MODULERA Modular UPS Systems 60 / 100 / 200kVA 3Phase in / 3Phase out Main Features Hot Swappable Modularized Parallel Architecture Decentralized parallel structure DSP ( Digital Signal Processor ) Controlled Technology Modular N+X Parallel Redundancy Parallel Operation up to 10 Power Modules High Power Capacity up to 200kVA on per single Rack Invest as You Grow , Easy to Upgrade Common Battery Operation Cold Start Function Parallel connection availability of UPS Frames up to 4pcs Main Features Low Input Current Distortion (THDi <3% ) 10.0 9.0 8.0 THDI(%) 7.0 6.0 R 5.0 S T 4.0 3.0 2.0 1.0 0.0 25% 50% 75% LOAD(%) 100% Main Features High Input Power Factor ( p.f. = 0.99 ) 1.000 0.995 0.990 PF R S T 0.985 0.980 0.975 25% 50% 75% LOAD(%) 100% Main Features High Efficiency ( up to 94% ) Efficiency η 96.0 95.0 Efficiencyη(%) 94.0 93.0 η 92.0 91.0 90.0 89.0 25% 50% 75% LOAD(%) 100% Main Features High Output Power Factor ( p.f.= 0.9) Wide input voltage 208V~478Vac Wide input frequency range ( 40Hz – 70Hz ) Plug & Play Type Hot Swappable Power Modules Each Power module with individual LCD display Touch-screen Graphical LCD Display Panel Centralized module monitoring is also available Smart Fan Speed Control Fan spins according to load percentage ; 50%: Spin slowly / over 50%: Spin at full Speed Main Features High MTBF ( 250.000 hours ) and Low MTTR Battery Temperature Compensation Powerful Charger Built in Module ( Max. 6Amp ) Equip with Maintenance Bypass Switch for easy maintenance RS232 & 485 Ports as standard communication Remote EPO Function Megatec/Mod Bus Protocol Optional Communication Interfaces (SNMP or DRY contact) MODULERA FRAME TYPES MDL 3300-60K MDL 3300-100K 60kVA & 100kVA MDL 3300-200K 200kVA MODULERA FRAME TYPES MDL 3300-60K = 3+1 Modules ( 3modules for power upgrade + 1module for redundancy MDL 3300-100K = 5Modules MDL 3300-200K = 10Modules Max. 4Frames can be connected in parallel MODULERA POWER MODULE MDL3320-RM 3/3 Power Module 20KVA/18KW Module Compact Size Only 3U Height 3U Only Plug-and-Play Hot Swappable Module Safe Swappable Modular Concept Reduce SPOF(Single Points of Failure) Power Availability Increase High Power Capacity Reduced Footprint Flexibility/Scalability Less Service Cost Lowest Installation Cost Battery Temperature Compensation Set from LCD Display Compensate from 20 C: Reduce 0.001V*6 of floating voltage per 1°C. 0.002~0.006V * 6 per 1°C settable Battery Voltage Configurable 384/408/432/456/480Vdc Configurable Decrease Initial Investment Increase Competition Derating Operation Derating as per Temperature : Normal operation Temperature 0~40 C Max. operation Temperature 50 C De-rating operation: 10% per 5 C Derating as per Altitude : Max. Altitude for normal operation : 1500m The load capacity should be reduced as shown in the below table when the UPS is installed in a place where altitude is higher than 1500 m; Altitude (m) Load coefficient 1500 2000 2500 3000 3500 4000 4500 5000 100% 95% 90% 85% 80% 75% 70% 65% Powerful Charger Each Power Module: 6Amp 60K: Max. 18A 100K: Max. 30A 200K: Max. 60A Charging Current adjustable from LCD 3-Stage Intelligent Charging Modes Constant Current Constant Voltage Floating (Boost Charge 2.30V to 2.35V per cell & Float Charge 2.20V to 2.29V per cell) Power Module LCD Display Input Voltage/Frequency Output Voltage/Frequency Load Capacity, Battery Voltage/Current Charge Modes/Charger Status Internal/Ambient Temperature Module ID/Status Alarm Codes Touch-Screen Graphical LCD Display Panel Touch-Screen Graphical LCD Display Panel Complete status information about ; ONLINE 30KVA ID:01 ◄ Input / Output / Battery /Modules ◄ Output 22-12-2008 08:30 Module Phase Voltage(v) Phase Current(A) Frequency(HZ) Active Power(kw) Apparent Power(KVA) Load percent(%) Load crest factor Input A 220 1 50 0.0 0.0 0 0.0 Batt Output Module Mains Phase Voltage(V) Phase Current(A) Frequency(HZ) Power Factor Bypass Phase Voltage(V) Frequency(HZ) ONLINE 30KVA ID:01 22-12-2008 08:30 Input Batt A 380 220 50 0.97 220 50 ► State B C 380 380 220 220 0.97 0.97 220 220 ► State ONLINE 30KVA ID:01 ◄ ONLINE 30KVA ID:01 ◄ Output 22-12-2008 08:30 Module Module01 Invert Voltage(V) Invert Current(A) Frequency(HZ) Positive Bus Voltage(V) Negative Bus Voltage(V) Code 8000-8000 0000-0000 Input A 380 220 Batt ► State B C 380 380 220 220 50 400 400 D800-8000 0000-0000 Back Output 22-12-2008 08:30 Module Input Positive Battery Voltage (V) Negative Battery Voltage (V) Positive Battery Current (A) Negative Battery Current (A) Battery State Battery Temperature (℃) Lasting(min) Batt State 240.0 240.0 10.0 10.0 Charge 28 90 ► Touch-Screen Graphical LCD Display Panel UPS Management Commands; ONLINE 30KVA ID:01 ◄ 22-12-2008 08:30 Command Battery Test Buzzer Set Default Set Setting Record Version Battery Test ► Buzzer Set Mute ONLINE 30KVA ID:01 ◄ Default Set 22-12-2008 08:30 Command Language Change Password Date Setting Back-light Delay Contrast Self-Test Date Setting Record Self-Test Date Mode: Weekly Week: SAT Time: 18:36 Lasting: 60min Version ► ▲ ONLINE ▼ Back Ensure Cancel Next 30KVA ID:01 ◄ Command 22-12-2008 08:30 Setting Record Version ► Work Mode Single LBS Group Setting Ma System Voltage Level 220 LBS Group Setting System Frequence Level 50 Auto Turn-on En ▼Master▲ Bypass Frequence Range 2 Ensure Cancel Bypass Volt. Upper Limit 1 Back Bypass Volt. Lower Limit -30 Output crest factor 0% Next Touch-Screen Graphical LCD Display Panel Settings; ONLINE 30KVA ID:01 ◄ 22-12-2008 08:30 Command Setting Language Change Password Date Setting Back-Light Delay Contrast Self-Test Date Record Version ◄ ONLINE 30KVA 2008 ID:01 08:30 ◄ Command System Parameters 2008-12-22 08:30:00 10Min 20 STA 18:36 FOR:60min Back ON:MON 08:48 OFF:SUN 17:25 Next 30KVA ID:01 Timing of ON/OFF Language ► Working Modes ONLINE 22-12-2008 08:30 Command Setting Work Mode LBS Group Setting System Voltage Level System Frequency Level Auto Turn-on Bypass Frequency Range Bypass Volt. Upper Limit Bypass Volt. Lower Limit O/P Volt Micro tuning 22-12- Record Version Single Master 220V 50HZ Enable 2% 10% Back -30% 0% Next ► Parallel ID Battery Voltage/Capacity ONLINE 30KVA ID:01 ◄ Setting Single Battery Volt. Battery Number Battery Group Single Battery Capa. Boost Upper Limit Volt. Float Base Volt. Battery Protect Volt. Boost Charge Boost Last Time Max Charge Current Record 12V 20 1 100AH 2.31 2.25 1.70 Enable 231 Min 25A Version Back Next ► 22-12-2008 08:30 Command Parallel ID M/S hot standby Cyc. UPS Output Pre-Alarm Time Float Volt Revise Parallel Amount Parallel Redundancy Setting Record ► Version 01 6 Mon Enable 14 Min 0.001 04 01 Back Next Touch-Screen Graphical LCD Display Panel Record All Events/Alarm Message; ONLINE 30KVA ID:01 ◄ 0001 0002 0003 0004 0005 0006 22-12-2008 08:30 Command 12-21 12-21 12-21 12-21 12-21 12-21 15:00:26 15:00:25 15:00:10 15:00:08 15:00:05 15:00:00 Setting Record ► Version Display Up to 49 events On Line Rectifier Active.. Int.Input Switc.. Int.Bypass Swit.. Int.Output Swit.. Ext. Output Swit.. 50 alarm messages Back Next ONLINE 30KVA 2008 22-12- ID:01 08:30 ◄ Command Setting Record ID:00 Record:0001 2008-12-21 15:00:25 Status:On Line Event: On Line Alarm: CODE: CC00-0000 DF00-0000 0000 0000-0000 0000-0000 Quit ► Version ▲ ▼ Touch-Screen Graphical LCD Display Panel Charge Current Setting : ONLINE 30KVA ID:01 ◄ 22-12-2008 08:30 Command Single Battery Volt. Battery Number Battery Group Single Battery Capa. Boost Upper Limit Volt. Float Base Volt. Battery Protect Volt. Boost Charge Boost Last Time Max Charge Current Setting 12V 20 1 100AH 2.31 2.25 1.70 Enable 231 Min 25A Record Back Next Version Max Charge Current ▼ 25 ▲ Ensure Cancel ► Touch-Screen Graphical LCD Display Panel Battery Qty & Capacity Setting : ONLINE 30KVA 22-12-2008 ID:01 ◄ 08:30 Battery Number Record Setting Command Single Battery Volt. ▼ 20 Battery Number Battery Group Ensure Single Battery Capa. Boost Upper Limit Volt. Float Base Volt. Battery Protect Volt. Boost Charge Boost Last Time Max Charge Current ONLINE 30KVA ID:01 ◄ Command Setting Record 30KVA ◄ 9 4 5 6 1 2 3 . 0 08:30 Command Setting Record Version Single Battery Volt. Battery Group 12V Back Battery Number 20 Battery Group 1 Next ▼ 1 ▲ 100AH Single Battery Capa. Boost Upper Limit Volt. Ensure Cancel 2.31 Float Base Volt. 2.25 Battery Protect Volt. 1.70 Boost Charge Enable Back 22-12-2008Boost Last Time 231 Min 08:30Max Charge Current 25A Next Version ► 1000 8 22-12-2008 ID:01 Single Battery Capa. 7 ► ONLINE ▲ 12V 20 1 Cancel 100AH 2.31 2.25 1.70 Enable 231 Min 25A Version Can cel ← → Ens ure ► Single Line Diagram Multi-Communication Interfaces 2 x RS485 Ports 1 x RS232 Port 1 x Mod Bus Port 2 x Communication Slots Communication Interface Options SNMP Card Megatec Protocol Supported Communication Interface Options Dry Contact Board Pin Function 1 Utility Failure 2 / 3 Battery Low 4 On bypass O/P 5 UPS Fault 6 Inverter On 7 UPS Alarm 8 Common 9 +12V I/P 10 0V Fuses & Breakers MDL 3300-60K MDL3300-100K MDL3300-200K Input Breaker ( present on each power module as built in ) 3P 40Amp 230/400VAC 3P 40Amp 230/400VAC 3P 40Amp 230/400VAC Output Breaker ( present on the frame ) 3P 125Amp 380/400/415VAC 3P 250Amp 380/400/415VAC 3P 400Amp 380/400/415VAC By-Pass Breaker ( present on the frame ) 4P 125Amp 380/400/415VAC 4P 225Amp 380/400/415VAC 4P 400Amp 380/400/415VAC Batteries Breaker ( present on the frame ) 3P 175Amp 250VDC/415VAC 3P 250Amp 250VDC/415VAC 3P 600Amp 250VDC/415VAC Mission critical & industrial applications Operator Centres, Servers, Computer rooms, Telecom Switchgear & Infrastructures, Processing Control Equipments, Security Systems, Emergency Lighting, Fire Protection, Airport Infrastructure, Bank, Hospital, Healthcare Equipment …