FLOW CONTROLS Technical Help Guide Thermal Expansion Valves Solenoid Valves System Protectors Regulators Basic Rules of Good Practice Troubleshooting Guide 2006 Table of Contents Thermal Expansion Valves . . . . . . . . . . . . . . 1 Solenoid Valves . . . . . . . . . . . . . . . . . . . . . . 30 System Protectors . . . . . . . . . . . . . . . . . . . . 42 Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Basic Rules of Good Practice . . . . . . . . . . . 56 Troubleshooting Guide . . . . . . . . . . . . . . . . 59 Thermal Expansion Valves 1 2006 Thermal Expansion Valves The Thermal Expansion Valve is a precision device designed to regulate the rate of refrigerant liquid flow into the evaporator in the exact proportion to the rate of evaporation of the refrigerant liquid in the evaporator. This controlled flow prevents the return of refrigerant liquid to the compressor. The TXV controls the flow of gas by maintaining a pre determinated super heat. The amount of refrigerant gas leaving the evaporator can be regulated since the TXV responds to: (1) the temperature of the refrigerant gas leaving the evaporator and (2) the pressure in the evaporator. Three forces which govern the TXV operations are (1) the power element and remote bulb pressure (P1), (2) the evaporator pressure (P2), and the super-heat spring equivalent pressure (P3) see Fig. 1 We are concerned with the single outlet type of TXV and shall discuss it under two headings: (1) A valve with an internal equalizer, and (2) the use of external equalizer feature. Internal Equalizer gas leaving the evaporator decreases, the pressure in the remote bulb and power assembly also decreases and the combined evaporator and spring pressure cause the valve pin to move in a closing direction (P1 less than P2+P3). For example, when the evaporator is operating with 134a at a temperature of 40°F or a pressure of 35 psig and the refrigerant gas leaving the evaporator at the remote bulb location is 45°F a condition of 10°F superheat exists. Since the remote bulb and power assembly are charged with the same refrigerant as that used in the system R-134a, its pressure (P1) will follow its saturation pressure-temperature characteristics. With the liquid in the remote bulb at 45°F, the pressure inside the remote bulb and power assembly will be 40 psig acting in an opening direction. Beneath the diaphragm and acting in a closing direction are the evaporator pressure (P2) of 35 psig and the spring pressure (P3) for a 10°F superheat setting of 5 psig (35+5=40) making a total of 40 psig. The valve is balanced, 40 psig above the diaphragm and 40 psig below the diagraph. Three conditions present themselves in the operation of this valve: first, the balanced forces; second, an increase in superheat; third, a decrease in superheat. The remote bulb and power element make up a closed system (power assembly), and in the following discussion, it’s assumed that the remote bulb and power element are charged with the same refrigerant as that in the system. The remote bulb and power element pressure (P1), which corresponds to the saturation pressure of the refrigerant gas temperature leaving the evaporator, moves the valve pin in the opening direction. Opposed to this opening force on the underneath side of the diaphragm and acting in the closing direction are two forces: (1) the force exerted by the evaporator pressure (P2) and (2) that exerted by the superheat spring (P3). In the first condition, the valve will assume a stable control position when these three forces are in balance. (See figure 1A) (that is, when P1 = P2 + P3). In the next step, the temperature of the refrigerant gas at the evaporator outlet (remote bulb location) increases above the saturation temperature corresponding to the evaporator pressure as it becomes superheated. (P1 greater than P2+P3) and causes the valve pin to move in an opening direction. Conversely, as the temperature of the refrigerant Changes in load, increasing the superheat, will cause the TXV pin to move in an opening direction. Conversely, a change, decreasing the superheat will cause the TXV pin to move in a closing direction. (Fig 1) 2 Thermal Expansion Valves Factory Settings of Valves The factory superheat setting of TXVs is made with the valve pin just starting to move away from the seat. The superheat increase necessary to get the pin ready to move is called static superheat. Thermal Expansion Valves are so designed that an increase in superheat of refrigerant gas leaving the evaporator, usually over and beyond of the factory static superheat setting, is necessary for the valve pin to open to its rated position. This additional superheat is known as gradient. For example, if the factory static is 6°F superheat, the operating superheat at the rated stroke or pin position (full load rating of valve) will be 10°F to 14°F superheat (See fig. 2). If the operating superheat is raised unnecessarily high, the evaporator capacity decreases, since more of the evaporator surface is required to produce the superheat necessary to operate the TXV. Manufacturers usually furnish the adjustable type TXV with a factory static superheat setting of 6°F to 10°F unless otherwise specified by the customer. It also is obvious then that a minimum change of superheat to open the valve is of vital importance because it provides saving in both initial evaporator cost and cost of operation. When using non-adjustable TXVs, it’s important that they order with the correct factory superheat setting. For manufacture’s production lines it is recommended that an adjustable TXV be used in a pilot model lab test to determine the correct factory superheat setting before ordering the non-adjustable type TXV. The TXV operation discussed thus far pertains to the internal equalizer type of valve. The evaporator pressure at the valve outlet is admitted internally and allowed to exert its force beneath the diaphragm. External Equalizer psi is present (See fig. 3). The pressure at point “C” is 27 psig or 10 psi lower than at the valve outlet, point “A”, however, the pressure of 37 psig at point “A” is the pressure acting on the lower side of the diaphragm in a closing direction. With the valve spring set at a compression equivalent to 10°F superheat or a pressure of 9.7 psig, the required pressure above the diaphragm to equalize the forces is (37 + 9.7) or 46.7 psig. This pressure corresponds to a saturation temperature of 50°F. It is evident that the refrigerant temperature at point “C” must be 50°F if the valve is to be in equilibrium. Since the pressure at this point is only 27 psig and the corresponding saturation temperature is 28°F, a superheat of 50°F minus 28°F or 22°F is required to open the valve. This increase in superheat, from 10°F to 22°F makes it necessary to use more of the evaporator surface to produce this higher superheated refrigerant gas. Therefore, the amount of evaporator surface available for absorption of latent heat of vaporization of the refrigerants is reduced, the evaporator is starved before the required superheat is reached. When the pressure drop through the evaporator is of any consequence, i.e., in general a pressure drop equivalent to 3°F in the air conditioning range, 2°F in the commercial temperature range, and 1°F in the low temperature range, it will hold the TXV in a relatively “restricted” position and reduce the system capacity, unless a TXV with an external equalizer is used. The evaporator should be designed or selected for the operating conditions and the TXV selected and applied accordingly. For example, an evaporator is fed by a TXV with an internal equalizer, where a sizable pressure drops of 10 3 Thermal Expansion Valves Since the pressure drop across the evaporator, which causes this high superheat condition, increases with the load because of friction this “restricting” or “starving” effect is increased when the demand on the TXV capacity is greatest. side of the remote bulb location. In general and as a rule of thumb, the equalizer line should be connected to the suction line at the evaporator outlet. If the external equalizer type of TXV is used, with the equalizer line connected to the suction line, the true evaporator outlet pressure is exerted beneath the TXV diaphragm. The operating pressure on the valve diaphragm is now free from any effect of the pressure drop through the evaporator, and the TXV will respond to the superheat of the refrigerant gas leaving the evaporator. In order to compensate for an excessive pressure drop through an evaporator, the TXV must be of external equalizer type, with the equalizer line connected either into the evaporator at a point beyond greatest pressure drop into the suction line at a point on the compressor When in the same conditions of pressure drop exist in a system with a TXV, which has the external equalizer feature (see fig. 4), the same pressure drop still exists through the evaporator, however, the pressure under the diaphragm is now the same as the pressure at the end of the evaporator, point “C”, or 27psig. The required pressure above the diaphragm for equilibrium is 27 + 9.7 or 36.7 psig. This pressure, 36.7 psig, corresponds to a saturation temperature of 40°F and the superheat required is now (40°F minus 28°F) 12°F. The use of an external equalizer has reduced the superheat from 22°F to 12°F1 Thus the capacity of a system, having an evaporator with a sizable pressure drop, will be increased by the use of a TXV with the external equalizer as compared to the use of an internally equalized valve. When the pressure drop through an evaporator is in excess of limits previously defined, or when a refrigerant distributor is used at the evaporator inlet, the TXV must have the external equalizer feature for best performance. The diagram used in this Section thus far has shown the single outlet type of TXV. Although a multi-circuit evaporator in itself may not have an excessive pressure drop, the device used to obtain liquid distribution will introduce a pressure drop that will limit the action of the TXV without external equalizer, because the distributor is installed between the valve outlet and the evaporator inlet (See fig. 5). 1 This change from 10°F to 12°F in the operating superheat is caused by the change in the pressure-temperature characteristic of R-12 at the lower suction pressure of 27 psig. 4 Thermal Expansion Valves Location of External Equalizer If individual suction lines from the separate evaporator outlets to the common suction line are short, then install the external equalizer lines into the separate evaporator suction headers, or as described in the preceding paragraph. As pointed out earlier, the external equalizer line must be installed beyond the point of greatest pressure drop. Since it may be difficult to determinate this point, as a general rule it is safest to connect the equalizer line to the suction line at the evaporator outlet on the compressor side of the remote bulb location. (See fig. 4 & 5). When the external equalizer is connected to a horizontal line, always make the connection at the top of the line in order to avoid oil logging in the equalizer line. When the pressure drop through the evaporator is known to be within the limits defined on page 2, it is permissible to install the external equalizer connection at one of the return bend midway through the evaporator. Such an equalizer location will provide smoother valve control particularly when the TXV is used in conjunction with an Evaporator Pressure Regulator. However, in all case where any type of control valve is installed in the suction line, the external equalizer line for the TXV must be connected on the evaporator side of such a control valve or regulator. On a multi-evaporator system including two or more evaporators each fed by a separate TXV, the external equalizer lines must be located so that they will be free from the effect of pressure changes in the evaporators fed by other TXV. At no time should the equalizer lines must be joined together in a common line to the main suction line. Do not under any circumstance cap or plug the external equalizer connection on a TXV, as it will not operate. If the TXV is furnished with an external equalizer feature, the external equalizer line must be connected. Superheat A vapor is said to be superheated whenever its temperature is higher than the saturation temperature corresponding to its pressure. The amount of the superheat equals the amount of the temperature increase above the saturation temperature at the existing pressure. For example, a refrigeration evaporator is operating with Refrigerant 134a at 35 psig suction pressure (See fig. 6). The Refrigerant 134a saturation temperature at 35 psig is 40°F. As long as any liquid exist at this pressure, the refrigerant temperature will remain 40°F as it evaporates or boils off in the evaporator. As the refrigerant moves along in the coil, the liquid boils off into a vapor, causing the amount of liquid present to decrease. All of the liquids are finally evaporated at point B because it has absorbed sufficient heat from the surrounding atmosphere to change the refrigerant liquid to a vapor. The refrigerant gas continues along the coil and remains at the same pressure (35 psig); however, its temperature increases due to continued absorption of heat from the surrounding atmosphere. When the refrigerant gas reaches the end of the evaporator, (See point “C”) its temperature is 50°F. This refrigerant gas is now superheated and the amount of superheat is 10°F. (50°F minus 10°F). 5 The degree to which the refrigerant gas is superheated depends on (1) the amount of refrigerant being fed to the evaporator by TXV and (2) the heat load to which the evaporator is exposed. Thermal Expansion Valves Adjustment of Superheat superheat, the recommended practice is to install a calibrated pressure gauge in a gauge connection at the evaporator outlet. In the absence of a gauge connection, a tee installed in the TXV external equalizer line can be used just as effectively. The function of a TXV is to control the superheat of the suction gas leaving the evaporator in accordance with the valve setting. A TXV which is performing this function within reasonable limits, it can be said to be operating in a satisfactory manner. A refrigeration type pocket thermometer with appropriate bulb clamp may be used or more effective is the use of a service type potentiometer (electric thermometer) with thermocouples (leads & probes). Good superheat control is the criterion of TXV performance. It is important that this function be measured as accurately as possible, or in the absence of accuracy, to be aware of the magnitude and direction of whatever error is present. The temperature element from your Temperature Meter should be taped to the suction line at the point of remote bulb location and must be insulated against the ambient. Temperature elements of this type, as well as thermometers, will give an average reading of suction line and ambient if not insulated. Assuming an accurate gauge and Temperature Meter, this method will provide sufficiently accurate superheat readings for all practical purpose. Superheat has been previously defined as the temperature increase of refrigerant gas above the saturation temperature at the existing pressure. Based on this definition, the pressure and temperature increase of the refrigerant suction gas passing the TXV remote bulb are required for an accurate determination of superheat. Thus, when measuring Common Incorrect Methods of Reading Superheat On installation where a gauge connection is not available and the valve is internally equalized there are two alternate methods possible. Both of these methods are approximation only and their use is definitely not recommended: unknown and will vary with the load. For this reason, the two-temperature method cannot be relied on for absolute superheat readings. It should be noted that the error in the two-temperature method is negative and always indicates a superheat lower than the actual figure. 1. The first of these is the two-temperature method, which utilizes the difference in temperature between the evaporator inlet and outlet as the superheat. This method is in error by a temperature equivalent of the pressure drop between the two points of temperature. 2. The other method commonly used to check superheats involves taking the temperature at the evaporator outlet and utilizing the compressor suction pressure as the evaporator saturation pressure. Where the pressure drop between the evaporator inlet and outlet is 1psi or less, the two-temperature method will yield fairly accurate results. However, evaporator pressure drop usually is an The error here is obviously due to the pressure drop in the suction line between the evaporator outlet and the compressor suction gauge. 6 Thermal Expansion Valves On packaged equipment and close-coupled installations, the pressure drop and resulting error are usually small. However, on large builtup systems or systems with long runs of suction lines, considerable discrepancies can result. trouble call is due to the use of improper methods of instrumentation rather than any malfunction of the valve. One other error that will be present when trouble shooting in mountain areas (such as Denver, Colorado or Salt Lake City, Utah), is the low gauge pressure compared to sea level readings. Use a Pressure-Temperature chart that has correct readings such as Emerson Climate Technology Flow Control’s 5,000 ft. correction pocket chart. Since estimates of suction line pressure drop are usually not accurate enough to give a true picture of the superheat, this method cannot be relied on for absolute values. It should be noted that the error in this instance will always be positive and the superheat resulting will be higher than the actual value. Restating the above, the only method of checking superheat that will yield an absolute value involves a pressure and temperature reading at the evaporator outlet. Other methods employed will yield a fictitious superheat that can prove misleading when used to analyze TXV performance. By realizing the limitations of these approximate methods and the direction of the error, it is often possible to determine that the cause of the Factors Involved in Valve Selection possible vertical lift. The only exception to this is where the valve is located considerably below the receiver and static head built up is more than enough to offset frictional loses. The liquid line should be properly sized giving due consideration to its length plus the additional equivalent length of line due to the use of fitting and hand valves. When a vertical lift in the liquid line is necessary, and additional pressure drop, due the loss in static head, must be included. Proper TXV size is determined by the BTU/HR or tons load requirement, the pressure drop across the valve, and the evaporator temperature. It should not be assumed that the pressure drop across the TXV is equal to the difference between discharge and suction pressures at the compressor. This assumption will lead to incorrect sizing of the valve. The pressure at the TXV outlet will be higher than the suction pressure indicated at the compressor, due the frictional losses through the distribution header, evaporator tubes, suction lines, fittings, and hand valves. The pressure drop across the TXV will be the difference between the discharge and suction pressures at the compressor less the pressure drops in the liquid line, through the distributor, evaporator, and suction line. ASHRAE tables should be consulted for determining pressure drops in liquid and suction line. The pressure at the TXV inlet will be lower than the discharge pressure indicated at the compressor, due to frictional losses created by length of liquid line, valves and fittings, and 7 Thermal Expansion Valves liquid refrigerant to ensure solid liquid entering the TXV at all time!! Since the capacity and the performance of the TXV is based on solid liquid entering the valve, careful consideration must be given to the total pressure drop in the liquid line to determine if there will be sufficient sub cooling of the liquid refrigerant to prevent the formation of flash gas. If the sub cooling of the liquid refrigerant from the condenser is not adequate then a heat exchanger, liquid sub cooler, or some other means must be used to obtain enough sub cooling of the Emerson Climate Technologies has prepared extended capacity tables for use with the above mentioned conditions in mind. These extended tables can be found in the catalog section of each type of Emerson’s TXVs. Therefore, where possible always select TXV for actual operating conditions rather than nominal valve capacities. Application In general, for best evaporator performance, the TXV should be applied as close to the evaporator as possible and in such location as to make it easily accessible for adjustment and servicing. On pressure drop and centrifugal type distributors, apply the valves as close to the distributor as possible. (See fig.7) The “T” Series valves [with the exception of the “W”-(MOP), G(MOP) or GS-(MOP) gas charged types] may be installed in any location in the system. The gas charged type must always be installed in such a manner that the power assembly will be warmer than the remote bulb. The remote bulb tubing must not be allowed to touch a surface colder than the remote bulb location. If the power assembly or remote bulb tubing becomes colder than remote bulb, the vapor charge will condense at the coldest point and remote bulb will lose control. Remote Bulb Location sure that remote bulb of each valve is applied to the suction line of the evaporator fed by that valve. Since evaporator performance depends largely upon good TXV control, and good valve control depends upon response to temperature change of the refrigerant gas leaving the evaporator, considerable care must be given to types of remote bulbs and their locations. In general, the external remote bulb meets the requirement of most installations. It should be clamped to the suction line near the evaporator outlet, and on a horizontal run. If more than one Thermal Expansion Valve is used on adjacent evaporators or evaporators section, make Clean the suction line thoroughly before clamping the remote bulb in place. When a steel suction line is used, it is advisable to paint the line with aluminum paint to minimize future corrosion and faulty remote bulb contact with the line. On lines under 7/8” OD the remote bulb may be installed on top of the line. With 7/8” OD and over, the remote bulb should be installed at the position of about 4 or 8 o’clock. (See fig. 8 on next page) 8 Thermal Expansion Valves If it is necessary to protect the remote bulb from the effect of an air stream, after it is clamped to the line, use material that will not absorb water with evaporator temperatures above 32°F. Below 32°F cork or similar material sealed against moisture is suggested to prevent ice logging at the remote bulb location. Remote Bulb Well is trapped (See fig. 10). If the liquid refrigerant collects at the point of remote bulb location, the Thermal Expansion Valve operation will be erratic and possibility the valve will be thought to be defective. When it becomes desirable to increase the sensitivity of the remote bulb, it may be necessary to use a remote bulb well. This is a particularly true for short coupled installations and installations with large suction lines (2 1/8” OD or larger). Remote bulb wells should be used (1) when very low superheats are desired and (2) where converted heat from warm room can influence the remote bulb. (See fig. 9). Large fluctuations in superheat in the suction gas are usually the result of trapped liquid at the remote bulb location. Even on properly designed suction lines, it’s sometimes necessary to move the remote bulb a few inches either way from the original location to obtain best valve action Do not under any circumstances locate either type of remote bulb in a location where the suction line On multi circuit evaporators fed by one valve, locate the remote bulb away from immediate suction outlet at point where the suction gas from several parallel circuits has had an opportunity to mix in the suction header. Be sure to pull up tight on clamps so that the remote bulb makes good contact with the suction line. NEVER APPLY HEAT NEAR REMOTE BULB LOCATION WITHOUT FIRST REMOVING THE REMOTE BULB!! 9 Thermal Expansion Valves Hunting “Hunting” of TXVs can be defined as the alternate overfeeding and starving of the refrigerant flow to the evaporator. It is recognized by extreme cyclic changes in both, the superheat or the refrigerant gas leaving the evaporator and the evaporator or suction pressure. “Hunting” is a function of the evaporator design, length and diameter of tubing in each circuit, load per circuit, refrigerant velocity in each circuit, temperature difference (TD) under which the evaporator is operated, arrangements of suction piping and application of the Thermal Expansion Valve remote bulb. “Hunting” can be minimized or eliminated by the correct rearrangement of the suction piping, relocation of the bulb and use of the recommended remote bulb and power assembly charge for the TXV. Operation at Reduced Capacity The conventional TXV is a self-contained direct operated regulator which does not have any built in anticipating or compensating factors. As such it is susceptible to “Hunting” for causes which are peculiar to both valve design and the design of the system to which it is applied. The ideal TXV flow rate would require a valve with perfect dynamic balance, capable of instantaneous response to any change in the rate of evaporation (anticipation) and with a means of preventing the valve from over shooting the control point due to inertia (compensation). With these features a TXV would be in phase with the system demand at all times and “Hunting” will not occur. A conventional TXV does not have built in anticipating or compensating factor. This means that a time lag will exist between demand and response, along with the tendency to over shoot the control point. Thus the conventional TXV may get out of phase with the system and “Hunt”. Assume that increase in load occurs, causing the superheat of suction gas to increase. The time interval between the instant the remote bulb senses the increase and causes the valve pin to move into opening direction allows the superheat of the gas to increase still further. In response to the rising superheat during the time lags, the valve has moved further in the opening direction, overshot the control point and admitted more refrigerant to the evaporator that can be boiled off by load. During the time lag between the instant the remote bulb senses the returning liquid refrigerant and the valve responds by moving in the closing direction, the valve continues to over-feed the coil. Thus, when the valve does move in a closing direction, it will again overshoot the control point and remain in an overly throttled position until most of the liquid refrigerant has left the evaporator. The ensuing time delay before the valve moves in the opening direction allows superheat of the suction gas to again rise beyond the control point. This cycle, being selfpropagating, continues to repeats itself. 10 Thermal Expansion Valves Experience has shown that a Thermal Expansion Valve is more liable to “Hunt” at low load conditions when the valve pin is close to the valve seat. This is generally thought to be due to an unbalance between the forces which operate that valve. In addition to the three main forces that operate the Thermal Expansion Valve the pressure difference across the valve port acts against the port area, and depending on valve construction, tends to force the valve either open or closed. When operating with the pin close to seat, the following will occur: With the valve closed, we have liquid pressure on the inlet side of the pin and evaporator pressure on the outlet. When the valve starts to open allowing flow to take place, the velocity through the valve throat will cause a point of lower pressure at the throat, increasing the pressure difference across the pin and seat. This sudden increase in pressure differential while acting on the port area will tend to force the valve pin back into the seat. When the valve again opens, the same type of action occurs and the pin bounces off the seat with a rapid frequency. This type of phenomenon is more frequently encountered with the larger single ported TXVs as the force due to the pressure differential is magnified by the larger port area. We have seen that a TXV may “Hunt” due the lack of anticipating and compensating features and an unbalance in the equilibrium forces at lower end of its stroke. We know from some experience that a TXV, when intelligently selected and applied, will overcome these factors and operate with virtual no ”Hunt” over a fairly wide load range. Single ported TXVs will generally operate satisfactory to somewhat below 50% of nominal capacity but it’s again dependant on evaporator design, refrigerant piping, size and length of evaporator, and rapid changes in loading. Nothing will cause a TXV to hunt quicker than unequal feeding of the parallel circuits by a distributor or unequal air loading across the evaporator circuits. Double-Ported Balanced Thermo Valves We have seen (above) that the flow pattern of the single ported TVX can cause difficulties at low load conditions. The larger the port area (larger tonnages) the more prone is the valve to hunt. Certain type of Emerson’s TXVs have been designed with two ports or “double ported”. The inlet is so designed as to create a “counter flow” against the double-ported balance ported valves and thus eliminate any unbalance across the two ports. (See fig. 11) Flow through the upper port enters the upper radial holes of the cage seat assembly, moves upward and across the upper seat, down through the internal passage of the spool and out the holes in bottom of the spool. The pressure drop across this port exerts a force in a closing (upward) direction. Flow through the bottom port enters the lower radial holes of the cage seat assembly and moves downward through the port formed by the cage seat and the valve spool. High-pressure liquid acts downward on the spool and the pressure drop across the spool and seat exert a force in an opening direction. Since the effective port area of both the upper and lower cage port is very nearly the same, the net force unbalance across them is negligible. This feature makes it possible for the double-ported cage assemblies to modulate over a much wider load range than was possible with the old style, single port valves. The reverse-flow valves provide satisfactory control at loads less than 15% of nominal valve capacity. Their performance is superior to any competitive product available. Actual field performance has proven the superiority of double-ported Emerson’s TXVs and their ability to reduce “Hunting” to a very minimum. 11 Thermal Expansion Valves TXV Charges Over the years or more precisely, since Emerson Climate Technologies produced the first valve for ammonia in 1925, the matter of a proper power charge in the thermal sensing element has been a major concern. Liquid charges, gas charges, cross liquid charges, cross vapor charges, high temperature charges, ultra-low temperature charges, commercial charges, etc. all have been tried with varying degrees of success. An explanation of each type of power element charge would be in order except for the fact that for the past several years Emerson has had and still uses a rather unique power element charge that covers nearly all types of applications in temperature ranges of –20°F to +50°F. This “C” charge is available for R-134a, R22, R404, R507 and others. The “C” Charge the refrigeration unit pulled down in temperature resulting in the necessity to make readjustment at times. The cross charges (C & Z) usually would create conditions of high superheat upon start up and reduce the superheat as the unit pulled down thus again the need to adjust as the unit got colder. Between the operating conditions of – 20°F to +50°F the straight C charge rarely if ever needs to be re-set after a satisfactory superheat has been established. In fact, the straight C charge as received from the factory will not have to be re-set at all in the majority of cases. Unlike certain past charges; i.e.: G, GA and Q, the straight C charge (no MOP) will not lose control in cross-ambient conditions. This is to say that if the TXV body should get colder than sensing bulb the gas charge will migrate from the bulb to the valve head and thus become inoperative. The straight C charge absolutely will not “cross ambient” or lose control as in the above conditions. The old liquid (L) and gas (G) charges could create conditions of low superheat upon start up and would increase the superheat conditions as M.O.P. Once below the MOP, the TXV will re-open and feed in a standard manner or until such time as there is an overload again. Maximum Operating Pressure (sometimes referred to as Motor Overload Protection) is the ability of a TXV to close down, starve, or completely shut off if the suction pressure should approach a dangerously high predetermined limit condition. A condition such as to cause overheating a suction cooled compressor or loading the crankcase with too dense a vapor pressure. The C charge can be supplied with the MOP feature if needed for system protection. This need rarely occurs in modern day refrigeration except such conditions as immediately after defrost or on gasoline driven compressors such as truck refrigeration. With the TXV in a closed condition due to MOP the compressor has a chance to gain on the excess low side pressure and pull the suction back down to satisfactory operating conditions. 12 CAUTION: The C charge with MOP will be effected by extreme cross ambient conditions. If this condition should exist install an electric strip heater around the top part of the TXV. Thermal Expansion Valves Emerson TXV Catalog Solder Bodies For exact valve selection (ie: refrigerant tonnage, connections, equalizer style, cap tube length, adjustment and proper application, air conditioning, commercial, low temperature) refer to Emerson catalog. When soldering, remove power assembly, cage assembly, and all gaskets. Keep heat away from all valve parts, except body flange. Use a brazing alloy or low temperature solder. Be careful to retain all the solder in the connection. Direction of Flow For integral (one-piece) body types be sure to use plenty of wet rags or chill blocks and direct flame away from valve body. Be sure the flow of refrigerant is in the direction indicated by the arrow on the valve body. Adjusting T-Series Valves To adjust, remove seal cap on side of valve and turn adjusting stem. Turning stem to right decreases flow and raises superheat. Turning stem to left increases flow and lowers superheat. Adjust all “T” series 2 turns (1°F) at a time. Adjust each valve separately and wait between each adjustment to observe all results. Always tighten any loosened connections and replace seal cap. It should be noted that superheat adjustment will change the M.O.P. point 13 Thermal Expansion Valves Installation & Service Data Emerson “T” series TXVs have three component parts. Power Assembly, Cage Assembly, and Body Flange. There are no working parts in the body flange. It is never necessary to break the line connections to service the valve. Emerson her- metic integral TXVs are assembled units which cannot be taken apart in the field; except that the strainer may be easily removed for inspection and cleaning by disconnecting the valve from the liquid line and removing the inlet flare connection. Servicing To inspect, clean, or replace parts on all take-apart types remove the two cap screws, lift off the power assembly, and remove cage assembly. Be sure gaskets are replaced in proper places when reassembling valve (See Figure 12). When assembling External Adjustment valves (TCL, TJL, TER, TIR or THR) be sure the two lugs on the cage assembly fit into the grooves provided for them in the power assembly (See ,Figure 13). Don’t force valve together. Make the cage fit properly before tightening body flange. See EMERSON’s “Service Hints” for detailed procedure recommended for “trouble shooting” a refrigeration or air conditioning system. Solenoid Liquid Stop Valves The TXVs, while produced as a tight seating device, cannot be depended upon for positive shut off since the seating surfaces are exposed to dirt, moisture, corrosion, and erosion. In addition, if the remote bulb is installed in a location where during the “off’ cycle it is influenced by a higher ambient temperature than the evaporator, the valve will open during a portion of the “off” cycle, and admit liquid to the evaporator. For these reasons the installation of a Solenoid Liquid Stop Valve ahead of any TXV is highly recommended. Filter-Driers for System Protection To protect the precision working parts of control valves from dirt and chips which can damage them and render them inoperative, and to protect the entire system from the damaging affects of moisture, sludge and acids, a filter-drier should be installed on every system. The EMERSON “EK” FILTER DRIER provides the finest possible protection available with superior filtering action and the removal of moisture, sludges, corrosive acids and waxes. 14 Thermal Expansion Valves Pressure Switch Setting On valves with M.O.P.- Pressure Switch must be set to cut in at a pressure lower than M.O.P. rating of the TXV. Factory Superheat Setting Unless otherwise specified, all valves will be preset at the factory at a bath temperature which is predetermined by the charge symbol and/or the MOP rating. The bath temperature at which the valve superheat has been set is coded alphabetically in the superheat block on the valve nameplate, as shown in Fig. 15. Thus a valve with “10A” stamped in the nameplate superheat block has been set for 10°F static superheat with a 32°F bath. In like manner, a valve stampled “10C” has been set for 10° of static superheat with a 0°F bath. When ordering a valve for an exact replacement, specify the code letter as well as the superheat setting desired. When ordering for general stock, it will not be necessary to specify either the superheat or the code letter, since the standard setting will cover most applications and minor superheat adjustments may be made in the field. Fig. 15 REFRIGERANT CODE NAMES ARI Standard 750-81 recommends the following color coding of the TXVs: R-12 R-22 R-502 R-134a R410A R404A Yellow Green Orchid Light Blue Rose Orange 15 Bath Temperature Code Letter +32°F +10°F 0°F -10°F -20°F A B C D E Thermal Expansion Valves TXVREPLACEMENTCHARGESYMBOLSCROSSREFERENCE OLD BULB CHARGES VS. NEW REPLACEMENT BULB CHARGE AIR CONDITIONING OLD CHARGE REPLACEMENT FW FG55 FW55 FQ55 FGA FLA FGS FWS FC FWS HC HW HG100 HW100 HQ100 HGA HLA HW85 HGS HWS HCA HC HW85 HWS COMMERCIAL REFRIGERATION OLD CHARGE REPLACEMENT REFRIGERANTR12/R134a F OR FL FC FC FW FG35 FW35 FW35 FQ35 — — FGS35 FGS35 FWS FWS REFRIGERANT R22 H OR HL HC HW HG65 HW65 HQ65 HC HW65 — — HGS65 HGS65 HWS HWS REFRIGERANTR502/R404A/R507 RL RC/SC/PC RW RW65 RW65 RWS RWS LOWTEMPERATURE OLD CHARGE REPLACEMENT — — FWZ — FW15 FW15 — FZ — FW15/MW15 — — FWS FZ/MZ FX FWS FZ/MZ FX — — HWZ — HW35 HQ35 — HZ — HW35 — — HWS HZ HX HWS HZ HX — — RWZ RZ RW35 RW45/SW45 RWS RWS RWS RZ RZ/SZ/PZ NOTE NOTE: ALL OTHER CHARGE SYMBOLS MUST BE REPLACED WITH AN IDENTICAL MODEL OR AT THE OPTION OF THE ALCO TECHNICAL SERVICE DEPARTMENT WHO MAY MAKE ENGINEERING AUTHORIZED SUBSTITUTION OF EQUIVALENT TYPE TO PROVIDE EQUIVALENT OPERATION AND PERFORMANCE. NOTE NOTE: FOR FIELD REPLACEMENT PURPOSES, HC CAN BE USED TO REPLACE HCA HCA. RW RW110 RWS RC/SC/PC 16 Thermal Expansion Valves Servicing Thermal Expansion Valves The How, The Why, The When! Thermal Expansion Valves (TXV) are critical parts of a heat pump, refrigeration, or air conditioning system. Proper sizing, installation and adjustment of a TXV makes the difference in whether the system operates properly or causes callbacks. TXV Meters the Flow Metering the refrigerant flow to the evaporator is the sole function of a TXV. What’s critical is that it must meter that flow at the same rate it is being vaporized by the heat load. To do this, it keeps the coil supplied with the proper amount of refrigerant to maintain the right superheat of the suction gas leaving the evaporator. Superheat: The Measurement Fig 1. How thermal expansion valve controls refrigerant flow. Figure 1 explains how it works. At A, hot, highpressure liquid refrigerant enters the TXV. At B, cold, low-pressure liquid, plus flash gas, enters the evaporator. At C, the entire liquid refrigerant has been boiled off, or vaporized by the heat load (latent heat). Between C and D, the vapor temperature increases dramatically as further heat load is applied (sensible heat). At this point, the gas is superheated above its saturation temperature. At D, suction line temperature of the superheated gas is monitored by the sensing bulb, which signals the TXV to open or close accordingly. 17 Thermal Expansion Valves How To Measure Accurately Because good superheat control is the criterion of TXV performance, accurate measurement is vital. That involves four steps, shown in Figure 2: Step A- Determine the suction pressure at the evaporator outlet with an accurate gage. If there is no gage connection, a tee installed in the valve’s external equalizer line can be used. Step B- Refer to a temperature pressure chart for the refrigerant used in the system, and determine the saturation temperature at the observed suction pressure. Step C- Measure the temperature of the suction line at the remote sensing bulb location. Fig 2. Measuring superheat for proper valve performance Servicing, Step One This can be accomplished by a “strap on” thermometer or an electric device similar to an “Annie” or “Simpson” meter. Be certain the spot chosen for measurement is clean, to ensure accurate readings. Step D- Subtract the saturation temperature determined in Step B from the suction gas temperature measured in Step C. The difference is the operating superheat. If the test indicates that a valve adjustment is required, remove the seal cap covering the adjusting stem. Rotate the stem clockwise to decrease refrigerant flow through the valve and increase superheat; counter clockwise increases flow and decreases superheat. When to Use Which Valve Some servicemen seem rather uncertain as to when to use an internally equalized thermal expansion valve and when to use an externally equalized one. Our experience has shown that whenever pressure drop through the evaporator reaches 3psi in a 3-ton (or 3-hp) air-conditioning system (evaporator temperature range of 30°-50°F), or 2psi in a 2-ton commercial refrigeration system (evaporator temperature of 10°-30°F), or 1psi in a 1-ton low temperature system (evaporator temperature of zero F or below), an externally equalized valve should be used. On this basis, an externally equalized valve would automatically be the selection for any system in excess of 3 tons, regardless of the application. 18 Thermal Expansion Valves More Rules of Thumb Always use an externally equalized valve whenever a refrigerant distributor is incorporated in the system. Good temperature feedback to the TXV is vital for control, so place the bulb where it will provide the best possible feedback. Where to Place the Bulb Fig 3. How to place remote bulb in relation to suction line size Figure 3 shows the ideal placement (horizontal) of the bulb in relation to suction line size. Never put the bulb at 6 o’clock because it may sense the temperature of the oil flowing through the pipe, rather than the temperature of the refrigerant. And be sure the bulb location is on a freedraining suction line. Emerson’s “T” Series: The Simple Answer Choosing the proper TXV for the specific system remains the first step in good service and no callbacks. Emerson’s exclusive “Take-A-Part” series remains the most versatile TXV on the market and is the only valve you can service in minutes with one wrench. And, with its long list of interchangeable power heads, cages and body flanges, you can mix and match from stock with over 1200 combinations to fit your job exactly. On anything from heat pumps to commercial units, 1/4 to 100 ton capacities. Be sure to carry a few Emerson “T” series Take-A-Part thermal expansion valves with you on every call. See your Emerson Wholesaler for complete specs, and for a look at the complete line of Emerson precision controls for all your refrigeration and air conditioning jobs. 19 Emerson’s TXV Thermal Expansion Valves Thermal Expansion Valve Charges: What They Do, and How They Do It. The basic function of a thermal expansion valve is to control super-heat. But there are several types of thermal valves, and several types of charges in them. Each has its own specific use; understanding the power element charge and how it affects the pressure to the power diaphragm is basic to good service. Types of Charges You’ll Meet About Liquid Charges Several basic types of charges are in common use today. Most common are: liquid charge, gas charge, liquid cross-charge, gas cross-charge, and adsorption charge. Here, the power element contains the same refrigerant as the system in which the valve is used. In manufacturing, it is put into the remote bulb in a liquid state. Volume is controlled so that within the design temperature range of the power element, some liquid always remains in the bulb. So power element pressure is always the saturation pressure corresponding to the temperature of the remote bulb. Liquid charges have both advantages and disadvantages. They include: not subject to cross-ambient control loss; little or no superheat at start-up; superheat increases at lower evaporator temperatures, and slow suction pressure pull down after start-up. Liquid Cross Charges When a liquid cross-charge is used, the power element contains a liquid refrigerant different from the system refrigerant. The pressure temperature curve of the charge crosses the curve of the system refrigerant (hence, cross-charge). Their advantages include: • Moderately slow pull down • Insensitive to cross-ambient conditions • Dampened response to suction line temperature changes (minimizes tendency for valve “hunting”) • Superheat characteristics can be tailored for special applications Gas and Gas Cross-Charges Using a gas charge in place of a liquid alters the operational characteristics, because gas compresses. At some predetermined temperature, the gas in the remote bulb becomes superheated, limiting the force it exerts. This produces higher superheat at higher evaporator loads and is labeled the Maximum Operating Pressure (MOP) effect. Fig 1. Typical cross-charge pressure/temperature relationship Note: Emerson charges “C” and “Z” are liquid cross-charges. Any MOP point temperature depends on how that bulb was initially charged and where it will be used. All gas charges are susceptible to cross-ambient control loss when the power element is colder than the remote bulb. They are inherently faster to respond, but tend to “hunt” for the proper operating level, so a ballast is often added to the remote bulb to minimize that tendency. As in liquid charges, the remote bulb can be filled with the same refrigerant as the system refrigerant. Or, it can be filled with a different refrigerant, producing a gas cross-charge. 20 Thermal Expansion Valves Adsorption Charges The final type of charge is adsorption. In adsorption, solids hold large quantities of gas, not by taking them into the body of the solid, as in absorption, but by gathering them and holding them on the surface of the solid without chemical reaction. The vapor penetrates into the cracks and furrows of the solid, allowing considerably greater capacity than possible with absorption. Fig 2. What happens with an adsorption charge The advantage of an adsorption charge is that in a fixed volume, the quantity of vapor adsorbed varies with the temperature and the system. So it can be used to exert operating pressure as a function of temperature. Typical adsorbents include: charcoal, silica gel, activated alumina. Where to Use Each Type The chart on the left can help match the charge to the application • Adsorption charge “W” – air conditioning, commercial medium temperature refrigeration, chillers • Liquid cross-charges “C” and “l”commercial (medium and low temp.) refrigeration, transport refrigeration, ice makers Other types of charges available include: Liquid charge “L” - icemakers, pilots, liquid injection valves; Gas charge “G” - air conditioning (including mobile), water chillers; Gas cross charge “B” – heat pumps. Fig 3. Typical operating ranges of today’s most common TXV charges If you would like copies of this chart for your wall, ask your participating Emerson Wholesaler. Emerson Delivers The Right Charge Since Emerson invented the modern control valve in 1925, we have carefully developed new charges to deliver closer control. Specific Emerson Thermal Expansion Valves are available with a variety of charges, developed in our own laboratory, each designed for long life and close control in specific applications. Ask Your Emerson Wholesaler When you plan to replace an expansion valve, check with your Emerson Wholesaler for the quality Thermal Expansion Valve that best fits your application. 21 Thermal Expansion Valves Troubleshooting Thermal Expansion Valves Part 1: Causes of Low Suction Pressure When a thermal expansion valve malfunctions, the cause may not be the valve itself. So many other components of the refrigeration or air conditioning system may affect it that the key is proper diagnosis of the problem. We can’t adequately cover the entire subject in one Tech Tips. So we’ll start with problems resulting in low suction pressure. A second Tech Tips deals with problems delivering high and fluctuating suction pressure. Low Suction Pressure With High Superheat Generally, this is caused by a flow restriction through the evaporator. If the thermal expansion valve itself is limiting the flow, look for these probable causes: 1. Inlet pressure might be too low because of excessive vertical lift; or the liquid line might be too small; or condensing temperature might be too low. All three result in inadequate pressure differential. Solution: Increase head pressure, or replace the liquid line with the proper size specified by the manufacturer. 2. There may be gas in the liquid line from pressure drop, an insufficient charge or non condensable gases in the system. Use a sight glass, or listen for a characteristic whistling sound at the expansion valve. Solution: Depending on the cause, either add charge to the system or purge the non condensable, clean the strainers and replace the filter-driers, check for proper line size, or increase head pressure, decrease temperature (provide sufficient sub-cooling) to assure solid liquid at the valve inlet. 3. The valve might be restricted by the pressure drop through the evaporator. Solution: Switch to an Emerson thermal expansion valve with an external equalizer. 4. The valve orifice might be plugged. Solution: If ice (moisture) or wax plugs it, there’ll be a sudden suction line pressure rise after the system is shut down and warms up or the valve body is artificially warmed. Moisture and dirt problems are remedied by an Emerson EK filter-drier. Wax or oil buildup is usually caused by the wrong type of oil. Replace it with the proper oil. 5. Superheat adjustment may be set too high. Solution: Readjust it to the manufacturer’s specifications, following the instructions supplied with the valve. Fig. 2 Basic forces at work on TXV 6. The valve’s power assembly might have lost charge or failed. Solution: Either replace the assembly or the entire valve. 7. In a cross-ambient condition, a gas-charged power assembly or the remote bulb tubing may become colder than the sensing bulb, and the bulb loses control. Solution: a) insulate or provide artificial heat to the power assembly; b) replace with an Emerson Liquid Cross Charged Valve. 8. The system’s filter screens might become clogged. Solution:Clean all filter screens. 22 Thermal Expansion Valves Something other than the thermal expansion valve could cause a restriction. If so, you’ll usually find frost or lower than normal temperatures at the restriction point. Look for these probable causes: 1. Strainers or filter-driers could be clogged or too small. Solution: Replace or clean all the strainers, and then add an Emerson EK filter-drier to the system. 2. A solenoid valve could be malfunctioning or failed. Solution: Either way, replace it with the proper Emerson solenoid valve. 3. The service valve at the liquid receiver, a hand valve, or the discharge/suction service valve might be too small or not fully opened. Solution: Repair or replace the faulty valve if you determine it can’t be fully opened, and replace any undersized valves with the correct-sized unit. Fig 3. Highly efficient Emerson’s EK Liquid line filter-drier Protect the System No matter what the cause, every time you provide major service to any system, be sure to protect it (and reduce callbacks) by installing an Emerson EK liquid line or an Emerson ASD suction line filter-drier. You’ll be glad you did. 4. Miscellaneous problems could cause trouble, like plugged lines, too small liquid lines and suction lines. Solutions are self-explanatory, once you have determined the cause. Low Suction Pressure With Low Superheat Low pressure and low superheat usually mean the system has poor distribution or inadequate evaporator loading. Look for these probable causes: 1. When distribution is poor in the evaporator, liquid can short-circuit along favored passes and throttle the valve before all passes are properly charged. Solution: Clamp the power assembly to a free draining suction line. Clean the line before clamping the bulb in place. Install a distributor and balance the evaporator load distribution. 3. The evaporator may be too small, demonstrated by excessive ice formation. Solution: Install the proper-sized evaporator. 4. Low air flow resulting from plugged filters or an inoperative fan motor. Solution: Clean or replace filter. Check fan motor speed and repair or replace. There are additional possibilities but generally you will find that these are the major problems associated with low suction pressure. 2. The compressor can be oversized, or it can be running too fast due to a wrong-size pulley. Solution: Provide compressor capacity control for oversize; change to the proper-sized pulley. 23 Thermal Expansion Valves Troubleshooting Thermal Expansion Valves Part 2: Causes of High Suction Pressure When troubleshooting a thermal expansion valve malfunction, the key to correcting it is knowing how to diagnose the problem. And the cause might not be the valve itself. So many other components of the refrigeration or air conditioning system may affect the valve that it is impossible to adequately cover the entire subject in one Tech Tips. In a previous Tech Tips we covered problems resulting in Low Suction Pressure. This Tech Tips covers High and Fluctuating Suction Pressure. High Suction Pressure With High Superheat High Suction Pressure With Low Superheat Generally, this is caused by an unbalanced system due to an oversized evaporator, undersized compressor, and/ or a high load on the evaporator. Either way, the load will be in excess of design conditions. Solution: The system must be balanced by increasing compressor size or decreasing evaporator size. Test system capabilities with proper meters. Your Emerson Wholesaler can supply a chart listing proper temperature pressure relationships for all popular refrigerants to help you. Several system conditions cause this problem. Look for these probable causes: A second cause of high suction pressure and high superheat can be leaking compressor valves. Solution: Test compressor and replace valves, or compressor. 1. The compressor may be undersized. Solution: Test the system’s capacity and replace with specified compressor size. 2. The valve superheat setting may be too low. Solution: Determine the suction pressure with an accurate gauge. Determine the saturation temperature at the observed suction pressure. Measure the suction gas temperature at the remote bulb by taping a thermocouple to the bulb. Then subtract the saturation temperature from the remote bulb temperature to determine the superheat of the gas. Follow the valve manufacturer’s directions to adjust superheat to the proper setting. 3. There may be gas in the liquid line (from pressure drop or an insufficient charge) with an oversized TXV. Solution: Replace the TXV with a proper-sized valve and then correct the cause of the “flash gas” (see Tech Tips TT-01285 on Low Suction Pressure Causes). 4. The valve may be held open by foreign material at the seat with liquid flood-back. Solution: Clean or replace the damaged parts. Then install an Emerson EK filter-drier to remove all foreign material from the system. 5. Either the diaphragm or the bellows in a constant pressure (automatic) TXV may have ruptured with liquid flood-back. Solution: Replace the valve. 6. The valve’s external equalizer line may be plugged, or capped. Solution: Clean a plugged equalizer, or repair it. Or, completely replace the valve with one having a correct equalizer. Fig 1. Emerson expansion valve for small refrigeration systems 7. Moisture in the line may be freezing the valve open. Solution: Apply hot rags to the valve to melt the ice. Then install an Emerson EK filter drier to have a moisture24free system. Thermal Expansion Valves Causes of Fluctuating Suction Pressure Fluctuating pressure indicates a variety of possible causes: 1. Superheat adjustment may be incorrect. Solution: Adjust the superheat following guidelines in #2 under high suction pressure with low superheat, above. 2. The cause could be a trapped suction line. Solution: Install a “P” trap to allow for free drainage in the suction line. 3. Liquid refrigerant may flood back because of an improper distributor, uneven evaporator loading, or improperly mounted evaporator. Solution: Replace the faulty distributor; install power load distribution devices to balance air velocity evenly over the evaporator coils; finally, check the evaporator mounting to provide the proper angle. 4. The external equalizer lines may be tapped at a common source with more than one TXV in the same system. Solution:Each valve must have its own separate equalizer line going directly to an appropriate location on the evaporator outlet. See Figure 3 for an example. Fig 3. Recommended piping of suction lines to common main 5. Radical pressure differences across the TXV may be caused by excessive condenser or blower cycling. Solution: Check coil surfaces, control circuits, thermostat overloads, etc., and repair or replace any defective parts. There are additional possibilities, but these are the most common. Choose the Proper TXV Every manufacturer offers a variety of thermal expansion valves to match the many conditions you will meet in the field. If you have any questions about the proper size, consult your Emerson Representative. He can advise you and offer detailed information on which Emerson valve to select for any application. Fig 2. Basic refrigeration system schematic 25 Thermal Expansion Valves How to Select the Right Capacity TXV for the Job Assume you must install a new thermal expansion valve in a system because the old one failed and you don’t know the proper capacity valve. What do you do? Install a too large valve and you’ll get erratic performance or evaporator flooding. Too small and you get a starving condition which could result in compressor failure Don’t Trust Labels Box labels, valve labels, compressor labels all give you a rating. But it is a nominal rating based on a specific set of conditions determined by ARI or ASHRAE, and may be totally different than your job. Follow them blindly and you may end up with expensive callbacks. Extended Capacity Charts Each valve manufacturer has an extended capacity chart to help you determine exactly what valve goes in what application. To use them, you need to determine four basic facts: • • • • Refrigeration system load; Liquid temperature entering the valve; Saturated evaporator temperature; Pressure drop across the valve. Here’s how to obtain the information you need: 1. Refrigeration system load Determine the size of the system in BTU’s or Tons (12,000 BTU /hr. = 1 Ton). Check the system manufacturer’s literature, if available. If not, find the compressor rating on its label, but don’t try to match your valve to that rating, because the compressor’s rating may vary, depending on the desired temperature of the cooled space. Average evaporator temperature for air conditioning is 45°F; for refrigeration, it’s 15° to 20°F below the temperature of the coldest product stored. The capacity of the compressor in refrigeration may be considerably less than its nominal rating on the label. It’s only a guide to the true valve rating. Fig 1. Emerson TCLE 2HC, a typical thermal expansion valve. 2. Liquid temperature entering the valve With a strap-on thermometer, determine the temperature of the liquid entering the valve. Nominal valve capacities are established 100°F, vapor-free liquid entering the valve. If liquid temperature entering the valve is higher or lower, correction factors on the extended capacity chart will help you compensate. 3. Evaporator temperature If unknown, estimate the temperature of the evaporator, following the guidelines under (1.) above. It must be lower than the temperature required in the cooled space, or no heat transfer will take place. 4. Pressure drop across the valve Determine the difference between the pressure on the inlet side versus that on the outlet side of the valve, not the difference between the head pressure and the suction pressure, a common mistake. It may be necessary to estimate taking into consideration pressure drop in fittings, valves, driers, distributors, etc. 26 Thermal Expansion Valves Here’s An Example In Figure 2, we selected a nominal 2-ton Emerson TCL (E) 2FC TXV operating at +20°F. evaporator pressure, with a 175lb. Pressure drop - giving a capacity of 3.4 tons. Operating at liquid temperature of 110°F, the 3.4-ton capacity becomes 3.2 tons when multiplied by the .94 correction factor. In this case, a nominally-rated 2-ton valve has plenty of capacity for a 3-ton system. In the same situation, a nominally-rated 3-ton valve would actually be too big, delivering 4.7 tons and possibly flooding the evaporator. So, when you don’t know the exact valve size, take a few minutes to follow this scenario and you may save yourself some expensive call backs. If you would like an Extended Capacity Chart to help you in your work, ask your participating Emerson Wholesaler. Fig 2. Typical Extended Capacity Chart TCL(E) 2FC shown in the shaded bar Valve Capacities are based on 100°F vapor free liquid refrigerant entering the valve. To determine the capacities for other temperatures of vapor free liquid refrigerant entering the valve, multiply the capacity listed in the above chart by the correction factor listed here. Liquid Temperature Correction Factors Refrigerant Type R-12 R134a R-22 R404A Refrigerant Liquid Temperature (°F) 0 1.60 1.70 1.56 2.00 10 1.54 1.63 1.51 1.90 20 1.48 1.56 1.45 1.80 30 1.42 1.49 1.40 1.70 40 1.36 1.42 1.34 1.60 50 1.30 1.36 1.29 1.50 60 1.24 1.29 1.23 1.40 70 1.18 1.21 1.17 1.30 80 1.12 1.14 1.12 1.20 90 1.06 1.07 1.06 1.10 Fig. 3 Typical correction factor chart 27 100 1.00 1.00 1.00 1.00 110 120 130 140 .94 .88 .82 .75 .93 .85 .78 .71 .94 .88 .82 .76 .90 .80 .70 .50 Thermal Expansion Valves Balanced Port Valves: Old Solution to New Problems Back in the days when energy was cheap, refrigeration engineers would routinely overspec their systems. Often, condensing temperatures would run as high as 100°, using much more energy, but they allowed plenty of “slop” to compensate for a wide range of varying ambient conditions. And everyone was satisfied with the results. But times change. Many of today’s systems use base condensing temperatures in the range of 60° to 70°. They’re more efficient; they provide greater capacity; and they last longer. But they can also unbalance much more readily, changing superheat, capacity and efficiency, maybe even flooding the compressor. Balanced Port: Balanced System Cancelled Forces A useful solution to the unbalance problem is an idea that has been around for a long time, 30 years in fact, balanced port valves (sometimes called “double-port valves”). The difference in construction of the two types of valves makes all the difference. In the balanced port valve, Fig. C, a small shaft connects the valve pin to the closefitting rod above the line opening. It is equal in area to the effective port area. In effect, balanced-port valves “balance” the system by operating at a constant superheat over a wide range of head pressure and load variations. How It Works In a conventional expansion valve, Fig. B, with the flow direction such that inlet pressure is applied under the valve pin, as pressure increases, the valve tends to move in an opening direction. Conversely, when inlet pressure falls, the valve tends to move in a closing direction. This change in valve pin position with a change in inlet pressure is called unbalance. It results in erratic operation and variation from the original superheat setting. When increased pressure is applied, it pushes on both the pin and the rod. Because it is acting on two equal areas in opposite directions, the pressure change Fig A: Emerson HF – cancels out - and the valve remains in its typical balanced port TXV original modulating position. Applications It would seem, then, that a balanced port TXV is a system “cure all.” But although it will allow the system to operate in a slightly wider range of head pressure and load conditions, valves must still be properly selected to ensure proper system performance. Fig B: Standard TXV in unbalanced condition: pin being forced open The same phenomenon occurs when the outlet (evaporator) pressure varies as load conditions vary, with the same results. 28 Normally, the properly sized standard TXV will work well in the system for which it was designed. When properly sized, it will keep the system operating at high efficiency, with good economy. If your area has a tendency toward rapid wide swings in temperature (30° or more in 24 hours), you may want to consider balanced port TXVs on some of the “trouble” systems. Thermal Expansion Valves Emerson’s HF Line At that time, see your Emerson Wholesaler about the Emerson HF line of balanced port valves. He can give you full specs and fit your needs perfectly with Emerson quality. HF Series Features • Capacities 1/8 thru 13 tons for R-404A/R502 • Bar-stock brass body • Replaceable power assembly • Internal/external equalizer • Field-proven internal seal construction • Tailored bulb charges for specific temperature ranges • Interchangeable with other commercial refrigeration TXV’s Fig C. Balanced port TXV, forces balanced Advantages/Benefits • HF-series TXV’s improve valve operation and stability under varying system conditions such as: high and low head pressures; high and low degrees of sub-cooling; wide range of pressure drops across the valve; and varying evaporator loads. • Wider load range characteristics of HF valves can result in fewer models required to cover the normal range of commercial refrigeration requirements. • Larger H-size removable power element provides smoother and consistent valve control. • Replaceable power element offers flexibility in matching charge requirements with system refrigerant. 29 Solenoid Valves 30 2006 Solenoid Valves Introduction In most refrigeration applications, it is necessary to start or stop the flow in a refrigerant circuit in order to automatically control the flow of fluids in the system. An electrically operated solenoid valve is usually used for this purpose. Its basic function is the same as a manually operated shut off valve, but by being solenoid actuated, it can be positioned in remote locations and may be conveniently controlled by simple electrical switches. Solenoid valves can be operated by a thermostatic switch, float switches, low pressure switches, high pressure switches or any other device for making or breaking an electric circuit, with the thermostatic switch being the most common device used in refrigeration systems. What Are Solenoid Valves? A solenoid valve consists of two distinct but integral acting parts, a solenoid and a valve. The solenoid is nothing more than electrical wire wound in a spiral around the surface of a cylindrical form usually of circular cross section. When an electric current is sent thru the windings, they act as an electromagnet. The force field that is created in the center of the solenoid is the driving force for opening the valve. Inside is a moveable magnetic steel plunger that is drawn toward the center of the coil when energized. The valve contains an orifice through which fluid flows when open. A needle or rod is seated on or in the orifice and is attached directly to the lower part of the plunger. When the coil is energized, the plunger is forced toward the center of the coil, thus lifting the needle valve off of the orifice and allowing flow. When the coil is de-energized, the weight of the plunger and in some designs, a spring, causes it to fall and close off the orifice, thus stopping the flow through the valve. Figure 1A and 1 B show a simple schematic of a solenoid valve in operation. Solenoid Anatomy 31 Solenoid Valves Principles of Solenoid Operation Solenoids are either direct acting or pilot operated. The application determines the need for either of the above types. The direct acting valve is used on valves with low capacities and small port sizes. The pilot operated type is used on the larger valves, thus eliminating the need for larger coils and plungers. 1. Direct Acting In the direct acting type valve, as discussed under Solenoid Valve operation, the plunger is mechanically connected to the needle valve. When the coil is energized, the plunger pulling the needle off the orifice is raised into the center of the coil. This type of valve will operate from zero pressure differential to its maximum rated pressure differential, regardless of the line pressure. The direct acting type valve is only used on small capacity circuits because of the increased coil size that would be required to counteract the large pressure differential of large capacities. The required coil would be large, uneconomical, and not feasible for very large capacity circuits. In order to overcome this problem on large systems, pilot operated solenoid valves are used. 2. Pilot Operated Valve The pilot operated solenoid valves use a combination of the solenoid coil and the line pressure to operate. In this type valve the plunger is attached to a needle valve covering a pilot orifice rather than the main port. The line pressure holds an independent piston or diaphragm closed against the main port. See figures 2a and 2b. When the coil is energized, the plunger is pulled into the center of the coil, opening the pilot orifice. Once the pilot port is opened, the line pressure above the diaphragm is allowed to bleed off to the low side or outlet of the valve, thus relieving the pressure on the top of the diaphragm. The inlet pressure then pushes the diaphragm up and off of the main valve port and holds it there allowing full flow of the fluid. When the coil is de-energized, the plunger drops and closes the pilot orifice. Pressure begins to build up above the diaphragm by means of a bleed hole in the piston diaphragm until it, plus the diaphragm’s weight and spring cause it to close on the main valve port. This type solenoid valve requires a minimum pressure difference between inlet and outlet in order to operate. Types of Solenoids So far we have explained how a solenoid valve operates. Now we will discuss the many types of valves and their respective applications. The three main types of valves are the 2-way, 3-way, and 4way valves. 2 Way Valves The 2-way valve, which is the most common type of solenoid valve, controls fluid flow in one line. It has an inlet and an outlet connection. This valve can be of the direct acting or pilot operated type of valve depending on the need. When the coil is deenergized, the 2-way valve is normally closed. Although normally closed is the most widely used, two way valves are manufactured to be normally open when the coil is de-energized. See Figure 3 for an example Fig 3 of a 2-way valve. 32 Solenoid Valves Solenoid Valve Selection and outlet valve pressures. If a valve has a 500 psi inlet pressure and a 250 outlet pressure, and a MOPD rating of 300 psi it will operate, since the pressure difference (or 500-250) is less than the 300 MOPD rating. If the pressure difference is larger than the MOPD, the valve will not open. The selection of a Solenoid Valve for a particular control application requires the following information: 1. Fluid to be controlled 2. Capacity required 3. Maximum opening pressure differential (MOPD) 4. Electrical characteristics 5. Maximum working pressure required (MWP) The capacities of Solenoid Valves for normal liquid or suction gas refrigerant service are given in tons of refrigeration at some nominal pressure drop and standard conditions. Manufacturers’ catalogs provide extended tables to cover nearly all operating conditions for common refrigerants. Follow the manufacturer’s sizing recommendations. Do not select a valve based on line size. Pilot operated valves require a pressure drop to operate and selecting an oversize valve will result in the valve failing to open. Undersized valves result in excessive pressure drops. The solenoid valve selected must have a MOPD rating equal to or in excess of the maximum possible differential against which the valve must open. The MOPD or Maximum Operating Pressure Differential takes into consideration both the inlet Consideration of the maximum working pressure required is also important for proper and safe operation. A solenoid valve should not be used for an application when the pressure is higher than the maximum working pressure. Solenoid valves are designed for a given type of fluid so that the materials of construction will be compatible with that fluid. Steel or ferrous metals and aluminum are used in solenoid valves for ammonia service. Special seat materials and synthetics may be used for high temperature or ultra-low temperature service. Special materials are required for corrosive fluids. Special attention to the electrical characteristics is also important. Required voltage and Hertz must be specified to ensure proper selection. Valves for DC service often have different internal construction than valves for AC applications, so it is important to study the manufacturer’s catalog information carefully. Minimum Operating Pressure Differential 33 Solenoid Valves Installation Solenoid Valves having a spring loaded plunger or diaphragm may be installed and operated in any position, however, the older style conventional solenoid valve with a plunger, which depends on gravity to close, must always be installed with the plunger in an upright vertical position with the pipe horizontal. An adequate strainer or filter drier should be installed ahead of each solenoid valve to keep scale, pipe dope, solder, and other foreign matter out of the valve. When installing a solenoid valve, be sure the arrow on the valve body points in the direction of refrigerant flow. When brazing solder type connections do not use too hot a torch and point the flow away from the valve. Allow the valve body to cool before replacing the valve’s operating insides to ensure that the seat material and gaskets are not damaged by the heat. Wet rags and or chill blocks are recommended during brazing. They are necessary to keep the valve body cool so that body warpage on closecoupled valves will not occur. When reassembling, do not over torque. Application Overview Application Product Family Liquid Line Service 50RB 100RB 200RB/500RB Liquid or Suction Line Service 240RA/540RA Hot Gas By-Pass 50RB 100RB 200RB/500RB 240RA/540RA Pressure Differential Valve for Hot Gas By-Pass 34 710RA 713RA Solenoid Valves Solenoid Valve Service Hints Symptom Cause Effect Normally Closed Valve 1- Movement of plunger (armature) or Valve Will Not Open diaphragm restricted. a) corroded parts or b) foreign material lodged in valve c) dented or bent enclosing tube Normally Open Valve d) warped or distorted body due to: Valve Will Not Close 1. improper brazing, 2. crushing in vise. 1- Clean affected parts and replace parts as required. Correct the cause of corrosion or source of foreign materials in the system. 2- Improper wiring. 2- Check electrical circuit for loose or broken connections. Attach voltmeter and/or ammeter to coil leads and check voltage, inrush and holding currents 3- Faulty contacts on relays or thermostats. 3- Check contacts in relays and thermostats. Clean or replace as required. 4- Voltage & frequency rating of solenoid coil not matched to electrical supply: a) low voltage b) high voltage c) incorrect frequency. 4- Check voltage & frequency stamped on coil assembly to make certain it matches electrical source. If it does not, obtain new coil assembly with proper voltage & frequency rating. a) Locate cause of voltage drop and correct. Install proper transformer, wire size as needed. Be sure all connections are tight and that relays function properly. b) Excessively high voltage will cause coil burnout. Obtain new coil as sembly with proper voltage rating. c) Obtain new coil assembly with proper frequency rating. 5- Oversized Valve 5- Install correct size valve – see solenoid catalog and extended capacity table. 6- Valve improperly assembled. 6- Assemble parts in proper position making certain none are missing from valve assembly 35 Solenoid Valves Solenoid Valve Service Hints Symptom Cause Effect Normally Closed Valve 7- Coil Burnout Valve Will Not Open a) Supply voltage at coil too low (below 85% of rated coil voltage). or Normally Open Valve Valve Will Not Close 7- Coil Burnout a) Locate cause of low voltage and correct (check transformer, wire size, and control rating). b) Supply voltage at valve too high (more than 10% above coil voltage rating). b) Locate cause of high voltage and correct (install proper transformer or service). c) Valve located at high ambient. c) Ventilate or isolate the area from high ambient. Remove covering or insulation from coil housing. d) Plunger (armature) restricted due d) Clean affected parts and replace to: corroded parts, foreign parts as required. Correct cause material lodged in the valve, of corrosion or source of foreign dented or bent enclosing tube or material in the system. warped or distorted body due to improper brazing or crushing in vise. e) With valve closed, pressure difference across valve is too high, preventing valve from opening. f) e) Reduce pressure differential to less than 300 psi. Improper wiring: f) Inrush voltage drop causing the plunger to fail to pull into magnetic field due to: • Wiring the valve to the load side of motor starter. • Wiring the valve in parallel with another appliance with high inrush current draw. • Poor connections, especially on low voltage, where connec tions should be soldered. Wire size of electrical supply too small. 8- Electrical supply (voltage & frequency) not matched to solenoid coil rating. 36 Correct wiring according to valve manufacturers instructions. Solder all low voltage connections. Use correct wire size. 8- Check coil voltage & frequency rating to be sure it is rated for the electrical service supplied. Install a new coil with the proper voltage & frequency rating. Solenoid Valves Solenoid Valve Service Hints Symptom Normally Closed Valve Valve Will Not Open or Normally Open Valve Valve Will Not Close Valve Closes, But Flow Continues (Seat Leakage) Cause Effect 9- Diaphragm or plunger (armature) restricted due to: corroded parts, foreign material lodged in the valve, dented or bent enclosing tube, or warped body due to improper brazing or crushing in vise. 9- Clean affected parts and replace parts as required. Correct the cause of corrosion or source of foreign material in the system. Install a filter-drier upstream of the solenoid valve 10- Manual opening stem holding valve in open position. 10- With coil de-energized, turn manual stem in counterclockwise direction, until valve closes. 11- Closing spring missing or inoperative. 11- Re-assemble with spring in proper position. 12- Electrical feedback keeping coil energized, or switch contacts not breaking circuit to solenoid coil. 12- Attach voltmeter at coil leads and check for feedback or closed circuit. Correct faulty contacts or wiring. 13- Reverse pressures (outlet pressure greater than inlet pressure), or valve installed backwards. 13- Install check valve at valve outlet, or install with flow arrow in proper direction. 1- Foreign material lodged under seat. 1- Clean all internal parts and remove all foreign material. 2- Valve Seat damaged. 2- Replace valve or affected parts. 3- Synthetic seat material chipped. 3- Replace valve or affected parts. 4- Valve improperly applied or assembled. 4- Replace with proper valve or assemble correctly. Special Considerations for Industrial Solenoid Valves on next page 37 Solenoid Valves Special Considerations for Industrial Solenoid Valves Symptom Cause Effect High Internal seat leakage (high temperature steam up to 400°) Wrong seat elastomer used (Buna N) Use valve with Teflon seat elastomer External leakage (high temperature steam up to 400°) Wrong gasket material used (Neoprene) Use Ethylene Propylene gasket High Internal seat leakage (high temperature steam up to 250° or water up to 210°) Wrong seat elastomer used (Buna N) Use valve with Ethylene Propylene seat elastomer External leakage (high temperature steam up to 250° or water up to 210°) Wrong gasket material used (Neoprene) Use Ethylene Propylene gasket 38 Solenoid Valves Selecting the Right Solenoid Valve for the Job Although solenoid valves are one of the most common controls in refrigeration and air conditioning systems, they are the source of an uncommon amount of service troubles if they are not properly applied. There are a series of do’s and don’ts that can make your working life a whole lot easier if followed. Basics of Solenoids The solenoid’s main function is to start or stop the refrigerant flow in the circuit automatically controlling the fluid flow to match requirements. When and how they act depends on the type of valve, capacity, the fluid charge and the valve’s characteristics. Simply stated, the solenoid valve consists of two parts: an electrical solenoid coil and a valve. When electricity passes through the windings of the solenoid, magnetism draws the valve plunger into the middle of the coil opening an orifice in the valve body and allowing fluid movement. When the current stops, the plunger returns to its normal position, closing the orifice. Emerson 100 RB direct-acting solenoid valve Valve Type is Important There are two types of solenoids: direct-acting and pilot-operated. As a generality, direct-acting solenoids are used on small capacity circuits; pilotoperated on large systems. For good reasons. Pilot-Operated Valves Typical pilot-operated solenoid valve in action. Note how pilot bypasses main valve seat. Direct-Acting Valves In this type valve, the plunger is mechanically connected to the needle valve and directly raises the needle from its seat when the coil is energized. It will operate from zero pressure differential to maximum rated pressure differential regardless of line pressure. These solenoids use a combination of mechanical action and line pressure to operate. Here, the plunger is connected to a needle valve covering a pilot orifice, rather than the main port. Line pressure holds an independent piston or diaphragm closed against the main port. When the needle valve opens, line pressure above the diaphragm bleeds off to the low side thus relieving pressure on top of the diaphragm, and inlet pressure opens the valve. Unlike the directing, the pilot-operated valve requires a minimum pressure difference between the inlet and outlet to operate. 39 Solenoid Valves Where the Problems Begin What seems simple has certain inherent potential trouble-makers if you disregard basics. To select the right valve for the job at hand, the serviceman must consider all these factors: Typical pilot-operated solenoid valve in action. Note how pilot bypasses main valve seat 1. Fluid to be controlled. Each valve is rated by its manufacturer for a specific refrigerant fluid. Don’t overlook that rating. When the wrong valve-fluid combination occurs, the valve’s capacity changes. Over-sized pilot-operated valves refuse to open; undersized valves cause excessive line drops. In addition, different types of materials are used in valve seats depending on the service. Special seat materials used for high temperatures may deteriorate rapidly in the wrong fluid. 2. Capacity vs. MOPD. Some servicemen select for line size rather than system capacity. For “safety’s sake” they pick the next size larger than needed. With too large or too small a differential, the valve just won’t work as it should, if it works at all. MOPD takes into consideration both the inlet and outlet valve pressures. If a valve has 500psi inlet and 250psi outlet pressure, and an MOPD of 300psi, it will operate because the difference (500-250) is less than the 300 MOPD rating. If it is greater than the MOPD, the valve won’t open. 3. Electrical ratings. Both voltage and Hertz ratings of the coil must match the system ratings. Yet some servicemen neglect these considerations - as they do the type of current involved. DC-rated valves frequently have different internal construction than do AC-rated valves. 4. Maximum working pressures (MWP). A solenoid valve must never be used for an application when the pressure is higher than the maximum working pressure. Study the Manufacturer’s Catalog As a general rule, study the manufacturer’s catalog and its specifications carefully before selecting the valve for the job. Emerson provides detailed information to guide you in selecting and installing, all its products. Read it carefully, then make your selection following the above guidelines. You’ll have a lot less trouble and fewer callbacks. 40 Solenoid Valves Solenoid Valves for Special Applications The relatively simple and reliable electromagnet makes the solenoid valve a basic workhorse in refrigeration systems. Energizing and de-energizing its coil, either by manual or automatic control, is the easiest means yet devised to provide on-off control of refrigerant flow. The most basic stripped-down model of solenoid valve is the normally-closed direct-acting configuration, which is held shut by a spring and opened by energizing the coil. A variation used in larger systems is the pilot-operated type, which is “powerassisted” by system pressure. The operation and applications of these basic types of solenoid valves will be covered at the end of this section. In this Tech Tips we will discuss other types of solenoid valves designed to meet more specialized needs. A general understanding of these special types will be helpful when you run into one, or a need for one. An important caution to bear in mind is that the applicable selection criteria should be used in every case to ensure that a given valve is compatible with the proposed application. If there’s any uncertainty, it’s a good idea to check with the valve manufacturer. “Bi-Flow” Two-way Solenoid With Check Valve This is a conventional normally-closed solenoid valve, usually a pilot-operated type that incorporates an integral check valve. It will provide positive shutoff in one direction but permit flow in the opposite direction. It will typically be installed in the liquid line in a heat pump system. Solenoid Coil (Energized) Internally Adjustable Solenoids These may be either normally-closed or normallyopen types, and may be applied as a conventional two-way solenoid or as an adjustable differential check valve. In the latter application, the valve will allow flow in one direction even when closed, when the pressure differential exceeds the level for which it is adjusted. These valves can be used in applications where there is a need for a solenoid valve and check valve in parallel, thereby simplifying the piping and reducing the number of joints. And, being adjustable, they also provide more precise pressure control. 41 System Protectors 42 2006 System Protectors Protecting Your Profits: General Guidelines on Selecting Filter-Driers Filter-driers, sometimes called System Protectors, remove harmful elements from the circulating refrigerant before they can damage the system. There’s no mystery surrounding them, but choosing the proper filter-drier for a specific system can be a problem if you do not fully understand what they are and how they work. Dirt, Waxes, Acid: Trouble Every system you deal with, whether new installation or a repair, has contaminants in it the second you open it. They may be insoluble, such as metal filings not removed in manufacturing, or airborne dirt that entered when the system was opened. Or, they may be soluble, such as waxes, acids, water and resins that develop through reactions between air, the refrigerant, or lubricant. Bead-style filter drier, Emerson’s EK-Plus. Types of Filter-Driers Commonly, there are two types of filter-driers; each type has multitudes of versions, but they operate essentially the same. Any of these can cause callbacks from system failure. However, installing a System Protector, an all-purpose filter-drier, can dramatically lessen chances for that trouble. There are simple basic differences to consider: type of filter, how it filters, and its true capacity. Core style - manufactured by mixing desiccants (which actually remove the soluble contaminants) with a bonding agent, then baking them to give them permanent shape and to activate the drying ingredients. Result: a porous block serving as both filter and drying agent. Compacted Bead style - as its name implies, the active desiccant is in bead or pellet form; no bonding material is used. Rather, compacting comes from mechanical pressure exerted by a spring. However, compacted bead-style filter-driers usually include an additional filter network to trap solid contaminants from the refrigerant, unlike most block styles. The separate and distinctive filter media can take various forms that permit depth filtration with significantly greater solid contaminant capacity and achieve optimum contaminant retention during start-up and shut- down when turbulent conditions exist. Fig 1. Proper placement of filter-drier in the system Compacted Bead vs. Core - core style filter-driers offer the maximum volume of desiccant in that both filtering and drying must be accomplished in the one mass. But, because the block is porous, it does not hold all solid contaminants; often particles are washed through channels within the block when pressures surge. Increasing the holding power is possible with a more compacted block. But pressure drops increase inversely. 43 System Protectors Most manufacturers rate their filters to ARI Standard 710. But even though two clean filter-driers may be rated the same, there can be a vast difference in flow as the quantity of solids picked UP increases. Absorption vs. Adsorption One factor to consider in selection is abvs. ad-sorption. Absorption means a material’s ability to take another substance into its inner molecular structure. An adsorbed substance doesn’t penetrate the molecular structure. It simply begins building up on the surface of the adsorbent. Walls, cracks, crevices are part of the surface area and are able to hold other substances, greatly increasing capacity. Modern desiccants are extremely porous and as such possess a very large amount of surface area and internal pore volume of a size and shape to effectively adsorb and retain water molecules. Moisture Capacities Emerson’s EK: State of the Art Two adsorbents are in general use today: activated alumina, and molecular sieve; the latter being the most popular, offering water capacity 3 to 4 times greater than other adsorbents. Moisture capacities of filter-driers are normally given in drops of water per ARI Standard 710, allowing direct comparison of different types and brands. The most advanced filter-drier today is the Emerson EK. Developed through extensive research in the Emerson Engineering Laboratories, EK combines a process controlled filter medium to remove solids with a powerful desiccant for maximum moisture adsorption. SAE or all-copper fittings allow easy installations. Be sure to carry a few Emerson’s EK filter-driers with you on every call. One Important Guide Tests have shown that the amount of acid and resin pick-up of an adsorbing agent is almost proportional to the weight of the desiccant. Size or granulation makes little difference. There is presently no industry-approved method for rating acid removal. So weight of the desiccant provides the handiest measure. 44 System Protectors The Case for Filter-Driers in the Suction Line The function of filter-driers in refrigeration and air conditioning systems to trap moisture and harmful contaminants is well understood and accepted by everyone involved with installing and maintaining such systems. But their use in the liquid line still tends to be thought of as the “standard” application; including them also in the suction line hasn’t yet become standard practice to the same degree. A filter-drier in the liquid line essentially protects the system controls - solenoid valves, expansion valves, pressure regulators, and the like. The function of the filter or filter-drier in the suction line is specifically to protect the compressor against the ingestion of contaminants. Emerson ASD suction line filter-drier Such protection is generally encouraged by compressor manufacturers in any case, but there are two sets of circumstances that make suction line filters or filter-driers particularly advisable Field Built-up Systems It is practically impossible to avoid contamination when assembling a refrigeration system in the field. Dirt, moisture, metal particles, copper oxide from brazing all can be present in the system despite the greatest care, and all are capable of damaging or reducing the service life of the compressor. In the case of large and complex systems, like a single system serving a number of food cases throughout a supermarket, it is a generally accepted practice to install a cartridge-type filter in the suction line. Then, because of the virtual certainty of contamination during assembly of the system, the initial cartridge is removed and replaced after the first few days of system operation. When considering the price of a compressor, the cost of protecting it with a suction line filter is quite insignificant. Cross-section shows desiccant beads surrounding accordiontype filter element 45 System Protectors Compressor Burnout A compressor burnout can be expected to release a variety of pollutants into the system, including acids. Standard procedures following any compressor burnout should include replacing the liquid line filter-drier with an over-size unit, in addition to installing a new suction line filter-drier. Then all control components and strainers should be thoroughly cleaned and the system triple evacuated to at least 50 microns before recharging. When a severe burnout occurs, characterized by discoloration of the oil, a strong acid odor, and the presence of contaminants throughout both the liquid and suction sides of the system, the system should be flushed and the oil changed, when possible. After operating the system for 48 hours while monitoring the pressure drop across the suction line filter-drier, the oil should be checked for acid. This can be done with an Emerson Acid Alert test kit, and if acid is still present, both filter-driers should be replaced again. A Look Inside Internally, suction line filter-driers employ the same types of elements as liquid line units. One is the core type, in which the filter-drier element consists of a rigid, cylindrical, porous block that may perform both the filter and drier functions, or be used in combination with a separate accordion-type filter element. The core type filter-drier is available either in a hermetically sealed configuration or in take-apart designs with a replaceable element. What to Look for… and Look Out for The latest advancement is the beadtype unit, in which the desiccant consists of loose beads compacted into the shell. Some manufacturers have been known to add an access valve to their liquid line filter-driers and declare them suction line filter-driers. This is not a recommended way to go for two reasons. This design offers several advantages over older types, including lower pressure drop, more desiccant surface area, and greater capacity. First, a suction line filter-drier should provide for greater capacity than a liquid line unit, both for better compressor protection and for less pressure drop. Emerson’s ASD filter-driers and ASF filters are both available in many sizes, all with copper fittings to make installation a snap. With their state of the art filter and desiccant materials, they’re the most advanced and most efficient suction line filters and filter-driers on the market. Typical system arrangements show suction line filter-drier installed ahead of the compressor. Second, when only one access valve is provided on the filter-drier itself, it is necessary to use the access valve on the compressor, if it has one, to measure pressure drop. By contrast, a state-of-the-art suction line filter-drier, such as Emerson’s ASD series, will include two access valves for fast and convenient measurement of the pressure drop across the filter-drier itself, which normally won’t exceed three pounds. And they’re oversized by design, so that all you have to do is match the line size and you’re assured of adequate capacity, even after a compressor burnout. 46 System Protectors All About Heat Pump Filter-Driers A heat pump is essentially nothing more than a refrigeration system that is capable of flowing in either direction. The key to its operation is a four-way reversing valve that routes the discharge gas from the compressor. Depending on whether the system is cooling or heating, the indoor and outdoor coils swap roles, taking turns serving as the condenser and evaporator. Since conventional refrigerant control components are designed for unidirectional operation, their use in heat pumps requires installation in pairs, one for each direction, with check valves routing the flow through or around them. Today, because of the growing use of heat pumps, components such as thermostatic expansion valves are available in bi-directional versions, as are filter-driers, the subject of this Tech Tips. One-Way Flow, Both Ways Emerson BKF bi-directional pump filter-drier Removing Contaminants Just like any other refrigeration system, heat pump system components should have the benefit of filter-drier protection to remove solid and soluble contaminants. This may be handled several ways. Inside a bi-directional filter-drier the refrigerant always flows the same direction regardless of which way the refrigerant is flowing through the system. The internal flow in this case is controlled by an inlet flapper valve and an outlet poppet valve on each side of the desiccant block. As the liquid enters the filter-drier from either direction, the inlet flapper valve routes it to the outside of the desiccant core. After it flows through to the inside of the desiccant core, it exits through the opposite poppet valve. First, in systems with one-way expansion valves and check valves, a one-way filterdrier might be installed in series with a check valve. This would be a “part-time” arrangement, in that filtration would be provided in only one direction. Second, a one-way filter-drier might be installed with each of the check valves, so that one provides filtration in each direction. And finally, the simplest arrangement is to install a bi-directional filter-drier in the common liquid line. Used in combination with a bi-directional thermostatic expansion valve such as Emerson’s HF series, the complexity of multiple expansion valves, check valves, and filter-driers can be completely eliminated Schematic of a basic heat pump system. 47 System Protectors The purpose of this arrangement is to prevent contaminants collected in one direction from being flushed back out when the flow reverses. Bi-directional components allow simplification of system Simplifying While Servicing When servicing or repairing heat pump systems, especially older units, it’s a good idea to simplify them whenever appropriate by replacing unidirectional components and check valves with bidirectional components such as two-way filter-driers. When a bidirectional thermostatic expansion valve and filter-drier are installed, one-way expansion valves, check valves, and filterdriers can all be replaced at once with copper tubing. That’s about as trouble-free as you can get. Cross section showing BFK internal components Refrigerant flow either direction passes from outside to inside of desiccant block 48 Regulators 49 2006 Regulators Hot Gas Bypass... What, Why & How The many and varied components of air conditioning systems are normally sized as necessary to provide adequate cooling capacity under the maximum load conditions that will be encountered during the system’s operation. Yet these same systems are also required to perform satisfactorily under substantially lesser loads. In a system operating under low load conditions, the evaporator if left to its own devices would continue to get colder and colder until it freezes up. As growing numbers of sealed office buildings required air conditioning systems to operate at lower ambient temperatures to remove internally generated heat, it became necessary to develop an efficient means of preventing evaporator freeze-up. Enter the Hot Gas Bypass Valve How it Works The function of the hot gas bypass valve is to feed in, preferably ahead of the evaporator, hot gas, which is bled from just down-stream of the compressor. This gas raises the pressure in the evaporator and hence the boiling point, thus retarding evaporation and cooling. In effect, it artificially loads the evaporator, reducing its cooling capacity to match load demand. Because the temperature in the evaporator is a function of the pressure, it can be controlled by a relatively simple pressure regulator. And that’s exactly what the hot gas bypass valve is. Through a pressure tap into the suction line ahead of the compressor, the hot gas bypass valve senses the pressure in the low side of the system. As the temperature in the evaporator drops lower and lower, the corresponding drop in pressure will cause the valve to open, admitting by-pass gas into the low side and boosting the pressure. Although the bypass gas can be introduced into the suction line between the evaporator and the compressor, as sometimes dictated by piping considerations, it is not the preferred method be- cause it might also require the addition of a liquid injector valve to de-superheat the gas to avoid overheating the compressor. Besides adding to the complexity of the system, oil return problems might also deliver a series of undesirable side effects. In the system, the hot gas bypass valve is operated by a pressure diaphragm working in opposition to a spring. System pressure acting on the diaphragm holds the valve in the closed position until it falls below the set point, at which time the spring overpowers the pressure and opens the valve. Bypass system showing preferred outgoing to evaporator inlet 50 Regulators Adjusting the Set Point The suction pressure at which the valve opens is selectable by increasing or decreasing the load on the spring by turning an adjusting screw. To set it, the evaporator must be cooled down by shutting off the fans, blocking off the airflow, or some other means, until the suction pressure drops to at least five pounds below the desired set point. Then, by allowing the pressure to be increased by the bypass gas, the spring load can be varied until the valve closes at precisely the desired set point. Generally, the pressure is set to maintain an evaporator temperature just above that at which frost forms. A Few Cautions • In systems that utilize a Venturi type distributor, the bypass gas should be fed into the system between the outlet of the expansion valve and the inlet to the distributor. In the case of pressure drop distributors that utilize an orifice, the inlet must be between the orifice and the inlet to the distributor. • The hot gas bypass line should be insulated to minimize system heat loss. • In systems with sequential compressor unloading, the valve should be set to begin opening at two to three pounds below the last stage of unloading, because compressor unloading is considerably more efficient and should be utilized before resorting to bypassing. • For oil return considerations. The bypass line must feed in ahead of the evaporator when the evaporator is physically located below the compressor. • The hot gas bypass valve should be located as close as practical to the condensing unit, to minimize condensing ahead of it. • In systems that operate on a pump down cycle, there must be a solenoid valve or some other means of shutoff in the bypass line. 51 Regulators Understanding Suction Line Regulators: Operation & Application Suction line regulators are used for a variety of refrigeration control functions. But their main purpose is to balance the capacity of the refrigeration system to the requirements of the load. By controlling the operating pressure of the evaporator, or the suction pressure of the compressor, they allow the system to meet the requirements of a wide range of load conditions, and maintain maximum system efficiency. You don’t have to install suction line regulators on systems of 5 tons or less (unless the system has a history of trouble), but they pay off nicely on larger refrigeration and commercial systems. Two Main Types Basically, there are two main types of suction line regulators: Upstream, or Evaporator Pressure Regulators (EPR), and Downstream Pressure Regulators. Because the latter regulate pres- sure at the compressor, they are sometimes called Crankcase Pressure Regulators (CPR). You’ll find both types located in the outlet side of the evaporator, between it and the compressor. In operation, EPRs keep gas pressure at or above a pre-set level; CPRs keep suction pressure at or below a pre-set level. Fig 2. Typical system using line regulators Figure 1. Emerson EPRBS, a typical suction line regulator How EPRs Work EPRs are the oldest and best known of these suction line controls. They are designed to work on multiple evaporator systems. Figure 3 shows a typical EPR. Operating pressure limit is set by adjusting the top-mounted screw, working against the adjustable spring. Pressure through the inlet gas passage keeps the diaphragm up, allowing pressure to flow into the pilot port chamber. This maintains the main piston in its open position. When pressure drops below the minimum, the diaphragm moves downward, opening the pilot valve and reducing pressure above the piston. In turn, the piston moves in a closing direction, restricting gas flow and increasing pressure in the line. Both the pilot and main valves can assume intermediate or throttling positions to more evenly regulate pressure in the lines. 52 Regulators Crankcase Regulators Normally open, the CPR (Fig. 4), closes when compressor pressure rises above the pre-set maximum, forcing the valve back onto its seat. As suction pressure drops, the valve begins reopening, maintaining the balance. How to Apply Them Normally, it isn’t necessary to use both types in most systems. In fact, about 90% of all installations are of EPRs only. Typical installations of EPRs are in supermarket systems, large chillers, and industrial processes where large amounts of heat must be absorbed. Smaller (including residential) systems of less than 5 tons are usually equipped with compressors designed to operate well within assigned 30°40°F. variations. One of the advantages of suction line regulators in modular systems, like those with many cases found in supermarkets, is that by adding EPRs you can control the operating temperatures of the individual cases in a single loop system. Fig 3. cutaway of evaporator pressure regulator (Emerson BEPR). Where to Apply Them EPRs are most commonly used on multiple evaporator systems, located in the branch lines close to the required control source. They are used for indirect temperature control. They also maintain evaporator pressure during defrost, conserving power, expediting the defrost and reducing flood back. CPRs are usually only applied if the system is being continually “over-pressured.” If you suspect that’s the case, check the amp draw on the compressor while it’s running. If it’s higher than the plate rating, the system may be a CPR candidate. It’s always a good idea to talk it over with your Emerson Wholesaler, who can answer questions about sizing and application. Fig 4. Cutaway of crankcase pressure regulator (Emerson OPR) 53 Regulators The What, Why and How of Head Pressure Control What does a head pressure control do? Why is it needed? How does it work? Knowing the answers to these questions is important in many refrigeration applications, and becoming increasingly important in air conditioning applications. Understanding the types of systems and applications calling for head pressure controls is especially important to assemblers of such systems, whether factory assembled or on-site assembled. Emerson Headmaster 3-way valve. How Head Pressure Contributes Methods of Maintaining Head Pressure To start with the basics, adequate head pressure, the system pressure imposed by the compressor, is necessary for optimum performance of most systems. The function of the pressure is to (1) maintain liquid sub cooling and prevent liquid line flash gas, (2) apply enough pressure at the inlet side of the thermal valve to create the pressure drop across the valve port needed for proper valve operation, (3) provide for proper operation of system with hot gas defrost or hot gas bypass, and (4) supply the pressure necessary for operation of heat reclaim systems. When the temperature of the condenser cooling air is an uncontrolled variable, as it typically is, head pressure can be boosted at lower ambient temperatures by reducing the exposure of the refrigerant to the cooling air. This, in turn, can be done by controlling either the flow of air or refrigerant through the condenser. Ordinarily, when ambient air temperature flowing through air-cooled condensers is warm enough, there is no problem maintaining head pressure. But as ambient temperature falls, there is a corresponding head pressure drop, calling for some means of artificially maintaining it. Applications in which systems are required to operate at lower outdoor temperatures traditionally include such obvious examples as refrigeration systems for food processing and storage. But with today’s “sealed” office buildings, there is a growing need for air conditioning systems, too, to operate at cooler temperatures, removing internally-generated heat. Computers are a primary source. Controlling the volume of airflow through the condenser coils can be done by cycling cooling fans on and off, or by a damper system that proportions airflow passing through, or through bypassing the condenser. Controlling the flow of refrigerant through the condenser is by valving, and, because this offers some distinct advantages over controlling the air- flow, we will concentrate here on valvetype head pressure controls. Among its major advantages, a head pressure control valve is capable of precision in maintaining optimum pressure, typically within a 5-10 psi range, while airflow control systems might vary as much as 50psi. In addition, airflow control systems are effective only down to a certain temperature, while the refrigerant valving system continues to maintain head pressure at much lower ambients. Finally, a valve system is simpler to install and maintain. 54 Regulators How it Works Inside of a typical head pressure control is a valve which, when closed, routes the refrigerant through the condenser to the receiver, and when open, allows refrigerant gas to by-pass the condenser. The valve is operated by a pressure charge in the head of the valve acting on a diaphragm. When ambient is warm enough, normal head pressure on the opposite side of the diaphragm counteracts the pressure charge, keeping the valve closed and routing the refrigerant through the condenser. As the ambient temperature falls, the pressure charge overcomes the resulting lower head pressure, opening the valve and allowing bypass gas to enter the receiver. This creates back pressure at the condenser outlet, causing a buildup of condensed liquid in the condenser, popularly referred to as “flooding the condenser,” which effectively reduces its working surface and its cooling capacity. Custom 3-way valve in single system Upper: Typical single-valve system, Lower: Typical Dual-valve system Single & Dual Valve System Generally speaking, the need for head pressure control, as dictated by the application, is adequately met with a single valve in systems up to about 15ton capacity. This is because such systems are usually factory-assembled, with components sized and pre-set for the specific system. Larger systems usually employ two adjustable pressure regulators, one ahead of and one after the condenser. These systems are normally assembled on-site from components procured independently, thus necessitating a means of adjusting pressures for system compatibility. The only other component that requires specific sizing for compatibility with head pressure controls is the receiver, which must be large enough to accommodate the normal operating charge plus the additional charge that would be necessary to totally flood the condenser. 55 Basic Rules of Good Practice 56 2006 Basic Rules of Good Practice Basic Rules of Good Practice Doing a good job in any line of work almost always involves following some basic “good practice” rules, and servicing refrigeration systems is no exception. Knowing and observing such basic rules, to the point that it becomes automatic, can prevent a lot of problems by cutting them off at the pass before they have a chance to happen. A list of DO’s, procedures that should be followed, and a list of DON’Ts representing pitfalls that should be avoided are presented here to promote the general adoption of good servicing practices and a better understanding of the WHYs behind them. An occasional quick review may serve to reinforce awareness and help make their application second nature. DOs DO maintain test instruments in good working order and periodically check them against accurately calibrated instruments. Good diagnoses can’t be made with faulty inputs. DO familiarize yourself with the operation of a control before attempting to make adjustments or repairs. If you don’t understand how a control is supposed to function, you can’t be sure if it’s defective or not. When you know what you’re doing, you achieve good results on purpose; when you don’t know what you’re doing, you achieve good results only by accident. DO make it a practice to check suction gas superheat at the compressor. Too low superheat may result in liquid flood-back, while high superheats cause high discharge temperatures. Always follow equipment manufacturers’ instructions. DO replace filter-driers or replaceable cartridges whenever it’s necessary to open a system for service. Regardless of how careful you are, it’s virtually impossible to prevent the entry of moisture and other contaminants while the system is open. Driers or cartridges cannot be successfully activated in the field for reuse. A new filter drier or cartridge is cheap insurance for a compressor. DO use an accurate moisture indicator in the liquid line to watch out for moisture contamination. It is the single most common contaminant, and it can lead to a variety of problems including acid, sludge, and freeze-ups. DO check expansion valve superheat by using the temperature-pressure method. This involves measuring the suction line pressure at the evaporator outlet and then referring to the appropriate temperature-pressure chart to determine the saturation temperature. Subtracting this temperature from the suction line temperature measured at the remote bulb gives you the operating superheat, which should be adjusted to the equipment manufacturer’s specifications. 57 Basic Rules of Good Practice DON’T be a “parts-changer.” DON’Ts Analyze problems based on the symptoms, and determine the specific cause before making any changes or repairs. Emerson’s Troubleshooting Expansion Valves, Parts I and II, describe a wide variety of problems that may be encountered, and their probable causes. DON’T think of a thermal expansion valve as a temperature or pressure control. Thinking of it as a superheat control is basic to achieving optimum system performance. DON’T attempt to use any control for any application other than the one it was designed for. Using a pressure regulator for a pressure relief valve-or any similar substitution - is not good practice and almost certainly won’t deliver proper performance. Misapplications can lead to equipment damage and even injury. When doubt exists, check with the manufacturer. DON’T energize a solenoid coil while it is removed from the valve. Without the magnetic effect of the solenoid core, the coil will burn out in a matter of minutes. DON’T install a previously used filter-drier or replaceable cartridge. It could introduce contaminants that it has picked up since its removal from a system DON’T select solenoid valves by line size or port size, but by valve capacity. They must also be compatible with the intended application with regard to the specific refrigerant used, the maximum opening pressure differential (MOPD), the maximum working pressure (MWP), and the electrical characteristics. Never apply a valve outside of its design limits or for uses not specifically catalogued. DON’T rely on sight or touch for temperature measurements. Use an accurate thermometer. Once again, you can’t get accurate diagnoses with faulty inputs. One last tip: DO read the instructions first. DON’T wait until all else fails! 58 Troubleshooting Guide 59 2006 TROUBLESHOOTING EXPANSION VALVES Superheat Is Too Low -- TXV Feeds Too Much Problem Symptoms 1) Liquid Slugging Valve Feeds 2) Low Superheat Too Much 3) Suction Pressure Normal or High Causes Corrective Action Oversized Valve Replace with correct size valve Incorrect Superheat Setting Adjust the superheat to correct setting Moisture Replace the filter-driers; evacuate the system and replace the refrigerant Dirt or Foreign Material Clean out the material or replace the valve Incorrect Change Selection Select proper charge based on refrigerant type Incorrect Bulb Location Relocate the bulb to proper location Incorrect Equalizer Location Relocate the equalizer to proper location Plugged Equalizer (Balanced Port Valve) Remove any restriction in the equalizer tube Superheat Is Too High -- TXV Doesn't Feed or Doesn't Feed Enough Problem Valve Doesn't Feed or Doesn't Feed Enough Symptoms 1) Evaporator Temperature Too High 2) High Superheat 3) Low Suction Pressure Causes Corrective Action Short of Refrigerant Add correct amount of refrigerant High Superheat Change superheat setting Flash Gas In Liquid Line Remove source of restriction Low or Lost Bulb Charge Replace power element or valve Moisture Replace driers or evacuate the system and replace refrigerant Plugged Equalizer (Conventional Valve) Remove restriction in equalizer tube Insufficient Pressure Drop or Valve Too Small Replace existing valve with properly sized valve Dirt or Foreign Material Clean out material or replace valve Incorrect Charge Selection Select correct charge Incorrect Bulb Location Move bulb to correct location Incorrect Equalizer Location Move equalizer to correct location Charge Migration (MOP Only, Vapor Charges) Move valve to a warmer location or apply heat tape to powerhead Wax Use charcoal drier Wrong equalizer Type Valve Use externally equalized valve Rod Leakage (Balanced Port Valve) Replace valve Heat Damaged Powerhead Replace powerhead or valve No Superheat At Start Up Only Problem Symptoms Valve Feeds 1) Liquid Slugging Too Much At 2) Zero Superheat Start Up 3) Suction Pressure Too High Causes Corrective Action Refrigerant Drainage Use pump down control; Install trap at the top of the evaporator Compressor or Suction Line in a Cold Location Install crankcase heater; Install suction solenoid Partially Restricted or Plugged External Equalizer (Balanced Port Valve) Remove restriction Liquid Line Solenoid Won't Shut Replace powerhead or valve Superheat Is Erratic Or Hunts Problem System Hunts or Cycles Symptoms 1) Suction Pressure Hunts 2) Superheat Hunts 3) Erratic Valve Feeding Causes Corrective Action Bulb Location Incorrect Reposition Bulb Valve Too Large Replace with correctly sized valve Incorrect Superheat Setting Adjust superheat to correct setting System Design Redesign system 60 Superheat Appears Normal -- System Performs Poorly Problem Valve Doesn't Feed Properly Symptoms 1) Poor System Performance 2) Low or Normal Superheat 3) Low Suction Pressure Causes Corrective Action Unequal Circuit Loading Make modification to balance load Flow From One Coil Affecting Another Coil Correct piping Low Load Correct conditions causing low load Mismatched Coil/Compressor Correct match Incorrect Distributor Install correct distributor Evaporator Oil-Logged Increase gas velocity through coil TROUBLESHOOTING SOLENOID VALVES Problem Normally Closed Valve Will Not Open -orNormally Open Valve Will Not Close Causes Corrective Action Movement of plunger or diaphragm restricted a) Corroded parts b) Foreign material lodged in valve c) Dented or bent enclosing tube d) Warped or distorted body due to improper brazing or crushing in vice Clean affected parts and replace parts as required. Correct the cause of corrosion or source of foreign materials in the system. Improper wiring Check electrical circuit for loose or broken connections. Attach voltmeter to coil leads and check voltage, inrush and holding currents Faulty contacts on relays or thermostats Check contacts in relays and thermostats. clean or replace as required. Voltage and frequency rating or solenoid coil not matched to electrical supply: a) low voltage b) high voltage c) incorrect frequency Check voltage and frequency stamped on coil assembly to make certain it matches electrical source. If it does not, obtain new coil assembly with proper voltage and frequency rating: a) Locate cause of voltage drop and correct. Install proper transformer, wire size as needed. Be sure all connections are tight and that relays function properly. b) Excessively high voltage will cause coil burnout. Obtain new coil assembly with proper voltage rating. c) Obtain new coil assembly with proper frequency rating. Oversized Valve Install correct sized valve. Consult extended capacities tables. Valve improperly assembled. Assemble parts in proper position making certain none are missing from valve assembly. Coil Burnout a) Supply voltage at coil too low (below 85% of rated coil voltage) b) Supply voltage at valve too high (more than 10% above coil voltage rating) c) Valve located at high ambient a) Locate cause of low voltage and correct (check transformer, wire size, and control rating) b) Locate cause of high voltage and correct (install proper transformer or service) c) Ventilate the area from high ambient. Remove covering from coil housing d) Plunger restricted due to: corroded parts, d) Clean affected parts and replace as required. foreign materials lodged in valve, dented or bent Connect cause of corrosion or source of foreign enclosing tube or warped or distorted body due to material in the system improper brazing or curshing in vise e) With valve closed, pressure difference across e) Reduce pressure differential to less than valve is too high preventing valve from opening 300psi f) Improper wiring. Inrush voltage drop causing f) Correct wiring according to valve manufacturers' plunger to fail to pull magnetic field due to: instructions. Solder all low voltage connections. - Wiring the valve to the load side of the motor Use correct wire size. starter - Wiring the valve in parallel with another appliance with high inrush current draw - Poor connetions, especially on low voltage, where connections should be soldered - Wire size of electrical supply too small g) Electrical supply (voltage and frequency) not Check coil coltage and frequency to ensure match matched to solenoid coil rating to electrical service rating. Install new coil with proper voltage and frequency rating. 61 Problem Causes Normally Closed Valve Will Not Close -orNormally Open Valve Will Not Open Corrective Action Diaphragm or plunger restricted due to: corroded parts, foreign material lodged in valve, dented or bent closing tube, or warped body due to improper brazing or crushing in vise Clean affected parts and replace parts as required. Correct the cause of corrosion or source of foreign materials in the system. Install a filterdrier upstream of solenoid valve Manual opening stem holding valve open With coil de-energized, turn manual stem in counter clockwise direction until valve closes Closing spring missing or inoperative Re-assemble with spring in proper position Electrical feedback keeping coil energized, or switch contacts not breaking circuit to coil Attach voltmeter at coil leads and check for feedack or closed circuit. Correct faulty contacts or wiring Reverse pressures (outlet pressure greater than inlet pressure), or valve installed backwards Install check valve at valve outlet, or install with flow arrow in proper direction Problem Causes Corrective Action Foreign material lodged under seat Valve Closes, But Flow Continues (Seat Leakage) Clean internal arts and remove foreign material Valve seat damaged Replace valve or affected parts Synthetic seat materials chipped Replace valve or affected parts Valve improperly applied or assembled Replace valve with proper valve or re-assemble Special Considerations For Industrial Solenoid Valves Symptoms Causes High Internal Seat Leakage (high temperature steam up to 400°) Corrective Action Wrong Seat Elastomer Used (Buna N) Use Valve with Teflon Seat Elastomer External Leakage (high temperature steam up to Wrong Gasket Material Used (Neoprene) 400°) Use Ethylene Propylene Gasket High Internal Seat Leakage (high temperature steam up to 250° or water up to 210°) Wrong Seat Elastomer Used (Buna N) Use Valve with Ethylene Propylene Seat Elastomer External leakage (high temperature steam up to 250° or water up to 210°) Wrong Gasket Material Used (Neoprene) Use Ethylene Propylene Gasket TROUBLESHOOTING BALL VALVES Symptoms Causes Doesn't Flow Corrective Action Valve Isn't Open Turn Stem Leak at Access Schrader Valve Schrader Valve Isn't Tight Tighten Schrader Valve Leak at Stem Valve Stem is Leaking Replace Valve Excessive Pressure Drop Valve Isn't Fully Open Turn Stem to Open Valve TROUBLESHOOTING SYSTEM PROTECTORS Allowable Pressure Drop -- Permanent Installation Evaporator Temperature Refrigerant 40°F 20°F 0°F -20°F -40°F R12, R134a 2.0 1.5 1.0 0.5 - R22, R410A 3.0 2.0 1.5 1.0 0.5 R502, R404A/507 3.0 2.0 1.5 1.0 0.5 TROUBLESHOOTING STORAGE DEVICES Suction Line Accumulators Problem Causes Bleed Hole in U-Tube Plugged Oil Not Returning to Compressor Corrective Action Replace Accumulator; Install Filter Ahead of Accumulator U-Tube Broken Off Replace Accumulator Accumulator Too Large for Application Replace with Smaller Accumulator Accumulator Installed Incorrectly Re-Install with Correct Inlet & Outlet Connections 62 Liquid Refrigerant Receivers Problem Causes Flashing In Liquid Sight Glass Downstream Of Receiver Corrective Action Receiver Outlet Not Fully Open Open Valve Fully On Receivers with Top Outlet Connections, the Dip Tube may be Broken Off Or Plugged Replace Receiver Receiver Installed Upside Down Re-Install Receiver Correctly TROUBLESHOOTING OIL CONTROLS - OMB Problem Causes OMB out of calibration Replace OMB Too much oil in system Remove oil from oil separator or reservoir until proper level is maintained Too much oil coming back from evaporator Check system piping design for: - Proper velocities - P-traps at the bottom of all suction risers - Piping pitched to compressor - Overlapping or defrosts that are not staggered Debris under solenoid valve seat Unscrew solenoid valve from TraxOil; clean & replace Oil Level Too High In Sight Glass Problem Oil Level Too Low In Sight Glass Problem Causes Corrective Action Oil separator or reservoir empty Add oil to maintain a liquid seal in teh bottom of the serparator or reservoir Plugged oil line filter Replace filter Plugged inlet strainer(s) on OMB Remove and clean strainer on all affected OMB Solenoid coil defective Replace coil Power loss to OMB Check power to OMBl. Green light should be lit. Causes Corrective Action Flood back through suction; Increase superheat on expansion valve; Refrigerant condensing in oil separator - add heater to oil separator and/or adjust system setting to eliminate flood back Liquid refrigerant in oil Foaming In Sight Glass Problem Corrective Action If so equipped, liquid injection overfeeding Correct liquid injection overfeed Excess quantity of oil in crankcase Remove excess oil Causes Corrective Action "Filling" light remains on even though level is 1/2 Replace OMB above sight glass Alarm light on all the time Replace OMB Intermittent oil return from system Check system piping design for: - Proper veloicties - P-traps at the bottom of all suction risers - Piping pitched to compressor - Overlapping or defrosts that are not staggered Nuisance Oil Alarms TROUBLESHOOTING OIL SEPARATORS Problem Causes Oil outlet valve closed or partially closed Open oil outlet valve Inadequate oil charge in system Add oil in system Oil float defective or dirty (will not open) Disassemble and clean or replace defective float component (flanged versions); Replace oil separator (welded version). Reduced or No Oil Feed to Compressor Heat Gas Entering Compressor Corrective Action Separator too small for application Replace separator with larger size Oil float defective or dirty (will not close) Disassemble and clean or replace defective float component (flanged versions); Replace oil separator (welded version). 63 TROUBLESHOOTING REGULATORS Problem Causes Pilot inlet filter screen obstructed Corrective Action Clean or replace. Erratic Pressure Control Piston bleed hole restriction Excessive dirt in pilot/solenoid Regulator Will Not Open (EPRBS Version) Disassemble valve and clean. Replace if necessary. Piston bleed hole restriction Coil is damaged or not energized Verify coil is energized. Replace if necessary. Piston bleed partially obstructed Disassemble and clean regulator. Excessive Pressure Drop Across the Regulator Pilot or solenoid leaking internally Replace pilot assembly. Refer to extended capacities table. Install correct sized regulator. Regulator undersized Piston bleed port obstructed Clean or replace. Pilot inlet filter screen obstructed Regulator Hunting-side Fluctuations in Controlled Pressure Regulator oversized Refer to extended capacities table. Install correct sized regulator. Regulator and TXV have control interaction Turn off pilot pressure. Ensure regulator is wide open. Adjust superheat to required setting. Turn pilot pressure back on. Regulator and cylinder unloaders have control interaction The unloader should be set to control at least 5 psig lower than regulator. Pilot inlet filter screen obstructed Clean or replace. Pilot inlet pressure is too low Increase pressure ot a minimum of 25 psi higher than the main valve outlet pressure. Regulator Will Not Provide Pressure Control Locate and remove the stoppage or dirt. Replace Piston jammed due to excessive dirt; Inoperative pilot. A broken diaphragm can be detected by pilot or broken diaphragm checking for leaks around the adjusting stem. Regulator Will Not Close (EPRBS Version) Dirt under seat Disassemble and clean. Excessive piston seal leakage Replace bell piston assembly. Plugged pilot filter Clean or replace. Pilot supply turned off or restricted Verify pilot inlet pressure is at least 25 psig greater than valve outlet. Excessive dirt in pilot/solenoid Replace pilot assembly. TROUBLESHOOTING HOT GAS REGULATORS Problem Causes Low Suction Pressure - Valve Open Will Not Bypass - Valve Not Open Suction Pressure Swings Erratically Bypass Continuously - Suction Pressure High Setpoint Drifts Corrective Action Valve undersized Replace valve with correct size 1. Solenoid (if present) not energized 2. Valve sticking closed 3. Not set properly 4. Bad pilot 1. Repair (replace solenoid coil) 2. Replace 3. Recalibrate 4. Replace Oversized valve Replace valve with correct size 1. Manual stem screwed down 2. Valve sticking open 3. Bad pilot 1. Back stem out 2. Repair/replace valve 3. Replace pilot Bad pilot Replace pilot TROUBLESHOOTING CRANKCASE REGULATORS Problem Valve Won't Adjust or Is Erratic Valve Throttles Constantly Causes Corrective Action With system running, open the valve adjustment to open the valve and flush away the contaminant. If this fails, replace valve. Dirt under seat Re-adjust bypass and/or CPR valve so that the On system equipped with Hot Gas Bypas Valves, CPR setting is higher than the discharge bypass the bypass valve setting is higher than CPR valve TXV with MOP feature used with the CPR To improve pull-down time, replace TXV with equivalent without MOP feature Valve setting is too low Re-adjust the CPR to a higher setting - see adjustment procedure Temperature Pull-Down After Defrost is Too Long 64 Problem Causes Compressor tripping on Internal Thermal Protector - Fails to Start-Up and Run Long Enough to Pull Down Temperature Corrective Action CPR setting too high Re-adjust the CPR to a lower setting - see adjustment procedure CPR setting is too low Valve Fails to Open Valve defective - bellows leak, pressurizing the upper adjustment assembly Replace valve TROUBLESHOOTING HEAD PRESSURE CONTROLS Problem Causes Low Head Pressure During Operation Systen Runs High Head Pressure -orCycles on High Pressure Cut-Out Corrective Action Valve unable to throttle "C" port 1. Foreign material wedged between "C" port seat and seat disc 2. Power element lost its charge 3. Insufficient winter-time system charge 1. Artificially raise head pressure and tap valve body to dislodge foreign material 2. Change valve 3. Add refrigerant per Table 3 Wrong charge pressure in valve for refrigerant Change valve Receiver exposed to low ambient conditions is acting as condenser Insulate the receiver Hot gas bypass line restricted or shut off Clear obstruction or open valve Compressor not pumping, restriction in liquid line, low side causing very low suction pressure Change or repair compressor; clear obstruction or other reason for low suction pressure Condenser fan not running or turning in wrong direction Replace or repair fan motor, belts, wiring or controls as required Fan cycling Run condenser fan continuously while system is running Pressure drop through condenser exceeds allowable 20 psi forcing "B" port partially open Repipe, recircuit, or change condenser as required to reduce condenser pressure drop to less than 20 psi Condenser undersized or air flow restricted or short circuiting Increase size of condenser or remove air flow restriction or short circuit as required "B" port wedged open due to foreign material between seat and seat disc Artificially reduce head pressure below valve setpoint and tap valve body with system running to dislodge foreign material "B" port seat damaged due to foreign material Change valve Wrong charge pressure in valve for refrigerant Excessive system charge or air in system Purge or bleed off refrigerant or noncondensables as system requires Obstruction or valve closed in discharge or condenser drain line Clear obstruction or open valve Liquid line solenoid fails to open Check solenoid CHARGING THE SYSTEM - THEORETICAL METHOD Weighing the Charge (Method has practical limitations) Add refrigerant until the sight glass is clear and free of bubbles. Determine refrigerant required to fill the condenser, see Table 3 below. Add this additional amount. Table 3 - Refrigerant lbs. per ft.* Condenser Tube Size - O.D. (in inches)** and Ambient Temperature ° F Refrigerant 3/8" 40° 0° 1/2" -20° -40° 5/8" 40° 0° -20° -40° 40° 0° -20° -40° R134a .051 .054 .055 .057 .095 .099 .102 .105 .150 .157 .164 .167 R22 .051 .054 .055 .056 .094 .099 .102 .104 .150 .159 .163 .167 R404A/R507 .053 .056 .058 .059 .098 .104 .107 .109 .157 .166 .171 .175 * Return bends: 3/8” O.D. - 20 ft; 1/2 O.D. - 25 ft.; 5/8 O.D. - 30 ft. ** Wall thickness: 3/8” O.D. - .016”; 1/2 O.D. - .017”; 5/8 O.D. - .018” 65 Emerson Climate Technologies Flow Controls St. Louis, Missouri 63141 (314) 569-4500 WEBSITE: www.emersonflowcontrols.com E-MAIL: sales@emersonclimate.com Form No. 2004FC-141 R2(4/06) Emerson Climate Technologies and the Emerson Climate Technologies logo are service marks and trademarks of Emerson Electric Co. All other trademarks are property of their respective owner. © 2004 Flow Controls. Printed in the USA.