NUMALIGARH REFINERY LIMITED Technical Specification For Motor Operated Valve Unit: DCU Page 1 of 10 CONTENTS 1.0 SCOPE 2.0 DATA SHEET FOR MOV ACTUATOR 3.0 DETAIL SCOPE FOR ELECTRICAL ACTUATOR 4.0 INSTRUMENTATION REQUIREMENTS 5.0 COMMISSIONING 1.0 Scope This specification shall be read in conjunction with NRL technical specification for procurement of valves (No. MM/Tech/02/2010). This specification covers details towards electrical and instrumentation items only. All standards mentioned in this specification shall invariably be the latest edition / revision. In case of any deviation the bidder is advised to use the deviation sheet attached with document MM/Tech/02/2010. In absence of any deviation sheet it will be assumed that bidder accepts all conditions mentioned in this specification. The bidder shall enclose a signed copy of this page as a token of acceptance of all clauses appearing in this specification. 2.0 DATA SHEET FOR MOV ACTUATOR Part –I: NRL DATA 1.0 Site Conditions 1.1 Altitude : Les than 1000 m 1.2 Design ambient temperature : 40oC 1.3 Humidity : Highly humid 1.4 Climate : Highly dusty, corrosive as prevalent in a refinery 1.5 Project site : Delayed Coker Unit 1.6 MOV Tag No. : 03-MOV-1401, 03-MOV-1402 2.0 System Conditions 2.1 Supply voltage : 415V + 10%, 3-phase AC 2.2 Supply frequency : 50HZ + 3% 2.3 System earthing : Solidly earthed 3.0 Operating Environment 3.1 Area Classification : Zone 2 3.2 Gas Group : IIA/ IIB 3.3 Temperature Class : T3 Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED Technical Specification For Motor Operated Valve Unit: DCU Page 2 of 10 3.4 Construction : Flameproof Ex (d) 3.5 Ingress Protection : IP65 3.6 Painting : Epoxy base 3.7 Whether ‘K Mass’ type or equivalent fireproofing required : Yes 3.7.1 For MOV Tag Nos. : Both 3.7.2 With Fireproof rating : 30 minutes 4.0 Valve Duty, Mode of Control and Device for Control 4.1 Valve duty a. Fully open and fully closed : Yes b. Partially open and partially closed : 4.2 Control requirement : Local & Remote for all MOV’s 4.3 Local/ Remote/ Off selector switch on MOV Actuator : Required 4.4 Compatibility for interfacing with 2 wire control system : Required 4.5 Setting of adjustable parameters of Actuator (For 2 wire control system) : NA 4.6 Continuous of position indication 4.6.1 Local : Mechanical/ LCD indication required 4.6.2 Remote – Potentiometer/ transducer for remote continuous indication : Required 4.7 Intermediate travel limit switch : Not required for all MOV’s 4.8 Potential free contacts for indication on remote panel and other interlocks : 4.8.1 For valve open position : Required 4.8.2 For valve closed position : Required 4.8.3 For remote indication of position of local/ Remote selector switch : Required 4.8.4 For availability of MOV actuator for remote Operation (contact from monitoring relay) : Required 4.8.5 For indication valve operation in progress : Required 4.9 Remote Emergency Stop push button for stopping actuator : Required 4.10 DCS interface for Remote control/ indication : Remote Control requirement shall be as per CI.4.2 above/ Remote indication Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED 4.11 Technical Specification For Motor Operated Valve Unit: DCU Page 3 of 10 Maximum time of operation - Opening : As per Valve data sheet - Closing : As per Valve data sheet 4.12 Double compression cable glands and plug for unused entries (To be supplied along with MOV actuator) : Flameproof & WP type 4.13 Make of MOV Actuator : Rotork 5.0 Test and Approval Certificates for Flameproof Actuators 5.1 For Indigenous make MOV Actuators : Yes 5.2 For Imported make MOV Actuators : Yes 5.3 Submission of Type test certificates : Yes 6.0 Applicable NRL Specification 6.1 Specification for electrical motor operated : Yes Valve actuators 7.0 Special Requirements : Both Soft and Hard copy of the following documents required1. Operation and maintenance manual of MOV 2. BOM of MOV 3. General arrangement (GA) drawing of MOV 4. Circuit diagram of MOV NOTES: 1. NA denotes ‘Not Applicable’. 2. Area Classification Zone, Gas Group and Temperature class indicated at S. no. 3.1 to 3.3 above refer to IS/ IEC standards. 3. The purchaser shall provide single point supply to the actuator as per S. No. 2.0 above. Any other control supply voltage required shall be internally derived by the manufacturer within the actuator. 4. In case ‘Remote continuous position indication’ is required as per S. No. 4.6.2 above, the potentiometer/ transducer required for position indication along with loose remote continuous position indicator shall be included in the quoted prices of respective MOV Actuator and supplied with it. 5. Vendor shall furnish complete data as per Part-II of this data sheet for each MOV actuator along with the offer. 6. Remote Input signals for Opening/Closing/Stopping the MOV shall be provided through the momentary closing of separate potential free contacts in owner’s panel. Necessary controls required for running the motor for the complete opening/ closing sequence of the valve using such input signals shall be provided by manufacturer in the actuator. Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED Technical Specification For Motor Operated Valve Unit: DCU Page 4 of 10 7. Vendor shall quote for Maintenance spares for two years trouble free operation and maintenance of the MOV actuators indicating recommended quantity and unit prices. 8. Vendors shall include the complete set of commissioning spares (spares which would be necessary during commissioning of the actuator and associated hardware, as envisaged by vendor) along with the offered actuator. Vendor shall quote the price of commissioning spares with a list of such spares. 9. Two separate earthing bosses shall be provided for all the actuators for carrying out the double earthing. 10. MOV’s shall be provided with min. 4 nos. entries. 11. Double compression cable glands & 1 no. Flameproof plug shall be provided for each MOV. 12. Any special tools/tackles for commissioning of MOV’s with two wire control system shall be supplied by vendor, along with actuators. SPECIAL REQUIREMENT FOR MOVs 1. a. Bidder shall provide filled in Data sheet for torque values of MOVs. Torque values submitted for MOVs shall be in line with the following requirements i.e. - Valve break and running torque figures with a safety factor of 1.5 shall be minimum 1.5 times the break and running torque values. - Actuator generated break and running torque shall be minimum equal to or greater than the break and running values with a safety factor of 1.5 respectively. - The actuator break and running torque shall be less than the maximum allowable valve stem torque. b. The functional test of complete assembly of MOVs along with the actuator and control system shall be performed by the supplier at works in presence of owner/ Owners representative. 2. Valve with motorized actuator shall be suitable for installation in horizontal/vertical lines. 3. MOVs to be operable from field and control room. 4. Bidder shall be solely responsible for selection of suitable actuators & actuator control system. Vendor shall also be single point responsible for the complete system. Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED Technical Specification For Motor Operated Valve Unit: DCU Page 5 of 10 Part –II: DATA FROM VENDOR DATA SHEET FOR MOV ACTUATOR 1.0 ACTUATOR 1.1 Make 1.2 Type & Catalogue 1.3 Applicable Wiring Diagram No. 1.4 Valve Duty 1.5 Max. Permission No. of Open / Close cycles per hour 1.6 Internal Control supply used in Actuator 1.7 Recommended Back up HRC fuse rating (Control) Recommended Back up HRC fuse rating (Power) Power fuse not provided in the actuator 1.8 2.0 Time in sec. for fully opening / closing MOTOR 2.1 Make 2.2 Kw rating 2.3 Rated speed in RPM 2.4 Enclosure 2.5 Locked rotor (Starting) current 2.6 Rated torque current 2.7 Average load current 3.0 BASIS FOR SIZING AND SELECTION OF ACTUATOR 4.0 TEST AND APPROVAL CERTIFICATES 5.0 COMPONENTS MAKE 5.1 Contactors 5.2 Push Buttons 5.3 Selected Switches Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED 3.0 Technical Specification For Motor Operated Valve Unit: DCU Page 6 of 10 DETAIL SCOPE FOR ELECTRICAL ACTUATOR This section covers design, manufacturer, assembly, shop testing and supply of electrical motor operated valve actuators intended for fully / partially opening and closing valve duty. 3.1 CODES AND STANDARDS 1. The equipment shall comply with the requirement of latest revision of the following standards issued by BIS (Bureau of Indian Standard) unless specified otherwise. IS 5 Colours for ready mixed paints and enamels. IS 325 Three-phase Induction Motors. IS 2148 Flameproof enclosures for electrical apparatus. IS 4691 Degrees of protection provided by enclosure for rotating electrical machinery. IS 4722 Rotating electrical machines – Specification IS 9334 Electric Motor Operate Actuators IS 13947 Low voltage Switchgear and Control gear 2. In case of imported equipment, the standards of the country of origin shall be applicable if these standards are equivalent or more stringent than the applicable Indian standards. 3. The equipment shall also conform to the provision of Indian Electricity Rules and other statutory regulations currently in force in the country. 4. In case Indian Standards are not available for any equipment, standards issued by IEC/ BS/ VDE/ IEEE/ NEMA or equivalent agency shall be applicable. 5. In case of any contradiction between various referred standards/ specifications/ data sheets and statutory regulations, the following order of decreasing priority shall govern: 3.2 - Statutory regulations - Data sheets - Job specifications - This specification - Codes and standards GENERAL REQUIREMENTS 1. This offered equipment shall be brand new with state of the art technology with a proven field track record. No prototype equipment shall be offered. 2. Vendor shall ensure availability of spare parts and maintenance support services for the offered equipment for at least 15 years from the date of supply. 3. Vendor shall give a notice of at least one year to NRL before phasing out the product/ spares to enable NRL to place order for spares and services. 4. The vendor shall be responsible for design, engineering and manufacturing of the complete actuator to fully meet the intent and requirements of this specification and attached data sheets. Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED 3.3 Technical Specification For Motor Operated Valve Unit: DCU Page 7 of 10 POWER SUPPLY The electrical motor operated valve actuators shall be suitable for power supply at 415V + 10%, 50Hz + 3%, 3 phase, unless specified otherwise in the data sheet. 3.4 TECHNICAL SPECIFICATIONS Each MOV actuator shall include the motor, actuator unit, gears, position indicators, limit switches, hand wheel, electrical starter and controls, terminal box etc. as a self-contained unit. The actuator shall be provided adequate torque and/ or thrust to ensure the complete intended travel of the valve under the worst operating and electrical power supply conditions. 3.4.1. Motor 1. The motor shall be 3-phase squirrel cage induction type unless specified otherwise in the data sheet. It shall have totally enclosed non-ventilated construction. 2. The motor shall be designed for valve actuator service with high starting torque and shall be suitable for direct on-line starting. It shall be rated for S2-15 minute duty and shall conform to IS 325 or equivalent international standards. 3. The motor shall be provided with thermostat(s)/ thermister(s)/ embedded in the hot spots of motor winding for protecting the motor. 4. The motor shall be able to operate the actuator at 75% of rated voltage. 5. The motor shall have class ‘F’ insulation with temperature rise limited to class ‘B’ limits. Motor winding shall be treated to resist corrosive agents and moisture. 6. Motor rotor shall preferably be of die-cast aluminium and, if brazed, shall be free from phosphorous. 3.4.2 Integral Starter and Control Transformer The reversing starter, control transformer and local controls shall be integral with the valve actuator, unless specified otherwise in the data sheet. Solid state control of valve actuator and electrically isolated interface for remote control requirement shall be provided, wherever these features exist in manufacturer’s design. The integral starter shall be supplied with the following device: a) Electrically and mechanically interlocked reversing contractors for opening and closing operations. b) Control transformer with necessary tapping and protected with suitable easily replaceable uses. c) Terminal block for external cable connection fully rewired for internal devices of valve actuator. MOV Actuator operating with AC power supply shall be provided with instantaneous Phase reversal protection. 3.4.3 Integral Push Button, Selector switches, Indications and Control devices The following local control devices shall be provided integral with the MOV actuator: a) Push buttons for ‘Opening/ Closing/ Stop’ or alternatively ‘Open/ Close’ selector switches. Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED Technical Specification For Motor Operated Valve Unit: DCU Page 8 of 10 b) ‘Local/ Off/ Remote’ selector switch, pad-lockable in each position. c) Local continuous position indication from ‘Valve fully open’ to ‘Valve fully closed’ position, which may be of analogue or digital type using mechanical indication/ Indicating lamps/ LEDs. d) Push button operation should be such that the action required for opening is different from action required for closing (e.g. Pull Type and Push Type) 3.4.4 Torque and Travel Limit Switches Torque limit switches shall be provided to protect the motor from over-loading by cutting off the power supply to motor during opening and closing operations. The limit switches shall be preset. However, it shall be possible to set the value of maximum torque during closing from 50% to 100% of rated torque of actuators. Travel limit switch shall be provided to cut-off the power supply to the motor at the end of preset limit of valve travel. The switches shall be provided with requisite number of potential-free contacts for valve actuator operation and for indication on remote panels as specified in data sheet. Instead of mechanical torque limit switches, magnetic pulse counter to measure and control the stroke of actuator may be provided, wherever this feature exists in manufacturer’s design. 3.4.5 Control Facilities The internal controls and monitoring circuits shall be incorporated within the integral starter along with transformer and control unit of valve actuator. Remote control facility shall be provided, if specified in the data sheet. The remote control circuits shall be powered from internally derived control supply voltage, unless the use of external supply for remote control is specified in data sheet. In order to cater to remote control and indication requirements for ‘Position of Remote/ Local/ Off selector switch’, if specified in the data sheet, an additional Monitoring relay/ auxiliary/ relays shall be provided as a part of the valve actuator. As an alternative, a common status contact indicating the availability of the MOV actuator for remote control may be provided by monitoring the following: - Loss of one or more phases of power supply. - Loss of control circuit supply - Selector switch in local mode - Local stop push button set of ‘Off’ - Motor thermostat tripped - Any other local fault/ abnormal condition 3.4.6 Hand Operation A hand wheel with hand/ auto lockable lever shall be provided for emergency operation of the MOV. The energisation of the motor shall automatically re-engage power operation. 3.4.7 Remote Position Indicator If specified in the data sheet, a 4-20 mA remote position transmitter shall be provided in the valve actuator and a continuous position indicator for mounting in purchaser’s remote panel shall be supplied as a loose item. The remote position indicator shall continuously indicate the position of travel f the valve. Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED Technical Specification For Motor Operated Valve Unit: DCU Page 9 of 10 3.4.8 Nameplate Each motorized valve actuator shall be provided with a stainless steel nameplate furnishing the following details, attached firmly to it at a place convenient for reading: a) Actuator tag number as per data sheet. b) Motor kW rating, motor time rating, motor supply voltage, nominal motor phase current, auxiliary switch rating. c) Maximum torque setting d) Actuator enclosure type, lubricant type e) Actuator type, wiring diagram number/ catalogue number, actuator serial number. A separate nameplate shall be provided for hazardous area application. 3.4.9 The enclosure of complete MOV actuator including motor, integral starter, control transformer unit and all control devices shall have minimum IP-65 degree of ingress protection. 3.4.10 Wiring and Terminals All devices provided in the actuator shall be wired up to the terminal block. The contacts for remote operation and indication shall also be wired up to the terminal block. Minimum 10% spare terminals shall be provided for future interlocks. Internal wiring for power and control circuits shall be appropriately sized for MOV actuator rating. Each wire shall be identified at both ends using PVC ferrules. The terminal compartments shall be separated from the inner electrical components of the actuator by means of a watertight seal so that the actuator electrical components are protected from the ingress of moisture and foreign materials when the terminal cover is removed during installation and maintenance. 3.4.11 Vendor shall be responsible for the compatibility of the MOV actuator with the valve and for the selection and sizing of various electrical devices and components in the actuator. 3.4.12 The actuator shall be provided with maximum three adequately sized cable entries viz., one for power cable and two for control cables. Suitable double compression cable glands shall be provided with each actuator for all cable entries and sealing plugs for all control cable entries. The cable glands and plugs shall be made of Nickel-plated brass. 3.5 EQUIPMENT FOR CALSSIFIED HAZARDOUS AREAS 3.5.1 Actuators meant for hazardous areas shall meet the requirements of IS 2148, IEC 79 or equivalent international standards and shall be suitable for Gas groups and Temperature class as specified in the data sheet. The manufacturer shall possess valid test certificates issued by a recognized independent test house (CMRI/ BASSEEFA/ LCIE/ UL/ FM or equivalent) for the offered actuators. All indigenous equipment shall conform to Indian standards and shall have been tested and certified by Indian testing agencies. All equipment indigenous and imported) shall also have valid statutory approvals as applicable for the specified hazardous locations from CCE or any other applicable statutory authority. All indigenous flameproof equipment shall have valid BIS license and corresponding marking as required by statutory authorities. 3.5.2 Apart from the nameplate indicating the Tag No., a separate nameplate shall also be provided on each actuator to indicate the details of the testing agency (CMRI or equivalent), test certificate Mechanical Maintenance Department NUMALIGARH REFINERY LIMITED Technical Specification For Motor Operated Valve Unit: DCU Page 10 of 10 number with date, statutory approval number with date, approval agency (CCE/ DGMS or equivalent), BIS license number with date, applicable Gas group and Temperature class etc. The nameplate shall be riveted/ fixed with screws and not pasted. In case any of the standard details listed above are embossed on the enclosures, the same need not be repeated. 3.6 FIREPROOFING 3.6.1 If specified in the Data Sheet, the MOV Actuators shall be provided with ‘K-Mass’ type or equivalent fireproofing. Unless specified otherwise, the fireproofing shall be rated for 30 minutes. The required certificates for the fireproof rating shall be furnished from an independent test laboratory. 3.6.2 MOV Actuators with fireproofing shall be suitable for termination of mica insulated fire survival type power and control cables. 3.7 INSPECTION, TESTING AND ACCEPTANCE The equipment shall be subject to inspection by NRL or by an agency authorized by the owner. Manufacturer shall furnish all necessary information concerning the supply to NRL. During the course of manufacturing, NRL or other authorized representative shall be free to visit the works and assess the progress of work and the manufacturer shall render him all possible assistance to do so. The vendor shall include all relevant tests for actuator including complete MOV testing in their QAP as per MM/Tech/02/2010. Type test certificates shall be furnished with bids. Final acceptance of MOVs at site shall be subject to successful testing of the MOV actuators with the valves. Type test certificates, original drawings referred in certificates and statutory approval certificates and BIS license, where applicable, shall be shown to the inspection agency on demand. The certificates and BIS license must be valid at the time of dispatch. 3.8 PACKING AND DESPATCH The equipment may be stored outdoors for long periods before installation. The packing shall be completely suitable for outdoor storage in areas with heavy rains and high ambient temperature unless otherwise agreed. In order to prevent movement of equipment/ components within the crates, proper packing supports shall be provided. A set of instruction manuals for erection, testing and commissioning, a set of operation and maintenance manuals and a set of final drawings shall be enclosed in a waterproof cover along with the shipment. 4.0 INSTRUMENTATION REQUIREMENTS 4.1 Remote open/close command from control room to MCC (of MOV) of electrical substation: Instrumentation will provide Potential free contact (using non latching push button) to electrical MCC of the MOV and the interposing/control voltage (not greater than 230 VAC/DC) will be from the electrical MCC of the MOV. 4.2 Fully open/ close feed back indication to control room: For fully open / close indication Instrumentation need potential free contact from the electrical MCC/ MOV for fully open indication. The interposing/control voltage (not greater than 110VAC) will be from NRL control system (DCS/PLC). 5.0 COMMISSIONING The vendor shall depute a commissioning engineer for commissioning of the valve with MOV. The payment shall be released only after successful site acceptance test. Mechanical Maintenance Department