® Packaged Domestic Hot Water Generator with Plate-Type Heat Exchanger and Storage Tank Energy Source: Boiler Water ® ENG I NEERED DUP L E X A L L OY AquaPLEX® Duplex Stainless Steel Tank with 25-year Corrosion Warranty Up to 6,000,000 Btuh Output 150 to 900 Gallon Storage Tanks Single-wall Brazed Plate Heat Exchangers Double-wall Plate-and-Frame Exchangers Domestic Water Temperature to 180°F Skid-mounted with Factory Pre-assembled Piping ® A S M E A S M E U HLW Engineered Water Heating Solutions® ® Hot Water Outlet ASHRAE compliant insulation TempTrac® Electronic Operating Control Boiler Water Supply Clean-in-Place Fittings AquaPLEX® Storage Tank Operating Thermostat Boiler Water Return Flow Diffusers Y-strainer Circulator Plate-type Heat Exchanger Cold Water Inlet Heat Transfer Characteristics of Plate Heat Exchangers Due to their unique heat transfer characteristics, plate-type heat exchangers excel when applied in lowtemperature boiler water loops. A plate-type exchanger, when supplied with 145°F boiler water, can produce 140°F domestic hot water while reducing boiler water return temperature to 100°F or lower. The is highly beneficial in condensing boiler systems where efficiency improves with reductions in both supply and return water temperature. By comparison, u-tube heat exchangers are typically sized for a 20°F difference between the entering boiler water temperature and the desired domestic hot water outlet temperature. In addition, the boiler return water cannot be lower than the domestic hot water outlet temperature. For example, to produce 140°F domestic hot water, a u-tube exchanger would require 160°F entering boiler water and return boiler water would be no less than 141°F; temperatures above the ideal range for condensing boilers. Domestic Water Outlet 140°F Boiler Water Inlet 145°F Domestic Water Inlet 40°F Boiler Water Outlet 100°F Inside the plate exchanger, counter-flows of boiler and domestic water maximize the temperature differentials and allow the temperatures of the opposing liquids to “cross” with boiler return water becoming colder than domestic outlet water. Sequence of Operation Domestic Hot Water to Building Demand for hot water causes a temperature drop in the storage tank as cold makeup water displaces the hot water in the tank. The tank thermostat senses this temperature drop and signals the operator to energize the circulator. Cold domestic water flows through the heat exchanger, captures heat from the boiler water and returns to the storage tank. Flow diffusers reduce the velocity of water leaving and returning to the storage tank from the heat exchanger. This eliminates turbulence in the storage tank and preserves the natural temperature stratification, allowing delivery of 80% of the storage tank’s capacity at the desired set point temperature. Boiler Water Supply When tank temperature returns to the desired set point, the circulator is de-energized. If the installation includes an optional boiler water control valve, the electronic operator will energize and de-energize the valve. 140 Heated Domestic Water Back to Tank Boiler Water Return Domestic Cold Water Makeup Boiler Water Control Options Hot Water Outlet Hot Water Outlet Storage Tank Storage Tank Heat Exchanger Boiler Water Supply Heat Exchanger Boiler Water Supply Boiler Water Return Boiler Water Return Cold Water Inlet Cold Water Inlet No Boiler Water Control Valve 2-Way Boiler Water Control Valve Constant boiler water flow through the heat exchanger is acceptable because heat transfer to the domestic water is controlled entirely by the circulator between the tank and heat exchanger. Constant flow at the water heater is also a logical choice for boiler loops equipped with VFD pump controls because domestic hot water is a year-round requirement in continual need of boiler water flow. If the water heater is not utilized as the constant flow bypass in a VFD-equipped boiler loop and boiler flow is to be allowed only during a domestic water call for heat, the plate heat exchanger can be equipped with a motorized 2-way valve. In this configuration, the boiler water 2-way valve and the circulator are controlled by the TempTrac operator. Double-Wall Heat Exchanger Performance with Different Boiler Water Temperatures Boiler Water Side 145°F Entering Boiler Water (Supply) ~ 100°F Leaving Boiler Water (Return) Double-wall heat exchangers are plate-and-frame design. ASME Stamp: Section VIII Operating Pressure (boiler side): 150 psi (standard) 300 psi (optional) Operating Temperature (boiler side): 338°F maximum rating Maximum boiler water temperature when operating EZ Plate water heater is 185°F. Consult PVI for higher boiler water temperatures. Connections: 2" NPT Stainless Steel Gasket Material: EPDM Plate Material: Stainless Steel DomesƟc Water Side 40°F to 140°F Heat Exchanger Model No. Boiler Water Flow (gpm) Boiler Water Pressure Drop (psi) Recovery (gph) BTU Output 600 10 1.6 270 225,000 900 15 2.1 400 333,000 1200 20 2.5 540 450,000 1800 30 3.0 810 675,000 2400 40 3.0 1080 900,000 3000 50 3.2 1350 1,125,000 3600 60 3.5 1590 1,325,000 4500 75 3.8 1980 1,650,000 5400 90 4.2 2400 2,000,000 7200 120 4.8 3180 2,650,000 Boiler Water Side 160°F Entering Boiler Water (Supply) ~ 88°F Leaving Boiler Water (Return) DomesƟc Water Side 40°F to 140°F Heat Exchanger Model No. Boiler Water Flow (gpm) Boiler Water Pressure Drop (psi) Recovery (gph) BTU Output 600 10 1.6 450 374,850 900 15 2.1 660 549,780 1200 20 2.5 870 724,710 1800 30 3.0 1260 1,049,580 2400 40 3.0 1710 1,424,430 3000 50 3.2 2160 1,799,280 3600 60 3.5 2580 2,149,140 4500 75 3.8 3180 2,648,940 5400 90 4.2 3900 3,248,700 7200 120 4.8 5160 4,298,280 For performance with other boiler water and domestic water conditions, refer to PVI web site. Warranty: 3-year Domestic side standard temperature is 180°F max. Domestic side standard pressure is 150 psi max. For higher operating pressure, consult your PVI representative. ® Single-Wall Heat Exchanger Performance with Different Boiler Water Temperatures Boiler Water Side 145°F Entering Boiler Water (Supply) ~ 105°F Leaving Boiler Water (Return) Single-wall heat exchangers are brazed plate design. ASME Stamp: Section VIII Operating Pressure (boiler side): 435 psi max Operating Temperature (boiler side): 450°F maximum rating Maximum boiler water temperature when operating EZ Plate water heater is 185°F. Consult PVI for higher boiler water temperatures. Connections: 2" NPT Stainless Steel Brazing Material: Copper Plate Material: Stainless Steel Warranty: 3-year Domestic side standard temperature is 180°F max. Domestic side standard pressure is 150 psi max. For higher operating pressure, consult your PVI representative. DomesƟc Water Side 40°F to 140°F Heat Exchanger Model No. Boiler Water Flow (gpm) Boiler Water Pressure Drop (psi) Recovery (gph) 600 10 1.6 270 225,000 900 15 2.1 390 325,000 1200 20 2.5 420 350,000 1800 30 3.0 630 525,000 2400 40 3.0 780 650,000 3000 50 3.2 960 800,000 3600 60 3.5 1260 1,050,000 4500 75 3.8 1500 1,250,000 5400 90 4.2 1800 1,500,000 7200 120 4.8 2400 2,000,000 Boiler Water Side 160°F Entering Boiler Water (Supply) ~ 95°F Leaving Boiler Water (Return) BTU Output DomesƟc Water Side 40°F to 140°F Heat Exchanger Model No. Boiler Water Flow (gpm) Boiler Water Pressure Drop (psi) Recovery (gph) BTU Output 600 10 1.6 450 375,000 900 15 2.1 690 575,000 1200 20 2.5 750 625,000 1800 30 3.0 1100 920,000 2400 40 3.0 1440 1,200,000 3000 50 3.2 1800 1,500,000 3600 60 3.5 2250 1,875,000 4500 75 3.8 2760 2,300,000 5400 90 4.2 3300 2,750,000 7200 120 4.8 4380 3,650,000 For performance with other boiler water and domestic water conditions, refer to PVI web site. ® ® ENGINEER ED D U PLEX A LLO Y EZ Plate water heaters use a storage tank that is fabricated from AquaPLEX duplex stainless steel. It is an engineered alloy that combines two different types of stainless steel; austenitic and ferritic, to create a material that captures the advantages of both. After the tank is completely fabricated, it is immersion pickle-passivated; a process that returns the duplex stainless steel to its original pristine condition. AquaPLEX is naturally immune to corrosion in hot potable water regardless of temperature and as a result requires no additional lining or any type of anode protection. Because there is no corrosion, an anode rod, whether sacrificial or impressed current, simply has nothing to do. Unlike 316L stainless steel, the addition of a ferritic grain structure renders the duplex stainless steel immune to chloride stress corrosion cracking; a known failure mode of 316L stainless steel in hot potable water. These properties allow PVI to provide an unprecedented 25-year tank corrosion warranty. Additionally, because there is no lining AquaPLEX tanks are maintenance-free and the water contacting surfaces are non-porous and do not absorb water. AquaPLEX can also withstand temperature elevation and hyper-chlorination methods if it’s ever necessary to eliminate bacteria from the building’s water system. Storage Tank is Equipped with Lead-Free Bronze Fittings All connections to the AquaPLEX tanks are made through removable cast-bronze fittings. This design avoids using lined steel fittings that are often the starting point for corrosion inside a water heater. There is also no galvanic corrosion because the bronze fittings are galvanically neutral to the AquaPLEX tank. Bolt-on Bronze Fitting O-ring Gasket More than one-quarter million of these removable bronze fittings are in service! Tank Wall Packaged Heater Dimensions Maximum Dimensions of Factory Packaged Heater Tank Size (gallons) Maximum Heater Model No. Height (H) Width (W) Depth (D) 150 4500 65 60 61.5 175 4500 71 60 61.5 215 4500 78 60 61.5 250 4500 63 77.5 69 300 4500 75 77.5 69 400 7200 87 77.5 69 500 7200 78 87 80 600 7200 90 87 80 750 7200 83 98 90.5 900 7200 95 98 90.5 For larger tank sizes, consult your PVI representative. Standard Equipment • • • • • • • • • • AquaPLEX storage tank. ASME stamped HLW for 150 psi MAWP Double-wall plate-and-frame or single-wall brazed-plate heat exchanger, ASME stamped ASME-rated pressure relief valve (on heat exchanger) ASME-rated temperature and pressure relief valve (on storage tanks) Clean-in-place valves for heat exchanger Bronze y-strainer with blow down valve on domestic water to the heat exchanger Bronze circulating pump Programmable electronic operating control with digital temperature readouts (BAS connectable via Modbus RTU) Immersion temperature limiting device (high limit control) Drain Valve D Optional Equipment • Electronic low water cutoff • Manual-reset, immersion temperature limiting device • • • • H Temperature and pressure gauges 2-way boiler water control valve Y-strainer for boiler water Higher operating pressures for storage tanks and heat exchangers (consult PVI representative) W ® Configuring an EZ Plate® Model Number (_ _ _ _) L (_ _ _ _) A-TRPF (plate-and-frame, double wall) A-TRBP (brazed plate, single wall) Storage tank size in gallons 150 175 215 250 300 400 500 600 750 900 (consult PVI representative for larger storage tanks or horizontal tank configuration) “L” designates AquaPLEX storage tank Heat exchanger model number 600 900 1200 1800 2400 3000 3600 4500 5400 7200 Example model number: 1800 L 300A-TRPF Plate-and-Frame heat exchanger number 1800 connected to a 300 gallon AquaPLEX storage tank. ® PV 8650 1-2016 Engineered Water Heating Solutions® www.pvi.com