ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu Announcements • HW5 is 3.4, 3.10, 3.14, 3.19, 3.23, 3.60, 2.38, 6.9 • It should be done before the first exam, but does not need to be turned in • First exam is Tuesday Oct 6 during class • • Closed book, closed notes, but you may bring one 8.5 by 11 inch note sheet and standard calculators. Last name starting with A to 0 in 3017; P to Z in 3013 1 Complex Power S V I cos(V I ) j sin(V I ) P jQ (Note: S is a complex number but not a phasor) V I* P = Real Power (W, kW, MW) Q = Reactive Power (var, kvar, Mvar) S = Complex power (VA, kVA, MVA) Power Factor (pf) = cos If current leads voltage then pf is leading If current lags voltage then pf is lagging 2 Reactive Compensation Key idea of reactive compensation is to supply reactive power locally. In the previous example this can be done by adding a 16 Mvar capacitor at the load 16.8 MW 16.0 MW 6.4 MVR 0.0 MVR 44.94 kV 16.8 MW 6.4 MVR 40.0 kV 16.0 MW 16.0 MVR 16.0 MVR Compensated circuit is identical to first example with just real power load 3 Reactive Compensation, cont’d • Reactive compensation decreased the line flow from 564 Amps to 400 Amps. This has advantages – – – Lines losses, which are equal to I2 R decrease Lower current allows utility to use small wires, or alternatively, supply more load over the same wires Voltage drop on the line is less • Reactive compensation is used extensively by utilities • Capacitors can be used to “correct” a load’s power factor to an arbitrary value. 4 Power Factor Correction Example Assume we have 100 kVA load with pf=0.8 lagging, and would like to correct the pf to 0.95 lagging S 80 j 60 kVA cos 1 0.8 36.9 PF of 0.95 requires desired cos 1 0.95 18.2 Snew 80 j (60 Qcap ) 60 - Qcap 80 tan18.2 60 Qcap 26.3 kvar Qcap 33.7 kvar 5 Balanced 3 -- No Neutral Current I n I a Ib I c V In (10 1 1 Z * * * * S Van I an Vbn I bn Vcn I cn 3 Van I an 6 Three-Phase - Wye Connection • There are two ways to connect 3 systems – – Wye (Y) Delta () Wye Connection Voltages Van V Vbn V Vcn V 7 Delta-Wye Transformation To simplify analysis of balanced 3 systems: 1) Δ-connected loads can be replaced by 1 Y-connected loads with ZY Z 3 2) Δ-connected sources can be replaced by VLine Y-connected sources with Vphase 330 8 Per Phase Analysis Procedure • 1. 2. 3. 4. To do per phase analysis Convert all load/sources to equivalent Y’s Solve phase “a” independent of the other phases Total system power S = 3 Va Ia* If desired, phase “b” and “c” values can be determined by inspection (i.e., ±120° degree phase shifts) 5. If necessary, go back to original circuit to determine line-line values or internal values. 9 Line Resistance Line resistance per unit length is given by R = where is the resistivity A Resistivity of Copper = 1.68 10-8 Ω-m Resistivity of Aluminum = 2.65 10-8 Ω-m Example: What is the resistance in Ω / mile of a 1" diameter solid aluminum wire (at dc)? 2.65 10-8 Ω-m m R 1609 0.084 2 mile mile 0.0127m 10 Magnetics Review • Ampere’s circuital law: F H dl I e F = mmf = magnetomtive force (amp-turns) H = magnetic field intensity (amp-turns/meter) dl = Vector differential path length (meters) Ie = Line integral about closed path (dl is tangent to path) = Algebraic sum of current linked by 11 Magnetics Review • Ampere’s circuital law: F H dl I e F = mmf = magnetomtive force (amp-turns) H = magnetic field intensity (amp-turns/meter) dl = Vector differential path length (meters) Ie = Line integral about closed path (dl is tangent to path) = Algebraic sum of current linked by 12 Line Inductance Example Calculate the reactance for a balanced 3, 60Hz transmission line with a conductor geometry of an equilateral triangle with D = 5m, r = 1.24cm (Rook conductor) and a length of 5 miles. Since system is assumed balanced ia ib ic 0 1 1 1 a ia ln( ) ib ln( ) ic ln( ) 2 r' D D 13 Line Inductance Example, cont’d Substituting ia ib ic Hence 0 1 1 a ia ln ia ln 2 r ' D 0 D ia ln 2 r' 0 D 4 107 5 La ln ln 3 2 r ' 2 9.67 10 1.25 106 H/m 14 Conductor Bundling To increase the capacity of high voltage transmission lines it is very common to use a number of conductors per phase. This is known as conductor bundling. Typical values are two conductors for 345 kV lines, three for 500 kV and four for 765 kV. 15 Bundled Conductors, cont’d Rb geometric mean radius (GMR) of bundle (r ' d12 d13d14 ) (r ' d12 D1b d1b 1 4 1 ) b for our example in general geometric mean distance (GMD) of conductor 1 to phase b. (d15d16 d17 d18 ) D1c 1 4 D2b D3b D4b Dab (d19 d1,10 d1,11d1,12 ) 1 4 D2c D3c D4c Dac 16 Inductance of Bundle, cont’d But remember each bundle has b conductors in parallel (4 in this example). So 0 D La L1 / b ln 2 Rb 17 Bundle Inductance Example Consider the previous example of the three phases symmetrically spaced 5 meters apart using wire with a radius of r = 1.24 cm. Except now assume each phase has 4 conductors in a square bundle, spaced 0.25 meters apart. What is the new inductance per meter? r 1.24 102 m r ' 9.67 103 m 0.25 M 0.25 M 3 R b 9.67 10 0.25 0.25 2 0.25 0.25 M 1 4 0.12 m (ten times bigger!) 0 5 La ln 7.46 107 H/m 2 0.12 18 Transposition • To keep system balanced, over the length of a transmission line the conductors are rotated so each phase occupies each position on tower for an equal distance. This is known as transposition. Aerial or side view of conductor positions over the length of the transmission line. 19 Inductance of Transposed Line Define the geometric mean distance (GMD) Dm d12 d13d 23 1 3 Then for a balanced 3 system ( I a - I b - I c ) 0 Dm 1 1 0 a I a ln I a ln I a ln 2 r' Dm 2 r' Hence 0 Dm Dm 7 La ln 2 10 ln H/m 2 r' r' 20 Inductance with Bundling If the line is bundled with a geometric mean radius, R b , then 0 Dm a I a ln 2 Rb 0 Dm Dm 7 La ln 2 10 ln H/m 2 Rb Rb Line Conductors, cont’d • Total conductor area is given in circular mils. One circular mil is the area of a circle with a diameter of 0.001 = 0.00052 square inches • Example: what is the area of a solid, 1” diameter circular wire? Answer: 1000 kcmil (kilo circular mils) • Because conductors are stranded, the equivalent radius must be provided by the manufacturer. In tables this value is known as the GMR and is usually expressed in feet. 22 Review of Electric Fields To develop a model for line capacitance we first need to review some electric field concepts. Gauss's law: A D da = qe (integrate over closed surface) where D = electric flux density, coulombs/m 2 da = differential area da, with normal to surface A = total closed surface area, m 2 q e = total charge in coulombs enclosed 23 Gauss’s Law Example •Similar to Ampere’s Circuital law, Gauss’s Law is most useful for cases with symmetry. •Example: Calculate D about an infinitely long wire that has a charge density of q coulombs/meter. Since D comes radially out integrate over the cylinder bounding D d a D 2 Rh q qh e A the wire q D ar where ar radially directed unit vector 2 R 24 Line Capacitance, cont’d To eliminate mutual capacitance we'll again assume we have a uniformly transposed line. For the previous three conductor example: Va V Since q a = C Va qa 2 C Va ln D r 25 Bundled Conductor Capacitance Similar to what we did for determining line inductance when there are n bundled conductors, we use the original capacitance equation just substituting an equivalent radius R cb (rd12 1 d1n ) n Note for the capacitance equation we use r rather than r' which was used for R b in the inductance equation 26 Line Capacitance, cont’d For the case of uniformly transposed lines we use the same GMR, D m , as before. 2 C Dm ln Rbc where Dm R cb d ab d ac dbc (rd12 1 d1n ) n 1 3 (note r NOT r') ε in air o 8.854 10-12 F/m 27 Line Capacitance Example •Calculate the per phase capacitance and susceptance of a balanced 3, 60 Hz, transmission line with horizontal phase spacing of 10m using three conductor bundling with a spacing between conductors in the bundle of 0.3m. Assume the line is uniformly transposed and the conductors have a 1cm radius. 28 Line Capacitance Example, cont’d Rbc Dm C Xc 1 (0.01 0.3 0.3) 3 1 (10 10 20) 3 0.0963 m 12.6 m 2 8.854 1012 1.141 1011 F/m 12.6 ln 0.0963 1 1 C 2 60 1.141 1011 F/m 2.33 10 -m (not / m) 8 29 Transmission Line Equivalent Circuit •Our current model of a transmission line is shown below Units on z and y are per unit length! For operation at frequency , let z = r + jL and y = g +jC (with g usually equal 0) 30 Derivation of V, I Relationships We can then derive the following relationships: dV I z dx dI (V dV ) y dx V y dx dV ( x) dI ( x) zI yV dx dx 31 Setting up a Second Order Equation dV ( x) dI ( x) zI yV dx dx We can rewrite these two, first order differential equations as a single second order equation d 2V ( x) dI ( x) z zyV 2 dx dx 2 d V ( x) zyV 0 2 dx 32 V, I Relationships, cont’d Define the propagation constant as yz j where the attenuation constant the phase constant Use the Laplace Transform to solve. System has a characteristic equation ( s ) ( s )( s ) 0 2 2 33 Determining Line Voltage, cont’d V ( x) K1 cosh( x) K 2 sinh( x) V (0) VR K1 cosh(0) K 2 sinh(0) Since cosh(0) 1 & sinh(0) 0 K1 VR dV ( x) dx zI K1 sinh( x) K 2 cosh( x) K2 zI R IR z z IR y yz V ( x) VR cosh( x) I R Z c sinh( x) where Zc z y characteristic impedance 34 Lossless Transmission Lines For a lossless line the characteristic impedance, Zc , is known as the surge impedance. Zc jwl l (a real value) jwc c If a lossless line is terminated in impedance VR Zc IR Then I R Z c VR so we get... 35 Lossless Transmission Lines V ( x) VR cosh x VR sinh x I ( x) I R cosh x I R sinh x V ( x) Zc I ( x) 2 V(x) Define as the surge impedance load (SIL). Zc Since the line is lossless this implies V ( x) VR I ( x) I R If P > SIL then line consumes vars; otherwise line generates vars. 36 Transmission Matrix Model, cont’d VS A B VR With I I C D R S Use voltage/current relationships to solve for A,B,C,D VS VR cosh l Z c I R sinh l VR I S I R cosh l sinh l Zc cosh l A B 1 T sinh l C D Z c Z c sinh l cosh l 37 Equivalent Circuit Model The common representation is the equivalent circuit Next we’ll use the T matrix values to derive the parameters Z' and Y'. 38 Equivalent Circuit Parameters VS VR Y' VR I R Z' 2 Z 'Y ' VS 1 VR Z ' I R 2 Y' Y' I S VS VR I R 2 2 Z 'Y ' Z 'Y ' I S Y ' 1 VR 1 IR 4 2 1 Z 'Y ' Z ' VR VS 2 I Z 'Y ' Z 'Y ' I R S Y ' 1 1 4 2 39 Three Line Models Long Line Model (longer than 200 miles) l tanh sinh l Y ' Y 2 use Z ' Z , l 2 2 l 2 Medium Line Model (between 50 and 200 miles) Y use Z and 2 Short Line Model (less than 50 miles) use Z (i.e., assume Y is zero) 40 Power Transfer in Lossless Lines If we assume a line is lossless with impedance jX and are just interested in real power transfer then: 2 P12 jQ12 V1 V1 V2 90 90 12 Z Z Since - cos(90 12 ) sin 12 , we get V1 V2 P12 sin 12 X Hence the maximum power transfer is P12Max V1 V2 X 41 Ideal Transformer • First we review the voltage/current relationships for an ideal transformer – – – no real power losses magnetic core has infinite permeability no leakage flux • We’ll define the “primary” side of the transformer as the side that usually takes power, and the secondary as the side that usually delivers power. – primary is usually the side with the higher voltage, but may be the low voltage side on a generator step-up transformer. 42 Ideal Transformer Relationships Assume we have flux m in magnetic material. Then 1 N1m d 1 2 N 2m d 2 d m d m v1 N1 v2 N2 dt dt dt dt d m v1 v2 v1 N1 a = turns ratio dt N1 N2 v2 N2 43 Current/Voltage Relationships If is infinite then 0 N1i1 N 2i2' . Hence i1 N2 or ' N1 i2 i1 N2 1 i2 N1 a Then v1 i 1 a 0 v 2 1 0 i2 a 44 Transformer Equivalent Circuit Using the previous relationships, we can derive an equivalent circuit model for the real transformer This model is further simplified by referring all impedances to the primary side r2' a 2 r2 re r1 r2' x2' a 2 x2 xe x1 x2' 45 Simplified Equivalent Circuit 46 Calculation of Model Parameters • The parameters of the model are determined based upon – – – nameplate data: gives the rated voltages and power open circuit test: rated voltage is applied to primary with secondary open; measure the primary current and losses (the test may also be done applying the voltage to the secondary, calculating the values, then referring the values back to the primary side). short circuit test: with secondary shorted, apply voltage to primary to get rated current to flow; measure voltage and losses. 47 Per Unit Calculations • A key problem in analyzing power systems is the large number of transformers. – It would be very difficult to continually have to refer impedances to the different sides of the transformers • This problem is avoided by a normalization of all variables. • This normalization is known as per unit analysis. actual quantity quantity in per unit base value of quantity 48 Per Unit Conversion Procedure, 1 1. Pick a 1 VA base for the entire system, SB 2. Pick a voltage base for each different voltage level, VB. Voltage bases are related by transformer turns ratios. Voltages are line to neutral. 3. Calculate the impedance base, ZB= (VB)2/SB 4. Calculate the current base, IB = VB/ZB 5. Convert actual values to per unit Note, per unit conversion on affects magnitudes, not the angles. Also, per unit quantities no longer have units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts) 49 Per Unit Example Solve for the current, load voltage and load power in the circuit shown below using per unit analysis with an SB of 100 MVA, and voltage bases of 8 kV, 80 kV and 16 kV. Original Circuit 50 Three Phase Per Unit Procedure is very similar to 1 except we use a 3 VA base, and use line to line voltage bases 1. Pick a 3 VA base for the entire system, S B3 2. Pick a voltage base for each different voltage level, VB. Voltages are line to line. 3. Calculate the impedance base ZB VB2, LL S B3 ( 3 VB , LN ) 2 3S 1B VB2, LN S 1B Exactly the same impedance bases as with single phase! 51 Three Phase Per Unit, cont'd 4. Calculate the current base, IB I3B S B3 3 S 1B S 1B I1B 3 VB , LL 3 3 VB , LN VB , LN Exactly the same current bases as with single phase! 5. Convert actual values to per unit 52 Three Phase Transformers • There are 4 different ways to connect 3 transformers Y-Y - Usually 3 transformers are constructed so all windings share a common core 53 3 Transformer Interconnections -Y Y- 54 Load Models • Ultimate goal is to supply loads with electricity at constant frequency and voltage • Electrical characteristics of individual loads matter, but usually they can only be estimated – – actual loads are constantly changing, consisting of a large number of individual devices only limited network observability of load characteristics • Aggregate models are typically used for analysis • Two common models – – constant power: Si = Pi + jQi constant impedance: Si = |V|2 / Zi 55 Bus Admittance Matrix or Ybus • First step in solving the power flow is to create what is known as the bus admittance matrix, often call the Ybus. • The Ybus gives the relationships between all the bus current injections, I, and all the bus voltages, V, I = Ybus V • The Ybus is developed by applying KCL at each bus in the system to relate the bus current injections, the bus voltages, and the branch impedances and admittances 56 Ybus Example Determine the bus admittance matrix for the network shown below, assuming the current injection at each bus i is Ii = IGi - IDi where IGi is the current injection into the bus from the generator and IDi is the current flowing into the load 57 Ybus Example, cont’d We can get similar relationships for buses 3 and 4 The results can then be expressed in matrix form I Ybus V YA YB I1 YA YB I Y YA YC YD YC 2 A YC YB YC I 3 YB I 0 YD 0 4 0 V1 YD V2 0 V3 YD V4 For a system with n buses, Ybus is an n by n symmetric matrix (i.e., one where Aij = Aji) 58 Ybus General Form • The diagonal terms, Yii, are the self admittance terms, equal to the sum of the admittances of all devices incident to bus i. • The off-diagonal terms, Yij, are equal to the negative of the sum of the admittances joining the two buses. • With large systems Ybus is a sparse matrix (that is, most entries are zero) • Shunt terms, such as with the line model, only affect the diagonal terms. 59 Modeling Shunts in the Ybus Ykc Since I ij (Vi V j )Yk Vi 2 Ykc Yii Yk 2 Rk jX k Rk jX k 1 1 Note Yk 2 Z k Rk jX k Rk jX k Rk X k2 Yiifrom other lines 60 Two Bus System Example Yc (V1 V2 ) I1 V1 Z 2 1 12 j16 0.03 j 0.04 I1 12 j15.9 12 j16 V1 I 12 j16 12 j15.9 V 2 2 61 Power Flow Analysis • When analyzing power systems we know neither the complex bus voltages nor the complex current injections • Rather, we know the complex power being consumed by the load, and the power being injected by the generators plus their voltage magnitudes • Therefore we can not directly use the Ybus equations, but rather must use the power balance equations 62 Power Balance Equations, cont’d * n Si Vi I i* Vi YikVk Vi Yik*Vk* k 1 k 1 This is an equation with complex numbers. Sometimes we would like an equivalent set of real power equations. These can be derived by defining n Yik Gik jBik Vi Vi e ji Vi i ik i k Recall e j cos j sin 63 Real Power Balance Equations n Si Pi jQi Vi Yik*Vk* k 1 n Vi Vk k 1 n j ik V V e (Gik jBik ) i k k 1 (cos ik j sin ik )(Gik jBik ) Resolving into the real and imaginary parts Pi Qi n Vi Vk (Gik cosik Bik sinik ) PGi PDi k 1 n Vi Vk (Gik sinik Bik cosik ) QGi QDi k 1 64 Gauss Iteration There are a number of different iterative methods we can use. We'll consider two: Gauss and Newton. With the Gauss method we need to rewrite our equation in an implicit form: x = h(x) To iterate we first make an initial guess of x, x (0) , and then iteratively solve x (v +1) h( x ( v ) ) until we find a "fixed point", x, ˆ such that xˆ h(x). ˆ 65 Gauss Iteration Example Example: Solve x - x 1 0 x ( v 1) 1 x ( v ) Let v = 0 and arbitrarily guess x (0) 1 and solve v 0 1 2 3 4 x(v ) 1 2 2.41421 2.55538 2.59805 v 5 6 7 8 9 x(v) 2.61185 2.61612 2.61744 2.61785 2.61798 66 Gauss Power Flow We first need to put the equation in the correct form * n Vi YikVk Vi Yik*Vk* k 1 k 1 n Si Vi I i* n n k 1 k 1 S*i Vi* I i Vi* YikVk Vi* YikVk S*i * Vi n YikVk k 1 YiiVi n k 1,k i n 1 S*i Vi * YikVk Yii V k 1,k i i YikVk 67 Gauss Two Bus Power Flow Example •A 100 MW, 50 Mvar load is connected to a generator •through a line with z = 0.02 + j0.06 p.u. and line charging of 5 Mvar on each end (100 MVA base). Also, there is a 25 Mvar capacitor at bus 2. If the generator voltage is 1.0 p.u., what is V2? SLoad = 1.0 + j0.5 p.u. 68 Gauss Two Bus Example, cont’d The unknown is the complex load voltage, V2 . To determine V2 we need to know the Ybus . 1 5 j15 0.02 j 0.06 5 j14.95 5 j15 Hence Ybus 5 j 15 5 j 14.70 ( Note B22 - j15 j 0.05 j 0.25) 69 Gauss Two Bus Example, cont’d n 1 S*2 V2 * YikVk Y22 V2 k 1,k i -1 j 0.5 1 V2 (5 j15)(1.00) * 5 j14.70 V2 Guess V2(0) 1.00 (this is known as a flat start) v 0 1 2 V2( v ) 1.000 j 0.000 0.9671 j 0.0568 0.9624 j 0.0553 v 3 4 V2( v ) 0.9622 j 0.0556 0.9622 j 0.0556 70 Gauss Two Bus Example, cont’d V2 0.9622 j 0.0556 0.9638 3.3 Once the voltages are known all other values can be determined, such as the generator powers and the line flows S1* V1* (Y11V1 Y12V2 ) 1.023 j 0.239 In actual units P1 102.3 MW, Q1 23.9 Mvar 2 The capacitor is supplying V2 25 23.2 Mvar 71 Slack Bus • In previous example we specified S2 and V1 and then solved for S1 and V2. • We can not arbitrarily specify S at all buses because total generation must equal total load + total losses • We also need an angle reference bus. • To solve these problems we define one bus as the "slack" bus. This bus has a fixed voltage magnitude and angle, and a varying real/reactive power injection. 72