Modeling of Power System Components Paulo F. Ribeiro, PhD, PE BWX Technologies, Inc. Product Development Department Lynchburg, VA 25502 0 5 0 5 1 A Complex Environment: A Philosophical Reflection These things are so delicate and numerous that it takes a sense of great delicacy and precision to perceive them and judge them correctly and accurately: Most often it is not possible to set it out logically as in mathematics, because the necessary principles are not ready at hand, and it would be an endless task to undertake. The thing must be seen all at once, at a glance, and not as a result of progressive reasoning, at least up to a point. 2 0 Blaise Pascal, 1650 2 10 5 0 5 10 2 Outline Introduction General Considerations The Modeling of Linear Loads Recommended Models Other Considerations Sensitivity Tests Modeling of Other Elements Distribution Lines and Cables Transformers Rotating Machines Induction Motors Supply System Equivalent Distribution System Example The Need for a Complete Load Representation Conclusions 3 Introduction One difficulty in calculating harmonic voltages and currents throughout a transmission system is the need for an adequate equivalent to represent the distribution system and consumers' loads fed radially from each busbar. It has become evident that the use of equivalents without a comprehensive check on the effect of all impedances actually present can lead to inaccurate estimation of harmonic voltages and currents in the transmission system. On the other hand, it is not practicable to obtain and represent all the system details. A detailed analysis of distribution systems, loads and other linear system elements is presented, models discussed and a simple but more realistic approach adopted. It consists basically of representing the dominant characteristics of the network using alternative configurations and models. Simpler equivalents for extended networks are also suggested. 4 General Considerations Although further considerations leading to simpler equivalents are given later, the basic assumptions used in this paper are as follows: (1) Distribution lines and cables (say, 69-33kV, for example) should be represented by an equivalent pi. For short lines, estimate the total capacitance at each voltage level and connect it at the termination buses. (2) Transformers between distribution voltage level should be represented by an equivalent element. (3) As the active power absorbed by rotating machines does not correspond to a damping value, the active and reactive power demand at the fundamental frequency may not be used straightforwardly. Alternative models for load representation should be used according to their composition and characteristics. (4) Power factor correction (PFC) capacitance should be estimated as accurately as possible and allocated at the corresponding voltage level. (5) Other elements such as transmission line inductors, filters and generators should be represented according to their actual configuration and composition. (6) The representation should be more detailed nearer the points of interest. Simpler equivalents, either for the transmission or distribution systems should be used only for remote points. (7) For distribution system studies, all the elements may be assumed to be uncoupled three-phase branches with no mutuals, but allowing unbalanced parameters per phase. 5 230kV 69kV loads 69kV identical circuits 13.8kV 13.8kV 380kV p.f.c. cap. A distribution system comprises a number of loads conveniently supplied by circuits from the nearest distribution point. The distribution circuit configuration depends on the particular load requirements. In general, a considerable number of loads are located so close together and supplied from the main distribution point, that they can be considered as a whole. For the majority of installations, whether supplying a small factory, domestic/commercial consumers, or a large plant, a simple radial system is used. A typical distribution network is shown in Figure 3.1 Figure 3.1: Typical distribution system configuration 6 A simplified dominant configuration can be derived as illustrated in Figure 3.2, based on the basic assumptions. This arrangement would represent the dominant characteristics (impedances) of the supply circuit fed radially from each transmission busbar. 230kV 69kV 69kV 13.8kV Figure 3.2 7 In order to simplify the manipulation of the distribution system, load and other elements data, the following procedure based on the configuration of Figure 3.2, is suggested. The dotted lines in Figure 3.3 mean different possibilities of connecting the load or other elements such as, compensator filters, generator, etc. The total equivalent impedance is then calculated at each harmonic frequency and connected to the transmission busbar as a shunt element. Consequently, there is no alteration of the dimension of the transmission system matrix. See illustration in Figures 3.3 and 3.4. A composition of different arrangements can be represented at the same busbar. p.f.c. cap. Transf. 1 Line/Cable Different possibilities of connection Fig. 3.3 Transmission System 3-phase Representation Transf. 2 Load & Other Elements Distribution system and other elements Fig. 3.4 8 The Modeling of Loads In this section, the modeling of individual elements is discussed in detail. Considering that there is some disagreement regarding which harmonic models are best for loads, transformers, generators, etc, various proposed models are discussed. Also simpler equivalents for distribution and transmission systems at remote points of the area of interest are discussed. Consumers' loads play a very important part in the harmonic network characteristic. They constitute not only the main element of the damping component, but may affect the resonance conditions, particularly at higher frequencies. Indeed, measurements have shown that maximum plant conditions resulted in a lowering of the impedance at the lower frequencies, but cause an increase at higher frequencies. Simulations have shown that the addition of load can result in either an increase or decrease in harmonic flow. Consequently, an adequate representation of the system loads is needed. However, it is very hard to obtain detailed information about this. Moreover, as the general loads consist of an aggregate number of components, it is difficult to establish a model based on theoretical analysis. 9 The necessity of practical measurements on distribution points, at 13.8kV for example, together with detailed information of the network under study, is vital for the understanding and establishment of a realistic model. Attempts to deduce a model from measurements have been made. However, more comprehensive measurements and system data are needed. Although practical experience is still insufficient to guarantee the best model, system studies have to proceed with whatever information is available. Thus, load characteristics are looked at in detail and alternative models developed in the following. A typical composition of consumers' plant may be as shown in Table 3.1 . From Table 3.1, it seems evident that there are basically two sorts of linear loads -resistive and motive. That would imply a simple combination of resistances and inductances. However, the difficulty in obtaining detailed information about composition, power and variation with time makes the task very hard. Nevertheless, it is possible to approach the problem of representing loads for harmonic studies by using alternative models according to the load characteristics and information available. 10 TABLE 3.1 Load Composition Nature Type of Load Domestic Incandescent Lamp Compact Fluorescent Small Motors Computers Home Electronics Incandescent Lamp Air Conditioner Resistive Heater Refrigeration Washing Machine Fluorescent Lamp (Std) ASDs Fluorescent (Electronics) Computers Other Electronic Loads Fan Pump Compressor Resistive Heater Arc Furnace ASDs Other Electronic Loads Commercial Small industrial Plants (Low Voltage) Electrical Characteristics Passive Resistive Non-linear Passive Inductive Non-linear Non-linear(*) Passive Resistive Passive Inductive Passive Resistive Passive Inductive Passive Inductive Non-linear(*) Non-linear(*) Non-linear(*) Non-linear(*) Non-linear(*) (*)These loads are harmonic producing. Hence, they do not exhibit a constant R, L, or C, ie. they are non-linear and therefore cannot be included in an equivalent network of impedances. Fortunately, there is every reason to believe they have insignificant effect (open circuit) on the harmonic impedance. Passive Inductive Passive Inductive Passive Inductive Passive Resistive Non-linear(*) Non-linear(*) Non-linear(*) 11 Recommended Models Loads are generally expressed by their active and reactive power P and Q, respectively, which are used to calculate the equivalent impedance for load flow studies at fundamental frequency, assuming the system voltage. However, at harmonic frequency, P and Q cannot be used straightforwardly because the active power absorbed by a rotating machine does not exactly correspond to a damping value and so additional information is necessary. The following alternative models can be used according to the load characteristics and information available: 12 A. At harmonic frequencies, the reactive power estimated may have a negligible effect in some cases. Thus, the P is considered equivalent to a resistance of value R=V2/P, V being the nominal voltage at fundamental frequency (see Figure 3.5). This representation should be used when the motor part is very small, i.e. for commercial and domestic loads in which the motive part is so partitioned that the resistive effect is predominant. R resistive part only Fig. 3.5 13 B. The equivalent resistance is estimated as above, but with an inductance in parallel. This should be evaluated using an estimation of the number of motors in service, their installed unitary power, not demand, and their negative sequence inductance. However, if precise information on the number of motors, etc. in use at any given time is unavailable, a fraction K of the total MW demand must be used to represent the motor part. This is then multiplied by a factor of, for example, 1.2 in order to consider the installed power which should be used. To calculate the equivalent negative sequence inductance, a factor K1, proportional to the severity of the starting condition should be used. Therefore, we will have: R= where P K K K1 w V2 _ P(1-K) L = V2 ____ ______ 1.2 (K+KE) K1 Pw =total MW demand =motor fraction of the total MW =electronic controlled load fraction of total MW =severity of starting condition = radian frequency R L R I Fig. 3.6 K assumes values around 0.80 for industrial loads and around 0.15 for commercial and domestic loads. K1 assumes values between 4 and 7. KE can assumes values around 0. It may well be that it is sufficiently accurate to ignore the resistive component of the motor part. However, an additional resistance representing the motor damping can be included as R1=L/K2, where K2 is a fraction of the negative sequence inductance or locked-rotor inductance. K2 assumes values around 0.20. 14 C. When a big induction motor or group of motors are connected directly at intermediate voltage levels, which is the case in industrial plants, the motive part is better represented by a resistance in series with the negative sequence inductance of the motor. The model can be assessed as follows: -- The equivalent resistance, the resistive part, and the negative sequence inductance of the motor is estimated as in B, and the series resistance estimated by R1 = wL/K3, where K3 =effective Q of the motor circuit ~ 8 w =radian fundamental frequency Alternatively, a series inductance LT to represent the equivalent leakage reactance of the distribution transformers at lower voltage connecting the resistance load can be incorporated (see Figure 3.7). A value of wLT = 0.1R can be assumed. LT R 1 L R Fig. 3.7 resistiv e par t motive part part 15 D. This model was developed from experiments performed on medium voltage outputs using audio-frequency ripple-control generators at EDF. The circuit suggested was an inductance in series with a resistance. This branch was connected in parallel with another inductance. The estimated P and Q are used in empirical formulae to calculate the equivalent impedances. Thus, R = V2/P; L1 = 0.073R/w; L2 = R/(6.7tg(phi)-0.74)w; tg(phi) = Q/P L1 resistive part R L2 motive part Fig. 38 (See Figure 3.8). Although this model was obtained based on two frequencies only, 175 and 495Hz, and the information available is not clear enough on how the equivalent circuit was derived, the parameters do not differ substantially from models B and C. L2 seems equivalent to the motor part inductance and R/L1 to the resistive circuit. 16 Other Considerations When the harmonic number increases, it is necessary to use larger values of R. As no information is yet available, a factor of h1/2, where h is the harmonic order, seems a reasonable value as a first approximation. linear load Z C P.F.C. capacitance Fig. 3.9 The harmonic impedance of distribution systems and loads has actually been measured on many locations. The results could not be satisfactorily reproduced digitally until the downstream system from 33kV and capacitance at 415V were represented. Measurements showed that there is a strong indication of an effect of power factor correction capacitance on the harmonic impedance of 11kV, 33kV, and 132kV systems. Therefore, there are reasons to believe that PFC capacitance should be represented. The PFC MVAr could be up to half of the MW numerically, depending on the local PFC policy and system conditions, i.e. whether maximum or minimum plant. Hence, the overall load representation should be as Figure 3.9. The PFC MVAr should be represented as a fraction of the total MW estimated. 17 3.3.3 Sensitivity Tests In order to illustrate the sensitivity of the equivalent harmonic impedance with the load level and composition, a set of examples is shown in Figures 3.10 to 3.12. Typical parameters for a 69 kV distribution system are used. The resistive, inductive, and capacitive parts of the load are varied and the equivalent impedance calculated. The examples show considerable variation in the equivalent impedance for variations of the resistive and reactive components of the load. For instance, when the resistive part of the load approximates the surge impedance of the line, the resonance effect is significantly reduced (see Figure 3.10). Conversely, changes in the reactive part may affect considerably the equivalent impedance. A general point is the magnitude of the peak impedance at resonance. These examples do show very clearly the importance of an accurate estimation and representation of the distribution system and loads. Although the variations imposed seem exaggerated, it is very likely that such deviations between the estimated and the actual parameters may occur, as the information is not easily obtainable. 18 Fig. 3.10 19 Modeling of Other Elements Distribution Lines and Cables Distribution lines and cables are represented by their exact equivalent pi. An estimated correction factor for skin effect is applied by increasing the line resistance with frequency by: 0.646h2 ) 192+0.518h2 R = R(0.187+0.532h1/2 ) R = R (1 + lines cables Transformers Complete representation of transformers, including capacitances, is not practical and cannot be justified for harmonic frequencies. Experience has shown that capacitances start to have some effect at 10KHz, i.e. well above the common harmonic frequencies present in power systems, i.e. 2hkz. Transformer impedance is shown to be proportional to the leakage reactance and linear with frequency. Various impedance representations have been suggested. The following alternative models can be represented:- 20 A. A resistance in series with the leakage inductance. Here a correction factor of h1.15 can be used (See Figure 3.13). R L Fig. 3.13 B. The leakage reactance in parallel with a resistance. This is calculated by multiplying a factor times the reactance. A factor of 80 has been suggested (See Figure 3.14). R Fig. 3.14 L C. Pesonen et al suggested a resistance Rs in series with an assembly of inductance L in parallel with a resistance Rp. Resistances Rs and Rp are constant whatever the frequency and an estimate of their value can be obtained as provided by expressions:-- 90<V2/SRs<110 13<SRp/V2<30 with S being the rated power of the transformer, (see Figure 3.15). R1 R2 L Fig. 3.15 21 Rotating Machines (a) Synchronous Generators When non-linear currents/voltages appear in the stator of a synchronous machine, the fundamental component is responsible for the energy conversion process and sets up a rotating mmf wave which reacts with the rotor mmf to produce the resultant fundamental mmf gap flux. Conversely, the harmonic components set up mmf waves rotating at different frequencies, but there is no armature reaction. Therefore, the reaction offered to harmonics is not related to synchronous parameters but an equivalent impedance which should be a function of the leakage path. Also, it may be assumed that synchronous machines produce no harmonic voltages, and they can be represented by a shunt equivalent impedance. However, the literature is not in agreement regarding appropriate impedances at harmonic frequencies. Westinghouse, Williamson, and Pesonen et al suggest a reactance derived from either the subtransient or negative sequence inductance:-X = 1/2(Xd"+Xq") =X2 Shilling suggest X = Xd", while Campbell and Murray suggest X =Xd'. Fresl suggests X =1/2(Xd"+X2), where X2 = 1/2(Xd"+Xq"). Westinghouse suggests a correction of the equivalent inductance. This is because when frequency increases, a smaller amount of flux penetrates the rotor. The amount is not known accurately but normally taken as the unity for the fundamental and 0.8 at 1000Hz. When using typical values of synchronous machine reactance to calculate the equivalent reactance X, it can be observed that the subtransient reactance seems a reasonable value and should be used. A resistance representing the damping can be incorporated. Electra 32 suggests a skin effect correction factor of h0.96. Regarding the equivalent circuit, Personen et al suggest a parallel combination of R and L. Here a series combination is more appropriate, as the equivalent circuit of a synchronous generator can be visualized as an induction motor for harmonic frequency. However, regarding practical values, the skin effect representation and the way to combine the impedances will not cause any significant difference on the equivalent impedance. In the program, a series or parallel combination can be used. Skin effect and inductance correction can be represented too. A damping resistance based on the losses can be added for both series or parallel combination. 22 (b) Induction Motor The well known configuration of an equivalent circuit of an inducting motor is shown in Figure 3.17a. The slip, s, at harmonic frequencies s(h) is approximately equal to 1 as s(h) = h±(1-s(1)/h) ~ 1, where s(1) ~0.02 With Xm negligible, the equivalent circuit in Figure 3.17 is a reasonable approximation. Here L is the locked-rotor inductance, which can be calculated from the severity of starting condition. R is the damping resistance which is derived from the motor losses. Induction motors are generally present as part of the load and in a group of different sizes. R R ‘‘ L R 1 L L 1 L ‘‘ Ld R 2 / 5(h) 1 (a) R d m 2 L L-- locked rotor inductance (a) (b) (b) FIGURE 3.16: Synchronous generator representation (a) Series combination (b) Parallel combination Fig. 3.17 23 3.5 Supply System Equivalent In supergrid studies there is a need for an equivalent of the transmission system as the representation of the whole network is not practicable. A simple inductance based on the fault level contribution has been used in the past, but its representation is clearly unsatisfactory. The factors influencing the equivalent impedance are discussed and a simple but more realistic model is adopted. The harmonic impedance of a transmission system is determined/affected by factors such as fault level, system loads, capacitance of lines and cables, compensations, etc. In general, an increase in fault level reduces the harmonic impedance at lower frequencies. However, the behavior for higher frequencies is unpredictable as small capacitance may have a dominant effect producing resonances. Measurements have shown that in some cases the minimum impedance at the higher frequencies occurred at the minimum fault level. The net effect of increasing the load is to reduce the impedance to both fundamental and harmonic frequencies. The combined effect of increasing generation and load is to reduce system resonances by increasing system inductive elements and increasing the damping by lower resistance paths to ground. The effect of the line capacitance is to reduce the harmonic impedance for higher frequencies. However, the combined effect with inductances may cause parallel resonances and, thus, having the opposite effect. 24 There is no typical equivalent that can be used in any system without question, but measurements have shown similar characteristics in the harmonic impedance of a transmission system. A general point is the prominence of the first two resonance frequencies, i.e. parallel (wp) and series (ws). This can be observed from Figures 3.18 and 3.19 Inspection of the impedance characteristic shows that a T circuit can be assumed as in Figure 3.20a. This produces an impedance as in figure 3.20b, which represents the system impedance more accurately than the fault level inductance when the necessary data are available. There are reasons to believe that the inductive part is inversely proportional to the fault level contribution. That is:L = L1 + L2 = (nominal voltage in kV)2 (fault level in MVA). 2.pi.f. The line capacitance is responsible for the capacitance C in the circuit of Figure 3.20a. Thus, the impedance is given by: Z(w)=wL1 -[wL2.(1/wC)]/[wL2 -(1/wC)]= =wL1 - [wL2/(w2L2 C-1)] (1) In order to give more flexibility to the model, the parameters L1, L2, and C. as a function of wp and ws can be assessed. That is because the transmission lines determine fundamentally the behavior of the a.c. network and thus wp and ws could be estimated from the knowledge of the lines, which would better approximate the system impedance. 25 FIG. 3.18: Harmonic impedance of 132kV system FIG. 3.19: Harmonic impedance of 132kV cable system without local generation, minimum plant condition 26 FIG. 3.20:Transmission system equivalent model 27 L - fault level inductance - p, s - frequencies of resonance Equation (3.1) above is a second-order equation. Therefore, considering the two frequencies where the parallel and series resonances occur, the equations can be solved in terms of L1, L2, and C. 1. Z(wp) = infinite, therefore wp2L2C=1 C = 1/wpL2 = 1/wp2(L-L1) 2. Z(wS) = 0, therefore wSL1 = wSL2/(wS2L2C-1) L1 = L2/(w22L2C-1), wS2L2C = 1+L2/L1 = L/L1 C = (L/L1)×(1/wS2L2) Comparing C from (1) and (2), it will result:L1 = L(wp/ws)2 , and the equivalent circuit is completely determined . Resistances in series with the inductances can be incorporated to provide a damping component to attenuate resonance peak. In order to illustrate the accuracy of the model, the measured impedances of Figures 3.18 and 3.19 are reconstructed in Figures 3.21 and 3.22, respectively. 28 FIG. 3.21 Calculated harmonic impedance 132kV system corresponding to measurements of Figure 3.23 FIG. 3.22: Calculated harmonic impedance 132 kV system corresponding to measurements of Figure 3.24 29 Distribution System Example A simple, but typical 11 kV distribution system, was modeled, as shown in Figure 3.23. In the diagram the consumer has a connected load of 865 kVA at a power factor of 0.8 lagging and a power factor correction capacitor of 250 kVA. The consumer wishes to connect an adjustable speed drive using a 6-pulse converter at the 11kV busbar. The system fault level at the busbar, including the transformer, is 30MVA and the source impedance may be considered as purely inductive. The maximum harmonic currents (5th, 7th, 11th, and 13th) injected are specified and typical for 6 pulse drives. Figure 3.23 - System Schematic Diagram 30 In order to illustrate the influence of the load modeling in harmonic studies, Figures 3.24 to 3.26 show the equivalent harmonic impedance viewed from the 11 kV bus using different load models. The dominant parallel resonance harmonic frequency is estimated commonly by: h MVA sc MVAr cap which can be derived by finding the unity power-factor frequency of the system. This calculation assuming no load indicates that the resonance frequency is around 10.95 times the fundamental frequency. At the resonance frequency, the impedance of the 11 kV bus becomes very large as it can be seen on Figure 3.24, when load model 1 is used. Thus, significant voltage distortion may result at the 11th harmonic. The high harmonic voltages will also result in high harmonic currents both in the capacitor bank and the system reactance. A more detailed analysis, however, reveals that the resonance frequency varies with the resistance of the system, and the amplitude of equivalent harmonic impedance or the output voltage is not necessarily maximum at the resonant frequency, and is also a function of the damping (resistance) of the circuit. However, since current is only injected at the 11th harmonic, one does not need to consider other frequencies, but rather remember the sensitivity of the system harmonic impedance (around the resonance frequencies) to parameters variations. 31 Figure 3.24 - Equivalent 11 kV Frequency Response Impedance - Load Represented by Series Model 1 Figure 3.25 - Equivalent 11 kV Frequency Response Impedance - Load Represented by Parallel Model 2 Figure 3.26 - Equivalent 11 kV Frequency Response Impedance - Load Represented by EdF/CIGRE Model 7 32 When the harmonic currents are injected, it can be observed that at the 11th harmonic the resultant voltage obtained with a parallel representation(model 2) is 66 V or 1.04%, whereas with the series representation (model 1), the 11th harmonic voltage on the 11kV bus was 332 V or 3.23%. Thus, near the resonance parallel frequency, the impact of the load representation can be very significant. Using an alternative series/parallel load representation (EdF model 7), the frequency response of the equivalent impedance is shown below in Figure 3.26. Two important facts can be noted. First the resultant voltage on the 11kV bus was now 48 V or 0.69%. Second the resonant frequency shifted slightly higher (from 11th harmonic to near the 13th harmonic). Table 2 shows a summary of the cases simulated where the model and load and composition were varied. Table 2 - Load Modeling and Conditions Simulated Case Linear Load Model Case 1 No Load Representation Case 2 P, Q - Basic Load Flow Case 3 P, Q - Basic Load Flow Case 4 50% Induction Motor Case 5 25 % Induction Motor Case 6 50% Induction Motor Case 7 75% Induction Motor Case 8 90% Induction Motor Case 9 25% Ind. Motor + Skin Effect Case 10 75% Ind. Motor + Skin Effect 33 Skin effect was included in cases 9 and 10 to account for the impact on the system impedance of the frequency dependence of the resistive component of the load. Figure 3.28 illustrates the amplitude of the 5th and 11th harmonic voltage (%) at the 11 kV bus for all models used. Figure 3.29 demonstrates more clearly how much the resultant voltage can vary depending on the model and load composition used. When comparing to standards such as the IEEE 519, it becomes clear that the violation of the standard may depend on the load model used for the calculation of the resultant distortion. Modeling loads using just the economic model (P and Q only) is inadequate for harmonic studies. No load (case 1) representation should not be used for harmonic studies. The load models suggested in the literature can not be used indiscriminately without a comprehensive check of the actual load characteristics and composition. The appropriate representation is particularly crucial near the parallel resonant frequencies of the system, exactly where an accurate estimation of the system behavior is most necessary. Frequency response of the system impedance is sensitive to both the methodology (modeling/topology) and the actual load composition. A comprehensive list of linear load models for harmonic studies found in the literature is illustrated in Annex 1 34 Figure 3.28- Harmonic Voltage (%) for Different Load Model 100 V5 (% ) V1 1 (% ) 10 1 C a se 1 C a se C a se 2 3 C a se C a se 4 5 C a se C a se 6 C a se 7 8 0 .1 C a se 9 C a se 10 V 5 (% ) V 1 1 (% ) 4 3.5 3 V5 (%) V11(%) 2.5 2 1.5 1 Case 3 Case 4 Case 5 Case 6 Case Case 7 8 0.5 Figure 3.29- Harmonic Voltage (%) at the 11kV Bus for Different Load Models 0 Case 9 Case 10 V11(%) V5 (%) 35 The Need for a Complete Load Representation General loads in a transmission or distribution system are generally expressed by their active and reactive power P and Q, respectively, which are used to calculate the equivalent impedance for load flow studies at the fundamental frequency, assuming the system voltage. However, at harmonic frequencies, P and Q cannot be used directly because, for example, the power absorbed by rotating machines does not exactly correspond to a damping value, Fig. 3.30 neither does the motor equivalent inductance bear any direct or simple relationship to the reactive power estimated at the fundamental frequency. In addition a measurable percentage of any general load nowadays is electronically controlled and needs to be properly represented. Electronic loads are harmonic producing and consequently do not exhibit a constant R, L or C. Therefore, they cannot be included as part of the passive component of the equivalent impedance. They should be represented by a harmonic source at all frequencies of importance. With the proliferation of the utilization of power electronics, a progressive conversion of traditionally linear loads to electronically controlled will happen. Another component normally overlooked in harmonic studies is the Power Factor Correction capacitance of distribution systems. Measurements have shown that there is a strong correlation of the effect of power factor connection capacitance on the harmonic impedance of distribution systems. The PFC MVAr could be up to half of the MW numerically, depending on the local PFC policy and system conditions. Therefore, the proposed model shown in Figure 3.30 makes an attempt to incorporate all these aspects in the modeling general loads for harmonic studies, and consequently make the so called general, normal or "linear" load representation for harmonic studies much more realistic. Detailed research should be carried out to assess the actual load composition and determine the proper representation and parameters of each load or aggregate of loads. The equivalent impedance should consist of a combination of series and parallel combination of resistances, inductances, capacitances, and harmonic current source as indicated in Figure 3.30. 36 Since the reactive power of the load estimated at the fundamental frequency has little to do with the equivalent impedance of the load at harmonic frequencies, it is suggested that Q (estimated for the load without any PFC) should be totally disregarded for the estimation of the equivalent harmonic impedance of the load. Thus, starting with the total active power P and additional information about the load composition, the following procedure is suggested for calculating parameters for harmonic studies. V = System Voltage XL1 = Transformer Reactance C1 = Estimated Capacitance of the Load I1 = Estimated Harmonic Current Source where P = Total Active Power K = Fraction of Induction Motors KE = Fraction of Electronic Loads R1 = Equivalent resistance representing the purely resistive component of the load factor for skin effect correction XL2 = Equivalent inductance representing the induction motors R2 = Damping factor for the induction motor representation K1 = Severity of Starting Condition Km = Installed Motor Factor K2 = Fraction of the locked-rotor (or negative sequence) inductance h = Harmonic order XL1 = Leakage inductance of transformers at lower voltages connecting the resistive load I1 = Ideal harmonic current source (use typical values according to type of load feeder). 37 The resistance R1 is estimated from the actual resistive load connected to the bus, that is, discounting the induction motor and electronic load part. The skin effect can be incorporated in the equivalent resistance by choosing an appropriate factor as indicated. The inductance of the induction motors should be evaluated using an estimation of the fraction of the total load that represents induction motors and their installed unitary power (not the demand). Also a factor K1 representing the severity of the starting condition should be used to calculate the equivalent inductance. R2 represents the damping component of the equivalent induction motor impedance. Also background distortion should not be neglected. Harmonic simulation studies will have to include background distortion if they are to be become more accurate. Background distortion can increase or decrease the resultant distortion depending on phase relationship. A harmonic current or voltage source representing the harmonic contribution of the non-linear component of the load must be modeled. 38 Conclusions This document demonstrates that the representation of the power system loads and extended networks can be improved by using alternative models. The distribution system, loads, other elements and equivalents of extended networks have been considered in detail. The models developed allow a more realistic representation of the system and, consequently, a more accurate assessment of the harmonic currents and voltages throughout the transmission network. Guidance has been provided on modeling of individual loads and on typical load composition. System tests are necessary to provide verification of the modeling methodology developed, as well as adding to the knowledge of system load characteristics. This paper demonstrates that the representation of linear elements is very important for harmonic studies and should not be neglected or represented without full consideration of the load characteristics and composition. Guidance has been provided on modeling of individual loads and on typical load composition. System tests are necessary to provide verification of the modeling methodology developed, as well as adding to the knowledge of system load characteristics. Consequences regarding system predictions: Wrong indication of excessive high harmonic distortion. And don't be fooled: utilization of sophisticated harmonic penetration programs with inaccurate basic information, and or inadequate modeling is a waste of money, and the consequences of the interpretation of the results might cost even more. Remember: that the accuracy of any calculation cannot be better than the data on which it is based. 39 Model 4 Parallel Combination Model Description Model 1 Series Combination (Common Practice) From P and Q Model 2 Parallel Combination 1 (Common Practice) From P and Q plus skin effect Model 3 Parallel Combination 2 From Pand fraction of induction motors Equivalent Circuit From P and fraction of motors Model 5 Series/Parallel Combination 1 (CIGRE/EdF Model) Model 6 Series/Parallel Combination 2 Error! Bookmark not defined. Model 7 Series/Parallel Combination 2 From P, inductance of distributioon transformers and induction motors 40