70-8313—02 - Programmer Control Cross Reference

advertisement
Programmer Control
Cross Reference
CROSS REFERENCE
Honeywell has provided proprietary and/or “labelled” controls to certain Original Equipment Manufacturers (OEM) at
their request. Proprietary controls are available only from the OEM, while “labelled” controls can, in some instances, be
purchased directly from Honeywell. Where a control is available only from the OEM, we have placed a footnote in the
“Replacement Control” column. Refer questions about a particular OEM control to the particular OEM (see list below):
Cleaver Brooks Div.
Aqua—Chem Inc.
ATTN: Parts Manager
P.O. Box 421
Milwaukee, WI 53201
414-577-2710
Fulton
972 Centerville Road
Pulaski, NY13142
315-298-5121
Lennox Industries Inc.
Lennox Parts Center
P.O. Box 7658
4251 121st Street
Urbandale, IA 50322
515-251-4440
Ray Burner Co.
Engineering & Sales Dept.
401 Parr Boulevard
Richmond, CA 94801
610-236-4272
Vapor Power International
551 S. County Line Road
Franklin Park, IL 60131
630-694-5500
70-8313-02
PROGRAMMER CONTROL CROSS REFERENCE
CROSS REFERENCE DATA
Page
HONEYWELL R4126 PROGRAMMER CROSS REFERENCE .................................................................................................
3
HONEYWELL R4127 PROGRAMMER CROSS REFERENCE .................................................................................................
6
HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. ................................................................................................
9
HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. ................................................................................................ 15
HONEYWELL R4181 PROGRAMMER CROSS REFERENCE. ................................................................................................ 21
HONEYWELL R8169 PROGRAMMER CROSS REFERENCE. ................................................................................................ 22
HONEYWELL PROGRAM MODULE PROGRAMMER CROSS REFERENCE. ....................................................................... 23
HONEYWELL BC7000 PROGRAMMER CROSS REFERENCE. ............................................................................................. 26
HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. .................................................................................... 27
FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. .................................................................... 35
FIREYE® C SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. .................................................................... 41
FIREYE® D SERIES PROGRAMMER TO HONEYWELL CROSS REFERENCE. .................................................................... 45
FIREYE® E SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. .................................................................... 48
70-8313—02
2
Table 1. HONEYWELL R4126 PROGRAMMER CROSS REFERENCE
3
Frequency
Voltage
Modulation
Postpurge
Spark Term
INTR Pilot
INTM Pilot
Lo-fire
Lockout
Device to be 1 2 3 4 5 6 7 8 9 10 Replacement
Lo-Fire
LHL OP
Replaced
Purge Timer Timing On-Off LHL PRV Damp
11 12
Start
Running
Type
Closest 7800
Series
Replacement
Hi-fire
Interlocks
Preignition
Prepurge
R4126A1008 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60 With R7253A
208
240
R4126A1016 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60 With Q535 and
R7253A
208
240
R4126A1024 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60 With Q536 and
208
R7253A
240
R4126A1032 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60 With Q535
208
240
R4126A1040 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60 With Q536
208
240
R4126A1057 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60
208
240
R4126A1065 None
X
X X
X 10
X 15,30
15 4-wire 120 50 With Q535
208
international model
240
X X
X 10
X 15,30
15 4-wire 120 60
208
240
X X
X 10
X 15,30
15 4-wire 120 60
208
240
X X
X 5
X 10
3
R4126A1073 RM7840L1018 ST7800A1054 60
or
RM7840L1075
R4126A1081 RM7840G1014 ST7800A1047 40
or
RM7840G1022
R4126A1099 None
70-8313—02
See footnotes on page 5.
10
X
HL
X
MFEP
Comments
120 60 Proprietary to Vapor
Corporation
PROGRAMMER CONTROL CROSS REFERENCE
40
PFEP
Frequency
Voltage
Modulation
Postpurge
MFEP
Spark Term
INTR Pilot
PFEP
INTM Pilot
Lo-fire
Lockout
Running
Device to be 1 2 3 4 5 6 7 8 9 10 Replacement
Lo-Fire
LHL OP
Replaced
Purge Timer Timing On-Off LHL PRV Damp
11 12
Start
Closest 7800
Series
Replacement
Hi-fire
Interlocks
Type
Preignition
Prepurge
Comments
R4126A1107 None
Produced in Japan
R4126A1115 None
Produced in Japan
R4126A1123 None
Never Produced
R4126A1131 None
Never Produced
4
R4126A1149 RM7840G1014 ST7800A1047 40
or
RM7840G1022
R4126A1156 None
X
10
X
X X
X 10
X 15,30
15 4-wire 120 60 Produced in Canada
X X
X 5
X
3
X X 10
X 15,30
15 4-wire 120 60
208
240
Proprietary to Vapor
Corporation
R4126A1164 RM7840L1018 ST7800A1054 60
or
RM7840L1075
X
R4126A1172 RM7840L1018 ST7800A1054 60
or
RM7840L1075
X
X X X X 10
X 15,30
15 4-wire 120 60
R4126A1180 RM7840L1018 ST7800A1054 60
or
RM7840L1075
X
X X X X 10
X 15,30
20 4-wire 120 60 Tamper resistant
R4126A1198 RM7840L1018 ST7800A1054 60
or
RM7840L1075
X
X X X X 10
X 10, 30 X 15 4-wire 120 60
See footnotes on page 5.
X X
120
208
240
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 1. HONEYWELL R4126 PROGRAMMER CROSS REFERENCE
Table 1. HONEYWELL R4126 PROGRAMMER CROSS REFERENCE
X 5
X 10
3
X
MFEP
Frequency
X X
10
Voltage
R4126A1206 None
PFEP
Modulation
Postpurge
Spark Term
INTR Pilot
INTM Pilot
Lo-fire
Lockout
Running
Device to be 1 2 3 4 5 6 7 8 9 10 Replacement
Lo-Fire
LHL OP
Replaced
Purge Timer Timing On-Off LHL PRV Damp
11 12
Start
Hi-fire
Interlocks
Type
Preignition
Prepurge
Closest 7800
Series
Replacement
Comments
120 60 Proprietary to Vapor
Corporation, fungus
proofed
R4126B1006 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60 With infrared
208
amplifier
240
R4126B1014 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60 With Q536 and
infrared amplifier
208
240
R4126B1022 RM7840G1014 ST7800A1047 40
or
RM7840G1022
X
X X
X 10
X 15,30
15 4-wire 120 60 With Q535 and
208
infrared amplifier
240
See footnotes on page 5.
5
Table 1 Footnotes
1
RM7840G meets current UL requirements.
RM7840L meets current insurance requirements.
3 R4126 Start Interlocks become RM7840 Preignition Interlocks.
4 Replacement controls are 120 Vac, 50/60 Hz.
5 RM7840G1014, G1022 MFEP is 10, 15, or 30 seconds.
6 RM7840L1018, L1075 MFEP is 10 or 15 seconds.
7 RM7840G1014, G1022, RM7840L1018 and L1075 PFEP is 4 or 10 seconds.
8 Select proper flame amplfier.
9 Use with existing Honeywell Flame Detectors.
10 With selectable air-flow switch check (AFSC).
11 Requires Q7800A or Q7800B Subbase.
12 Refer to conversion wiring diagrams in Modernization Wiring Information section.
2
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Frequency
Modulation
15
15 3-wire 120 60 With R7253A
208
240
R4127A1015 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X
15
15 3-wire 120 60 With Q535 and
R7253A
208
240
R4127A1023 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X
15
15 3-wire 120 60 With Q536 and
208
R7253A
240
R4127A1031 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X
15
15 3-wire 120 60 With Q535
208
240
R4127A1049 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X
15
15 3-wire 120 60 With Q536
208
240
R4127A1056 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
R4127A1064 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
R4127A1072 None
30
X
X X
10
R4127A1080 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
R4127A1098 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
R4127A1106 None
See footnotes on page 8
None
None
MFEP
Voltage
X
INTR Pilot
10
Lo-fire
X X
Hi-fire
X
Lockout
R4127A1007 RM7840G1014 ST7800A1039 30
or
RM7840G1022
Running
PFEP
INTM Pilot
6
Device to be 1 2 3 4 5 6 7 8 9 10 Replacement
Lo-Fire
LHL OP
Replaced
Purge Timer Timing On-Off LHL PRV Damp
11 12
Start
Postpurge
Type
Closest 7800
Series
Replacement
Spark Term
Interlocks
Preignition
Prepurge
Comments
X 15, 60
15 3-wire 120 60
X
15
15 3-wire 120 60
208
240
X
15
15 3-wire 120 50 With Q535
208
international model
240
X 15, 60
X
15
15 3-wire 120 60 Produced in
208
Canada
240
15 3-wire 120 60
International model
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 2. HONEYWELL R4127 PROGRAMMER CROSS REFERENCE
Table 2. HONEYWELL R4127 PROGRAMMER CROSS REFERENCE (Continued)
Frequency
Voltage
Modulation
Postpurge
Spark Term
MFEP
Comments
None
R4127A1122 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
R4127A1130 RM7840G1014 ST7800A1062 90
or
RM7840G1022
X
X X
10
R4127A1148 RM7840G1014 ST7800A1062 90
or
RM7840G1022
X
X X
R4127A1155 RM7840G1014 ST7800A1054 60
or
RM7840G1022
7
R4127A1163 None
INTR Pilot
PFEP
INTM Pilot
Lo-fire
Hi-fire
Lockout
Running
Start
Device to be 1 2 3 4 5 6 7 8 9 10 Replacement
Lo-Fire
LHL OP
Replaced
Purge Timer Timing On-Off LHL PRV Damp
11 12
R4127A1114 None
Interlocks
Type
Preignition
Prepurge
Closest 7800
Series
Replacement
None
30
X
X
R4127A1189 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X X
X
X
R4127A1197 RM7840G1014 ST7800A1054 60
or
RM7840G1022
X X
X X
X
X X
X 8
10
X
X 9
10
X 9
X
15 3-wire 120 60
208
240
15
15 3-wire 120 60
208
240
X 15, 55
15 3-wire 120 60
208
240
X 15, 30
15 4-wire 120 60
15
15 3-wire 120 50 International model
208
240
X 15, 30
15 4-wire 120 60 Ray Burner RC2D,
uses special Q535/
Q536
10
15 3-wire 120 60
X 10, 30
15 4-wire 120 60
R4127B1005 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X 15
15 3-wire 120 60
208
240
R4127B1013 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X 15
15 3-wire 120 60 With Q535
208
240
70-8313—02
See footnotes on page 8
PROGRAMMER CONTROL CROSS REFERENCE
R4127A1171 RM7840G1014 ST7800A1054 60
or
RM7840G1022
X X
X
X 15, 55
8
Frequency
Voltage
Modulation
Postpurge
Spark Term
INTR Pilot
INTM Pilot
Lo-fire
Lockout
Running
Device to be 1 2 3 4 5 6 7 8 9 10 Replacement
Lo-Fire
LHL OP
Replaced
Purge Timer Timing On-Off LHL PRV Damp
11 12
Start
Closest 7800
Series
Replacement
Hi-fire
Interlocks
Type
Preignition
Prepurge
R4127B1021 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X 15
15 3-wire 120 60 With Q536
208
240
R4127B1039 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X 15
15 3-wire 120 60 Ray Burner RC2A
with R7254A, Q536
R4127B1047 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X 15
15 3-wire 120 60 Ray Burner RC2B
with R7254A,Q535
R4127B1054 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X 15
15 3-wire 120 60 Ray Burner
R4127C1003 RM7840G1014 ST7800A1039 30
or
RM7840G1022
X
X X
10
X 15
15 3-wire 120 60 Ray Burner with
R7255A
See footnotes on page 8
Table 2 Footnotes
1
RM7840G meets current UL requirements.
RM7840L meets current insurance requirements.
3 R4127A,B,C Start Interlocks become RM7840 Preignition Interlocks.
4 Replacement controls are 120 Vac, 50/60 Hz.
5 RM7840G1014, G1022 MFEP is 10, 15, or 30 seconds.
6 RM7840L1018, L1075 MFEP is 10 or 15 seconds.
7 RM7840G1014, G1022, RM7840L1018 and L1075 PFEP is 4 or 10 seconds.
8 Select proper flame amplfier.
9 Use with existing Honeywell Flame Detectors.
10 With selectable air-flow switch check (AFSC).
11 Requires Q7800A or Q7800B Subbase.
12 Refer to conversion wiring diagrams in Modernization Wiring Information section.
2
PFEP
MFEP
Comments
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 2. HONEYWELL R4127 PROGRAMMER CROSS REFERENCE (Continued)
Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE.
Frequency
Voltage
Modulation
Postpurge
MFEP
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
Hi-fire
Purge Timer
Preignition
2, 6, 7, 8, 9
Lockout
7800 Series
Running
Direct
2, 6, 7,11
Interlocks
Start
Device to be
Replaced
Prepurge
Timing
Replacement
Comment
R4140D1004 None
None
30
X X
10 X
10
R4140E1001 None
None
31
X X
3
10
R4140G1007 R7140G1000
RM7840G1014 or ST7800A1054 60 LHL, LF
RM7840G1022
Proven
X
X
X 10
X 10, 30
16 4-wire 120 60
R4140G1015 R7140G1000
RM7840G1014 or ST7800A1054 60 LHL, LF
RM7840G1022
Proven
X
X
X 10
X 10, 30
16 4-wire 120 60
X
X
X 10
X 10, 15
16 4-wire 120 60 Proprietary to Cleaver
Brooks CB20
R4140G1023 Consult Original Equipment
Manufacturer
72 LHL, LF
Proven
X 55 4-wire 120 60 Maxon special sequence
for postpurge pilot
systems. Uses special
Q520A1196.
15 4-wire 120 60 For direct spark ignition
systems
X 10
X 10, 30 X 16 4-wire 120 60
R4140G1049 R7140G20081
RM7840G1014 or ST7800A1054 60 LHL, LF X X
Proven
RM7840G10221
X 10
X 10, 30 X 16 4-wire 120 60
R4140G1056 R7140G20081
RM7840G1014 or ST7800A1054 60 LHL, LF X X
Proven
RM7840G10221
X 10 X
10
X 16 4-wire 120 60
R4140G1064 R7140G20081
RM7840G1014 or ST7800A1054 60 LHL, LF X X
Proven
RM7840G10221
X 10 X
10
X 16 4-wire 120 60
R4140G1072 R7140G20081
RM7840G1014 or ST7800A1054 60 LHL, LF X X
Proven
RM7840G10221
X 10 X
10
16 4-wire 120 60
R4140G1080 R7140G20081
RM7840G1014 or ST7800A1054 60 LHL, LF X X
Proven
RM7840G10221
X 10 X
10
16 4-wire 120 60
R4140G1098 None
None
X 10 X
10, 30 X 16 4-wire 240 50 International model
R4140G1106 R7140G1000
RM7840G1014 or ST7800A1054 60 LHL, LF
RM7840G1022
Proven
R4140G1114 None
None
R4140G1122 None
None
70-8313—02
See footnotes on page 14
60 LHL, LF X X
Proven
X
X
X 10
X 10, 15
16 4-wire 120 60
70 LHL, LF X X
Proven
X 10
X 10,
X 25 4-wire 240 60
30, 60
70 LHL, LF X X
Proven
X 10
X 10,
X 25 4-wire 208 60
30, 60
PROGRAMMER CONTROL CROSS REFERENCE
RM7840G1014 or ST7800A1054 60 LHL, LF X X
Proven
RM7840G10221
9
R4140G1031 R7140G20081
Frequency
Voltage
Modulation
Postpurge
MFEP
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
Hi-fire
Purge Timer
Preignition
2, 6, 7, 8, 9
Lockout
7800 Series
Running
Direct
2, 6, 7,11
Interlocks
Start
Device to be
Replaced
Prepurge
Timing
Replacement
R4140G1130 R7140G20081
RM7840G1014 or ST7800A1054 60 LHL, LF X X
Proven
RM7840G10221
X 10
X 10, 15 X 16 4-wire 120 60
R4140G1148 R7140G20081
RM7840G1014 or ST7800A1054 60 LHL, LF X X
Proven
RM7840G10221
X 10
X 10, 15 X 16 4-wire 120 60
R4140G1155 None
EC7850A1122
ST7800A1054 60 LHL, LF
Proven
R4140G1163 R7140G20081
RM7840G10141
ST7800A1054 60 LHL, LF X X
Proven
X
X X X 5
X 10 X
R4140G1171 R7140G20081,3 RM7840G10141, 3 ST7800A1062 70 LHL, LF X X
(90 seconds)
Proven
X 10
X
X X X 10
X 5
10
Comment
X 15 4-wire 240 50 Proprietary to GordonPiatt Energy
X 16 4-wire 120 60
X 10,
X 25 4-wire 120 60
30, 60
X 10
X 15 4-wire 120 60 Gordon-Piatt Energy
GP201
10
R4140G1189 R7140L100910
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
R4140G1197 None
EC7850A1122
R4140L1006 R7140L1009
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10, 15
16 4-wire 120 60
R4140L1014 R7140L1009
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10, 15
16 4-wire 120 60
72 LHL,
HF-LF
Proven
X X X X 10
X 10, 15
15 4-wire 120 60 Cleaver Brooks CB40
R4140L1030 R7140L1009
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10, 15 X 16 4-wire 120 60 With nonrotatable timer
R4140L1048 None
EC7850A1122
ST7800A1047 45 LHL,
(40 seconds)
HF-LF
Proven
X X X X 10
X 2, 5,
10
R4140L1055 R7140L1009
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10, 30
R4140L1022 Consult Original Equipment
Manufacturer
See footnotes on page 14
ST7800A1054 60 LHL, LF X X
Proven
X 5
X 5, 10, X 16 4-wire 240 50 International model
15
X 15 4-wire 220 50 International model
15 4-wire 120 60
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued)
Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued)
X X X X 6.5 X
Frequency
Voltage
Modulation
Postpurge
MFEP
8
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
9.5 LHL,
HF-LF
Proven
Hi-fire
Purge Timer
Preignition
2, 6, 7, 8, 9
R4140L1063 Consult Original Equipment
Manufacturer
Lockout
7800 Series
Running
Direct
2, 6, 7,11
Interlocks
Start
Device to be
Replaced
Prepurge
Timing
Replacement
Comment
3.5 2-wire 120 60 Vapor Corporation
11
R4140L1071 None
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10,
X 15 4-wire 240 50 International model
15, 30
R4140L1089 R7140L100910
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10
R4140L1097 R7140L1009
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10, 15 X 15 4-wire 120 60
R4140L1105 R7140L1009
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10, 15 X 16 4-wire 120 60
R4140L1113 None
EC7840L101412 ST7800A1054 60 LHL,
HF-LF
or EC7850A1122
Proven
X X X X 5
X 5, 10, X 15 4-wire 240 50 International model
15
5.5 LHL,
HF-LF
Proven
X X X X
8
R4140L1139 R7140L1009
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10, 15 X 15 4-wire 120 60
R4140L1147 R7140L1009
RM7840L1018 or ST7800A1054 60 LHL,
RM7840L1075
HF-LF
Proven
X X X X 10
X 10,
X 15 4-wire 120 60
15, 30
R4140L1154 None
EC7850A1122
Sel LHL,
ect HF-LF
abl Proven
e
X X X X 10
X 5, 10
60 LHL,
HF-LF
Proven
X X X X 10
X 5, 15
R4140L1162 Consult Original Equipment
Manufacturer
70-8313—02
See footnotes on page 14
Check R4140
for purge
timing
ICI Model
X 15 4-wire 240 50 Approved by Australian
Gas Association
16 4-wire 120 60 Fulton Special
PROGRAMMER CONTROL CROSS REFERENCE
R4140L1121 Consult Original Equipment
Manufacturer
X 15 4-wire 120 60 Gordon-Piatt Energy
GP301
X X X X 10
Frequency
Voltage
Modulation
Postpurge
MFEP
X 5, 10
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
Hi-fire
Purge Timer
Preignition
2, 6, 7, 8, 9
Lockout
7800 Series
Running
Direct
2, 6, 7,11
Interlocks
Start
Device to be
Replaced
Prepurge
Timing
Replacement
Comment
X 15 4-wire 240 50
R4140L1170 None
EC7850A1122
ST7800A1054 60 LHL,
HF-LF
Proven
R4140M1004 R7140M10071
RM7840M10171
ST7800A1039 31 On-Off, X X
(30 seconds)
LF
Proven
10 X
10
15
120 60
R4140M1012 R7140M10071
RM7840M10171
ST7800A1039 31 On-Off, X X
(30 seconds)
LF
Proven
10 X
10
15
120 60
R4140M1020 R7140M1007
RM7840M10171, 4 ST7800A1047 42 On-Off, X X
(40 seconds)
LF
Proven
X 10 X
10
X 15
120 60 Isolated damper motor
contact
RM7840M10171, 4 ST7800A1047 42 On-Off, X X
(40 seconds)
LF
Proven
X 10 X
10
X 15
120 60 Isolated damper motor
contact
RM7840M10171, 4 ST7800A1062 96 On-Off, X X
(90 seconds)
LF
Proven
X 10 X
10
X 25
120 60 Isolated damper motor
contact
RM7840M10171, 4 ST7800A1062 96 On-Off, X X
(90 seconds)
LF
Proven
X 10 X
10
X 25
120 60 Isolated damper motor
contact
10
X 5, 10
X 15
240 50 International model
10
X 25
120 60 Gordon-Piatt Energy
GP101
1, 4, 5
R4140M1038 R7140M1007
1, 4, 5
12
R4140M1046 R7140M1007
1, 4, 5
R4140M1053 R7140M1007
1, 4, 5
R4140M1061 None
None
R4140M1079 R7140M1007
RM7840M1017
R4140M1087 None
None
31 On-Off, X X
LF
Proven
ST7800A1062 90 On-Off, X
LF
Proven
31 On-Off, X X
LF
Proven
X
10 X
10
X 5, 10, X 15
15
240 50 International model
R4140M1095 Never produced
R4140M1103
R7140M10071
See footnotes on page 14
Never produced
RM7840M10171
ST7800A1039 31 On-Off, X X
(30 seconds)
LF
Proven
10
X 10, 30
15
120 60
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued)
Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued)
R4140M1111 R7140M10071
1
RM7840M1017
X 10, 30
15
Frequency
Voltage
Modulation
Postpurge
MFEP
10
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
ST7800A1039 31 On-Off, X X
(30 seconds)
LF
Proven
Hi-fire
Purge Timer
Preignition
2, 6, 7, 8, 9
Lockout
7800 Series
Running
Direct
2, 6, 7,11
Interlocks
Start
Device to be
Replaced
Prepurge
Timing
Replacement
Comment
120 60
R4140M1129 Never produced
R4140M1137 Never produced
R4140M1145 R7140M1007
1, 4, 5
R4140M1152 R7140M1007
1, 4, 5
RM7840M10171, 4 ST7800A1047 42 On-Off, X X
(40 seconds)
LF
Proven
X
X 10 X
10
X 15
120 60 Isolated damper motor
contact
RM7840M10171, 4 ST7800A1047 42 On-Off, X X
(40 seconds)
LF
Proven
X
X 10 X
10
X 15
120 60 Isolated damper motor
contact
13
ST7800A1062 96 On-Off,
(90 seconds)
LF
Proven
X
X
X 10 X
10
X 25
120 60 Isolated damper motor
contact
R4140M1178 R7140M10074, 5 RM7840M10174
ST7800A1062 96 On-Off,
(90 seconds)
LF
Proven
X
X
X 10 X
10
X 25
120 60 Isolated damper motor
contact
R4140M1186 R7140M10071, 5 RM7840M10171
ST7800A1047 42 On-Off, X X
(40 seconds)
LF
Proven
X 10 X
10
X 15
120 60
R4140M1194 R7140M10071, 5 RM7840M10171
ST7800A1062 96 On-Off, X X
(90 seconds)
LF
Proven
X 10 X
10
X 15
120 60
X 5, 10
X 15
240 50 Approved by Australian
Gas Association
R4140M1202 None
None
R4140M1210 Consult Original Equipment
Manufacturer
31 On-Off, X X
LF
Proven
31 On-Off, X X
LF
Proven
X 5
10 X
10
25
120 60 Fulton Special
70-8313—02
R4140P1007 None
RM7896C1010 or ST7800A1062 90 On-Off
RM7897C1000
X X
10
X 15
15
120 60 Gordon Piatt GP001
R4140Y1005 None
RM7896A1012 or ST7800A1013 7
RM7897A1002
On-Off
X X
10
X 15
15
120 60
R4140Y1013 None
RM7896A1012 or ST7800A1013 7
RM7897A100212
On-Off
X X
4
X 15
15
120 60
See footnotes on page 14
PROGRAMMER CONTROL CROSS REFERENCE
R4140M1160 R7140M10074, 5 RM7840M10174
Frequency
Voltage
Modulation
Postpurge
MFEP
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
Hi-fire
Purge Timer
Preignition
2, 6, 7, 8, 9
Lockout
7800 Series
Running
Direct
2, 6, 7,11
Interlocks
Start
Device to be
Replaced
Prepurge
Timing
Replacement
R4140Y1021 None
RM7896A1012 or ST7800A1039 30 On-Off
RM7897A1002
X X
10
X 15
15
120 60
R4140Y1039 None
RM7896A1012 or ST7800A1039 30 On-Off
RM7897A100212
X X
4
X 15
15
120 60
R4140Y1047 None
RM7896A1012 or ST7800A1054 60 On-Off
RM7897A1002
X X
10
X 15
15
120 60
R4140Y1054 None
RM7896A1012 or ST7800A1054 60 On-Off
RM7897A100212
X X
4
X 15
15
120 60
R4140Y1062 None
RM7896A1012 or ST7800A1062 90 On-Off
RM7897A1002
X X
10
X 15
15
120 60
R4140Y1070 None
RM7896A1012 or ST7800A1062 90 On-Off
RM7897A100212
X X
4
X 15
15
120 60
See footnotes on page 14
14
Table 3 Footnotes
1
2
3
4
5
6
R4140 Start Interlocks become Pre-Ignition Interlock (must remain closed throughout purge)
4 or 10 Second PFEP
60 second MFEP is not available with replacement device
Spring return Firing Rate Motor (damper motor)
Remove Jumper J1 and J2
Select Proper Amplifier:
Old Amplifer Replacement Amplifer
R7247A1005 R7847A1033
R7247A1021 R7847A1025
R7247B1003 R7847B1031
R7247C1001 R7861A1026 See Note 8
R7248A1004 R7848A1008
R7248B1028 R7848B1006
R7249A1003 R7849A1023
R7476A1007 R7886A1001
7
With Selectable Airflow Switch Check (AFC)
Used with Existing Flame Detectors - EXCEPT - C7012E, F - Replace with C7061A, F and appropriate R7861 Flame Amplifier
9 Requires Q7800A or B Wiring Subbase
10
Locate High Fire (or Purge Rate Switch) connection on Terminal D. Remove Wire and Connect onto Terminal M
11 Check the wiring base - if 3 terminal strips - system must be updated to the 7800 SERIES option - do not use the R7140 option.
12 Clip JR1
8
Comment
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued)
Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE.
Frequency
Voltage
Modulation
Postpurge
MFEP
Spark Term
INTR Pilot
INTM Pilot
PFEP
Type
Lo-fire
Purge Timer
Hi-fire
1, 2, 6, 7, 8, 9
Preignition
7800 Series
1, 2, 6, 7, 8, 10
Lockout
Device to be
Replaced
Running
Direct
Interlocks
Start
Prepurge
Timing
Replacement
Comment
R4150A1007 None
RM7840M1017 ST7800A1039 30 On-Off X X
10 X
15
15
120 60 Includes R7257 Amplifier.
R4150A1015 None
RM7840M1017 ST7800A1039 30 On-Off X X
10 X
15
15
120 50
R4150A1023 None
RM7840M1017 ST7800A1039 30 On-Off X X
10 X
15
15
120 60
R4150A1031 None
RM7840M1017 ST7800A1039 30 On-Off X X
10
X 15, 30 X 15
120 60 Kewanee label.
10
X 5
X 15
200 60 Includes R7257 International model.
R4150A1049 International Model
30 On-Off X X
R4150A1056 None
RM7840M1017 ST7800A1039 30 On-Off X X
15
X 15
X 15
120 60
R4150A1064 None
RM7840M1017 ST7800A1039 30 On-Off X X
10
X 15, 30
15
120 60
15
R4150A1072 International Model
R4150A1080 None
30 On-Off X X
10
X 15
RM7840M1017 ST7800A1039 30 On-Off X X
10
X 15, 30 X 15
200 60 International model.
120 60 Kewanee label.
R4150A1098 Never Produced
Never produced
15
R4150A1106 None
RM7840M1017 ST7800A1039 30 On-Off X X
15 X
5
R4150A1114 None
RM7840M1017 ST7800A1054 60 On-Off X X
10 X
15
R4150A1122 None
RM7840M1017 ST7800A1062 90 On-Off X X
10 X
15
15
120 60
R4150A1130 None
RM7840M1017 ST7800A1054 60 On-Off X X
10
X 15, 30
20
120 60
R4150A1148 None
RM7840M1017 ST7800A1062 90 On-Off X X
10
X 15, 30
15
120 60
R4150A1155 None
RM7840M1017 ST7800A1062 90 On-Off X X
10
X 15, 30 X 15
120 60 Kewanee label.
R4150A1163 None
RM7840M1017 ST7800A1039 30 On-Off X X
15
X 15
X 15
120 60
R4150A1171 None
RM7840M1017 ST7800A1062 90 On-Off X X
15 X
X 15
120 60
R4150A1189 None
RM7840M1017 ST7800A1062 90 On-Off X X
15
X 20
120 60
R4150A1197 None
RM7840M1017 ST7800A1039 30 On-Off X X
120 60
120 50 International model
10
X 2
20
220 50 International model
R4150A1213 International Model
37 On-Off X X
10
X 5
20
220 50 International model
R4150A1221 International Model
37 On-Off X X
10
X 5
20
240 50 International model
R4150A1239 None
RM7840M1017 ST7800A1062 90 On-Off X X
15
X 15
X 20
120 60
R4150A1247 None
RM7840M1017 ST7800A1039 30 On-Off X X
10 X
15
15
120 60
R4150A1254 None
RM7840M1017 ST7800A1062 90 On-Off X X
120 60
10 X
15
20
30 On-Off X X
10 X
15
X 15
RM7840M1017 ST7800A1039 30 On-Off X X
30 X
15
15
R4150A1262 International Model
220 50 International model
70-8313—02
120 60
PROGRAMMER CONTROL CROSS REFERENCE
15
37 On-Off X X
See footnotes on page 20
15
120 60
R4150A1205 International Model
R4150A1270 None
10 X
X 15
X 15
R4150A1288 None
Frequency
Voltage
Modulation
Postpurge
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
MFEP
15
15
120 60 5 second stabilization before PFEP.
30 On-Off X X
10 X
15
15
220 50 International model. Ignition on 3 secs
before pilot valve.
RM7840M1017 ST7800A1039 30 On-Off X X
10 X
15
15
120 60 R7258A included
10 X
15
15
120 60 R7259A included
X 10
15
120 60 R7259A included
R4150B1013 Never Produced
R4150C1003 None
Comment
10 X
R4150A1296 International Model
R4150B1005 None
Type
Hi-fire
Purge Timer
RM7840M1017 ST7800A1047 35 On-Off X X
(40 seconds)
Preignition
1, 2, 6, 7, 8, 9
Lockout
7800 Series
1, 2, 6, 7, 8, 10
Running
Device to be
Replaced
Interlocks
Start
Prepurge
Timing
Replacement
Direct
Never produced
RM7840M1017 ST7800A1039 30 On-Off X X
R4150C1011 Never Produced
R4150C1029 None
RM7840M1017 ST7800A1039 30 On-Off
X X
10
R4150D1001 Never Produced
R4150E1008 None
None
Never produced
30
X X
3
15
120 60 For direct spark ignition applications
16
R4150F1006 International Model
International - Japan
R4150F1014 International Model
International - Japan
R4150G1004 R7140G2008 RM7840G1014 ST7800A1054 50 LHL, X X
(60 seconds)
LF
or
Proven
RM7840G1022
X 9 X
15
R4150G1012 R7140M1007 RM7840M1017 ST7800A1062 72 OnX X
4,5
(90 seconds)
Off, LF
Proven
X 13 X
15
R4150G1020 R7140G2008 RM7840G1014 ST7800A1054 50 LHL, X X
or
(60 seconds)
LF
RM7840G1022
Proven
X 9 X
10
8
3120 60 Kewanee label
wire
50 LHL, X X
LF
Proven
X 9 X
15
8
3220 50 International model
wire
R4150G1046 R7140G2008 RM7840G1014 ST7800A1054 50 LHL, X X
or
(60 seconds)
LF
RM7840G1022
Proven
X 9 X
10
8
3120 60
wire
R4150G1053 Consult Original Equipment Manufacturer
72 LHL, X X
LF
Proven
X 10 X
10, 15
9
3120 60 Cleaver Brooks CB2
wire
R4150G1061 Consult Original Equipment Manufacturer
72 LHL,
LF
Proven
X X X X 10 X
10, 15
15 3120 60 Cleaver Brooks CB4, CB4-1
wire
R4150G1038 International Model
See footnotes on page 20
8
X 15
3120 60
wire
120 60
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. (Continued)
Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. (Continued)
Prepurge
Interlocks
R4150G1111 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X
or
LF
RM7840G1022
Proven
X 10 X
15
15 4120 60
wire
X
X X X 10 X
10
15 4120 60 Gordon-Piatt Energy GP200
wire
Frequency
15 3120 60
wire
Voltage
10, 30
Modulation
X 10 X
Postpurge
R4150G1103 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X
or
LF
RM7840G1022
Proven
INTR Pilot
15 4120 60 Cleaver Brooks CB2-1
wire
INTM Pilot
10, 15
PFEP
X 10 X
Lo-fire
72 LHL, X X
LF
Proven
Hi-fire
R4150G1087 Consult Original Equipment Manufacturer
Type
Preignition
X 15
Purge Timer
Lockout
15
1, 2, 6, 7, 8, 9
Running
X 13 X
7800 Series
1, 2, 6, 7, 8, 10
Start
R4150G1079 R7140M1007 RM7840M1017 ST7800A1062 72 LHL, X X
(90 seconds)
LF
Proven
Device to be
Replaced
Timing
MFEP
Spark Term
Replacement
Direct
R4150G1095 Never Produced
R4150G1129 None
Never produced
17
RM7840L1018 ST7800A1054 60 LHL,
LF
or
Proven
RM7840L1075
X 10
R4150G1145 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X
or
LF
RM7840G1022
Proven
X 10 X
X 10, 30
15 4120 60
wire
10
15 4120 60
wire
R4150G1152 Never Produced
Never produced
72 LHL,
LF
Proven
X X
X 10
R4150G1178 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X
LF
or
Proven
RM7840G1022
R4150G1186 R7140G1000 RM7840G1014 ST7800A1054 60 LHL,
or
LF
RM7840G1022
Proven
R4150G1194 Never Produced
See footnotes on page 20
X
X 10 X
X
X 10
X 10, 15
15 4120 60 Cleaver Brooks CB2-1A
wire
15
15 4120 60
wire
X 10, 15
15 4120 60
wire
Never produced
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
R4150G1137 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X
or
LF
RM7840G1022
Proven
R4150G1160 Consult Original Equipment Manufacturer
Comment
120 60
X
X X X 10
Frequency
Voltage
Modulation
Postpurge
MFEP
X 5
Spark Term
INTR Pilot
INTM Pilot
PFEP
Type
Lo-fire
Purge Timer
Hi-fire
1, 2, 6, 7, 8, 9
Preignition
7800 Series
Lockout
1, 2, 6, 7, 8, 10
Running
Device to be
Replaced
Interlocks
Start
Prepurge
Timing
Replacement
Direct
Comment
X 15 4240 50 International model to Gordon-Piatt
wire
Energy Specifications.
R4150G1202 International Model
62 LHL,
LF
Proven
R4150H1002 International Model
30 On-Off X X
9
X 13, 58
15 3120 60 International model
wire
R4150H1010 International Model
30 On-Off X X
9
X 13, 58
15 3240 60 International model
wire
R4150H1028 International Model
30 On-Off X X
9
X 13, 58
15 3220 50 International model
wire
R4150H1036 International Model
30 On-Off X X
9
X 13, 58
15 3208 60
wire
R4150J1007 International Model
37 On-Off X
5
X 2
20
220 50 International model
R4150K1005 International Model
37 On-Off X
5
X 5
20
220 50 International model
18
R4150L1003 R7140L1009 RM7840L1018 ST7800A1062 72 LHL,
or
(90 seconds)
HF-LF
RM7840L1075
Proven
X X X X 10
X 10, 15
15 3120 60
wire
R4150L1011 R7140L1009 RM7840L1018 ST7800A1062 72 LHL,
(90 seconds)
HF-LF
or
Proven
RM7840L1075
X X X X 10
X 10, 15
15 3120 60
wire
R4150L1029 R7140L1009 RM7840L1018 ST7800A1054 60 LHL,
or
HF-LF
RM7840L1075
Proven
X X X X 10
X 10
15 4120 60 Gordon-Piatt Energy GP300 (original)
wire
R4150L1037 R7140L1009 RM7840L1018 ST7800A1062 72 LHL,
or
(90 seconds)
HF-LF
RM7840L1075
Proven
X X X X 10
X 10, 15
15 4120 60
wire
R4150L1045 R7140L1009 RM7840L1018 ST7800A1062 72 LHL,
(90 seconds)
HF-LF
or
Proven
RM7840L1075
X X X X 10
X 10, 15
15 4120 60
wire
R4150L1052 Never Produced
Never produced
72 LHL,
HF-LF
Proven
X X X X 10
X 10, 15
15 4120 60 Cleaver Brooks CB4-1A
wire
R4150L1078 R7140L1009 RM7840L1018 ST7800A1054 60 LHL,
or
HF-LF
RM7840L1075
Proven
X X X X 10
X 10
15 4120 60 Gordon-Piatt Energy GP300
wire
R4150L1060 Consult Original Equipment Manufacturer
See footnotes on page 20
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. (Continued)
Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. (Continued)
R4150M1019 None
10 X
20
Frequency
Voltage
Modulation
Postpurge
MFEP
10
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
R4150M1001 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X
Hi-fire
Purge Timer
Preignition
1, 2, 6, 7, 8, 9
Lockout
7800 Series
1, 2, 6, 7, 8, 10
Running
Device to be
Replaced
Interlocks
Start
Prepurge
Timing
Replacement
Direct
Comment
120 60 Ray Burner
RM7840M1017 ST7800A1062 90 On-Off X X
10 X
10
20
120 60 Ray Burner - Special Base
R4150M1027 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X
10 X
15
15
120 60
R4150M1035 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X
10 X
15
15
120 60
R4150M1043 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X
10
X 15
X 15
120 60
R4150M1050 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X
10
X 15, 30
15
120 60
R4150M1068 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X
10 X
15
15
120 60
R4150M1076 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X
10
X 15
X 15
120 60
R4150M1084 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X
10 X
15
15
120 60
10 X
15
X 20
R4150M1092 None
RM7840M1017 ST7800A1062 90 On-Off
X
X
120 60 Gordon-Piatt Energy GP100 (original)
19
R4150M1100 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X
10
X 10, 30
15
120 60
R4150M1118 None
RM7840M1017 ST7800A1039 30 On-Off X X
15
X 15
X 15
120 60
R4150M1126 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X
10
X 10
X 15
120 60
R4150M1134 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X
10 X
R4150M1142 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X
10
R4150M1159 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X
15
120 60
X 20
120 60
10 X
10
20
120 60
10 X
10
X 20
120 60 Gordon-Piatt Energy GP100
R4150M1167 Never Produced
R4150M1175 None
Never produced
RM7840M1017 ST7800A1062 90 On-Off
X
X
R4150X1004 International Model
30 On-Off X X
5
X 5
X 15
220 50 International model
R4150X1012 International Model
30 On-Off X X
5
X 5
X 15
240 50 International model
R4150X1020 International Model
See footnotes on page 20
International model
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
10
X 10
1
2
3
4
5
6
R4150 Start Interlocks become Pre-Ignition Interlock (must remain closed throughout purge)
4 or 10 Second PFEP
60 second MFEP is not available with replacement device
Spring return Firing Rate Motor (damper motor)
Remove Jumper J1 and J2
Select Proper Amplifier
Old Amp
Replacement Amp.
R7257A1028 R7847A1033
R7258A1001 R7848A1008
R7259A1000 R7849A1023
7
With Selectable Airflow Switch Check (AFC)
Used with Existing Flame Detectors - EXCEPT - C7012E, F - Replace with C7061A, F and appropriate R7861 Flame Amplifier
9 Requires Q7800A or B Wiring Subbase
10 Check the wiring base - if 3 terminal strips - update to the 7800 Series option - Do not use the R7140 option.
8
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 4 Footnotes
20
Table 5. HONEYWELL R4181 PROGRAMMER CROSS REFERENCE.
Frequency
Voltage
Modulation
MFEP
40
ST7800A1054
60
R4181A1026 RM7840G1014 ST7800A1047
or
RM7840G1022
40
R4181A1034 RM7840L1018
or
RM7840L1075
ST7800A1054
60
X
R4181A1042 RM7840L1018
or
RM7840L1075
ST7800A1054
60
X
X X X X 10
X 10, 15 X 20 4-wire 120 60
R4181A1059 RM7840L1018
or
RM7840L1075
ST7800A1054
(60 seconds)
55
X
X X X X 7
X 10, 30 X 16 4-wire 120 60
21
Table 5 Footnotes
1
Replacement suggestion is 120Vac, 50/60 Hz.
X
LF PRV
X X
X 10
X 15, 30
15 4-wire 120 60
208
240
X X
X X 10
X 15, 30
15 4-wire 120 60
208
240
X X
X 10
X 15, 30
15 4-wire 120 60
208
240
X X
X X 10
X 10, 15
15 4-wire 120 60
208
240
Comments
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
R4181A1000 RM7840G1014 ST7800A1047
or
RM7840G1022
R4181A1018 RM7840L1018
or
RM7840L1075
LF PRV
OP
Damp
Postpurge
LHL
PRV
Spark Term
LHL
INTR Pilot
Lo-Fire
Timing On-Off
INTM Pilot
Purge Timer
PFEP
1
Lockout
7800 Series
Replacement
Running
Device to be
Replaced
Start
Type
Lo-fire
Interlocks
Hi-fire
Prepurge
Preignition
Replacement
Frequency
Voltage
Modulation
Postpurge
MFEP
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Lockout
OP
Damp
Running
Current
Device to be Replacement 7800 Series
Lo-Fire
LHL
Replaced
Replacement Timing On-Off LHL PRV
1
Start
Type
Hi-fire
Interlocks
Preignition
Prepurge
Comments
R8169A1007 Consult
Original
Equipment
None
60
X
X X
7 X
13
80
120 60 Proprietary to Lennox
R8169A1015 Consult
Original
Equipment
None
60
X
X X
7 X
13
80
240 50 Proprietary to Lennox
R8169B1005 Consult
Original
Equipment
None
60
HL
X X
7 X
13
80
120 60 Proprietary to Lennox
R8169B1013 Consult
Original
Equipment
None
60
HL
X X
7 X
13
80
240 50 Proprietary to Lennox
22
Table 6 Footnotes
1
Contact OEM for replacement suggestions.
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 6. HONEYWELL R8169 PROGRAMMER CROSS REFERENCE.
Table 7. HONEYWELL PROGRAM MODULE PROGRAMMER CROSS REFERENCE.
Frequency
Voltage
Postpurge
MFEP
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
Hi-fire
Purge Timer
Preignition
1 2 3 4 5 6 7
Lockout
1 3 4 5
7800 Series
Replacement
Interlocks
Running
Used With
Direct
Prepurge
Start
Program
Module
Replacement
Timing
Device to be Replaced
Comments
PM720G1197 BC7000L1042 Consult Original Equipment
Manufacturer
40 4-wire LHL,
LF Proven
X X X
X 10
X 10,15
15 120 60 Proprietary to York-Shipley, LWCO
annunciation on terminal 18
PM720G1205 BC7000L1042 Consult Original Equipment
Manufacturer
40 4-wire LHL,
LF Proven
X X X
X 10
X 10,15
15 120 60 Proprietary to York-Shipley, LWCO
annunciation on terminal 18
23
PM720G2005 BC7000L1000 R7140G2008 RM7800G1018 ST7800A1047 40 4-wire LHL,
or
LF Proven
RM7840G1022
X
X
X 10
X 10,15,
30
X 15 120 60
PM720G2013 BC7000L1000 R7140G2008 RM7800G1018 ST7800A1047 40 4-wire LHL,
or
LF Proven
RM7840G1022
X
X
X 10
X 10*
X 15 120 60 * 10 sec MFEP or intermittent pilot
PM720G2021 BC7000L1000 Consult Original Equipment
Manufacturer
60 4-wire LHL,
LF Proven
X
X
X 7
X 13*
30 120 60 * 13 sec MFEP or intermittent pilot
proprietary to Lennox
PM720G2039 BC7000L1000 R7140G2008 RM7800G1018 ST7800A1047 40 4-wire LHL,
LF Proven
or
RM7840G1022
X
X
X 10
X 10,15,
30
30 4-wire LHL,
HF-LF
Proven
X X X
X 7
X 8
PM720L1030 BC7000L1000 R7140L2007 RM7800L1012 ST7800A1039 30 4-wire LHL,
or
HF-LF
RM7800L1087
Proven
X X X
X 10
X 10,15
PM720L1063 BC7000L1034 Consult Original Equipment
Manufacturer
4-wire LHL,
HF-LF
Proven
X X X
X 7
X 8
4
120 60 Proprietary to Vapor Corporation
PM720L1097 BC7000L1018 Consult Original Equipment
Manufacturer
30 4-wire LHL,
HF-LF
Proven
X X X
X 7
X 8
4
120 50 Proprietary to Cleaver Brooks
PM720L1105 BC7000L1034 Consult Original Equipment
Manufacturer
8
4-wire LHL,
HF-LF
Proven
X X X
X 7
X 8
4
120 50 Proprietary to Vapor Corporation
PM720L1113 BC7000L1042 Consult Original Equipment
Manufacturer
30 4-wire LHL,
HF-LF
Proven
X X X
X 10
X 10,15
15 120 60 Proprietary to York-Shipley, LWCO
annunciation on terminal 18
PM720L1022 BC7000L1018 Consult Original Equipment
Manufacturer
4
120 60 Proprietary to Cleaver Brooks
X 15 120 60
PM720L1089 NEVER PRODUCED
70-8313—02
See footnotes on page 25
PROGRAMMER CONTROL CROSS REFERENCE
8
X 15 120 50
Frequency
Voltage
Postpurge
MFEP
Spark Term
INTR Pilot
INTM Pilot
PFEP
Lo-fire
Type
Hi-fire
Purge Timer
Preignition
1 2 3 4 5 6 7
Lockout
1 3 4 5
7800 Series
Replacement
Interlocks
Running
Used With
Direct
Prepurge
Start
Program
Module
Replacement
Timing
Device to be Replaced
Comments
30 4-wire LHL,
HF-LF
Proven
X X X
X 10
X 10,15
PM720L1139 BC7000L1000 R7140L2007 RM7800L1012 ST7800A1039 30 4-wire LHL,
or
HF-LF
RM7800L1087
Proven
X X X
X 10
X 10,15
X 15 120 60 Reduced sensitivity to line noise
PM720L2004 BC7000L1000 None
RM7800E1010 ST7800A1039 30 4-wire LHL,
HF-LF
Proven
X X X
X 10
X 10,15
X 15 120 60 Energy saving prepurge (ESP)
PM720L2012 BC7000L1000 R7140L2007 RM7800L1012 ST7800A1039 30 4-wire LHL,
HF-LF
or
Proven
RM7800L1087
X X X
X 10
X 10,15
X 15 120 50
PM720L2020 BC7000L1000 R7140L2007 RM7800L1012 ST7800A1021 10 4-wire LHL,
or
HF-LF
RM7800L1087
Proven
X X X
X 10
X 10,15
X 15 120 60
PM720L1121 BC7000L1042 Consult Original Equipment
Manufacturer
15 120 60 Proprietary to York-Shipley, LWCO
annunciation on terminal 18, energy
saving prepurge (ESP)
24
PM720M2002 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1039 30, 2-wire On(30 seconds), 90 Off, LF
ST7800A1062
Proven
(90 seconds)
X
X
X 10
X 10*
X 15 120 60 * 10 second MFEP or intermittent
pilot
PM720M2010 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1013 7
(7 seconds)
2-wire OnOff, LF
Proven
X
X
X 10
X 10*
X 15 120 60 * 10 second MFEP or intermittent
pilot
PM720M2036 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1013 7, 2-wire On(7 seconds), 30 Off, LF
Proven
ST7800A1039
(30 seconds)
X
X
X 10
X 10*
X 15 120 60 * 10 second MFEP or intermittent
pilot
PM720M2044 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1039 30, 2-wire On(30 seconds), 90 Off, LF
ST7800A1062
Proven
(90 seconds)
X
X
X 10
X 10*
X 15 120 50 * 10 second MFEP or intermittent
pilot
PM720M2051 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1013 7, 2-wire On(7 seconds), 30 Off, LF
ST7800A1039
Proven
(30 seconds)
X
X
X 10
X 10*
X 15 120 50 * 10 second MFEP or intermittent
pilot
See footnotes on page 25
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 7. HONEYWELL PROGRAM MODULE PROGRAMMER CROSS REFERENCE. (Continued)
Table 7 Footnotes
1
4 or 10 second PFEP
With S7800A1001 Keyboard Display Module
3
Select Proper Amplifier
2
Old Amplifer Replacement Amplifer
R7247A1005 R7847A1033
R7247A1021 R7847A1025
R7247B1003 R7847B1031
R7247C1001 R7861A1026 See Note 5
R7248A1004 R7848A1008
R7248B1028 R7848B1006
R7249A1003 R7849A1023
R7476A1007 R7886A1001
4
With Selectable Airflow Switch Check
Used with Existing Flame Detectors - EXCEPT - C7012E, F - Replace with C7061A, M, F and appropriate R7861 Flame Amplifier
6 Requires Q7800A or B Wiring Subbase
7 For RM7840, order S7800A1142 display seperately
5
25
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Frequency
Voltage
Modulation
Postpurge
MFEP
Spark Term
INTR Pilot
PFEP
INTM Pilot
Lo-fire
Lockout
Running
Device to be
Current
7800 Series
Lo-Fire
LHL
Replaced
Replacement Replacement Timing On-Off LHL PRV
Start
Type
Hi-fire
Interlocks
Preignition
Prepurge
Comments
BC7000L1000 None
See Program Module for Current Replacements
120
BC7000L1018 None
Consult Original Equipment Manufacturer
120
Proprietary to Cleaver
Brooks
BC7000L1034 None
Consult Original Equipment Manufacturer
120
Proprietary to Vapor
Corporation
BC7000L1042 None
Consult Original Equipment Manufacturer
120
Proprietary to YorkShipley, LWCO
annunciation on
terminal 18
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 8. HONEYWELL BC7000 PROGRAMMER CROSS REFERENCE.
26
Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE.
Interlocks
EC7810A1035
EC7810A1027
EC7810A1035
Selectable
Selectable
Selectable
X
Selectable 2-wire
using
LF Proven
ST7800B
X
Selectable 2-wire
LF Proven
X
Selectable 2-wire
LF Proven
X
Selectable 2-wire
Proven
using
LF Proven
ST7800B
X
Selectable 2-wire
Proven
using
LF Proven
ST7800B
X
Selectable 2-wire
Proven
LF Proven
X
Selectable 2-wire
Proven
LF Proven
X
Selectable 2-wire
using
LF Proven
ST7800B
X
Selectable LF Proven Proven
using
ST7800B
X
X
EC7820A1018
EC7820A1026
EC7820A1034
EC7810A1001
EC7830A1009
EC7820A1026
EC7820A1034
EC7820A1026
EC7820A1034
EC7810A1027
EC7830A1033
70-8313—02
See footnotes on page 34
Selectable
Selectable
Selectable
Selectable
Selectable
Selectable
5, 8
220
to
240
50
With 5 second Pilot and 5 second
Main Stabilization Time. FFRT 1.0
or 2.0 seconds Less Fan Output
CE Listed
X
X
X
Config X
urable
5, 10
X
X
5, 8
220
to
240
50
With 5 second Pilot and 5 second
Main Stabilization Time. FFRT 1.0
or 2.0 seconds Less Fan Output
CE Listed
Config X
urable
5, 10
X
X
5, 8
220
to
240
50/ With 5 second Pilot and 5 second
60 Main Stabilization Time. FFRT 1.0
or 2.0 seconds Less Fan Output
CE Listed
Config X
urable
5, 10
X
X
5, 8
220
to
240
50/ With 5 second Pilot and 5 second
60 Main Stabilization Time. FFRT 1.0
or 2.0 seconds Less Fan Output
CE Listed
Config X
urable
5, 10
X
X
5, 8
220
to
240
50
With 5 second Pilot and 5 second
Main Stabilization Time. FFRT 1.0
or 2.0 seconds With Fan Output
CE Listed
Config X
urable
5, 10
X
X
5, 8
220
to
240
50
With 5 second Pilot and 5 second
Main Stabilization Time. FFRT 1.0
or 2.0 seconds With Fan Output
CE Listed
Config X
urable
5, 10
X
X
5, 8
220
to
240
50/ With 5 second Pilot and 5 second
60 Main Stabilization Time. FFRT 1.0
or 2.0 seconds With Fan Output
CE Listed
Config X
urable
5, 10
X
X
5, 8
220
to
240
50/ With 5 second Pilot and 5 second
60 Main Stabilization Time. FFRT 1.0
or 2.0 seconds With Fan Output
CE Listed
Config X
urable
5, 10
X
X
5, 8
220
to
240
50
With 5 second Pilot and 5 second
Main Stabilization Time. FFRT 1.0
or 2.0 seconds Less Fan Output
CE Listed
Config X
urable
3 or 5
X
X
3 or 5
220
to
240
50
With 5 second Pilot Stabilization
Time.
FFRT 1.0 or 2.0 seconds CE Listed
4
X
X
X
4
X
X
X
4
X
X
X
4
X
X
X
4
X
X
X
4
X
X
X
4
X
X
X
4
X
X
X
4
2
Frequency
X
Voltage
X
PFEP
Postpurge
5, 10
4
27
EC7820A1000
MFEP
Config X
urable
Run/Test
Switch3
X
Lo-fire
X
Comments
PROGRAMMER CONTROL CROSS REFERENCE
Selectable 2-wire
using
LF Proven
ST7800B
Hi-fire
Airflow
INTR Pilot
EC7810A1027
EC7810A1035
Selectable
Damper
Position
INTM Pilot
EC7810A1019
EC7810A1027
1
Preignition
EC7810A1001
Timing
Lockout
Enhanced
Flame
Replacement Amplifier
Device to be
Current
option
Replaced Replacement
2
Start
Running
Type
Dynamic Air-Flow
SW Check
Prepurge
Interlocks
EC7830A1025
EC7830A1066
Selectable
Selectable LF Proven Proven
using
ST7800B
X
X
X
X
Selectable LF Proven Proven
X
EC7830A1033
EC7830A1033
Selectable
MFEP
Config X
urable
3 or 5
X
X
3 or 5
30 220
to
240
50
With 5 second Pilot Stabilization
Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
15 220
to
240
50
With 5 second Pilot Stabilization
Time.
FFRT 1.0 or 2.0 seconds CE Listed
Fulton Proprietary
Config X
urable
3 or 5
X
X
3 or 5
2
220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Fulton Proprietary
Config X
urable
3 or 5
X
X
3 or 5
15 220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
4, 10
X
10, 15 15 240
50/ Programmer control with Valve
60 Proving Feature and
Programmable Post
Purge.Requires S7800A1142
Display Module to program. With
Blinkum Fault Messaging.
Config X
urable
3 or 5
X
X
3 or 5
2
220
to
240
50
With 5 second Pilot Stabilization
Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 220
to
240
50
With 5 second Pilot Stabilization
Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
2
220
to
240
60
With 5 second Pilot Stabilization
Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 220
to
240
60
With 5 second Pilot Stabilization
Time.
FFRT 1.0 or 2.0 seconds CE Listed
PFEP
4
4
X
X
X
4
EC7830A1041
EC7830A1041
Selectable
Selectable LF Proven Proven
X
X
X
X
EC7830A1058
EC7830A1058
Selectable
Selectable LF Proven Proven
X
X
X
X
4
28
4
EC7830A1066
EC7830A1066
Selectable
Selectable LF Proven Proven
X
X
X
X
4
EC7840L1014
EC7840L1014
EC7840L1014
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
4
EC7850A1007
EC7850A1072
Selectable
Selectable 4-wire
Proven
using
LHL HF, LF
ST7800B PRV
X
X
X
X
EC7850A1015
EC7850A1080
Selectable
Selectable 4-wire
Proven
using
LHL HF, LF
ST7800B PRV
X
X
X
X
EC7850A1031
EC7850A1106
Selectable
Selectable 4-wire
Proven
using
LHL HF, LF
ST7800B PRV
X
X
X
X
Selectable 4-wire
Proven
using
LHL HF, LF
ST7800B PRV
X
EC7850A1049
EC7850A1114
See footnotes on page 34
Selectable
4
4
4
X
X
X
4
Frequency
X
Voltage
X
Postpurge
X
INTR Pilot
X
Airflow
INTM Pilot
Selectable LF Proven Proven
using
ST7800B
Damper
Position
Run/Test
Switch3
Selectable
1
Lo-fire
EC7830A1041
Timing
Hi-fire
Preignition
EC7830A1017
Enhanced
Flame
Device to be
Current
Replacement Amplifier
Replaced Replacement
option
2
Start
Running
Lockout
Type
Dynamic Air-Flow
SW Check
Prepurge
Comments
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued)
Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued)
Interlocks
EC7850A1072
Selectable
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
X
X
X
X
X
X
X
EC7850A1098
EC7850A1098
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
EC7850A1080
Selectable
3 or 5
X
X
3 or 5
30 220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
2
220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds
CE Listed Fulton Proprietary
Config X
urable
3 or 5
X
X
3 or 5
2
220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
15 220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
2
220
to
240
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds
PFEP with Early Spark Termination
(2 or 6 seconds based on
Configuration Resistor. CE Listed
220
to
240
50/ Fulton Proprietory
60 Pulse Firing
4
X
X
X
4
X
X
X
4
EC7850A1122
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
EC7850A1148
EC7850A1072
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
4
4
EC7865A1005
RM7800E1002 RM7800E1010
RM7800E1010 RM7800E1010
70-8313—02
See footnotes on page 34
Selectable
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
X
X
Comments
With 5 second Pilot Stabilization
Time.
FFRT 1.0 or 2.0 seconds
CE Listed Fulton Proprietary
Config X
urable
4, 10
X
10, 15 15 120
50
Config X
urable
4, 10
X
10, 15 15 120
50/ with Energy Saving Purge and
60 display module
4
X
Frequency
Config X
urable
Voltage
60
Postpurge
30 220
to
240
4
EC7850A1122
EC7865A1005
3 or 5
4
with Energy Saving Purge and
display module
PROGRAMMER CONTROL CROSS REFERENCE
X
29
Selectable 4-wire
Proven
LHL HF, LF
PRV
EC7850A1114
X
4
Selectable
Selectable
X
PFEP
4
EC7850A1080
EC7850A1072
3 or 5
4
EC7850A1080
EC7850A1106
MFEP
Config X
urable
Run/Test
Switch3
X
Lo-fire
X
Hi-fire
Airflow
INTR Pilot
EC7850A1072
EC7850A1064
Selectable
Damper
Position
INTM Pilot
EC7850A1064
EC7850A1098
1
Preignition
EC7850A1056
Timing
Lockout
Enhanced
Flame
Device to be
Current
Replacement Amplifier
Replaced Replacement
option
2
Start
Running
Type
Dynamic Air-Flow
SW Check
Prepurge
Interlocks
RM7800G1018 RM7800G1018 RM7840G1022 Selectable
add
S7800A1142
Display
Selectable 4-wire
LHL LF
PRV
Proven
RM7800L1004 RM7800L1012 RM7800L1087 Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
RM7800L1012 RM7800L1012 RM7800L1087 Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
RM7800L1038 RM7800L1038
Contact
OEM
Contact
OEM
4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
RM7800L1046 RM7800L1046
Contact
OEM
Contact
OEM
4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
RM7800L1053 RM7800L1053
X
X
X
X
X
X
X
X
X
50
Config X
urable
4, 10
X
X
10, 15, 15 120
30
50/ With display module
60
Config X
urable
4, 10
X
10, 15 15 120
50
Config X
urable
4, 10
X
10, 15 15 120
50/ With display module
60
Config X
urable
4, 10
X
10, 15 15 120
50/ Fulton Proprietary
60
Config X
urable
4, 10
X
10, 15 15 120
50/ Vapor Proprietary (49320086)
60
Config X
urable
4, 10
X
10, 15 15 120
50/ With display module-Intermittent
60 Pilot
Config X
urable
4, 10
X
10, 15 15 120
50/ Cleaver Brook Proprietary (83360 2719)
Config X
urable
4, 10
X
10, 15 15 120
50/ Cleaver Brook Proprietary (83360 2718)
Config X
urable
4, 10
X
10, 15 15 120
50/ Programmer control with Valve
60 Proving Feature and
Programmable Post Purge comes
with S7800A1142 display module,
With Blinkum Fault Messaging.
Config X
urable
4, 10
X
10, 15 15 120
50/ Programmer control with Valve
60 Proving Feature and
Programmable Post Purge comes
with S7800A1142 display module,
With Blinkum Fault Messaging.
Cleaver Brook Proprietary (83303517)
4
4
4
X
X
X
X
4
4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
RM7800L1079 RM7800L1079
Contact
OEM
Contact
OEM
4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
RM7800L1087 RM7800L1087
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
Contact
OEM
X
4-wire
Proven
LHL HF, LF
PRV
MFEP
Frequency
10, 15, 15 120
30
Voltage
X
Postpurge
X
PFEP
Comments
With display module
With display module
4
Contact
OEM
See footnotes on page 34
4, 10
4
Contact
OEM
Contact
OEM
Config X
urable
4
RM7800L1061 RM7800L1079
RM7800L1095 RM7800L1095
INTR Pilot
Proven
INTM Pilot
Selectable 4-wire
LHL LF
PRV
30
RM7800G1000 RM7800G1018 RM7840G1022 Selectable
add
S7800A1142
Display
Run/Test
Switch3
Airflow
Lo-fire
Damper
Position
Hi-fire
1
Preignition
Timing
Lockout
Enhanced
Flame
Device to be
Current
Replacement Amplifier
Replaced Replacement
option
2
Start
Running
Type
Dynamic Air-Flow
SW Check
Prepurge
4
4
4
X
X
X
4
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued)
Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued)
Interlocks
X
X
X
RM7800M1011 RM7800M1011
Selectable
Selectable 2-wire On- Proven
Off, LF
PRV
X
X
X
Contact
OEM
Contact
OEM
2-wire On- Proven
Off, LF
PRV
X
RM7830A1003 RM7830A1003
Selectable
Selectable LF Proven Proven
X
X
X
X
RM7830A1011 RM7830A1011
Selectable
Selectable LF Proven Proven
X
X
X
X
RM7830A1029 RM7830A1029
Selectable
Selectable LF Proven Proven
X
X
X
X
RM7800M1037 RM7800M1037
4, 10
X
X
10
15 120
50
Config X
urable
4, 10
X
X
10
15 120
50/ With display module
60
Config X
urable
4, 10
X
X
10
15 120
50/ Fulton Proprietary
60
Config X
urable
3 or 5
X
X
3 or 5
2
120
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
15 120
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 120
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
4, 10
X
10, 15 15 120
50
Config X
urable
4, 10
X
10, 15 15 120
50/ with Energy Saving Purge
60
Config X
urable
4, 10
X
X
10, 15, 15 120
30
50
Config X
urable
4, 10
X
X
10, 15, 15 120
30
50/
60
Config X
urable
4, 10
X
X
10, 15, 15 120
30
50/ Programmer control with Valve
60 Proving Feature and
Programmable Post
Purge.Requires S7800A1142
Display Module to program. With
Blinkum Fault Messaging.
Config X
urable
4, 10
X
10, 15 15 120
50
PFEP
4
X
X
4
4
31
4
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
X
X
X
4
RM7840G1006 RM7840G1014 RM7840G1022 Selectable
Selectable 4-wire
LHL LF
PRV
Proven
X
X
X
RM7840G1014 RM7840G1014 RM7840G1022 Selectable
Selectable 4-wire
LHL LF
PRV
Proven
X
X
X
Selectable 4-wire
LHL LF
PRV
Proven
RM7840G1022 RM7840G1022
Selectable
RM7840L1000 RM7840L1018 RM7840L1075 Selectable
70-8313—02
See footnotes on page 34
4
4
Selectable 4-wire
Proven
LHL HF, LF
PRV
with Energy Saving Purge
4
X
X
X
4
X
X
X
X
4
PROGRAMMER CONTROL CROSS REFERENCE
RM7840E1016 RM7840E1016
Selectable
Comments
With display module
4
4
RM7840E1008 RM7840E1016
Frequency
Config X
urable
Voltage
MFEP
Postpurge
Selectable 2-wire On- Proven
Off, LF
PRV
INTR Pilot
Selectable
INTM Pilot
RM7800M1003 RM7800M1011
Run/Test
Switch3
Airflow
Lo-fire
Damper
Position
Hi-fire
1
Preignition
Timing
Lockout
Enhanced
Flame
Device to be
Current
Replacement Amplifier
Replaced Replacement
option
2
Start
Running
Type
Dynamic Air-Flow
SW Check
Prepurge
RM7840L1026 RM7840L1026
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
Contact
OEM
Contact
OEM
4-wire
Proven
LHL HF, LF
PRV
X
Contact
OEM
Contact
OEM
4-wire
Proven
LHL HF, LF
PRV
X
RM7840L1034 RM7840L1042
RM7840L1042 RM7840L1042
Selectable
MFEP
X
10, 15 15 120
50/
60
X
10, 15 15 120
50/ Intermittent Pilot
60
4, 10
X
10, 15 15 120
50
4, 10
X
10, 15 15 120
50/ Cleaver Brook Proprietary (83360 2720)
PFEP
Config X
urable
4, 10
Config X
urable
4, 10
Config X
urable
Config X
urable
4
X
4
X
X
X
Frequency
X
Voltage
Lo-fire
X
Airflow
Postpurge
Hi-fire
X
Damper
Position
INTR Pilot
Preignition
X
1
INTM Pilot
Lockout
Selectable 4-wire
Proven
LHL HF, LF
PRV
Timing
Start
Running
RM7840L1018 RM7840L1018 RM7840L1075 Selectable
Enhanced
Flame
Device to be
Current
Replacement Amplifier
Replaced Replacement
option
2
Run/Test
Switch3
Interlocks
Type
Dynamic Air-Flow
SW Check
Prepurge
4
X
X
X
4
Comments
Cleaver Brook Proprietary (8332721)
RM7840L1059 Never Produced
Never Produced
RM7840L1067 Never Produced
Never Produced
32
RM7840L1075 RM7840L1075
RM7840L1083 RM7840L1083
RM7840L1091 RM7840L1091
RM7840M1009 RM7840M1017
RM7840M1017 RM7840M1017
See footnotes on page 34
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
Contact
OEM
Contact
OEM
4-wire
Proven
LHL HF, LF
PRV
X
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
Selectable
Selectable
X
X
X
Config X
urable
4, 10
X
10, 15 15 120
50/ Programmer control with Valve
60 Proving Feature and
Programmable Post
Purge.Requires S7800A1142
Display Module to program. With
Blinkum Fault Messaging.
Config X
urable
4, 10
X
10, 15 15 120
50/ Programmer control with Valve
60 Proving Feature and
Programmable Post
Purge.Requires S7800A1142
Display Module to program. With
Blinkum Fault Messaging. Cleaver
Brook Proprietary (833-03518)
Config X
urable
4 (fixed)
X
10, 15 15 120
50/ Programmer control with Valve
60 Proving Feature and
Programmable Post
Purge.Requires S7800A1142
Display Module to program. With
Blinkum Fault Messaging.
Config X
urable
4, 10
X
X
10
15 120
50
Config X
urable
4, 10
X
X
10
15 120
50/
60
4
X
X
X
4
X
X
X
4
Selectable 2-wire On- Proven
Off, LF
PRV
X
Selectable 2-wire On- Proven
Off, LF
PRV
X
X
X
4
X
X
4
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued)
Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued)
Lo-fire
X
X
X
Frequency
Hi-fire
X
15 120
50/
60
X
X
3 or 5
2
120
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
3 or 5
X
X
3 or 5
`5 120
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
30 120
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds CE Listed
Config X
urable
3 or 5
X
X
3 or 5
2
120
50/ With 5 second Pilot Stabilization
60 Time.
FFRT 1.0 or 2.0 seconds
PFEP with Early Spark Termination
(2 or 6 seconds based on
Configuration Resistor. CE Listed
RM7865A1009 RM7865C1007
120
50/ Fulton Proprietory
60 Pulse Firing
RM7865B1008 RM7865C1007
120
50/ Fulton Proprietory
60 Pulse Firing
RM7865C1007 RM7865C1007
120
50/ Fulton Proprietory
60 Pulse Firing
1
Damper
Position
Airflow
RM7845A1001 RM7845A1001 RM7840L1075 Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
RM7850A1001 RM7850A1001
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
RM7850A1019 RM7850A1019
Selectable
Selectable
PFEP
Config X
urable
4, 10
Config X
urable
3 or 5
Config X
urable
Voltage
10
Timing
Run/Test
Switch3
X
Enhanced
Flame
Device to be
Current
Replacement Amplifier
Replaced Replacement
option
2
Start
Running
MFEP
Postpurge
Preignition
X
INTR Pilot
Lockout
X
INTM Pilot
Interlocks
Type
Dynamic Air-Flow
SW Check
Prepurge
4
X
4
X
X
X
4
RM7850A1027 RM7850A1027
Selectable
Proven
Selectable 4-wire
LHL HF, LF
PRV
X
X
X
X
RM7850A1035 RM7850A1035
Selectable
Selectable 4-wire
Proven
LHL HF, LF
PRV
X
X
X
X
4
4
33
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
See footnotes on page 34
Comments
1
Amplifier Options
FFRT* (seconds)
Standard
Ampli-check
Rectification
Flame Rods
0.8 or 1.0
R7847A1025
R7847B1023
C7012A, C
2.0 or 3.0
R7847A1033
R7847B1031
>50 feet leadwire run
>50 feet leadwire run
R7847A1074
R7847B1064
R7847A1082
R7847B1072
0.8 or 1.0
R7849A1015
R7849B1013
2.0 or 3.0
R7849A1023
R7849B1021
Rectifier pilot burners
(Q179, C7005)
UV
C7027, C7035, C7044
Shutter-Check UV Detector
34
C7012E, F
2.0 or 3.0
R7847C1005
C7061A, M, F
0.8 or 1.0
R7861A1034
2.0 or 3.0
R7861A1026
C7076A, D
2.0 or 3.0
R7886A1001
C7961E, F
2.0 or 3.0
R7851C1008
Optical
C7927 (UV)
0.8 or 1.0
R7851B1018
C7962 (Visible)
2.0 or 3.0
R7851B1000
Infrared
C7915
2
3
4
2.0 or 3.0
R7852A1001
R7852B1009
*Flame Failure Response Time
Purge Timer Options
Timing
ST7800
Timing
ST7800
2 seconds
A1005
2.5 Minute
A1070
7 seconds
A1013
4 Minute
A1088
10 seconds
A1021
6 Minute
A1096
30 seconds
A1039
9 Minute
A1104
40 seconds
A1047
12 Minute
A1112
60 seconds
A1054
15 Minute
A1120
90 seconds
A1062
22 Minute
A1138
30 Minute
A1146
Flame-out timer used with Run/Test Switch. Allows pilot to be momentarily extinguished and caused LOCKOUT if total no flame time exceeds 15 seconds.
Selected with Configuration Resistor, See instruction sheet.
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 9 7800 PROGRAMMER SERIES FOOTNOTES:
Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE.
24PJ8 1000
2 6 10 14
2 6 11
RM7840G1014 or RM7840L1018 or
RM7840G1022
RM7840L1075
Amplifier
R7847A1033
Purge Timer
ST7800A1005
Timing
0
None
25RU8 4580 NONE
RM7840L1018 or 18
R7861A1026
RM7840L1075
ST7800A1054
(60 seconds)
47
On-Off,
LF Proving
25RU8 6558
10 14
10
ST7800A1039
(30 seconds)
33
3-wire,
LHL,
LF Proving
25RU8 6560
14
RM7840L1018 or 18
RM7840G1014 or RM7840L1075
R7849A1015
RM7840G1022
(0.8 FFRT)
R7849A1023
(3.0 FFRT)
ST7800A1054
60
24RU8 6566
14
RM7840L1018 or 18
RM7840G1014 or RM7840L1075
R7849A1023
RM7840G1022
ST7800A1039
35
24RJ8 1000 None
18
15, 30
Frequency
Voltage
Postpurge
Spark Term
INTR Pilot
MFEP
PFEP
X
60
RM7840G1014 or RM7840L1018 or R7849A1023
RM7840G1022
RM7840L1075
INTM Pilot
Hi-fire
Lo-fire
Lockout
Type
On-Off,
LF Proving
Preignition
Interlocks
Start
Prepurge
Running
Replacement Control
7800 Series
Replacement
Current
to meet
Device to Replacement to
Insurance
be
meet UL
1 4 5 7 9 11 12
Replaced 1 4 5 7 8 12 17
13 17
X
Comments
15
0
115
230
50/60
Rectification type flame
sensor, low voltage
controller, vacuum tube.
80 120
50/60
1-4 sec FFRT, low voltage
special for air heaters,
vacuum tube electronics.
20 120
50/60
4 sec FFRT, used with selfcheck UV flame detector
X
X
8
X
10, 15
X
X
7
X
10, 60
X
15 120
50/60
4 sec FFRT, UV type flame
detector.
4-wire
LHL,
LF Proving
X
X
7
X
15, 40
X
10 120
50/60
1-4 sec FFRT, UV type
flame detector.
30
2-wire
On-Off,
LF Proving
X
X
10
X
15, 25
10 120
50/60
4 sec FFRT, UV type flame
detector.
X
X
X
7
X
15, 30
X
15 120
50/60
4 sec FFRT, UV type flame
detector.
X
X
10
X
10, 15,
30
X
20 120
50/60
1-2 sec FFRT, UV type
flame detector.
X
X
X
X
25RU8 6570 NONE
RM7840L1018 or 18
R7849A1023
RM7840L1075
ST7800A1054
(60 seconds)
63
4-wire
LHL,
HF, LF
Proving
25RU8 6580 NONE
RM7840L1018 or 18
R7849A1015
RM7840L1075
ST7800A1054
(60 seconds)
45
4-wire
LHL,
HF & LF
Proving
26RJ8 1000
2 6 14
2 6
18
ST7800A1039
30
3-wire,
LHL,
LF Proving
X
10
X
15
30 115
230
50/60
4 sec FFRT, IR type flame
detector, low voltage
controller.
26RJ8 1001
2 6 14
2 6
18
ST7800A1039
30
4-wire
LHL,
LF Proving
X
10
X
15
30 115
230
50/60
Orr and Sewbower
special, IR type flame
detector, low voltage
controller.
30
On-Off,
LF Proving
X
10
X
15
30 115
230
50/60
Cleaver Brooks special, 4
sec FFRT, IR type flame
detector, low voltage
controller.
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
26RJ8 1002 Cleaver Brook
Proprietary
See footnotes on page 40
X
X
X
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
7
Amplifier
Purge Timer
Timing
Type
PFEP
Frequency
Voltage
Postpurge
Spark Term
INTR Pilot
INTM Pilot
Hi-fire
Lo-fire
Lockout
Preignition
Interlocks
Start
Prepurge
Running
Replacement Control
7800 Series
Replacement
Current
to meet
Device to Replacement to
Insurance
be
meet UL
1 4 5 7 9 11 12
Replaced 1 4 5 7 8 12 17
13 17
MFEP
Comments
36
26RJ8 1003
2 6 14
2 6
18
ST7800A1039
30
On-Off,
LF Proving
X
10
X
10
60 115
230
50/60
North America special, 4
sec FFRT, IR type flame
detector, low voltage
controller.
26RJ8 1004
6 14
6
18
ST7800A1039
30
On-Off,
LF Proving
X
10
X
60
15 115
230
50/60
4 sec FFRT, IR type flame
detector, B&W FM boiler
special, vacuum tube
circuitry.
26RJ8 1005
6
6
18
ST7800A1039
30
On-Off,
LF Proving
X
10
X
10
60 115
230
50/60
4 sec FFRT, IR type flame
detector, B&W FM boiler
special, vacuum tube
circuitry.
26RJ8 1006
2 6 10 14
2 6 10
18
ST7800A1039
30
On-Off,
LF Proving
X
10
X
15
30 115
230
50/60
4 sec FFRT, IR type flame
detector, low voltage
controller, vacuum tube
circuitry.
26RJ8 1008
2 6 14
2 6
18
ST7800A1039
30
On-Off,
LF Proving
X
10
X
15, 60
15 115
230
50/60
4 sec FFRT, IR type flame
detector, low voltage
controller, vacuum tube
circuitry.
26RJ8 1009
2 6 14
2 6
18
ST7800A1039
30
On-Off,
LF Proving
X
10
X
10, 15
60 115
230
50/60
4 sec FFRT, IR type flame
detector, low voltage
controller, vacuum tube
circuitry.
26RJ8 1011
2 6 10 14
2 6 10
18
ST7800A1005
(2 seconds)
0
On-Off,
LF Proving
X
10
X
10, 55
30 115
230
50/60
North America special, IR
type flame detector, low
voltage controller, vacuum
tube circuitry.
2 3 6
3 18
26RJ8 1012 2 3 6 14
RM7840G1014 or RM7840L1018 or R7852A1001
26RJ8
RM7840G1022
RM7840L1075
(3.0 sec)
1012T
ST7800A1047
(40 seconds)
35
4-wire
LHL,
LF Proving
10
X
15
25 115
230
50/60
North America special,
dual IR type flame
detectors, vacuum tube
circuitry.
2 3 6
3 18
26RJ8 1016 2 3 6 14
RM7840G1014 or RM7840L1018 or R7852A1001
26RJ8
RM7840G1022
RM7840L1075
(3.0 sec)
1016T
ST7800A1062
(90 seconds)
65
10
X
15
10 115
230
50/60
1 sec FFRT, dual IR type
flame detectors, vacuum
tube circuitry.
26RJ8 1018
ST7800A1054
(60 seconds)
45
4-wire
LHL,
LF Proving
10
X
15, 30
15 115
230
50/60
2-4 sec FFRT, IR type
flame detectors, low
voltage controller, vacuum
tube circuitry
45
4-wire
LHL,
LF Proving
10
X
15, 30
15 120
208
240
50/60
U.S. Navy special, no
replacement
available,voltage
controller, vacuum tube
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840M1017
RM7840L1018 or R7852A1001
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
2 6 14
2 6
18
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
26RJ8 1114, NONE
26RJ8 1115,
26RJ8 5914
See footnotes on page 40
NONE
X
X
X
X
X
X
X
X
X
X
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued)
Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued)
Amplifier
Purge Timer
Timing
Type
37
26RJ8 6008
2 6 14
2 6
18
ST7800A1047
(40 seconds)
35
3-wire,
LHL,
LF Proving
X
26RJ8 6009
2 6 14 15
2 6
18
ST7800A1047
(40 seconds)
35
On-Off,
LF Proving
26RJ8 6012
2 3 6
2 3 6
3 18
ST7800A1047
(40 seconds)
35
26RJ8 6016
2 3 6
2 3 6
3 18
ST7800A1062
(90 seconds)
26RJ8 6018
2 10 14
2 10
18
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840M1017
RM7840L1018 or R7852A1001
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
PFEP
Frequency
Voltage
Postpurge
MFEP
Comments
X
15, 55
15 120
208
240
60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
X
10
X
15
55 120
208
240
50/60
B&W FM boiler special, 14 sec FFRT, IR type flame
detector, low voltage
controller, vacuum tube
circuitry.
4-wire
LHL,
LF Proving
X
10
X
15
30 120
208
240
50/60
1-4 sec FFRT, dual IR type
flame detectors, low
voltage controller, vacuum
tube circuitry.
65
4-wire
LHL,
LF Proving
X
10
X
15
15 120
208
240
50/60
1-4 sec FFRT, dual IR type
flame detectors, low
voltage controller, vacuum
tube circuitry.
ST7800A1054
(60 seconds)
45
4-wire
LHL,
LF Proving
X
15, 30
15 120
208
240
50/60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
ST7800A1054
60
On-Off,
LF Proving
15
80 120
60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, special
for air heaters
X
X
10
X
X
7
26RJ8 6026 NONE
NONE
26RJ8 6058
10 14
10
18
ST7800A1047
(40 seconds)
35
3-wire,
LHL,
LF Proving
X
X
X
10
X
15, 55
15 120
60
1-4 sec FFRT, IR type
flame detector, vacuum
tube circuitry.
26RJ8 6060
10 14
10
18
ST7800A1054
60
4-wire
LHL,
LF Proving
X
X
X
7
X
10, 30
20 120
50/60
1-4 sec FFRT, IR type
flame detector, vacuum
tube circuitry.
26RJ8 6066
10 14
10
18
ST7800A1039
30
On-Off,
LF Proving
X
X
X
10
X
15, 25
10 120
50/60
1-4 sec FFRT, IR type
flame detector, vacuum
tube circuitry.
26RJ8 6068
10 14
10
18
ST7800A1054
(60 seconds)
45
4-wire
LHL,
LF Proving
X
X
10
X
15, 30
15 120
60
1-4 sec FFRT, IR type
flame detector, vacuum
tube circuitry, for Canada.
ST7800A1062
(90 seconds)
65
4-wire
LHL,
HF & LF
Proving
10
X
15, 30
15 120
60
1-4 sec FFRT, IR type
flame detector, vacuum
tube circuitry.
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
26RJ8 6070 NONE
70-8313—02
See footnotes on page 40
RM7840L1018 or 18
R7852A1001
RM7840L1075
(3.0 sec)
X
X
X
X
PROGRAMMER CONTROL CROSS REFERENCE
10
X
X
Spark Term
INTR Pilot
INTM Pilot
Hi-fire
Lo-fire
Lockout
Preignition
Interlocks
Start
7800 Series
Replacement
Current
to meet
Device to Replacement to
Insurance
be
meet UL
1 4 5 7 9 11 12
Replaced 1 4 5 7 8 12 17
13 17
Prepurge
Running
Replacement Control
45
4-wire
LHL,
HF & LF
Proving
26RJ8 6160
14
RM7840L1018 or 18
RM7840G1014 or RM7840L1075
R7852A1001
RM7840G1022
(3.0 sec)
ST7800A1054
60
4-wire
LHL,
LF Proving
X
26RJ8 CB-1 Cleaver Brook
Proprietary
45
4-wire
LHL,
LF Proving
X
26RJ8 CB-3 Cleaver Brook
Proprietary
45
4-wire
LHL,
HF & LF
Proving
1-2 sec FFRT, IR type
flame detector, vacuum
tube circuitry.
X
7
X
10, 30
X
20 120
50/60
1-4 sec FFRT, IR type
flame detector, vacuum
tube circuitry.
X
10
X
15
15 120
50/60
Cleaver Brooks special, IR
type flame detector, low
voltage controller.
X
10
X
10, 15,
30
20 120
50/60
Cleaver Brooks special, IR
type flame detector, low
voltage controller.
X
10
15 115
230
50/60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
X
13
15 115
230
50/60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
PFEP
X
X
X
X
Frequency
50/60
X
Voltage
20 120
X
INTR Pilot
X
X
INTM Pilot
Postpurge
ST7800A1054
(60 seconds)
10, 15,
30
Hi-fire
RM7840L1018 or 18
RM7840G1014 or RM7840L1075
R7852A1001
RM7840G1022
(3.0 sec)
X
X
Type
14
10
Lo-fire
Timing
Lockout
Purge Timer
Preignition
Amplifier
26RJ8 6080
Spark Term
Interlocks
Start
Prepurge
Running
Replacement Control
7800 Series
Replacement
Current
to meet
Device to Replacement to
Insurance
be
meet UL
1 4 5 7 9 11 12
Replaced 1 4 5 7 8 12 17
13 17
MFEP
Comments
29RF5 1000
2 6 10 14
2 6 10
18
ST7800A1039
(30 seconds)
15
On-Off,
LF Proving
X
X
5
29RF5 1001
2 6 10 14
2 6 10
18
ST7800A1039
(30 seconds)
25
On-Off,
LF Proving
X
X
7
29RF5 1002
2 6 10 14
2 6 10
18
ST7800A1039
(30 seconds)
15
On-Off,
LF Proving
X
X
5
X
15
15 115
230
50/60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
29RF5 1005
2 6 14
2 6
18
ST7800A1039
(30 seconds)
15
On-Off,
LF Proving
X
5, 10
X
15
15 115
230
50/60
2-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
29RF5 1009
2 6 10 14
2 6 10
18
ST7800A1039
(30 seconds)
25
On-Off,
LF Proving
X
7
X
13
15 114
230
50/60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
29RF5 1015
2 6 14
2 6
18
ST7800A1039
(30 seconds)
15
On-Off,
LF Proving
X
5, 10
X
15
15 115
230
50/60
2-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
15
On-Off,
LF Proving
X
5
X
15
15 115
230
50/60
Military special, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
38
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
29RF5 1103 NONE
See footnotes on page 40
NONE
X
X
X
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued)
Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued)
Purge Timer
Timing
Type
2 6 14
2 6
18
ST7800A1013
(7 seconds)
5
On-Off,
LF Proving
29RF5 6009
2 6 10 14
2 6 10
18
ST7800A1039
(30 seconds)
25
On-Off,
LF Proving
29RF5 6015
2 6 10 14
2 6 10
18
ST7800A1039
(30 seconds)
18
On-Off,
LF Proving
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
RM7840G1014 or RM7840L1018 or R7852A1001
RM7840G1022
RM7840L1075
(3.0 sec)
NONE
PFEP
X
5
X
X
7
X
X
5, 10
Frequency
Voltage
Postpurge
Spark Term
INTR Pilot
INTM Pilot
Hi-fire
Lo-fire
Lockout
Preignition
Amplifier
29RF5 1104
29RF5 6103 NONE
Interlocks
Start
7800 Series
Replacement
Current
to meet
Device to Replacement to
Insurance
be
meet UL
1 4 5 7 9 11 12
Replaced 1 4 5 7 8 12 17
13 17
Prepurge
Running
Replacement Control
MFEP
X
X
X
Comments
15
15 115
230
50/60
A.E.C. Kilns special, IR
type flame detector, low
voltage controller, vacuum
tube circuitry.
13
15 120
208
240
60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
15
12 120
208
240
60
1-4 sec FFRT, IR type
flame detector, low
voltage controller, vacuum
tube circuitry.
Military special, IR type
flame detector, vacuum
tube circuitry.
See footnotes on page 40
39
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
1
Refer to Modernization Wiring Information for conversion wiring information.
Low Voltage controller will need to be upgraded to line voltage controller.
3 Replacement suggestion does not support dual IR detector feature, be sure to confirm application requirements.
4
Replacement control has 15 second postpurge.
5 Replacement control has 15 second postpurge, RM7840G1022 or RM7840L1075 have programmable postpurge option.
6 Replacement suggestion is 120 Vac, 50/60 Hz.
7 Requires Q7800A or Q7800B Wiring Subbase.
8 RM7840G,M meets current UL requirements.
9 RM7840L meets current insurance requirements.
10 Start interlocks become running interlocks using the replacment controls. (Required to start the equiment, and maintained throughout the call for heat).
11 Running Interlocks become lockout interlocks. (Opening interlock results in safety shutdown and control reset).
12 Replacement control has 10 second PFEP, 4 seconds available with JR1 clipped
13
Replacement has 10, 15 second MFEP.
14 Replacement has 10, 15, 30 second MFEP or intermittent pilot.
15 Replacement has 10 second MFEP or intermittent pilot.
16 5 second ignition early spark termination when ignition wired to terminal 10.
17 Display Module is available by ordering model shown in the table, or ordering seperately.
2
Suggestion Model
Display Model
40
RM7840M1017
RM7800M1011
RM7840G1014
RM7800G1018
RM7840G1022
Order S7800A1142 seperately
RM7840L1018
RM7800L1012
RM7840L1075
RM7800L1087
R7120D
Order S7800A1001 seperately
18 Select
appropriate flame detector and amplifier from table
Flame Detection
Type
FFRT
0.8 sec
3.0 sec
Comments
Rectification
R7847A1025 R7847A1033 Use existing Flame Rod
Ultraviolet
R7849A1015 R7849A1023 Order Honeywell flame detector C7027 or C7035
Infrared
Self Check UV
R7852A1001 Order Honeywell flame detector C7915
C7861A1034 R7861A1026 Order Honeywell flame detector C7061
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 10 FIREYE FOOTNOTES:
Table 11. FIREYE® C SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE.
Amplifier
Purge Timer Timing
Type
10
10
R7847A1033
ST7800A1047
(40 seconds)
33
On-Off,
X X
LF Proving
7
X
24CJ5 3000
10
10
R7847A1033
ST7800A1039
30
On-Off,
X X
LF Proving
7
X
24CJ5 3010
10
10
R7847A1033
ST7800A1047
(40 seconds)
37
On-Off,
X X
LF Proving
X
7
24CJ5 3011
10
10
R7847A1025
RM7840M1017 RM7840L1018 (0.8 FFRT)
or
R7847A1033
RM7840L1075 (3.0 FFRT)
ST7800A1070
(2.5 minutes)
98
On-Off,
X X
LF Proving
X
24CJ5 3014
10,14
10
R7847A1025
RM7840G1014 RM7840L1018 (0.8 FFRT)
or
or
R7847A1033
RM7840G1022 RM7840L1075 (3.0 FFRT)
ST7800A1054
60
3-wire,
X X
LHL,
LF Proving
RM7840M1017 RM7840L1018
or
RM7840L1075
RM7840M1017 RM7840L1018
or
RM7840L1075
Frequency
Voltage
Modulation
Postpurge
MFEP
PFEP
24CJ5 1000
RM7840M1017 RM7840L1018
or
RM7840L1075
Spark Term
Interlocks
INTM Pilot
INTR Pilot
Prepurge
Start
Running
Lockout
Preignition
Hi-fire
Lo-fire
Replacement Control
7800 Series
Current
Replacement
Current Plug Replacement
to meet
In
to meet UL
Insurance
Device to be Replacement 1 4 5 7 8 12 1 4 5 7 9 11
Replaced
12 13 17
17
17
Comments
10
X
8
120 50/ 4 sec FFRT,
60 rectification type
flame sensor,
vacuum tube
circuitry.
41
10
X
15
120 60
2-4 sec FFRT,
rectification type
flame sensor.
X
10
X
15
120 60
2-4 sec FFRT,
rectification type
flame sensor.
7
X
10
X
25
120 60
1-4 sec FFRT,
rectification type
flame sensor.
X
7
X
10
20 3-wire 120 60
1-4 sec FFRT,
rectification type
flame sensor.
R7120D3007
10
10
R7847A1025
RM7840M1017 RM7840L1018 (0.8 FFRT)
or
R7847A1033
RM7840L1075 (3.0 FFRT)
ST7800A1047
(40 seconds)
37
On-Off,
X X
LF Proving
X
5
X
10
X
15
120 60
1-4 sec FFRT,
rectification type
flame sensor.
24CJ5 5011
R7120D3007
10
10
R7847A1025
RM7840M1017 RM7840L1018 (0.8 FFRT)
or
R7847A1033
RM7840L1075 (3.0 FFRT)
ST7800A1070
(2.5 minutes)
98
On-Off,
X X
LF Proving
X
5
X
10
X
25
120 60
1-4 sec FFRT,
rectification type
flame sensor.
24CJ5 5015
R7120D2000
14
RM7840L1018 R7847A1033
RM7840G1014 or
or
RM7840L1075
RM7840G1022
ST7800A1054
60
4-wire,
LHL,
LF Proving
X
X
X
7
X
10, 15
15 4- wire 120 50/ 4 sec FFRT,
60 rectification type
flame sensor.
24RJ8 1000
R7120D2000
14
RM7840L1018 R7847A1033
RM7840G1014 or
or
RM7840L1075
RM7840G1022
ST7800A1054
60
4-wire,
LHL,
LF Proving
X
X
X
7
X
10, 15
15 4- wire 120 50/ 4 sec FFRT,
60 rectification type
flame sensor.
10
ST7800A1039
30
On-Off,
X X
LF Proving
25CU6 1050
70-8313—02
See footnotes on page 44
10
18
RM7840M1017 RM7840L1018 R7849A1023
or
RM7840L1075
7
X
10
X
15
120 60
4 sec FFRT, UV
type flame
detector.
PROGRAMMER CONTROL CROSS REFERENCE
24CJ5 5010
Replacement Control
Interlocks
ST7800A1047
(40 seconds)
37
On-Off,
X X
LF Proving
X
7
X
10
X
15
120 60
1-4 sec FFRT, UV
type flame
detector.
25CU6 1063
10
10
18
ST7800A1070
(2.5 minutes)
98
On-Off,
X X
LF Proving
X
7
X
10
X
25
120 60
1-4 sec FFRT, UV
type flame
detector.
25CU6 1065
10
10
18
ST7800A1054
60
3-wire,
X X
LHL,
LF Proving
X
7
X
10
20 3-wire 120 60
1-4 sec FFRT, UV
type flame
detector.
120 60
1-4 sec FFRT, UV
type flame
detector.
120 60
1-4 sec FFRT, UV
type flame
detector.
Amplifier
RM7840M1017 RM7840L1018 R7849A1015
or
(0.8 FFRT)
RM7840L1075 R7849A1023
(3.0 FFRT)
RM7840M1017 RM7840L1018 R7849A1015
or
(0.8 FFRT)
RM7840L1075 R7849A1023
(3.0 FFRT)
RM7840G1014 RM7840L1018 R7849A1015
or
or
(0.8 FFRT)
RM7840G1022 RM7840L1075 R7849A1023
(3.0 FFRT)
Purge Timer Timing
Type
PFEP
Frequency
18
Voltage
10
Modulation
10
INTM Pilot
INTR Pilot
25CU6 1062
Start
Running
Lockout
Preignition
Hi-fire
Lo-fire
Postpurge
Prepurge
Spark Term
7800 Series
Current
Replacement
Current Plug Replacement
to meet
In
to meet UL
Insurance
Device to be Replacement 1 4 5 7 8 12 1 4 5 7 9 11
Replaced
17
12 13 17
17
MFEP
Comments
R7120D3007
10
10
18
ST7800A1047
(40 seconds)
37
On-Off,
X X
LF Proving
X
7
X
10
X
25CU6 5063
R7120D3007
10
10
18
ST7800A1070
(2.5 minutes)
98
On-Off,
X X
LF Proving
X
7
X
10
X
25CU6 5065
25CU6 5065A
R7120D1002
18
RM7840L1018 10
RM7840L1018 R7849A1023
or
RM7840L1075 or
RM7840L1075
ST7800A1054
60
4-wire
LHL,
HF & LF
Proving
X
7
X
10, 15
20 4-wire 120 50/ 4 sec FFRT, UV
60 type flame
detector.
25CU6 5066
25CU6 5066A
R7120D1002
18
RM7840G1014 10
RM7840L1018 R7849A1023
or
RM7840G1022 or
RM7840L1075
ST7800A1054
60
3-wire,
LHL,
LF Proving
X
7
X
10, 30
15 4-wire 120 50/ 4 sec FFRT, UV
60 type flame
detector.
25CU6 RS-2
25CU6 RS-2D
10
10
18
ST7800A1039
30
On-Off,
X X
LF Proving
X
10
X
15
120 60
Ray Burner
special, 4 sec
FFRT, UV type
flame detector.
25CU6 RS-2RE R7120D3007
10
10
18
ST7800A1070
(2.5 minutes)
98
On-Off,
X X
LF Proving
X
25
120 60
Ray Burner
special, 1-4 sec
FFRT, UV type
flame detector.
26CF6 1000
10
10
18
ST7800A1039
30
On-Off,
X X
LF Proving
15
120 50/ 1-4 sec FFRT, IR
60 type flame
detector.
42
25CU6 5062
See footnotes on page 44
RM7840M1017 RM7840L1018 R7849A1015
or
(0.8 FFRT)
RM7840L1075 R7849A1023
(3.0 FFRT)
RM7840M1017 RM7840L1018 R7849A1015
or
(0.8 FFRT)
RM7840L1075 R7849A1023
(3.0 FFRT)
RM7840M1017 RM7840L1018 R7849A1023
or
RM7840L1075
RM7840M1017 RM7840L1018 R7849A1023
or
RM7840L1075
RM7840M1017 RM7840L1018 R7852A1001
or
(3.0 sec)
RM7840L1075
X
X
X
X
X
7
X
X
5
X
10
X
7
X
10
25
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 11. FIREYE® C SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued)
Table 11. FIREYE® C SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued)
Amplifier
Purge Timer Timing
Type
PFEP
MFEP
Frequency
Voltage
Modulation
Postpurge
Spark Term
Interlocks
INTM Pilot
INTR Pilot
7800 Series
Current
Replacement
Current Plug Replacement
to meet
In
to meet UL
Insurance
Device to be Replacement 1 4 5 7 8 12 1 4 5 7 9 11
Replaced
17
12 13 17
17
Prepurge
Start
Running
Lockout
Preignition
Hi-fire
Lo-fire
Replacement Control
Comments
26CF6 1010
10
10
18
ST7800A1047
(40 seconds)
37
On-Off,
X X
LF Proving
X
7
X
10
X
15
120 50/ 1-4 sec FFRT, IR
60 type flame
detector.
26CF6 1011
10
10
18
ST7800A1070
(2.5 minutes)
98
On-Off,
X X
LF Proving
X
7
X
10
X
25
120 50/ 1-4 sec FFRT, IR
60 type flame
detector.
26CF6 1012
10 14
10
18
ST7800A1054
60
X X
3-wire,
LHL,
LF Proving
X
7
X
10
20
120 50/ 1-4 sec FFRT, IR
60 type flame
detector.
RM7840M1017 RM7840L1018 R7852A1001
or
(3.0 sec)
RM7840L1075
RM7840M1017 RM7840L1018 R7852A1001
or
(3.0 sec)
RM7840L1075
RM7840G1014 RM7840L1018 R7852A1001
or
or
(3.0 sec)
RM7840G1022 RM7840L1075
10
10
18
ST7800A1047
(40 seconds)
37
On-Off,
X X
LF Proving
X
X
10
X
26CF6 5021
R7120D3007
10
10
18
ST7800A1070
(2.5 minutes)
98
On-Off,
X X
LF Proving
X
X
10
X
26CF6 5022
26CF6 5022A
R7120D1002
NONE
RM7840L1018 18
R7852B1009
or
RM7840L1075 (3.0 sec)
ST7800A1054
60
4-wire
LHL,
HF & LF
Proving
X
26CF6 5023
26CF6 5023A
R7120D2000
14
RM7840L1018 18
RM7840G1014 or
R7852A1001
or
RM7840L1075 (3.0 sec)
RM7840G1022
ST7800A1054
60
4-wire
LHL,
LF Proving
X
RM7840L1018 18
RM7840G1014 or
R7852A1001
or
RM7840L1075 (3.0 sec)
RM7840G1022
ST7800A1054
60
4-wire
LHL,
LF Proving
X
26CF6 RC-3A
See footnotes on page 44
RM7840M1017 RM7840L1018 R7852A1001
or
(3.0 sec)
RM7840L1075
RM7840M1017 RM7840L1018 R7852A1001
or
(3.0 sec)
RM7840L1075
14
X
X
X
120 50/ 1-4 sec FFRT, IR
60 type flame
detector.
25
120 50/ 1-4 sec FFRT, IR
60 type flame
detector.
10, 15
20
120 50/ With
60 AUTOCHECK
feature, same as
Honeywell
R7852B AMPLICHECK™.
X
7
X
X
7
X
10, 30
15
120 50/ 4 sec FFRT, IR
60 type flame
detector.
X
X
7
X
10, 30
15
120 50/ Ray Burner
60 special, 2 sec
FFRT.
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
R7120D3007
43
26CF6 5020
1
Refer to Modernization Wiring Information for conversion wiring information.
Low Voltage controller will need to be upgraded to line voltage controller.
3 Replacement suggestion does not support dual IR detector feature, be sure to confirm application requirements.
4
Replacement control has 15 second postpurge.
5 Replacement control has 15 second postpurge, RM7840G1022 or RM7840L1075 have programmable postpurge option.
6 Replacement suggestion is 120 Vac, 50/60 Hz.
7 Requires Q7800A or Q7800B Wiring Subbase.
8 RM7840G,M meets current UL requirements.
9 RM7840L meets current insurance requirements.
10 Start interlocks become running interlocks using the replacment controls. (Required to start the equiment, and maintained throughout the call for heat).
11 Running Interlocks become lockout interlocks. (Opening interlock results in safety shutdown and control reset).
12 Replacement control has 10 second PFEP, 4 seconds available with JR1 clipped
13
Replacement has 10, 15 second MFEP.
14 Replacement has 10, 15, 30 second MFEP or intermittent pilot.
15 Replacement has 10 second MFEP or intermittent pilot.
16 5 second ignition early spark termination when ignition wired to terminal 10.
17 Display Module is available by ordering model shown in the table, or ordering seperately.
2
Suggestion Model
Display Model
44
RM7840M1017
RM7800M1011
RM7840G1014
RM7800G1018
RM7840G1022
Order S7800A1142 seperately
RM7840L1018
RM7800L1012
RM7840L1075
RM7800L1087
R7120D
Order S7800A1001 seperately
18 Select
appropriate flame detector and amplifier from table.
FFRT
Flame Detection Type
0.8 sec
3.0 sec
Comments
R.ectification
R7847A1025 R7847A1033 Use existing Flame Rod
Ultraviolet
R7849A1015 R7849A1023 Order Honeywell flame detector C7027 or C7035
Infrared
Self Check UV
R7852A1001 Order Honeywell flame detector C7915
C7861A1034 R7861A1026 Order Honeywell flame detector C7061
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 11 FIREYE FOOTNOTES:
Table 12. FIREYE® D SERIES PROGRAMMER TO HONEYWELL CROSS REFERENCE.
Frequency
Voltage
Postpurge
Early Spark Term
Hi-fire
RM7840L1018 R7847A1033 ST7800A1054 60
or
RM7840L1075
4-wire
LHL,
HF & LF Proving
X
X
X
X
10
X
10, 15 X
15 120 50/ 4 sec FFRT, rectification
60 type flame detector,
solid state circuitry.
D10-5022 R7120D1002
ST7800A1054 60
RM7840L1018 18
R7852B1009
or
RM7840L1075
4-wire
LHL,
HF & LF Proving
X
X
X
X
10
X
10, 15 X
15 120 50/ 4 sec FFRT, IR type
60 flame detector, auto
check amplifier, solid
state circuitry.
D10-5065 R7120D1002
ST7800A1054 60
RM7840L1018 18
R7849A1023
or
RM7840L1075
4-wire
LHL,
HF & LF Proving
X
X
X
X
10
X
10, 15 X
15 120 50/ 4 sec FFRT, UV type
60 flame detector, solid
state circuitry.
X
X
X
10
X
10, 15 X
15 120 50/ 4 sec FFRT, rectification
60 type flame detector,
solid state circuitry.
Start
D10-5016 R7120D1002
Amplifier
Purge Timer Timing
Running
Lo-fire
INTR Pilot
Interlocks
Lockout
Prepurge
Preignition
7800 Series
Functional
Replacement
to Meet
Current Plug 7800 Series
Device to
Functional
Insurance
In
be
Needs
Replacement Replacement
Replaced
17
1 7 9 16 17
1 7 8 16 17
INTM Pilot
Functional Replacement
Type
MFEP
PFEP
Comments
45
14
14
RM7840L1018 R7847A1033 ST7800A1054 60
RM7840G1014 or
or
RM7840L1075
RM7840G1022
4-wire
LHL,
LF Proving
D20-5023
14
14
RM7840L1018 18
ST7800A1054 60
RM7840G1014 or
R7852A1001
or
RM7840L1075
RM7840G1022
4-wire
LHL,
LF Proving
X
X
X
X
10, 15 X
15 120 50/ 4 sec FFRT, IR type
60 flame detector, solid
state circuitry.
D20-5066
14
14
RM7840L1018 18
ST7800A1054 60
RM7840G1014 or
R7849A1023
or
RM7840L1075
RM7840G1022
4-wire
LHL,
LF Proving
X
X
X
X
10, 15 X
15 120 50/ 4 sec FFRT, UV type
60 flame detector, solid
state circuitry.
R7120D2000
R7120D2000
R7120D2000
D30-5010 R7120D3007
RM7840M1017
13
R7847A1033 ST7800A1039 30
On-Off,
LF Proving
X
X
X
X
X
10
X
15 120 50/ 4 sec FFRT, rectification
60 type flame detector,
solid state circuitry.
D30-5011 R7120D3007
RM7840M1017
13
R7847A1033 ST7800A1062 90
On-Off,
LF Proving
X
X
X
X
X
10
X
15 120 50/ 4 sec FFRT, rectification
60 type flame detector,
solid state circuitry.
See footnotes on page 47
RM7840L1018
or
RM7840L1075
RM7840L1018
or
RM7840L1075
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
D20-5015
Interlocks
X
X
X
10
X
15 120 50/ 4 sec FFRT, IR type
60 flame detector, solid
state circuitry.
D30-5021 R7120D3007
RM7840M1017
13
18
ST7800A1062 90
On-Off,
LF Proving
X
X
X
X
X
10
X
15 120 50/ 4 sec FFRT, IR type
60 flame detector, solid
state circuitry.
D30-5062 R7120D3007
RM7840M1017
13
18
ST7800A1039 30
On-Off,
LF Proving
X
X
X
X
X
10
X
15 120 50/ 4 sec FFRT, IR type
60 flame detector, solid
state circuitry.
D30-5063
RM7840M1017 RM7840L1018
or
RM7840L1075
X
X
10
X
15 120 50/ 4 sec FFRT, IR type
60 flame detector, solid
state circuitry.
46
See footnotes on page 47
RM7840L1018 R7852A1001
or
RM7840L1075
RM7840L1018 R7852A1001
or
RM7840L1075
RM7840L1018 R7852A1001
or
RM7840L1075
PFEP
7
MFEP
Frequency
X
Voltage
X
Type
Postpurge
On-Off,
LF Proving
Purge Timer Timing
Hi-fire
ST7800A1039 30
Amplifier
Lo-fire
18
Lockout
13
Preignition
RM7840M1017
Start
D30-5020 R7120D3007
Running
INTR Pilot
Prepurge
INTM Pilot
7800 Series
Functional
Replacement
to Meet
Current Plug 7800 Series
Device to
Functional
Insurance
In
be
Needs
Replacement Replacement
Replaced
1 7 8 16 17
17
1 7 9 16 17
Early Spark Term
Functional Replacement
Comments
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 12. FIREYE® D SERIES PROGRAMMER TO HONEYWELL CROSS REFERENCE. (Continued)
Table 12 FIREYE FOOTNOTES:
1
Refer to Modernization Wiring Information for conversion wiring information.
Low Voltage controller will need to be upgraded to line voltage controller.
3
Replacement suggestion does not support dual IR detector feature, be sure to confirm application requirements.
4 Replacement control has 15 second postpurge.
5 Replacement control has 15 second postpurge, RM7840G1022 or RM7840L1075 have programmable postpurge option.
6 Replacement suggestion is 120 Vac, 50/60 Hz.
7
Requires Q7800A or Q7800B Wiring Subbase.
8 RM7840G,M meets current UL requirements.
9 RM7840L meets current insurance requirements.
10 Start interlocks become running interlocks using the replacment controls. (Required to start the equiment, and maintained throughout the call for heat).
11
Running Interlocks become lockout interlocks. (Opening interlock results in safety shutdown and control reset).
12
Replacement control has 10 second PFEP, 4 seconds available with JR1 clipped
13 Replacement has 10, 15 second MFEP.
14 Replacement has 10, 15, 30 second MFEP or intermittent pilot.
15 Replacement has 10 second MFEP or intermittent pilot.
16 5 second ignition early spark termination when ignition wired to terminal 10.
17 Display Module is available by ordering model shown in the table, or ordering seperately.
2
Suggestion Model
Display Model
47
RM7800M1011
RM7840G1014
RM7800G1018
RM7840G1022
Order S7800A1142 seperately
RM7840L1018
RM7800L1012
RM7840L1075
RM7800L1087
R7120D
Order S7800A1001 seperately
18 Select
appropriate flame detector and amplifier from table
FFRT
Flame Detection Type
0.8 sec
3.0 sec
Comments
Rectification
R7847A1025 R7847A1033 Use existing Flame Rod
Ultraviolet
R7849A1015 R7849A1023 Order Honeywell flame detector C7027 or C7035
Infrared
Self Check UV
R7852A1001 Order Honeywell flame detector C7915
C7861A1034 R7861A1026 Order Honeywell flame detector C7061
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
RM7840M1017
X
X
d
R7120D1002
RM7840L1018 RM7840L1018
or
or
RM7840L1075 RM7840L1075
ST7800A1039
30
4-wire
LHL,
HF & LF Proving
X
X
X
k
R7120D1002
RM7840L1018 RM7840L1018
or
or
RM7840L1075 RM7840L1075
k
k
4-wire
LHL,
HF & LF Proving
X
X
X
X
k
d h i
R7120D1002
RM7840L1018 RM7840L1018
or
or
RM7840L1075 RM7840L1075
ST7800A1039
30
4-wire
LHL,
HF & LF Proving
I
X
X
X
10
d
R7120D1002
RM7840L1018 RM7840L1018
or
or
RM7840L1075 RM7840L1075
ST7800A1039
30
4-wire
LHL,
HF & LF Proving
X
X
X
X
d j
R7120D1002
RM7840L1018 RM7840L1018
or
or
RM7840L1075 RM7840L1075
ST7800A1039
30
4-wire
LHL,
HF & LF Proving
X
X
X
X
d
R7120D1002
RM7840L1018 RM7840L1018
or
or
RM7840L1075 RM7840L1075
ST7800A1039
30
4-wire
LHL,
HF & LF Proving
X
X
X
d
9
9
RM7840L1018
RM7840G1014 or
or
RM7840L1075
RM7840G1022
ST7800A1039
30
4-wire
LHL,
LF Proving
X
X
d
9
9
8
ST7800A1039
30
4-wire
LHL,
LF Proving
X
d, h
9
9
8
ST7800A1039
30
4-wire
LHL,
LF Proving
d
9
9
RM7840L1018
RM7840G1014 or
or
RM7840L1075
RM7840G1022
ST7800A1039
30
e f g
R7120D3007
RM7840M1017
ST7800A1039
30
EP161
EPD161
EP163
EP165
EPD165
48
EP166
EPD166
EPD167
EP170
EPD170
EP260
EPD260
EP261
EPD261
EP265
EPD265
EP270
EPD270
EP380
EPD380
R7120D2000
R7120D2000
R7120D2000
R7120D2000
RM7840G1014 RM7840L1018
or
or
RM7840G1022 RM7840L1075
RM7840G1014 RM7840L1018
or
or
RM7840G1022 RM7840L1075
See footnotes on page 49
8
RM7840L1018
or
RM7840L1075
Comments
10
X
10, 15
15 120 50/60
4 sec FFRT
10
X
10, 30
15 120 50/60
4 sec FFRT
k
15 120 50/60
4 sec FFRT, Purge and
Ignition timings are
programmable using
the ED Display Module.
X
10
15 120 50/60
2 sec FFRT
10
X
15
15 120 50/60
2 sec FFRT, locks out
on power inerruption
10
X
10, 15
15 120 50/60
4 sec FFRT
5, 10
X
10
15 120 50/60
4 sec FFRT, Waits
indefinitely for Low Fire
Switch to close.,
X
10
X
10, 15
15 120 50/60
4 sec FFRT
X
X
10
X
10, 30
15 120 50/60
4 sec FFRT
X
X
X
10
X
10
15 120 50/60
2 sec FFRT
4-wire
LHL,
LF Proving
X
X
X
5, 10
X
10
15 120 50/60
4 sec FFRT
On-Off,
LF Proving
h
X
X
X
10
15 120 50/60
4 sec FFRT
X
X
Frequency
X
MFEP
Voltage
4-wire
LHL,
HF & LF Proving
PFEP
Postpurge
Hi-fire
30
Type
Lo-fire
Preignition
ST7800A1039
Lockout
RM7840L1018 RM7840L1018
or
or
RM7840L1075 RM7840L1075
Running
R7120D1002
EP160
EPD160
Start
d
Early Spark Term
Interlocks
INTR Pilot
Prepurge
7800 Series
Functional
Current Plug 7800 Series Replacement
Device to
Functional
to Meet
In
be
Timing
Replacement Replacement Insurance Amplifier
b
Replaced
Purge Timerb
12
1 3 5 11 12
13
b
1 3 4 11 12
INTM Pilot
Functional Replacement
f
X
10
X
X
f
X
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Table 13. FIREYE® E SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE.
Type
PFEP
MFEP
5, 10
10
e f g
R7120D3007
RM7840M1017
8
ST7800A1039
(30 seconds)
15
On-Off,
LF Proving
h
X
X
X
e f g
R7120D3007
RM7840M1017
8
ST7800A1005
(2 seconds)
0
On-Off,
LF Proving
h
X
X
X
g
R7120D3007
RM7840M1017
8
l
l
On-Off,
LF Proving
X
X
m
f g h
R7120D3007
RM7840M1017
13
ST7800A1062
90
On-Off,
LF Proving
X
X
5, 10
EP381
EPD381
EP382
EPD382
EP383
EP390
EPD390
RM7840L1018
or
RM7840L1075
RM7840L1018
or
RM7840L1075
RM7840L1018
or
RM7840L1075
RM7840L1018
or
RM7840L1075
h
X
f
X
e
X
m
f
X
f
X
f
X
m
10
f
X
f
X
Frequency
Voltage
Postpurge
INTR Pilot
INTM Pilot
Lo-fire
Hi-fire
Preignition
Start
7800 Series
Functional
Current Plug 7800 Series Replacement
Device to
Functional
to Meet
In
be
Timing
Replacement Replacement Insurance Amplifier
Replacedb
Purge Timerb
12
1 3 5 11 12
13
b
1 3 4 11 12
Interlocks
Lockout
Prepurge
Running
Functional Replacement
Early Spark Term
Table 13. FIREYE® E SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued)
Comments
15 120 50/60
4 sec FFRT
15 120 50/60
m 120 50/60
m
15 120 50/60
4 sec FFRT
See footnotes on page 49
49
Table 13 FIREYE FOOTNOTES:
Honeywell Solution Suggestion
70-8313—02
All programmers have selectable 3 to P "prove open on Start" feature using a
dipswitch
Clip JR3 if dipswitch feature is enabled.
b
Purge timings can be extended using the dipswitches located on the porgrammer
module.
Check dipswitches and select appropriate ST7800 Purge Timer
c
EPD programmers include a built in LED display.
See display models suggestion in table I.
d
Programmer adds 30 seond after pre-purge to allow damper motor to drive to low
fire position.
Honeywell Model adds 30 seconds for jumpered or closed interlock
e
EP380, EM381, EP382 and EP390 have selectable intermittent or interrupted (15
sec PTFI) operation of terminal 6 using dipswitch.
Honeywell suggestion dependant on terminals wired
f
These programmers can use terminal X for spark termination. Requires terminals
10 and 5 to be jumpered.
Available when Ignition is wired to terminal 10.
g
EP380, EM381, EP382 and EP390 have selectable recycle or non recycle
operation using a dipswitch.
Honeywell suggestion DOES NOT offer non recycle, if required select an "L model.
h
During MTFI, terminal 6 is energized for 5 seconds before 10 second MTFI for
EP165 and EP265; 15 second MTFI for EP166 only.
Honeywell suggestion does not offer the energize the spark early.
i
EP165 locks out on power inerruption
Honeywell suggestion DOES NOT offer this feature.
PROGRAMMER CONTROL CROSS REFERENCE
Fireye Notes
a
Honeywell Solution Suggestion
The EPD167 waits indefinitely for the Low Fire Start Switch (M-D) to close.
Honeywell suggestion DOES NOT offer this feature.
k
The EP163 Purge and Ignition timings are programmable using the ED Display
Module.
Honeywell suggestion DOES NOT offer feature to program Purge and Ignition
l
The EP383 Purge, Ignition, FFRT and Post Purge time are programmable using the Honeywell suggestion DOES NOT offer feature to program Purge, Ignition, FFRT
ED Display Module.
and Post Purge Time.
m
Intermittent or Interrupted Pilot opertion may be selected using a dipswitch (or
using the ED Display Module with EP383)
Honeywell suggestion offers feature based on the terminal the pilot valve is wired.
Other Footnotes
1 Replacement
control has 15 second postpurge.
control has 15 second postpurge, RM7840G1022 or RM7840L1075
have programmable postpurge option.
3
Requires Q7800A or Q7800B Wiring Subbase.
4 RM7840G,M meets current UL requirements.
5 RM7840L meets current insurance requirements.
6 Start interlocks become running interlocks using the replacment controls.
(Required to start the equiment, and maintained throughout the call for heat).
7 Replacement control has 10 second PFEP, 4 seconds available with JR1 clipped
8 Replacement has 10, 15 second MFEP.
9 Replacement has 10, 15, 30 second MFEP or intermittent pilot.
10Replacement has 10 second MFEP or intermittent pilot.
115 second ignition early spark termination when ignition wired to terminal 10.
12Display Module is available by ordering model shown in the table, or ordering
seperately.
2 Replacement
50
Display Model Suggestions
Suggestion Model
Display Model
RM7840M1017
RM7800M1011
RM7840G1014
RM7800G1018
RM7840G1022
Order S7800A1142 seperately
RM7840L1018
RM7800L1012
RM7840L1075
RM7800L1087
13Select
appropriate flame detector and amplifier from table
Amplifier
Selection
Type
FFRT
(seconds) Replacement
Comments
72D1R1
IR
2-4
R7852A1001
Select C7915 flame
detector
72D1R1T
IR
1
none available
72D1R3
IR
2-4 (For
solid fuel)
72D1R3T
IR
1 (For solid
fuel)
72DRT1
Flame
Rod
2-4
R7847A1033
72DRT1T
Flame
Rod
1
R7847A1025
72DUV1
UV
2-4
R7849A1023
Select C7027A1080
flame detector
72DUVS4
UV Self
Check
2-4
R7861A1026
Select C7061 flame
detector
72DUVS1T
UV Self
Check
1
R7861A1034
Select C7061 flame
detector
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
Fireye Notes
j
51
PROGRAMMER CONTROL CROSS REFERENCE
70-8313—02
PROGRAMMER CONTROL CROSS REFERENCE
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
70-8313—02 M.S. Rev. 09-11