INTERNATIONAL ENERGY AGENCY HYDROGEN IMPLEMENTING AGREEMENT TASK 11: INTEGRATED SYSTEMS Final report of Subtask A: Case Studies of Integrated Hydrogen Energy Systems Chapter 4 of 11 T. Schucan Paul Scherrer Institute Switzerland Chapter 4 PHOEBUS JÜLICH DEMONSTRATION PLANT 1. PROJECT GOALS 2. Due to the greatly varying availability and demand, future energy supply systems based on renewables will require energy storage. At present, the public grid can be used to store intermittent renewables, as long as the load penetration is low. If, therefore, larger supply contributions are to be provided from renewables, concepts of energy storage must be established for the short and long term as important system components of a regenerative energy supply. Appropriate measures for their realisation must be initiated now. The overriding objective of the PHOEBUS project is therefore the development and testing of a solar energy supply system in combination with energy storage. The task is centered on demonstrating the supply under real solar- and consumption-specific conditions. 3. GENERAL DESCRIPTION OF PROJECT 4. The PHOEBUS demonstration plant has been designed to provide an autonomous solar electricity supply to the central library building of the Research Centre Jülich with an installed capacity of 38 kWel. The major components of the plant in its first phase of operation are: · A photovoltaic field with four facade and rooftop integrated generators consisting of monocrystalline modules with an active area of 312 m2, peak power output of 43 kWp, and an electrical energy output of 29 MWh/yr; · A pair of DC/DC-converters (5 kW each) for each photovoltaic field, adjusting the voltage to the level given by the DC-grid which has the actual voltage level of the battery system; · A system of 110 lead batteries of the OPzS OCSM type with electrolyte recirculation, designed for a DC-grid voltage of 220 V (200-260 V), and a capacity of 304 kWh, 1380 Ah over 10 hours; · A bipolar 21 cell electrolyzer with an active cell area of 2500 cm2, a current of 750 A, a current density of 3 kA/m2, with 30% KOH solution, 80°C operating temperature, an operating pressure of 0.7 MPa and 90% efficiency in design load operation at a design power rating of 26 kW; maximum hydrogen production is 6.5 Nm3/h and maximum oxygen production is 3.25 Nm3/h; · A storage system for the product gases, hydrogen (6.5 Nm3/h) and oxygen (3.25 Nm3/h), leaving the electrolyzer at 0.7 MPa. The hydrogen is compressed to 12 MPa and stored in 18 pressure bottles of 1.4 m3 each with a total geometrical volume of 25 m3 for H2 (3,000 Nm3 H2). The oxygen is compressed to 7 MPa and stored in one high pressure storage unit of 20 m3, sufficient for the whole seasonal storage requirements; · An alkaline fuel cell system consisting of KOH gas diffusion electrode fuel cell of the Siemens BZA 4-2 type with a design power output of 6.5 kW at 48 V and 135 A, with a system efficiency at design load of 63% (LHV of H2) and 70% at 30% partial load. An overview of the experimental hall with fuel cell, alkaline electrolyzer, gas treatment unit, highpressure electrolyzer (added in phase 2), battery system (from left to right) and all other subsystems (except the gas storage vessels), is shown in Picture 4.1. The central task of this project is to test the required storage system using hydrogen as the energy carrier. Combining an electrolyzer and a fuel cell with all essential system steps of a solar electricity supply, the objective is to match the system components and optimise the overall plant so that energy losses are as low as possible and high system reliability is achieved. In considering the energy flows and their conversion in the individual plant components it is important to maximise the energy yield and adapt power supply as efficiently as possible to the supply task. This requires high system engineering demands on the utilization rates as well as on the regulation and control of the individual components in a wide power range. On the whole, the tasks to be fulfilled involve a complex system composed of interlinked components of energy converters and energy stores integrated between a greatly varying solar radiation input and a consumer with load fluctuations. Moreover, account must be taken of various requirements to be met by the electrochemical components with respect to service life, operational reliability (H2/O2 gases), start-up and shutdown processes as well as exclusion of specific operating conditions (e.g. low-load ranges diminishing the utilisation rate, avoidance of exhaustive discharge and gassing charge of the battery, abruptly changing load). An intelligent strategy must therefore be developed which, at any time of the day and year, distributes the energy flows to the individual paths and takes account of the boundary conditions of each system component with respect to its efficiency characteristics and its control and regulation dynamics. It can be seen from the above requirements that entirely new standards must be applied to the system management of such a stand-alone plant, which can only be coped with by a computerassisted energy management (EM). The overall system development of energy storage technology relies on plant and systems engineering as well as open-loop and closed-loop control technology. 3. PERFORMANCE AND OPERATIONAL EXPERIENCE The general aim was to determine design strengths and weaknesses from the operating experience, and with the measurement data obtained, verify the models used in simulation programs, to energetically optimize the plant, to check the operational reliability and to propose and implement cost-reducing and advanced system modifications. 3.1 Results of a twelve-month operation The energy balance for an annual scenario (1997) of PHOEBUS is shown in Figure 4.1. The energy flows and efficiencies measured were entered as annual sums or average annual efficiencies. The measurement result obtained is basically in agreement with the autonomy conditions calculated by simulation. It should be noted, however, that the energy driving the two pneumatic H2/O2 compressors was provided by the compressed-air grid and was not taken into account energetically, except for the leakage. Since September 24, 1997, PHOEBUS has operated without the PV converters, i.e. the PV generators are directly coupled with the busbar and battery, and maximum power point (MPP) tracking by the converters is omitted. The results show that this step provides a positive balance compared to previous operation. Although the solar-electric energy yield decreases by 3 - 4% due to the floating power point (without MPP tracking), the conversion losses of the converter amount to 9% and the converter investment costs are eliminated. An increase of the battery voltage by 18 V (9 cells) would even further improve the performance. A weak point in the storage system continues to be the fuel cell. The operation of the alkaline fuel cell (AFC) suffered from failures which were inherent in the system: failure of the electrolyte pumps, disturbances in the control electronics caused by failure of sensors measuring temperature, current and voltage, and leakages in the gap evaporator led to increased electrolyte concentrations in the cooling water and required a frequent supply of additional potassium hydroxide. The stored H2 and O2 gases could thus only be used to a minor extent. In order not to disturb plant operation by the failure of the fuel cell, the so-called "fuel cell simulator" switches itself on in this case. This is an AC-DC converter, which takes over the function of the fuel cell in conformity with power requirements so that autonomous operation continues to be ensured. On the whole, the fuel cell produced an electric energy of 387 kWh in the period under investigation. With an average power of 4 kW the fuel cell was thus in operation for 97 hours. This low availability was compensated by the "fuel cell simulator" supplying an amount of energy of 4162 kWh from the grid. In terms of control technology, there was no difference between the fuel cell and simulator. The balancing of plant operation was effected by the acquisition and storage of more than 200 data monitoring points measured by the sensors at intervals of one second. This includes checking of the data for plausibility with several computer programs, reducing them, forming the corresponding mean and summation values and considering data dropouts. The data are used to determine and balance the material and electrical energy flows, and power levels and efficiencies on all paths of the system from solar radiation input up to the consumer. The data are displayed graphically as time-variation curves or cumulative distributions for arbitrary periods of time. An example of the comparison between measured values and simulation results for the efficiency of the total photovoltaic system (summed over all 4 fields) is given in Figure 4.2. 3.2 Development of new system components A priority task was the joint development of a fuel cell based on the proton-exchange membrane technology (PEMFC) for use in PHOEBUS with Sammer, USA. Work for the development, construction and testing of two 2.5 kW units was largely completed and the units were incorporated into the PHOEBUS plant. The peripherals (gas supply, cooling, measurement, electrical installation, control, and power converters) of the two fuel cell stacks were installed. Initial operation was not satisfactory and further improvements were required which did not lead to success until the end of the period under investigation. Problems encountered included membrane ruptures, water management, and channel dimensions. This dashed the hope of being able to use the new PEMFC for the first time in the winter 1997/98. The gas storage system for H2 and O2 was operated for the first time without failure. Thanks to the high operational reliability of the electrolyzer it was possible to fill the gas storage tank for the first time at the end of the season (2257 m3), so that the gas quantities required for autonomous operation were available. The leakage rate (approximately 1 m3/day) was high in the hydrogen storage tanks at high pressure levels. A total of 19% of the annual production was thus lost. It was possible to reduce leakage by improving the flange construction. The two compressors continue to be a weak point of the storage system. Although it was possible to significantly increase the lifetimes by a new coating procedure for the cylinder bearing surfaces (approximately 300 h), this means two replacements during one season! In cooperation with the Central Department of Technology (ZAT) and the Central Electronics Laboratory (ZEL) of Research Centre Jülich (FZJ), the high-pressure electrolyzer (5 kW, 120 bar) and the two-stage solar thermal metal-hydride compressor (120 bar) were developed as an alternative to mechanical compression. The high-pressure electrolyzer is shown in Picture 4.2. It is currently being tested. The metalhydride compressor was subjected to a thorough practical test within the framework of a doctoral thesis (K. Bonhoff). This test has been successfully completed. In summary, the aim of an autonomous supply in automated operation has been achieved. An efficient control system has been developed by means of well-devised energy management with battery charge as the control parameter and electrolysis and fuel cell performance as the variables. 4. SIMULATION AND SYSTEM INTEGRATION The efficiency, control strategy, and optimum size and configuration of autonomous PHOEBUS plants are governed by many factors (load structure of electricity and heat requirements, storage concept, control, costs, site etc.), and they can ultimately only be treated by means of simulation techniques proven in practical application. Optimization analyses for plant operation (energy management) and system studies with different plant configurations were carried out with the aid of simulation programs validated by measurements in PHOEBUS. This has led to simplified and more efficient PHOEBUS concepts incorporating reduced expenditure on electrical power conditioning (omission of the three power converters) and omission of mechanical compression by the use of a high-pressure electrolyzer. The stability and controllability of direct coupling of the PV generator with the battery, electrolyzer, and fuel cell have been thoroughly investigated and feasibility was demonstrated by simulation. The efficiency of the overall plant can be improved from 54% to 65% and an appreciable reduction in construction costs may also be expected by the omission of the converters. The aim of a further investigation of different system concepts is to explore the possibilities of integrating regenerative energy converters in a combined heat and power package of decentralised energy supply plants and to present corresponding systems. Initial results have shown that a number of promising system variants based on the PHOEBUS concept and using the simulation tools are conceivable. These utilize the hydrogen storage system (electrolyzer/fuel cell) presented in order to either realize a purely electrical or an electrical and thermal energy supply. It is very advantageous to use another renewable source of energy (ambient heat) and incorporate it in the PHOEBUS system with the aid of an electricmotor- operated heat pump circuit for heating or cooling purposes. On the input side of the energy supply system, wind energy also offers itself as an alternative to or can be used in combination with PV energy. Depending on the site, a hybrid operation of both energy sources leads to a homogenization of the annual variation in energy generation. This generally leads to a reduction in storage requirements compared to operation with a single source, and long-time storage becomes entirely superfluous if energy surpluses are abandoned. Such hybrid systems also offer the possibility of adapting oneself more or less to the consumption time-variation curve by selectively choosing the nominal power of each plant with its outputs. This will then require, for example, a correspondingly higher wind generator power for covering the electric and heating energy requirements or a higher PV generator power for meeting the electric and cooling energy requirements in the case of a strictly demand-oriented heat-power/coolant coupling. 5. FUTURE PLANS With the aid of largely validated simulation programs, optimization analyses for plant operation and plant configuration were carried out and two advanced concepts, PHOEBUS-2 and PHOEBUS-3, developed. The PHOEBUS-2 concept involves a greatly reduced system expenditure and thus a cost reduction of the entire PHOEBUS plant. This can be mainly achieved by directly coupling the PV generator with the battery, electrolyzer, and fuel cell. In this way, the expenditure and plant losses can be reduced by omitting the power converters. The use of a high-pressure electrolyzer makes the mechanical compression of the H2 and O2 product gases superfluous. This leads to a further reduction of the losses on the storage path so that the overall plant efficiency can be reduced by 10% to 15% compared to the present-day plant. Initial successes in the practical application of new or extended systems seem to be achievable with this procedure. PHOEBUS-3 was conceived within the framework of a doctoral thesis (Ch. Meurer). It has been investigated whether and how an electrical and thermal supply in conformity with demand and purely based on renewable energy can be achieved with a modified system technology. It was shown in simulation calculations that the use of ambient heat (installation of heat pumps) makes it possible not only to uncouple energy supply (PV and/or wind energy) from energy demand in terms of time and power, but also to uncouple the electrical from the thermal energy requirements (heating) in terms of time using the same storage system (electrolyzer-H2-fuel cell). Wind and photovoltaic generators in hybrid operation prove to be particularly advantageous due to their complementary annual variation. The storage requirements are considerably reduced due to the relatively uniform annual energy production. 6. CONCLUSIONS PHOEBUS Jülich demonstrates that an electrical energy supply with purely renewable energy without connection to the public grid is basically possible. Plant operation is fully automated. The control strategy of the plant has been constantly improved so that a developed energy management system is now available as system software. The control system optimally distributes the energy flows and completely ensures the functionality of the plant by means of monitoring systems. It has been possible to identify weak points of the plant by simulation and measured data evaluation: The optimum system management strategies were determined for individual components using sensitivity analyses. The weak point of the storage system continues to be the fuel cell. Despite great efforts in developing the PEM fuel cell, it has not been possible to ensure operational reliability over prolonged periods. Worldwide efforts at making these fuel cells marketable in terms of technology and costs would also mean a breakthrough for the hydrogen (or fuel) storage system and its multiple application possibilities. As stated above, the long-term hydrogen storage system proves to be the central unit of every system variant to decouple energy supply and demand in terms of time and power, but also to decouple electric and thermal energy requirements in terms of time using the same storage system. This is above all a clear advantage compared to conventional CHP plants. Current investigations are also aimed at finding cost-optimized systems in addition to those technically optimized. This will primarily be achievable by minimizing the storage system. The know-how required for the above tasks can be utilized in further system studies and in the conceptual design and qualified handling of new tasks and projects. The experience of PHOEBUS, including the measurement evaluation of the plant and the results of system engineering studies obtained for the conceptual design of renewable energy supply systems, can open up new paths for the development or improvement of equipment and systems technology (PEM fuel cell, pressure-type electrolyzer, metal-hydride compressor, metal-hydride storage, H2 safety technology, H2/O2 gas treatment, system modelling, energy management, control and regulation technology). Plant costs can be further decreased with standardized system-engineering solutions and with the market introduction of electrochemical energy converters (electrolyzer or fuel cell). The opportunities for near-term market introduction are: wherever a connection to the public grid is not economically efficient (due to extremely long distances or insufficient load compatibility); where decentralised CHP plants can uncouple power and heat; reduced emissions; lower fuel costs (including transport and storage); or a specific peak load in the grid must be accommodated.