Centrifugal Roof Exhaust Fans

advertisement
Centrifugal Roof Exhaust Fans
Models H-G and H-GB
Downblast High Wind & Hurricane Fans, Miami-Dade NOA# 07-0503.07
November
2007
Models H-G and H-GB
®
The Greenheck Models H-G (direct drive) and H-GB (belt drive) are centrifugal roof exhaust fans designed
specifically for high wind applications, such as hurricanes, tornadoes, and other high wind areas. The down
blast design is ideal for general clean air applications where air is discharged directly onto the roof surfaces.
Performance ranges up to 14,000 cfm (24,000 m3/hr) and up to 2.75 inches wg (700 Pa).
High winds can reach upwards of 150 mph in much of the world. At these elevated wind speeds roof top
equipment can see a force of over 750 pounds (340 kg). High winds and extreme forces are the cause of most
storm damage. In 2005, over $125 billion dollars in damage is linked to high winds and storms.
Third Party Certified
•
Miami-Dade NOA # 07-0503.07.
•
Withstands wind loads up to 150 mph.
•
P.E. (Professional Engineer) calculations available.
•
Tested to ASTM and Florida Building Code standards.
•
No tie downs to roof required.
•
Installation details provided.
High Wind Resistance is Assured
•
Internal Bracing - High strength internal support structure and
bracing.
•
Shroud - Drawn shroud with integral rolled bead for consistent
material thickness and strength.
•
Drive assembly - Motor and drive frame are mounted on true
vibration isolators, and sized for 150% of maximum driven
horsepower.
•
Roof Curb - High wind roof curb is provided and tested as an
assembly.
Remember that the H-G and H-GB are the only powered roof exhaust fans that are tested and certified to
withstand 150 mph winds.
*UL/cUL is optional and must be specified.
H-G & H-GB models are listed for electrical
(UL/cUL 705) File no. E40001
Greenheck Fan Corporation certifies that Models H‑G
and H-GB fans shown herein are licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance with
AMCA Publication 211 and Publication 311 and comply
with the requirements of the AMCA Certified Ratings
Program. The certified ratings for Models H-G and
H‑GB are shown on pages 10 to 39.
Leading Edge Technical Support
When you need extensive product and IOM (Installation, Operating and Maintenance
Manual) information, our products are supported by the industry’s best product
literature, electronic media, and Computer Aided Product Selection (CAPS) program.
You’ll also find this information on our website at www.greenheck.com
You can always count on personal service and expertise from our national and
international representative organization. To locate your nearest Greenheck
representative, call 715-359-6171 or visit our website at www.greenheck.com
High Wind Force Standards
®
Greenheck is leading the High Wind Standard for roof top fans and ventilators. By analyzing calculations,
computer simulations, actual testing, and other standards Greenheck developed the High Wind Standard.
Outside Curb
Dimension
Use 3/8 inch (10 mm) expansion
anchor or equal into concrete.
Fasteners one each corner
as detailed.
H-GPF Curb Height
8 to 18 inches
(203 to 457 mm)
(Optional 24 inch
(610 mm) SD Curb)
1 inch (25 mm) Insulation
Each side at center of unit.
Maximum fastener spacing of 8
inches (203 mm), add additional
fasteners to satisfy.
Roof Opening
21/2 inch (64 mm) Embedment
Recommended minimum
15/8 inch (41 mm)
Minimum Concrete
Strength of 2000 PSI
Minimum 13/4 inch
(44 mm) edge distance
5 inch (127 mm) Mounting Flange
Center fasteners
on flange
Outside Flange Dimension
•
Structural calculations performed by a state
licensed Professional Engineer (P.E.) to verify the
150 mph (61 psf) capability of each fan and roof
curb assembly. These calculations include Finite
Element Analysis (FEA) and a stamped P.E. report
of the fans compliance to ASCE 7-02 Minimum
Design Loads for Buildings and Other Structures
Standard snd the Florida Building Code.
•
Detailed report specifying appropriate size,
number, and spacing of fasteners attaching the
fan to roof curb and to affix roof curb to building,
performed and stamped by a licensed P.E.
•
Certified independent third party testing
completed in accordance with ASTM Standard
E330 and Miami-Dade Test Protocol TAS202, Static Pressure Difference. The report
includes one set of manufacturer’s design
drawings marked and verified by the certified
testing laboratory. All tests are video taped for
documentation of test method and results.
What you get from
Greenheck – One Step Further
CONCRETE DECK ANCHORING DETAIL
Government Certification
The H-G and H-GB Models are the only downblast aluminum fans in the
industry that have received a Miami-Dade NOA for high wind (150 mph)
and hurricane zones. (NOA # 07-0503.07).
State Licensed P.E. Calculations
The H-G and H-GB Models have been analyzed and stamped by a state licensed P.E.
to the ASCE 7-02 Standard which meets the IBC, Florida and Miami-Dade codes. Both
models have been proven to withstand winds in excess of 150 mph (61 psf).
Testing
Each of the Greenheck models have been subjected to extensive testing procedures. The H-G and
H-GB have been certified by an independent third party to the ASTM E330 Static Pressure Difference
Standard and TAS-202 static pressure difference Florida Building Code Test Protocol.
Computational Fluid Dynamics (CFD)
All Greenheck high wind models have been analyzed using Computational Fluid Dynamics (CFD).
CFD is computer software designed to simulate the flow of high speed (150 mph) winds over the
surface of objects. The software records the force profile exerted on the fan, so it can be utilized in
Finite Element Analysis (FEA).
Finite Element Analysis (FEA)
Utilizing the results from CFD analysis Greenheck can accurately predict the stress, strain, and
deflection resulting from high wind loads. Greenheck high wind units have been proven to withstand
150 mph winds through Finite Element Analysis utilizing CFD results.
Standard Construction Features
Roof Curb - High wind load fans are certified
with one of two Greenheck high wind roof curbs.
Standard 12 inch (305 mm) in height H-GPF curb has
a 5 inch (127 mm) flashing flange. Roof curbs ship
separate for field installation with attachment details
provided.
Internal Supports - Heavy gauge supports and
bracing are added for additional strength to
withstand a wind of 150 mph.
Wheel - An aluminum, backward-inclined, nonoverloading centrifugal wheel is utilized to generate
high efficiency and minimal sound. Wheel cones
are carefully matched to the venturi for maximum
efficiency. Each wheel is robotically welded and
statically and dynamically balanced for long life and
quiet operation.
Disconnect Switch - NEMA-1 switch is factory
mounted and wiring is provided from the motor as
standard (other switches are available). All wiring
and electrical components comply with the National
Electric Codes (NEC) and are either UL listed or
recognized.
Internal Conduit Chase - A large diameter conduit
for installing electrical wiring through the curb cap
into the motor compartment.
Fan Shaft - Is precisely sized, ground, and polished
so the first critical speed is at least 25% over the
maximum operating speed. Where the shaft makes
contact with bearings, close tolerances result in
longer bearing life.
Bearings - 100% factory tested and designed
specifically for air handling applications with a
minimum (L10) life in excess of 100,000 hours (L50
average life of 500,000 hours).
Motor Cooling - Cooling fins located on top of
fan wheel draw outside air through a large space
between the fan shroud and the motor cover directly
into the motor compartment. Positive motor cooling
with fresh air results in maximum motor life.
®
Motor - Carefully matched to the fan load and is
mounted out of airstream.
Motor Cover - Constructed of aluminum, machine
punched, and attached with stainless steel hardware
for easy removal and access to motor compartment
and drive assembly.
Drive Assembly - Belts, pulleys, and keys are
oversized 150% of driven horsepower. Machined
cast pulleys are adjustable for final system balancing.
Belts are static free and oil resistant.
Vibration Isolation - Vibration isolators support the
drive assembly and wheel for long life and quiet
operation.
Fan Shroud - One piece, heavy gauge aluminum
with a rolled bead for extra strength directs exhaust
air away from the mounting surface. The curb cap
and integral deep spun venturi are attached to the
windband and also constructed of aluminum to
prevent corrosion.
Nameplate - Permanent stamped aluminum plate for
exact model and serial number identification.
Galvanized Birdscreen - Galvanized rigid wire
protects the fan’s discharge from birds or small
objects.
Curb Cap - Curb cap (with integral deep spun venturi)
is constructed of aluminum and is one piece for a
weather-tight fit.
Lower Windband - Heavy gauge aluminum with
formed edges for added strength and provide
weather resistance.
Lifting Points - Select models have various lifting
points located on the drive frame and bearing plates.
Motor Cooling
Space
®
Birdscreen
Bearing Plate
Lifting Points
Lower Windband
Curb Cap
Drive Frame
Lifting Points
Fan Shaft
Motor Cover
Bearings
Drive Assembly
Disconnect
Switch
Motor
Conduit
Chase
Fan Shroud
Shroud
Brace
Vibration
Isolators
Internal
Supports
Wheel
Nameplate
Roof Curb with
5 inch (127 mm)
Flashing Flange
Sizes 260 and Larger
Require Tie Downs
(Included)
Options and Accessories
®
Roof curbs are provided as a standard with the H-G and H-GB. The roof curb ships separate to allow for finishing of
the roof prior to the fan installation.
•
H-GPF is standard at 12 inch (305 mm) in height for typical
applications.
•
H-GPF is available up to 18 inch (460 mm) in height to meet
greater height requirements.
•
SD (Severe Duty) curbs are available to meet 24 inch (610 mm)
curb requirements.
•
Mounting details for the roof curb to the roof substrate and the
fan to the roof curb are included with each H-G and H-GB fan.
Birdscreen - Galvanized mesh is standard, optional aluminum or stainless steel rigid wire are also available.
Coatings - Wide variety of coatings and colors are available. Greenheck coatings and
resistance charts can be found in the coatings bulletin.
Disconnect Switches - A wide selection of NEMA rated switches are available for positive
electrical shutoff and safety, including: dust-tight, rainproof, and corrosion-resistant.
Switches may be internally or externally mounted.
Dampers - Designed to prevent outside air from entering back into the building when
fan is off. Includes: gravity and motorized dampers. Damper sizes are shown on each
performance data page.
Tie Down Points - Four brackets located on the shroud for securing the fan in heavy wind
applications. Cables and anchors by others.
Speed Controllers - Available for use with shaded pole and permanent split capacitor
(PSC) open motors on Model H-G fans. They provide an economical means of system
balancing with direct drive fans.
Curb Seal - Rubber seal between fan and curb to assure proper sealing when attached to a curb.
H-G and H-GB models are listed for electrical (UL/cUL 705) File no. E40001
Model Number Code
®
The Model Number Code is designed to completely identify the fan. The correct code letters must be specified to
designate belt or direct drive. The remainder of the model number is determined by the size and performance.
H
-
GB
-
240
HP
-
5
Motor HP (Belt Drive only)
Model
6
4
3
5
7
H - High-Wind / Hurricane Fan
Configuration
G - Direct Drive
GB - Belt Drive
=
=
=
=
=
1/6
1/4
1/3
1/2
3/4
10
15
20
30
=
=
=
=
1
11/2
2
3
50 = 5
75 = 71/2
100 = 10
150 = 15
Fan Size
060 through 300
Motor RPM (Direct Drive only)
A = 1725
B = 1140
C = 860
Pressure Level (Belt Drive only)
HP - High Pressure Wheel
D = 1550
E = 1050
G = 1300
Typical Installation
Models H-G and H-GB exhaust fans are designed to meet
the needs of general clean air applications. Tests were
conducted to assure safe, rugged and reliable fans.
Factory Wired
from Motor to
Disconnect
Due to the varying airstreams encountered in commercial
ventilation, system designers must be aware of national,
state, and local codes and guidelines governing these
installations. Local code authorities should be consulted
before proceeding with any ventilation project.
Roofing materials can extend to the top of the curb, roof
curbs should be 1 inch (25 mm) total, or 1/2 inch (13 mm)
on each side, less than the unit curb cap to allow for
roofing and flashing.
1/4 in. (6 mm)
Fastener
1/2 in. (13 mm)
Wiring by
Others
For recommended duct size, damper size, and roof
opening dimensions, refer to the performance data pages.
Damper
11/4 in. (32 mm)
Installation must include a means for inspecting, cleaning
and servicing the exhaust fan.
8 - 24 in.
(203 - 610 mm)
H-GPF or SD Curb
4 in. (102 mm)
From Curb Edge
Poor
Recommended
Duct and
Damper Size
11/4 in. (32 mm)
Poor
Go
Recommended
Roof Opening
Fan Inlet Connections
In order to assure proper fan performance, caution must be exercised in fan placement and connection to the
ventilation system. Obstructions, transitions, poorly designed elbows, improperly selected dampers, etc., can
cause reduced performance, excessive noise, and increased mechanical stress. For performance to be as
published, the system must provide uniform and stable airflow into the fan.
Good
Poor
Poor
Good
Typical Anchoring
®
Concrete Deck Anchoring
Use 3/8 inch (10 mm) expansion
anchor or equal into concrete.
Fasteners one on each corner
as detailed.
Outside of Roof Curb
(1 inch (25 mm) less than)
Fan Curb Cap
Each side at center of unit.
Maximum fastener spacing of 8
inches (203 mm), add additional
fasteners to satisfy.
11/4 inch (32 mm)
H-GPF Curb Height
8 to 18 inches
(203 to 457 mm)
(Optional 24 inch
(610 mm) SD Curb)
11/4 inch
(32 mm)
1 inch (25 mm) Insulation
Roof Opening
21/2 inch (64 mm) Embedment
Recommended.
Minimum 15/8 inch (41 mm).
Minimum Concrete
Strength of 2000 PSI
Corner Detail
Minimum 13/4 inch
(44 mm) edge distance
CORNER TOP VIEW
Center fasteners
on flange
5 inch (127 mm) Mounting Flange
Outside Flange
H-G
Size
H-GB
Size
060 - 075
-
17 x 17 (432 x 432)
080 - 095
-
101 - 121
071 - 131
131 - 141
141 - 161
22 x 22 (559 x 559)
150
-
26 x 26 (660 x 660)
160 - 180
180 - 200
-
Fan Curb Cap
Roof Opening
Fasteners Per Side
101/2 x 101/2 (267 x 267)
5
26 x 26 (660 x 660)
17 x 17 (432 x 432)
121/2 x 121/2 (318 x 318)
5
26 x 26 (660 x 660)
19 x 19 (483 x 483)
141/2 x 141/2 (368 x 368)
5
28 x 28 (711 x 711)
181/2 x 181/2 (470 x 470)
5
31 x 31 (787 x 787)
181/2 x 181/2 (470 x 470)
5
35 x 35 (889 x 889)
30 x 30 (762 x 762)
201/2 x 201/2 (521 x 521)
7
39 x 39 (991 x 991)
220 - 240
34 x 34 (864 x 864)
261/2 x 261/2 (673 x 673)
7
43 x 43 (1092 x 1092)
260 - 300
40 x 40 (1016 x 1016)
321/2 x 321/2 (826 x 826)
7
49 x 49 (1245 x 1245)
CONCRETE DECK ANCHORING DETAIL
Outside Flange
All dimensions in inches (millimeters).
Metal Building/Steel Deck Anchoring
Use #12-14 self-drilling
screws or equal.
Outside of Roof Curb
(1 inch (25 mm) less than)
Fan Curb Cap
H-GPF Curb Height
8 to 18 inches
(203 to 457 mm)
(Optional 24 inch
(610 mm) SD Curb)
11/4 inch (32 mm)
11/4 inch
(32 mm)
Fasteners one on each corner
as detailed.
Each side at center of unit.
Maximum fastener spacing
of 8 inches (203 mm), add
additional fasteners to satisfy.
1 inch (25 mm) Insulation
Roof Opening
Corrugated
Roof Deck
Minimum 12 Ga. Steel
Corner Detail
Roof Truss
5 inch (127 mm) Mounting Flange
CORNER TOP VIEW
Center fasteners
on flange
Outside Flange
H-G
Size
H-GB
Size
060 - 075
-
17 x 17 (432 x 432)
080 - 095
-
101 - 121
071 - 131
131 - 141
150
Fan Curb Cap
Roof Opening
Fasteners Per Side
101/2 x 101/2 (267 x 267)
5
26 x 26 (660 x 660)
17 x 17 (432 x 432)
121/2 x 121/2 (318 x 318)
5
26 x 26 (660 x 660)
19 x 19 (483 x 483)
141/2 x 141/2 (368 x 368)
5
28 x 28 (711 x 711)
141 - 161
22 x 22 (559 x 559)
181/2 x 181/2 (470 x 470)
5
31 x 31 (787 x 787)
-
26 x 26 (660 x 660)
181/2 x 181/2 (470 x 470)
5
35 x 35 (889 x 889)
160 - 180
180 - 200
30 x 30 (762 x 762)
201/2 x 201/2 (521 x 521)
7
39 x 39 (991 x 991)
-
220 - 240
34 x 34 (864 x 864)
261/2 x 261/2 (673 x 673)
7
43 x 43 (1092 x 1092)
-
260 - 300
40 x 40 (1016 x 1016)
321/2 x 321/2 (826 x 826)
7
49 x 49 (1245 x 1245)
All dimensions in inches (millimeters).
Outside Flange
Typical Anchoring Continued
Wood Deck Anchoring
®
Use #12 Wood Screws or equal into
minimum No. 1/No. 2 Southern Pine
wood support.
Outside of Roof Curb
(1 inch (25 mm) less than)
Fan Curb Cap
11/4 inch (32 mm)
Each side at center of unit. Maximum
fastener spacing of 6 inches (152 mm),
add additional fasteners to satisfy.
1 inch (25 mm) Insulation
H-GPF Curb Height
8 to 18 inches
(203 to 457 mm)
(Optional 24 inch
(610 mm) SD Curb)
11/4 inch
(32 mm)
Fasteners one on each corner
as detailed.
Roof Opening
2 inch (51 mm)
Minimum Embedment
Wood Decking
Corner Detail
5 inch (127 mm) Mounting Flange
CORNER TOP VIEW
Center fasteners
on flange
Wood Support Member
Nominal 2 x 4, 6, 8
Outside Flange
H-G
Size
H-GB
Size
060 - 075
-
17 x 17 (432 x 432)
080 - 095
-
101 - 121
071 - 131
131 - 141
150
Fan Curb Cap
Roof Opening
Fasteners Per Side
Outside Flange
101/2 x 101/2 (267 x 267)
5
26 x 26 (660 x 660)
17 x 17 (432 x 432)
121/2 x 121/2 (318 x 318)
5
26 x 26 (660 x 660)
19 x 19 (483 x 483)
141/2 x 141/2 (368 x 368)
5
28 x 28 (711 x 711)
141 - 161
22 x 22 (559 x 559)
181/2 x 181/2 (470 x 470)
5
31 x 31 (787 x 787)
-
26 x 26 (660 x 660)
181/2 x 181/2 (470 x 470)
7
35 x 35 (889 x 889)
160 - 180
180 - 200
30 x 30 (762 x 762)
201/2 x 201/2 (521 x 521)
7
39 x 39 (991 x 991)
-
220 - 240
34 x 34 (864 x 864)
261/2 x 261/2 (673 x 673)
7
43 x 43 (1092 x 1092)
-
260 - 300
40 x 40 (1016 x 1016)
321/2 x 321/2 (826 x 826)
9
49 x 49 (1245 x 1245)
All dimensions in inches (millimeters).
Typical Mounting
Fan to Curb
Model H-G
or H-GB
5/16 inch recommended
1/4 inch fastener minimum
See table for fastener quantities
H-G Size
H-GB Size
Fasteners Per
Side
Total
Fasteners
060 - 141
071 - 161
3
12
150 - 180
180 - 300
5
20
Tie downs are not required to
meet 150 MPH wind loads for
sizes 240 and smaller
(Tie downs are included
for larger sizes)
Model H-GPF
or SD Curb
Fasteners on each side of the fan are to be installed
with one fastener 4 inches (102 mm) from each edge and
one fastener centered. The remaining fasteners are to
be equally spaced.
Fan to curb tie down is not required to meet 150 mph
wind loads for sizes 240 and smaller.
H-G-060 and 065 - Direct Drive
193/8
(492)
H-
W.G.
*121/8
(308)
12
(305)
17
(432)
5 (127)
®
Damper Size = 8 x 8 (203 x 203)
Roof Opening = 101/2 x 101/2 (267 x 267)
^Approximate Unit Weight = 18 lb. (8 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Fan
RPM
H-G-060-E
1/200
1050
H-G-060-G
H-G-060-D
H-G-065-E
H-G-065-G
H-G-065-D
1/100
1/60
1/100
1/60
1/30
1300
1550
1050
1300
1550
CFM / Static Pressure in Inches WG
0
0.05
0.1
0.125
0.15
CFM
138
116
90
73
53
0.01
0.2
BHP
0.00
0.00
0.01
0.01
Sones
1.7
1.7
1.7
1.7
1.7
CFM
170
153
135
125
113
85
BHP
0.01
0.01
0.01
0.01
0.01
0.01
0.25
0.3
Sones
2.9
2.8
2.8
2.7
2.7
2.6
CFM
203
188
173
166
158
140
120
92
BHP
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.2
Sones
4.2
3.9
3.8
3.8
3.8
3.7
3.7
3.6
CFM
187
161
130
110
87
BHP
0.01
0.01
0.01
0.01
0.01
Sones
2.2
2.1
1.9
1.8
1.7
CFM
231
211
189
178
163
130
92
BHP
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.375
Sones
3.2
3.1
3.0
2.9
2.9
2.8
2.7
CFM
276
259
241
232
223
201
176
145
96
BHP
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.02
Sones
4.9
4.6
4.5
4.5
4.4
4.3
4.3
4.1
4.0
0.4
­­­
Performance
certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values
in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.
10
H-G-070 and 075 - Direct Drive
193/8
(492)
H-
W.G.
*121/8
(308)
12
(305)
17
(432)
5 (127)
®
Damper Size = 8 x 8 (203 x 203)
Roof Opening = 101/2 x 101/2 (267 x 267)
^Approximate Unit Weight = 18 lb. (8 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Fan
RPM
H-G-070-E
1/100
1050
H-G-070-G
H-G-070-D
H-G-075-E
H-G-075-G
H-G-075-D
1/60
1/30
1/80
1/50
1/25
1300
1550
1050
1300
1550
CFM / Static Pressure in Inches WG
0
0.05
0.1
0.125
0.15
CFM
253
226
195
179
152
0.01
0.2
0.25
BHP
0.01
0.01
0.01
0.01
Sones
2.7
2.1
1.7
1.5
1.2
CFM
314
292
269
2557
244
214
171
BHP
0.01
0.1
0.02
0.02
0.02
0.02
0.02
0.3
0.375
Sones
4.1
3.7
3.4
3.3
3.2
2.9
2.6
CFM
374
356
337
327
317
297
274
244
190
BHP
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.03
0.03
Sones
5.6
5.4
5.2
5.2
5.1
4.9
4.7
4.5
4.1
CFM
297
260
222
200
176
BHP
0.01
0.01
0.01
0.01
0.01
Sones
3.6
3.1
2.9
2.8
2.6
CFM
367
338
309
293
277
241
195
BHP
0.02
0.02
0.02
0.02
0.02
0.02
0.02
Sones
4.1
3.9
3.7
3.7
3.7
3.6
3.5
CFM
438
413
389
377
364
337
309
277
214
BHP
0.03
0.03
0.3
0.04
0.04
0.04
0.04
0.04
0.03
Sones
6.1
5.8
5.6
5.4
5.3
5.1
4.9
4.9
4.8
0.4
­­­
Performance
certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values
in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.
11
H-G-080 and 085 - Direct Drive
213/4
(552)
H-
W.G.
*145/8
(371)
12
(305)
17
(432)
5 (127)
®
Damper Size = 10 x 10 (254 x 254)
Roof Opening = 121/2 x 121/2 (318 x 318)
^Approximate Unit Weight = 26 lb. (12 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Fan
RPM
H-G-080-E
1/40
1050
H-G-080-G
H-G-080-D
H-G-085-E
H-G-085-G
H-G-085-D
1/30
1/20
1/40
1/30
1/20
1300
1550
1050
1300
1550
CFM / Static Pressure in Inches WG
0
0.1
0.125
0.15
0.2
0.25
CFM
335
268
249
230
189
134
0.02
0.3
0.375
BHP
0.01
0.02
0.02
0.02
0.02
Sones
3.8
3.7
3.6
3.7
3.9
4.2
CFM
415
361
348
333
303
272
239
174
BHP
0.02
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.5
Sones
5.4
5.4
5.4
5.4
5.4
5.5
5.6
5.9
CFM
495
450
439
427
404
379
354
314
237
BHP
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.6
Sones
7.3
7.3
7.3
7.3
7.3
7.2
7.3
7.3
7.6
CFM
398
326
307
286
240
179
BHP
0.01
0.02
0.02
0.02
0.02
0.02
Sones
4.0
3.9
3.9
3.9
4.1
4.3
CFM
493
436
420
405
375
340
302
233
BHP
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.625
Sones
5.5
5.3
5.3
5.3
5.3
5.3
5.4
5.5
CFM
588
541
528
515
490
464
439
394
308
168
BHP
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
Sones
7.6
7.4
7.4
7.4
7.4
7.4
7.4
7.4
7.6
8.1
­­­
Performance
certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values
in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.
12
H-G-090 and 095 - Direct Drive
213/4
(552)
H-
W.G.
*145/8
(371)
12
(305)
17
(432)
5 (127)
®
Damper Size = 10 x 10 (254 x 254)
Roof Opening = 121/2 x 121/2 (318 x 318)
^Approximate Unit Weight = 26 lb. (12 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Fan
RPM
H-G-090-E
1/40
1050
H-G-090-G
H-G-090-D
H-G-095-E
H-G-095-G
H-G-095-D
1/25
1/15
1/30
1/12
1/8
1300
1550
1050
1300
1550
CFM / Static Pressure in Inches WG
0
0.1
0.125
0.15
0.2
0.25
CFM
520
441
420
398
351
293
0.02
0.3
0.375
BHP
0.01
0.02
0.02
0.02
0.02
Sones
4.0
3.9
3.9
4.0
4.1
4.2
CFM
644
580
565
549
515
478
440
373
BHP
0.03
0.03
0.04
0.04
0.04
0.04
0.04
0.05
0.5
0.625
Sones
5.4
5.4
5.4
5.4
5.4
5.5
5.5
5.6
CFM
768
714
701
688
662
633
605
557
473
338
BHP
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.08
0.07
Sones
7.6
7.5
7.5
7.5
7.5
7.4
7.4
7.4
7.4
7.8
CFM
717
606
570
534
468
389
290
BHP
0.03
0.03
0.04
0.04
0.04
0.04
0.03
Sones
5.4
4.5
4.5
4.5
4.4
4.5
4.6
CFM
888
802
780
754
695
640
586
493
184
BHP
0.06
0.06
0.06
0.06
0.07
0.07
0.07
0.07
0.05
Sones
7.6
6.8
6.7
6.6
6.5
6.4
6.4
6.4
6.8
CFM
1059
987
969
950
912
863
814
745
623
474
BHP
0.10
0.10
0.10
0.11
0.11
0.11
0.11
0.12
0.12
0.11
Sones
9.6
9.4
9.3
9.2
9.0
8.8
8.7
8.7
8.7
8.7
­­­
Performance
certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values
in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.
13
H-G-101 and 121 - Direct Drive
245/8
(625)
H-
W.G.
*20
(508)
12
(305)
19
(483)
5 (127)
®
Damper Size = 12 x 12 (304 x 304)
Roof Opening = 141/2 x 141/2 (368 x 368)
^Approximate Unit Weight = 43 lb. (20 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Fan
RPM
H-G-101-C
1/8
860
H-G-101-B
H-G-101-A
H-G-121-C
H-G-121-B
H-G-121-A
1/6
1/4
1/8
1/6
1/4
1140
1725
860
1140
1725
CFM / Static Pressure in Inches WG
0
0.1
0.125
CFM
766
625
588
0.03
0.25
0.3
0.375
BHP
0.02
0.03
Sones
4.3
4.2
4.2
CFM
1015
917
893
747
683
569
BHP
0.05
0.06
0.06
0.06
0.06
0.06
0.5
0.625
0.75
Sones
7.1
7.0
7.0
6.8
6.8
6.6
CFM
1536
1470
1454
1374
1340
1277
1181
1086
974
BHP
0.17
0.18
0.19
0.20
0.20
0.20
0.21
0.22
0.22
Sones
12.1
11.9
11.8
11.6
11.5
11.3
11.2
11.3
11.7
CFM
922
767
723
450
BHP
0.03
0.03
0.04
0.04
Sones
5.6
5.2
5.2
5.2
CFM
1222
1107
1078
918
848
734
335
BHP
0.06
0.07
0.07
0.08
0.09
0.09
0.07
1
Sones
8.1
7.9
7.9
7.8
7.8
8.1
9.8
CFM
1849
1772
1753
1659
1621
1560
1453
1341
1223
911
BHP
0.22
0.23
0.24
0.25
0.26
0.27
0.28
0.29
0.3
0.29
Sones
14.1
14.0
13.9
13.8
13.6
13.4
13.4
13.4
13.4
14.1
­­­
Performance
certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values
in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.
14
H-G-131 and 141 - Direct Drive
287/8
(733)
H-
W.G.
*20
(508)
12
(305)
22
(559)
5 (127)
®
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
^Approximate Unit Weight = 59 lb. (27 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Fan
RPM
H-G-131-C
1/8
860
H-G-131-B
H-G-131-A
H-G-141-C
H-G-141-B
1/6
1/2
1/8
1/6
1140
1725
860
1140
CFM / Static Pressure in Inches WG
0
0.1
0.125
0.25
0.3
CFM
1193
1050
1011
771
626
0.055
0.375
0.5
BHP
0.04
0.049
0.051
0.056
Sones
6.5
6.1
6.0
5.9
5.9
CFM
1581
1482
1452
1304
1239
1130
889
BHP
0.094
0.105
0.108
0.12
0.123
0.13
0.129
0.625
0.75
1
Sones
9.9
9.8
9.7
9.4
9.2
9.0
8.8
CFM
2393
2340
2327
2225
2186
2127
2030
1931
1817
1555
BHP
0.325
0.339
0.342
0.366
0.376
0.389
0.407
0.423
0.426
0.453
Sones
19.2
18.9
18.9
18.4
18.4
18.2
18.1
18.1
17.8
17.4
CFM
1376
1205
1161
919
798
489
BHP
0.055
0.064
0.066
0.074
0.074
0.063
Sones
6.8
6.6
6.5
6.4
6.6
8.0
CFM
1824
1701
1667
1498
1425
1314
1113
794
BHP
0.129
0.141
0.144
0.158
0.163
0.17
0.175
0.158
Sones
10.4
10.4
10.3
9.8
9.5
9.1
8.7
8.4
­­­
Performance
certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values
in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.
15
H-G-150 and 160 - Direct Drive
®
35 /2
(902)
1
*211/8
(537)
5 (127)
H-
12
(305)
26
(660)
W.G.
Model H-G-150
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
^Approximate Unit Weight = 59 lb. (27 kg)
351/2
(902)
*215/8
(549)
12
(305)
30
(762)
5 (127)
Models H-G-160
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
^Approximate Unit Weight = 81 lb. (37 kg)
All dimensions in inches (millimeters). *May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Fan
RPM
H-G-150-C
1/8
860
H-G-150-B
H-G-160-C
H-G-160-B
1/4
1/8
1/3
1140
860
1140
CFM / Static Pressure in Inches WG
0
0.1
0.125
0.2
0.25
0.3
0.375
CFM
1772
1598
1553
1415
1304
1194
1005
0.13
.5
.625
.75
1114
BHP
0.09
0.09
0.10
0.12
0.12
0.13
Sones
7.9
7.8
7.8
7.5
7.4
7.5
7.7
CFM
2349
2217
2185
2085
2017
1949
1836
1628
1397
BHP
0.21
0.21
0.21
0.21
0.23
0.25
0.27
0.29
0.29
0.28
Sones
11.7
11.6
11.6
11.3
11.1
11.0
10.9
11.2
11.8
12.8
CFM
2008
1828
1784
1637
1535
1421
1230
0.14
BHP
0.10
0.11
0.12
0.13
0.13
0.13
Sones
8.0
7.7
7.7
7.5
7.4
7.3
7.3
CFM
2662
2521
2489
2392
2319
2245
2135
1933
1697
1411
BHP
0.23
0.25
0.25
0.27
0.28
0.28
0.29
0.31
0.32
0.32
Sones
13.6
13.4
13.4
13.3
13.1
13.1
13.1
12.9
12.7
12.6
­­­
Performance
certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values
in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.
16
H-G-170 and 180 - Direct Drive
®
351/2
(902)
*215/8
(549)
5 (127)
H-
12
(305)
30
(762)
W.G.
Models H-G-170
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
^Approximate Unit Weight = 81 lb. (37 kg)
351/2
(902)
*223/4
(578)
12
(305)
30
(762)
5 (127)
Model H-G-180
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
^Approximate Unit Weight = 118 lb. (54 kg)
All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight
shown is largest cataloged Open Drip Proof motor.
Model
Number
HP
(Size)
Fan
RPM
H-G-170-C
1/4
860
H-G-170-B
H-G-180-C
H-G-180-B
1/2
1/3
3/4
1140
860
1140
CFM / Static Pressure in Inches WG
0
0.1
0.125
0.25
0.3
0.375
0.5
CFM
2572
2379
2330
2077
1961
1782
1416
0.228
0.625
0.75
1
BHP
0.172
0.187
0.191
0.208
0.214
0.223
Sones
9.7
9.6
9.5
9.2
9.1
9.1
9.1
CFM
3409
3263
3227
3043
2969
2857
2647
2428
2181
1457
BHP
0.4
0.421
0.426
0.45
0.46
0.473
0.494
0.514
0.532
0.488
Sones
16.3
16.2
16.2
16.1
16.1
16.1
16.1
16.1
16.1
17.2
CFM
3240
3053
3002
2733
2603
2390
1978
1438
0.316
BHP
0.24
0.262
0.268
0.296
0.306
0.321
0.332
Sones
12.1
12.4
12.4
12.5
12.5
12.3
11.9
11.9
CFM
4295
4156
4121
3933
3855
3731
3509
3241
2971
2246
BHP
0.559
0.589
0.596
0.634
0.649
0.671
0.707
0.74
0.771
0.759
Sones
19.5
19.4
19.4
19.3
19.5
19.7
19.8
20
20
21
­­­
Performance
certified is for installation type A: Free inlet, Free outlet. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values
in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical fan sone levels.
17
H-GB-071 - Belt Drive
®
243/8
(619)
H-
W.G.
his sy
stem
cur
ve
*233/4
(603)
sele
ct t
o th
e lef
12
(305)
19
(483)
5 (127)
t of t
43/8 (111)
on
ot
Damper Size = 12 x 12 (305 x 305)
Roof Opening = 141/2 x 141/2 (368 x 368)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 58 lb. (26 kg)
D
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-071-6
or
H-GB-071-4
HP
(Size)
Fan
RPM
1/6
or
1/4
630
738
846
954
1062
1170
1278
1386
1494
1602
1710
18
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
137
0.01
1.3
161
0.01
1.9
184
0.02
2.7
208
0.02
3.5
231
0.03
4.5
255
0.04
5.7
279
0.05
6.7
302
0.07
7.6
326
0.09
8.6
349
0.11
9.8
373
0.13
11.1
0.125
79
0.01
1.4
112
0.01
2.1
144
0.02
2.6
172
0.02
3.6
200
0.03
4.6
227
0.04
5.7
254
0.05
6.7
280
0.07
7.6
305
0.09
8.6
329
0.11
9.7
353
0.13
11.0
0.25
CFM / Static Pressure in Inches WG
0.375
0.5
0.625
0.75
0.875
1
1.125
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM =- (RPM/3371)
(RPM/3371)33
MAXIMUM
MAXIMUM RPM
RPM =- 1710
1710
TIP SPEED
TIP SPEED
(ft/min.)
- RPM
= RPM
x 2.929
x 2.929
MAXIMUM
MAXIMUM MOTOR
MOTOR FRAME
FRAME SIZE
SIZE =- 56
56
95
0.01
2.6
132
0.02
3.4
164
0.03
4.4
196
0.04
5.5
226
0.05
6.5
253
0.07
7.4
280
0.09
8.4
308
0.11
9.6
335
0.13
11.0
76
0.02
3.2
127
0.03
4.2
162
0.04
5.2
195
0.05
6.2
226
0.07
7.2
257
0.09
8.2
286
0.11
9.3
312
0.13
10.6
123
0.04
5.0
164
0.05
6.0
197
0.07
6.9
230
0.09
7.9
262
0.11
9.1
292
0.13
10.3
124
0.05
5.8
169
0.07
6.7
203
0.08
7.6
237
0.10
8.8
269
0.13
10.0
129
0.06
6.5
177
0.08
7.5
212
0.10
8.5
246
0.13
9.8
138
0.07
7.3
186
0.10
8.4
223
0.12
9.5
150
0.09
8.1
198
0.12
9.3
164
0.11
9.1
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-081 - Belt Drive
®
243/8
(619)
H-
tem
c
W.G.
urve
*233/4
(603)
e le
ft o
12
(305)
19
(483)
no
ts
ele
ct t
o th
5 (127)
f th i
s sys
43/8 (111)
Damper Size = 12 x 12 (305 x 305)
Roof Opening = 141/2 x 141/2 in. (368 x 368)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 58 lb. (26 kg)
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-081-6
or
H-GB-081-4
HP
(Size)
Fan
RPM
1/6
or
1/4
630
738
864
954
1062
1170
1278
1386
1494
1602
1710
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
316
0.01
2.4
370
0.01
3.1
433
0.02
4.0
478
0.03
4.8
532
0.04
5.9
586
0.05
6.9
640
0.07
7.9
694
0.09
9.1
748
0.11
10.1
802
0.14
11.3
856
0.17
12.5
0.125
207
0.01
2.1
283
0.02
2.8
361
0.02
3.8
413
0.03
4.6
474
0.04
5.7
533
0.06
6.7
592
0.07
7.8
650
0.09
8.9
708
0.12
10.0
765
0.14
11.1
821
0.17
12.3
0.25
CFM / Static Pressure in Inches WG
0.375
0.5
0.625
0.75
0.875
1
1.125
MAXIMUM BHP AT A GIVEN RPM = (RPM/2985)3
MAXIMUM RPM = 1710
TIP SPEED (ft/min.) = RPM x 2.929
MAXIMUM MOTOR FRAME SIZE = 56
265
0.02
3.5
341
0.03
4.2
411
0.05
5.3
478
0.06
6.4
543
0.08
7.4
605
0.10
8.6
666
0.12
9.8
725
0.15
10.9
785
0.18
12.1
329
0.04
5.0
419
0.06
6.0
490
0.08
7.0
557
0.10
8.2
623
0.12
9.4
686
0.15
10.5
748
0.18
11.9
317
0.06
5.7
428
0.08
6.7
507
0.10
7.9
577
0.12
8.9
644
0.15
10.1
710
0.19
11.5
320
0.07
6.6
441
0.10
7.6
528
0.13
8.7
602
0.15
9.9
669
0.19
11.2
334
0.09
7.6
457
0.12
8.5
552
0.16
9.6
630
0.19
10.9
357
0.11
8.4
480
0.15
9.5
581
0.19
10.6
388
0.14
9.3
511
0.18
10.5
424
0.17
10.3
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
19
H-GB-091 - Belt Drive
®
243/8
(619)
H-
W.G.
ystem
curve
*233/4
(603)
t to
the
le
ft of
12
(305)
19
(483)
5 (127)
this
s
43/8 (111)
no
ts
ele
c
Damper Size = 12 x 12 (305 x 305)
Roof Opening = 141/2 x 141/2 in. (368 x 368)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 58 lb. (26 kg)
o
D
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-091-4
HP
(Size)
Fan
RPM
1/4
630
738
864
954
1062
1170
1278
1386
1494
1602
1710
20
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
477
0.01
2.9
559
0.02
3.7
655
0.03
4.9
723
0.04
5.9
805
0.05
7.2
886
0.07
8.7
968
0.09
9.5
1050
0.12
10.3
1132
0.15
11.2
1214
0.18
12.3
1296
0.22
13.4
0.125
309
0.01
3.0
421
0.02
3.6
539
0.03
4.8
619
0.04
5.7
711
0.06
7.0
802
0.08
8.4
891
0.10
9.3
979
0.12
10.1
1066
0.15
11.1
1152
0.19
12.1
1238
0.23
13.3
0.25
CFM / Static Pressure in Inches WG
0.375
0.5
0.625
0.75
0.875
1
1.125
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM =- (RPM/3371)
(RPM/2703)33
MAXIMUM
MAXIMUM RPM
RPM =- 1710
1710
TIP SPEED
TIP SPEED
(ft/min.)
- RPM
= RPM
x 2.929
x 2.929
MAXIMUM
MAXIMUM MOTOR
MOTOR FRAME
FRAME SIZE
SIZE =- 56
56
405
0.03
4.5
506
0.04
5.3
613
0.06
6.6
715
0.08
8.0
813
0.10
8.9
907
0.13
9.9
999
0.16
10.9
1090
0.19
12.0
1180
0.23
13.2
313
0.04
5.1
502
0.06
6.2
621
0.08
7.5
729
0.10
8.5
832
0.13
9.5
932
0.16
10.6
1028
0.20
11.8
1122
0.24
13.0
500
0.08
7.1
639
0.11
8.1
752
0.13
9.1
860
0.17
10.2
962
0.20
11.4
1062
0.24
12.7
516
0.10
7.8
666
0.14
8.8
785
0.17
9.9
894
0.20
11.1
999
0.25
12.4
545
0.13
8.5
698
0.17
9.6
823
0.21
10.8
934
0.25
12.1
584
0.16
9.3
738
0.21
10.5
867
0.25
11.8
631
0.20
10.2
785
0.25
11.6
685
0.24
11.2
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-101 - Belt Drive
®
243/8
(619)
H-
ystem
W.G.
curve
*233/4
(603)
ct t
o th
e le
12
(305)
19
(483)
ts
ele
5 (127)
f t of
this
s
43/8 (111)
no
Damper Size = 12 x 12 (305 x 305)
Roof Opening = 141/2 x 141/2 (368 x 368)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 63 lb. (29 kg)
o
D
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-101-4
HP
(Size)
Fan
RPM
1/4
830
930
1030
1130
1230
1330
1430
1530
1635
H-GB-101-3
1/3
1718
1800
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
703
0.03
4.5
788
0.04
5.1
873
0.05
5.7
958
0.07
6.5
1042
0.09
7.3
1127
0.12
8.3
1212
0.14
9.1
1297
0.18
10.0
1386
0.22
11.1
1456
0.25
12.1
1526
0.29
13.2
0.125
594
0.03
3.5
688
0.04
4.3
781
0.06
5.1
873
0.08
5.9
965
0.10
6.8
1055
0.12
7.8
1144
0.15
8.8
1233
0.18
9.7
1326
0.22
10.8
1399
0.26
11.7
1471
0.30
12.8
0.25
420
0.03
2.6
572
0.05
3.7
688
0.06
4.7
795
0.08
5.6
894
0.11
6.5
987
0.13
7.6
1080
0.16
8.5
1173
0.19
9.5
1269
0.23
10.4
1345
0.27
11.3
1419
0.30
12.5
CFM / Static Pressure in Inches WG
0.375
0.5
0.625
0.75
0.875
1
1.25
MAXIMUM BHP AT A GIVEN RPM = (RPM/2593)3
MAXIMUM RPM = 1800
TIP SPEED (ft/min.) = RPM x 2.913
MAXIMUM MOTOR FRAME SIZE = 56
539
0.06
3.8
690
0.08
5
807
0.11
6.2
917
0.14
7.4
1021
0.17
8.2
1117
0.20
9.1
1215
0.24
10.2
1291
0.28
11.1
1368
0.31
12.3
420
0.07
3.6
693
0.11
5.5
827
0.14
6.9
943
0.17
7.8
1053
0.21
8.6
1162
0.25
9.8
1244
0.29
10.8
1321
0.33
12.2
696
0.13
6.4
851
0.17
7.3
975
0.21
8.2
1095
0.25
9.3
1185
0.29
10.2
1270
0.34
11.3
715
0.16
6.6
883
0.21
7.8
1020
0.25
8.9
1118
0.29
9.8
1209
0.34
10.8
744
0.19
7.1
929
0.25
8.4
1043
0.29
9.4
1142
0.34
10.6
793
0.24
7.8
943
0.29
8.9
1065
0.34
10.1
793
0.30
9.3
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
21
H-GB-101HP - Belt Drive
®
243/8
(619)
H-
t of t
his sy
stem
W.G.
curve
*233/4
(603)
43/8 (111)
lec
t
5 (127)
to t
he le
f
12
(305)
19
(483)
no
t se
Damper Size = 12 x 12 (305 x 305)
Roof Opening = 141/2 x 141/2 (368 x 368)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 63 lb. (29 kg)
o
D
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-101HP-4
HP
(Size)
Fan
RPM
1/4
1300
1445
1590
1735
1880
2025
H-GB-101HP-3
1/3
2137
2229
H-GB-101HP-5
1/2
2336
2443
2550
22
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
571
0.06
6.6
635
0.08
8.4
699
0.10
10.4
762
0.13
11.5
826
0.17
12.7
890
0.21
14.2
939
0.25
15.4
979
0.29
15.8
1026
0.33
16.4
1073
0.38
17.3
1120
0.43
18.2
0.25
477
0.06
5.7
553
0.09
7.5
626
0.11
9.5
697
0.15
10.8
767
0.18
12.2
836
0.23
13.6
889
0.26
14.8
931
0.30
15.4
981
0.34
16.0
1030
0.39
16.9
1078
0.44
17.9
0.5
342
0.07
5.3
449
0.09
7.0
537
0.12
9.1
619
0.15
10.7
697
0.20
11.9
772
0.24
13.3
830
0.28
14.4
875
0.31
14.8
928
0.36
15.4
981
0.41
16.4
1032
0.46
17.4
CFM / Static Pressure in Inches WG
0.75
1
1.25
1.5
243
0.08
6.3
417
0.12
8.3
527
0.16
10.3
618
0.20
12
702
0.24
13.2
765
0.28
14.2
814
0.32
14.5
871
0.37
14.9
927
0.42
16.0
982
0.48
17.2
1.75
2
2.25
MAXIMUM BHP AT A GIVEN RPM = (RPM/3165)3
MAXIMUM RPM = 2550
TIP SPEED (ft/min.) = RPM x 2.978
MAXIMUM MOTOR FRAME SIZE = 56
376
0.15
10.2
518
0.21
11.4
622
0.26
12.6
693
0.30
13.4
748
0.33
14.1
809
0.37
14.7
869
0.42
928
0.48
16.3
337
0.18
11.9
515
0.25
12
607
0.30
13.1
674
0.35
13.7
742
0.39
14.0
807
0.44
14.9
869
0.49
16.1
313
0.22
11.4
474
0.28
12.1
574
0.33
13.2
661
0.40
14.1
739
0.46
14.5
807
0.51
15.1
406
0.31
543
0.38
13.5
649
0.44
14.7
735
0.52
15.6
358
0.34
13.6
519
0.42
15.0
639
0.50
16.2
497
0.47
17.2
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-121 - Belt Drive
®
243/8
(619)
H-
is s
yst
em
cur
ve
W.G.
*233/4
(603)
43/8 (111)
to
to
th
e
lef
5 (127)
f th
12
(305)
19
(483)
ct
Damper Size = 12 x 12 (305 x 305)
Roof Opening = 141/2 x 141/2 (368 x 368)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 66 lb. (30 kg)
s
ot
e
n
Do
le
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-121-4
HP
(Size)
Fan
RPM
1/4
595
728
861
994
1127
1260
1395
H-GB-121-3
1/3
1473
1550
H-GB-121-5
1/2
1638
1725
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
722
0.02
3.3
883
0.03
4.2
1044
0.05
5.4
1206
0.08
6.7
1367
0.11
8.2
1528
0.16
10.1
1692
0.21
12.5
1787
0.25
13.5
1880
0.30
14.6
1987
0.35
16.0
2093
0.40
17.4
0.125
542
0.02
3.4
747
0.04
4.3
933
0.06
5.5
1111
0.09
6.7
1284
0.12
8.2
1454
0.17
10.1
1625
0.23
12.4
1723
0.27
13.4
1820
0.31
14.5
1930
0.36
15.8
2038
0.42
17.2
0.25
543
0.04
4.2
798
0.06
5.2
1004
0.09
6.6
1195
0.13
8.2
1377
0.18
10.0
1557
0.24
12.3
1659
0.28
13.3
1759
0.32
14.3
1872
0.38
15.6
1984
0.44
17.0
CFM / Static Pressure in Inches WG
0.375
0.5
0.625
0.75
1
1.25
1.5
MAXIMUM BHP AT A GIVEN RPM = (RPM/2170)3
MAXIMUM RPM = 1725
TIP SPEED (ft/min.) = RPM x 3.420
MAXIMUM MOTOR FRAME SIZE = 56
584
0.06
5.2
872
0.10
6.4
1092
0.14
7.9
1292
0.19
9.9
1484
0.25
12.2
1591
0.29
13.1
1696
0.33
14.2
1814
0.39
15.5
1928
0.45
16.8
673
0.09
6.3
969
0.14
7.8
1196
0.19
9.6
1404
0.26
12.0
1518
0.30
12.9
1629
0.34
14.0
1751
0.40
15.3
1871
0.46
16.7
799
0.13
7.7
1084
0.19
9.5
1315
0.26
11.7
1438
0.31
12.7
1555
0.35
13.8
1684
0.41
15.1
1810
0.47
16.4
938
0.19
9.3
1214
0.26
11.5
1352
0.31
12.4
1475
0.36
13.5
1613
0.42
14.9
1743
0.48
16.2
907
0.25
11.3
1127
0.30
12.0
1289
0.36
12.9
1452
0.43
14.0
1600
0.50
15.5
974
0.33
12.4
1238
0.42
13.5
1426
0.50
14.9
1180
0.48
14.0
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
23
H-GB-131 - Belt Drive
®
283/8
(721)
H-
W.G.
*233/4
(603)
12
(305)
ef t
of
19
(483)
th
el
5 (127)
th i
ss
yst
em
cur
ve
4 (102)
tt
o
Damper Size = 12 x 12 (305 x 305)
Roof Opening = 141/2 x 141/2 in. (368 x 368)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 67 lb. (30 kg)
s
ot
Do n
c
ele
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-131-4
HP
(Size)
Fan
RPM
1/4
595
700
800
900
1000
1100
1200
1315
H-GB-131-3
1/3
1440
H-GB-131-5
1/2
1563
1685
24
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
844
0.02
4.5
993
0.03
5.2
1135
0.05
6.0
1277
0.07
7.0
1419
0.10
8.1
1516
0.13
9.5
1703
0.17
11.1
1866
0.22
13.2
2044
0.294
15.0
2218
0.375
16.0
2391
0.47
16.9
0.125
655
0.02
4.6
845
0.04
5.2
1012
0.06
6.0
1169
0.08
6.9
1223
0.11
8.0
1475
0.14
9.2
1624
0.18
10.8
1794
0.23
12.8
1978
0.306
15.0
2158
0.389
15.8
2335
0.485
16.6
0.25
585
0.04
5.0
843
0.06
5.7
1039
0.08
6.6
1213
0.11
7.7
1381
0.15
9.0
1539
0.19
10.5
1718
0.24
12.5
1911
0.318
15.1
2097
0.402
15.6
2279
0.499
16.3
CFM / Static Pressure in Inches WG
0.375
0.5
0.625
0.75
1
1.25
1.5
MAXIMUM BHP AT A GIVEN RPM = (RPM/2047)3
MAXIMUM RPM = 1685
TIP SPEED (ft/min.) = RPM x 3.436
MAXIMUM MOTOR FRAME SIZE = 56
845
0.08
6.3
1075
0.12
7.4
1268
0.15
8.6
1443
0.20
10.1
1637
0.25
12.1
1838
0.327
15.1
2031
0.413
15.5
2219
0.512
16.0
867
0.11
7.0
1124
0.16
8.3
1330
0.20
9.7
1545
0.26
11.7
1759
0.336
14.5
1964
0.424
15.2
2158
0.523
15.7
898
0.15
7.9
1191
0.20
9.4
1435
0.26
11.2
1674
0.344
13.9
1887
0.432
14.8
2093
0.534
15.4
964
0.19
8.8
1305
0.26
10.9
1571
0.347
13.4
1807
0.44
14.3
2020
0.543
15.1
1299
0.342
12.5
1606
0.445
13.6
1857
0.555
14.5
1300
0.427
12.8
1654
0.557
13.9
1312
0.522
13.5
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-141 - Belt Drive
®
283/8
(721)
H-
curv
e
W.G.
*233/4
(603)
to
t
he
left
o
f th
12
(305)
22
(559)
5 (127)
is s y
stem
4 (102)
se
le
ct
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 83 lb. (38 kg)
t
no
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-141-4
HP
(Size)
Fan
RPM
1/4
525
663
801
939
1075
H-GB-141-3
1/3
1170
H-GB-141-5
1/2
1265
1360
H-GB-141-7
3/4
1453
1545
H-GB-141-10
1
1705
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
974
0.03
4.4
1230
0.06
5.3
1486
0.10
6.5
1742
0.16
7.9
1994
0.24
10.0
2170
0.31
11.4
2347
0.39
12.9
2523
0.48
14.6
2695
0.59
16.2
2866
0.71
17.6
3163
0.95
20
0.125
709
0.03
4.2
1046
0.06
5.5
1337
0.11
6.6
1614
0.17
7.8
1882
0.25
9.9
2067
0.32
11.3
2250
0.40
12.7
2433
0.50
14.3
2612
0.60
15.9
2787
0.72
18.0
3091
0.97
20
0.25
732
0.06
4.4
1161
0.11
6.1
1482
0.17
7.5
1771
0.26
9.4
1966
0.33
10.8
2158
0.41
12.3
2347
0.51
13.9
2530
0.62
15.6
2710
0.74
17.4
3020
0.98
20
CFM / Static Pressure in Inches WG
0.375
0.5
0.75
1
1.25
1.5
1.75
MAXIMUM BHP AT A GIVEN RPM = (RPM/1676)3
MAXIMUM RPM = 1705
TIP SPEED (ft/min.) = RPM x 3.829
MAXIMUM MOTOR FRAME SIZE = 145T
850
0.10
5.3
1313
0.18
7.0
1647
0.26
8.9
1859
0.33
10.3
2062
0.42
11.9
2259
0.52
13.5
2449
0.63
15.3
2634
0.75
17.1
2952
1.00
19.6
1040
0.16
6.4
1490
0.26
8.4
1734
0.34
9.9
1955
0.42
11.4
2166
0.52
13.1
2365
0.64
14.8
2556
0.76
16.8
2883
1.02
19.2
1356
0.32
8.7
1677
0.42
10.4
1943
0.53
12.2
2173
0.64
13.9
2384
0.77
14.9
2739
1.03
18.1
1048
0.35
8.8
1602
0.51
11.0
1914
0.64
13.0
2177
0.78
14.7
2574
1.03
16.9
1513
0.60
11.8
1890
0.75
14.7
2370
1.05
16.7
2120
1.02
16.6
1731
0.96
16.4
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
25
H-GB-141HP - Belt Drive
®
283/8
(721)
H-
this
syste
m
W.G.
curve
*233/4
(603)
4 (102)
e le
ft of
sel
ect
to t
h
5 (127)
12
(305)
22
(559)
no
t
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 83 lb. (38 kg)
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-141HP-4
HP
(Size)
Fan
RPM
1/4
905
1054
1203
1352
1500
H-GB-141HP-3
1/3
1655
H-GB-141HP-5
1/2
1737
1818
1900
H-GB-141HP-7
3/4
2035
2170
26
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.5
270
0.05
5.5
537
0.09
6.7
714
0.13
8.4
870
0.18
10.9
1009
0.24
13.1
1151
0.32
15.0
1224
0.37
16.4
1295
0.42
17.9
1366
0.47
19.0
1483
0.57
21
1598
0.68
22
0.75
1
CFM / Static Pressure in Inches WG
1.25
1.5
1.75
2
2.25
2.5
2.75
MAXIMUM BHP AT A GIVEN RPM = (RPM/2351)3
MAXIMUM RPM = 2170
TIP SPEED (ft/min.) = RPM x 3.829
MAXIMUM MOTOR FRAME SIZE = 145T
527
0.13
8.3
740
0.19
10.3
903
0.26
12.3
1064
0.34
14.1
1143
0.38
15.6
1218
0.44
17.3
1294
0.49
18.4
1417
0.60
20
1536
0.71
22
547
0.19
10.4
774
0.26
12.2
959
0.35
13.3
1048
0.40
14.9
1133
0.45
16.8
1218
0.51
18.0
1347
0.62
19.6
1472
0.73
21
592
0.25
12.4
833
0.35
13.1
946
0.40
14.4
1037
0.46
15.9
1127
0.53
17.4
1269
0.63
19.1
1407
0.76
21
668
0.34
13.6
802
0.40
14.4
920
0.46
15.7
1033
0.53
16.8
1184
0.65
18.6
1328
0.77
21
619
0.38
15.0
773
0.45
16.0
901
0.52
16.7
1095
0.65
18.4
1248
0.78
21
561
0.42
16.7
753
0.51
17.0
969
0.64
18.1
1163
0.79
21
832
0.63
18.2
1045
0.78
20
633
0.59
18.5
919
0.77
19.7
757
0.74
19.8
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-161 - Belt Drive
®
283/8
(721)
H-
th i
s sy
ste
mc
ur v
e
W.G.
*233/4
(603)
4 (102)
th
e
lef
t
5 (127)
of
12
(305)
22
(559)
tt
o
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 89 lb. (40 kg)
le c
se
ot
n
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-161-4
HP
(Size)
Fan
RPM
1/4
478
575
670
765
865
H-GB-161-3
1/3
945
H-GB-161-5
1/2
1023
1100
H-GB-161-7
3/4
1175
1250
H-GB-161-10
1
1375
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
1412
0.40
4.7
1698
0.07
5.7
1979
0.11
7.0
2260
0.16
8.6
2555
0.24
10.6
2791
0.31
12.6
3022
0.39
14.0
3249
0.49
15.3
3471
0.59
16.5
3692
0.71
17.9
4062
0.95
21
0.125
1030
0.04
4.5
1399
0.08
5.6
1727
0.12
6.7
2040
0.17
8.2
2360
0.25
10.1
2612
0.32
12.0
2856
0.41
13.4
3095
0.50
14.7
3326
0.61
16.0
3557
0.73
17.4
3938
0.97
20
0.25
937
0.07
5.3
1429
0.12
6.5
1802
0.18
8.0
2162
0.26
9.7
2434
0.33
11.5
2693
0.42
12.8
2943
0.52
14.1
3184
0.62
15.5
3422
0.75
17.0
3815
0.99
19.6
CFM / Static Pressure in Inches WG
0.375
0.5
0.75
0.875
1
1.25
1.5
MAXIMUM BHP AT A GIVEN RPM = (RPM/1355)3
MAXIMUM RPM = 1375
TIP SPEED (ft/min.) = RPM x 4.352
MAXIMUM MOTOR FRAME SIZE = 145T
1494
0.18
7.5
1933
0.26
9.4
2236
0.34
11.2
2520
0.43
12.5
2787
0.53
13.8
3040
0.64
15.1
3289
0.76
16.6
3694
1.01
19.2
1624
0.25
8.8
2010
0.34
10.7
2327
0.43
12.1
2615
0.53
13.5
2888
0.65
14.8
3149
0.77
16.3
3571
1.02
18.9
1785
0.40
11.0
2198
0.52
12.5
2541
0.65
14.0
2838
0.79
15.6
3304
1.04
18.4
1900
0.50
12.0
2313
0.64
13.6
2658
0.78
15.2
3161
1.05
18.0
2025
0.61
13.0
2444
0.76
14.9
3007
1.04
17.6
2609
1.01
17.2
2073
0.93
15.4
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
27
H-GB-161HP - Belt Drive
®
283/8
(721)
H-
syste
m
W.G.
curve
*233/4
(603)
ct t
o th
e lef
12
(305)
22
(559)
sel
e
5 (127)
t of
this
4 (102)
o
no
t
Damper Size = 16 x 16 (406 x 406)
Roof Opening = 181/2 x 181/2 (470 x 470)
Shroud Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 89 lb. (40 kg)
D
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-161HP-4
HP
(Size)
Fan
RPM
1/4
825
960
1095
H-GB-161HP-3
1/3
1210
H-GB-161HP-5
1/2
1270
1330
1390
H-GB-161HP-7
3/4
1485
1580
H-GB-161HP-10
1
1660
1740
28
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.5
702
0.11
6.5
1093
0.18
7.7
1380
0.26
9.0
1606
0.34
10.6
1718
0.39
11.4
1829
0.44
12.3
1938
0.50
13.3
2109
0.60
14.9
2275
0.72
16.7
2414
0.82
18.3
2551
0.94
20
0.625
919
0.17
7.6
1271
0.26
9.0
1514
0.35
10.3
1636
0.40
11.2
1753
0.45
12.1
1865
0.51
13.0
2041
0.61
14.7
2214
0.73
16.7
2357
0.84
18.8
2497
0.96
21
0.75
585
0.15
8.0
1139
0.26
8.9
1416
0.35
10.4
1545
0.40
11.1
1668
0.46
11.9
1789
0.52
12.8
1973
0.63
14.4
2150
0.75
16.4
2297
0.85
18.3
2442
0.97
21
CFM / Static Pressure in Inches WG
1
1.25
1.5
1.75
2
2.25
2.5
MAXIMUM BHP AT A GIVEN RPM = (RPM/1708)3
MAXIMUM RPM = 1740
TIP SPEED (ft/min.) = RPM x 4.352
MAXIMUM MOTOR FRAME SIZE = 145T
589
0.21
9.5
1149
0.34
10.3
1333
0.41
11.1
1483
0.47
12.1
1619
0.53
12.7
1822
0.64
13.8
2016
0.77
15.5
2175
0.89
16.7
2325
1.01
18.4
949
0.37
11.4
1204
0.45
12.0
1399
0.53
12.7
1654
0.65
13.7
1868
0.77
14.7
2037
0.89
16.2
2200
1.03
17.5
1032
0.48
13.1
1416
0.63
14.0
1704
0.791
14.8
1887
0.91
15.8
2066
1.03
17.2
1012
0.57
14.7
1447
0.75
15.4
1702
0.90
15.8
1917
1.05
16.8
1034
0.67
16.6
1441
0.86
17.1
1714
1.03
17.2
996
0.75
20
1452
0.98
19.2
987
0.85
28
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-180 - Belt Drive
®
351/2
(902)
H-
cur
ve
W.G.
*28
(711)
he
lef
to
f th
is s
12
(305)
30
(762)
to
t
5 (127)
yste
m
51/2 (140)
el
ec
t
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 125 lb. (57 kg)
n
Do
ot
s
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-180-4
HP
(Size)
Fan
RPM
1/4
495
730
H-GB-180-3
1/3
810
H-GB-180-5
1/2
875
940
H-GB-180-7
3/4
1055
H-GB-180-10
1
1120
1185
H-GB-180-15
11/2
1260
1335
H-GB-180-20
2
1460
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
1925
0.07
4.3
2839
0.21
7.4
3150
0.29
8.8
3402
0.37
10.5
3655
0.46
12.7
4102
0.65
16.2
4355
0.77
17.5
4608
0.91
19.0
4899
1.10
21
5191
1.31
22
5677
1.71
26
0.125
1646
0.08
4.7
2668
0.23
8.7
2997
0.31
9.9
3263
0.38
11.1
3527
0.47
12.8
3990
0.67
15.7
4249
0.79
16.9
4508
0.94
18.4
4805
1.12
19.9
5102
1.33
22
5596
1.74
25
0.25
1150
0.08
4.1
2469
0.27
7.2
2832
0.33
8.7
3113
0.41
10.2
3388
0.49
12.0
3867
0.68
14.9
4134
0.81
16.4
4401
0.96
17.8
4706
1.15
19.3
5010
1.36
21
5514
1.77
24
CFM / Static Pressure in Inches WG
0.5
0.75
1
1.25
1882
0.25
6.7
2375
0.35
8.2
2728
0.44
9.4
3052
0.54
11.1
3596
0.74
14.0
3891
0.88
15.5
4179
1.03
17.1
4498
1.21
18.8
4814
1.41
21
5336
1.81
24
1.5
1.75
2
MAXIMUM BHP AT A GIVEN RPM = (RPM/1149)3
MAXIMUM RPM = 1460
TIP SPEED (ft/min.) = RPM x 4.843
MAXIMUM MOTOR FRAME SIZE = 184T
2144
0.43
8.5
2601
0.54
10.3
3252
0.77
12.9
3587
0.92
14.5
3900
1.07
16.2
4256
1.27
18.0
4599
1.49
19.9
5155
1.93
23
2811
0.77
12.4
3217
0.93
13.8
3575
1.10
15.4
3977
1.32
17.3
4344
1.54
19.2
4938
1.97
23
2686
0.89
13.0
3178
1.09
14.7
3641
1.32
16.8
4052
1.57
18.7
4699
2.03
22
2499
0.99
13.7
3223
1.29
16.1
3713
1.56
18.2
4426
2.05
22
3262
1.51
17.6
4123
2.05
22
3765
2.02
21
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
29
H-GB-180HP - Belt Drive
®
351/2
(902)
H-
urv
e
W.G.
*28
(711)
f th
is s
lef
to
12
(305)
30
(762)
to
the
5 (127)
yste
mc
51/2 (140)
ele
ct
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 125 lb. (57 kg)
Do
ts
no
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-180HP-4
HP
(Size)
Fan
RPM
1/4
795
845
H-GB-180HP-3
1/3
935
H-GB-180HP-5
1/2
1075
H-GB-180HP-7
3/4
1150
1225
H-GB-180HP-10
1
1350
H-GB-180HP-15
11/2
1445
1540
H-GB-180HP-20
2
1620
1700
30
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.5
1547
0.22
8.6
1759
0.26
9.1
2114
0.35
10.3
2601
0.51
12.9
2847
0.61
14.6
3088
0.73
16.3
3485
0.96
19.5
3782
1.16
22
4076
1.39
25
4319
1.60
27
4560
1.84
30
0.75
1
CFM / Static Pressure in Inches WG
1.25
1.5
1.75
2
2.25
2.5
2.75
MAXIMUM BHP AT A GIVEN RPM = (RPM/1325)3
MAXIMUM RPM = 1700
TIP SPEED (ft/min.) = RPM x 4.843
MAXIMUM MOTOR FRAME SIZE = 184T
1686
0.35
9.6
2316
0.53
12.1
2607
0.64
13.1
2880
0.77
14.7
3296
1.00
17.6
3604
1.21
20
3909
1.44
22
4163
1.66
25
4414
1.90
27
1920
0.52
11.6
2298
0.65
12.6
2610
0.78
13.9
3095
1.04
16.4
3428
1.25
18.8
3744
1.49
21
4005
1.71
24
4263
1.96
26
1811
0.62
12.3
2277
0.78
13.3
2840
1.05
15.8
3213
1.28
17.8
3576
1.53
20
3848
1.76
23
4114
2.01
25
1711
0.72
13.2
2540
1.05
15.0
2969
1.29
17.3
3353
1.55
19.6
3663
1.79
22
3964
2.06
24
2059
0.99
15.1
2670
1.28
16.4
3119
1.56
18.9
3450
1.81
21
3764
2.08
23
2216
1.21
16.6
2827
1.55
18.1
3223
1.82
20
3560
2.10
22
2407
1.48
18.3
2923
1.80
19.7
3340
2.11
22
2512
1.72
19.8
3037
2.07
21
2642
1.99
21
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-200 - Belt Drive
®
351/2
(902)
H-
curv
e
W.G.
*28
(711)
the
left
of t
h
12
(305)
30
(762)
t to
5 (127)
is sy
stem
51/2 (140)
ts
ele
c
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 138 lb. (63 kg)
Do
no
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-200-4
HP
(Size)
Fan
RPM
1/4
440
600
H-GB-200-3
1/3
665
H-GB-200-5
1/2
718
770
H-GB-200-7
3/4
860
H-GB-200-10
1
965
H-GB-200-15
11/2
1028
1090
H-GB-200-20
2
1145
1200
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
2435
0.10
6.5
3320
0.25
8.5
3680
0.34
9.6
3973
0.43
10.8
4261
0.53
12.1
4759
0.73
14.1
5340
1.03
16.7
5689
1.25
18.5
6032
1.49
20
6336
1.73
22
6640
1.99
24
0.125
1976
0.10
5.8
2984
0.26
7.9
3378
0.34
9.0
3700
0.43
10.0
4013
0.53
11.0
4548
0.74
13.3
5158
1.04
16.0
5517
1.26
17.8
5870
1.50
19.6
6182
1.74
21
6494
2.00
23
0.25
2637
0.26
7.3
3085
0.36
8.5
3422
0.45
9.6
3744
0.55
10.7
4289
0.75
12.9
4927
1.05
15.4
5309
1.27
17.2
5682
1.51
18.9
6010
1.75
21
6336
2.01
23
CFM / Static Pressure in Inches WG
0.375
0.5
0.75
1
2089
0.25
6.1
2706
0.35
7.7
3109
0.45
9.0
3477
0.55
10.2
4068
0.77
12.4
4720
1.08
15.0
5101
1.29
16.8
5473
1.52
18.4
5809
1.76
20
6145
2.02
22
1.25
1.5
1.75
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM == (RPM/3371)
(RPM/938)33
MAXIMUM RPM = 1200
1710
TIP SPEED
TIP SPEED
(ft/min.)
= RPM
= RPM
x 2.929
x 5.596
MAXIMUM
MAXIMUMMOTOR
MOTORFRAME
FRAMESIZE
SIZE==184T
56
2087
0.33
6.7
2684
0.44
8.3
3141
0.55
9.8
3811
0.77
11.8
4520
1.09
14.5
4918
1.31
16.4
5301
1.56
18.1
5637
1.79
19.8
5969
2.04
22
3085
0.74
11.1
4015
1.08
13.7
4488
1.32
15.6
4925
1.56
17.5
5299
1.81
19.2
5651
2.09
21
3240
1.02
13.0
3911
1.29
14.7
4450
1.56
16.8
4870
1.82
18.7
5274
2.09
21
2941
1.14
14.6
3751
1.48
15.8
4333
1.77
17.7
4829
2.08
19.9
3517
1.64
16.6
4177
1.96
18.6
3077
1.69
16.7
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
31
H-GB-200HP - Belt Drive
®
351/2
(902)
H-
this
syste
m
W.G.
curve
*28
(711)
51/2 (140)
ft of
e le
ct t
o th
5 (127)
12
(305)
30
(762)
no
ts
ele
Damper Size = 18 x 18 (457 x 457)
Roof Opening = 201/2 x 201/2 (521 x 521)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 138 lb. (63 kg)
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-200HP-5
HP
(Size)
Fan
RPM
1/2
740
895
H-GB-200HP-7
3/4
958
1020
H-GB-200HP-10
1
1125
H-GB-200HP-15
11/2
1205
1285
H-GB-200HP-20
2
1350
1415
H-GB-200HP-30
3
1520
1625
32
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.5
1961
0.30
8.7
2809
0.52
11.4
3116
0.63
12.8
3409
0.75
14.1
3885
0.99
16.9
4229
1.19
18.8
4569
1.43
21
4843
1.65
23
5114
1.88
24
5550
2.31
27
5982
2.80
32
0.75
2331
0.53
10.9
2715
0.65
12.1
3050
0.77
13.6
3584
1.02
16.4
3967
1.24
17.9
4343
1.49
20
4638
1.71
22
4919
1.95
24
5368
2.38
27
5812
2.88
31
1
1424
0.45
10.3
2153
0.63
11.6
2602
0.78
13.1
3243
1.04
15.5
3663
1.27
17.2
4070
1.52
19.1
4384
1.75
21
4692
2.00
23
5182
2.45
27
5642
2.95
31
CFM / Static Pressure in Inches WG
1.25
1.5
2
2.5
2.75
3
3.25
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM =- (RPM/3371)
(RPM/1106)33
MAXIMUM
MAXIMUM RPM
RPM =- 1710
1625
TIP SPEED
TIP SPEED
(ft/min.)
- RPM
= RPM
x 2.929
x 5.596
MAXIMUM
MAXIMUMMOTOR
MOTORFRAME
FRAMESIZE
SIZE=-184T
56
1857
0.71
12.6
2804
1.04
15.3
3314
1.29
16.5
3770
1.55
18.1
4109
1.78
19.8
4442
2.04
22
4952
2.50
26
5448
3.02
29
2136
0.97
15.2
2884
1.27
16.4
3416
1.57
17.8
3811
1.81
19.3
4169
2.07
21
4713
2.53
24
5233
3.06
28
2278
1.40
18.9
2996
1.76
19.1
3492
2.07
19.7
4166
2.58
23
4767
3.13
27
2250
1.78
23
3458
2.53
22
4196
3.16
25
2850
2.38
22
3859
3.12
24
2046
2.06
22
3377
3.01
23
2725
2.76
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-220 - Belt Drive
®
423/4
(1086)
H-
ur v
e
W.G.
*311/2
(800)
tt
ot
he
l
ef t
of
thi
s
12
(305)
34
(864)
5 (127)
sys
tem
c
53/4 (146)
le c
Damper Size = 24 x 24 (610 x 610)
Roof Opening = 261/2 x 261/2 (673 x 673)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 158 lb. (72 kg)
n
Do
se
ot
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-220-4
HP
(Size)
Fan
RPM
1/4
425
465
500
H-GB-220-3
1/3
550
H-GB-220-5
1/2
640
H-GB-220-7
3/4
710
H-GB-220-10
1
755
800
H-GB-220-15
­11/2
848
895
H-GB-220-20
2
985
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
3230
0.14
7.4
3533
0.18
8.1
3799
0.23
8.8
4179
0.30
10.0
4863
0.48
13.0
5395
0.65
15.0
5737
0.79
15.7
6079
0.93
16.6
6444
1.11
17.8
6801
1.31
19.4
7485
1.74
23
0.125
2879
0.16
7.2
3219
0.20
7.8
3512
0.25
8.4
3924
0.32
9.6
4654
0.50
12.8
5206
0.68
14.9
5559
0.82
15.6
5911
0.97
16.4
6286
1.15
17.5
6651
1.34
19.1
7349
1.78
23
0.25
2296
0.16
6.9
2758
0.21
7.4
3132
0.26
7.9
3629
0.34
8.9
4403
0.53
12.1
4990
0.71
14.4
5362
0.84
15.2
5732
1.00
16.1
6122
1.18
17.2
6501
1.38
18.8
7212
1.82
23
CFM / Static Pressure in Inches WG
0.375
0.5
0.625
0.75
1951
0.19
7.0
2542
0.26
7.5
3158
0.35
8.4
4120
0.54
11.2
4762
0.73
13.6
5148
0.87
14.6
5530
1.02
15.6
5932
1.21
16.9
6323
1.41
18.5
7062
1.86
22
1
1.25
1.5
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM == (RPM/3371)
(RPM/782)33
MAXIMUM
MAXIMUM RPM
RPM == 1710
985
TIP SPEED
TIP SPEED
(ft/min.)
= RPM
= RPM
x 2.929
x 6.283
MAXIMUM
MAXIMUMMOTOR
MOTORFRAME
FRAMESIZE
SIZE==184T
56
2526
0.33
8.0
3702
0.55
10.5
4459
0.74
12.8
4920
0.89
14.0
5326
1.05
15.2
5741
1.23
16.5
6142
1.44
18.2
6898
1.89
22
3208
0.54
9.7
4077
0.75
12.1
4579
0.90
13.4
5049
1.06
14.6
5540
1.26
16.2
5960
1.47
18.0
6734
1.92
22
3633
0.74
11.2
4206
0.90
12.7
4716
1.07
14.2
5236
1.27
15.7
5723
1.49
17.6
6568
1.95
22
3095
0.82
11.2
3929
1.05
12.5
4566
1.27
14.5
5122
1.50
16.9
6107
1.99
21
3542
1.17
13.4
4401
1.47
15.5
5548
2.00
20
4883
1.96
19.0
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
33
H-GB-220HP - Belt Drive
®
423/4
(1086)
H-
to
the
left
o
f th
12
(305)
34
(864)
5 (127)
is sy
stem
53/4 (146)
curv
e
W.G.
*311/2
(800)
ot
se
lec
t
Damper Size = 24 x 24 (610 x 610)
Roof Opening = 261/2 x 261/2 (673 x 673)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 158 lb. (72 kg)
n
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-220HP-5
HP
(Size)
Fan
RPM
1/2
650
680
H-GB-220HP-7
3/4
728
775
H-GB-220HP-10
1
850
H-GB-220HP-15
11/2
913
975
H-GB-220HP-20
2
1025
1075
H-GB-220HP-30
3
1127
1230
34
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.5
2952
0.47
8.9
3215
0.53
9.4
3614
0.65
10.6
3973
0.77
12.0
4532
1.00
15.0
4975
1.22
16.7
5400
1.46
18.7
5740
1.68
21
6076
1.93
23
6422
2.20
24
7100
2.82
28
0.625
2555
0.46
8.5
2871
0.53
9.2
3312
0.65
10.3
3719
0.79
11.5
4317
1.02
13.8
4791
1.25
16.0
5245
1.50
18.2
5591
1.72
20
5935
1.97
22
6289
2.24
24
6981
2.87
27
0.75
1892
0.42
8.3
2440
0.52
8.9
2974
0.65
9.9
3424
0.79
11.1
4083
1.04
13.5
4590
1.27
15.3
5060
1.53
17.5
5432
1.76
19.4
5794
2.01
21
6154
2.29
23
6858
2.92
27
CFM / Static Pressure in Inches WG
1
1.25
1.5
1.75
2
2.25
2.5
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM -=(RPM/3371)
(RPM/838)33
MAXIMUM
MAXIMUM RPM
RPM =- 1710
1230
TIP SPEED
TIP SPEED
(ft/min.)
- RPM
= RPM
x 2.929
x 6.414
MAXIMUM
MAXIMUMMOTOR
MOTORFRAME
FRAMESIZE
SIZE=-184T
56
2643
0.75
10.5
3536
1.03
12.7
4119
1.29
14.4
4660
1.57
16.3
5075
1.81
18.2
5459
2.06
20
5852
2.36
22
6611
3.01
27
2648
0.95
12.0
3545
1.27
13.5
4185
1.56
15.4
4643
1.82
17.1
5082
2.10
18.7
5520
2.41
21
6316
3.08
25
2557
1.13
13.0
3602
1.53
14.8
4157
1.804
16.4
4649
2.10
18.3
5124
2.42
20
6009
3.14
25
3492
1.74
15.6
4136
2.07
17.7
4703
2.41
19.3
5649
3.15
23
3346
1.93
16.4
4173
2.37
18.6
5263
3.14
22
3299
2.17
17.7
4812
3.10
22
4265
3.02
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-240 - Belt Drive
®
423/4
(1086)
H-
W.G.
f thi
s sys
53/4 (146)
t to
the
l
ef t o
12
(305)
34
(864)
5 (127)
tem
curv
e
*311/2
(800)
no
ts
ele
c
Damper Size = 24 x 24 (610 x 610)
Roof Opening = 261/2 x 261/2 (673 x 673)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 158 lb. (72 kg)
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-240-4
HP
(Size)
Fan
RPM
1/4
425
460
H-GB-240-3
1/3
505
H-GB-240-5
1/2
585
H-GB-240-7
3/4
623
660
H-GB-240-10
1
730
H-GB-240-15
11/2
778
825
H-GB-240-20
2
870
910
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
3902
0.19
5.9
4223
0.24
6.7
4637
0.32
7.8
5371
0.50
10.3
5720
0.60
11.7
6060
0.71
13.1
6702
0.96
15.8
7143
1.16
17.7
7575
1.39
19.7
7988
1.63
22
8355
1.86
24
0.125
3422
0.21
5.9
3785
0.26
6.6
4242
0.35
7.5
5031
0.53
9.7
5400
0.64
11.0
5757
0.75
12.4
6428
1.01
15.0
6886
1.21
16.6
7332
1.44
18.6
7757
1.68
21
8135
1.92
23
0.25
2691
0.20
4.7
3188
0.27
5.7
3761
0.35
6.9
4666
0.54
9.1
5069
0.65
10.4
5449
0.78
11.8
6158
1.05
14.3
6632
1.26
15.9
7092
1.49
17.7
7529
1.73
19.6
7916
1.97
21
CFM / Static Pressure in Inches WG
0.375
0.5
0.625
0.75
2036
0.22
4.2
3060
0.34
6.1
4195
0.55
8.8
4660
0.66
10.0
5094
0.79
11.3
5861
1.05
13.8
6363
1.27
15.4
6844
1.51
17.2
7300
1.77
19.1
7700
2.02
21
1
1.25
1.5
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM == (RPM/3371)
(RPM/715)33
MAXIMUM
MAXIMUM RPM
RPM == 1710
910
TIP SPEED
TIP SPEED
(ft/min.)
= RPM
= RPM
x 2.929
x 6.414
MAXIMUM
MAXIMUMMOTOR
MOTORFRAME
FRAMESIZE
SIZE==184T
56
3562
0.53
8.2
4131
0.65
9.6
4636
0.78
11.0
5507
1.06
13.4
6058
1.28
15.0
6574
1.52
16.8
7055
1.78
18.7
7467
2.03
21
2112
0.41
7.2
3428
0.61
9.1
4073
0.76
10.6
5077
1.06
13.1
5700
1.29
14.7
6261
1.54
16.4
6775
1.80
18.3
7215
2.05
20
3217
0.69
10.4
4568
1.03
12.9
5266
1.28
14.4
5901
1.53
16.2
6457
1.80
17.9
6933
2.06
19.6
4145
1.18
13.2
5002
1.48
14.8
5680
1.77
16.9
6240
2.05
19.2
7757
1.68
21
5388
1.97
16.7
3707
1.66
13.6
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
35
H-GB-240HP - Belt Drive
®
423/4
(1086)
H-
to
the
le
ft o
12
(305)
34
(864)
5 (127)
f th
is s
yste
m
53/4 (146)
curv
e
W.G.
*311/2
(800)
ele
ct
Damper Size = 24 x 24 (610 x 610)
Roof Opening = 261/2 x 261/2 (673 x 673)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 158 lb. (72 kg)
ts
no
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-240HP-5
HP
(Size)
Fan
RPM
1/2
635
685
H-GB-240HP-7
3/4
733
780
H-GB-240HP-10
1
860
H-GB-240HP-15
11/2
920
980
H-GB-240HP-20
2
1030
1080
H-GB-240HP-30
3
1133
1240
36
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.5
3035
0.42
8.0
3475
0.53
9.4
3877
0.64
11.0
4247
0.76
12.7
4860
0.99
15.9
5310
1.20
18.5
5751
1.43
22
6114
1.65
24
6474
1.89
27
6853
2.16
29
7610
2.80
31
0.625
2586
0.41
7.6
3147
0.53
8.8
3603
0.65
10.3
4005
0.77
11.9
4654
1.02
15.2
5118
1.23
17.4
5574
1.47
19.9
5948
1.69
23
6315
1.92
26
6702
2.20
27
7471
2.84
30
0.75
2693
0.51
8.4
3272
0.65
9.7
3740
0.78
11.3
4434
1.04
14.3
4925
1.25
16.6
5392
1.49
19.1
5776
1.72
21
6154
1.96
24
6550
2.24
26
7333
2.89
29
CFM / Static Pressure in Inches WG
1
1.25
1.5
1.75
2
2.25
2.5
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM -=(RPM/3371)
(RPM/845)33
MAXIMUM
MAXIMUM RPM
RPM =- 1710
1240
TIP SPEED
TIP SPEED
(ft/min.)
- RPM
= RPM
x 2.929
x 6.414
MAXIMUM
MAXIMUMMOTOR
MOTORFRAME
FRAMESIZE
SIZE=-184T
56
2964
0.75
10.3
3915
1.05
13.2
4496
1.29
15.0
5010
1.54
17.2
5428
1.77
19.6
5826
2.02
23
6237
2.31
24
7053
2.97
28
3105
0.99
12.2
3944
1.27
13.8
4562
1.55
15.6
5039
1.80
17.6
5468
2.06
20
5914
2.36
22
6767
3.04
27
3958
1.52
14.8
4560
1.80
16.3
5062
2.08
18.2
5560
2.40
21
6469
3.10
25
3896
1.73
15.7
4555
2.05
17.3
5133
2.39
19.3
6146
3.14
24
3763
1.93
16.7
4588
2.35
18.7
5775
3.14
23
5364
3.13
23
4776
3.04
22
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-260 - Belt Drive
®
50
(1270)
H-
W.G.
m cu
rve
*36
(914)
this
syste
81/4 (210)
f t of
e le
to t
h
ec t
5 (127)
12
(305)
40
(1016)
no
t
sel
Damper Size = 30 x 30 (762 x 762)
Roof Opening = 321/2 x 321/2 (826 x 826)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 305 lb. (138 kg)
Do
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-260-4
HP
(Size)
Fan
RPM
1/4
300
365
H-GB-260-3
1/3
405
H-GB-260-5
1/2
465
H-GB-260-7
3/4
520
H-GB-260-10
1
580
H-GB-260-15
11/2
665
2
700
H-GB-260-20
735
H-GB-260-30
3
785
835
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
3875
0.12
8.0
4714
0.22
9.2
5231
0.30
10.4
6005
0.45
11.4
6716
0.63
12.9
7491
0.88
14.4
8588
1.33
16.7
9041
1.55
17.8
9493
1.79
18.9
10138
2.18
21
10784
2.62
23
0.125
3121
0.14
7.1
4130
0.25
8.8
4716
0.33
10.3
5570
0.50
10.9
6324
0.68
12.1
7137
0.93
13.7
8278
1.39
16.2
8746
1.61
17.4
9212
1.86
18.6
9875
2.26
20
10537
2.70
23
0.25
1727
0.12
7.4
3393
0.26
8.6
4095
0.35
10.3
5063
0.52
10.4
5898
0.72
11.3
6775
0.98
13.0
7979
1.44
15.8
8460
1.67
17.0
8938
1.92
18.3
9617
2.33
20
10292
2.78
22
CFM / Static Pressure in Inches WG
0.5
0.75
1
1.25
1.5
1.75
2
MAXIMUM BHP AT A GIVEN RPM = (RPM/572)3
MAXIMUM
MAXIMUM RPM
RPM == 1710
835
TIP SPEED
TIP SPEED
(ft/min.)
= RPM
= RPM
x 7.985
x 7.985
MAXIMUM MOTOR FRAME SIZE = 184T
3745
0.53
9.6
4869
0.75
10.3
5912
1.04
12.2
7274
1.53
15.0
7811
1.77
16.2
8335
2.03
17.6
9069
2.44
19.7
9794
2.91
22
3008
0.64
9.4
4826
1.03
11.0
6474
1.57
14.2
7068
1.82
15.5
7649
2.10
16.8
8452
2.53
18.9
9225
3.02
21
5465
1.55
13.3
6227
1.83
14.8
6878
2.13
16.2
7769
2.58
18.2
8606
3.08
20
3608
1.29
12.8
4912
1.71
13.8
5916
2.09
15.6
7006
2.59
17.9
7932
3.12
19.9
4236
1.80
14.9
5949
2.49
17.1
7157
3.10
19.7
4189
2.11
16.7
6024
2.93
18.7
4294
2.49
18.6
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
37
H-GB-300 - Belt Drive
®
50
(1270)
H-
of t
his
syst
em
c
urve
W.G.
*36
(914)
81/4 (210)
t to
the
5 (127)
left
12
(305)
40
(1016)
ot
se
lec
Damper Size = 30 x 30 (762 x 762)
Roof Opening = 321/2 x 321/2 (826 x 826)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 320 lb. (145 kg)
Do
n
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-300-3
HP
(Size)
Fan
RPM
1/3
300
365
H-GB-300-5
1/2
420
H-GB-300-7
3/4
475
H-GB-300-10
1
530
H-GB-300-15
11/2
600
H-GB-300-20
2
665
3
713
H-GB-300-30
760
H-GB-300-50
5
825
890
38
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0
4859
0.18
9.3
5912
0.33
9.2
6803
0.50
9.6
7694
0.72
11.4
8585
1.00
13.4
9719
1.45
15.9
10772
1.97
18.8
11549
2.43
21
12311
2.94
23
13363
3.76
25
14416
4.73
28
0.125
3976
0.19
5.3
5222
0.35
6.2
6222
0.52
8.0
7197
0.75
10.6
8150
1.04
12.9
9334
1.49
15.4
10425
2.02
18.2
11226
2.48
20
12007
3.00
22
13084
3.82
25
14157
4.79
28
0.25
4340
0.35
5.7
5537
0.53
7.0
6616
0.77
9.6
7640
1.06
12.2
8907
1.53
14.9
10060
2.06
17.7
10901
2.53
19.6
11704
3.05
21
12804
3.88
24
13898
4.85
28
CFM / Static Pressure in Inches WG
0.5
0.75
1
1.25
1.5
1.75
2
MAXIMUM
MAXIMUM BHP
BHP AT
AT AA GIVEN
GIVEN RPM
RPM =- (RPM/518)
(RPM/517)33
MAXIMUM
MAXIMUM RPM
RPM -=1710
890
TIP SPEED
TIP SPEED
(ft/min.)
- RPM
= RPM
x 7.985
x 7.985
MAXIMUM
MAXIMUM MOTOR
MOTOR FRAME
FRAME SIZE
SIZE =- 184T
184T
5095
0.74
8.1
6456
1.07
10.7
7952
1.55
13.8
9228
2.11
16.8
10129
2.59
18.9
10997
3.13
21
12175
3.97
24
13335
4.96
27
4195
0.91
9.4
6721
1.52
12.2
8269
2.11
15.7
9297
2.61
18.0
10242
3.16
19.8
11501
4.02
23
12716
5.03
26
7025
2.03
13.7
8283
2.57
16.4
9369
3.15
18.6
10770
4.05
22
12073
5.06
25
6691
2.38
13.7
8293
3.06
16.8
9909
4.01
20
11379
5.09
24
6437
2.76
14.0
8885
3.90
18.7
10536
5.02
22
7128
3.56
16.1
9568
4.89
21
7963
4.54
18.7
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
H-GB-300HP - Belt Drive
®
50
(1270)
H-
yste
mc
ur v
e
W.G.
*36
(914)
12
(305)
l ef
40
(1016)
to
the
5 (127)
to
f th
is s
81/4 (210)
ec
t
Damper Size = 30 x 30 (762 x 762)
Roof Opening = 321/2 x 321/2 (826 x 826)
Shroud Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 320 lb. (145 kg)
ts
el
Do
no
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number
H-GB-300HP-5
HP
(Size)
Fan
RPM
1/2
460
495
H-GB-300HP-7
3/4
565
H-GB-300HP-10
1
620
H-GB-300HP-15
11/2
710
2
748
H-GB-300HP-20
785
H-GB-300HP-30
3
840
895
H-GB-300HP-50
5
980
1065
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
0.5
2912
0.41
9.7
3602
0.53
10.3
4662
0.77
11.8
5398
1.01
13.4
6542
1.48
17.2
7013
1.71
18.8
7460
1.96
20
8107
2.37
23
8746
2.84
25
9722
3.68
32
10688
4.67
44
0.75
1
CFM / Static Pressure in Inches WG
1.25
1.5
1.75
2
2.25
2.5
2.75
MAXIMUM BHP AT A GIVEN RPM = (RPM/613)3
MAXIMUM RPM = 1065
TIP SPEED (ft/min.) = RPM x 7.985
MAXIMUM MOTOR FRAME SIZE = 184T
3600
0.76
10.4
4652
1.04
12.3
5954
1.53
16.0
6462
1.78
17.5
6943
2.04
19.1
7642
2.46
22
8328
2.95
24
9356
3.81
31
10351
4.81
42
3309
0.94
10.6
5269
1.55
15.3
5889
1.81
17.0
6402
2.08
18.5
7146
2.52
21
7870
3.03
23
8951
3.90
29
10006
4.94
37
4221
1.47
13.4
5027
1.78
15.7
5737
2.10
17.9
6636
2.57
21
7394
3.07
23
8531
3.99
28
9621
5.04
37
4800
2.00
16.2
5922
2.56
19.7
6892
3.11
23
8094
4.03
27
9233
5.12
36
4992
2.43
18.0
6150
3.08
22
7657
4.08
26
8831
5.17
35
5245
2.92
19.8
7029
4.09
25
8429
5.23
33
6264
3.95
24
7903
5.24
31
5222
3.69
23
7255
5.17
30
6543
5.01
29
Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a
birdscreen. The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for
installation type A: Free hemispherical inlet fan sone levels.
39
Specifications
Direct Drive Specifications
Model H-G spun aluminum exhaust fans shall be centrifugal direct
driven type. The fan wheel shall be centrifugal backward inclined,
constructed of aluminum and shall include a wheel cone carefully
matched to the inlet cone for precise running tolerances. Wheels
shall be statically and dynamically balanced. The fan housing shall be
drawn from high strength aluminum and connected to a heavy gauge
steel internal frame with integral bracing and a birdscreen.
Motors shall be heavy duty ball bearing type, carefully matched to the
fan load, and furnished mounted to the steel drive assembly at the
specified voltage, phase, and enclosure. Motors or drive assembly
shall be mounted on vibration isolators. Fresh air for motor cooling
shall be drawn into the motor compartment through a large space
between the fan shroud and motor cover. Motors shall be readily
accessible for maintenance.
A disconnect shall be NEMA rated and factory installed with wiring
included from the fan motor to a junction box installed within the
motor compartment. A conduit chase shall be provided through the
base to the motor compartment for ease of electrical wiring.
All fans shall bear the AMCA Certified Ratings Seal for sound and air
performance
Each fan shall bear a permanently affixed manufacturer’s engraved
nameplate constructed of aluminum and containing the model number
and individual serial number for future identification
Fans shall meet all Greenheck wind load standards and shall contain
the following third party certifications
•
Miami-Dade NOA# 07-0503.07
•
Licensed P.E. calculations shall be available for fan per ASCE 702 Minimum Design Loads for Buildings and Other Structures for
exposure class C, 60 foot building height, and a type II building.
•
Fan shall be tested in accordance with ASTM E330-02.
Structural Performance of Exterior Windows, Doors, Skylights,
and Curtain Walls by Uniform Static Air Pressure Difference and
Florida Building Code Test Protocol TAS-202 at the ASCE 7-02
calculated design load.
•
Licensed P.E. calculations for attachment of fan to curb shall be
available for ASCE 7-02 determined design pressure.
•
All calculations and testing shall be done by a state licensed
P.E., and a certified test lab.
Motors shall be heavy-duty ball bearing
type, carefully matched to the fan load, and
furnished mounted to the steel drive frame at
the specified voltage, phase, and enclosure.
Drive frame assembly shall be constructed of
heavy gauge steel with engineered forms for
added strength. Motors and drives shall be
mounted on vibration isolators with no metal
to metal contact, out of the airstream. Fresh
air for motor cooling shall be drawn into the
motor compartment through a large space
between the fan shroud and the motor cover.
Motors and drives shall be readily accessible
for maintenance.
Precision ground and polished fan shafts shall
be mounted in pillow block ball bearings.
Bearings shall be selected for a minimum (L10)
life in excess of 100,000 hours (L50 average
life of 500,000 hours) at maximum cataloged
operating speed. Drives shall be sized for
a minimum of 150% of driven horsepower.
Pulleys shall be of the cast type, keyed and
securely attached to the wheel and motor shafts.
Motor pulleys shall be adjustable for final system balancing. A
disconnect switch shall be NEMA rated and factory installed with
wiring included from the fan motor to a junction box installed within
the motor compartment. A conduit chase shall be provided through
the base to the motor compartment for ease of electrical wiring.
All fans shall be third party tested and certified for sound and air
performance.
Each fan shall bear a permanently affixed manufacturer’s engraved
metal nameplate containing the model number and individual serial
number for future identification.
Fans shall meet all Greenheck wind load standards and shall contain
the following third party certifications
•
Miami-Dade NOA# 07-0503.07
•
Licensed P.E. calculations shall be available for fan per ASCE 702 Minimum Design Loads for Buildings and Other Structures for
exposure class C, 60 foot building height, and a type II building.
•
Fan shall be tested in accordance with ASTM E 330-02.
Structural Performance of Exterior Windows, Doors, Skylights
and Curtain Walls by Uniform Static Air Pressure Difference and
Florida Building Code Test Protocol TAS-202 at the ASCE 7-02
calculated design pressure.
•
Licensed P.E. calculations for attachment of fan to curb shall be
available for ASCE 7-02 determined design pressure.
•
All calculations and testing shall be done by a state licensed P.E.,
and a certified test lab.
Fans shall be Greenheck model H-G manufactured by Greenheck Fan
Corporation in Schofield Wisconsin.
Belt Drive Specifications
Model H-GB spun aluminum exhaust fans shall be centrifugal belt
driven type. The fan wheel shall be centrifugal backward inclined,
constructed of aluminum and shall include a wheel cone carefully
matched to the inlet cone for precise running tolerances. Wheels
shall be statically and dynamically balanced. The fan housing shall be
drawn from high strength aluminum and connected to a heavy gauge
steel internal frame with integral bracing and a birdscreen.
Fans shall be Greenheck models H-GB and H-GB-HP, manufactured
by Greenheck Fan Corporation in Schofield, Wisconsin.
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of
one year from the purchase date. Any units or parts which prove defective during the warranty period will
be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the
motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during
this period, they should be returned to the nearest authorized motor service station. Greenheck will not be
responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com
Prepared to Support
Green Building Efforts
Catalog H-G & H-GB Rev. 2 November 2007
Copyright © 2007 Greenheck Fan Corp.