need not meet these tenant check-metering requirements. 3) Power factor correction All 3-phase electricity supplies exceeding 100 A shall maintain a power factor between 0.90 lag and unity at the point of connection. 4) Adjustment of installed power Electrical systems in a building shall be estimated, designed and operated to provide the maximum concurrent load factor possible as specified in Table 2.17 and the highest allowed installed power as specified in Table 2.18. Table 2.17. Maximum concurrent load factor ks, by points of use End-use load Lighting Socket outlets Air conditioning, ventilation Hot water system Other major load centers Entire building Concurrent load factor ks 0.9 0.4 0.9 0.9 0.9 0.8 Table 2.18. Maximum allowed installed power Installed power, W/m2 70 80 75 65 65 Type of building Upscale apartment buildings Hotels Offices, public use buildings Commercial, service, public service buildings Schools, hospitals 2.5.2 Electric motors All permanently wired 3-phase induction motors that are used in the building shall have a nominal full-load motor efficacy of no less than the values required in Table 2.19. The manufacturer’s labels on the motors must provide minimum efficacy, nominal efficacy and outputs at full load. Table 2.19. Minimum efficacy for electric motors Motor output, kW kW Required efficacy, % 2-pole 4-pole 19 Unofficial translation - QCVN 09: 2013/BXD 1.1 82.2 83.8 1.5 84.1 85.0 2.2 85.6 86.4 3.0 86.7 87.4 4.0 87.6 88.3 5.5 88.5 89.2 7.5 89.5 90.1 11.0 90.6 91.0 15.0 91.3 91.8 18.5 91.8 92.2 22.0 92.2 92.6 30.0 92.9 93.2 37.0 93.3 93.6 45.0 93.7 93.9 55.0 94.0 94.2 75.0 90.0 94.6 95.3 94.7 95.1 110.0 95.4 95.6 132.0 95.5 95.7 160.0 95.8 95.8 200.0 96.1 95.9 250.0 96.2 96.1 280.0 96.3 96.4 315.0 96.4 96.5 355.0 96.5 96.6 400.0 96.7 96.7 450.0 96.7 96.8 500.0 96.8 96.9 560.0 96.9 97.0 630.0 96.9 97.1 Notes: Motors with outputs in between two numbers shall adopt the higher efficacy value. 2.6.Service water heating system 2.6.1 General requirements Designed loads for service water heating systems shall be calculated based on system sizing and follow the manufacturers’ recommendations. In case other (non-resistance) service water heating solutions of higher efficiency are available, resistance-based service water heating systems shall not be allowed. 20 QCVN 09:2013/BXD Buildings in need of high, concentrated service water heating with installation input of over 50 kW or power consumption of over 50,000 kWh/year are not allowed to use resistance-based service water heating solutions. Order of priority for civil buildings: 1) Temperature range ≤60oC a) Service water heating using heat recovery air conditioning; b) Service water heating using solar power combined with heat pumps/electric heaters; c) Service water heating using heat pumps; d) Service water heating using gas water heaters; e) Service water heating using electric heaters for buildings with less than 25 rooms. 2) Temperature range ≥ 115oC (cooking, washing, disinfection, sauna) For buildings in concurrent needs of hot water of ≤ 600C (for household uses) and hot water/steam of ≥1150C (for cooking, laundering, sauna and disinfection), priorities shall be given to water heating up to 600C, before further heating the water or steam up to ≥1150C using gas or fuel oil-fired heaters. 2.6.2 Water heating equipment efficacy All water heating and supply equipment used internally for heating potable water, keeping warm, hot swimming pool and hot water storage tanks shall meet the requirements listed in Table 2.20. For heat pump water heaters, refer to Table 2.21. Table 2.20.Minimum efficacy for water heating equipment Equipment type Minimum efficiency ET, % 1. Gas-fired storage water heaters 78 2. Gas-fired instantaneous water heaters 78 3. Gas-fired hot water supply boilers 77 4. Fuel oil-fired hot water heaters and supply systems 80 5. Duel fuel gas/oil-fired hot water supply boilers 80 6. Firewood/paper-fired boiler of 10÷350 kW output 60*) 7. Boilers of 10÷2000 kW, burnt with molded brown coal 70*) 8.Pitcoal-fired boilers of 10÷2000 kW 73*) Notes: 1. The minimum efficiency for oil or gas-fired water heaters is given in terms of Thermal efficiency (ET), which includes thermal losses from the heater shell. 2. *) According to DIN 4702 – Part 1 (DIN – German standards). Efficacy for electric resistance-based water heaters in particular is given in terms of maximum Standby loss (SL), where a 40°C temperature difference between stored water and ambient requirements exists, and is determined using the equation: Emin = 5.9 + 5.3V0.5, W (2.2) Where -V is volume in liters. Table 2.21. Minimum coefficient of performance - COP for water heating heat pumps Equipment type Air-heated heat pumps Water-heated heat pumps Heat recovery air conditioners COP, kW/kW ≥ 3.0 ≥ 3.5 21 Unofficial translation - QCVN 09: 2013/BXD - Hot water supply only Air conditioning and hot water supply ≥ 3.0 ≥ 5.5 Electric resistance-based water heating equipment is not recommended except for supporting solar power systems. Electric heat pump water heating equipment with higher energy efficiency than electric resistance-based water heaters is recommended. Where eligible, solar powered service water heating systems may be used to meet all or part of water heating needs for the building. Solar powered water heaters shall have at least 60% efficacy and minimum thermal insulation R of 2.2 m2.K/W at the back of the solar panels. 2.6.3 Service water heating piping insulation The following hot water piping shall be insulated. 1) Steam piping serving such needs as laundry, cooking etc. 2) Hot water piping for bath, keeping warm, cooking etc. The insulation thickness of the piping shall be equal or greater than the insulation thicknesses listed in Tables 2.22 and 2.23. Table 2.22. Insulation thickness for hot water steel piping Air temperature; t = 5 37oC Hot water temperature (oC) Pipe size ≥ 115 mm 50÷90 Insulation thickness (mm) 20÷50 50 20 65÷80 50 20 90÷150 63 25 200÷250 63 25 Notes: 1. Insulating materials shall have conductivity of 0.06 ÷ 0.07 W/m.K, applicable to 115oC. 2. Closed particle structured, porous polymer insulating materials with thermal conductivity λ of 0.032 ÷ 0.04 W/m.K adopt the temperature range of 5090oC. 3. The insulation thicknesses in Table 2.22 shall ensure that the exterior temperature is lower than 43oC. 4. For insulating materials with conductivity outside the above mentioned range, the minimum thickness (bmin) is determined using equation (2.1). Table 2.23. Insulation thickness for PPR, PE hot water piping Outer diameter of PN20/ PN25 plastic pipes Conductivity 0.2 W/mK mm 20 50 22 Air temperature; t = 5 37oC Hot water temperature (oC) 50÷90 16 QCVN 09:2013/BXD 65 19 25 80 125 Notes: 1) For residential buildings, insulation may be optional for PPR hot piping. 2) Insulating materials shall maintain conductivity of 0.034 ÷ 0.04 W/m.K. 3) For insulating materials with conductivity outside the above mentioned range, the minimum thickness (bmin) is determined using formula (2.1). 2.6.4 Service water heating system controls 1) Temperature controls shall be provided to limit point-of-use water temperatures not to exceed 50°C. 2) Temperature controls shall be provided to limit the maximum temperature of water delivered to wash basin faucets in public restrooms up to 43°C. 3) Systems designed to maintain usage temperatures in hot water pipes shall be equipped with automatic ON/OFF switches that can be set to maintain desirable temperatures for recirculating hot water. 4) Recirculating pumps used to maintain storage tank water temperatures shall be controlled in ways to operate in harmony with the operating mode of the service water supply system. III.MANAGEMENT REGULATIONS 3.1. Design documentations of newly developed, reconditioned and retrofitted buildings with sizes subject to the scope of QCVN 09:2013/BXD shall include a narrative demonstration of compliance with the requirements of this Code. 3.2. Review and assessment of building designs shall be done in accordance with prevailing rules, including verification of compliance with the requirements of QCVN 09:2013/BXD for buildings that fall under the scope of this Code. IV.IMPLEMENTATION ARRANGMENT 4.1. The Department of Science,-Technology and Environment (Ministry of Construction) is responsible for popularizing and providing the implementation guidelines for QCVN 09:2013/BXD to interested parties. 4.2. Local regulators shall monitor compliance with the requirements of QCVN 09:2013/BXD for building design and construction works taking place in their jurisdictions and in accordance with the existing laws. 4.3. Any concerns that may arise during the adoption of this Code may be relayed to the Department of Science, Technology and Environment (Ministry of Construction) for guidance and responses. 23 Unofficial translation - QCVN 09: 2013/BXD ANNEXES (For reference) PHYSICAL SPECIFICATIONS OF MATERIALS, COMPOSITION AND THERMAL RESISTANCE CALCULATION FOR ENCLOSING ASSEMBLIES 1. Equation for the calculation of thermal resistance and overall heat transfer coefficient (U-value) of enclosing assembly Ro n b 1 1 ∑ i Ra hN 1 i hT , m2.K/W (1) where: hN , hT – respectively, the heat transfer coefficients of outer and inner surfaces of building envelope, W/m2.K ; bi - thickness of ith material layer, m; i - thermal conductivity of the ith material layer of the enclosing assembly, W/m.K; n - number of material layers in the enclosing assembly; Ra - thermal resistance of the air layer inside the enclosing assembly, if any, m2.K/W . Uo 1 Ro , W/m2.K (2) where: Thermal conductivity I listed in Table 1. See Table 3 for hN and hT. See Table 4 for the thermal resistance of air layer Ra. 2. Key parameters needed for building envelope calculations Table 1. Physical specifications of building materials Name of materials Asbestos-cement boards and panels Asbestos-cement insulating boards Asbestos-cement insulating boards Steel-net cement roof tile Reinforced concrete Broken rock and macadam concrete Broken brick concrete Light concrete (cinder concrete) Light concrete (cinder concrete) Light concrete (cinder concrete) Heat absorbing sponge concrete Heat absorbing sponge concrete Heat absorbing sponge concrete Heat absorbing sponge concrete 24 Unit weight , kg/m3 Thermal conductivity ,W/m.K I. Asbestos-based materials 1900 0.35 500 0.13 300 0.09 II. Concrete panels 2500 2400 2200 1800 1500 1200 1000 1000 800 600 400 1.55 1.28 0.87 0.70 0.52 0.41 0.40 0.29 0.21 0.15 Specific heat capacity, kJ/kg.K Moisture conductivity mg/m.h.kPa 0.84 0.84 0.84 0.03 0.39 - 0.84 0.84 1.21 0.84 0.80 0.75 0.75 0.84 0.84 0.84 0.84 0.00 0.03 0.05 0.07 0.09 0.11 0.14 0.08 0.08 0.13 0.20 QCVN 09:2013/BXD Heat absorbing silicate sponge concrete Heat absorbing silicate sponge concrete Heat absorbing silicate sponge concrete Drywall Pure gypsum boards and pieces Kiln cinder gypsum concrete 800 600 400 0.29 0.21 0.15 0.84 0.84 0.84 0.18 0.21 0.24 III. Gypsum-based materials 1000 0.23 1000 0.41 1000 0.37 0.84 0.84 0.80 0.05 0.11 0.15 IV. Terracotta materials, cushion materials, building brick blocks and coating layers Rammed clay and clay bricks 2000 0.93 0.84 Adobe 1600 0.70 1.05 Underneath humus 1800 1.16 0.84 Dry sand used as a cushion material 1600 0.58 0.84 Cushion materials made of sifted dry humus 1400 0.52 0.84 Silicate soil used as a cushion layer 600 0.17 0.84 Common bricks laid with heavy mortar 1800 0.81 0.88 Common bricks laid with light mortar 1700 0.76 0.88 Silicate bricks laid with heavy mortar 1900 0.87 0.84 Multi-hole bricks (γ = 1300) laid with light mortar (γ = 1400) 1350 0.58 0.88 Multi-hole bricks laid with heavy mortar 1300 0.52 0.88 Heavy mortar and coating cement mortar 1800 0.93 0.84 3-constituent mortar and 3-constituent coating mortar 1700 0.87 0.84 Lime mortar 1600 0.81 0.84 V. Non-fired brick, autoclaved aerated concrete AAC non-fired brick 400-900 0.12-0.13 Autoclaved aerated concrete (AAC lightweight 400-800 0.153 brick) Autoclaved aerated concrete brick 400-1000 0.11-0.22 300 0.10 400 0.12 500 0.14 Autoclaved aerated concrete (Chinese standard GB-11968:2006) 600 0.16 700 0.18 800 0.20 Peat-based insulating board Kiln cinder Kiln cinder Blast furnace cinder in particle state Cinder brick Light cinder mortar Light cinder mortar VI. Coal and cinder materials 225 1000 700 500 1400 1400 1200 0.07 0.29 0.22 0.16 0.58 0.64 0.52 1.67 0.75 0.75 0.75 0.75 0.75 0.75 0.10 0.17 0.17 0.19 0.30 0.11 0.12 0.11 0.15 0.09 0.10 0.12 0.19 0.20 0.22 0.23 0.11 0.14 25 Unofficial translation - QCVN 09: 2013/BXD External coating lime mortar Internal coating lime mortar External coating mortar for wood lath Internal coating mortar for wood lath Lime coating mortar mixed with slag Surface coating hard wood fiber board Quality paperboard Normal paperboard Corrugated paperboard Resin paper, bitumen paper Rice husk Rush Straw Straw-based panel Rush-based panel 1900 Window glass Fiberglass Vapor glass and bubble glass Vapor glass and bubble glass Pine and (cross the grain) Pine and (along the grain) Sawdust Treated sawdust Sawdust mixed with resin Plywood Fiberboard -ditto -ditto Soft wood board (corkwood) Boards made of corkwood waste Steel – sheet metal Pig iron Aluminum Indoor matting (cotton rug) 26 1600 1600 1400 1400 1200 700 0.87 0.70 0.70 0.52 0.47 0.23 0.84 0.84 1.05 1.05 0.80 1.47 0.14 0.14 0.12 0.12 0.14 0.08 VII. Scrolling materials 1000 700 150 600 0.23 0.17 0.06 0.17 1.47 1.47 1.47 1.47 - VIII. Agricultural products 250 400 320 300 0.21 0.14 0.09 0.10 1.88 1.47 1.51 1.47 - 0.10 1.51 - 2500 0.78 200 0.06 500 0.16 300 0.12 X. Wooden and cork materials 0.84 0.84 0.84 0.84 0.00 0.49 0.02 0.02 360 IX. Glass materials 550 550 250 300 300 600 600 250 150 250 150 XI. Metals 0.17 0.35 0.09 0.13 0.12 0.17 0.16 0.08 0.06 0.07 0.06 2.51 2.51 2.51 2.30 1.88 2.51 2.51 2.51 2.51 2.09 1.88 0.32 0.26 0.26 0.25 0.02 0.11 0.09 0.34 0.04 0.05 7850 7200 2600 XI. Other materials 58 50 220 0.48 0.48 0.48 0 0 0 0.06 1.88 0.34 150 QCVN 09:2013/BXD Mineral cotton rug Mineral cotton rug Patterned silicate boards and patterned silicate cement boards 200 250 0.07 0.08 0.75 0.75 0.49 0.45 600 0.23 2.30 - Patterned silicate boards and patterned silicate cement boards 400 0.16 2.30 - Patterned silicate boards and patterned silicate cement boards 250 0.12 2.30 - Notes: 1 W/m.K=0.86 kcal/m.h.oC; 1 kJ/kg.K=0.24 kcal/kg.oC ; For new building materials not listed in this table, designers may use other international standards. Table 2. Solar heat gain coefficient α of material surface No 1 2 3 4 Surface, materials and colors 1. Materials White paper Dry peat Particle ceramics Cinder 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 2. Wall surface Polished, bright colored limestone Ditto, dark colored Brownish yellow sandstone Dark yellow sandstone Red sandstone Polished, white marble Ditto, dark colored Polished, light grey granite Grey, polished granite Enameled, white brick Ditto, bright brown colored Common, dusted bricks Ditto, new red colored Surface coating bricks, bright colored Smooth, even concrete surface Mortared surface, yellow-white painted Ditto, dark colored Ditto, white colored Ditto, light blue colored Ditto, light cement colored Ditto, snow-white colored Vapor silicate Plain wood Wood painted in dark colors Wood painted in light yellow colors Smooth polished bamboo Normal bamboo α ratio 0.20 0.64 0.8 - 0.85 0.81 0.35 0.50 0.54 0.62 0.73 0.30 0.65 0.55 0.60 0.26 0.55 0.77 0.70 - 0.74 0.45 0.54 - 0.65 0.42 0.73 0.40 0.59 0.47 0.32 0.56 - 0.59 0.59 0.77 0.60 0.43 0.60 27 Unofficial translation - QCVN 09: 2013/BXD 59 60 61 62 63 64 65 3. Roofing surface New, white fibrocement boards Ditto, used for 6 months Ditto, used for 12 months Ditto, re-coated with cement water Ditto, used for 6 years Corrugated mineral cotton boards Light brownish mineral cotton boards Roofing oilpaper, coarse finish Ditto, sprinkle-coated with mineral particles Ditto, sprinkled with grey colored sand particles Ditto, sprinkled with dark colored sand particles Light colored sheet metal Black sheet metal Red or brown roof tile Grey cement roof tile Polished or white plated steel Ditto, in blue color Galvanized steel, new Ditto, dusted Unpolished aluminum Polished aluminum 4. Paint coated surface Painted in bright red (pink) color Painted in blue color Painted with cobalt-based materials, in bright blue color Ditto, purple color Painted in yellow Painted in red 5. Sidewalk and road surface New asphalt Old asphalt Cinder concrete Granite macadam Sand mixed with gravel Wet sand Granite rock and gravel 66 67 68 69 70 71 72 73 74 75 6. Transparent materials Polyclovinil screen, thickness 0.1 mm AFF polyamide screen, thickness 0.08 mm Polyethylene screen, thickness 0.085 mm 7 mm-thick glass 4,5 mm-thick door glass 6 mm-thick glass with heat absorbing surface 17 mm-thick imaging glass 1.2 mm-thick colorless organic glass Ditto, yellow colored, 2.7 mm in thickness Ditto, blue colored, 1.4 mm in thickness 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 28 0.42 0.61 0.71 0.59 0.83 0.61 0.53 0.91 0.84 0.88 0.90 0.26 0.86 0.65 - 0.72 0.65 0.45 0.76 0.30 0.90 0.52 0.26 0.52 0.64 0.58 0.83 0.44 0.63 0.89 0.67 0.89 0.80 0.66 0.80 0.67 0.096 0.164 0.109 0.076 0.04 0.306 0.02 0.123 0.46 0.34 QCVN 09:2013/BXD Table 3. Surface heat transfer coefficient of envelope structures h, W/m2.K (in accordance with TCVN 298:2003 and ISO 6946:1996 standards) Heat flux direction Horizontal Upward Downward (for walls) (for roofing) (for roofing) Outer surface heat transfer coefficient hN, W/m2.K 25 25 25 Inner surface heat transfer coefficient hT, W/m2.K 7.692 10 5.882 Name of coefficient Table 4. Thermal resistance of unventilated air layer Ra, m2.K/W (in accordance with TCVN 298:2003 and ISO 6946:1996 standards) Heat flux direction Horizontal Upward Downward (for vertical air layer) (for horizontal air layer) (for horizontal air layer) 0 0.00 0.00 0.00 5 0.11 0.11 0.11 7 0.13 0.13 0.13 10 0.15 0.15 0.15 15 0.17 0.16 0.17 25 0.18 0.16 0.19 50 0.18 0.16 0.21 100 0.18 0.16 0.22 300 0.18 0.16 0.23 Air layer thickness, mm Notes: Intermediate values may be determined using linear interpolation. 3. Select common exterior wall and roof designs, and total thermal resistance Ro may be calculated using equation (1). 3.1. WALLS T1. Single-leaf wall (conventional bricks thickness: 110 mm), fireclay solid - L í p v÷a tr¸ t = 15 m m - G¹ ch ®Êt sÐt nung = 105 m m - L í p v÷a tr¸ t = 15 m m 29 15 105 15 Unofficial translation - QCVN 09: 2013/BXD - Plaster δ=15 mm - FireclayThermal bricks δ=105 mm Thickness, - Plaster δ=15 mm conductivity, No Material layers, outside in 1 Exterior plaster Fireclay solid brick and heavy (cement) mortar brickwork Interior plaster 2 3 m , W/(m.K) 0.015 0.93 0.105 0.81 0.015 0.93 Total thermal resistance Ro, m2.K/W Qualified or not qualified for Code requirements 0.332 Ro<0.56 m2.K/W Not qualified! T2. One brick thick wall (conventional thickness: 220 mm), fireclay solid bricks Plaster δ=15 mm L í p v÷a tr¸ t = 15 m m Fireclay bricks δ=105 mm G¹ ch ®Êt sÐt nung = 105 m m Joint mortar δ=10 mm V ÷a chÌ n δ=105 m ¹ ch Fireclay bricks mm = 10 m m Plaster G¹ chδ=15 ®Êtmm sÐt nung = 105 m m - L í p v÷a tr¸ t = 15 m m 60 10 ---- 15 Material layers, outside in 1 Exterior plaster Fireclay solid brick and heavy (cement) mortar brickwork Interior plaster 3 15 Thermal Thickness, conductivity, m , W/(m.K) No 2 105 10 105 0.015 0.93 0.220 0.81 0.015 0.93 Total thermal resistance Ro, m2.K/W Qualified or not qualified for Code requirements 0.474 Ro<0.56 m2.K/W Not qualified! T3. Single-leaf wall (conventional thickness: 110 mm), fireclay hollow bricks --- Plaster L í p δ=15 v÷amm tr¸ t = 15 m m Hollow bricks δ=105 mm G¹ chδ=15 rç ng Plaster mm = 105 m m - L í p v÷a tr¸ t = 15 m m 15 30 105 15 QCVN 09:2013/BXD Thermal Thickness, conductivity, m , W/(m.K) No Material layers, outside in 1 Exterior plaster Hollow bricks (γ = 1300) and light plaster (γ = 1400) brickwork Interior plaster 2 3 0.015 0.93 0.105 0.58 0.015 0.93 Total thermal resistance Ro, m2.K/W Qualified or not qualified for Code requirements 0.383 Ro<0.56 m2.K/W Not qualified! T4. Calculating thermal resistance for one brick thick walls (conventional thickness: 20 mm), fireclay hollow bricks ---- 60 10 15 105 10 105 Material layers, outside in 1 Exterior plaster Hollow bricks (γ = 1300) and light mortar (γ = 1400) brickwork or Multi-hole bricks with heavy (cement) mortar brickwork Interior plaster 3 15 Thermal Thickness, conductivity, m , W/(m.K) No 2 Plaster δ=15 mm L í p v÷a tr¸ t = 15 m m Hollow bricks δ=105 mm G¹ rç ng = 105 m m Jointch mortar δ=10mm Hollow bricksδ=105 mm = 10 m m V ÷a chÌ n m ¹ ch Plaster mm = 105 m m G¹ chδ=15 rç ng - L í p v÷a tr¸ t = 15 m m 0.015 0.93 0.220 0.58 or 0.52 0.015 0.93 Total thermal resistance Ro, m2.K/W 0.584 or 0.625 Qualified or not qualified for Code requirements Ro>0.56 m2.K/W Qualified or Qualified and over qualified T5. Brick, porous concrete and single-leaf walls (conventional thickness: 110 mm) -- Plaster L í p δ=15 v÷amm tr¸ t = 15 m m - Autoclaved lightweight concreteδ=105 mm Bl ècδ=15 bª mm t«ng nhÑ =105 m m -- Plaster - L í p v÷a tr¸ t = 15 m m 15 105 15 31 Unofficial translation - QCVN 09: 2013/BXD Thermal Thickness, conductivity, m , W/(m.K) No Material layers, outside in 1 Exterior plaster 0.015 0.93 2 Porous concrete bricks 0.105 0.37 Total thermal resistance Ro, m2.K/W Qualified or not qualified for Code requirements Ro<0.56 m2.K/W Not qualified! 0.486 3 Interior plaster 0.015 0.93 T6. Brick, porous concrete and one brick thick walls (conventional thickness: 220 mm) 60 10 ----- Plasterδ=15 mm L í p v÷alightweight tr¸ t =concrete 15 m m Autoclaved δ=105 mm Bl èc bª t«ng nhÑ = 105 m m Joint mortar δ=10 mm Autoclaved = 10 m mmm V ÷a chÌlightweight n m ¹ chconcreteδ=105 Plaster mm nhÑ = 105 m m Bl èc δ=15 bª t«ng - L í p v÷a tr¸ t = 15 m m 15 105 10 105 15 Thermal Thickness, conductivity, m , W/(m.K) No Material layers, outside in 1 Exterior plaster 0.015 0.93 2 Porous concrete bricks 0.220 0.37 3 Interior plaster 0.015 0.93 Total thermal resistance Ro, 2 m .K/W Qualified or not qualified for Code requirements Ro>0.56 m2.K/W Qualified and over qualified 0.797 T7. 3D 180 mm thick panels --- Plasterδ=15 mm L í p v÷a tr¸ t = 15 m m Sand cement layer, with steel mesh δ=50 mm = 50 m m L í p x i panel m ¨ ng c¸ tmm Polystyrol δ=20-50 Sand layer, cã lcement - í i thÐ p with steel mesh δ=50 mm Plasterδ=15 T Êm polmm y sty rol = 20 - 50 m m - L í p x i m ¨ ng c¸ t = 50 m m cã l - í i thÐp - L í p v÷a tr¸ t = 15 m m 15 No Material layers, outside in 1 Exterior plaster 32 50 2050 15 Thickness, m Thermal conductivi ty, , W/(m.K) 0.015 0.93 Total thermal resistance Ro, 2 m .K/W 0.81÷ 1.56 Qualified or not qualified for Code requirements QCVN 09:2013/BXD Cement, sand and steel mesh Ro>0.56 m2.K/W 0.05 0.93 3D panels Qualified and over qualified Porous polystyrol insulating 3 0.02÷ 0.05 0.04 or excessively over layer qualified Cement, sand and steel mesh 4 0.05 0.93 3D panels 5 Interior plaster 0.015 0.93 Notes: The total thermal resistance of exterior walls is calculated using the heat transfer coefficient of the exterior surface - hN= 25 W/m2.K and heat transfer coefficient of the interior surface - hT= 7,692 W/m2.K – see Table 3, Annexes. 3.2. ROOF 2 M1. Roofing with a 105 mm thick hollow brick insulating layer -- Terra cotta tile 200x200x15 mm G¹ ch l ¸ nem 200 200 15 m m Tiling mortar δ=10 mm V ÷a l ¸ t = 10 m m Heat resistant brick 200x200x105 mm, δ=105 mm G¹ ch chèng nãng 200 200 105 m m , = 105 m m Damp resistant steel mesh cement mortar δ=20 mm V ÷a x i m ¨ ng l - í i thÐp chèng thÊm = 20 m m Roof reinforced concrete δ=120 mm Bª t«ng cèt thÐp m ¸ i = 120 m m Ceiling plaster δ=15 V ÷a tr¸ t trÇ n mm = 15 m m Thermal conductivity , , W/(m.K) No Material layers, top down Thickne ss, m 1 Terra cotta tile 0.015 0.81 2 Tile plaster 0.01 0.93 3 Fireclay tile (continuous parts) 0.105 0.81 4 0.053 0.81 6 Fireclay tile (partition walls) Aerated hollow holes, Ra = 0.22 m2. K /W Vertical plaster lining 0.105 0.93 7 Cement and steel mesh plaster 0.02 0.93 8 Reinforced concrete 0.12 1.55 9 Interior plaster 0.015 0.93 5 0.053 Total thermal resistance Ro, m2.K/W Qualified or not qualified for Code requirements 0.640 Ro< 1.0 m2.K / W Not qualified M2. Roofing with a 105 mm thick hollow brick insulating layer and 150 mm thick porous concrete =1000 kg/m3 With composition similar to the M1 roof, but with an additional 150 mm thick lightweight concrete – porous concrete layer =1000 kg/m3 - =0.41 W/(m.K) on top of the heat insulating tiles, resulting in a total thermal resistance of the M2 roof of Ro=1.006 m2.K/W – qualified. 33 Unofficial translation - QCVN 09: 2013/BXD No Material layers, top down Thicknes s, m 1 Terra cotta tile 0.015 Total Thermal thermal conductivit resistance y, , Ro, W/(m.K) m2.K/W 0.81 2 Tile plaster Lightweight-porous concrete layer (=1000 kg/m3) Fireclay tile (continuous parts) 0.01 0.93 0.150 0.41 0.105 0.81 0.053 0.81 7 Fireclay tile (partition walls) Aerated hollow holes, Ra = 0.22 m2. K / W Vertical plaster lining 0.105 0.93 8 Cement and steel mesh plaster 0.02 0.93 9 Reinforced concrete 0.12 1.55 10 Interior plaster 0.015 0.93 3 4 5 6 1.006 0.053 Qualified or not qualified for Code requirements Ro> 1.0 m2.K / W Qualified M3. Roofing with 30 mm thick polystyrol porous panels ---- Terrach cotta 200x200x15 mm G¹ l ¸ tile nem 200 200 15 m m Tiling mortar δ=10 mm V ÷a l ¸ t =10 m m Polystyrol panel δ=30 mm TÊm x èp pol y sty rol = 30 m m Cement mortar δ=5 mm V ÷a x i m ¨ ng =5 m m Damp resistant polymer cement δ=2 mm X i m ¨ ng pol i m er chèng thÊm =2 m m Roof reinforced concrete δ=120 mm Bª t«ng cèt thÐ p m ¸ i = 120 m m Ceiling plaster δ=15 mm - V ÷a tr¸ t trÇn =15 m m Thickne ss, m Thermal conductivi ty, , W/(m.K) No Material layers, top down 1 Terra cotta tile 0.015 0.81 2 Tile plaster 0.01 0.93 3 Polystyol panel 0.03 0.04 4 0.05 0.93 0.002 0.93 6 Cement plaster Damp resistance polymer cement plaster Reinforced concrete 0.12 1.55 7 Interior plaster 0.015 0.93 5 34 Total thermal resistance Ro, m2.K/W Qualified or not qualified for Code requirements 1.140 Ro > 1.0 m2.K / W Qualified QCVN 09:2013/BXD Notes: The total thermal resistance of roofing is calculated using the heat transfer coefficient of the exterior surface - hN= 25 W/m2.K and heat transfer coefficient of the interior surface - hT= 5,882 W/m2.K – see Table 3, Annexes. 35