JACT JACT, Inc. University Park, PA Project 2: STC & NC Design IM Building Addition Phase One University Park, PA Andrew Aumiller / Kevin Clement / Sebastian Jongerius / Goli Razaghi / Luke Thompson Group #5 JACT Index 1.0 Introduction ….………………………………………………………………………………………....... 2-3 2.0 Room Acoustics Background .………………………………………………………………………. 3-4 3.0 Background Noise Level Recommendations ..………………………………………………. 4-5 4.0 STC Analysis & Recommendations .……………………………………………………….…….. 7-14 4.1 STC of Original Partitions ..……………………………………………………….………… 7 4.2 Analysis of Original Partitions ..…………………………………………….……………. 8-10 4.3 Analysis of Moveable Partition …………………………………………….……………. 11-14 5.0 Summary ….……………………………………………………………………………….………………… 15 5.1 Report Highlights .………………………………………………………….………………….. 15 5.2 Recommendations …………………………………………………………………………….. 15 6.0 Appendix …………………………………………………………………………………………………….. 16 7.0 References…………………………………………………………………………………………………… 17 1 JACT 1. INTRODUCTION Located on the corner of University Drive and Bigler Road across from Beaver Stadium lies the Intramural Building, a facility used for recreational and educational purposes by faculty and staff at Penn State. This is outlined in the buildings mission statement which explains, “We strive to satisfy all Penn State students, faculty and staff with the friendliest service and the most diverse selection of sports activities, all in one location [5].” The IM Building is home to a number of different types of spaces which require certain acoustical characteristics specific to each task being done in each space. When conducting an acoustical analysis of the spaces within the Intramural Building Addition in terms of sound isolation and background noise, it is important to identify which spaces are likely to generate a lot of noise and which spaces require low background noise levels requiring high amounts of isolation. For example, the mechanical rooms (M004 and M202) are likely to generate a lot of noise due to the acoustical nature of HVAC equipment and increased structure-borne noise from massive vibrating machines within these rooms. Other rooms that are likely to generate a lot of noise include the fitness areas (103 and 203) as well as the multipurpose rooms (007, 124, 125) due to the amount of people that occupy these spaces at one time as well as the structure-borne noise generated from workout equipment hitting the floor. Multipurpose room 007 will be especially noisy since it will be used for group fitness classes that use amplified music causing a prevalent amount of airborne noise. Rooms that require low background noise levels include classroom 008 in the basement, all the offices on the first floor (101A-101K and fitness office 103A), the conference room 101L and both workrooms (101M and 203A). Special attention should be placed on office 101J as well as workroom 101M. The zone approach was used to pick Office 101J to be used as an academic advisor’s office for athletes due to the amount of privacy an academic advisor needs. This space was picked because it is next to a quiet director’s room as well as very far away from the noisy multipurpose rooms. The workroom 101M, which will 2 JACT be used for physical therapy and first aid, should have high STC rated partitions due to the importance of clear communication between an athlete and a physical therapist. 2. ROOM ACOUSTICS BACKGROUND Before an acoustical analysis can be completed a foundation in how room acoustics work is needed. In Project one the acoustical analysis was focused on how sound produced in a room affected that room. To do that the absorptive properties of the room surfaces were studied to obtain and alter the reverberation times associated with rooms in the Intramural Building. In this project our acoustical analysis focus has shifted to how adjacent rooms affect each other’s background noise levels, Noise Control (NC) ratings, Sound Transmission Class (STC) ratings, and the Transmission Loss (TL) of the partition separating the rooms. Background noise levels refer to the sound pressure levels in a room at the different octave bands. It is difficult to look at all of the background noise levels for every octave bands so a single number system was developed called NC rating. To find the NC rating of a room its background noise levels must be plotted on the NC curve graph. The nearest NC curve that is completely above all of the background noise levels is that NC the room is rated. There are many standard target NC values for different types of rooms found in the notes that were used for the acoustical analysis. Transmission Loss and Sound Transmission Class have a similar relationship as that of background noise level and NC. The key difference is that TL and STC deal with the partitions between different rooms. TL is the amount of sound that can pass through a partition and is measured at different frequencies. This presented the same problem we had with background noise levels the fact that no one wants to look through the values for every octave band. This lead to the creation of the STC curves. The TL values are plotted onto the STC diagram and then analyzed to determine which STC value the partition falls in. There are two criteria that the partition has to meet to be classified for that STC curve. No TL value can be more than eight dB above the STC 3 JACT curve and the sum of all deficiencies cannot be greater than 32 dB. A deficiency is the amount that any TL value is above the STC curve. To find STC values a spreadsheet using logic statements is used to make sure that both criteria are met. So rooms that have similar NC values will need lower STC walls because nether room will be bothered by the noise levels in the adjacent room. While adjacent rooms with drastically different NC values will need a higher STC partition to prevent the louder room from affecting the quite room. These factors are what were taken into account when the acoustical analysis was performed for this project. 3. BACKGROUND NOISE LEVEL RECOMMENDATIONS The recommendation for the background noise level of each room in the IM Building addition were found using Table 1, corresponding rooms to their appropriate tasks while taking into account the surrounding rooms for additional assumptions. The noise criteria found for the desired rooms of the IM Building addition are shown in table 2. The multi-purpose rooms on both the basement and the first floor were given a NC value of 25 considering their various uses, mainly that of group fitness classes using amplified music and as a classroom on occasion which can vary in loudness. The work room was given the role of physical therapy and was attributed a NC value of 30. The office located next to the director’s office was chosen to be the advisors room with an NC value of 30, this location was chosen because the director’s office having to be relatively quiet. All of the other offices including the break room and the office lobby were given an NC value of 35 as they do not require being as quiet and isolating as the directors or advisors office. Each of the rooms were designed to meet the maximum specified noise criteria design target value. Table 1: Recommended Noise Criteria (NC) Design Targets for various spaces: Recommended NC (or RC) for rooms Types of Room or Space Recording or broadcast studios, concert halls, large auditoriums, large churches Small auditoriums, movie theatres, music practice rooms, large meeting & teleconferencing rooms, small churches, courtrooms, chapels Bedrooms, hospitals, residences, hotels, classrooms (classrooms must be ≤ 35 dBA) Private or semiprivate offices, libraries, small conference rooms NC 15-20 20-30 25-30 30-35 4 Large offices, reception areas, retail stores, restaurants, gymnasiums Lobbies, laboratories, drafting rooms, secretarial areas, maintenance shops Kitchens, laundries, school & industrial shops, computer equipment rooms JACT 35-40 40-50 45-55 Table 2: Summary of Noise Criteria targets for desired room: Room #'s 7 8 101 101A 101B 101C 101D 101E 101F 101G 101H 101J 101K 101M 101L 103 124 125 Room Multi-purpose Classroom Office Lobby Office Office Break Room Office Office Office Office Office Advisors Director’s Office Physical therapy Conference Fitness Multi-purpose Multi-purpose NC Target 25 30 35 35 35 35 35 35 35 35 35 30 30 30 30 25 25 25 The location of the rooms and their corresponding noise criteria values are show in color-coded layouts of the basement and first floor. The color-coded layout for the first floor is shown in Figure 1. Both multipurpose rooms are coded in blue for an NC of 25, these two rooms as separated by a movable partition. The fitness room also had an NC of 25, but this room is isolated on the right wing of the building. All the offices were grouped together around the office lobby and next to the break room, each with an NC value of 35. The conference room, physical therapy room, advisors office, and director’s office are also grouped together next to the offices spaces, each with an NC value of 30. The color-coded layout for the basement is shown in Figure 2. The multi-purpose room, of NC value 25 is located adjacent to the classroom, of NC value 30 on lower left corner of the plan. 5 JACT Figure 1: Color-coded layout of Noise Criteria targets for the First Floor Figure 2: Color-coded layout of Noise Criteria targets for the Basement 6 JACT 4. STC ANALYSIS & RECOMMENDATIONS 4.1 STC of Original Partitions The partitions for each of the rooms analyzed are important in determining whether the proper noise control value is suitable in each room. In order to find the type of partitions used, it was determined by using the schedule in the IM Building addition construction drawings. From the description in the drawings, it was then compared to partition types in the NRC-CNRC for the transmission loss data in gypsum board walls. The actual walls in the IM Building were not exactly the same in the NRC-CNRC document because of the conversion from imperial units to the metric system. Jact, Inc. found the most similar type of wall to obtain the transmission loss data. The data provided by the document was then double-checked in a spreadsheet to make sure the correct sound transmission class (STC) was provided to properly adjust the design. Every partition STC class was the same except for partition D which was one value smaller. The STC value obtained through the spreadsheet was used throughout the rest of the proposal rather than the STC value from the NRC-CNRC. There were three different STC values found for the wall partitions. The lowest was a value of forty between the offices and the office lobby. This wall partition was also used between the corridor and the multipurpose room along with the classroom. A larger STC value for forty-seven was used to divide office spaces, which was an acceptable in most cases. The last type of partition was used to divide the classroom and the multi-purpose room in the basement. It has a value of fifty-one. 7 4.2 Analysis of Original Partitions JACT When recommending the STC value for partitions between spaces it was very essential to understand what each space was going to be used for. A general office was important to have fairly quiet so the faculty members would be able to work efficiently without being distracted. However, the conversations held in these offices most likely not being very important that no sound can leave the room. Therefore, it was decided the STC target should be a value of about fifty between two offices. The office lobby was a place for mostly faculty to walk to their individual offices and sometimes have visitors wait outside for a particular meeting. For this reason the STC target value between a general office and the office lobby was determined to be slightly lower at 45. The advisors and directors offices were decided to need higher STC values based upon their important and private conversations that the faculty would not want others to hear outside of the room. The conference and physical therapy room were also found to need higher STC values because of the potential private conversation, but also partially loud conversations, especially in the conference room. The classroom was another room that required high STC values on its partitions so the professor and students would not be distracted by sounds outside of the room. The multi-purpose partitions main goal was to isolate the sound from important rooms that did not want any loud noise. A complete list of the STC target values developed by JACT, Inc., original partition information, and new recommendations can be found in Table 3. Further details of the original partitions can be found in Table 4. 8 JACT Table 3: Summary of the Original Partitions with STC Targets and new Recommendations Room #'s 007 & Q002 007 & 008 008 & Q002 101A & 101 101A & 101B 101B & 101 101C & 101 101C & 101D 101D & 101 101D & 101E 101E & 101 101E & 101F 101F & 101 101F & 101G 101G & 101 101G & 101H 101H & 101 101H & 101J 101J & 101 101J & 101K 101K & 101 101L & 101 101L & 101M 101M & 101 124 & 125 103 & Q101 Room 1 Room 2 STC Target Multi-purpose Corridor Multi-purpose Classroom Classroom Corridor Office Office Lobby Office Office Office Office Lobby Breakroom Office Lobby Breakroom Office Office Office Lobby Office Office Office Office Lobby Office Office Office Office Lobby Office Office Office Office Lobby Office Office Office Office Lobby Office Advisors Advisors Office Lobby Advisors Directors Directors Office Lobby Office Office Lobby Conference Physical Therapy Physical Therapy Office Lobby Multi-purpose Multi-purpose Fitness Main Level Hall 50 60 60 45 50 45 40 60 45 50 45 50 45 50 45 50 45 55 50 60 55 45 60 50 41 40 Original Partition Type STC B 40 D 51 B 40 B 40 A 47 B 40 B 40 A 47 B 40 A 47 B 40 A 47 B 40 A 47 B 40 A 47 B 40 A 47 B 40 C 47 B 40 B 40 B 40 B 40 E 32.8 B 40 Suitable No No No Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No Yes No No No Yes Recommended Partition (STC) II I I I II II I I I II Refer to Note (1) - Note (1): due to the small opening in the wall connecting the two rooms, we are unable to increase the STC value and make the wall and partition more absorptive. Table 4: Description of Original Partitions in the IM Building Addition Code from Drawings NRC TL # (Page) A 3T TL-92-413 (Page 50) B 3D TL-93-365 (Page 44) C 3C TL-92-413 (Page 50) D 4D Tl-93-299 (Page 27) Partition 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 Decription single layer of 13 mm type gypsum board 90 mm steel studs at 610 mm on centre 90 mm of glass fibre insulation in cavity single layer of 13 mm type gypsum board single layer of 13 mm type gypsum board 90 mm steel studs at 406 mm on centre 90 mm of glass fibre insulation in cavity single layer of 13 mm type gypsum board single layer of 13 mm type gypsum board 90 mm steel studs at 610 mm on centre 90 mm of glass fibre insulation in cavity single layer of 13 mm type gypsum board single layer of 13 mm type X gypsum board 150 mm steel studs at 610 mm on centre 150 mm of glass fibre insulation in cavity single layer of 13 mm type X gypsum board NRC STC Spreadsheet STC 47 47 40 40 47 47 52 51 9 JACT The recommendations provided in this report were needed because the original partition STC values were found to be not adequate. The spaces that lacked proper STC rated walls were rooms that generate particularly loud noise and ones that needed to be quiet inside to allow for important and private conversations. The most notable recommendation change was dealing with the physical therapy room and conference room. The new partitions being recommended were found using the Architectural Acoustics Principles and Design [2]. After the recommendations are put into place it will greatly improve the spaces in the IM Building Addition to not only isolate sound from other spaces, but also to allow the private conversations held by faculty and students to be kept private when necessary. Table 5, provides detailed descriptions on the recommended wall partitions. Table 5: Summary of the Descriptions of the Recommended Partitions Partition I II Reference Architectural Acoustics Principles and Design (Appendix J - Page 414) Architectural Acoustics Principles and Design (Appendix J - Page 414) Description Reported STC Spreadsheet STC 5/8" gypsum (3+3 layers) on 3-5/8" metal studs 24" o.c., 3" fiberglass 61 61 5/8" gypsum (2+1 layers) on 3 5/8" studs 24" o.c., and 2" fiberglass 51 51 10 JACT 4.3 Analysis of Moveable Partition Table I: Summary of Transmission Loss data and STC Contour Levels for the Dorma Moveo alternate movable partition STC 50 1/3 OctaveAdjustment Contour Band for Contour Level Frequency Level (dB) (dB) (Hz) 125 -16 34 160 -13 37 200 -10 40 250 -7 43 315 -4 46 400 -1 49 500 0 50 630 1 51 800 2 52 1000 3 53 1250 4 54 1600 4 54 2000 4 54 2500 4 54 3150 4 54 4000 4 54 TL (dB) 33 33 36 40 42 46 48 52 52 52 53 53 52 53 53 54 Total Max Deficiency Deficiency (dB) ≤ X dB? 1 4 4 3 4 3 2 0 0 1 1 1 2 1 1 0 28 OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK Pass 60 Transmission Loss (dB) 50 40 30 TL values STC contour 20 10 0 125 1250 1/3 Octave Bands (Hz) Figure 1: The transmission loss values from 125 to 4,000 Hz ⅓ octave bands and information required to solve the STC value of Dorma Moveo alternative moveable partition 11 Table II: Summary of Transmission Loss data and STC Contour Levels for the Panelfold Moduflex® Model 640 Gypsum Face Panel alternate movable partition STC JACT 52 1/3 OctaveAdjustment Contour Band for Contour Level Frequency Level (dB) (dB) (Hz) 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 -16 -13 -10 -7 -4 -1 0 1 2 3 4 4 4 4 4 4 TL (dB) 36 39 42 45 48 51 52 53 54 55 56 56 56 56 56 56 36 35 39 42 44 46 47 52 54 56 56 58 60 61 61 63 Total Max Deficiency Deficiency (dB) ≤ X dB? 0 4 3 3 4 5 5 1 0 0 0 0 0 0 0 0 OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK 25 Pass 70 Transmission Loss (dB) 60 50 40 TL values 30 STC contour 20 10 0 125 1250 1/3 Octave Bands (Hz) Figure 2: The transmission loss values from 125 to 4,000 Hz ⅓ octave bands and information required to solve the STC value of Panelfold Moduflex® Model 640 Gypsum Face Panel alternative moveable partition 12 JACT Before beginning the analysis of the alternative moveable partitions, first an STC rating of the current moveable partition was found as a baseline comparison for the alternative partitions. Online research found that the Modernfold Acousti-Seal Model 933E partition that is installed in the multipurpose room has an STC rating of 41 dB [4]. The two alternative movable partitions analyzed came from Panelfold Incorporated and Dorma. The Dorma partition is the Moveo model which helps add flexibility and convenience within a space. It’s sealed composite lightweight construction with acoustic core helps increase transmission loss and isolates sound within the room the sound is meant for. The Dorma Moveo is designed for spaces which include conference rooms, exhibition and studio spaces, and gymnasiums. This movable partition offers multifunctional and open-plan spatial configurations and has an STC rating of 50 [1] The second partition analyzed was the Panelfod Moduflex Model 640. This movable partition is made of Gypsum face panels and is ideal for high, expansive areas where remote operation is required. This partition is made specifically for gymnasium and folds in accordion style just like the partition currently installed in the multipurpose room. The STC rating of this partition is 52, which is greater than both the Dorma Moveo model and the current Modernfold model [3]. A TL analysis of the composite wall was done to find what STC rating the entire wall was, which consists of the permanent wall above the moveable partition, the moveable partition itself, as well as an opening at the top, end section of the permanent wall. The first step to find the composite wall TL value was to find the transmission coefficient of each material in the wall. Working backward from the Transmission Loss (TL) equation an equation for transmission coefficient can be found as TL = 10log(1⁄τ) (1) −TL τ = 10 10 (2) 13 JACT Where TL is the rated STC of the partition (dB) and τ is the transmission coefficient. The permanent wall has a rated STC of 40dB and the moveable partition, as stated previously, was found to have a rated STC of 41dB. The rated STC of an opening is known to be zero because there is no material to stop the sound. The next equation needed is the equation for the TL of a composite wall. This equation is dependent on the areas and transmission coefficients of each material. The area of each section of the composite wall includes 450 ft2 for the moveable partition, 369.5 ft2 for the permanent wall, and 0.5 ft2 for the opening in the wall. This comes to a total of 820 ft2. The equation used to find TL of the composite wall is ∑n S TLcomp = 10log [∑ni=1τ Si ](3) i=1 i i Where TLcomp is the TL of the composite wall, Si is the surface area of each individual section, and τi is the individual transmission coefficient of each section. The TL of the composite wall, TLcomp, is calculated as 820 TLcomp = 10log [(10−4.1 x450)+(10−4 x369.5)+(100 x0.5)] = 32dB (4) This shows the rated STC for the current composite wall is 32 dB. Replacing the current movable partition with a Panelfold Moduflex Model 640 STC 52 Gypsum Face Panel system which has a much higher STC than the original partition only increases the STC of the composite wall by 0.2dB. This change is negligible so we elected to keep the original partition type therefore not adding costs from uninstalling and reinstalling a new moveable partition. The reason it is impossible to make a big impact on the composite walls STC is that the opening in the wall makes such a huge impact in the walls STC value. 14 JACT 5.0 SUMMARY 5.1 Report Highlights The IM Building Addition has many spaces with multiple uses. This varies from offices, multi-purpose rooms, to classrooms that all require and make different noise levels. In this report JACT, Inc. analyzed some of the existing rooms within the new addition. It was found that the offices and classrooms needed to have relatively low noise criteria because of the tasks in these rooms. STC ratings for all of the partitions between the rooms analyzed were found. Some of the partitions were found to be acceptable to the STC targets determined. While other partitions were not suitable for the intended purposes, therefor recommended partitions had to be provided. 5.2 Recommendations Based on the calculations done on the different partitions in the building, not all of the partitions meet the criteria and are 5-10% of the targeted STC. The original partitions used in the building have a lower sound isolating system and make it possible for sound to travel to other rooms easier, creating more background noise in the adjacent rooms. Therefore, two partitions were recommended as a replacement for the partitions that did not meet the criteria. The difference between the original partitions and the recommended partitions is about a 10 dB increase in STC value. This increase is made by adding to the number of layers of gypsum board and increasing the thickness of the fiberglass used in the partition to increase the sound isolation. The recommendation for the moveable partition was to keep the existing partition even though it has a low STC. This is because the composite wall it is part of has an opening to the other multipurpose room. This opening is so influential in the composite wall transmission loss calculation that the changing of the moveable partition to a higher STC is negligible. The recommendations provided in the advisors office and other confidential areas required a partition with a high STC, while having a low a transmission loss. This allows for the privacy of conversations and other activities to be mostly kept within the room. 15 JACT 6.0 APPENDIX Partition A Spreadsheet STC 47 1/3 Octave-Band Frequency (Hz) Adjustment for Contour level (dB) Partition A Contour Level (dB) TL (dB) Deficiency (dB) 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 3 3 3 3 3 1 0 1 1 1 1 0 0 0 0 0 31 34 37 40 43 46 47 48 49 50 51 51 51 51 51 51 25.3 29.3 31 35 40.2 45.2 50.6 55.1 58.5 60.9 63.7 65.5 65.2 54.2 47.7 48.7 5.7 4.7 6 5 2.8 0.8 0 0 0 0 0 0 0 0 3.3 2.3 Max Deficiency ≤ 8 dB? Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Total Pass Pass Wall is STC: 47 80 70 60 Transmission Loss, TL (dB) 50 40 STC 47 30 20 10 0 125 500 2000 One-Third Octave Band Frequency (Hz) 16 JACT 7.0 REFERENCES 1) "DORMA MOVEO." MOVEO – operable sound-insulating partitions. N.p., n.d. Web. 14 Apr. 2014. <http://www.dorma.com/ae/en/products/dividing/operable_partitions/moveo_en/index-3723-389913425.html>. 2) Mehta, Madan, James Johnson, and Jorge Rocafort. Architectural Acoustics: Principles and Design. Upper Saddle River, pp 27, 44, and 50 NJ: Prentice Hall, 1999. Print. 3) "Moduflex® Model 640." Panelfold®. N.p., n.d. Web. 14 Apr. 2014. <http://www.panelfold.com/productsub.asp?categoryID=3&productID=24>. 4) "Operable Partitions: ACOUSTI-SEAL® CONTINUOUSLY HINGED ELECTRIC WALL." Modernfold Operable Partitions. N.p., n.d. Web. 14 Apr. 2014. <http://www.modernfold.com/operable_partitions_con_hinged.aspx>. 5) "The Official Site of the IM Building." Recreation Facilities. Athletics Penn State University. Web. 14 Apr. 2014. <http://www.athletics.psu.edu/rec/imbldg/>. 17