Troubleshooting refrigeration systems ► 1 The design of industrial refrigeration systems is in theory straightforward. In practice, poorly tuned or malfunctioning components, fouling especially by oil, inert gas in the system, misplaced pipe lines, etc., can lead to capacity loss, control problems, frequent shut downs and other difficult to find and explain phenomena. This is typical for large custom made plants. Manufacturers of small standard units such as air conditioning OEMs, can usually iron out the problems before a chiller line goes into production. An industrial contractor usually does not have this luxury; the plant has to work immediately. General rules are hard to give as all systems are different and the troubleshooter has to be a bit of a detective. Below is an arbitrarily classification of possible malfunctions: ► Mechanical failures such as worn-out pumps, broken valves or compressor slides, i.e. all types of malfunctioning in machines (by definition, a machine has moving parts). ► Leakages in various components (a special case will be treated below). ► Construction errors such as faulty welds , components not made as conceived, wrong components, e.g. a solenoid valve closing instead of opening, a far too small valve, compressor, pipe, etc. General considerations, I. ◄ ► 2 ► Fouling, corrosion and fatigue. ► Electrical, i.e. all parts of the electrical power circuit. ► Control, e.g. outright failures or wrong control algorithms. ► Faulty refrigerant, oil, brine or brine of wrong concentration. ► The above items are usually but not always clear-cut and the source of the trouble can usually be found and will not be treated here. However, sometimes more difficult to find troubles arise. The source can be any of the malfunctions above or simply that each component is faultless but together they do no work. ► The operator of the refrigeration plant has three interfaces to the system: the electrical power consumption, the condenser and the evaporator. We will deal here with troubleshooting the two latter, especially plate heat exchangers. ► The condenser pressure is too high, alternatively it increases and finally, the compressor HP cut out activates. ► The refrigeration system does not give the required capacity at specified conditions. “The evaporator is too small” is a frequent complaint. General considerations, II. ◄ ► 3 The pressure is too high but remains stable but sometimes the pressure continues to increase until the compressor HP cut-out is activated. Below are some frequent causes. ► Fouling on the water side, less frequent on the refrigerant side. ► A condenser which is too small, either by area, heat transfer coefficient or temperature difference. ► Higher load than foreseen. Double check with evaporator & oil cooler load and compressor load. Sometimes, the load of a refrigerant cooled oil cooler, which ultimately has to be removed by the condenser, is forgotten. ► A flooded condenser. A condenser can flood for four reasons: Pressure drop is too high in one of the parallel connected condensers, a misplaced equalization line, an obstruction at the exit or a refrigerant overcharge. ► Inerts in the vapour. ► Subcooling in the condenser. To be effective, there has to be a liquid level in the condenser but then the condensing area is decreased. The most serious consideration is that inerts can get trapped in the condenser. ► Obstruction of the exit. This usually less of a problem. As the condensate will flash to a pretty low temperature, the condenser could support a very large pressure drop. The drawback is that it might flash in the pipes before the expansion valve. Flashing refrigerant should be discovered by a sight glass, which always should be installed in the liquid line just before the expansion valve. Troubleshooting condensers ◄ ► 4 An evaporator that doesn’t give the required capacity is sometimes a complaint from operators of refrigeration plants. The designer of the evaporator then patiently has to explain that an evaporator is a passive component, which can only give capacity presumed there is capacity, i.e. a sufficient refrigerant flow, on the other side. Below are some effects, which can lower the evaporation temperature, the most frequent claim: ► What happens if the evaporator really is too small? Too small in this respect is that either the area or the K-value is too small. The evaporator then produces less vapour than the compressor can handle. The pressure falls, which increases the vapour volume, the evaporator produces more vapour because of the higher MTD, the capacity of compressor decreases and finally the system stabilizes at a lower evaporation temperature. ► What happens if there is not enough refrigerant entering the evaporator. As before, the flow is less than the compressor can handle, the temperature decreases and the MTD increases but this has no effect on the capacity and there is not sufficient refrigerant. The evaporator has to be in balance and it solves the MTD equation by superheating the vapour, effectively decreasing the MTD again. This is valid for a DX evaporator. A flooded flow evaporator is connected to a fairly large refrigerant charge and this can provide sufficient refrigerant to even out a temporarily refrigerant shortage but if this persists, the charge is consumed and the same occurs. ► A superheated refrigerant is a sure sign that an evaporator is operating below its possible capacity. Troubleshooting evaporators, I. ◄ ► 5 ► Oil in an ammonia system can foul an evaporator and has to be drained regularly. ► If water is present, oil will form a slurry, which fouls the evaporator. ► Water in ammonia will increase the evaporation temperature for a given pressure, thus decrease the capacity. By pumping down the system to a low temperature, most of the water remains as a liquid phase and can be drained from the system ► A separator placed too high. When the two-phase mixture enters the separator it is at the boiling point. When the refrigerant then descends to the evaporator, the pressure increases and the refrigerant is now subcooled. ► The K-value in the subcooling section is low. ► The refrigerant is preheated above the nominal evaporation temperatureand the MTD decreases. ► The return leg is likely to be long and high, giving a high pressure drop and thus a large temperature difference between evaporator and separator. ► All this contributes to decrease the capacity of the evaporator. This is especially important at low temperatures. With a liquid column of 10 meters, the subcooling of ammonia is about 3.9 K for an evaporation temperature of 0 °C. For an evaporation temperature of -40 °C, the subcooling increases to 17.6 K. That means that the evaporator will probably not work at all, the pressure at the evaporator is simply to large for the evaporation to take place. ► A far too low liquid level in a flooded flow system might not be able to lift the flow through the return leg. The result is low circulation and low capacity. ► Demisters, vapour superheaters and filters in the suction line obstruct the refrigerant flow and increases the difference between the evaporator and suction temperatures. Troubleshooting evaporators, II. ◄ ► 6 ► A too small pipe diameter or a too long pipe, valves, many bends and other obstructions in the return leg in a flooded system cause the exit pressure drop to increase and the result might be a large difference between the evaporator and separator pressures. As above, the effect increases with decreasing temperature. ► The difference between the evaporator and separator pressures is frequently a subject of contention between the evaporator and the system designer. ► Pumped flow in flooded system allows a designer a lot of options, which he maybe shouldn’t use, e.g. a too highly placed separator. That means a long subcooling zone and a high pressure drop in the return leg. ► Sometimes an ejector pump, driven by the flashing refrigerant, is inserted in the thermosiphon loop in order to improve the circulation. In order to do so, it has to be properly designed, something which is not always done. An ejector is unfortunately also a good oil atomizer and the oil can enter the channels and foul the surface. ► Distribution of the refrigerant and of high viscosity brines between parallel channels is a difficult problem especially for DX evaporator, somewhat less for flooded flow evaporators. ► Both the above problems can be revealed as unequal temperature distribution on the outside of the evaporator. A thermal camera or the formation of frost on the evaporator is a good help. ► Frost formation at start up of an evaporator is an excellent way of discovering distribution problems. Troubleshooting evaporators, III. ◄ ► 7 ► Distribution problem can also happen for water at high temperatures if the flow and thus the pressure drop is very low, more so in DX than in thermosiphons. Use multiple passes on the water side to increase the ΔP. ► Maldistribution can also cause freezing as the water cools unevenly, a problem in DX more than in flooded. ► A TEV before a DX evaporator has to be correctly placed. Unfortunately, a lot of valves give a well separated two-phase mixture and some evaporators are very sensitive to this. Don’t install bends after the TEV. ► There are some questionable control algorithms for some electronic EVs. One such, if not correctly adjusted, increases the superheat when the capacity increases. That means that the evaporation temperature has to be lower than necessary just to accommodate a too high superheat. ► The rated capacity for a TEV is usually given for around 11 K. If the evaporator superheat is 5 K, there is no possibility for the valve to give its rated capacity. Choose a larger valve. Troubleshooting evaporators, IV. ◄ ► 8 Propane condenser Propane to Propane tank trucks Propane from tanker Comments: Discussion: Solution: The A condenser further results check ofwas the showed not propane designed that analysis ita was for an not are inert installed interesting. gas condensation. in aAs refrigeration theNo inert Even as content Problem:The The compressors cut out after very short operating time. particular system small is veryquantities low, but used itwas means offor ancondensing, that inert the gas propane increase after content compression, the size is close of the ofto propane condenser 100 %. vapour Moreover, considerably. fromit awas tank It it information given about the process it was going to operate in. Consequently farm had calibrated when replaced for adesigned tanker butane. with unloaded Analyzing propane. a concentration larger Whenin condenser. the tank to fills 100 up,%vapour with anleaves. uncalibrated wasto it be was asaaconsiderably normal condenser aclose refrigeration system. An inspection at However, analyzer could whengive the storage large particular errors. tank It unloads, is– not possible it has tobeget charged a reading withcloser nitrogen thantoa couple the site showed nothing except the to compressor cut-out. An analysis of the of keep percent thepoints.100 pressure above % propane atmospheric, means no otherwise inerts, 99 air% might means leak 1% in andtoan that explosion increases the propane content was made with a butane analyzer and recalculated propane. could occur.size condenser Theconsiderably. propane recovery It would system have thus beenhas better to be to designed have a nitrogen not foranalyzer pure as propane the difference but forisalarge propane-nitrogen between 0 and mixture. 1 %. Fig. 1. Inert gas in a propane vapour. ◄ ► 9 Discussion: inspection of Problem: Ammonia Solution: TheAncondenser is easy could tothe vent. system showed nothing particular. operate A vent was for only placed one onofthe theLR two and The condenser be wellof compressors. the vapour was seemed fed into atobucket drained to Ifthe LR.isIt air hadinrecently ice water. there ammonia, been opened, inspected and found itOnce bubbles, the pure ammonia started, the doesn’t presclean. No second physical obstruction was sure bubble. and cut out the foundincreased in the adjacent pipes. compressors. However, a reading of the inlet After half an hour bubbling, the water and the exit condensate manometer calmed down and temperature showed practically the became steady after four more same temperature. hours venting. It was then possible The cause the could be with either of two to operate plant both the or possibilities, a flooded condenser compressors. inerts in the vapour, but it is difficult to determine which. Comments: An undampened The compressor manometers gave manometer is a valuable tool for a hint.checks, There were three with difficult inerts especially undampened manometers of the to ventdesign, halocarbons. same oil, suction and discharge. The oil was rock steady, the suction vibrated a little, while the discharge needle was almost impossible to see. A vibrating discharge manometer hints of inerts. Fig. 2. Compressor cut-out. ◄ ► 10 Discussion: The condenser and its Problem: Solution: The The capacity separator ofwas neither lowered theexit to theboth LR the – nor normally a critical point evaporator and evaporator the condenser and condenser was – were correctly made. Venting was sufficient problemsfrom indisappeared this flooded possible the LR butevaporator no inerts were system. Both had recently been opened, present. inspected Comments: andPlacement cleaned. of the expan-sion However, the separator placed can very valve and LR above thewas condenser high up, some ten meters and the evaThe condenser shown here, exhibited be done but the risk for malfunc-tioning poration temperature was well below zero large capacity and pressure oscillations increases - especially ventingwith will the be Celcius. This led to problems and occasionally compressor cut-outs. evaporator, difficult - and see troubleshooting also Figure 10. will be more complicated. The expansion valve was placed close to the separator and connected to the LR by is thus not pipe. recommended, for aIt fairly large The heightneither difference to the condenser meant that there was a flooded nor for DX evaporators. very large danger of vapour flashing in the vertical pipe. When the valve closes, the condensate then flows back into the receiver – the large pipe makes it easy - and from this it floods the condenser. The system ammonia filling was pretty high, which compounded this problem. Fig. 3. A too high placed expansion valve. ◄ ► 11 A B1 C B2 B3 h h Discussion: ΔPwas is higher in the than in the S&THEs. Obviously, the ΔP Problem: This Solution: TheThe collector PHE pipe replacing was lowered a PHE corroded and S&THEs, the liquid column equal to isthe now two created others, in from the point A to C have to be same regardless if the path is A -B1(2)-C or A - B3 - C. vertical pipe outside thethe PHE. However, PHE didn’t give the the capacity. subcooled At the exitthe of the condensers, pressure A is substantially lower in B3 than in B1 &condensate B2. The indicated a flooded condenser. condensate lines form a communicating system with a lower pressure in one leg, B3. That causes a higher liquid column – h - to form in this leg. Unfortunately in this case, the condensate pipes connect just below the exits, the higher liquid column in B3 builds up in the plate channels, floods these and the effective area is decreased. Fig. 4. Parallel connected condensers. ◄ ► 12 Discussion: Problem: Solution: The system was equipped The plate condenser didn’t with give athe Reconnection of the equalization “surge” LR. rated A substantially line tocapacity. immediately before the PHE The condensate doesn’t pass a subcooled drained thecondensate condenser. indicated through, it is just in communication flooded condenser. to take up load variations. To Comments: facilitate this, it is to case the The difference to connected the previous condenser inlet via an equalization Misplaced equalization lines and is that here there is only onethis line. Vapour moves through in poorly conceived LRs are aconcommon condenser, parallel. & and out ofnot themany LR asin the densateofmoves in andtroubles. out. source condenser The vapour entering the condenser inlet from the LR should then recondense. As the pressure is higher at the condenser inlet than at the exit, it is necessary with a liquid column to compensate for this ΔP. The total ΔP in two parallel legs should be equal. In this case, the equalization line was connected upstream a desuperheater with a fairly large ΔP and the resulting liquid column became high and flooded the condenser. Fig. 5. A misplaced equalization line. ◄ ► 13 Underside of pipe Ambient temperature Equalization line To bulb The result was that baffling that attempt madeexpansion to pictures fromMoreover, the back side, Problem: A check ofThe the valve installation showed was that aan pretty there normal waswas a leakage direct in take the packing evaporator box. equipped the with where the bulb and the equalization line connection thesmall exit pipe could be seen. a standard equalization thermostatic connection expansion at the suction valve gas with pipeexternal was to very equalization, – high but ΔP. it simply Thus: didn’t produce any cooling at The start up showed theall. sequence At first was orange, i.e. ambient - HP condensate leaks through thebelow. packing box everything into the equalization chamber. temperature. Then: Discussion: A check with a thermal camera showed some interesting results. The first -- Exit Theofdiaphragm is pressed down and the valve closes. EQ line. The connection turning blue. pictures were taken from the frontwas sideslowly only as the back side was difficult to reach. -- Below No more refrigerant leaves the normal exit. part of the pipe below the connection connection. A little later, thetemperature” bottom The exit EQ pipe, above marked “Ambient was just that, i.e. no cooling was turned -discovered. Liquid blue. condensate flows through the EQ line to the connection, expands and cools. -Astonishingly Further downenough, the pipe. blue colour slowly spread downwards. Liquid cold refrigerant theThe drops pipe down marked to “Cold the pipe pipe bottom underside“ and cools several this.meters after the TEV, became blue on the picture somewhat after the start, indicating a low temperature. Solution: The TEV was exchanged and everything worked. The part just behind the PHE could not be seen. The equalization line was ambient temperature. A thermal camera is an extremely useful tool when troubleshooting. Comments: Fig. 6. A broken expansion valve. ◄ ► 14 Oil drain. A. Ejector inlet (NH3 in a SWPHE) B. Pipe-in-pipe inlet (R134a in a CB). Solution: Both Problem: Discussion: Injection were flooded redesigned offlow theevaporators flashing as normal refrigerant above thermosiphons. had in the injection circulation of flashing loop can refrigerant improve in the loop in order circulation if atoproperly increasedesigned the circulation. ejector None pumpof is them used.gave the intended capacity. A. The pipe was made slightly upwards inclining and with an oil drain at the lowest point. A. The The ejector low capacity in A waswas a home at least made partly design due toofoilquestionable fouling on thefunctionality. ammonia side. When A was B. A soluble oil does not need an oil drain. dismounted, it turned out that there was a lot of oil in the evaporator, not astonishingly as B. This CBishad stability problems and and occasionally reversed flow. an ejector a good atomizer. A closer inspection of B design showedcan thatimprove there was flow of drop Comments: An ejector the back operation butrefrigerant a correct through design isthe difficult leg back to the separator. The pipe-in-pipe design had no ejector function at all. It was to make. easier for the vapour to pass back through the drop leg than through the evaporator. Figure 7. Flooded flow evaporators with ejector. ◄ ► 15 To unit coolers Return from SWPHE To SWPHE ► Broken parts, forgotten tools, ► Mechanical. At the installation, there were probably bothorShortly ► ►after ItAisliquid not installation unconceivable line, passing to imagine a hot a area unit or Vertical Problem: the of athrough Solution: metal pieces can get trapped not lines liquid lines at the roof top and but vapour cooler exposed closing to the and sun, thecan resulting be sufficiently liquid column separator new PHE in evaporator – a flooded, forced flow The cause of bangs the noise found until unmovable and cause the noise. system the cold storage. inheated thewas vertical fornot refrigerant feeder pipe to vaporize line flow when down the or – loud and noises were heard year later, when refrigerant the openedthe flowsystem stops.towas Restarting evaporate, with flow ensuing will cause noise, a ina the system. Moreover, seevalve the figure above; there were a ► An expansion is sometimes, especially for maintenance. Asee broken valve vapour movehad with high speed along Slideplug 3. tostem number floodedpreceded flow unit coolers connected The source of noises in metal piping can be in DX systems, by a solenoid valve. moved to the first upwards after the the pipe. bend The vapour can easily pass a in pumpdown parallel to the liquid evaporator. These difficult to find but as the evaporator was the If is made, the pipe after the sole► However, the noise had metallic pumps. The liquid velocity then a definite valve but the was subsequent liquid column units coolers installedofatliquid least tennew meter only item was the prime suspect. noid valve willwere be emptied refrigerant. By using a at time insufficient to itlift itquality. further, it damages stayed thehonoured can’t, i.e. and noise. method – higher the thansolenoid the PHE. It is opens, difficult,a to say swirled the When valve liquid coputting ear to thelarge pipe at various locabend, and an made The evaporatoraround was installed in a noise. very ► If the pressure is suddenly e.g. least, with to operate parallel units in general andthe lumn increasing speed moves towards tions, it was possible to find increased, the place with commercial cold storage. a hot gas defrosting, canatcause a different types at different heights can be from TEV, which easily can be damaged apart the strongest noise. It itwas the upwards (previous) low pressure vapour to implode. close to impossible. the minor problem of noise. InstallDiscussion: the solenoidLoud, bend sharp noise from an itemcirculation after the ammonia pumps. is the same phenomena as cavitation. just before the TEV. with no moving partsThis is unlikely but then, where does the noise originate? ► In a vapour line, e.g. for hot gas defrost, pasThere are a couple of causes for noise shown sing through the cold storage, refrigerant can onAt the next page: condense when the line is shut off. restart, a SWPHE highPump speedstation liquid plug can damage a valve. Figure 8. Bangs in a pumped flow evaporator.. ◄ ► 16 Problem: A chiller manufacturer had problems with a custom made unit. The nominal temperature program was: 20 % Ethylene glycol +3 → Propane of -8 +(5) ← -3 °C -8 °C. The unit was assembled from parts purchased in some four different countries. At start-up the end temperature was about 10 K instead of the nominal 5 K Not surprisingly, all component manufacturers claimed that their particular component was faultless and worked well in similar applications. The technical manager was helpless. Discussion: During a technical seminar, the manager understood that the valve was not correctly installed; he remembered that the valve was possibly installed before a bend. Solution: The valve position was changed the same day and nominal duty was obtained. Figure 9. An incorrectly installed thermostatic expansion valve. ◄ ► 17 The final There was measured a strong suspicion was taken that six months the pressure later at Problem: This large ammonia thermosiphon the annual drop from the It turned exitdidn’t –out thethat evaporation the installation inoverhaul. a evaporator chemical plant give the angle capacity. valve was far via temperature, toothe small separator and was– ex-changed. the separatorThis There wasdecreased a problem with hunting. measure pressure –also to the compressor considerably suction the difference connection – between the suction thepressure evaporation - could and besuction very Discussion: An inspection of the plant large. showed a very temperatures. Unfortunately, a The refrigeration remaining vessel, difference as opposite was mainly to nice installation, everything – including the tightening due a chemical to the internals vessel, has of the no separator. man hole. The Inspection huntingof bolts of the PHE – properly insulated and clad by alsointerior the decreased. was not possible. aluminium sheets. The separatorWe Comments: was here placed encounter very high, threemuch of thehigher most Unfortunately there were hardly That any instruments or frequent than the evaporator problems inrequired. a flooded installation. increases the subcooling zone, especiallyhad at as lowonly temperatures, sight glasses, the separator ► Oil drain. Keep of the 25 °C, inthe thisinterior installation. instrumentation the pressure andseparator the ammoniaas level. It ► The difference betweenYou the evaporation simple as possible. never was really aTwo black box. Solution: measures were taken atknow site.andif ► suction temperatures. itfurther is built conceived. There was aas possibility to drain the oil from A inspection showed that there was no a ► A separator placed too high. connection closer todrain the evaporator than automatic oilmuch drain and the point was from thethe original oilrather drain. Draining reveal quite aevaporator. lot of oil in separator than from head just before the Conclusion: If the large is not necessary, the system. This improved the capacity The somewhat place the separator as low as possible. but not entirely. Discussion contractor revealeddescribed that the capacity ofwith the the evaporator in also the system separator was full of baffles, guide pipe temin slide 3 improved the separator was An try was made to when measure the vanes, evaporation distributors the gas,when protection sheets lowered. There are cases thethe evaporator perature. Itfor had toflash be done outside returnand leg.a needs large pressure drop butdue then, This is adifficult, especially here, to the the entire solid demister. thermosiphon has to be for this and not insulation. As aloop reference, thedesign separator temperaonly was the evaporator. ture also measured in the same way. The result confirmed the suspicion that the temperature difference was very large, i.e. the evaporation temperature was far above the suction temp. Figure 10. Lack of capacity in a low temperature evaporator. ◄ 18