Centrifugal Roof Downblast Exhaust Fans Models G and GB • General Clean Air • Light Contaminants • Seismic • High Wind • Variable Volume ® Performance data now included. March 2013 Models G and GB Spun Aluminum • Downblast Centrifugal Roof Exhaust Fans Contents PERFORMANCE AND DIMENSIONS: Model Comparison . . . . . . . . . . . . . . . . . . . . . . 3 Models G-060-095 . . . . . . . . . . . . . . . . . . 14-17 Construction Features . . . . . . . . . . . . . . . . . 4-5 Models G-097-G203 . . . . . . . . . . . . . . . . . 18-31 Emergency Smoke Control . . . . . . . . . . . . . . . 6 GB-071-200HP . . . . . . . . . . . . . . 18-32 Models GB-220-540 . . . . . . . . . . . . . . . . . 33-46 Seismic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 SPECIFICATIONS: High Wind & Hurricane. . . . . . . . . . . . . . . . . . . 7 Vari-Green® Motors and Controls . . . . . 47 Vari-Green® Motor and Controls . . . . . . . . . 8-9 Direct Drive, Model G . . . . . . . . . . . . . . . 48 Demand Control Ventilation. . . . . . . . . . . . . . . 9 High Wind & Hurricane, Seismic . . . 49 Roof Curbs, Options, Accessories . . . . . 10-11 Belt Drive, Model GB . . . . . . . . . . . . . . . . 50 Typical Installations . . . . . . . . . . . . . . . . . 12-13 High Wind & Hurricane, Seismic & Smoke Control . . . . . . . . 51 Model Number Code . . . . . . . . . . . . . . . . . . . 13 Quick Build Programs . . . . . . . . . . . . . . . . . . 52 Our Commitment . . . . . . . . . . . . . . . . . . . . . . 52 Codes and Certifications Greenheck Fan Corporation certifies that the Models G and GB fans shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. The certified ratings for Models G and GB are shown on pages 14 - 46. G and GB models are listed for electrical (UL/cUL 705) File no. E40001 GB models for Emergency Smoke Control Systems (UL/cUL Listed for 500˚F (260˚C) for 4 hours and 1,000˚F (538˚C) for 15 minutes) File no. MH17511 *UL/cUL is optional and must be specified High Wind Certification Seismic Certification Miami-Dade NOA No. 12-0120.13 for high wind and hurricane zones OSHPD No. 0148-10 - Office of Statewide Health Planning and Development (California) IBC 2009 and 2012 - International Building Code Models G and GB Spun Aluminum • Downblast Centrifugal Roof Exhaust Fans Model Comparison 9 9 9 9 9 9 9 9 9 6,308 1.75 $ 44,700 3.25 $ Mixed Flow Propeller/Axial Centrifugal Direct Belt Continuous High Temp (above 200°F ) High Wind** Smoke Control (UL)* Grease (UL 762) Spark Resistant Contaminated Air General/Clean Air 9 9 Relative Cost 9 9 Recirculate Reversible Supply Wall Hanging Base/Floor Roof Curb 9 9 Impeller Type Performance Maximum Static Pressure (in. wg) GB 9 9 Drive Type Application Maximum Volume (cfm) G Indoor Outdoor Model Airflow Exhaust Mounting Ceiling Mounted Location * Smoke Control available on models: 101, 101HP, 121, 131, 141, 141HP, 161, 161HP, 200, 240, 300, 360, 420 and 480. ** High wind limited to sizes 300 and smaller Greenheck models G and GB centrifugal roof exhaust fans provide the industry’s best performance and durability for general clean air applications where air is discharged downward, toward the roof surface. • Broadest performance in the industry, up to 3.25 in. wg (810 Pa) and 45,000 cfm (76,500 m3/hr). • Most advanced motor cooling of any fan in its class. • Performance as cataloged is assured. All fan sizes are tested in our AMCA Accredited Laboratory, and all models are licensed to bear the AMCA Sound and Air Performance seals. • UL Listed for electrical. • Greenheck subjects these products to extensive life testing, assuring you that the fans will provide years of reliable performance. Direct Drive, G • Use for short and/or low resistance ductwork Belt Drive, GB • For average length and/or average resistance ductwork • High volume/average pressure High Pressure, GB-HP and G-HP • For long and/or high resistance ductwork • Low volume/high pressure 3 Construction Features Models G and GB Standard Construction Features 1 Wheel An aluminum, backward-inclined, non-overloading centrifugal wheel is utilized to generate high-efficiency and minimal sound. Wheel cones are carefully matched to the venturi for maximum efficiency. Each wheel is robotically welded and statically and dynamically balanced for long life and quiet operation. 2 Disconnect Switch NEMA-1 switch is factory mounted and wiring is provided from the motor as standard (other switches are available). All wiring and electrical components comply with the National Electrical Code® (NEC) and are either UL Listed or Recognized. 3 Fan Shaft Precisely sized, ground and polished so the first critical speed is at least 25% over the maximum operating speed. Where the shaft makes contact with bearings, tight tolerances result in longer bearing life. 4 Bearings 100% factory tested and designed specifically for air handling applications with a minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours). 5 Motor Carefully matched to the fan load and is mounted out of the airstream. 6 Motor Cover Constructed of aluminum and attached with fasteners that provide for easy removal and access to motor compartment and drive assembly. 7 Motor Cooling Cooling fins located on top of the fan wheel draw outside air through a large space between the fan shroud and the motor cover directly into the motor compartment. Positive motor cooling with fresh air results in maximum motor life. 8 Lifting Points Various lifting points are located on the drive frame and bearing plate (on select sizes). 9 True Vibration Isolation Vibration isolators, with no metal-to-metal contact, support the drive assembly and wheel for long life and quiet operation. 10 Drive Assembly Belts, pulleys, and keys are oversized 150% of driven horsepower. Machined cast pulleys are adjustable for final system balancing. Belts are static-free and oil-resistant. 11 Lower Windband Heavy-gauge aluminum with formed edges for added strength and provides weather resistance. 12 Curb Cap Curb cap (with integral deep spun venturi) is constructed of aluminum and is one-piece for a weather-tight fit. 13 Internal Conduit Chase A large diameter conduit for installing electrical wiring through the curb cap into the motor compartment. 14 Nameplate Permanent stamped aluminum plate for exact model and serial number identification. 15 Galvanized Birdscreen Rigid wire protects the fan discharge from birds and small objects. 16 Fan Shroud One-piece, heavy-gauge aluminum with a rolled bead for extra strength directs exhaust air downward. 17 Mounting Holes Curb cap has prepunched mounting holes to ensure correct attachment to the roof. High Wind Construction Features 4 18 Internal Supports Heavy-gauge supports and bracing are added for additional strength to withstand a load of 75 psf. 19 Reinforced Wind Band High wind fans include additional reinforcement for maximum strength. Roof Curb (page 10) High wind-load fans are certified for use with Greenheck model GPFHL, GPFHD, GPF or equivalent in high wind applications. Roof curbs ship separate for field installation with attachment details provided. Construction Features Models G and GB 6 7 5 15 1 11 14 12 8 MODEL G DIRECT DRIVE 8 DRIVE FRAME (BELT DRIVE) 6 3 10 4 8 16 2 9 13 18 19 MODEL GB BELT DRIVE 17 5 Applications G and GB models Emergency Smoke Control - GB When you buy a Greenheck model GB with the smoke control option, you receive a fan with the industry’s best performance and durability for smoke control applications (as found in emergency smoke control systems). GB smoke control models are: 101, 101-HP, 121, 131, 141, 141-HP, 161, 161-HP, 200, 240, 300, 360, 420, 480 Seismic - G and GB • UL/cUL Listed for 500°F (260°C) for 4 hours and 1,000°F (538°C) for 15 minutes. • Half the weight of traditional smoke control fans, ideal choice for roof load concerns. • Low profile, height is less than half of traditional smoke control fans, maximum of 521⁄2 inches (1334 mm) from curb cap to top of fan. • Multiple applications, capable of exhausting general clean air and satisfying emergency smoke control regulations. With changes in building codes and standards, more equipment is being required to be seismically certified in areas of the country not commonly thought of as being in seismically active zones. The International Building Code (IBC) is designed to provide model code regulations that safeguard public health and safety in all U.S. communities. This code is intended to improve the performance and design of non-structural systems subject to seismic events. The State of California, one of the most active seismic areas in the United States, has the Office of Statewide Health Planning and Development (OSHPD) to regulate the design and construction of healthcare facilities to ensure they are safe and capable of providing ens services to the public after a seismic event. sser OSHPD developed their own unique certification O process to incorporate the IBC and ASCE p testing standards to ensure equipment remains t operable after a seismic event. o Note: All G and GB models meet seismic requirements. Protocols designed for seismic standards: 6 Seismic Testing Criteria All Greenheck seismically certified models have been tested using the most severe seismic event that is found on the Spectral Response Map per IBC Figures 1613.5 (1-2). Our testing is performed under the worst case scenario using the highest mapped seismic load, highest level occupancy category, worst case site class, and highest code mandated importance factor, thereby allowing Greenheck’s seismically certified fans to be used anywhere in the United States under any conditions California OSHPD Test Protocols The California Office of Statewide Health Planning and Development (OSHPD) requires all certified models be shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected to the same or greater forces than they will see during a seismic event. Subjecting Greenheck model G and GB fans to this type of testing ensures the fans will operate without problems after a seismic event. OSHPD Certification No. 0148-10 The OSHPD certification numbers and supporting documents can be viewed on OSHPD’s website ensuring that the fan has been subjected to and passed rigorous testing standards. State Licensed P.E. Calculations When using the fans in applications which are not covered by California OSHPD standards, Greenheck models G and GB have been certified by a third party engineering firm to IBC 2009, 2012 and ASCE 7-05 standards. These engineers hold professional engineering (P.E.) licenses in all 50 states, so no matter where your job is located, you are backed by a P.E. signature for your state. Certified Independent Third-Party Testing All Greenheck seismically certified fan models have gone through extensive testing procedures. Greenheck models G and GB have been certified to IBC 2009, 2012, ASCE 7-05 and California OSHPD standards through both engineering calculations and shake table testing of all models by independent third party engineering firms. Applications G and GB models High Wind and Hurricane - G and GB Greenheck is leading the High Wind Standard for roof top fans and ventilators. Forceful winds and wind-borne debris are the cause of most hurricane damage. Hurricane winds start at 75 mph. and can exert a force of 75 pounds per square foot of pressure—or over 900 pounds on a fan and curb. Forceful winds are not the only problem, wind-borne debris can also cause detrimental effects to objects and structures. High winds and extreme forces are the cause of most storm damage. By analyzing calculations, computer simulations, actual testing, and other standards—Greenheck developed the High Wind Standard. U.S. continent averaged ed tornado frequency. Protocols designed to protect against wind-borne debris and severe wind-loads: Atlantic, Gulf and Pacific history of major hurricane tracks. Structural Performance Load A static load that is 1.5 times the design load (91.5 pounds per square foot of pressure) is applied both positively and negatively to simulate wind force loads in each direction. Structural Performance per Dade County Protocol TAS-202 (ASTM-E330). Miami-Dade County Test Protocols Greenheck worked with Miami-Dade County to outline a High Velocity Hurricane Zone standard for rooftop fans. Greenheck model USGF was the first rooftop fan certified and approved by the MiamiDade Building Code Compliance office and Texas Department of Insurance for use in hurricane zones. Models G and GB have been certified by an independent third party to the ASTM E-330 Static Pressure Difference Standard, Florida Building Code Test Protocol TAS-201 (large missile impact), 202 (static pressure difference) and 203 (cyclic pressure) Static Pressure Difference. Miami-Dade NOA Numbers The certifications can be viewed on the Miami-Dade County website under the NOA numbers listed here. Models G and GB are the first downblast aluminum fans in the industry that have received a Miami-Dade NOA for high wind and hurricane zones. Miami-Dade NOA 12-0120.13 for models G and GB. Florida Product Approval Florida Product Approval ensures that products which have been approved can be used anywhere in the State of Florida which are not governed by the Miami-Dade County high wind regulations. More information can be found on the Florida Building Code website. Florida Product Approval FL13225.1 for models G and GB State Licensed P.E. Calculations Structural calculations performed by a licensed Professional Engineer (P.E.) on models G and GB include Finite Element Analysis (FEA) and a stamped P.E. report of the fans compliance to ASCE 7-05 Minimum Design Loads for Buildings and Other Structures Standard and the Florida Building Code. The ASCE 7-05 Standard meets the IBC, Florida and Miami-Dade codes. Computational Fluid Dynamics (CFD) All Greenheck high wind models have been analyzed using Computational Fluid Dynamics (CFD). CFD is computer software designed to simulate the flow of high speed winds over the surface of objects. The software records the force profile exerted on the fan so it can be utilized in Finite Element Analysis (FEA). Finite Element Analysis (FEA) Utilizing the results from CFD analysis, Greenheck can accurately predict the stress, strain, and deflection resulting from high wind loads. Greenheck high wind units have been proven to withstand high winds through Finite Element Analysis utilizing CFD results. 7 Vari-Green® Motor Option Model G Features ® Greenheck’s electronically commutated (EC) Vari-Green (VG) motor combines motor technology, controllability and energy-efficiency into one single low maintenance unit and is the industry’s first fully controllable motor. When combined with Greenheck’s G fans, all the CFM and static pressure ranges of a belt drive can be attained with the benefits of a direct drive. 1. Dial on Motor Control - a potentiometer (dial on motor control) is mounted on the motor for easy speed adjustment for system balance. Simply turn the dial. There are no belts and pulleys to adjust. 2. Control Wire Inputs - the motor accepts a 0-10V DC signal from Building Automated Systems or other controls to adjust motor speed. Motor Information HP RPM 1/6 1725 1/4 1725 1/2 1725 3/4 1725 1 1725 2 1725 Extended RPM Motors 1/2 2500 3/4 2200 Voltage 115, 208-240 115, 208-240 115, 208-240 115, 208-240 115, 208-240 208-240 HZ 50/60 50/60 50/60 50/60 50/60 50/60 115 115 50/60 50/60 1 2 Comparisons: Belt, Direct Drive with PSC and Direct Drive with Vari-Green Motor Turndown Comparison Benefits • The motor can attain up to 85% efficiency and reduce energy consumption. • Watt savings of 30-70% depending on RPM. Note: As motor speed is turned down, efficiency stays high as compared to an AC motor that decreases dramatically. • Operates cooler than a standard AC motor at lower RPMs. A cooler motor has longer motor life and reduces energy consumption. • 80% usable RPM turndown versus 30%, see Motor Turndown Comparison chart at right. • G fans with Vari-Green motors can provide all the CFM and static pressure ranges of a comparable belt drive. • Maintenance costs are reduced as there are no belts or bearings to replace and no pulleys to adjust. • Direct drive fans are often preferred where maintenance access is difficult. • Provides a solution for demand controlled ventilation applications. Vari-Green Advantages • Initial cost is similar to a belt drive 500 INPUT POWER (WATTS) Operates on AC power that’s converted to DC— providing a more efficient motor operation as compared to an AC operation. 50% 75% 100% 600 G-123 with PSC 400 Not recommended 300 EEnergy S Savings GB-123 Single Phase* 200 G-123 with 100 0 0 350 FAN SPEED (RPM) 1750 * GB is a belt driven fan The length of each curve indicates the practical turndown range. Data is for 1/2 hp motors with load of 0.35 Bhp at full speed Constant Volume Life Cycle Analysis Three Year Cost Comparison $2,000 1,750 1,500 1,250 1,000 750 500 250 $0 CUBEGB121 121 CUEG121-A5 123-A5 CUEG121-VG 123-VG Initial Cost Maintenance cost over three years Operating cost over three years • No maintenance, no belts, pulleys or bearings Analysis is based on operating costs for a period of three years where the fans operate continuously at 1725 rpm, 24/7, with an energy rate of $0.10/kWh. Maintenance on the GB-121 is estimated at $65/yr. • Easy RPM adjustment Note: Example is based on a relative cost. Use and installation variables may produce different results. • Lower operating cost 8 Vari-Green® Control Options Vari-Green® Controls Transformer - Provides 24V power from the existing line voltage at the fan to the Vari-Green motor and controls. Dual voltage primary (120/240V) transformer provided with the fan. Remote Dial - Allows for remote, manual airflow adjustments. Wall plate with dial may be mounted in a standard 2x4 inch electrical junction box. Two Speed Control with Integral Transformer Control allows motor rpm to be set at two independent speeds (high or low). Meets minimum airflow requirements with the ability to bump up to high speed in an emergency or meet maximum airflow requirements, or reset down to low for energy conservation. Contact fans@greenheck.com for more information. Daily Operating Comparison: Variable Volume and Constant Volume % of Operation Applications requiring constant pressure or variable volume can utilize G fans with Vari-Green motors and Vari-Green controls. Variable Volume Demand control Operating Cost Analysis Variable Volume vs. Constant Volume ventilation systems $ 2,000 reduce the amount of energy used by 1,750 decreasing the speed of 1,500 the fan when demand 1,250 is low. This in turn 1,000 lessens the amount 750 of conditioned air 500 exhausted and further 250 reduces total operating $0 costs associated with Constant Variable Volume air conditioning and Volume heating in multistoried Heating Cost Cooling Cost buildings such as hotels, Fan Operating Cost multifamily complexes, Example of potential savings institutional facilities, and high rise commercial based on a northeast city in the USA using Vari-Green buildings. components for variable volume. The Vari-Green constant pressure control is preprogramed and easy to install for applications that include venting dryers, bathrooms, residential type kitchen space or industrial process exhaust. Hypothetical (Hotel Bathroom) Variable Volume - Load Shape 100 80$$$$$$$$$$$$$$$$$$$$$$$$ 60$$$$$$$$$$$$$$$$$$$$$$$$ 40$$$$$$$$$$$$$$$$$$$$$$$$ 20$$$$$$$$$$$$$$$$$$$$$$$$ 0%$$$$$$$$$$$$$$$$$$$$$$$$ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time of Day Series 1 Demand-controlled ventilation offers significant energy savings by exhausting only the necessary amount of air throughout the day. % of Operation Demand Control Ventilation for Multistory Buildings Constant Volume - Load Shape 100 80 60 40 20 0% 1 2 3 4 Series 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Time of Day Note: A standard VFD compatible motor can also function within a Variable Volume system. Constant Pressure Control - Outdoor Control a Vari-Green motor via static pressure on the inlet side of the fan. Includes one duct probe and transducer for use in: • Multifamily structures - Apartments, condos, hotels; residential kitchen, dryer facilities and bathrooms. • Institutional facilities - Schools, prisons, multistory. Air Quality – VOC - Control a Vari-Green motor via changes in volatile organic compounds (VOC’s). VOC’s are gasses that are emitted from humans, building materials, perfumes, foods, and furniture off-gassing. Range is 0-2000 CO2 PPM equivalent. • Institutional facilities – Schools, court house, hospitals; bathrooms, waiting rooms, cafeteria. • Commercial buildings – Office space, conference rooms, bathrooms, break room. Constant Pressure Control - Indoor - Control VariGreen motor via static (variable volume) or velocity (constant CFM) pressure on the inlet or outlet side of the fan. Optional one or two duct or room probes for use in: Air Quality – Temperature and Humidity - Control Vari-Green motor via changes in temperature, humidity, or both. Range is 32 to 120°F and 0 to 100% relative humidity. • Multifamily structures - Apartments, condos, hotels; clothes dryers, residential kitchens and bathrooms. • Multifamily structures - Apartments, condos, hotels; bathrooms, utility rooms. • Institutional facilities - Schools, prisons, multistory office buildings; bathrooms. • Commercial buildings - Office buildings, office space, conference rooms, utility rooms, bathrooms. 9 Options and Accessories Roof Curbs High Wind and Severe Duty Roof Curbs Prefabricated roof curbs reduce installation time and costs by ensuring compatibility between the fan, the curb and roof opening. All curbs are insulated with fiberglass. A wide variety of roof curbs are available, including: flanged, pitched and sound-absorbing. GPF/GPFP/GPFR – Approved for high wind applications up to a 75 psf wind-load rating. Constructed of 18 gauge steel, formed and welded sides, and a 5-inch flashing flange. GPF is available up to 42 inches in height. GPFP and GPFR are available up to 24 inches in height. Hinged Curb Cap with Cables (Field Installed) Mounted to the curb cap, allows entire fan to tilt away from curb for access to wheel and ductwork. Includes restraint cables. Hinged Base (Factory Mounted) Allows for easy maintenance. Hinge and restraining cables are factory mounted to a subbase attached directly to curb without additional height added. Curb Seal Rubber seal between fan and curb to assure proper sealing when attached to a curb. Curb Extensions Extensions raise the fan discharge above the roofline and provide an accessible mounting location for dampers. Insect screen bases, constructed with a removable fine mesh, are recommended for applications where insect entry must be prevented. 10 Severe Duty Curbs – Designed for heavy compression loads exceeding 1,000 lbs. and carry a 130 psf wind-load rating. GPFHL (Heavy Load) - 14 gauge galvanized steel with internal vertical support members and a 5-inch flashing flange. GPFHD (Heavy Duty) - 12 gauge galvanized steel with internal vertical support members and a double thick 5-inch flashing flange. GPFHL and HD are available up to 24 inches in height. Note: Maximum 24 inch height restriction on all curb models certified for high wind. For detailed curb information refer to Roof Curbs, Extensions and Equipment Supports catalog. Mounting details for the roof curb to the roof substrate and the fan to the curb are included with each model G and GB installation manual. For additional severe duty information, refer to the Greenheck High Wind brochure. Tie-Down Points Four brackets located on the shroud for securing the fan in high wind applications. Cables and anchors by others. Options and Accessories Speed Controllers for Standard Motors Available for use with shaded pole and permanent split capacitor (PSC) open motors on model G fans. They provide an economical means of system balancing with direct drive fans. Birdscreen Galvanized mesh is standard, optional aluminum or stainless steel rigid wire are also available. Disconnect Switches A wide selection of NEMA rated switches are available for positive electrical shutoff and safety, including: dust-tight, rainproof, and corrosion-resistant. Switches may be internally or externally mounted. G and GB models are Listed for electrical (UL/cUL 705) File no. E40001 GB models for Emergency Smoke Control Systems (UL/cUL Listed for 500˚F (260˚C) for 4 hours and 1,000˚F (538˚C) for 15 minutes) File no. MH17511 Note: UL/cUL is optional and must be specified. Dampers Coatings Designed to prevent outside air from entering back into the building when fan is off. Includes gravity and motorized dampers. Damper sizes are shown on each performance data page. A wide variety of coatings and colors are available. Greenheck coatings and resistance charts can be found in the Performance Coatings Commercial and Industrial Fans catalog and in our Product Application Guide—Performance Coatings for Ventilation Products. Motor Starters The fundamental function of a motor starter is to protect the motor from damage that can occur from overheating. With a Greenheck motor starter you will be provided with the best motor protection available. Specific model components may include; SmartStart™ technology, physical interface, overload protection, disconnect, magnetic contactor, NEMA-1 or NEMA-3R steel enclosures and pre-engineered easy system integration. For complete information on specific Greenheck Motor Starter models refer to greenheck.com, Motor Starter page. Primer is applied at the factory to allow for final finish in the field. PRIMER TM PERMATECTOR HI-PRO POLYESTER Permatector™ is our standard coating. Typically used for applications that require corrosion resistance in indoor and outdoor environments. Hi-Pro Polyester is resistant to salt water, chemical fumes and moisture in more corrosive atmospheres. Typically used for applications that require superior chemical resistance, excellent abrasion and outdoor UV protection. This coating exceeds protective qualities of Air Dried Heresite and Air Dry Phenolic. Baked Enamel Decorative Coatings are heat cured enamels applied either as wet paints or electrostatic powders. Customers can choose from 16 standard decorative colors or color match any color. 11 Typical Installations Models G and GB General Clean Air (figure 1) Factory Wired from Motor to Disconnect Models G and GB exhaust fans are designed to meet the needs of general clean air applications. Tests were conducted to assure safe, rugged and reliable fans. Due to the varying types of airstreams encountered in commercial ventilation, system designers must be aware of national, state, and local codes and guidelines governing these installations. Local code authorities should be consulted before proceeding with any ventilation project. figure 1 Wiring by Others 3/4 in. 8 or 12 in. (19 mm) (203 or 305 mm) • When roofing materials extend to the top of the curb, roof curbs should be 11⁄2 inches (3⁄4 inch on each side) less than the unit curb cap to allow for roofing and flashing. Damper 11/4 in. (32 mm) • For recommended duct size, damper size, and roof opening dimensions, refer to the performance data pages. (starting on pg. 14) • Installation must include a means for inspecting, cleaning and servicing the exhaust fan. Recommended Duct and Damper Size 11/4 in. (32 mm) Recommended Roof Opening 1/4 in. (6 mm) Fastener figure 2 High Wind, Hurricane and Seismic (figure 2) • Roofing materials can extend to the top of the curb, roof curbs should be 1 inch (25 mm) total, or 1⁄2 inch (13 mm) on each side, less than the unit curb cap to allow for roofing and flashing. Note: The typical installations shown are recommendations based on national codes. Local authority may supersede these recommendations. 1/2 in. (13 mm) 4 in. (102 mm) From Curb Edge Wiring by Others 8 - 24 in. (203 - 610 mm) GPF or SD Curb Damper 11/4 in. (32 mm) Recommended Duct and Damper Size 11/4 in. (32 mm) Recommended Roof Opening Wheel Rotation Direction of rotation is very critical. Rotation in the wrong direction will result in excessive horsepower, possible motor burnout, and increased noise levels. Check rotation by energizing the unit momentarily. The rotation should be the same as the rotation decals affixed to the unit and is clockwise when viewed from the top of the unit. Clockwise 12 Typical Installations Models G and GB Fan Inlet Connections In order to assure proper fan performance, caution must be exercised in fan placement and connection to the ventilation system. Obstructions, transitions, poorly designed elbows, improperly selected dampers, etc., can cause reduced performance, excessive noise, and increased mechanical stress. For performance to be as published, the system must provide uniform and stable airflow into the fan. A Provide uniform airflow at fan inlet to assure optimum performance. B Provide uniform airflow at fan inlet and through the damper to assure optimum performance. C Dampers must open fully. Use motorized dampers in low airflow applications to reduce losses. D Avoid sharp turns or entrance conditions which cause uneven flow. Use turning vanes in elbows to reduce adverse effects. Good Good A B Poor Poor D C Model Number Code The model number code system is designed to completely identify the fan. The correct code letters must be specified to designate belt or direct drive. The remainder of the model code is determined by the size and performance. GB - 240 HP - VG/ 5 / A - X VG X = UL 705 F = UL Smoke = Vari-Green® (Direct Drive only) Configuration G - Direct Drive GB - Belt Drive Fan Size 060 through 540 Wheel Pressure Level Control Systems Motor HP (Belt Drive only) 6 4 3 5 7 = = = = = = = = = 1/6 1/4 1/3 1/2 3/4 10 15 20 30 1 1½ 2 3 50 = 5 75 = 7½ 100 = 10 150 = 15 HP - High Pressure Motor RPM (Direct Drive only) A = 1725 B = 1140 C = 860 D = 1550 E = 1050 G = 1300 International (See CAPS for performance) K = 950 RPM J = 1475 RPM 13 Roof Downblast - Exhaust Direct Drive G-060 • G-065 0.6 193⁄8 140 (492) RPM (Direct) RPM (Vari-Green) Density 0.075 lb/ft3 0.5 17 06 06 0- 5- G D 06 5- D 06 0- G 065 -E 06 0- E DO 0 0.0 Damper Size = 8 x 8 (203 x 203) Roof Opening = 10½ x 10½ (267 x 267) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 15 lbs. (7 kg) 0 60 120 180 240 300 360 Volume (cfm) 0 100 200 300 400 500 600 3 Volume (m /hr) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Direct Drive THIS SYS TEM CUR VE 0.1 20 (432) VG VG 40 0.2 5- 0- 13⁄4 (44) 60 0.3 06 06 3 (76) 80 0.4 TO THE LEF T OF (308) Density 1.2 kg/m3 NO TS ELE CT *12 ⁄8 Static Pressure (Pa) 100 1 Static Pressure (in. wg) 120 G-1300-RPM E-1050-RPM D-1550-RPM 0 0.05 0.1 Static Pressure in Inches wg 0.125 0.15 0.2 0.25 0.3 0.375 0.4 CFM BHP Sones CFM G-1/100 1300 BHP Sones CFM D-1/60 1550 BHP Sones CFM 1725 BHP Sones 138 0.00 1.7 170 0.01 2.9 203 0.01 4.3 226 0.02 5.4 116 0.00 1.7 153 0.01 2.8 188 0.01 3.9 213 0.02 4.9 90 0.01 1.7 135 0.01 2.8 173 0.01 3.8 199 0.02 4.9 73 0.01 1.7 125 0.01 2.7 166 0.01 3.8 193 0.02 4.8 53 0.01 1.7 113 0.01 2.7 158 0.02 3.8 186 0.02 4.8 85 0.01 2.6 140 0.02 3.7 173 0.02 4.8 120 0.02 3.7 155 0.02 4.7 92 0.02 3.6 137 0.02 4.6 101 0.02 4.5 89 0.02 4.4 CFM BHP Sones CFM 1300 BHP Sones CFM 1550 BHP Sones CFM 1725 BHP Sones 187 0.01 2.2 231 0.01 3.2 276 0.02 4.9 307 0.03 6.4 161 0.01 2.1 211 0.01 3.1 259 0.02 4.6 292 0.03 5.8 130 0.01 1.9 189 0.01 3 241 0.02 4.5 276 0.03 5.8 110 0.01 1.8 178 0.01 2.9 232 0.02 4.5 268 0.03 5.8 87 0.01 1.7 163 0.01 2.9 223 0.02 4.4 260 0.03 5.8 130 0.01 2.8 201 0.02 4.3 243 0.03 5.8 92 0.01 2.7 176 0.02 4.3 223 0.03 5.7 145 0.02 4.1 201 0.03 5.7 96 0.02 4 160 0.03 5.7 146 0.03 5.7 Motor HP Fan RPM 060 VG1/6 E-1/200 1050 065 VG1/6 E-1/100 1050 G-1/60 D-1/30 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 14 Roof Downblast - Exhaust Direct Drive G-070 • G-075 0.6 193⁄8 140 RPM (Direct) 0.0 SYS TEM CUR VE Static Pressure (Pa) DO 07 5- G 07 5- E 0 90 180 270 360 450 540 Volume (cfm) 0 200 400 600 800 3 Volume (m /hr) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP D 0- 0 Damper Size = 8 x 8 (203 x 203) Roof Opening = 10½ x 10½ (267 x 267) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 15 lbs. (7 kg) Direct Drive D E (432) 5- 0- 20 VG 0- 0.1 07 07 17 40 0.2 VG G 0- 13⁄4 (44) 60 0.3 5- 07 3 (76) 80 07 07 (308) 0.4 07 *121⁄8 Static Pressure (in. wg) 120 100 RPM (Vari-Green) Density 0.075 lb/ft3 Density 1.2 kg/m3 0.5 NO TS EL EC TT OT HE LEF TO FT HIS (492) E-1050-RPM G-1300-RPM D-1550-RPM 0 0.05 0.1 Static Pressure in Inches wg 0.125 0.15 0.2 0.25 0.3 0.375 0.4 CFM BHP Sones CFM 1300 BHP Sones CFM 1550 BHP Sones CFM 1725 BHP Sones 253 0.01 2.7 314 0.01 4.1 374 0.02 5.6 416 0.03 6.8 226 0.01 2.1 292 0.01 3.7 356 0.02 5.4 400 0.03 6.7 195 0.01 1.7 269 0.02 3.4 337 0.02 5.2 383 0.03 6.7 179 0.01 1.5 257 0.02 3.3 327 0.03 5.1 375 0.03 6.6 152 0.01 1.2 244 0.02 3.2 317 0.03 5.1 366 0.03 6.6 214 0.02 2.9 297 0.03 4.9 348 0.04 6.5 171 0.02 2.6 274 0.03 4.7 329 0.04 6.3 244 0.03 4.5 309 0.04 6.2 190 0.03 4.1 270 0.04 5.9 253 0.04 5.7 CFM BHP Sones CFM 1300 BHP Sones CFM 1550 BHP Sones CFM 1725 BHP Sones 297 0.01 3.6 367 0.02 4.1 438 0.03 6.1 487 0.05 8.0 260 0.01 3.1 338 0.02 3.9 413 0.03 5.8 465 0.05 7.5 222 0.01 2.9 309 0.02 3.7 389 0.03 5.6 443 0.05 7.2 200 0.01 2.8 293 0.02 3.7 377 0.04 5.4 432 0.05 7.1 176 0.01 2.6 277 0.02 3.7 364 0.04 5.3 421 0.05 6.8 241 0.02 3.6 337 0.04 5.1 399 0.05 6.5 195 0.02 3.5 309 0.04 4.9 374 0.05 6.2 277 0.04 4.9 349 0.05 6.1 214 0.03 4.8 306 0.05 6.0 292 0.05 6.0 Fan RPM 070 VG1/6 E-1/100 1050 G-1/60 D-1/30 075 VG1/6 E-1/80 G-1/50 D-1/25 1050 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 15 Roof Downblast - Exhaust Direct Drive G-080 • G-085 200 13⁄4 (44) 120 100 80 60 17 0.6 0.5 0.4 0.3 0.2 (432) 0.1 20 0 0.0 Damper Size = 10 x 10 (254 x 254) Roof Opening = 12½ x 12½ (318 x 318) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 19 lbs. (9 kg) 0 All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Direct Drive RPM Direct Motor HP Drive 085 -VG 0- VG 08 5-D 08 0- D 08 5-G 08 0- G 08 5-E 08 0- DO 40 RPM (Direct Drive) RPM (Vari Green) 3 Density 0.075 lb/ft Density 1.2 kg/m3 08 TO T 4 (102) 140 0.7 Static Pressure (in. wg) (371) Static Pressure (Pa) *145⁄8 HE L EFT OF T HIS S YSTE M 0.8 180 160 CURV E 0.9 220 NO TS ELE CT 213⁄4 (552) 100 E 200 300 400 500 600 Volume (cfm) 0 100 200 300 400 500 600 700 800 900 1000 3 Volume ( m /hr ) E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM 0 0.1 0.125 Static Pressure in Inches wg 0.15 0.2 0.25 0.3 0.375 0.5 0.625 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 335 0.01 3.8 415 0.02 5.4 495 0.04 7.3 551 0.05 9.1 268 0.02 3.7 361 0.03 5.4 450 0.04 7.3 511 0.06 9.1 249 0.02 3.6 348 0.03 5.4 439 0.04 7.3 501 0.06 9.1 230 0.02 3.7 333 0.03 5.4 427 0.05 7.3 490 0.06 9.1 189 0.02 3.9 303 0.03 5.4 404 0.05 7.3 469 0.06 9 134 0.02 4.2 272 0.03 5.5 379 0.05 7.2 449 0.07 8.9 239 0.03 5.6 354 0.05 7.3 426 0.07 8.9 174 0.03 5.9 314 0.06 7.3 392 0.07 8.9 237 0.06 7.6 332 0.08 9.1 260 0.08 9.4 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 398 0.01 4 493 0.02 5.5 588 0.04 7.6 654 0.05 9.5 326 0.02 3.9 436 0.03 5.3 541 0.04 7.4 612 0.06 9.4 307 0.02 3.9 420 0.03 5.3 528 0.05 7.4 602 0.06 9.4 286 0.02 3.9 405 0.03 5.3 515 0.05 7.4 590 0.06 9.3 240 0.02 4.1 375 0.03 5.3 490 0.05 7.4 567 0.07 9.3 179 0.02 4.3 340 0.04 5.3 464 0.05 7.4 544 0.07 9.3 302 0.04 5.4 439 0.06 7.4 521 0.07 9.3 233 0.04 5.5 394 0.06 7.4 486 0.08 9.3 308 0.06 7.6 419 0.08 9.4 168 0.06 8.1 340 0.09 9.4 Fan RPM 080 VG- E-1/40 1050 1/6 or 1/4 G-1/30 1300 D-1/20 1550 1725 085 VG- E-1/40 1050 1/6 or 1/4 G-1/30 1300 D-1/20 1550 1725 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 16 Roof Downblast - Exhaust Direct Drive G-090 • G-095 213⁄4 1.0 13⁄4 (44) 17 0.4 50 0.2 0 0.0 RPM RPM (Vari Green) 3 Density 0.075 lb/ft Density 1.2 kg/m3 095-VG 090 -VG 095D 090 -D 095G 0-G 09 095 09 -E 0E DO (432) 100 0.6 THE L E 4 (102) 150 NO T SE LECT TO (371) 0.8 Static Pressure (in. wg) *145⁄8 Static Pressure (Pa) 200 FT OF THIS S YSTEM CURVE (552) Damper Size = 10 x 10 (254 x 254) Roof Opening = 12½ x 12½ (318 x 318) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 22 lbs. (10 kg) 200 400 600 800 1000 1200 Volume (cfm) 0 500 1000 1500 2000 3 Volume ( m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Direct Motor HP Drive 0 E-1050-RPM G-1300-RPM D-1550-RPM VG-1725-RPM 0 0.1 0.125 Static Pressure in Inches wg 0.15 0.2 0.25 0.3 0.375 0.5 0.625 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 520 0.01 4 644 0.03 5.4 768 0.05 7.6 855 0.06 9.7 441 0.02 3.9 580 0.03 5.4 714 0.05 7.5 806 0.07 9.5 420 0.02 3.9 565 0.04 5.4 701 0.06 7.5 794 0.07 9.5 398 0.02 4 549 0.04 5.4 688 0.06 7.5 782 0.08 9.5 351 0.02 4.1 515 0.04 5.4 662 0.06 7.5 759 0.08 9.5 293 0.02 4.2 478 0.04 5.5 633 0.06 7.4 735 0.08 9.4 440 0.04 5.5 605 0.07 7.4 709 0.09 9.4 373 0.05 5.6 557 0.07 7.4 671 0.09 9.2 473 0.08 7.4 600 0.10 9.1 338 0.07 7.8 522 0.11 9.1 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 717 0.03 5.4 888 0.06 7.6 1059 0.10 9.6 1179 0.13 11.4 606 0.03 4.5 802 0.06 6.8 987 0.10 9.4 1114 0.14 11.4 570 0.04 4.5 780 0.06 6.7 969 0.10 9.3 1098 0.14 11.4 534 0.04 4.5 754 0.06 6.6 950 0.11 9.2 1081 0.14 11.5 468 0.04 4.4 695 0.07 6.5 912 0.11 9 1048 0.15 11.4 389 0.04 4.5 640 0.07 6.4 863 0.11 8.8 1013 0.15 11.2 290 0.03 4.6 586 0.07 6.4 814 0.11 8.7 969 0.15 11 493 0.07 6.4 745 0.12 8.7 903 0.16 10.9 184 0.05 6.8 623 0.12 8.7 800 0.16 11.3 474 0.11 8.7 688 0.16 11.3 Fan RPM 090 VG- E-1/40 1/6 or 1/4 1050 G-1/25 1300 D-1/15 1550 1725 095 VG- E-1/30 1/6 or 1/4 1050 G-1/12 1300 D-1/8 1550 1725 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 17 Roof Downblast Exhaust Belt & Direct Drive GB-071 • G-097 1.4 243⁄8 (619) HP 300 RPM (Belt) RPM (Direct) 8 1/ 097-A 1.2 RPM (Vari-Green) HP Density 0.075 lb/ft3 Density 1.2 kg/m3 Static Pressure (in. wg) 0.4 50 0.2 0 0.0 Motor HP Direct 071 097 Fan RPM CFM 720 BHP VG1/4 790 C-1/8 860 930 1000 1/6 or 1/8 1070 B-1/6 1140 1285 1435 1580 A-1/4 40 1725 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 0.125 157 0.01 1.8 172 0.01 2.3 187 0.02 2.8 203 0.02 3.3 218 0.03 3.9 233 0.03 4.6 248 0.04 5.3 280 0.06 6.8 313 0.08 8.0 344 0.10 9.5 376 0.13 11.3 107 0.01 2.0 128 0.01 2.3 148 0.02 2.7 166 0.02 3.4 184 0.03 4.0 202 0.03 4.7 220 0.04 5.4 255 0.06 6.7 292 0.08 8.0 324 0.10 9.5 356 0.13 11.2 86 0 720 0 50 100 150 250 200 300 350 400 Volume (cfm) 0 100 200 300 400 500 600 3 Volume (m /hr) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt 11 097-C Damper Size = 12 x 12 (305 x 305) Roof Opening = 14½ x 14½ (368 x 368) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 54/60 lbs. (24/27 kg) P 097-B 19 (483) 4H 1/ 25 17 100 0.6 35 13⁄4 (44) 150 0.8 14 43⁄8 (111) 200 HP (603) 1.0 1/6 *233⁄4 Static Pressure (Pa) 250 C-860-RPM 0.25 70 0.01 2.2 101 0.02 2.7 124 0.02 3.2 146 0.03 3.9 167 0.03 4.5 187 0.04 5.1 228 0.06 6.6 265 0.08 7.9 302 0.10 9.4 339 0.13 11.2 B-1140-RPM Static Pressure in Inches wg 0.375 0.5 0.625 0.75 A-1725-RPM 0.875 VG-1725-RPM 1 1.125 MAXIMUM BHP AT A GIVEN RPM = (RPM/3371)3 MAXIMUM RPM - GB-071=1710, G-097=1725 TIP SPEED (ft/min) = RPM x 2.929 MAXIMUM MOTOR FRAME SIZE = 56 100 0.02 3.6 130 0.03 4.2 152 0.04 4.9 197 0.05 6.3 240 0.08 7.6 281 0.10 9.1 316 0.13 10.8 109 0.03 4.7 166 0.05 6.0 212 0.08 7.3 255 0.10 8.8 297 0.13 10.5 127 0.05 5.9 185 0.07 7.1 230 0.10 8.5 273 0.13 10.2 151 0.07 6.9 205 0.10 8.3 250 0.13 9.9 177 0.09 8.1 227 0.13 9.7 140 0.09 7.9 205 0.12 9.5 171 0.12 9.3 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 18 Roof Downblast Exhaust Belt & Direct Drive GB-081 • G-098 243⁄8 RPM (Belt) RPM (Direct) (619) RPM (Vari-Green) HP 43⁄8 (111) YST EM CUR VE SE LE CT TO 13⁄4 (44) TH EL EF TO FT HIS S (603) Static Pressure (in. wg) *233⁄4 Static Pressure (Pa) Density 0.075 lb/ft3 Density 1.2 kg/m3 19 (483) DO NO T Damper Size = 12 x 12 (305 x 305) Roof Opening = 14½ x 14½ (368 x 368) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 54/60 lbs. (24/27 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt Motor HP Direct 081 098 Fan RPM CFM 720 BHP VG1/4 790 C-1/8 860 930 1000 1/6 1070 B-1/6 1140 1315 1490 1670 1/4 A-1/4 1725 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 0.125 361 0.01 3.0 396 0.02 3.5 431 0.02 4.0 466 0.03 4.6 501 0.03 5.3 536 0.04 5.9 571 0.05 6.6 659 0.08 8.3 746 0.11 10.1 836 0.16 12.0 864 0.17 12.7 272 0.01 2.7 315 0.02 3.2 358 0.02 3.7 399 0.03 4.4 439 0.04 5.1 478 0.04 5.8 517 0.05 6.5 612 0.08 8.1 706 0.12 9.9 800 0.16 11.9 829 0.18 12.5 C-860-RPM 0.25 181 0.02 3 261 0.02 3.4 323 0.03 4.0 372 0.04 4.7 416 0.05 5.4 460 0.06 6.1 564 0.08 7.8 663 0.12 9.8 763 0.16 11.7 793 0.18 12.3 B-1140-RPM Static Pressure in Inches wg 0.375 0.5 0.625 0.75 A-1725-RPM 0.875 VG-1725-RPM 1 1.125 MAXIMUM BHP AT A GIVEN RPM = (RPM/2985)3 MAXIMUM RPM - GB-081=1710, G-098=1725 TIP SPEED (ft/min) = RPM x 2.929 MAXIMUM MOTOR FRAME SIZE = 56 259 0.04 4.4 338 0.05 5.0 396 0.06 5.7 513 0.09 7.4 621 0.12 9.3 725 0.17 11.4 756 0.18 12.1 283 0.05 5.5 456 0.09 7.0 574 0.12 8.9 686 0.17 11.0 719 0.19 11.7 362 0.08 6.9 525 0.12 8.6 645 0.17 10.7 679 0.19 11.4 452 0.12 8.5 603 0.17 10.4 640 0.19 11.1 353 0.11 8.4 550 0.18 10.1 592 0.19 10.8 466 0.17 10.0 527 0.19 10.6 377 0.16 9.9 441 0.18 10.5 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 19 Roof Downblast Exhaust Belt & Direct Drive GB-091 • G-099 243⁄8 RPM (Belt) RPM (Direct) (619) RPM (Vari-Green) HP 13⁄4 (44) SYS TEM CUR VE LEF TO FT HIS 43⁄8 (111) Density 1.2 kg/m3 TO TH E (603) Static Pressure (in. wg) *233⁄4 Static Pressure (Pa) Density 0.075 lb/ft3 SE LE CT 19 O T (483) DO N Damper Size = 12 x 12 (305 x 305) Roof Opening = 14½ x 14½ (368 x 368) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 54/61 lbs. (24/28 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt Motor HP Direct 091 099 Fan RPM CFM 720 BHP VG1/4 790 C-1/8 860 930 1000 1/4 1070 B-1/6 1140 1285 1435 1580 A-1/4 1725 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 0 0.125 546 0.02 3.6 599 0.02 4.2 652 0.03 4.9 705 0.04 5.6 758 0.04 6.4 811 0.05 7.3 864 0.07 8.3 974 0.09 9.5 1087 0.13 10.7 1197 0.17 12.1 1307 0.23 13.6 403 0.02 3.5 471 0.02 4.1 536 0.03 4.7 598 0.04 5.5 659 0.05 6.2 718 0.06 7.1 777 0.07 8.1 897 0.10 9.4 1018 0.14 10.6 1135 0.18 12.0 1250 0.23 13.5 C-860-RPM 0.25 291 0.02 3.9 400 0.03 4.5 481 0.04 5.1 552 0.05 5.8 621 0.06 6.7 687 0.07 7.6 819 0.10 9.0 949 0.14 10.4 1072 0.19 11.9 1192 0.24 13.4 B-1140-RPM A-1725-RPM Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 VG-1725-RPM 1 1.125 MAXIMUM BHP AT A GIVEN RPM = (RPM/2703)3 MAXIMUM RPM - GB-091=1710, G-099=1725 TIP SPEED (ft/min) = RPM x 2.929 MAXIMUM MOTOR FRAME SIZE = 56 414 0.05 5.6 512 0.06 6.3 590 0.07 7.1 736 0.10 8.5 877 0.14 10.0 1009 0.19 11.5 1135 0.24 13.2 457 0.07 6.8 647 0.11 8.2 801 0.15 9.6 941 0.19 11.2 1076 0.25 12.9 526 0.10 7.9 721 0.15 9.3 872 0.20 10.9 1013 0.25 12.6 615 0.15 9.0 799 0.20 10.6 949 0.26 12.3 404 0.12 8.4 707 0.20 10.3 883 0.26 12.0 583 0.19 9.8 806 0.26 11.8 707 0.25 11.5 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 20 Roof Downblast Exhaust Belt & Direct Drive GB-101 • G-103 243⁄8 RPM (Belt) RPM (Direct) (619) RPM (Vari-Green) HP CUR VE SYS TEM SE LE CT 19 50 13⁄4 (44) 13 43⁄8 (111) TO TH EL EFT OF THI S (603) Static Pressure (in. wg) *233⁄4 Static Pressure (Pa) Density 0.075 lb/ft3 Density 1.2 kg/m3 O T (483) DO N Damper Size = 12 x 12 (305 x 305) Roof Opening = 14½ x 14½ (368 x 368) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 54/61 lbs. (24/28 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt Motor HP Direct 101 Fan RPM 0 0.125 610 0.02 3.8 729 0.03 4.6 848 0.05 5.5 966 0.07 6.6 1055 0.10 7.5 1144 0.12 8.5 1229 0.15 9.3 1318 0.19 10.2 1407 0.23 11.4 1462 0.25 12.2 1525 0.29 13.3 477 0.02 2.7 623 0.04 3.7 753 0.05 4.8 883 0.08 6.0 978 0.10 7.0 1073 0.13 8.1 1162 0.16 9.0 1255 0.19 10.0 1348 0.23 11.1 1405 0.26 11.9 1471 0.30 12.8 C-860-RPM 0.25 B-1140-RPM Static Pressure in Inches wg 0.375 0.5 0.625 0.75 A-1725-RPM 0.875 VG-1725-RPM 1 1.25 103 CFM 720 BHP VG1/4 C-1/8 860 1000 B-1/6 1/4 1140 1245 1350 1450 1555 1660 A-1/4 1725 1/3 1800 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 473 0.04 2.9 654 0.06 4.4 805 0.09 5.7 908 0.11 6.7 1006 0.13 7.8 1099 0.16 8.7 1196 0.20 9.7 1292 0.24 10.7 1351 0.27 11.5 1419 0.30 12.5 MAXIMUM BHP AT A GIVEN RPM = (RPM/2593)3 MAXIMUM RPM = 1800 TIP SPEED (ft/min) = RPM x 2.913 MAXIMUM MOTOR FRAME SIZE = 56 481 0.05 3.4 702 0.09 5.2 824 0.11 6.3 938 0.14 7.7 1041 0.17 8.4 1140 0.21 9.4 1238 0.25 10.4 1298 0.28 11.2 1368 0.31 12.4 507 0.08 4.1 715 0.11 5.7 851 0.14 7.2 965 0.17 8.0 1079 0.22 8.9 1187 0.26 10.1 1250 0.29 10.9 1321 0.33 12.2 731 0.14 6.7 878 0.17 7.5 1005 0.22 8.4 1122 0.26 9.6 1193 0.29 10.3 1270 0.33 11.4 750 0.17 6.9 917 0.22 8.0 1050 0.26 9.1 1126 0.29 10.0 1209 0.33 10.9 791 0.21 7.5 963 0.26 8.7 1052 0.29 9.5 1142 0.33 10.6 841 0.25 8.1 955 0.29 9.0 1065 0.33 10.2 793 0.30 9.3 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 21 Roof Downblast Exhaust Belt & Direct Drive GB-101HP • G-103HP 243⁄8 (619) RPM (Belt) RPM (Direct) RPM (Vari-Green) (603) 43⁄8 (111) 13⁄4 (44) URVE NO TS EL EC TT OT HE LEF TO F TH IS S YSTE MC Static Pressure (in. wg) Static Pressure (Pa) *233⁄4 HP Density 0.075 lb/ft3 Density 1.2 kg/m3 19 O (483) D Damper Size = 12 x 12 (305 x 305) Roof Opening = 14½ x 14½ (368 x 368) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 58/63 lbs. (26/29 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt Motor HP Direct 101HP Fan RPM 0 0.25 0.5 571 0.06 6.6 635 0.08 8.4 699 0.10 10.4 758 0.13 11.4 826 0.17 12.7 890 0.21 14.2 939 0.25 15.4 979 0.28 15.8 1026 0.33 16.4 1098 0.40 17.8 1120 0.43 18.2 477 0.06 5.7 553 0.09 7.5 626 0.11 9.5 692 0.14 10.7 767 0.18 12.2 836 0.23 13.6 889 0.26 14.8 931 0.30 15.4 981 0.34 16 1056 0.42 17.4 1078 0.44 17.9 342 0.07 5.3 449 0.09 7 537 0.12 9.1 613 0.15 10.6 697 0.19 11.9 772 0.24 13.3 830 0.28 14.4 875 0.31 14.8 928 0.36 15.4 1008 0.43 16.9 1032 0.46 17.4 VG-2550-RPM Static Pressure in Inches wg 0.75 1 1.25 1.5 1.75 2 2.25 103HP CFM 1300 BHP VG1/2 1445 1590 1/4 A-1/4 1725 1880 2025 2137 1/3 2229 2336 1/2 A-1725 RPM 2500 2550 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 243 0.08 6.3 417 0.12 8.3 521 0.16 10.1 618 0.20 12 702 0.24 13.2 765 0.28 14.2 814 0.32 14.5 871 0.36 14.9 956 0.45 16.7 982 0.47 17.2 MAXIMUM BHP AT A GIVEN RPM = (RPM/3165)3 MAXIMUM RPM = 2550 TIP SPEED (ft/min) = RPM x 2.978 MAXIMUM MOTOR FRAME SIZE = 56 364 0.15 10 518 0.20 11.4 622 0.26 12.6 693 0.29 13.4 748 0.33 14.1 809 0.37 14.7 901 0.45 15.8 928 0.47 16.3 337 0.18 11.9 515 0.25 12 607 0.30 13.1 674 0.35 13.7 742 0.39 14 840 0.46 15.5 869 0.49 16.1 313 0.22 11.4 474 0.28 12.1 574 0.33 13.2 661 0.40 14.1 775 0.48 14.8 807 0.51 15.1 406 0.31 12.0 543 0.37 13.5 695 0.48 15.2 735 0.52 15.6 358 0.34 13.6 583 0.46 15.7 639 0.50 16.2 416 0.42 16.6 497 0.47 17.2 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 22 Roof Downblast Exhaust Belt & Direct Drive GB-121 • G-123 243⁄8 (619) RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 43⁄8 (111) CU RV E TH E 13⁄4 (44) LE FT OF TH IS SY ST EM (603) Static Pressure (in. wg) *233⁄4 Static Pressure (Pa) Density 0.075 lb/ft3 Density 1.2 kg/m3 TO 19 (483) DO T NO CT LE SE Damper Size = 12 x 12 (305 x 305) Roof Opening = 14½ x 14½ (368 x 368) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 58/66 lbs. (26/30 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt Motor HP Direct 121 Fan RPM 0 0.125 704 0.02 3.2 873 0.03 4.2 1043 0.05 5.4 1213 0.08 6.7 1383 0.12 8.4 1535 0.16 10.2 1692 0.21 12.5 1789 0.25 13.5 1880 0.29 14.6 1983 0.34 15.9 2093 0.40 17.4 515 0.02 3.3 735 0.04 4.3 932 0.06 5.5 1119 0.09 6.8 1300 0.13 8.4 1460 0.17 10.1 1625 0.23 12.4 1726 0.27 13.4 1820 0.31 14.5 1926 0.36 15.8 2038 0.42 17.2 C-860-RPM 0.25 B-1140-RPM Static Pressure in Inches wg 0.375 0.5 0.625 0.75 A-1725-RPM 1 VG-1725-RPM 1.25 1.5 123 CFM 580 BHP VG1/2 720 C-1/8 1/4 860 1000 B-1/6 1140 1265 1395 1475 1/3 1550 1635 1/2 A-1/2 1725 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 523 0.04 4.1 796 0.06 5.2 1013 0.09 6.7 1213 0.14 8.4 1384 0.18 10.1 1557 0.24 12.3 1661 0.28 13.3 1759 0.32 14.3 1868 0.37 15.6 1984 0.44 17.0 MAXIMUM BHP AT A GIVEN RPM = (RPM/2170)3 MAXIMUM RPM = 1725 TIP SPEED (ft/min) = RPM x 3.420 MAXIMUM MOTOR FRAME SIZE = 56 580 0.06 5.2 883 0.10 6.4 1112 0.14 8.1 1299 0.19 9.9 1484 0.25 12.2 1594 0.29 13.2 1696 0.33 14.2 1810 0.39 15.4 1928 0.45 16.8 694 0.09 6.4 993 0.14 7.9 1204 0.19 9.7 1404 0.26 12.0 1521 0.30 13.0 1629 0.34 14.0 1747 0.40 15.3 1871 0.46 16.7 831 0.14 7.8 1093 0.20 9.6 1315 0.26 11.7 1441 0.31 12.7 1555 0.35 13.8 1680 0.41 15.0 1810 0.47 16.4 950 0.19 9.4 1214 0.26 11.5 1356 0.31 12.4 1475 0.36 13.5 1608 0.42 14.8 1743 0.48 16.2 907 0.24 11.3 1132 0.31 12.0 1289 0.36 12.9 1446 0.43 13.9 1600 0.50 15.5 974 0.33 12.4 1231 0.41 13.4 1426 0.50 14.9 1180 0.47 14.0 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 23 Roof Downblast - Exhaust Belt & Direct Drive GB-131 • G-133 283⁄8 (721) RPM (Belt) RPM (Direct) RPM (Vari-Green) 13⁄4 (44) CU RV E SY ST EM TH IS TH E 19 OF 4 (102) (483) DO NO T EC EL TS TO Damper Size = 12 x 12 (305 x 305) Roof Opening = 14½ x 14½ (368 x 368) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 62/67 lbs. (28/30 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt 131 Motor HP Direct Fan RPM 0 0.125 823 0.02 4.5 1022 0.04 5.4 1221 0.06 6.6 1419 0.10 8.1 1618 0.15 10.0 1774 0.19 12.0 1866 0.22 13.2 2044 0.29 15.0 2271 0.40 16.2 2391 0.47 16.9 2448 0.50 17.4 626 0.02 4.5 879 0.04 5.4 1106 0.07 6.5 1323 0.11 8.0 1535 0.16 9.8 1698 0.2 11.7 1794 0.23 12.8 1978 0.31 15.0 2212 0.42 16.0 2335 0.48 16.6 2393 0.52 17.0 C-860-RPM 0.25 B-1140-RPM A-1725-RPM Static Pressure in Inches wg 0.375 0.5 0.625 0.75 1 VG-1725-RPM 1.25 1.5 133 CFM 580 BHP VG3/4 720 C-1/8 1/4 860 1000 B-1/6 1140 1250 1315 1/3 1440 1600 1/2 1685 3/4 HP Density 0.075 lb/ft3 Density 1.2 kg/m3 LE FT (603) Static Pressure (in. wg) *233⁄4 Static Pressure (Pa) A A-1/2 1725 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 650 0.04 5.2 962 0.07 6.3 1213 0.11 7.7 1444 0.16 9.6 1617 0.21 11.3 1718 0.24 12.5 1911 0.32 15.1 2152 0.43 15.8 2279 0.50 16.3 2338 0.53 16.7 MAXIMUM BHP AT A GIVEN RPM = (RPM/2047)3 MAXIMUM RPM - GB-131=1725, G-133=1725 TIP SPEED (ft/min) = RPM x 3.436 MAXIMUM MOTOR FRAME SIZE = 56 727 0.07 6.0 1075 0.12 7.4 1340 0.17 9.2 1528 0.22 11.0 1637 0.25 12.1 1838 0.33 15.1 2088 0.44 15.6 2219 0.51 16.0 2281 0.55 16.3 867 0.11 7.0 1211 0.17 8.8 1426 0.23 10.5 1545 0.26 11.7 1759 0.34 14.5 2023 0.45 15.3 2158 0.52 15.7 2220 0.56 15.9 1031 0.17 8.5 1133 0.22 9.7 1435 0.26 11.2 1674 0.34 13.9 1873 0.47 14.6 2093 0.54 15.1 2159 0.57 15.6 1305 0.26 10.9 1571 0.35 13.4 1783 0.47 14.2 2020 0.55 14.8 2089 0.58 15.4 1299 0.34 12.5 1686 0.48 13.9 1857 0.56 14.5 1935 0.59 14.9 1425 0.47 13.2 1654 0.56 13.9 1746 0.60 14.3 1312 0.52 13.5 1474 0.58 13.8 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 24 Roof Downblast - Exhaust Belt & Direct Drive GB-141 • G-143 283⁄8 (721) RPM (Belt) RPM (Direct) RPM (Vari-Green) HP Density 0.075 lb/ft3 (603) 4 (102) 13⁄4 (44) 22 SE LE CT (559) TO Static Pressure (Pa) Static Pressure (in. wg) *233⁄4 TH EL EF TO FT HIS SY STE MC URV E Density 1.2 kg/m3 DO NO T Damper Size = 16 x 16 (406 x 406) Roof Opening = 18½ x 18½ (470 x 470) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 77/86 lbs. (35/39 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt 141 Motor HP Direct Fan RPM CFM VG3/4 1/4 720 C-1/8 860 950 1075 1/3 B-1/3 1140 1265 1/2 1360 1450 VG-1 1550 1 0.125 1076 0.04 4.7 1336 0.07 5.8 1595 0.12 7.1 1762 0.16 8.1 1994 0.24 10.0 2115 0.28 11.0 2347 0.39 12.9 2523 0.48 14.6 2690 0.58 16.2 2875 0.71 17.7 3200 0.98 20.0 855 0.04 4.7 1169 0.08 5.9 1457 0.13 7.0 1636 0.17 8.0 1882 0.25 9.9 2008 0.30 10.9 2250 0.40 12.7 2433 0.50 14.3 2606 0.60 15.9 2797 0.73 18.0 3129 1.00 21.0 0.25 Static Pressure in Inches wg 0.375 0.5 0.75 A-1725-RPM 1 1.25 VG-1725-RPM 1.5 1.75 143 580 BHP 3/4 0 B-1140-RPM C-860-RPM A-1 1725 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 938 0.08 5.2 1304 0.13 6.6 1506 0.18 7.6 1771 0.26 9.4 1905 0.31 10.4 2158 0.41 12.3 2347 0.51 13.9 2524 0.61 15.6 2719 0.74 17.4 3059 1.02 20.0 MAXIMUM BHP AT A GIVEN RPM = (RPM/1676)3 MAXIMUM RPM - GB-141=1725, G-143=1725 TIP SPEED (ft/min) = RPM x 3.829 MAXIMUM MOTOR FRAME SIZE = 145T 1085 0.13 6.1 1344 0.18 7.1 1647 0.26 8.9 1792 0.31 9.9 2062 0.42 11.9 2259 0.52 13.5 2443 0.63 15.2 2644 0.76 17.2 2991 1.03 19.9 1085 0.17 6.5 1490 0.26 8.4 1660 0.31 9.4 1955 0.42 11.4 2166 0.52 13.1 2358 0.63 14.7 2566 0.77 16.8 2923 1.05 19.6 1233 0.29 8.2 1677 0.42 10.4 1943 0.53 12.2 2165 0.64 13.8 2396 0.78 15.0 2782 1.07 18.5 1048 0.35 8.8 1602 0.51 11.0 1905 0.63 12.9 2191 0.79 14.8 2619 1.07 17.2 1501 0.59 11.7 1910 0.76 14.8 2427 1.09 17.0 1297 0.65 14.9 2184 1.06 16.8 1815 1.00 16.7 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 25 Roof Downblast - Exhaust Belt Drive Belt Drive Size-&: Direct GB • H-GB GB-141HP • G-143HP 283⁄8 (721) RPM (Belt) RPM (Direct) RPM (Vari-Green) HP Density 0.075 lb/ft3 Static Pressure (in. wg) Static Pressure (Pa) *233⁄4 (603) 4 (102) 13⁄4 (44) TO TH EL EFT OF THI SS YST EM CUR VE Density 1.2 kg/m3 00 SE LE CT 22 22 T (559) DO NO Damper Size = 16 x 16 Roof Opening = 18½ x 18½ (470 x 470) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 75/83 lbs. (34/38 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt Motor HP Direct 141HP Fan RPM .5 CFM VG3/4 B-1/4 1140 1320 1500 1/3 1655 A-1/2 1/2 1 A-1725-RPM Static Pressure in Inches wg 1.25 1.5 1.75 2 VG-2200-RPM 2.25 2.5 2.75 143HP 1020 BHP 1/4 .75 B-1140-RPM 1725 1812 1900 2050 3/4 2170 2200 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 488 0.08 6.3 645 0.11 7.7 837 0.17 10.3 1009 0.24 13.1 1151 0.32 15.0 1213 0.36 16.2 1289 0.41 17.8 1366 0.47 19.0 1495 0.58 21.0 1598 0.68 22.0 1623 0.71 23.0 413 0.11 7.6 700 0.18 9.8 903 0.26 12.3 1064 0.34 14.1 1132 0.38 15.4 1213 0.43 17.2 1294 0.49 18.4 1430 0.61 20.0 1536 0.71 22.0 1562 0.74 22.0 MAXIMUM BHP AT A GIVEN RPM = (RPM/2351)3 MAXIMUM RPM - GB-141HP=2200, G-143HP=2200 TIP SPEED (ft/min) = RPM x 3.829 MAXIMUM MOTOR FRAME SIZE = 145T 486 0.17 9.9 774 0.26 12.2 959 0.35 13.3 1035 0.39 14.7 1127 0.45 16.6 1218 0.51 18.0 1361 0.63 19.8 1472 0.73 21.0 1500 0.76 22.0 592 0.25 12.4 833 0.35 13.1 932 0.39 14.2 1030 0.46 15.8 1127 0.53 17.4 1285 0.65 19.3 1407 0.76 21.0 1436 0.78 22.0 668 0.34 13.6 784 0.39 14.3 911 0.45 15.6 1033 0.53 16.8 1200 0.66 18.8 1328 0.77 21.0 1360 0.80 21.0 588 0.37 14.9 763 0.45 15.9 901 0.52 16.7 1113 0.66 18.6 1248 0.78 21.0 1281 0.82 21.0 545 0.41 16.6 753 0.51 17.0 991 0.66 18.3 1163 0.79 21.0 1200 0.82 21.0 857 0.65 18.3 1045 0.78 20.0 1088 0.81 21.0 672 0.61 18.6 919 0.77 19.7 968 0.80 20.0 757 0.74 19.8 834 0.79 20.0 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 26 Roof Downblast - Exhaust Belt & Direct Drive GB-161 • G-163 283⁄8 2 163-A 600 HP 2.5 RPM (Belt) HP 1.5 (619) RPM (Direct) RPM (Vari-Green) HP P 1H TH EL EF TO FT HIS SY ST EM CU RV E TO SE LE CT NO T 75 50 Static Pressure (in. wg) 25 17 15 75 12 0 40 5 0 1000 2000 3000 4000 5000 Volume (cfm) 0 2000 4000 6000 8000 3 Volume (m /hr) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Fan RPM 0.0 11 94 86 DO 13 0 161 HP 0.5 100 Damper Size = 16 x 16 Roof Opening = 18½ x 18½ (470 x 470) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 101/88 lbs. (46/40 kg) Motor HP Direct 163-B 1.0 163-C (559) Belt HP 3/4 200 22 1.5 4 1/ 1 ⁄4 (44) 3 300 HP 1/3 4 (102) 400 P (603) 2.0 H 1/2 *233⁄4 Static Pressure (Pa) 500 Density 0.075 lb/ft3 Density 1.2 kg/m3 B-1140-RPM C-860-RPM 0 0.125 0.25 1713 0.07 5.8 2127 0.14 7.8 2540 0.23 10.5 2791 0.31 12.6 3249 0.48 15.3 3367 0.54 15.9 3545 0.63 17.0 3692 0.71 17.9 4062 0.95 21 4652 1.42 26 5095 1.87 30 1417 0.08 5.6 1893 0.15 7.5 2344 0.24 10.0 2612 0.32 12.0 3095 0.50 14.7 3219 0.56 15.4 3403 0.65 16.5 3557 0.73 17.4 3938 0.97 20 4545 1.45 25 4997 1.89 30 970 0.07 5.3 1632 0.15 7.2 2145 0.25 9.6 2434 0.33 11.5 2943 0.52 14.1 3072 0.57 14.9 3263 0.66 16.0 3422 0.75 17.0 3815 0.99 19.6 4437 1.47 25 4899 1.92 30 Static Pressure in Inches wg 0.375 0.5 0.75 0.875 A-1725-RPM 1 1.25 1.5 163 CFM 580 BHP VG-1 1/4 720 C-1/4 860 1/3 945 1/2 1100 B-1/2 1140 1200 3/4 1250 1 1375 VG-2 1 ⁄2 1575 1 A-2 1725 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1243 0.14 6.8 1913 0.26 9.3 2236 0.34 11.2 2787 0.53 13.8 2922 0.58 14.5 3123 0.68 15.6 3289 0.76 16.6 3694 1.01 19.2 4330 1.49 24 4800 1.94 29 MAXIMUM BHP AT A GIVEN RPM = (RPM/1355)3 MAXIMUM RPM - GB-161=1575, G-163=1725 TIP SPEED (ft/min) = RPM x 4.352 MAXIMUM MOTOR FRAME SIZE = 145T 1596 0.24 8.7 2010 0.34 10.7 2615 0.53 13.5 2761 0.59 14.2 2977 0.69 15.3 3149 0.77 16.3 3571 1.02 18.9 4225 1.51 24 4704 1.97 29 2198 0.52 12.5 2382 0.59 13.3 2641 0.69 14.6 2838 0.79 15.6 3304 1.04 18.4 4007 1.54 24 4510 2.01 28 1900 0.50 12.0 2125 0.57 12.9 2429 0.68 14.1 2658 0.78 15.2 3161 1.05 18.0 3894 1.56 23 4409 2.03 28 1808 0.54 12.1 2167 0.66 13.7 2444 0.76 14.9 3007 1.04 17.6 3769 1.56 23 4308 2.04 28 2609 1.01 17.2 3512 1.57 22 4082 2.06 27 2073 0.93 15.4 3198 1.54 22 3845 2.06 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 27 Exhaust Roof Downblast - Belt Drive Belt Drive Size: GB • H-GB GB-161HP 283⁄8 RPM (Belt) (721) HP Static Pressure (in. wg) Static Pressure (Pa) *233⁄4 (603) 4 (102) 13⁄4 (44) SE LE CT TO THE LEF TO F TH IS S YST EM C URV E Density 0.075 lb/ft3 Density 1.2 kg/m3 22 O NO T (559) D Damper Size = 16 x 16 (406 x 406) Roof Opening = 18½ x 18½ (470 x 470) Shroud Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 88 lbs. (40 kg) Volume (cfm) 3 Volume (m /hr) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0.5 0.625 0.75 Static Pressure in Inches wg 1 1.25 1.5 1.75 2 2.25 2.5 161HP 825 1/4 960 1095 1/3 1210 1270 1/2 1330 1390 1485 3/4 1580 1660 1 1740 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 702 0.11 6.5 1093 0.18 7.7 1380 0.26 9.0 1606 0.34 10.6 1718 0.39 11.4 1829 0.44 12.3 1938 0.50 13.3 2109 0.60 14.9 2275 0.72 16.7 2414 0.82 18.3 2551 0.94 20 919 0.17 7.6 1271 0.26 9.0 1514 0.35 10.3 1636 0.40 11.2 1753 0.45 12.1 1865 0.51 13.0 2041 0.61 14.7 2214 0.73 16.7 2357 0.84 18.8 2497 0.96 21 585 0.15 8.0 1139 0.26 8.9 1416 0.35 10.4 1545 0.40 11.1 1668 0.46 11.9 1789 0.52 12.8 1973 0.63 14.4 2150 0.75 16.4 2297 0.85 18.3 2442 0.97 21 MAXIMUM BHP AT A GIVEN RPM = (RPM/1708)3 MAXIMUM RPM = 1740 TIP SPEED (ft/min) = RPM x 4.352 MAXIMUM MOTOR FRAME SIZE = 145T 589 0.21 9.5 1149 0.34 10.3 1333 0.41 11.1 1483 0.47 12.1 1619 0.53 12.7 1822 0.64 13.8 2016 0.77 15.5 2175 0.89 16.7 2325 1.01 18.4 949 0.37 11.4 1204 0.45 12.0 1399 0.53 12.7 1654 0.65 13.7 1868 0.77 14.7 2037 0.89 16.2 2200 1.03 17.5 1032 0.48 13.1 1416 0.63 14.0 1704 0.791 14.8 1887 0.91 15.8 2066 1.03 17.2 1012 0.57 14.7 1447 0.75 15.4 1702 0.90 15.8 1917 1.05 16.8 1034 0.67 16.6 1441 0.86 17.1 1714 1.03 17.2 996 0.75 20 1452 0.98 19.2 987 0.85 28 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 28 Roof Downblast - Exhaust Belt & Direct Drive GB-180 • G-183 351⁄2 2.5 RPM (Belt) RPM (Direct) RPM (Vari-Green) HP 2 600 HP 1H HP 1.5 (902) P Density 0.075 lb/ft3 CU RVE TH EL EF TO FT HIS SY STE M 60 14 TO SE LE CT 55 NO T 35 85 10 DO 13 11 40 183-C 11 Static Pressure (in. wg) P HP HP 1.0 0.5 (762) H 3/4 183-B 3 1/ 30 Density 1.2 kg/m3 P 13⁄4 (44) 200 1.5 4 1/ 51⁄2 (140) 400 H 1/2 *28 (711) Static Pressure (Pa) 2.0 94 0 8 81 60 0 73 0 49 5 Damper Size = 18 x 18 (457 x 457) Roof Opening = 20½ x 20½ (521 x 521) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 108/142 lbs. (49/64 kg) 0 180 Motor HP Direct Fan RPM CFM 730 BHP VG-1 1/3 810 C-1/2 860 1/2 940 1000 3/4 1055 B-1 1140 VG-2 1185 11⁄2 1000 2000 3000 4000 5000 6000 0 2000 4000 6000 8000 10000 3 Volume (m /hr) Direct Drive RPM C-860-RPM 0 0.125 0.25 2839 0.21 7.4 3150 0.29 8.8 3344 0.35 10.1 3655 0.46 12.7 3888 0.55 15.2 4102 0.65 16.2 4433 0.81 17.9 4608 0.91 19.0 5191 1.31 22 5444 1.51 24 5677 1.71 26 2668 0.23 8.7 2997 0.31 9.9 3202 0.36 10.8 3527 0.47 12.8 3769 0.57 14.7 3990 0.67 15.7 4329 0.84 17.4 4508 0.94 18.4 5102 1.33 22 5359 1.54 23 5596 1.74 25 2469 0.25 7.2 2832 0.33 8.7 3049 0.39 9.8 3388 0.49 12.0 3638 0.58 13.7 3867 0.68 14.9 4216 0.85 16.8 4401 0.96 17.8 5010 1.36 21 5273 1.56 23 5514 1.77 24 B-1140-RPM Static Pressure in Inches wg 0.5 0.75 1 1.25 1.5 1.75 2 183 1/4 1 0 Volume (cfm) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Belt 0.0 1335 1400 2 1460 Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1882 0.25 6.7 2375 0.35 8.2 2647 0.42 9.1 3052 0.54 11.1 3339 0.64 13.0 3596 0.74 14.0 3980 0.93 16.0 4179 1.03 17.1 4814 1.41 21 5086 1.61 22 5336 1.81 24 MAXIMUM BHP AT A GIVEN RPM = (RPM/1149)3 MAXIMUM RPM = 1460 TIP SPEED (ft/min) = RPM x 4.843 MAXIMUM MOTOR FRAME SIZE = 184T 2015 0.4 8.1 2601 0.54 10.3 2953 0.66 11.9 3252 0.77 12.9 3684 0.96 15.1 3900 1.07 16.2 4599 1.49 19.9 4892 1.71 22 5155 1.93 23 2387 0.63 11.1 2811 0.77 12.4 3328 0.98 14.3 3575 1.1 15.4 4344 1.54 19.2 4655 1.75 21 4938 1.97 23 2856 0.95 13.6 3178 1.09 14.7 4052 1.57 18.7 4401 1.81 21 4699 2.03 22 2499 0.99 13.7 3713 1.56 18.2 4097 1.81 20 4426 2.05 22 3262 1.51 17.6 3747 1.79 19.7 4123 2.05 22 3253 1.71 19.2 3765 2.02 21 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 29 Roof Downblast - Exhaust Belt Drive GB-180HP 351⁄2 RPM (Belt) (902) HP Density 0.075 lb/ft3 13⁄4 (44) CU RVE SY ST EM FT HIS EF TO 51⁄2 (140) TH EL *28 (711) Static Pressure (in. wg) Static Pressure (Pa) Density 1.2 kg/m3 TO 30 LE CT (762) DO T NO SE Damper Size = 18 x 18 (457 x 457) Roof Opening = 20½ x 20½ (521 x 521) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 142 lbs. (64 kg) Volume (cfm) 3 Volume (m /hr ) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0.5 0.75 1 Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 2.5 2.75 180HP 795 1/4 845 1/3 935 1/2 1075 1150 3/4 1225 1 1350 1445 11⁄2 1540 1620 2 1700 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1547 0.22 8.6 1759 0.26 9.1 2114 0.35 10.3 2601 0.51 12.9 2847 0.61 14.6 3088 0.73 16.3 3485 0.96 19.5 3782 1.16 22 4076 1.39 25 4319 1.60 27 4560 1.84 30 MAXIMUM BHP AT A GIVEN RPM = (RPM/1325)3 MAXIMUM RPM = 1700 TIP SPEED (ft/min) = RPM x 4.843 MAXIMUM MOTOR FRAME SIZE = 184T 1686 0.35 9.6 2316 0.53 12.1 2607 0.64 13.1 2880 0.77 14.7 3296 1.00 17.6 3604 1.21 20 3909 1.44 22 4163 1.66 25 4414 1.90 27 1920 0.52 11.6 2298 0.65 12.6 2610 0.78 13.9 3095 1.04 16.4 3428 1.25 18.8 3744 1.49 21 4005 1.71 24 4263 1.96 26 1811 0.62 12.3 2277 0.78 13.3 2840 1.05 15.8 3213 1.28 17.8 3576 1.53 20 3848 1.76 23 4114 2.01 25 1711 0.72 13.2 2540 1.05 15.0 2969 1.29 17.3 3353 1.55 19.6 3663 1.79 22 3964 2.06 24 2059 0.99 15.1 2670 1.28 16.4 3119 1.56 18.9 3450 1.81 21 3764 2.08 23 2216 1.21 16.6 2827 1.55 18.1 3223 1.82 20 3560 2.10 22 2407 1.48 18.3 2923 1.80 19.7 3340 2.11 22 2512 1.72 19.8 3037 2.07 21 2642 1.99 21 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 30 Roof Downblast - Exhaust Belt & Direct Drive GB-200 • G-203 351⁄2 RPM (Belt) (902) RPM (Direct) HP Density 0.075 lb/ft3 CUR VE TO 13⁄4 (44) TH EL EF TO FT HIS SYS TEM 51⁄2 (140) Static Pressure (in. wg) *28 (711) Static Pressure (Pa) Density 1.2 kg/m3 SE LE CT 30 T (762) DO NO Damper Size = 18 x 18 (457 x 457) Roof Opening = 20½ x 20½ (521 x 521) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight G/GB = 119/144 lbs. (54/65 kg) Volume (cfm) 3 Volume (m /hr ) Direct Drive RPM All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Belt Direct 200 Fan RPM 0.125 2435 0.1 6.5 3320 0.25 8.5 3680 0.34 9.6 3973 0.43 10.8 4261 0.52 12.1 4759 0.73 14.1 5340 1.03 16.7 5689 1.25 18.5 6032 1.49 20 6308 1.7 22 6640 1.99 24 1976 0.1 5.8 2984 0.26 7.9 3378 0.34 9 3700 0.43 10 4013 0.53 11 4548 0.74 13.3 5158 1.04 16 5517 1.26 17.8 5870 1.5 19.6 6154 1.71 21 6494 2 23 0.25 Static Pressure in Inches wg 0.375 0.5 0.75 B-1140-RPM 1.0 1.25 1.5 1.75 203 440 1/4 600 1/3 665 718 1/2 770 3/4 0 C-860-RPM C-3/4 1 860 965 1028 11⁄2 1090 B-2 1140 2 1200 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2637 0.26 7.3 3085 0.35 8.5 3422 0.45 9.6 3744 0.55 10.7 4289 0.75 12.9 4927 1.05 15.4 5309 1.27 17.2 5682 1.51 18.9 5980 1.72 21 6336 2.01 23 2089 0.25 6.1 2706 0.35 7.7 3109 0.45 9 3477 0.55 10.2 4068 0.77 12.4 4720 1.08 15 5101 1.29 16.8 5473 1.52 18.4 5779 1.74 20 6145 2.02 22 MAXIMUM BHP AT A GIVEN RPM = (RPM/938)3 MAXIMUM RPM = 1200 TIP SPEED (ft/min) = RPM x 5.596 MAXIMUM MOTOR FRAME SIZE = 184T 2087 0.33 6.7 2684 0.44 8.3 3141 0.55 9.8 3811 0.77 11.8 4520 1.09 14.5 4918 1.31 16.4 5301 1.56 18.1 5606 1.77 19.7 5969 2.04 22 3085 0.74 11.1 4015 1.08 13.7 4488 1.32 15.6 4925 1.56 17.5 5267 1.79 19.1 5651 2.09 21 3240 1.02 13 3911 1.28 14.7 4450 1.56 16.8 4832 1.79 18.5 5274 2.09 21 2941 1.14 14.6 3751 1.48 15.8 4287 1.75 17.5 4829 2.08 19.9 3439 1.61 16.5 4177 1.99 18.6 3077 1.69 16.7 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 31 Roof Downblast - Exhaust Belt Drive GB-200HP 351⁄2 RPM (Belt) (902) HP Density 0.075 lb/ft3 13⁄4 (44) 30 URV E IS S YST EM C L EF TO F TH 51⁄2 (140) TO TH E *28 (711) Static Pressure (in. wg) Static Pressure (Pa) Density 1.2 kg/m3 N OT SE LE CT (762) DO Damper Size = 18 x 18 (457 x 457) Roof Opening = 20½ x 20½ (521 x 521) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 166 lbs. (75 kg) Volume (cfm) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0.5 0.75 1 1.25 Static Pressure in Inches wg 1.5 2 2.5 2.75 3 3.25 200HP 740 1/2 895 958 3/4 1020 1 1125 1205 1 ⁄2 1 1285 1350 2 1415 1520 3 1625 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1961 0.30 8.7 2809 0.52 11.4 3116 0.63 12.8 3409 0.75 14.1 3885 0.99 16.9 4229 1.19 18.8 4569 1.43 21 4843 1.65 23 5114 1.88 24 5550 2.31 27 5982 2.80 32 2331 0.53 10.9 2715 0.65 12.1 3050 0.77 13.6 3584 1.02 16.4 3967 1.24 17.9 4343 1.49 20 4638 1.71 22 4919 1.95 24 5368 2.38 27 5812 2.88 31 1424 0.45 10.3 2153 0.63 11.6 2602 0.78 13.1 3243 1.04 15.5 3663 1.27 17.2 4070 1.52 19.1 4384 1.75 21 4692 2.00 23 5182 2.45 27 5642 2.95 31 MAXIMUM BHP AT A GIVEN RPM = (RPM/1106)3 MAXIMUM RPM = 1625 TIP SPEED (ft/min) = RPM x 5.596 MAXIMUM MOTOR FRAME SIZE = 184T 1857 0.71 12.6 2804 1.04 15.3 3314 1.29 16.5 3770 1.55 18.1 4109 1.78 19.8 4442 2.04 22 4952 2.50 26 5448 3.02 29 2136 0.97 15.2 2884 1.27 16.4 3416 1.57 17.8 3811 1.81 19.3 4169 2.07 21 4713 2.53 24 5233 3.06 28 2278 1.40 18.9 2996 1.76 19.1 3492 2.07 19.7 4166 2.58 23 4767 3.13 27 2250 1.78 23 3458 2.53 22 4196 3.16 25 2850 2.38 22 3859 3.12 24 2046 2.06 22 3377 3.01 23 2725 2.76 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 32 Roof Downblast - Exhaust Belt Drive GB-220 423⁄4 (1086) RPM (Belt) HP 53⁄4 (146) 13⁄4 (44) YS TE MC UR VE (800) TH EL EF TO FT HIS S *311⁄2 Static Pressure (in. wg) Static Pressure (Pa) Density 0.075 lb/ft3 Density 1.2 kg/m3 LE CT TO 34 (864) DO NO T SE Damper Size = 24 x 24 (610 x 610) Roof Opening = 26½ x 26½ (673 x 673) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 164 lbs. (74 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 0.25 3230 0.14 7.4 3533 0.18 8.1 3799 0.23 8.8 4179 0.30 10.0 4863 0.48 13.0 5395 0.65 15.0 5737 0.79 15.7 6079 0.93 16.6 6444 1.11 17.8 6801 1.31 19.4 7485 1.74 23 2879 0.16 7.2 3219 0.20 7.8 3512 0.25 8.4 3924 0.32 9.6 4654 0.50 12.8 5206 0.68 14.9 5559 0.82 15.6 5911 0.97 16.4 6286 1.15 17.5 6651 1.34 19.1 7349 1.78 23 2296 0.16 6.9 2758 0.21 7.4 3132 0.26 7.9 3629 0.34 8.9 4403 0.53 12.1 4990 0.71 14.4 5362 0.84 15.2 5732 1.00 16.1 6122 1.18 17.2 6501 1.38 18.8 7212 1.82 23 Static Pressure in Inches wg 0.375 0.5 0.625 0.75 1 1.25 1.5 220 425 1/4 465 500 1/3 550 1/2 640 3/4 710 755 1 800 848 11⁄2 895 2 985 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 1951 0.19 7.0 2542 0.26 7.5 3158 0.35 8.4 4120 0.54 11.2 4762 0.73 13.6 5148 0.87 14.6 5530 1.02 15.6 5932 1.21 16.9 6323 1.41 18.5 7062 1.86 22 MAXIMUM BHP AT A GIVEN RPM = (RPM/782)3 MAXIMUM RPM = 985 TIP SPEED (ft/min) = RPM x 6.283 MAXIMUM MOTOR FRAME SIZE = 184T 2526 0.33 8.0 3702 0.55 10.5 4459 0.74 12.8 4920 0.89 14.0 5326 1.05 15.2 5741 1.23 16.5 6142 1.44 18.2 6898 1.89 22 3208 0.54 9.7 4077 0.75 12.1 4579 0.90 13.4 5049 1.06 14.6 5540 1.26 16.2 5960 1.47 18.0 6734 1.92 22 3633 0.74 11.2 4206 0.90 12.7 4716 1.07 14.2 5236 1.27 15.7 5723 1.49 17.6 6568 1.95 22 3095 0.82 11.2 3929 1.05 12.5 4566 1.27 14.5 5122 1.50 16.9 6107 1.99 21 3542 1.17 13.4 4401 1.47 15.5 5548 2.00 20 4883 1.96 19.0 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 33 Roof Downblast - Exhaust Belt Drive GB-220HP 423⁄4 (1086) YST EM CUR VE SE LE CT TO 13⁄4 (44) FT HIS S 53⁄4 (146) TH EL EF TO (800) Static Pressure (in. wg) *311⁄2 Static Pressure (Pa) RPM (Belt) HP Density 0.075 lb/ft3 Density 1.2 kg/m3 34 T (864) DO NO Damper Size = 24 x 24 (610 x 610) Roof Opening = 26½ x 26½ (673 x 673) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 186 lbs. (84 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0.5 0.625 0.75 2952 0.47 8.9 3215 0.53 9.4 3614 0.65 10.6 3973 0.77 12.0 4532 1.00 15.0 4975 1.22 16.7 5400 1.46 18.7 5740 1.68 21 6076 1.93 23 6422 2.20 24 7100 2.82 28 2555 0.46 8.5 2871 0.53 9.2 3312 0.65 10.3 3719 0.79 11.5 4317 1.02 13.8 4791 1.25 16.0 5245 1.50 18.2 5591 1.72 20 5935 1.97 22 6289 2.24 24 6981 2.87 27 1892 0.42 8.3 2440 0.52 8.9 2974 0.65 9.9 3424 0.79 11.1 4083 1.04 13.5 4590 1.27 15.3 5060 1.53 17.5 5432 1.76 19.4 5794 2.01 21 6154 2.29 23 6858 2.92 27 1 Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 2.5 220HP 650 1/2 680 728 3/4 775 1 850 913 11⁄2 975 1025 2 1075 1127 3 1230 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones MAXIMUM BHP AT A GIVEN RPM = (RPM/838)3 MAXIMUM RPM = 1230 TIP SPEED (ft/min) = RPM x 6.414 MAXIMUM MOTOR FRAME SIZE = 184T 2643 0.75 10.5 3536 1.03 12.7 4119 1.29 14.4 4660 1.57 16.3 5075 1.81 18.2 5459 2.06 20 5852 2.36 22 6611 3.01 27 2648 0.95 12.0 3545 1.27 13.5 4185 1.56 15.4 4643 1.82 17.1 5082 2.10 18.7 5520 2.41 21 6316 3.08 25 2557 1.13 13.0 3602 1.53 14.8 4157 1.804 16.4 4649 2.10 18.3 5124 2.42 20 6009 3.14 25 3492 1.74 15.6 4136 2.07 17.7 4703 2.41 19.3 5649 3.15 23 3346 1.93 16.4 4173 2.37 18.6 5263 3.14 22 3299 2.17 17.7 4812 3.10 22 4265 3.02 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 34 Roof Downblast - Exhaust Belt Drive GB-240 423⁄4 (1086) 13⁄4 (44) EFT OF THI S SY STE MC URV E 53⁄4 (146) TT OT HE L (800) Static Pressure (in. wg) *311⁄2 Static Pressure (Pa) RPM (Belt) HP Density 0.075 lb/ft3 Density 1.2 kg/m3 SE LE C 34 N OT (864) DO Damper Size = 24 x 24 (610 x 610) Roof Opening = 26½ x 26½ (673 x 673) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 165 lbs. (75 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 0.25 3902 0.19 5.9 4223 0.24 6.7 4637 0.32 7.8 5371 0.50 10.3 5720 0.60 11.7 6060 0.71 13.1 6702 0.96 15.8 7143 1.16 17.7 7575 1.39 19.7 7988 1.63 22 8355 1.86 24 3422 0.21 5.9 3785 0.26 6.6 4242 0.35 7.5 5031 0.53 9.7 5400 0.64 11.0 5757 0.75 12.4 6428 1.01 15.0 6886 1.21 16.6 7332 1.44 18.6 7757 1.68 21 8135 1.92 23 2691 0.20 4.7 3188 0.27 5.7 3761 0.35 6.9 4666 0.54 9.1 5069 0.65 10.4 5449 0.78 11.8 6158 1.05 14.3 6632 1.26 15.9 7092 1.49 17.7 7529 1.73 19.6 7916 1.97 21 Static Pressure in Inches wg 0.375 0.5 0.625 0.75 1 1.25 1.5 240 425 1/4 460 1/3 505 1/2 585 623 3/4 660 1 730 778 11⁄2 825 870 2 910 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2036 0.22 4.2 3060 0.34 6.1 4195 0.55 8.8 4660 0.66 10.0 5094 0.79 11.3 5861 1.05 13.8 6363 1.27 15.4 6844 1.51 17.2 7300 1.77 19.1 7700 2.02 21 MAXIMUM BHP AT A GIVEN RPM = (RPM/715)3 MAXIMUM RPM = 910 TIP SPEED (ft/min) = RPM x 6.414 MAXIMUM MOTOR FRAME SIZE = 184T 3562 0.53 8.2 4131 0.65 9.6 4636 0.78 11.0 5507 1.06 13.4 6058 1.28 15.0 6574 1.52 16.8 7055 1.78 18.7 7467 2.03 21 2112 0.41 7.2 3428 0.61 9.1 4073 0.76 10.6 5077 1.06 13.1 5700 1.29 14.7 6261 1.54 16.4 6775 1.80 18.3 7215 2.05 20 3217 0.69 10.4 4568 1.03 12.9 5266 1.28 14.4 5901 1.53 16.2 6457 1.80 17.9 6933 2.06 19.6 4145 1.18 13.2 5002 1.48 14.8 5680 1.77 16.9 6240 2.05 19.2 7757 1.68 21 5388 1.97 16.7 3707 1.66 13.6 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 35 Roof Downblast - Exhaust Belt Drive GB-240HP GB423⁄4 (1086) RPM (Belt) HP 53⁄4 (146) CU RVE TO 13⁄4 (44) HIS SY ST EM (800) TH EL EF TO FT Static Pressure (Pa) *311⁄2 Static Pressure (in. wg) Density 0.075 lb/ft3 Density 1.2 kg/m3 EL EC T 34 (864) DO NO T S Damper Size = 24 x 24 (610 x 610) Roof Opening = 26½ x 26½ (673 x 673) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 187 lbs. (85 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0.5 0.625 3035 0.42 8.0 3475 0.53 9.4 3877 0.64 11.0 4247 0.76 12.7 4860 0.99 15.9 5310 1.20 18.5 5751 1.43 22 6114 1.65 24 6474 1.89 27 6853 2.16 29 7610 2.80 31 2586 0.41 7.6 3147 0.53 8.8 3603 0.65 10.3 4005 0.77 11.9 4654 1.02 15.2 5118 1.23 17.4 5574 1.47 19.9 5948 1.69 23 6315 1.92 26 6702 2.20 27 7471 2.84 30 0.75 1 Static Pressure in Inches wg 1.25 1.5 1.75 2 2.25 2.5 240HP 635 1/2 685 733 3/4 780 1 860 920 1 ⁄2 1 980 1030 2 1080 1133 3 1240 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2693 0.51 8.4 3272 0.65 9.7 3740 0.78 11.3 4434 1.04 14.3 4925 1.25 16.6 5392 1.49 19.1 5776 1.72 21 6154 1.96 24 6550 2.24 26 7333 2.89 29 MAXIMUM BHP AT A GIVEN RPM = (RPM/845)3 MAXIMUM RPM = 1240 TIP SPEED (ft/min) = RPM x 6.414 MAXIMUM MOTOR FRAME SIZE = 184T 2964 0.75 10.3 3915 1.05 13.2 4496 1.29 15.0 5010 1.54 17.2 5428 1.77 19.6 5826 2.02 23 6237 2.31 24 7053 2.97 28 3105 0.99 12.2 3944 1.27 13.8 4562 1.55 15.6 5039 1.80 17.6 5468 2.06 20 5914 2.36 22 6767 3.04 27 3958 1.52 14.8 4560 1.80 16.3 5062 2.08 18.2 5560 2.40 21 6469 3.10 25 3896 1.73 15.7 4555 2.05 17.3 5133 2.39 19.3 6146 3.14 24 3763 1.93 16.7 4588 2.35 18.7 5775 3.14 23 5364 3.13 23 4776 3.04 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 36 Roof Downblast - Exhaust Belt Drive GB-260 50 (1270) RPM (Belt) HP Density 0.075 lb/ft3 Static Pressure (in. wg) Static Pressure (Pa) *36 (914) 81⁄4 (210) OT HE LEF TO F TH IS S YST EM C URV E Density 1.2 kg/m3 TS EL EC TT 13⁄4 (44) 40 NO (1016) DO Damper Size = 30 x 30 (762 x 762) Roof Opening = 32½ x 32½ (826 x 826) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.051 (1.3) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 305 lbs. (138 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 0.25 3875 0.12 8.0 4714 0.22 9.2 5231 0.30 10.4 6005 0.45 11.4 6716 0.63 12.9 7491 0.88 14.4 8588 1.33 16.7 9041 1.55 17.8 9493 1.79 18.9 10138 2.18 21 10784 2.62 23 3121 0.14 7.1 4130 0.25 8.8 4716 0.33 10.3 5570 0.50 10.9 6324 0.68 12.1 7137 0.93 13.7 8278 1.39 16.2 8746 1.61 17.4 9212 1.86 18.6 9875 2.26 20 10537 2.70 23 1727 0.12 7.4 3393 0.26 8.6 4095 0.35 10.3 5063 0.52 10.4 5898 0.72 11.3 6775 0.98 13.0 7979 1.44 15.8 8460 1.67 17.0 8938 1.92 18.3 9617 2.33 20 10292 2.78 22 0.5 Static Pressure in Inches wg 0.75 1 1.25 1.5 1.75 2 260 300 1/4 365 1/3 405 1/2 465 3/4 520 1 580 11⁄2 665 700 2 735 785 3 835 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones MAXIMUM BHP AT A GIVEN RPM = (RPM/572)3 MAXIMUM RPM = 835 TIP SPEED (ft/min) = RPM x 7.985 MAXIMUM MOTOR FRAME SIZE = 184T 3745 0.53 9.6 4869 0.75 10.3 5912 1.04 12.2 7274 1.53 15.0 7811 1.77 16.2 8335 2.03 17.6 9069 2.44 19.7 9794 2.91 22 3008 0.64 9.4 4826 1.03 11.0 6474 1.57 14.2 7068 1.82 15.5 7649 2.10 16.8 8452 2.53 18.9 9225 3.02 21 5465 1.55 13.3 6227 1.83 14.8 6878 2.13 16.2 7769 2.58 18.2 8606 3.08 20 3608 1.29 12.8 4912 1.71 13.8 5916 2.09 15.6 7006 2.59 17.9 7932 3.12 19.9 4236 1.80 14.9 5949 2.49 17.1 7157 3.10 19.7 4189 2.11 16.7 6024 2.93 18.7 4294 2.49 18.6 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 37 Roof Downblast - Exhaust Belt Drive GB-300 50 (1270) 13⁄4 (44) FT HIS SYS TEM TH EL EF TO 81⁄4 (210) SE LE CT TO Static Pressure (Pa) Static Pressure (in. wg) *36 (914) CUR VE RPM (Belt) HP Density 0.075 lb/ft3 Density 1.2 kg/m3 40 T (1016) DO NO Damper Size = 30 x 30 (762 x 762) Roof Opening = 32½ x 32½ (826 x 826) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.051 (1.3) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 320 lbs. (145 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 4859 0.18 9.3 5912 0.33 9.2 6803 0.50 9.6 7694 0.72 11.4 8585 1.00 13.4 9719 1.45 15.9 10772 1.97 18.8 11549 2.43 21 12311 2.94 23 13363 3.76 25 14416 4.73 28 3976 0.19 5.3 5222 0.35 6.2 6222 0.52 8.0 7197 0.75 10.6 8150 1.04 12.9 9334 1.49 15.4 10425 2.02 18.2 11226 2.48 20 12007 3.00 22 13084 3.82 25 14157 4.79 28 0.25 0.5 Static Pressure in Inches wg 0.75 1 1.25 1.5 1.75 2 300 300 1/3 365 1/2 420 3/4 475 1 530 11⁄2 600 2 665 713 3 760 825 5 890 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 4340 0.35 5.7 5537 0.53 7.0 6616 0.77 9.6 7640 1.06 12.2 8907 1.53 14.9 10060 2.06 17.7 10901 2.53 19.6 11704 3.05 21 12804 3.88 24 13898 4.85 28 MAXIMUM BHP AT A GIVEN RPM = (RPM/517)3 MAXIMUM RPM = 890 TIP SPEED (ft/min) = RPM x 7.985 MAXIMUM MOTOR FRAME SIZE = 184T 5095 0.74 8.1 6456 1.07 10.7 7952 1.55 13.8 9228 2.11 16.8 10129 2.59 18.9 10997 3.13 21 12175 3.97 24 13335 4.96 27 4195 0.91 9.4 6721 1.52 12.2 8269 2.11 15.7 9297 2.61 18.0 10242 3.16 19.8 11501 4.02 23 12716 5.03 26 7025 2.03 13.7 8283 2.57 16.4 9369 3.15 18.6 10770 4.05 22 12073 5.06 25 6691 2.38 13.7 8293 3.06 16.8 9909 4.01 20 11379 5.09 24 6437 2.76 14.0 8885 3.90 18.7 10536 5.02 22 7128 3.56 16.1 9568 4.89 21 7963 4.54 18.7 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 38 Roof Downblast - Exhaust Belt Drive GB-300HP 50 (1270) Static Pressure (Pa) 81⁄4 (210) 13⁄4 (44) Static Pressure (in. wg) *36 (914) TH EL EF TO FT HIS SY ST EM CU RVE RPM (Belt) HP Density 0.075 lb/ft3 Density 1.2 kg/m3 LE CT TO 40 (1016) N DO OT SE Damper Size = 30 x 30 (762 x 762) Roof Opening = 32½ x 32½ (826 x 826) Shroud Thickness = 0.064 (1.6) Motor Cover Thickness = 0.051 (1.3) Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 320 lbs. (145 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0.5 0.75 1 1.25 Static Pressure in Inches wg 1.5 1.75 2 2.25 2.5 2.75 300HP 460 1/2 495 3/4 565 1 620 11⁄2 710 748 2 785 840 3 895 980 5 1065 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 2912 0.41 9.7 3602 0.53 10.3 4662 0.77 11.8 5398 1.01 13.4 6542 1.48 17.2 7013 1.71 18.8 7460 1.96 20 8107 2.37 23 8746 2.84 25 9722 3.68 32 10688 4.67 44 MAXIMUM BHP AT A GIVEN RPM = (RPM/613)3 MAXIMUM RPM = 1065 TIP SPEED (ft/min) = RPM x 7.985 MAXIMUM MOTOR FRAME SIZE = 184T 3600 0.76 10.4 4652 1.04 12.3 5954 1.53 16.0 6462 1.78 17.5 6943 2.04 19.1 7642 2.46 22 8328 2.95 24 9356 3.81 31 10351 4.81 42 3309 0.94 10.6 5269 1.55 15.3 5889 1.81 17.0 6402 2.08 18.5 7146 2.52 21 7870 3.03 23 8951 3.90 29 10006 4.94 37 4221 1.47 13.4 5027 1.78 15.7 5737 2.10 17.9 6636 2.57 21 7394 3.07 23 8531 3.99 28 9621 5.04 37 4800 2.00 16.2 5922 2.56 19.7 6892 3.11 23 8094 4.03 27 9233 5.12 36 4992 2.43 18.0 6150 3.08 22 7657 4.08 26 8831 5.17 35 5245 2.92 19.8 7029 4.09 25 8429 5.23 33 6264 3.95 24 7903 5.24 31 5222 3.69 23 7255 5.17 30 6543 5.01 29 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 39 Roof Downblast - Exhaust Belt Drive GB-330 583⁄4 (1492) RPM (Belt) HP 87⁄8 (225) TO 13⁄4 (44) CU RVE (978) TH EL EF TO FT HIS SY STE M *381⁄2 Static Pressure (in. wg) Static Pressure (Pa) Density 0.075 lb/ft3 Density 1.2 kg/m3 EL EC T 46 (1168) DO T NO S Damper Size = 36 x 36 (914 x 914) Roof Opening = 38½ x 38½ (978 x 978) Shroud Thickness = 0.080 (2.0) Motor Cover Thickness = 0.064 (1.6) Curb Cap Thickness = 0.080 (2.0) ^Approximate Unit Weight = 385 lbs. (175 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 0.25 6159 0.22 5.2 6643 0.28 5.9 7850 0.46 8.5 8937 0.68 10.2 10024 0.95 12.6 11232 1.34 15.1 12319 1.77 17.7 13285 2.22 19.6 14251 2.74 22 15580 3.57 24 16908 4.57 28 5043 0.25 4.9 5633 0.31 5.5 7029 0.50 8.3 8232 0.73 9.8 9401 1.01 11.9 10683 1.40 14.6 11824 1.84 17.2 12828 2.29 19.2 13825 2.82 21 15190 3.66 24 16549 4.66 27 3236 0.22 4.8 4308 0.31 5.2 6036 0.52 7.4 7410 0.76 9.2 8713 1.06 11.3 10087 1.46 14.0 11294 1.91 16.6 12340 2.37 18.7 13376 2.90 21 14786 3.75 24 16185 4.761 27 Static Pressure in Inches wg 0.375 0.5 0.75 1 1.25 1.5 1.75 330 255 1/3 275 1/2 325 3/4 370 1 415 11⁄2 465 2 510 550 3 590 645 5 700 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones MAXIMUM BHP AT A GIVEN RPM = (RPM/405)3 MAXIMUM RPM = 700 TIP SPEED (ft/min) = RPM x 9.425 MAXIMUM MOTOR FRAME SIZE = 215T 4757 0.50 7.1 6480 0.76 8.4 7927 1.07 10.6 9425 1.50 13.4 10719 1.96 16.1 11822 2.43 18.2 12908 2.98 20 14366 3.84 23 15798 4.86 27 5257 0.72 8.3 7050 1.07 10.0 8706 1.51 12.8 10085 1.98 15.6 11266 2.47 17.7 12408 3.03 19.8 13922 3.91 23 15408 4.95 27 6966 1.46 11.7 8696 1.99 14.4 10041 2.51 16.7 11307 3.09 18.8 12958 4.00 22 14564 5.08 26 6472 1.79 13.9 8616 2.46 15.7 10081 3.08 17.7 11912 4.04 21 13624 5.14 25 8536 2.95 17.1 10749 4.01 20 12640 5.17 24 9292 3.85 19.4 11538 5.12 23 10184 4.94 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 40 Roof Downblast - Exhaust Belt Drive GB-360 583⁄4 (1492) RPM (Belt) HP SY ST EM TO 13⁄4 (44) LE FT OF TH IS 87⁄8 (225) TH E (978) Static Pressure (in. wg) Static Pressure (Pa) *381⁄2 CU RV E Density 0.075 lb/ft3 Density 1.2 kg/m3 EC T 46 (1168) DO NO T L SE Damper Size = 36 x 36 (914 x 914) Roof Opening = 38½ x 38½ (978 x 978) Shroud Thickness = 0.080 (2.0) Motor Cover Thickness = 0.064 (1.6) Curb Cap Thickness = 0.080 (2.0) ^Approximate Unit Weight = 415 lbs. (188 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 0.25 8024 0.40 7.6 8693 0.51 8.7 9763 0.72 10.8 10966 1.02 13.7 12304 1.45 15.9 12919 1.67 17.0 13507 1.91 18.1 14524 2.38 20 15513 2.90 22 16931 3.77 26 18322 4.77 30 7070 0.43 6.6 7830 0.54 7.7 9024 0.76 10.0 10330 1.07 13.3 11737 1.50 15.6 12379 1.73 16.7 12991 1.97 17.8 14043 2.44 19.8 15064 2.96 22 16519 3.84 25 17941 4.85 30 5804 0.44 5.6 6756 0.56 6.8 8109 0.79 8.9 9558 1.11 11.9 11085 1.55 14.8 11776 1.78 16.1 12431 2.02 17.3 13551 2.5 19.4 14614 3.03 22 16107 3.91 25 17560 4.93 29 Static Pressure in Inches wg 0.375 0.5 0.625 0.75 1 1.25 1.5 360 300 1/2 325 3/4 365 1 410 11⁄2 460 483 2 505 543 3 580 633 5 685 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 5001 0.51 5.6 7013 0.78 7.9 8686 1.12 10.9 10360 1.58 14.1 11109 1.82 15.5 11795 2.07 16.8 12959 2.55 18.9 14077 3.09 21 15654 3.98 24 17179 5.01 29 MAXIMUM BHP AT A GIVEN RPM = (RPM/394)3 MAXIMUM RPM = 685 TIP SPEED (ft/min) = RPM x 9.425 MAXIMUM MOTOR FRAME SIZE = 215T 7641 1.11 9.6 9568 1.59 13.1 10355 1.83 14.8 11096 2.09 16.5 12350 2.59 18.6 13523 3.14 21 15146 4.04 24 16711 5.07 28 8607 1.56 12.1 9517 1.83 13.7 10368 2.10 15.5 11679 2.60 17.8 12917 3.17 20 14639 4.10 23 16243 5.14 28 7096 1.46 10.9 8488 1.78 12.9 9473 2.07 14.7 10965 2.60 16.9 12289 3.18 19.1 14072 4.12 23 15774 5.20 26 8917 2.46 15.6 10813 3.13 17.6 12892 4.13 21 14710 5.23 24 11465 4.05 19.7 13535 5.21 23 12119 5.10 22 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 41 Roof Downblast - Exhaust Belt Drive GB-360HP 583⁄4 (1492) RPM (Belt) HP Density 0.075 lb/ft3 87⁄8 (225) TO 13⁄4 (44) TH EL EF TO FT HIS S (978) Static Pressure (in. wg) Static Pressure (Pa) *381⁄2 YST EM CUR VE Density 1.2 kg/m3 SE LE CT 46 T (1168) DO NO Damper Size = 36 x 36 (914 x 914) Roof Opening = 38½ x 38½ (978 x 978) Shroud Thickness = 0.080 (2.0) Motor Cover Thickness = 0.064 (1.6) Curb Cap Thickness = 0.080 (2.0) ^Approximate Unit Weight = 460 lbs. (209 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0.5 0.75 1 1.25 Static Pressure in Inches wg 1.5 1.75 2 2.25 2.5 2.75 360HP 420 1 435 11⁄2 500 525 2 550 590 3 630 690 5 750 803 71⁄2 855 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 6097 0.91 10.4 6576 1.02 10.8 8432 1.56 13.4 9061 1.79 14.7 9681 2.05 16.0 10657 2.50 18.0 11616 3.01 20 13062 3.93 24 14487 5.02 27 15728 6.13 31 16918 7.37 35 MAXIMUM BHP AT A GIVEN RPM = (RPM/431)3 MAXIMUM RPM = 855 TIP SPEED (ft/min) = RPM x 9.425 MAXIMUM MOTOR FRAME SIZE = 215T 7000 1.53 12.5 7808 1.78 13.6 8589 2.06 14.8 9719 2.57 16.3 10772 3.11 18.6 12259 4.02 22 13711 5.10 25 14985 6.22 30 16236 7.47 33 5650 1.61 12.7 6998 1.98 14.2 8495 2.52 15.7 9767 3.10 17.6 11464 4.11 21 13002 5.22 24 14309 6.33 28 15568 7.58 33 6528 2.32 14.9 8525 3.04 16.9 10468 4.05 20 12220 5.26 24 13647 6.46 27 14946 7.71 31 6006 2.63 15.7 9335 3.99 19.2 11282 5.20 23 12863 6.44 26 14315 7.82 29 7159 3.60 18.1 10239 5.13 22 11960 6.37 25 13544 7.76 29 8513 4.83 21 10986 6.30 24 12676 7.69 27 9445 6.01 23 11761 7.61 27 10368 7.32 26 8273 6.63 25 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 42 Roof Downblast - Exhaust Belt Drive GB-420 651⁄4 (1657) RPM (Belt) HP Density 0.075 lb/ft3 CU RV E TH E 13⁄4 (44) OF TH IS SY ST EM Static Pressure (Pa) 93⁄4 (248) LE FT *44 (1118) Static Pressure (in. wg) Density 1.2 kg/m3 O 52 (1321) DO NO T CT LE SE T Damper Size = 42 x 42 (1067 x 1067) Roof Opening = 44½ x 44½ (1130 x 1130) Shroud Thickness = 0.080 (2.0) Motor Cover Thickness = 0.064 (1.6) Curb Cap Thickness = 0.100 (2.5) ^Approximate Unit Weight = 495 lbs. (225 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 8242 0.27 3.1 9890 0.46 4.6 11332 0.69 6.2 12568 0.95 8.0 14217 1.37 11.7 15659 1.83 14.4 17925 2.74 19.0 19574 3.57 22 21222 4.55 24 22994 5.79 27 24725 7.20 30 6454 0.29 2.9 8573 0.50 5.0 10219 0.75 6.8 11579 1.01 8.4 13357 1.45 11.3 14892 1.92 13.8 17264 2.86 18.4 18968 3.69 21 20663 4.68 24 22478 5.93 27 24245 7.35 30 0.25 Static Pressure in Inches wg 0.375 0.50 0.625 0.75 1.00 1.25 1.5 420 200 1/2 240 3/4 275 1 305 11⁄2 345 2 380 3 435 475 5 515 558 7 ⁄2 1 600 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 6365 0.48 4.9 8698 0.76 5.6 10320 1.03 7.5 12411 1.49 10.8 14043 1.97 13.3 16540 2.93 17.8 18320 3.78 20 20081 4.80 23 21957 6.07 26 23765 7.51 30 MAXIMUM BHP AT A GIVEN RPM = (RPM/302)3 MAXIMUM RPM = 600 TIP SPEED (ft/min) = RPM x 11.061 MAXIMUM MOTOR FRAME SIZE = 215T 8672 1.01 7.2 11102 1.50 10.1 12983 2.00 12.7 15792 2.97 17.3 17640 3.84 19.8 19459 4.87 22 21383 6.15 25 23243 7.61 29 9463 1.45 9.6 11787 2.00 12.3 14790 2.99 16.6 16887 3.88 19.3 18826 4.92 21 20805 6.22 24 22709 7.70 27 10108 1.91 12.0 13764 3.00 16.4 15929 3.90 18.6 18046 4.95 21 20219 6.28 24 22166 7.76 27 12502 2.95 16.5 14994 3.91 18.3 17162 4.98 20 19446 6.31 23 21621 7.81 26 12315 3.69 18.3 15254 4.92 19.4 17835 6.34 23 20104 7.87 26 12312 4.56 19.1 15908 6.21 22 18585 7.86 26 16590 7.64 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 43 Roof Downblast - Exhaust Belt Drive GB-480 GB733⁄4 (1873) RPM (Belt) 111⁄4 (286) CU RV E TH E 13⁄4 (44) LE FT OF TH IS SY ST EM Static Pressure (Pa) *471⁄4 (1200) Static Pressure (in. wg) HP Density 0.075 lb/ft3 Density 1.2 kg/m3 T TO 58 (1473) DO N OT C LE SE Damper Size = 48 x 48 (1219 x 1219) Roof Opening = 50½ x 50½ (1283 x 1283) Shroud Thickness = 0.080 (2.0) Motor Cover Thickness = 0.064 (1.6) Curb Cap Thickness = 0.100 (2.5) ^Approximate Unit Weight = 623 lbs. (283 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 0.25 12020 0.51 7.3 13522 0.73 8.3 15025 1.00 9.5 17129 1.48 11.8 18631 1.90 14.0 21636 2.98 17.6 23619 3.87 20 24942 4.56 22 25542 4.90 23 27345 6.01 27 29149 7.28 31 10059 0.55 6.6 11811 0.77 8.0 13516 1.05 9.5 15830 1.54 11.2 17437 1.97 13.0 20608 3.06 17.0 22678 3.66 19.9 24050 4.65 22 24672 4.99 23 26532 6.11 27 28386 7.39 31 6529 0.48 7.3 9500 0.76 7.6 11662 1.06 8.6 14379 1.58 10.7 16135 2.02 12.2 19548 3.13 16.4 21736 4.05 19.5 23158 4.75 22 23801 5.09 23 25719 6.22 27 27623 7.50 31 Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 1 1.25 480 1/2 200 3/4 225 1 250 11⁄2 285 2 310 3 360 393 5 415 425 455 71⁄2 485 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones MAXIMUM BHP AT A GIVEN RPM = (RPM/245)3 MAXIMUM RPM = 485 TIP SPEED (ft/min) = RPM x 12.632 MAXIMUM MOTOR FRAME SIZE = 215T 8820 0.98 8.1 12517 1.56 10.0 14589 2.02 12.0 18385 3.17 15.9 20683 4.10 18.8 22189 4.81 21 22868 5.16 22 24886 6.31 26 26860 7.61 31 9587 1.42 9.1 12656 1.97 11.5 17010 3.17 15.5 19605 4.14 18.3 21181 4.85 21 21883 5.20 22 23966 6.36 26 26016 7.67 30 15420 3.21 15.0 18254 4.12 18.0 20012 4.86 20 20799 5.22 21 23046 6.41 25 25153 7.72 29 13507 3.00 14.2 16764 4.06 17.5 18733 4.84 20 19550 5.20 21 21953 6.41 25 24290 7.78 29 15086 3.94 16.7 17211 4.74 19.1 18156 5.13 20 20786 6.38 24 23201 7.75 28 15486 4.58 18.1 16604 5.00 19.3 19471 6.30 24 22106 7.73 28 15870 5.85 21 19517 7.49 26 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 44 Roof Downblast - Exhaust Belt Drive GB-500 83 (2108) RPM (Belt) HP Density 0.075 lb/ft3 CU RV E EM TH IS SY ST OF TH E 13⁄4 (44) LE FT 141⁄2 (368) Static Pressure (in. wg) *503⁄4 (1289) Static Pressure (Pa) Density 1.2 kg/m3 O 64 (1626) DO NO T EC EL S T T Damper Size = 54 x 54 (1371 x 1371) Roof Opening = 56½ x 56½ (1435 x 1435) Shroud Thickness = 0.100 (2.5) Motor Cover Thickness = 0.064 (1.6) Curb Cap Thickness = 0.100 (2.5) ^Approximate Unit Weight = 687 lbs. (312 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 14102 0.50 6.7 16117 0.75 8.4 17245 0.92 9.5 19743 1.38 11.9 21677 1.83 14.0 24820 2.74 17.7 27157 3.59 19.9 29494 4.60 22 33764 6.90 27 35457 8.00 30 37068 9.14 32 11123 0.57 6.5 13588 0.85 8.0 14939 1.04 9.1 17749 1.54 11.5 19873 2.02 13.8 23263 3.00 17.4 25739 3.89 19.5 28188 4.92 22 32624 7.27 27 34371 8.38 29 36030 9.54 32 0.25 Static Pressure in Inches wg 0.375 0.5 0.625 0.75 0.875 1 1.25 500 175 1 200 214 11⁄2 245 2 269 3 308 337 5 366 71⁄2 419 440 10 460 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 10593 0.83 7.7 12242 1.04 8.7 15481 1.57 11.0 17857 2.06 13.2 21627 3.09 16.9 24253 4.01 19.1 26834 5.10 21 31467 7.57 27 33279 8.74 29 34991 9.94 32 MAXIMUM BHP AT A GIVEN RPM = (RPM/210)3 MAXIMUM RPM = 460 TIP SPEED (ft/min) = RPM x 14.137 MAXIMUM MOTOR FRAME SIZE = 256T 12983 1.53 10.7 15752 2.08 12.7 19752 3.11 16.2 22614 4.06 18.5 25429 5.20 21 30265 7.70 26 32134 8.87 29 33900 10.10 32 17903 3.11 15.8 20937 4.08 17.9 23831 5.20 20 29015 7.80 26 30989 9.01 29 32805 10.24 32 15284 2.96 15.6 19206 4.06 17.6 22310 5.24 19.8 27607 7.80 25 29679 9.03 28 31625 10.32 31 16671 3.88 17.4 20688 5.19 19.5 26276 7.84 24 28373 9.05 27 30342 10.32 30 18366 4.99 19.4 24940 7.88 24 27107 9.10 26 29127 10.36 29 23486 7.78 23 25801 9.09 26 27917 10.41 28 22407 8.73 25 25310 10.26 27 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 45 Roof Downblast - Exhaust Belt Drive GB-540 GB83 (2108) RPM (Belt) CU RV E LE FT 141⁄2 (368) OF TH IS SY ST EM *503⁄4 (1289) Static Pressure (in. wg) Static Pressure (Pa) HP Density 0.075 lb/ft3 Density 1.2 kg/m3 TH E 13⁄4 (44) O 64 (1626) DO NO T EC EL TS T Damper Size = 54 x 54 (1371 x 1371) Roof Opening = 56½ x 56½ (1435 x 1435) Shroud Thickness = 0.100 (2.5) Motor Cover Thickness = 0.064 (1.6) Curb Cap Thickness = 0.100 (2.5) ^Approximate Unit Weight = 748 lbs. (339 kg) Volume (cfm x 1000) 3 Volume (m /hr x 1000) All dimensions in inches (millimeters). *May be greater depending on motor. ^Weight shown is largest cataloged Open Drip-Proof motor. Motor HP Fan RPM 0 0.125 15488 0.61 6.9 17258 0.85 7.8 18143 0.99 8.3 20798 1.49 10.1 22922 1.99 12.3 26197 2.97 16.2 31064 4.96 21 35578 7.45 27 39118 9.90 32 41950 12.21 36 44694 14.77 40 1250 0.65 6.3 14674 0.90 7.5 15724 1.04 8.2 18814 1.57 10.4 21228 2.09 12.1 24874 3.11 15.6 30005 5.13 21 34653 7.65 26 38277 10.12 32 41165 12.45 36 43957 15.02 40 0.25 Static Pressure in Inches wg 0.375 0.5 0.75 1 1.25 1.5 1.75 540 175 1 195 205 11⁄2 235 2 259 3 296 5 351 71⁄2 402 10 442 474 15 505 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones 11068 0.87 7.2 12632 1.03 8.1 16229 1.56 10.5 18963 2.11 11.9 22870 3.14 15.3 28492 5.21 19.9 33552 7.80 26 37435 10.34 32 40381 12.68 37 43221 15.27 40 MAXIMUM BHP AT A GIVEN RPM = (RPM/202)3 MAXIMUM RPM = 505 TIP SPEED (ft/min) = RPM x 14.137 MAXIMUM MOTOR FRAME SIZE = 256T 12673 1.50 10.6 16439 2.08 11.6 20831 3.13 15.0 26810 5.24 19.3 32075 7.84 25 36109 10.39 32 39287 12.80 36 42332 15.45 40 18610 3.10 14.3 25115 5.23 18.7 30612 7.87 24 34766 10.44 32 38034 12.85 35 41157 15.51 39 21376 5.15 17.4 27519 7.82 23 32131 10.46 28 35558 12.90 33 38813 15.60 38 24274 7.73 21 29134 10.36 27 32927 12.84 31 36503 15.60 36 26111 10.24 26 30151 12.73 30 33869 15.48 35 26271 12.42 28 31293 15.36 32 26758 14.84 30 Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings include the effects of a birdscreen. The sound ratings shown are loudness values in hemispherical sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. 46 Specifications Vari-Green® Vari-Green Control – Indoor Air Quality – Temperature / Humidity Control to be a packaged indoor air quality control designed to regulate fan speed based on level of temperature and/or relative humidity in a space. Control shall include a Proportional Integral Derivative (PID) feedback loop and shall have labeled terminal strips for easy wiring. Fan shall be direct drive including an electronic commutation (EC) Vari-Green Motor. Control package shall be Vari-Green Indoor Air Quality – Temperature / Humidity Control. Vari-Green® Motor Motor to be an electronic commutation (EC) motor specifically designed for fan applications. AC induction type motors are not acceptable. Examples of unacceptable motors are: Shaded Pole, Permanent Split Capacitor (PSC), Split Phase, Capacitor Start and 3 phase induction type motors. Motors shall be permanently lubricated with heavy-duty ball bearings to match the fan load and prewired to the specific voltage and phase. Internal motor circuitry shall convert AC power supplied to the fan to DC power to operate the motor. Motor shall be speed controllable down to 20% of full speed (80% turndown). Speed shall be controlled by either a potentiometer dial mounted on the motor or by a 0-10 VDC signal. Motor shall be a minimum of 85% efficient at all speeds. Vari-Green® Control - Remote Dial Remote Dial shall be a Vari-Green Control specifically designed to provide 0-10 volt DC signal to Greenheck’s Vari-Green Motor. Vari-Green Control - Two Speed Two speed control shall be a Vari-Green Control specifically designed to allow the Vari-Green Motor to operate at two discrete speeds. Two speed control shall include two dials that may be set at any point between 0 and 10 volts DC and an integral transformer capable of reducing 115/208-240 volt AC power to 24 volt AC power. Vari-Green Control – Indoor Air Quality – VOC (Volatile Organic Compound) Control to be a packaged indoor air quality control designed to regulate fan speed based on level of VOC concentration in a space. Control shall include a Proportional Integral Derivative (PID) feedback loop and shall have labeled terminal strips for easy wiring. Fan shall be direct drive including an electronic commutation (EC) Vari-Green Motor. Control package shall be Vari-Green Indoor Air Quality – VOC Control. Vari-Green Control – Constant Pressure Control to be a packaged constant pressure control designed to regulate fan speed based on demand. Control shall include a Proportional Integral Derivative (PID) feedback loop and shall have all components prewired to labeled terminal strips for easy wiring. System shall include the appropriate pressure tap and preset pressure transducer. Fan shall be direct drive including an electronic commutation (EC) Vari-Green Motor. Control package shall be Vari-Green Constant Pressure Control. Indoor installations shall include pressure tap (duct or room) and control box with integral pressure transducer. Outdoor installations shall include duct pressure tap, pressure transducer, and control box. Control box shall be prewired and in a NEMA-3R weather tight enclosure for mounting outdoors near the fan location. LEED information Greenheck became one of the first manufacturers in the Air Movement and Control industry to join the LEED/green movement when they joined the United States Green Building Council (USGBC) in 2005. Greenheck has been actively researching qualification requirements for our products to meet LEED credits and prerequisites. The Vari-Green® motor significantly helps qualification efforts for the Energy and Atmosphere credits and prerequisites; specifically credit one, Optimize Energy Performance and prerequisite two, Minimum Energy Performance. 47 Direct Drive Specifications Model G For models G-060 through G-095, the fan shall have sleeve bearing motors, carefully matched to the fan load, and furnished at specified voltage, phase and enclosure. For models G-097 through G-203, motors shall be heavy-duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Models G-060 through G-095 have three-speed motors as standard. Motors shall be mounted on true vibration isolators, out of the airstream. Fresh air for motor cooling shall be drawn into the motor compartment from an area free of discharge contaminants. Motors shall be readily accessible for maintenance. True vibration isolators shall be double-studded with no metal-to-metal contact. Each vibration isolator shall be sized to match the weight of each fan. Spun aluminum downblast exhaust fans shall be direct drive type. These fans are specifically designed for roof mounted applications exhausting relatively clean air. Performance capabilities range up to 6,308 cfm (11,281 m3/hr) and 1.75 in. wg (249 Pa) of static pressure. The maximum continuous operating temperature shall be 180°F (82°C). Model G fans are available in 20 sizes with nominal wheel diameters ranging from 7 to 20 inches (178 to 457 mm) (060-203 unit sizes). Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number. All fans shall bear the AMCA Sound and Air Performance seal. The fan wheel shall be centrifugal non-overloading backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced in accordance to AMCA Standard 204-05. 48 The fan housing shall consist of the motor cover, shroud, curb cap and lower windband, and shall be constructed of heavy-gauge aluminum. The housing shall have a rigid internal support structure and leakproof design. The fan shroud shall be one piece with a rolled bead for extra strength which directs exhaust air downward. The lower windband shall be one piece with formed edges for added strength and the curb cap shall include prepunched mounting holes to ensure correct attachment. A disconnect switch is a positive electrical shutoff and shall be wired from the fan motor to a junction box installed within the motor compartment. Factory standard shall be a NEMA-1 disconnect switch with other NEMA rated options also available. Disconnect switches shall be factory mounted and/or shipped loose for field mounting. Options and accessories shall include: curb extension, curb seal, dampers, finishes, hinge kit, hinge base, pressure probe, roof curbs, and tie-down points. Fans shall be model G as manufactured by Greenheck Fan Corporation of Schofield, Wisconsin, USA. Direct Drive, Severe Duty Specifications Model G Seismic Specifications Fans shall meet International Building Code (IBC) 2009, 2012 and the California Office of Statewide Health Planning and Development (OSHPD) requirements for seismic certifications as listed. • All Greenheck seismically certified models shall be tested to the most severe seismic event on the Spectral Response Map per IBC Figures 1613.5 (1-2). Testing shall be performed under the worst case scenario, using the highest mapped seismic load, highest level occupancy category, worst case site class, and highest code mandated importance factor. • Fans shall be shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected to the same or greater forces as experienced during a seismic event. High Wind Specifications Fans shall meet all Greenheck wind-load standards and shall contain the following third-party certifications: • Miami-Dade NOA# 12-0120.13 • Licensed P.E. calculations shall be available for fan per ASCE 7-05 Minimum Design Loads for Buildings and Other Structures for exposure Class C, 60 foot building height, and a type II building. • Fan shall be tested in accordance with ASTM E-330-02 Structural Performance of Exterior Windows, Doors, Skylights, and Curtain Walls by Uniform Static Air Pressure Difference and Florida Building Code Test Protocol TAS-201, 202 and 203 at the ASCE 7-05 calculated design load. • For applications which are not covered by California OSHPD standards, Greenheck seismic models G shall be certified by a third party engineering firm to IBC 2009, 2012 and ASCE 7-05 standards. • Greenheck seismic model G has been certified to IBC 2009, 2012, ASCE 7-05 and California OSHPD standards through engineering calculations and shake table testing of all models by independent third party engineering firms. Fans shall be Greenheck model G, as specified on page 48, with seismic rated construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. • Licensed P.E. calculations for attachment of fan to curb shall be available for ASCE 7-05 determined design pressure. • All calculations and testing shall be done by a state licensed P.E., and a certified test lab. Fans shall be Greenheck model G, as specified on page 48, with high wind-resistant construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. 49 Belt Drive Specifications Model GB Fan shafts shall be precision ground and polished solid steel with an anti-corrosive coating. Fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. The first critical speed on a fan shaft shall be at least 25 percent over maximum operating speed. Bearings shall be selected for a minimum L10 life in excess of 100,000 hours (L 50 life of 500,000 hours) at maximum cataloged operating speed. All bearings are 100 percent factory tested. Spun aluminum downblast exhaust fans shall be belt drive type. These fans are specifically designed for roof mounted applications exhausting relatively clean air. Performance capabilities range up to 44,700 cfm (75,946 m3/hr) and 3.25 in. wg (809 Pa) of static pressure. The maximum continuous operating temperature shall be 180°F (82°C). Model GB fans are available in twenty sizes with nominal wheel diameters ranging from 11 to 54 inches (279 to 1372 mm) (071-540 unit sizes). Each fan shall bear a permanently affixed manufacturer’s engraved metal nameplate containing the model number and individual serial number. All fans shall bear the AMCA Sound and Air Performance seal. The fan wheel shall be centrifugal non-overloading backward-inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced in accordance to AMCA Standard 204-05. Motors shall be heavy-duty ball bearing type, carefully matched to the fan load and furnished at the specified voltage, phase and enclosure. Drives shall be sized for a minimum of 150% of driven horsepower. Motors and drives shall be mounted on true vibration isolators, out of the airstream. Fresh air for motor cooling shall be drawn into the motor compartment from an area free of discharge contaminants. Motors shall be readily accessible for maintenance. True vibration isolators shall be double-studded or pedestal mount with no metal-to-metal contact. Each vibration isolator shall be sized to match the weight of each fan. 50 The fan housing shall consist of the motor cover, shroud, curb cap and lower windband, and shall be constructed of heavy-gauge aluminum. Housing shall have a rigid internal support structure and leakproof design. The fan shroud shall be one piece with a rolled bead for extra strength which directs exhaust air downward. The lower windband shall be one piece with formed edges for added strength and the curb cap shall include prepunched mounting holes to ensure correct attachment. Drive frame assemblies shall be constructed of heavygauge steel and mounted on true vibration isolators. Pulleys shall be of the fully machined cast iron-type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. A disconnect switch is a positive electrical shutoff and shall be wired from the fan motor to a junction box installed within the motor compartment. Factory standard shall be a NEMA-1 disconnect switch with other NEMA rated options also available. Disconnect switches shall be factory mounted and/or shipped loose for field mounting. Options and accessories shall include: auto belt tensioner, curb extension, curb seal, dampers, coatings, hinge kit, hinge base, pressure probe, roof curbs, and tie-down points. Fans shall be model GB as manufactured by Greenheck Fan Corporation of Schofield, Wisconsin, USA. Belt Drive, Severe Duty Specifications Model GB Seismic Specifications Fans shall meet International Building Code (IBC) 2009, 2012 and the California Office of Statewide Health Planning and Development (OSHPD) requirements for seismic certifications as listed. • All Greenheck seismically certified models shall be tested to the most severe seismic event on the Spectral Response Map per IBC Figures 1613.5 (1-2). Testing shall be performed under the worst case scenario, using the highest mapped seismic load, highest level occupancy category, worst case site class, and highest code mandated importance factor. • Fans shall be shake table tested in accordance with ICC ES AC-156, in which the fans are physically subjected to the same or greater forces as experienced during a seismic event. High Wind Specifications Fans shall meet all Greenheck wind load standards and shall contain the following third-party certifications: • Miami-Dade NOA# 12-0120.13 • Licensed P.E. calculations shall be available for fan per ASCE 7-05 Minimum Design Loads for Buildings and Other Structures for exposure Class C, 60 foot building height, and a type II building. • Fan shall be tested in accordance with ASTM E-330-02 Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference and Florida Building Code Test Protocol TAS-201, 202 and 203 at the ASCE 7-05 calculated design pressure. • Licensed P.E. calculations for attachment of fan to curb shall be available for ASCE 7-05 determined design pressure. • All calculations and testing shall be done by a state licensed P.E., and a certified test lab. Fans shall be Greenheck model GB, as specified on page 50, with high wind-resistant construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. • For applications which are not covered by California OSHPD standards, Greenheck seismic model GB shall be certified by a third party engineering firm to IBC 2009, 2012 and ASCE 7-05 standards. • Greenheck seismic model GB has been certified to IBC 2009, 2012, ASCE 7-05 and California OSHPD standards through engineering calculations and shake table testing of all models by independent third party engineering firms. Fans shall be Greenheck model GB, as specified on page 50, with seismic rated construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. Smoke Control Specifications • Fans wheel shall be centrifugal backward-inclined, constructed of steel and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. • Dual drives shall be sized for a minimum of 150% of driven horsepower. • A NEMA-3R disconnect switch shall be factory installed and wired from the fan motor to a junction box installed outside the motor compartment. • Fans shall be Listed by Underwriters Laboratory for UL/cUL 705 for electrical components and UL/cUL Listed for Emergency Smoke Control Systems [500°F (260°C) for 4 hours and 1,000°F (538°C) for 15 minutes]. Fans shall be Greenheck model GB, as specified on page 50, with smoke control rated construction option and manufactured by Greenheck Fan Corporation in Schofield, Wisconsin, USA. 51 Quick Delivery and Quick Build Programs Greenheck’s Quick Delivery Program provides many options to help you meet your project’s schedule. Stocking warehouses and distribution centers around the world ensure same-day pickup and same-day shipment for orders in by 2 p.m. (CST). Hundreds of custom products can be manufactured through our Quick Build program in just days. Please refer to chart shown for model size and availability for QD and QB programs. The Greenheck Stock & Quick Build Catalog is a great resource for specific options and accessories available with QD and QB fans. Anywhere. Anytime. Regional warehouses are nearby and fully stocked. U.S. California Florida North Carolina Texas Wisconsin WORLDWIDE Mexico MANUFACTURING LOCATIONS California Kentucky North Carolina Wisconsin China Mexico 1 HOUR LOCAL STOCK CUSTOMER PICK UP QD STOCK SAME-DAY OR NEXT DAY SHIPMENTS 1-DAY CUSTOM-BUILT PRODUCTS SHIPPED IN ONE DAY 3-5-10-DAYS CUSTOM-BUILT PRODUCTS SHIPPED IN 3, 5 OR 10 DAYS STANDARD LEAD TIME ALL GREENHECK PRODUCTS ARE SHIPPED AS FAST AS POSSIBLE FROM ONE OF OUR FOUR U.S. MANUFACTURING PLANTS. Quick Delivery & Quick Build Model Size Availability Size Model G Number 060-095 097-098 099-103 103HP 123 133 143 143HP 163 183 203 QD-1-3-5-10 1-3-5-10 QD-1-3-5-10 1-3-5-10 QD-1-3-5-10 QD-1-3-5-10 QD-1-3-5-10 1-3-5-10 QD-1-3-5-10 1-3-5-10 1-3-5-10 Size Model GB Number 071-091 101 101HP 121 131 141 141HP 161 161HP 180 180HP 200 200HP 220 220HP 240 240HP 260 300 300HP 330 360 360HP 420 480 500 540 QD-1-3-5-10 QD-1-3-5-10 1-3-5-10 QD-1-3-5-10 QD-1-3-5-10 QD-1-3-5-10 1-3-5-10 QD-1-3-5-10 1-3-5-10 QD-1-3-5-10 1-3-5-10 QD-1-3-5-10 1-3-5-10 1-3-5-10 1-3-5-10 QD-1-3-5-10 1-3-5-10 1-3-5-10 QD-1-3-5-10 1-3-5-10 1-3-5-10 1-3-5-10 1-3-5-10 1-3-5-10 1-3-5-10 1-3-5-10 1-3-5-10 Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com Prepared to Support Green Building Efforts 00.F&V.1000 R8 3-2013 SP Copyright © 2013 Greenheck Fan Corp.