Suggestion on How to Use • Industry Trainers are encouraged to use this material in their sessions • Download the presentation file • Print the Notes pages and read them as you view the presentation in the “Slide Show” view. In this way you see the slides in large format and have animation (when available) © 2015 Eaton. All Rights Reserved.. 1 Types of Overcurrent & Calculations © 2015 Eaton. All Rights Reserved.. NEC® Article 100 – Definitions Overcurrent Any current in excess of the rated current of equipment or the ampacity of a conductor. It may result from overload, short circuit, or ground fault. © 2015 Eaton. All Rights Reserved.. 3 NEC® Article 100 – Definitions Overload Operation of equipment in excess of normal, full-load rating, or of a conductor in excess of rated ampacity that, when it persists for a sufficient length of time, would cause damage or dangerous overheating. A fault, such as a short circuit or ground fault, is not an overload. © 2015 Eaton. All Rights Reserved.. 4 Normal Load IL= VS / RT IL VS R Source R R Load IL R R R R © 2015 Eaton. All Rights Reserved.. 5 Overload IOL= VS / RT VS R R Source R Load R R R R Within the normal path © 2015 Eaton. All Rights Reserved.. 6 Short Circuit ISC= VS / RT VS R R Source R Load R R R R Out of the circuit Outside the normal path © 2015 Eaton. All Rights Reserved.. 7 Types of Faults • Bolted Faults • Arcing Faults © 2015 Eaton. All Rights Reserved.. 8 Bolted Short Circuit Arcing Fault Current Thru Air A B © 2015 Eaton. All Rights Reserved.. A B 9 Bolted Faults –Various Types A 480Y/277 V 3 / 4W B C Solid Grd N Ground © 2015 Eaton. All Rights Reserved.. 10 Bolted Faults – Three Phase A 480Y/277 V 3 / 4W B C Solid Grd N Ground Typically considered the “worst case” or highest magnitude © 2015 Eaton. All Rights Reserved.. 11 Bolted Faults – Line to Line A 480Y/277 V 3 / 4W B C Solid Grd N Ground 87 % of the three phase bolted fault © 2015 Eaton. All Rights Reserved.. 12 Bolted Faults – Line to Ground A 480Y/277 V 3 / 4W B C Solid Grd N Ground Typically much lower than 3 fault, but can be > 3 fault near Xfmr terminals © 2015 Eaton. All Rights Reserved.. 13 Arcing Faults – Many Variables Affect Current & Whether It Is Sustainable System Voltage Gap spacing Available 3 Short Circuit Amps Amount of Copper Vaporized Degree of Containment Configuration of Equipment Typically does not sustain on 208Y/120V A © 2015 Eaton. All Rights Reserved.. B 14 Arcing Faults – Progression A 480Y/277 V B 3 / 4W Solid Grd C N Ground © 2015 Eaton. All Rights Reserved.. 15 Arcing Faults – Three Phase A 480Y/277 V 3 / 4W B C Solid Grd N Ground Can vary widely possibly up to 89% of 3 bolted fault © 2015 Eaton. All Rights Reserved.. 16 Arcing Faults – Line to Line A 480Y/277 V 3 / 4W B C Solid Grd N Ground Can vary widely possibly up to 74% of 3 bolted fault © 2015 Eaton. All Rights Reserved.. 17 Arcing Faults – Line to Ground A 480Y/277 V 3 / 4W B C Solid Grd N Ground Can vary widely © 2015 Eaton. All Rights Reserved.. 18 Arcing Faults – Sustainability A 480Y/277 V 3 / 4W B C Solid Grd N Ground Rule of thumb: Arcing faults will typically not sustain at less than 38% of 3 © 2015 Eaton. All Rights Reserved.. bolted fault 19 How do you know what the short-circuit current is throughout a system? and What are some typical values © 2015 Eaton. All Rights Reserved.. 20 Short Circuit Currents Vary Depending on Many Factors Transformer Size & % Z Voltage Conductor Size & Length MSB M M © 2015 Eaton. All Rights Reserved.. 21 Short Circuit Currents Vary Depending on Many Factors 60,000 A 60,000 A MSB 40,000 A 18,000 A 27,000 A 9,000 A M M © 2015 Eaton. All Rights Reserved.. 22 Short Circuit Current Examples #1 500 KVA 1500 KVA 5%Z 5% Z 480/277V 1 1500 KVA 5% Z 208/120V 480/277V 2 3 500 KVA 1500 KVA 1500 KVA 2%Z 2%Z 2%Z 480/277V 1A 480/277V 2A © 2015 Eaton. All Rights Reserved.. 208/120V 3A 23 How to Calculate Transformer Secondary (assuming infinite primary) Isca = (Xfmr FLA) x 100 / %Z (increase result by 10% due to UL tolerance for transformer impedances) © 2015 Eaton. All Rights Reserved.. 24 Short Circuit Current Example #1 Answers 500 KVA 1500 KVA 5%Z 5% Z 480/277V 5% Z 208/120V 480/277V 13,222 A 1 1500 KVA 39,666 A 2 91,608 A 3 500 KVA 1500 KVA 1500 KVA 2%Z 2%Z 2%Z 480/277V 480/277V 33,055 A 1A 208/120V 99,165 A 2A © 2015 Eaton. All Rights Reserved.. 3A 229,020 A 25 Short Circuit Current Example #2 208/120V 4 480/277V 40,000 A. 5 480/277V 40,000 A. 6 50 ft # 1 4A 40,000 A. 50 ft 250 kcm 5A © 2015 Eaton. All Rights Reserved.. 6A 26 Calculating Short Circuit Currents Utilize Point-to-Point Method Steps 4, 5 & 6 for 3 Faults © 2015 Eaton. All Rights Reserved.. 27 Short Circuit Current Example #2 Answers 208/120V 4 480/277V 40,000 A. 5 480/277V 40,000 A. 6 50 ft # 1 4A 50 ft 250 kcm 5A 12,367 A. 40,000 A. 6A 20,322 A. © 2015 Eaton. All Rights Reserved.. 28,818 A. 28 Summary / Questions / To come • Overcurrents – overloads, bolted faults, & arcing faults • Fault currents can be determined throughout distribution system • Available short circuit currents are needed to assess I.R., short-circuit current ratings, selective coordination, arc flash hazards & OCPD selection © 2015 Eaton. All Rights Reserved.. 29 © 2015 Eaton. All Rights Reserved.. 30