Programmer Control Cross Reference CROSS REFERENCE Honeywell has provided proprietary and/or “labelled” controls to certain Original Equipment Manufacturers (OEM) at their request. Proprietary controls are available only from the OEM, while “labelled” controls can, in some instances, be purchased directly from Honeywell. Where a control is available only from the OEM, we have placed a footnote in the “Replacement Control” column. Refer questions about a particular OEM control to the particular OEM (see list below): Cleaver Brooks Div. Aqua—Chem Inc. ATTN: Parts Manager P.O. Box 421 Milwaukee, WI 53201 414-577-2710 Fulton 972 Centerville Road Pulaski, NY13142 315-298-5121 Lennox Industries Inc. Lennox Parts Center P.O. Box 7658 4251 121st Street Urbandale, IA 50322 515-251-4440 Ray Burner Co. Engineering & Sales Dept. 401 Parr Boulevard Richmond, CA 94801 610-236-4272 Vapor Power International 551 S. County Line Road Franklin Park, IL 60131 630-694-5500 70-8313-02 PROGRAMMER CONTROL CROSS REFERENCE CROSS REFERENCE DATA Page HONEYWELL R4126 PROGRAMMER CROSS REFERENCE ................................................................................................. 3 HONEYWELL R4127 PROGRAMMER CROSS REFERENCE ................................................................................................. 6 HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. ................................................................................................ 9 HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. ................................................................................................ 15 HONEYWELL R4181 PROGRAMMER CROSS REFERENCE. ................................................................................................ 21 HONEYWELL R8169 PROGRAMMER CROSS REFERENCE. ................................................................................................ 22 HONEYWELL PROGRAM MODULE PROGRAMMER CROSS REFERENCE. ....................................................................... 23 HONEYWELL BC7000 PROGRAMMER CROSS REFERENCE. ............................................................................................. 26 HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. .................................................................................... 27 FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. .................................................................... 35 FIREYE® C SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. .................................................................... 41 FIREYE® D SERIES PROGRAMMER TO HONEYWELL CROSS REFERENCE. .................................................................... 45 FIREYE® E SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. .................................................................... 48 70-8313—02 2 Table 1. HONEYWELL R4126 PROGRAMMER CROSS REFERENCE 3 Frequency Voltage Modulation Postpurge Spark Term INTR Pilot INTM Pilot Lo-fire Lockout Device to be 1 2 3 4 5 6 7 8 9 10 Replacement Lo-Fire LHL OP Replaced Purge Timer Timing On-Off LHL PRV Damp 11 12 Start Running Type Closest 7800 Series Replacement Hi-fire Interlocks Preignition Prepurge R4126A1008 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 With R7253A 208 240 R4126A1016 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 With Q535 and R7253A 208 240 R4126A1024 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 With Q536 and 208 R7253A 240 R4126A1032 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 With Q535 208 240 R4126A1040 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 With Q536 208 240 R4126A1057 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 208 240 R4126A1065 None X X X X 10 X 15,30 15 4-wire 120 50 With Q535 208 international model 240 X X X 10 X 15,30 15 4-wire 120 60 208 240 X X X 10 X 15,30 15 4-wire 120 60 208 240 X X X 5 X 10 3 R4126A1073 RM7840L1018 ST7800A1054 60 or RM7840L1075 R4126A1081 RM7840G1014 ST7800A1047 40 or RM7840G1022 R4126A1099 None 70-8313—02 See footnotes on page 5. 10 X HL X MFEP Comments 120 60 Proprietary to Vapor Corporation PROGRAMMER CONTROL CROSS REFERENCE 40 PFEP Frequency Voltage Modulation Postpurge MFEP Spark Term INTR Pilot PFEP INTM Pilot Lo-fire Lockout Running Device to be 1 2 3 4 5 6 7 8 9 10 Replacement Lo-Fire LHL OP Replaced Purge Timer Timing On-Off LHL PRV Damp 11 12 Start Closest 7800 Series Replacement Hi-fire Interlocks Type Preignition Prepurge Comments R4126A1107 None Produced in Japan R4126A1115 None Produced in Japan R4126A1123 None Never Produced R4126A1131 None Never Produced 4 R4126A1149 RM7840G1014 ST7800A1047 40 or RM7840G1022 R4126A1156 None X 10 X X X X 10 X 15,30 15 4-wire 120 60 Produced in Canada X X X 5 X 3 X X 10 X 15,30 15 4-wire 120 60 208 240 Proprietary to Vapor Corporation R4126A1164 RM7840L1018 ST7800A1054 60 or RM7840L1075 X R4126A1172 RM7840L1018 ST7800A1054 60 or RM7840L1075 X X X X X 10 X 15,30 15 4-wire 120 60 R4126A1180 RM7840L1018 ST7800A1054 60 or RM7840L1075 X X X X X 10 X 15,30 20 4-wire 120 60 Tamper resistant R4126A1198 RM7840L1018 ST7800A1054 60 or RM7840L1075 X X X X X 10 X 10, 30 X 15 4-wire 120 60 See footnotes on page 5. X X 120 208 240 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 1. HONEYWELL R4126 PROGRAMMER CROSS REFERENCE Table 1. HONEYWELL R4126 PROGRAMMER CROSS REFERENCE X 5 X 10 3 X MFEP Frequency X X 10 Voltage R4126A1206 None PFEP Modulation Postpurge Spark Term INTR Pilot INTM Pilot Lo-fire Lockout Running Device to be 1 2 3 4 5 6 7 8 9 10 Replacement Lo-Fire LHL OP Replaced Purge Timer Timing On-Off LHL PRV Damp 11 12 Start Hi-fire Interlocks Type Preignition Prepurge Closest 7800 Series Replacement Comments 120 60 Proprietary to Vapor Corporation, fungus proofed R4126B1006 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 With infrared 208 amplifier 240 R4126B1014 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 With Q536 and infrared amplifier 208 240 R4126B1022 RM7840G1014 ST7800A1047 40 or RM7840G1022 X X X X 10 X 15,30 15 4-wire 120 60 With Q535 and 208 infrared amplifier 240 See footnotes on page 5. 5 Table 1 Footnotes 1 RM7840G meets current UL requirements. RM7840L meets current insurance requirements. 3 R4126 Start Interlocks become RM7840 Preignition Interlocks. 4 Replacement controls are 120 Vac, 50/60 Hz. 5 RM7840G1014, G1022 MFEP is 10, 15, or 30 seconds. 6 RM7840L1018, L1075 MFEP is 10 or 15 seconds. 7 RM7840G1014, G1022, RM7840L1018 and L1075 PFEP is 4 or 10 seconds. 8 Select proper flame amplfier. 9 Use with existing Honeywell Flame Detectors. 10 With selectable air-flow switch check (AFSC). 11 Requires Q7800A or Q7800B Subbase. 12 Refer to conversion wiring diagrams in Modernization Wiring Information section. 2 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Frequency Modulation 15 15 3-wire 120 60 With R7253A 208 240 R4127A1015 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 With Q535 and R7253A 208 240 R4127A1023 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 With Q536 and 208 R7253A 240 R4127A1031 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 With Q535 208 240 R4127A1049 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 With Q536 208 240 R4127A1056 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 R4127A1064 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 R4127A1072 None 30 X X X 10 R4127A1080 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 R4127A1098 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 R4127A1106 None See footnotes on page 8 None None MFEP Voltage X INTR Pilot 10 Lo-fire X X Hi-fire X Lockout R4127A1007 RM7840G1014 ST7800A1039 30 or RM7840G1022 Running PFEP INTM Pilot 6 Device to be 1 2 3 4 5 6 7 8 9 10 Replacement Lo-Fire LHL OP Replaced Purge Timer Timing On-Off LHL PRV Damp 11 12 Start Postpurge Type Closest 7800 Series Replacement Spark Term Interlocks Preignition Prepurge Comments X 15, 60 15 3-wire 120 60 X 15 15 3-wire 120 60 208 240 X 15 15 3-wire 120 50 With Q535 208 international model 240 X 15, 60 X 15 15 3-wire 120 60 Produced in 208 Canada 240 15 3-wire 120 60 International model PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 2. HONEYWELL R4127 PROGRAMMER CROSS REFERENCE Table 2. HONEYWELL R4127 PROGRAMMER CROSS REFERENCE (Continued) Frequency Voltage Modulation Postpurge Spark Term MFEP Comments None R4127A1122 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 R4127A1130 RM7840G1014 ST7800A1062 90 or RM7840G1022 X X X 10 R4127A1148 RM7840G1014 ST7800A1062 90 or RM7840G1022 X X X R4127A1155 RM7840G1014 ST7800A1054 60 or RM7840G1022 7 R4127A1163 None INTR Pilot PFEP INTM Pilot Lo-fire Hi-fire Lockout Running Start Device to be 1 2 3 4 5 6 7 8 9 10 Replacement Lo-Fire LHL OP Replaced Purge Timer Timing On-Off LHL PRV Damp 11 12 R4127A1114 None Interlocks Type Preignition Prepurge Closest 7800 Series Replacement None 30 X X R4127A1189 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X X R4127A1197 RM7840G1014 ST7800A1054 60 or RM7840G1022 X X X X X X X X 8 10 X X 9 10 X 9 X 15 3-wire 120 60 208 240 15 15 3-wire 120 60 208 240 X 15, 55 15 3-wire 120 60 208 240 X 15, 30 15 4-wire 120 60 15 15 3-wire 120 50 International model 208 240 X 15, 30 15 4-wire 120 60 Ray Burner RC2D, uses special Q535/ Q536 10 15 3-wire 120 60 X 10, 30 15 4-wire 120 60 R4127B1005 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 208 240 R4127B1013 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 With Q535 208 240 70-8313—02 See footnotes on page 8 PROGRAMMER CONTROL CROSS REFERENCE R4127A1171 RM7840G1014 ST7800A1054 60 or RM7840G1022 X X X X 15, 55 8 Frequency Voltage Modulation Postpurge Spark Term INTR Pilot INTM Pilot Lo-fire Lockout Running Device to be 1 2 3 4 5 6 7 8 9 10 Replacement Lo-Fire LHL OP Replaced Purge Timer Timing On-Off LHL PRV Damp 11 12 Start Closest 7800 Series Replacement Hi-fire Interlocks Type Preignition Prepurge R4127B1021 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 With Q536 208 240 R4127B1039 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 Ray Burner RC2A with R7254A, Q536 R4127B1047 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 Ray Burner RC2B with R7254A,Q535 R4127B1054 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 Ray Burner R4127C1003 RM7840G1014 ST7800A1039 30 or RM7840G1022 X X X 10 X 15 15 3-wire 120 60 Ray Burner with R7255A See footnotes on page 8 Table 2 Footnotes 1 RM7840G meets current UL requirements. RM7840L meets current insurance requirements. 3 R4127A,B,C Start Interlocks become RM7840 Preignition Interlocks. 4 Replacement controls are 120 Vac, 50/60 Hz. 5 RM7840G1014, G1022 MFEP is 10, 15, or 30 seconds. 6 RM7840L1018, L1075 MFEP is 10 or 15 seconds. 7 RM7840G1014, G1022, RM7840L1018 and L1075 PFEP is 4 or 10 seconds. 8 Select proper flame amplfier. 9 Use with existing Honeywell Flame Detectors. 10 With selectable air-flow switch check (AFSC). 11 Requires Q7800A or Q7800B Subbase. 12 Refer to conversion wiring diagrams in Modernization Wiring Information section. 2 PFEP MFEP Comments PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 2. HONEYWELL R4127 PROGRAMMER CROSS REFERENCE (Continued) Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. Frequency Voltage Modulation Postpurge MFEP Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type Hi-fire Purge Timer Preignition 2, 6, 7, 8, 9 Lockout 7800 Series Running Direct 2, 6, 7,11 Interlocks Start Device to be Replaced Prepurge Timing Replacement Comment R4140D1004 None None 30 X X 10 X 10 R4140E1001 None None 31 X X 3 10 R4140G1007 R7140G1000 RM7840G1014 or ST7800A1054 60 LHL, LF RM7840G1022 Proven X X X 10 X 10, 30 16 4-wire 120 60 R4140G1015 R7140G1000 RM7840G1014 or ST7800A1054 60 LHL, LF RM7840G1022 Proven X X X 10 X 10, 30 16 4-wire 120 60 X X X 10 X 10, 15 16 4-wire 120 60 Proprietary to Cleaver Brooks CB20 R4140G1023 Consult Original Equipment Manufacturer 72 LHL, LF Proven X 55 4-wire 120 60 Maxon special sequence for postpurge pilot systems. Uses special Q520A1196. 15 4-wire 120 60 For direct spark ignition systems X 10 X 10, 30 X 16 4-wire 120 60 R4140G1049 R7140G20081 RM7840G1014 or ST7800A1054 60 LHL, LF X X Proven RM7840G10221 X 10 X 10, 30 X 16 4-wire 120 60 R4140G1056 R7140G20081 RM7840G1014 or ST7800A1054 60 LHL, LF X X Proven RM7840G10221 X 10 X 10 X 16 4-wire 120 60 R4140G1064 R7140G20081 RM7840G1014 or ST7800A1054 60 LHL, LF X X Proven RM7840G10221 X 10 X 10 X 16 4-wire 120 60 R4140G1072 R7140G20081 RM7840G1014 or ST7800A1054 60 LHL, LF X X Proven RM7840G10221 X 10 X 10 16 4-wire 120 60 R4140G1080 R7140G20081 RM7840G1014 or ST7800A1054 60 LHL, LF X X Proven RM7840G10221 X 10 X 10 16 4-wire 120 60 R4140G1098 None None X 10 X 10, 30 X 16 4-wire 240 50 International model R4140G1106 R7140G1000 RM7840G1014 or ST7800A1054 60 LHL, LF RM7840G1022 Proven R4140G1114 None None R4140G1122 None None 70-8313—02 See footnotes on page 14 60 LHL, LF X X Proven X X X 10 X 10, 15 16 4-wire 120 60 70 LHL, LF X X Proven X 10 X 10, X 25 4-wire 240 60 30, 60 70 LHL, LF X X Proven X 10 X 10, X 25 4-wire 208 60 30, 60 PROGRAMMER CONTROL CROSS REFERENCE RM7840G1014 or ST7800A1054 60 LHL, LF X X Proven RM7840G10221 9 R4140G1031 R7140G20081 Frequency Voltage Modulation Postpurge MFEP Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type Hi-fire Purge Timer Preignition 2, 6, 7, 8, 9 Lockout 7800 Series Running Direct 2, 6, 7,11 Interlocks Start Device to be Replaced Prepurge Timing Replacement R4140G1130 R7140G20081 RM7840G1014 or ST7800A1054 60 LHL, LF X X Proven RM7840G10221 X 10 X 10, 15 X 16 4-wire 120 60 R4140G1148 R7140G20081 RM7840G1014 or ST7800A1054 60 LHL, LF X X Proven RM7840G10221 X 10 X 10, 15 X 16 4-wire 120 60 R4140G1155 None EC7850A1122 ST7800A1054 60 LHL, LF Proven R4140G1163 R7140G20081 RM7840G10141 ST7800A1054 60 LHL, LF X X Proven X X X X 5 X 10 X R4140G1171 R7140G20081,3 RM7840G10141, 3 ST7800A1062 70 LHL, LF X X (90 seconds) Proven X 10 X X X X 10 X 5 10 Comment X 15 4-wire 240 50 Proprietary to GordonPiatt Energy X 16 4-wire 120 60 X 10, X 25 4-wire 120 60 30, 60 X 10 X 15 4-wire 120 60 Gordon-Piatt Energy GP201 10 R4140G1189 R7140L100910 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven R4140G1197 None EC7850A1122 R4140L1006 R7140L1009 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, 15 16 4-wire 120 60 R4140L1014 R7140L1009 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, 15 16 4-wire 120 60 72 LHL, HF-LF Proven X X X X 10 X 10, 15 15 4-wire 120 60 Cleaver Brooks CB40 R4140L1030 R7140L1009 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, 15 X 16 4-wire 120 60 With nonrotatable timer R4140L1048 None EC7850A1122 ST7800A1047 45 LHL, (40 seconds) HF-LF Proven X X X X 10 X 2, 5, 10 R4140L1055 R7140L1009 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, 30 R4140L1022 Consult Original Equipment Manufacturer See footnotes on page 14 ST7800A1054 60 LHL, LF X X Proven X 5 X 5, 10, X 16 4-wire 240 50 International model 15 X 15 4-wire 220 50 International model 15 4-wire 120 60 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued) Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued) X X X X 6.5 X Frequency Voltage Modulation Postpurge MFEP 8 Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type 9.5 LHL, HF-LF Proven Hi-fire Purge Timer Preignition 2, 6, 7, 8, 9 R4140L1063 Consult Original Equipment Manufacturer Lockout 7800 Series Running Direct 2, 6, 7,11 Interlocks Start Device to be Replaced Prepurge Timing Replacement Comment 3.5 2-wire 120 60 Vapor Corporation 11 R4140L1071 None RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, X 15 4-wire 240 50 International model 15, 30 R4140L1089 R7140L100910 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10 R4140L1097 R7140L1009 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, 15 X 15 4-wire 120 60 R4140L1105 R7140L1009 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, 15 X 16 4-wire 120 60 R4140L1113 None EC7840L101412 ST7800A1054 60 LHL, HF-LF or EC7850A1122 Proven X X X X 5 X 5, 10, X 15 4-wire 240 50 International model 15 5.5 LHL, HF-LF Proven X X X X 8 R4140L1139 R7140L1009 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, 15 X 15 4-wire 120 60 R4140L1147 R7140L1009 RM7840L1018 or ST7800A1054 60 LHL, RM7840L1075 HF-LF Proven X X X X 10 X 10, X 15 4-wire 120 60 15, 30 R4140L1154 None EC7850A1122 Sel LHL, ect HF-LF abl Proven e X X X X 10 X 5, 10 60 LHL, HF-LF Proven X X X X 10 X 5, 15 R4140L1162 Consult Original Equipment Manufacturer 70-8313—02 See footnotes on page 14 Check R4140 for purge timing ICI Model X 15 4-wire 240 50 Approved by Australian Gas Association 16 4-wire 120 60 Fulton Special PROGRAMMER CONTROL CROSS REFERENCE R4140L1121 Consult Original Equipment Manufacturer X 15 4-wire 120 60 Gordon-Piatt Energy GP301 X X X X 10 Frequency Voltage Modulation Postpurge MFEP X 5, 10 Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type Hi-fire Purge Timer Preignition 2, 6, 7, 8, 9 Lockout 7800 Series Running Direct 2, 6, 7,11 Interlocks Start Device to be Replaced Prepurge Timing Replacement Comment X 15 4-wire 240 50 R4140L1170 None EC7850A1122 ST7800A1054 60 LHL, HF-LF Proven R4140M1004 R7140M10071 RM7840M10171 ST7800A1039 31 On-Off, X X (30 seconds) LF Proven 10 X 10 15 120 60 R4140M1012 R7140M10071 RM7840M10171 ST7800A1039 31 On-Off, X X (30 seconds) LF Proven 10 X 10 15 120 60 R4140M1020 R7140M1007 RM7840M10171, 4 ST7800A1047 42 On-Off, X X (40 seconds) LF Proven X 10 X 10 X 15 120 60 Isolated damper motor contact RM7840M10171, 4 ST7800A1047 42 On-Off, X X (40 seconds) LF Proven X 10 X 10 X 15 120 60 Isolated damper motor contact RM7840M10171, 4 ST7800A1062 96 On-Off, X X (90 seconds) LF Proven X 10 X 10 X 25 120 60 Isolated damper motor contact RM7840M10171, 4 ST7800A1062 96 On-Off, X X (90 seconds) LF Proven X 10 X 10 X 25 120 60 Isolated damper motor contact 10 X 5, 10 X 15 240 50 International model 10 X 25 120 60 Gordon-Piatt Energy GP101 1, 4, 5 R4140M1038 R7140M1007 1, 4, 5 12 R4140M1046 R7140M1007 1, 4, 5 R4140M1053 R7140M1007 1, 4, 5 R4140M1061 None None R4140M1079 R7140M1007 RM7840M1017 R4140M1087 None None 31 On-Off, X X LF Proven ST7800A1062 90 On-Off, X LF Proven 31 On-Off, X X LF Proven X 10 X 10 X 5, 10, X 15 15 240 50 International model R4140M1095 Never produced R4140M1103 R7140M10071 See footnotes on page 14 Never produced RM7840M10171 ST7800A1039 31 On-Off, X X (30 seconds) LF Proven 10 X 10, 30 15 120 60 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued) Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued) R4140M1111 R7140M10071 1 RM7840M1017 X 10, 30 15 Frequency Voltage Modulation Postpurge MFEP 10 Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type ST7800A1039 31 On-Off, X X (30 seconds) LF Proven Hi-fire Purge Timer Preignition 2, 6, 7, 8, 9 Lockout 7800 Series Running Direct 2, 6, 7,11 Interlocks Start Device to be Replaced Prepurge Timing Replacement Comment 120 60 R4140M1129 Never produced R4140M1137 Never produced R4140M1145 R7140M1007 1, 4, 5 R4140M1152 R7140M1007 1, 4, 5 RM7840M10171, 4 ST7800A1047 42 On-Off, X X (40 seconds) LF Proven X X 10 X 10 X 15 120 60 Isolated damper motor contact RM7840M10171, 4 ST7800A1047 42 On-Off, X X (40 seconds) LF Proven X X 10 X 10 X 15 120 60 Isolated damper motor contact 13 ST7800A1062 96 On-Off, (90 seconds) LF Proven X X X 10 X 10 X 25 120 60 Isolated damper motor contact R4140M1178 R7140M10074, 5 RM7840M10174 ST7800A1062 96 On-Off, (90 seconds) LF Proven X X X 10 X 10 X 25 120 60 Isolated damper motor contact R4140M1186 R7140M10071, 5 RM7840M10171 ST7800A1047 42 On-Off, X X (40 seconds) LF Proven X 10 X 10 X 15 120 60 R4140M1194 R7140M10071, 5 RM7840M10171 ST7800A1062 96 On-Off, X X (90 seconds) LF Proven X 10 X 10 X 15 120 60 X 5, 10 X 15 240 50 Approved by Australian Gas Association R4140M1202 None None R4140M1210 Consult Original Equipment Manufacturer 31 On-Off, X X LF Proven 31 On-Off, X X LF Proven X 5 10 X 10 25 120 60 Fulton Special 70-8313—02 R4140P1007 None RM7896C1010 or ST7800A1062 90 On-Off RM7897C1000 X X 10 X 15 15 120 60 Gordon Piatt GP001 R4140Y1005 None RM7896A1012 or ST7800A1013 7 RM7897A1002 On-Off X X 10 X 15 15 120 60 R4140Y1013 None RM7896A1012 or ST7800A1013 7 RM7897A100212 On-Off X X 4 X 15 15 120 60 See footnotes on page 14 PROGRAMMER CONTROL CROSS REFERENCE R4140M1160 R7140M10074, 5 RM7840M10174 Frequency Voltage Modulation Postpurge MFEP Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type Hi-fire Purge Timer Preignition 2, 6, 7, 8, 9 Lockout 7800 Series Running Direct 2, 6, 7,11 Interlocks Start Device to be Replaced Prepurge Timing Replacement R4140Y1021 None RM7896A1012 or ST7800A1039 30 On-Off RM7897A1002 X X 10 X 15 15 120 60 R4140Y1039 None RM7896A1012 or ST7800A1039 30 On-Off RM7897A100212 X X 4 X 15 15 120 60 R4140Y1047 None RM7896A1012 or ST7800A1054 60 On-Off RM7897A1002 X X 10 X 15 15 120 60 R4140Y1054 None RM7896A1012 or ST7800A1054 60 On-Off RM7897A100212 X X 4 X 15 15 120 60 R4140Y1062 None RM7896A1012 or ST7800A1062 90 On-Off RM7897A1002 X X 10 X 15 15 120 60 R4140Y1070 None RM7896A1012 or ST7800A1062 90 On-Off RM7897A100212 X X 4 X 15 15 120 60 See footnotes on page 14 14 Table 3 Footnotes 1 2 3 4 5 6 R4140 Start Interlocks become Pre-Ignition Interlock (must remain closed throughout purge) 4 or 10 Second PFEP 60 second MFEP is not available with replacement device Spring return Firing Rate Motor (damper motor) Remove Jumper J1 and J2 Select Proper Amplifier: Old Amplifer Replacement Amplifer R7247A1005 R7847A1033 R7247A1021 R7847A1025 R7247B1003 R7847B1031 R7247C1001 R7861A1026 See Note 8 R7248A1004 R7848A1008 R7248B1028 R7848B1006 R7249A1003 R7849A1023 R7476A1007 R7886A1001 7 With Selectable Airflow Switch Check (AFC) Used with Existing Flame Detectors - EXCEPT - C7012E, F - Replace with C7061A, F and appropriate R7861 Flame Amplifier 9 Requires Q7800A or B Wiring Subbase 10 Locate High Fire (or Purge Rate Switch) connection on Terminal D. Remove Wire and Connect onto Terminal M 11 Check the wiring base - if 3 terminal strips - system must be updated to the 7800 SERIES option - do not use the R7140 option. 12 Clip JR1 8 Comment PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 3. HONEYWELL R4140 PROGRAMMER CROSS REFERENCE. (Continued) Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. Frequency Voltage Modulation Postpurge MFEP Spark Term INTR Pilot INTM Pilot PFEP Type Lo-fire Purge Timer Hi-fire 1, 2, 6, 7, 8, 9 Preignition 7800 Series 1, 2, 6, 7, 8, 10 Lockout Device to be Replaced Running Direct Interlocks Start Prepurge Timing Replacement Comment R4150A1007 None RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15 15 120 60 Includes R7257 Amplifier. R4150A1015 None RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15 15 120 50 R4150A1023 None RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15 15 120 60 R4150A1031 None RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15, 30 X 15 120 60 Kewanee label. 10 X 5 X 15 200 60 Includes R7257 International model. R4150A1049 International Model 30 On-Off X X R4150A1056 None RM7840M1017 ST7800A1039 30 On-Off X X 15 X 15 X 15 120 60 R4150A1064 None RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15, 30 15 120 60 15 R4150A1072 International Model R4150A1080 None 30 On-Off X X 10 X 15 RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15, 30 X 15 200 60 International model. 120 60 Kewanee label. R4150A1098 Never Produced Never produced 15 R4150A1106 None RM7840M1017 ST7800A1039 30 On-Off X X 15 X 5 R4150A1114 None RM7840M1017 ST7800A1054 60 On-Off X X 10 X 15 R4150A1122 None RM7840M1017 ST7800A1062 90 On-Off X X 10 X 15 15 120 60 R4150A1130 None RM7840M1017 ST7800A1054 60 On-Off X X 10 X 15, 30 20 120 60 R4150A1148 None RM7840M1017 ST7800A1062 90 On-Off X X 10 X 15, 30 15 120 60 R4150A1155 None RM7840M1017 ST7800A1062 90 On-Off X X 10 X 15, 30 X 15 120 60 Kewanee label. R4150A1163 None RM7840M1017 ST7800A1039 30 On-Off X X 15 X 15 X 15 120 60 R4150A1171 None RM7840M1017 ST7800A1062 90 On-Off X X 15 X X 15 120 60 R4150A1189 None RM7840M1017 ST7800A1062 90 On-Off X X 15 X 20 120 60 R4150A1197 None RM7840M1017 ST7800A1039 30 On-Off X X 120 60 120 50 International model 10 X 2 20 220 50 International model R4150A1213 International Model 37 On-Off X X 10 X 5 20 220 50 International model R4150A1221 International Model 37 On-Off X X 10 X 5 20 240 50 International model R4150A1239 None RM7840M1017 ST7800A1062 90 On-Off X X 15 X 15 X 20 120 60 R4150A1247 None RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15 15 120 60 R4150A1254 None RM7840M1017 ST7800A1062 90 On-Off X X 120 60 10 X 15 20 30 On-Off X X 10 X 15 X 15 RM7840M1017 ST7800A1039 30 On-Off X X 30 X 15 15 R4150A1262 International Model 220 50 International model 70-8313—02 120 60 PROGRAMMER CONTROL CROSS REFERENCE 15 37 On-Off X X See footnotes on page 20 15 120 60 R4150A1205 International Model R4150A1270 None 10 X X 15 X 15 R4150A1288 None Frequency Voltage Modulation Postpurge Spark Term INTR Pilot INTM Pilot PFEP Lo-fire MFEP 15 15 120 60 5 second stabilization before PFEP. 30 On-Off X X 10 X 15 15 220 50 International model. Ignition on 3 secs before pilot valve. RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15 15 120 60 R7258A included 10 X 15 15 120 60 R7259A included X 10 15 120 60 R7259A included R4150B1013 Never Produced R4150C1003 None Comment 10 X R4150A1296 International Model R4150B1005 None Type Hi-fire Purge Timer RM7840M1017 ST7800A1047 35 On-Off X X (40 seconds) Preignition 1, 2, 6, 7, 8, 9 Lockout 7800 Series 1, 2, 6, 7, 8, 10 Running Device to be Replaced Interlocks Start Prepurge Timing Replacement Direct Never produced RM7840M1017 ST7800A1039 30 On-Off X X R4150C1011 Never Produced R4150C1029 None RM7840M1017 ST7800A1039 30 On-Off X X 10 R4150D1001 Never Produced R4150E1008 None None Never produced 30 X X 3 15 120 60 For direct spark ignition applications 16 R4150F1006 International Model International - Japan R4150F1014 International Model International - Japan R4150G1004 R7140G2008 RM7840G1014 ST7800A1054 50 LHL, X X (60 seconds) LF or Proven RM7840G1022 X 9 X 15 R4150G1012 R7140M1007 RM7840M1017 ST7800A1062 72 OnX X 4,5 (90 seconds) Off, LF Proven X 13 X 15 R4150G1020 R7140G2008 RM7840G1014 ST7800A1054 50 LHL, X X or (60 seconds) LF RM7840G1022 Proven X 9 X 10 8 3120 60 Kewanee label wire 50 LHL, X X LF Proven X 9 X 15 8 3220 50 International model wire R4150G1046 R7140G2008 RM7840G1014 ST7800A1054 50 LHL, X X or (60 seconds) LF RM7840G1022 Proven X 9 X 10 8 3120 60 wire R4150G1053 Consult Original Equipment Manufacturer 72 LHL, X X LF Proven X 10 X 10, 15 9 3120 60 Cleaver Brooks CB2 wire R4150G1061 Consult Original Equipment Manufacturer 72 LHL, LF Proven X X X X 10 X 10, 15 15 3120 60 Cleaver Brooks CB4, CB4-1 wire R4150G1038 International Model See footnotes on page 20 8 X 15 3120 60 wire 120 60 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. (Continued) Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. (Continued) Prepurge Interlocks R4150G1111 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X or LF RM7840G1022 Proven X 10 X 15 15 4120 60 wire X X X X 10 X 10 15 4120 60 Gordon-Piatt Energy GP200 wire Frequency 15 3120 60 wire Voltage 10, 30 Modulation X 10 X Postpurge R4150G1103 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X or LF RM7840G1022 Proven INTR Pilot 15 4120 60 Cleaver Brooks CB2-1 wire INTM Pilot 10, 15 PFEP X 10 X Lo-fire 72 LHL, X X LF Proven Hi-fire R4150G1087 Consult Original Equipment Manufacturer Type Preignition X 15 Purge Timer Lockout 15 1, 2, 6, 7, 8, 9 Running X 13 X 7800 Series 1, 2, 6, 7, 8, 10 Start R4150G1079 R7140M1007 RM7840M1017 ST7800A1062 72 LHL, X X (90 seconds) LF Proven Device to be Replaced Timing MFEP Spark Term Replacement Direct R4150G1095 Never Produced R4150G1129 None Never produced 17 RM7840L1018 ST7800A1054 60 LHL, LF or Proven RM7840L1075 X 10 R4150G1145 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X or LF RM7840G1022 Proven X 10 X X 10, 30 15 4120 60 wire 10 15 4120 60 wire R4150G1152 Never Produced Never produced 72 LHL, LF Proven X X X 10 R4150G1178 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X LF or Proven RM7840G1022 R4150G1186 R7140G1000 RM7840G1014 ST7800A1054 60 LHL, or LF RM7840G1022 Proven R4150G1194 Never Produced See footnotes on page 20 X X 10 X X X 10 X 10, 15 15 4120 60 Cleaver Brooks CB2-1A wire 15 15 4120 60 wire X 10, 15 15 4120 60 wire Never produced 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE R4150G1137 R7140G2008 RM7840G1014 ST7800A1054 60 LHL, X X or LF RM7840G1022 Proven R4150G1160 Consult Original Equipment Manufacturer Comment 120 60 X X X X 10 Frequency Voltage Modulation Postpurge MFEP X 5 Spark Term INTR Pilot INTM Pilot PFEP Type Lo-fire Purge Timer Hi-fire 1, 2, 6, 7, 8, 9 Preignition 7800 Series Lockout 1, 2, 6, 7, 8, 10 Running Device to be Replaced Interlocks Start Prepurge Timing Replacement Direct Comment X 15 4240 50 International model to Gordon-Piatt wire Energy Specifications. R4150G1202 International Model 62 LHL, LF Proven R4150H1002 International Model 30 On-Off X X 9 X 13, 58 15 3120 60 International model wire R4150H1010 International Model 30 On-Off X X 9 X 13, 58 15 3240 60 International model wire R4150H1028 International Model 30 On-Off X X 9 X 13, 58 15 3220 50 International model wire R4150H1036 International Model 30 On-Off X X 9 X 13, 58 15 3208 60 wire R4150J1007 International Model 37 On-Off X 5 X 2 20 220 50 International model R4150K1005 International Model 37 On-Off X 5 X 5 20 220 50 International model 18 R4150L1003 R7140L1009 RM7840L1018 ST7800A1062 72 LHL, or (90 seconds) HF-LF RM7840L1075 Proven X X X X 10 X 10, 15 15 3120 60 wire R4150L1011 R7140L1009 RM7840L1018 ST7800A1062 72 LHL, (90 seconds) HF-LF or Proven RM7840L1075 X X X X 10 X 10, 15 15 3120 60 wire R4150L1029 R7140L1009 RM7840L1018 ST7800A1054 60 LHL, or HF-LF RM7840L1075 Proven X X X X 10 X 10 15 4120 60 Gordon-Piatt Energy GP300 (original) wire R4150L1037 R7140L1009 RM7840L1018 ST7800A1062 72 LHL, or (90 seconds) HF-LF RM7840L1075 Proven X X X X 10 X 10, 15 15 4120 60 wire R4150L1045 R7140L1009 RM7840L1018 ST7800A1062 72 LHL, (90 seconds) HF-LF or Proven RM7840L1075 X X X X 10 X 10, 15 15 4120 60 wire R4150L1052 Never Produced Never produced 72 LHL, HF-LF Proven X X X X 10 X 10, 15 15 4120 60 Cleaver Brooks CB4-1A wire R4150L1078 R7140L1009 RM7840L1018 ST7800A1054 60 LHL, or HF-LF RM7840L1075 Proven X X X X 10 X 10 15 4120 60 Gordon-Piatt Energy GP300 wire R4150L1060 Consult Original Equipment Manufacturer See footnotes on page 20 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. (Continued) Table 4. HONEYWELL R4150 PROGRAMMER CROSS REFERENCE. (Continued) R4150M1019 None 10 X 20 Frequency Voltage Modulation Postpurge MFEP 10 Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type R4150M1001 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X Hi-fire Purge Timer Preignition 1, 2, 6, 7, 8, 9 Lockout 7800 Series 1, 2, 6, 7, 8, 10 Running Device to be Replaced Interlocks Start Prepurge Timing Replacement Direct Comment 120 60 Ray Burner RM7840M1017 ST7800A1062 90 On-Off X X 10 X 10 20 120 60 Ray Burner - Special Base R4150M1027 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15 15 120 60 R4150M1035 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15 15 120 60 R4150M1043 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15 X 15 120 60 R4150M1050 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X 10 X 15, 30 15 120 60 R4150M1068 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X 10 X 15 15 120 60 R4150M1076 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X 10 X 15 X 15 120 60 R4150M1084 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X 10 X 15 15 120 60 10 X 15 X 20 R4150M1092 None RM7840M1017 ST7800A1062 90 On-Off X X 120 60 Gordon-Piatt Energy GP100 (original) 19 R4150M1100 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X 10 X 10, 30 15 120 60 R4150M1118 None RM7840M1017 ST7800A1039 30 On-Off X X 15 X 15 X 15 120 60 R4150M1126 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X 10 X 10 X 15 120 60 R4150M1134 R7140M1007 RM7840M1017 ST7800A1039 30 On-Off X X 10 X R4150M1142 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X 10 R4150M1159 R7140M1007 RM7840M1017 ST7800A1062 90 On-Off X X 15 120 60 X 20 120 60 10 X 10 20 120 60 10 X 10 X 20 120 60 Gordon-Piatt Energy GP100 R4150M1167 Never Produced R4150M1175 None Never produced RM7840M1017 ST7800A1062 90 On-Off X X R4150X1004 International Model 30 On-Off X X 5 X 5 X 15 220 50 International model R4150X1012 International Model 30 On-Off X X 5 X 5 X 15 240 50 International model R4150X1020 International Model See footnotes on page 20 International model 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE 10 X 10 1 2 3 4 5 6 R4150 Start Interlocks become Pre-Ignition Interlock (must remain closed throughout purge) 4 or 10 Second PFEP 60 second MFEP is not available with replacement device Spring return Firing Rate Motor (damper motor) Remove Jumper J1 and J2 Select Proper Amplifier Old Amp Replacement Amp. R7257A1028 R7847A1033 R7258A1001 R7848A1008 R7259A1000 R7849A1023 7 With Selectable Airflow Switch Check (AFC) Used with Existing Flame Detectors - EXCEPT - C7012E, F - Replace with C7061A, F and appropriate R7861 Flame Amplifier 9 Requires Q7800A or B Wiring Subbase 10 Check the wiring base - if 3 terminal strips - update to the 7800 Series option - Do not use the R7140 option. 8 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 4 Footnotes 20 Table 5. HONEYWELL R4181 PROGRAMMER CROSS REFERENCE. Frequency Voltage Modulation MFEP 40 ST7800A1054 60 R4181A1026 RM7840G1014 ST7800A1047 or RM7840G1022 40 R4181A1034 RM7840L1018 or RM7840L1075 ST7800A1054 60 X R4181A1042 RM7840L1018 or RM7840L1075 ST7800A1054 60 X X X X X 10 X 10, 15 X 20 4-wire 120 60 R4181A1059 RM7840L1018 or RM7840L1075 ST7800A1054 (60 seconds) 55 X X X X X 7 X 10, 30 X 16 4-wire 120 60 21 Table 5 Footnotes 1 Replacement suggestion is 120Vac, 50/60 Hz. X LF PRV X X X 10 X 15, 30 15 4-wire 120 60 208 240 X X X X 10 X 15, 30 15 4-wire 120 60 208 240 X X X 10 X 15, 30 15 4-wire 120 60 208 240 X X X X 10 X 10, 15 15 4-wire 120 60 208 240 Comments 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE R4181A1000 RM7840G1014 ST7800A1047 or RM7840G1022 R4181A1018 RM7840L1018 or RM7840L1075 LF PRV OP Damp Postpurge LHL PRV Spark Term LHL INTR Pilot Lo-Fire Timing On-Off INTM Pilot Purge Timer PFEP 1 Lockout 7800 Series Replacement Running Device to be Replaced Start Type Lo-fire Interlocks Hi-fire Prepurge Preignition Replacement Frequency Voltage Modulation Postpurge MFEP Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Lockout OP Damp Running Current Device to be Replacement 7800 Series Lo-Fire LHL Replaced Replacement Timing On-Off LHL PRV 1 Start Type Hi-fire Interlocks Preignition Prepurge Comments R8169A1007 Consult Original Equipment None 60 X X X 7 X 13 80 120 60 Proprietary to Lennox R8169A1015 Consult Original Equipment None 60 X X X 7 X 13 80 240 50 Proprietary to Lennox R8169B1005 Consult Original Equipment None 60 HL X X 7 X 13 80 120 60 Proprietary to Lennox R8169B1013 Consult Original Equipment None 60 HL X X 7 X 13 80 240 50 Proprietary to Lennox 22 Table 6 Footnotes 1 Contact OEM for replacement suggestions. PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 6. HONEYWELL R8169 PROGRAMMER CROSS REFERENCE. Table 7. HONEYWELL PROGRAM MODULE PROGRAMMER CROSS REFERENCE. Frequency Voltage Postpurge MFEP Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type Hi-fire Purge Timer Preignition 1 2 3 4 5 6 7 Lockout 1 3 4 5 7800 Series Replacement Interlocks Running Used With Direct Prepurge Start Program Module Replacement Timing Device to be Replaced Comments PM720G1197 BC7000L1042 Consult Original Equipment Manufacturer 40 4-wire LHL, LF Proven X X X X 10 X 10,15 15 120 60 Proprietary to York-Shipley, LWCO annunciation on terminal 18 PM720G1205 BC7000L1042 Consult Original Equipment Manufacturer 40 4-wire LHL, LF Proven X X X X 10 X 10,15 15 120 60 Proprietary to York-Shipley, LWCO annunciation on terminal 18 23 PM720G2005 BC7000L1000 R7140G2008 RM7800G1018 ST7800A1047 40 4-wire LHL, or LF Proven RM7840G1022 X X X 10 X 10,15, 30 X 15 120 60 PM720G2013 BC7000L1000 R7140G2008 RM7800G1018 ST7800A1047 40 4-wire LHL, or LF Proven RM7840G1022 X X X 10 X 10* X 15 120 60 * 10 sec MFEP or intermittent pilot PM720G2021 BC7000L1000 Consult Original Equipment Manufacturer 60 4-wire LHL, LF Proven X X X 7 X 13* 30 120 60 * 13 sec MFEP or intermittent pilot proprietary to Lennox PM720G2039 BC7000L1000 R7140G2008 RM7800G1018 ST7800A1047 40 4-wire LHL, LF Proven or RM7840G1022 X X X 10 X 10,15, 30 30 4-wire LHL, HF-LF Proven X X X X 7 X 8 PM720L1030 BC7000L1000 R7140L2007 RM7800L1012 ST7800A1039 30 4-wire LHL, or HF-LF RM7800L1087 Proven X X X X 10 X 10,15 PM720L1063 BC7000L1034 Consult Original Equipment Manufacturer 4-wire LHL, HF-LF Proven X X X X 7 X 8 4 120 60 Proprietary to Vapor Corporation PM720L1097 BC7000L1018 Consult Original Equipment Manufacturer 30 4-wire LHL, HF-LF Proven X X X X 7 X 8 4 120 50 Proprietary to Cleaver Brooks PM720L1105 BC7000L1034 Consult Original Equipment Manufacturer 8 4-wire LHL, HF-LF Proven X X X X 7 X 8 4 120 50 Proprietary to Vapor Corporation PM720L1113 BC7000L1042 Consult Original Equipment Manufacturer 30 4-wire LHL, HF-LF Proven X X X X 10 X 10,15 15 120 60 Proprietary to York-Shipley, LWCO annunciation on terminal 18 PM720L1022 BC7000L1018 Consult Original Equipment Manufacturer 4 120 60 Proprietary to Cleaver Brooks X 15 120 60 PM720L1089 NEVER PRODUCED 70-8313—02 See footnotes on page 25 PROGRAMMER CONTROL CROSS REFERENCE 8 X 15 120 50 Frequency Voltage Postpurge MFEP Spark Term INTR Pilot INTM Pilot PFEP Lo-fire Type Hi-fire Purge Timer Preignition 1 2 3 4 5 6 7 Lockout 1 3 4 5 7800 Series Replacement Interlocks Running Used With Direct Prepurge Start Program Module Replacement Timing Device to be Replaced Comments 30 4-wire LHL, HF-LF Proven X X X X 10 X 10,15 PM720L1139 BC7000L1000 R7140L2007 RM7800L1012 ST7800A1039 30 4-wire LHL, or HF-LF RM7800L1087 Proven X X X X 10 X 10,15 X 15 120 60 Reduced sensitivity to line noise PM720L2004 BC7000L1000 None RM7800E1010 ST7800A1039 30 4-wire LHL, HF-LF Proven X X X X 10 X 10,15 X 15 120 60 Energy saving prepurge (ESP) PM720L2012 BC7000L1000 R7140L2007 RM7800L1012 ST7800A1039 30 4-wire LHL, HF-LF or Proven RM7800L1087 X X X X 10 X 10,15 X 15 120 50 PM720L2020 BC7000L1000 R7140L2007 RM7800L1012 ST7800A1021 10 4-wire LHL, or HF-LF RM7800L1087 Proven X X X X 10 X 10,15 X 15 120 60 PM720L1121 BC7000L1042 Consult Original Equipment Manufacturer 15 120 60 Proprietary to York-Shipley, LWCO annunciation on terminal 18, energy saving prepurge (ESP) 24 PM720M2002 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1039 30, 2-wire On(30 seconds), 90 Off, LF ST7800A1062 Proven (90 seconds) X X X 10 X 10* X 15 120 60 * 10 second MFEP or intermittent pilot PM720M2010 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1013 7 (7 seconds) 2-wire OnOff, LF Proven X X X 10 X 10* X 15 120 60 * 10 second MFEP or intermittent pilot PM720M2036 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1013 7, 2-wire On(7 seconds), 30 Off, LF Proven ST7800A1039 (30 seconds) X X X 10 X 10* X 15 120 60 * 10 second MFEP or intermittent pilot PM720M2044 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1039 30, 2-wire On(30 seconds), 90 Off, LF ST7800A1062 Proven (90 seconds) X X X 10 X 10* X 15 120 50 * 10 second MFEP or intermittent pilot PM720M2051 BC7000L1000 R7140M1007 RM7800M1011 ST7800A1013 7, 2-wire On(7 seconds), 30 Off, LF ST7800A1039 Proven (30 seconds) X X X 10 X 10* X 15 120 50 * 10 second MFEP or intermittent pilot See footnotes on page 25 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 7. HONEYWELL PROGRAM MODULE PROGRAMMER CROSS REFERENCE. (Continued) Table 7 Footnotes 1 4 or 10 second PFEP With S7800A1001 Keyboard Display Module 3 Select Proper Amplifier 2 Old Amplifer Replacement Amplifer R7247A1005 R7847A1033 R7247A1021 R7847A1025 R7247B1003 R7847B1031 R7247C1001 R7861A1026 See Note 5 R7248A1004 R7848A1008 R7248B1028 R7848B1006 R7249A1003 R7849A1023 R7476A1007 R7886A1001 4 With Selectable Airflow Switch Check Used with Existing Flame Detectors - EXCEPT - C7012E, F - Replace with C7061A, M, F and appropriate R7861 Flame Amplifier 6 Requires Q7800A or B Wiring Subbase 7 For RM7840, order S7800A1142 display seperately 5 25 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Frequency Voltage Modulation Postpurge MFEP Spark Term INTR Pilot PFEP INTM Pilot Lo-fire Lockout Running Device to be Current 7800 Series Lo-Fire LHL Replaced Replacement Replacement Timing On-Off LHL PRV Start Type Hi-fire Interlocks Preignition Prepurge Comments BC7000L1000 None See Program Module for Current Replacements 120 BC7000L1018 None Consult Original Equipment Manufacturer 120 Proprietary to Cleaver Brooks BC7000L1034 None Consult Original Equipment Manufacturer 120 Proprietary to Vapor Corporation BC7000L1042 None Consult Original Equipment Manufacturer 120 Proprietary to YorkShipley, LWCO annunciation on terminal 18 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 8. HONEYWELL BC7000 PROGRAMMER CROSS REFERENCE. 26 Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. Interlocks EC7810A1035 EC7810A1027 EC7810A1035 Selectable Selectable Selectable X Selectable 2-wire using LF Proven ST7800B X Selectable 2-wire LF Proven X Selectable 2-wire LF Proven X Selectable 2-wire Proven using LF Proven ST7800B X Selectable 2-wire Proven using LF Proven ST7800B X Selectable 2-wire Proven LF Proven X Selectable 2-wire Proven LF Proven X Selectable 2-wire using LF Proven ST7800B X Selectable LF Proven Proven using ST7800B X X EC7820A1018 EC7820A1026 EC7820A1034 EC7810A1001 EC7830A1009 EC7820A1026 EC7820A1034 EC7820A1026 EC7820A1034 EC7810A1027 EC7830A1033 70-8313—02 See footnotes on page 34 Selectable Selectable Selectable Selectable Selectable Selectable 5, 8 220 to 240 50 With 5 second Pilot and 5 second Main Stabilization Time. FFRT 1.0 or 2.0 seconds Less Fan Output CE Listed X X X Config X urable 5, 10 X X 5, 8 220 to 240 50 With 5 second Pilot and 5 second Main Stabilization Time. FFRT 1.0 or 2.0 seconds Less Fan Output CE Listed Config X urable 5, 10 X X 5, 8 220 to 240 50/ With 5 second Pilot and 5 second 60 Main Stabilization Time. FFRT 1.0 or 2.0 seconds Less Fan Output CE Listed Config X urable 5, 10 X X 5, 8 220 to 240 50/ With 5 second Pilot and 5 second 60 Main Stabilization Time. FFRT 1.0 or 2.0 seconds Less Fan Output CE Listed Config X urable 5, 10 X X 5, 8 220 to 240 50 With 5 second Pilot and 5 second Main Stabilization Time. FFRT 1.0 or 2.0 seconds With Fan Output CE Listed Config X urable 5, 10 X X 5, 8 220 to 240 50 With 5 second Pilot and 5 second Main Stabilization Time. FFRT 1.0 or 2.0 seconds With Fan Output CE Listed Config X urable 5, 10 X X 5, 8 220 to 240 50/ With 5 second Pilot and 5 second 60 Main Stabilization Time. FFRT 1.0 or 2.0 seconds With Fan Output CE Listed Config X urable 5, 10 X X 5, 8 220 to 240 50/ With 5 second Pilot and 5 second 60 Main Stabilization Time. FFRT 1.0 or 2.0 seconds With Fan Output CE Listed Config X urable 5, 10 X X 5, 8 220 to 240 50 With 5 second Pilot and 5 second Main Stabilization Time. FFRT 1.0 or 2.0 seconds Less Fan Output CE Listed Config X urable 3 or 5 X X 3 or 5 220 to 240 50 With 5 second Pilot Stabilization Time. FFRT 1.0 or 2.0 seconds CE Listed 4 X X X 4 X X X 4 X X X 4 X X X 4 X X X 4 X X X 4 X X X 4 X X X 4 2 Frequency X Voltage X PFEP Postpurge 5, 10 4 27 EC7820A1000 MFEP Config X urable Run/Test Switch3 X Lo-fire X Comments PROGRAMMER CONTROL CROSS REFERENCE Selectable 2-wire using LF Proven ST7800B Hi-fire Airflow INTR Pilot EC7810A1027 EC7810A1035 Selectable Damper Position INTM Pilot EC7810A1019 EC7810A1027 1 Preignition EC7810A1001 Timing Lockout Enhanced Flame Replacement Amplifier Device to be Current option Replaced Replacement 2 Start Running Type Dynamic Air-Flow SW Check Prepurge Interlocks EC7830A1025 EC7830A1066 Selectable Selectable LF Proven Proven using ST7800B X X X X Selectable LF Proven Proven X EC7830A1033 EC7830A1033 Selectable MFEP Config X urable 3 or 5 X X 3 or 5 30 220 to 240 50 With 5 second Pilot Stabilization Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 15 220 to 240 50 With 5 second Pilot Stabilization Time. FFRT 1.0 or 2.0 seconds CE Listed Fulton Proprietary Config X urable 3 or 5 X X 3 or 5 2 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Fulton Proprietary Config X urable 3 or 5 X X 3 or 5 15 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 4, 10 X 10, 15 15 240 50/ Programmer control with Valve 60 Proving Feature and Programmable Post Purge.Requires S7800A1142 Display Module to program. With Blinkum Fault Messaging. Config X urable 3 or 5 X X 3 or 5 2 220 to 240 50 With 5 second Pilot Stabilization Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 220 to 240 50 With 5 second Pilot Stabilization Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 2 220 to 240 60 With 5 second Pilot Stabilization Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 220 to 240 60 With 5 second Pilot Stabilization Time. FFRT 1.0 or 2.0 seconds CE Listed PFEP 4 4 X X X 4 EC7830A1041 EC7830A1041 Selectable Selectable LF Proven Proven X X X X EC7830A1058 EC7830A1058 Selectable Selectable LF Proven Proven X X X X 4 28 4 EC7830A1066 EC7830A1066 Selectable Selectable LF Proven Proven X X X X 4 EC7840L1014 EC7840L1014 EC7840L1014 Selectable Selectable 4-wire Proven LHL HF, LF PRV X X X X 4 EC7850A1007 EC7850A1072 Selectable Selectable 4-wire Proven using LHL HF, LF ST7800B PRV X X X X EC7850A1015 EC7850A1080 Selectable Selectable 4-wire Proven using LHL HF, LF ST7800B PRV X X X X EC7850A1031 EC7850A1106 Selectable Selectable 4-wire Proven using LHL HF, LF ST7800B PRV X X X X Selectable 4-wire Proven using LHL HF, LF ST7800B PRV X EC7850A1049 EC7850A1114 See footnotes on page 34 Selectable 4 4 4 X X X 4 Frequency X Voltage X Postpurge X INTR Pilot X Airflow INTM Pilot Selectable LF Proven Proven using ST7800B Damper Position Run/Test Switch3 Selectable 1 Lo-fire EC7830A1041 Timing Hi-fire Preignition EC7830A1017 Enhanced Flame Device to be Current Replacement Amplifier Replaced Replacement option 2 Start Running Lockout Type Dynamic Air-Flow SW Check Prepurge Comments PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued) Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued) Interlocks EC7850A1072 Selectable Selectable Selectable 4-wire Proven LHL HF, LF PRV X Selectable 4-wire Proven LHL HF, LF PRV X Selectable 4-wire Proven LHL HF, LF PRV X X X X X X X X X X X EC7850A1098 EC7850A1098 Selectable Selectable 4-wire Proven LHL HF, LF PRV X X X X Selectable 4-wire Proven LHL HF, LF PRV X Selectable 4-wire Proven LHL HF, LF PRV X EC7850A1080 Selectable 3 or 5 X X 3 or 5 30 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 2 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Fulton Proprietary Config X urable 3 or 5 X X 3 or 5 2 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 15 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 2 220 to 240 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds PFEP with Early Spark Termination (2 or 6 seconds based on Configuration Resistor. CE Listed 220 to 240 50/ Fulton Proprietory 60 Pulse Firing 4 X X X 4 X X X 4 EC7850A1122 Selectable Selectable 4-wire Proven LHL HF, LF PRV X X X X EC7850A1148 EC7850A1072 Selectable Selectable 4-wire Proven LHL HF, LF PRV X X X X 4 4 EC7865A1005 RM7800E1002 RM7800E1010 RM7800E1010 RM7800E1010 70-8313—02 See footnotes on page 34 Selectable Selectable Selectable 4-wire Proven LHL HF, LF PRV X Selectable 4-wire Proven LHL HF, LF PRV X X X X X X Comments With 5 second Pilot Stabilization Time. FFRT 1.0 or 2.0 seconds CE Listed Fulton Proprietary Config X urable 4, 10 X 10, 15 15 120 50 Config X urable 4, 10 X 10, 15 15 120 50/ with Energy Saving Purge and 60 display module 4 X Frequency Config X urable Voltage 60 Postpurge 30 220 to 240 4 EC7850A1122 EC7865A1005 3 or 5 4 with Energy Saving Purge and display module PROGRAMMER CONTROL CROSS REFERENCE X 29 Selectable 4-wire Proven LHL HF, LF PRV EC7850A1114 X 4 Selectable Selectable X PFEP 4 EC7850A1080 EC7850A1072 3 or 5 4 EC7850A1080 EC7850A1106 MFEP Config X urable Run/Test Switch3 X Lo-fire X Hi-fire Airflow INTR Pilot EC7850A1072 EC7850A1064 Selectable Damper Position INTM Pilot EC7850A1064 EC7850A1098 1 Preignition EC7850A1056 Timing Lockout Enhanced Flame Device to be Current Replacement Amplifier Replaced Replacement option 2 Start Running Type Dynamic Air-Flow SW Check Prepurge Interlocks RM7800G1018 RM7800G1018 RM7840G1022 Selectable add S7800A1142 Display Selectable 4-wire LHL LF PRV Proven RM7800L1004 RM7800L1012 RM7800L1087 Selectable Selectable 4-wire Proven LHL HF, LF PRV X RM7800L1012 RM7800L1012 RM7800L1087 Selectable Selectable 4-wire Proven LHL HF, LF PRV X X X X RM7800L1038 RM7800L1038 Contact OEM Contact OEM 4-wire Proven LHL HF, LF PRV X X X X RM7800L1046 RM7800L1046 Contact OEM Contact OEM 4-wire Proven LHL HF, LF PRV X X X X Selectable Selectable 4-wire Proven LHL HF, LF PRV X RM7800L1053 RM7800L1053 X X X X X X X X X 50 Config X urable 4, 10 X X 10, 15, 15 120 30 50/ With display module 60 Config X urable 4, 10 X 10, 15 15 120 50 Config X urable 4, 10 X 10, 15 15 120 50/ With display module 60 Config X urable 4, 10 X 10, 15 15 120 50/ Fulton Proprietary 60 Config X urable 4, 10 X 10, 15 15 120 50/ Vapor Proprietary (49320086) 60 Config X urable 4, 10 X 10, 15 15 120 50/ With display module-Intermittent 60 Pilot Config X urable 4, 10 X 10, 15 15 120 50/ Cleaver Brook Proprietary (83360 2719) Config X urable 4, 10 X 10, 15 15 120 50/ Cleaver Brook Proprietary (83360 2718) Config X urable 4, 10 X 10, 15 15 120 50/ Programmer control with Valve 60 Proving Feature and Programmable Post Purge comes with S7800A1142 display module, With Blinkum Fault Messaging. Config X urable 4, 10 X 10, 15 15 120 50/ Programmer control with Valve 60 Proving Feature and Programmable Post Purge comes with S7800A1142 display module, With Blinkum Fault Messaging. Cleaver Brook Proprietary (83303517) 4 4 4 X X X X 4 4-wire Proven LHL HF, LF PRV X X X X RM7800L1079 RM7800L1079 Contact OEM Contact OEM 4-wire Proven LHL HF, LF PRV X X X X RM7800L1087 RM7800L1087 Selectable Selectable 4-wire Proven LHL HF, LF PRV X X X X Contact OEM X 4-wire Proven LHL HF, LF PRV MFEP Frequency 10, 15, 15 120 30 Voltage X Postpurge X PFEP Comments With display module With display module 4 Contact OEM See footnotes on page 34 4, 10 4 Contact OEM Contact OEM Config X urable 4 RM7800L1061 RM7800L1079 RM7800L1095 RM7800L1095 INTR Pilot Proven INTM Pilot Selectable 4-wire LHL LF PRV 30 RM7800G1000 RM7800G1018 RM7840G1022 Selectable add S7800A1142 Display Run/Test Switch3 Airflow Lo-fire Damper Position Hi-fire 1 Preignition Timing Lockout Enhanced Flame Device to be Current Replacement Amplifier Replaced Replacement option 2 Start Running Type Dynamic Air-Flow SW Check Prepurge 4 4 4 X X X 4 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued) Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued) Interlocks X X X RM7800M1011 RM7800M1011 Selectable Selectable 2-wire On- Proven Off, LF PRV X X X Contact OEM Contact OEM 2-wire On- Proven Off, LF PRV X RM7830A1003 RM7830A1003 Selectable Selectable LF Proven Proven X X X X RM7830A1011 RM7830A1011 Selectable Selectable LF Proven Proven X X X X RM7830A1029 RM7830A1029 Selectable Selectable LF Proven Proven X X X X RM7800M1037 RM7800M1037 4, 10 X X 10 15 120 50 Config X urable 4, 10 X X 10 15 120 50/ With display module 60 Config X urable 4, 10 X X 10 15 120 50/ Fulton Proprietary 60 Config X urable 3 or 5 X X 3 or 5 2 120 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 15 120 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 120 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 4, 10 X 10, 15 15 120 50 Config X urable 4, 10 X 10, 15 15 120 50/ with Energy Saving Purge 60 Config X urable 4, 10 X X 10, 15, 15 120 30 50 Config X urable 4, 10 X X 10, 15, 15 120 30 50/ 60 Config X urable 4, 10 X X 10, 15, 15 120 30 50/ Programmer control with Valve 60 Proving Feature and Programmable Post Purge.Requires S7800A1142 Display Module to program. With Blinkum Fault Messaging. Config X urable 4, 10 X 10, 15 15 120 50 PFEP 4 X X 4 4 31 4 Selectable Selectable 4-wire Proven LHL HF, LF PRV X Selectable 4-wire Proven LHL HF, LF PRV X X X X X X X 4 RM7840G1006 RM7840G1014 RM7840G1022 Selectable Selectable 4-wire LHL LF PRV Proven X X X RM7840G1014 RM7840G1014 RM7840G1022 Selectable Selectable 4-wire LHL LF PRV Proven X X X Selectable 4-wire LHL LF PRV Proven RM7840G1022 RM7840G1022 Selectable RM7840L1000 RM7840L1018 RM7840L1075 Selectable 70-8313—02 See footnotes on page 34 4 4 Selectable 4-wire Proven LHL HF, LF PRV with Energy Saving Purge 4 X X X 4 X X X X 4 PROGRAMMER CONTROL CROSS REFERENCE RM7840E1016 RM7840E1016 Selectable Comments With display module 4 4 RM7840E1008 RM7840E1016 Frequency Config X urable Voltage MFEP Postpurge Selectable 2-wire On- Proven Off, LF PRV INTR Pilot Selectable INTM Pilot RM7800M1003 RM7800M1011 Run/Test Switch3 Airflow Lo-fire Damper Position Hi-fire 1 Preignition Timing Lockout Enhanced Flame Device to be Current Replacement Amplifier Replaced Replacement option 2 Start Running Type Dynamic Air-Flow SW Check Prepurge RM7840L1026 RM7840L1026 Selectable 4-wire Proven LHL HF, LF PRV X X X X Contact OEM Contact OEM 4-wire Proven LHL HF, LF PRV X Contact OEM Contact OEM 4-wire Proven LHL HF, LF PRV X RM7840L1034 RM7840L1042 RM7840L1042 RM7840L1042 Selectable MFEP X 10, 15 15 120 50/ 60 X 10, 15 15 120 50/ Intermittent Pilot 60 4, 10 X 10, 15 15 120 50 4, 10 X 10, 15 15 120 50/ Cleaver Brook Proprietary (83360 2720) PFEP Config X urable 4, 10 Config X urable 4, 10 Config X urable Config X urable 4 X 4 X X X Frequency X Voltage Lo-fire X Airflow Postpurge Hi-fire X Damper Position INTR Pilot Preignition X 1 INTM Pilot Lockout Selectable 4-wire Proven LHL HF, LF PRV Timing Start Running RM7840L1018 RM7840L1018 RM7840L1075 Selectable Enhanced Flame Device to be Current Replacement Amplifier Replaced Replacement option 2 Run/Test Switch3 Interlocks Type Dynamic Air-Flow SW Check Prepurge 4 X X X 4 Comments Cleaver Brook Proprietary (8332721) RM7840L1059 Never Produced Never Produced RM7840L1067 Never Produced Never Produced 32 RM7840L1075 RM7840L1075 RM7840L1083 RM7840L1083 RM7840L1091 RM7840L1091 RM7840M1009 RM7840M1017 RM7840M1017 RM7840M1017 See footnotes on page 34 Selectable Selectable 4-wire Proven LHL HF, LF PRV X Contact OEM Contact OEM 4-wire Proven LHL HF, LF PRV X Selectable Selectable 4-wire Proven LHL HF, LF PRV X Selectable Selectable X X X Config X urable 4, 10 X 10, 15 15 120 50/ Programmer control with Valve 60 Proving Feature and Programmable Post Purge.Requires S7800A1142 Display Module to program. With Blinkum Fault Messaging. Config X urable 4, 10 X 10, 15 15 120 50/ Programmer control with Valve 60 Proving Feature and Programmable Post Purge.Requires S7800A1142 Display Module to program. With Blinkum Fault Messaging. Cleaver Brook Proprietary (833-03518) Config X urable 4 (fixed) X 10, 15 15 120 50/ Programmer control with Valve 60 Proving Feature and Programmable Post Purge.Requires S7800A1142 Display Module to program. With Blinkum Fault Messaging. Config X urable 4, 10 X X 10 15 120 50 Config X urable 4, 10 X X 10 15 120 50/ 60 4 X X X 4 X X X 4 Selectable 2-wire On- Proven Off, LF PRV X Selectable 2-wire On- Proven Off, LF PRV X X X 4 X X 4 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued) Table 9. HONEYWELL 7800 SERIES PROGRAMMER CROSS REFERENCE. (Continued) Lo-fire X X X Frequency Hi-fire X 15 120 50/ 60 X X 3 or 5 2 120 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed 3 or 5 X X 3 or 5 `5 120 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 30 120 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds CE Listed Config X urable 3 or 5 X X 3 or 5 2 120 50/ With 5 second Pilot Stabilization 60 Time. FFRT 1.0 or 2.0 seconds PFEP with Early Spark Termination (2 or 6 seconds based on Configuration Resistor. CE Listed RM7865A1009 RM7865C1007 120 50/ Fulton Proprietory 60 Pulse Firing RM7865B1008 RM7865C1007 120 50/ Fulton Proprietory 60 Pulse Firing RM7865C1007 RM7865C1007 120 50/ Fulton Proprietory 60 Pulse Firing 1 Damper Position Airflow RM7845A1001 RM7845A1001 RM7840L1075 Selectable Selectable 4-wire Proven LHL HF, LF PRV RM7850A1001 RM7850A1001 Selectable 4-wire Proven LHL HF, LF PRV X Selectable 4-wire Proven LHL HF, LF PRV X RM7850A1019 RM7850A1019 Selectable Selectable PFEP Config X urable 4, 10 Config X urable 3 or 5 Config X urable Voltage 10 Timing Run/Test Switch3 X Enhanced Flame Device to be Current Replacement Amplifier Replaced Replacement option 2 Start Running MFEP Postpurge Preignition X INTR Pilot Lockout X INTM Pilot Interlocks Type Dynamic Air-Flow SW Check Prepurge 4 X 4 X X X 4 RM7850A1027 RM7850A1027 Selectable Proven Selectable 4-wire LHL HF, LF PRV X X X X RM7850A1035 RM7850A1035 Selectable Selectable 4-wire Proven LHL HF, LF PRV X X X X 4 4 33 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE See footnotes on page 34 Comments 1 Amplifier Options FFRT* (seconds) Standard Ampli-check Rectification Flame Rods 0.8 or 1.0 R7847A1025 R7847B1023 C7012A, C 2.0 or 3.0 R7847A1033 R7847B1031 >50 feet leadwire run >50 feet leadwire run R7847A1074 R7847B1064 R7847A1082 R7847B1072 0.8 or 1.0 R7849A1015 R7849B1013 2.0 or 3.0 R7849A1023 R7849B1021 Rectifier pilot burners (Q179, C7005) UV C7027, C7035, C7044 Shutter-Check UV Detector 34 C7012E, F 2.0 or 3.0 R7847C1005 C7061A, M, F 0.8 or 1.0 R7861A1034 2.0 or 3.0 R7861A1026 C7076A, D 2.0 or 3.0 R7886A1001 C7961E, F 2.0 or 3.0 R7851C1008 Optical C7927 (UV) 0.8 or 1.0 R7851B1018 C7962 (Visible) 2.0 or 3.0 R7851B1000 Infrared C7915 2 3 4 2.0 or 3.0 R7852A1001 R7852B1009 *Flame Failure Response Time Purge Timer Options Timing ST7800 Timing ST7800 2 seconds A1005 2.5 Minute A1070 7 seconds A1013 4 Minute A1088 10 seconds A1021 6 Minute A1096 30 seconds A1039 9 Minute A1104 40 seconds A1047 12 Minute A1112 60 seconds A1054 15 Minute A1120 90 seconds A1062 22 Minute A1138 30 Minute A1146 Flame-out timer used with Run/Test Switch. Allows pilot to be momentarily extinguished and caused LOCKOUT if total no flame time exceeds 15 seconds. Selected with Configuration Resistor, See instruction sheet. PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 9 7800 PROGRAMMER SERIES FOOTNOTES: Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. 24PJ8 1000 2 6 10 14 2 6 11 RM7840G1014 or RM7840L1018 or RM7840G1022 RM7840L1075 Amplifier R7847A1033 Purge Timer ST7800A1005 Timing 0 None 25RU8 4580 NONE RM7840L1018 or 18 R7861A1026 RM7840L1075 ST7800A1054 (60 seconds) 47 On-Off, LF Proving 25RU8 6558 10 14 10 ST7800A1039 (30 seconds) 33 3-wire, LHL, LF Proving 25RU8 6560 14 RM7840L1018 or 18 RM7840G1014 or RM7840L1075 R7849A1015 RM7840G1022 (0.8 FFRT) R7849A1023 (3.0 FFRT) ST7800A1054 60 24RU8 6566 14 RM7840L1018 or 18 RM7840G1014 or RM7840L1075 R7849A1023 RM7840G1022 ST7800A1039 35 24RJ8 1000 None 18 15, 30 Frequency Voltage Postpurge Spark Term INTR Pilot MFEP PFEP X 60 RM7840G1014 or RM7840L1018 or R7849A1023 RM7840G1022 RM7840L1075 INTM Pilot Hi-fire Lo-fire Lockout Type On-Off, LF Proving Preignition Interlocks Start Prepurge Running Replacement Control 7800 Series Replacement Current to meet Device to Replacement to Insurance be meet UL 1 4 5 7 9 11 12 Replaced 1 4 5 7 8 12 17 13 17 X Comments 15 0 115 230 50/60 Rectification type flame sensor, low voltage controller, vacuum tube. 80 120 50/60 1-4 sec FFRT, low voltage special for air heaters, vacuum tube electronics. 20 120 50/60 4 sec FFRT, used with selfcheck UV flame detector X X 8 X 10, 15 X X 7 X 10, 60 X 15 120 50/60 4 sec FFRT, UV type flame detector. 4-wire LHL, LF Proving X X 7 X 15, 40 X 10 120 50/60 1-4 sec FFRT, UV type flame detector. 30 2-wire On-Off, LF Proving X X 10 X 15, 25 10 120 50/60 4 sec FFRT, UV type flame detector. X X X 7 X 15, 30 X 15 120 50/60 4 sec FFRT, UV type flame detector. X X 10 X 10, 15, 30 X 20 120 50/60 1-2 sec FFRT, UV type flame detector. X X X X 25RU8 6570 NONE RM7840L1018 or 18 R7849A1023 RM7840L1075 ST7800A1054 (60 seconds) 63 4-wire LHL, HF, LF Proving 25RU8 6580 NONE RM7840L1018 or 18 R7849A1015 RM7840L1075 ST7800A1054 (60 seconds) 45 4-wire LHL, HF & LF Proving 26RJ8 1000 2 6 14 2 6 18 ST7800A1039 30 3-wire, LHL, LF Proving X 10 X 15 30 115 230 50/60 4 sec FFRT, IR type flame detector, low voltage controller. 26RJ8 1001 2 6 14 2 6 18 ST7800A1039 30 4-wire LHL, LF Proving X 10 X 15 30 115 230 50/60 Orr and Sewbower special, IR type flame detector, low voltage controller. 30 On-Off, LF Proving X 10 X 15 30 115 230 50/60 Cleaver Brooks special, 4 sec FFRT, IR type flame detector, low voltage controller. RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) 26RJ8 1002 Cleaver Brook Proprietary See footnotes on page 40 X X X 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE 7 Amplifier Purge Timer Timing Type PFEP Frequency Voltage Postpurge Spark Term INTR Pilot INTM Pilot Hi-fire Lo-fire Lockout Preignition Interlocks Start Prepurge Running Replacement Control 7800 Series Replacement Current to meet Device to Replacement to Insurance be meet UL 1 4 5 7 9 11 12 Replaced 1 4 5 7 8 12 17 13 17 MFEP Comments 36 26RJ8 1003 2 6 14 2 6 18 ST7800A1039 30 On-Off, LF Proving X 10 X 10 60 115 230 50/60 North America special, 4 sec FFRT, IR type flame detector, low voltage controller. 26RJ8 1004 6 14 6 18 ST7800A1039 30 On-Off, LF Proving X 10 X 60 15 115 230 50/60 4 sec FFRT, IR type flame detector, B&W FM boiler special, vacuum tube circuitry. 26RJ8 1005 6 6 18 ST7800A1039 30 On-Off, LF Proving X 10 X 10 60 115 230 50/60 4 sec FFRT, IR type flame detector, B&W FM boiler special, vacuum tube circuitry. 26RJ8 1006 2 6 10 14 2 6 10 18 ST7800A1039 30 On-Off, LF Proving X 10 X 15 30 115 230 50/60 4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 26RJ8 1008 2 6 14 2 6 18 ST7800A1039 30 On-Off, LF Proving X 10 X 15, 60 15 115 230 50/60 4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 26RJ8 1009 2 6 14 2 6 18 ST7800A1039 30 On-Off, LF Proving X 10 X 10, 15 60 115 230 50/60 4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 26RJ8 1011 2 6 10 14 2 6 10 18 ST7800A1005 (2 seconds) 0 On-Off, LF Proving X 10 X 10, 55 30 115 230 50/60 North America special, IR type flame detector, low voltage controller, vacuum tube circuitry. 2 3 6 3 18 26RJ8 1012 2 3 6 14 RM7840G1014 or RM7840L1018 or R7852A1001 26RJ8 RM7840G1022 RM7840L1075 (3.0 sec) 1012T ST7800A1047 (40 seconds) 35 4-wire LHL, LF Proving 10 X 15 25 115 230 50/60 North America special, dual IR type flame detectors, vacuum tube circuitry. 2 3 6 3 18 26RJ8 1016 2 3 6 14 RM7840G1014 or RM7840L1018 or R7852A1001 26RJ8 RM7840G1022 RM7840L1075 (3.0 sec) 1016T ST7800A1062 (90 seconds) 65 10 X 15 10 115 230 50/60 1 sec FFRT, dual IR type flame detectors, vacuum tube circuitry. 26RJ8 1018 ST7800A1054 (60 seconds) 45 4-wire LHL, LF Proving 10 X 15, 30 15 115 230 50/60 2-4 sec FFRT, IR type flame detectors, low voltage controller, vacuum tube circuitry 45 4-wire LHL, LF Proving 10 X 15, 30 15 120 208 240 50/60 U.S. Navy special, no replacement available,voltage controller, vacuum tube RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840M1017 RM7840L1018 or R7852A1001 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) 2 6 14 2 6 18 RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) 26RJ8 1114, NONE 26RJ8 1115, 26RJ8 5914 See footnotes on page 40 NONE X X X X X X X X X X PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Amplifier Purge Timer Timing Type 37 26RJ8 6008 2 6 14 2 6 18 ST7800A1047 (40 seconds) 35 3-wire, LHL, LF Proving X 26RJ8 6009 2 6 14 15 2 6 18 ST7800A1047 (40 seconds) 35 On-Off, LF Proving 26RJ8 6012 2 3 6 2 3 6 3 18 ST7800A1047 (40 seconds) 35 26RJ8 6016 2 3 6 2 3 6 3 18 ST7800A1062 (90 seconds) 26RJ8 6018 2 10 14 2 10 18 RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840M1017 RM7840L1018 or R7852A1001 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) PFEP Frequency Voltage Postpurge MFEP Comments X 15, 55 15 120 208 240 60 1-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. X 10 X 15 55 120 208 240 50/60 B&W FM boiler special, 14 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 4-wire LHL, LF Proving X 10 X 15 30 120 208 240 50/60 1-4 sec FFRT, dual IR type flame detectors, low voltage controller, vacuum tube circuitry. 65 4-wire LHL, LF Proving X 10 X 15 15 120 208 240 50/60 1-4 sec FFRT, dual IR type flame detectors, low voltage controller, vacuum tube circuitry. ST7800A1054 (60 seconds) 45 4-wire LHL, LF Proving X 15, 30 15 120 208 240 50/60 1-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. ST7800A1054 60 On-Off, LF Proving 15 80 120 60 1-4 sec FFRT, IR type flame detector, low voltage controller, special for air heaters X X 10 X X 7 26RJ8 6026 NONE NONE 26RJ8 6058 10 14 10 18 ST7800A1047 (40 seconds) 35 3-wire, LHL, LF Proving X X X 10 X 15, 55 15 120 60 1-4 sec FFRT, IR type flame detector, vacuum tube circuitry. 26RJ8 6060 10 14 10 18 ST7800A1054 60 4-wire LHL, LF Proving X X X 7 X 10, 30 20 120 50/60 1-4 sec FFRT, IR type flame detector, vacuum tube circuitry. 26RJ8 6066 10 14 10 18 ST7800A1039 30 On-Off, LF Proving X X X 10 X 15, 25 10 120 50/60 1-4 sec FFRT, IR type flame detector, vacuum tube circuitry. 26RJ8 6068 10 14 10 18 ST7800A1054 (60 seconds) 45 4-wire LHL, LF Proving X X 10 X 15, 30 15 120 60 1-4 sec FFRT, IR type flame detector, vacuum tube circuitry, for Canada. ST7800A1062 (90 seconds) 65 4-wire LHL, HF & LF Proving 10 X 15, 30 15 120 60 1-4 sec FFRT, IR type flame detector, vacuum tube circuitry. RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) 26RJ8 6070 NONE 70-8313—02 See footnotes on page 40 RM7840L1018 or 18 R7852A1001 RM7840L1075 (3.0 sec) X X X X PROGRAMMER CONTROL CROSS REFERENCE 10 X X Spark Term INTR Pilot INTM Pilot Hi-fire Lo-fire Lockout Preignition Interlocks Start 7800 Series Replacement Current to meet Device to Replacement to Insurance be meet UL 1 4 5 7 9 11 12 Replaced 1 4 5 7 8 12 17 13 17 Prepurge Running Replacement Control 45 4-wire LHL, HF & LF Proving 26RJ8 6160 14 RM7840L1018 or 18 RM7840G1014 or RM7840L1075 R7852A1001 RM7840G1022 (3.0 sec) ST7800A1054 60 4-wire LHL, LF Proving X 26RJ8 CB-1 Cleaver Brook Proprietary 45 4-wire LHL, LF Proving X 26RJ8 CB-3 Cleaver Brook Proprietary 45 4-wire LHL, HF & LF Proving 1-2 sec FFRT, IR type flame detector, vacuum tube circuitry. X 7 X 10, 30 X 20 120 50/60 1-4 sec FFRT, IR type flame detector, vacuum tube circuitry. X 10 X 15 15 120 50/60 Cleaver Brooks special, IR type flame detector, low voltage controller. X 10 X 10, 15, 30 20 120 50/60 Cleaver Brooks special, IR type flame detector, low voltage controller. X 10 15 115 230 50/60 1-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. X 13 15 115 230 50/60 1-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. PFEP X X X X Frequency 50/60 X Voltage 20 120 X INTR Pilot X X INTM Pilot Postpurge ST7800A1054 (60 seconds) 10, 15, 30 Hi-fire RM7840L1018 or 18 RM7840G1014 or RM7840L1075 R7852A1001 RM7840G1022 (3.0 sec) X X Type 14 10 Lo-fire Timing Lockout Purge Timer Preignition Amplifier 26RJ8 6080 Spark Term Interlocks Start Prepurge Running Replacement Control 7800 Series Replacement Current to meet Device to Replacement to Insurance be meet UL 1 4 5 7 9 11 12 Replaced 1 4 5 7 8 12 17 13 17 MFEP Comments 29RF5 1000 2 6 10 14 2 6 10 18 ST7800A1039 (30 seconds) 15 On-Off, LF Proving X X 5 29RF5 1001 2 6 10 14 2 6 10 18 ST7800A1039 (30 seconds) 25 On-Off, LF Proving X X 7 29RF5 1002 2 6 10 14 2 6 10 18 ST7800A1039 (30 seconds) 15 On-Off, LF Proving X X 5 X 15 15 115 230 50/60 1-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 29RF5 1005 2 6 14 2 6 18 ST7800A1039 (30 seconds) 15 On-Off, LF Proving X 5, 10 X 15 15 115 230 50/60 2-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 29RF5 1009 2 6 10 14 2 6 10 18 ST7800A1039 (30 seconds) 25 On-Off, LF Proving X 7 X 13 15 114 230 50/60 1-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 29RF5 1015 2 6 14 2 6 18 ST7800A1039 (30 seconds) 15 On-Off, LF Proving X 5, 10 X 15 15 115 230 50/60 2-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 15 On-Off, LF Proving X 5 X 15 15 115 230 50/60 Military special, IR type flame detector, low voltage controller, vacuum tube circuitry. RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) 38 RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) 29RF5 1103 NONE See footnotes on page 40 NONE X X X PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Table 10. FIREYE® P SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Purge Timer Timing Type 2 6 14 2 6 18 ST7800A1013 (7 seconds) 5 On-Off, LF Proving 29RF5 6009 2 6 10 14 2 6 10 18 ST7800A1039 (30 seconds) 25 On-Off, LF Proving 29RF5 6015 2 6 10 14 2 6 10 18 ST7800A1039 (30 seconds) 18 On-Off, LF Proving RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) RM7840G1014 or RM7840L1018 or R7852A1001 RM7840G1022 RM7840L1075 (3.0 sec) NONE PFEP X 5 X X 7 X X 5, 10 Frequency Voltage Postpurge Spark Term INTR Pilot INTM Pilot Hi-fire Lo-fire Lockout Preignition Amplifier 29RF5 1104 29RF5 6103 NONE Interlocks Start 7800 Series Replacement Current to meet Device to Replacement to Insurance be meet UL 1 4 5 7 9 11 12 Replaced 1 4 5 7 8 12 17 13 17 Prepurge Running Replacement Control MFEP X X X Comments 15 15 115 230 50/60 A.E.C. Kilns special, IR type flame detector, low voltage controller, vacuum tube circuitry. 13 15 120 208 240 60 1-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. 15 12 120 208 240 60 1-4 sec FFRT, IR type flame detector, low voltage controller, vacuum tube circuitry. Military special, IR type flame detector, vacuum tube circuitry. See footnotes on page 40 39 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 1 Refer to Modernization Wiring Information for conversion wiring information. Low Voltage controller will need to be upgraded to line voltage controller. 3 Replacement suggestion does not support dual IR detector feature, be sure to confirm application requirements. 4 Replacement control has 15 second postpurge. 5 Replacement control has 15 second postpurge, RM7840G1022 or RM7840L1075 have programmable postpurge option. 6 Replacement suggestion is 120 Vac, 50/60 Hz. 7 Requires Q7800A or Q7800B Wiring Subbase. 8 RM7840G,M meets current UL requirements. 9 RM7840L meets current insurance requirements. 10 Start interlocks become running interlocks using the replacment controls. (Required to start the equiment, and maintained throughout the call for heat). 11 Running Interlocks become lockout interlocks. (Opening interlock results in safety shutdown and control reset). 12 Replacement control has 10 second PFEP, 4 seconds available with JR1 clipped 13 Replacement has 10, 15 second MFEP. 14 Replacement has 10, 15, 30 second MFEP or intermittent pilot. 15 Replacement has 10 second MFEP or intermittent pilot. 16 5 second ignition early spark termination when ignition wired to terminal 10. 17 Display Module is available by ordering model shown in the table, or ordering seperately. 2 Suggestion Model Display Model 40 RM7840M1017 RM7800M1011 RM7840G1014 RM7800G1018 RM7840G1022 Order S7800A1142 seperately RM7840L1018 RM7800L1012 RM7840L1075 RM7800L1087 R7120D Order S7800A1001 seperately 18 Select appropriate flame detector and amplifier from table Flame Detection Type FFRT 0.8 sec 3.0 sec Comments Rectification R7847A1025 R7847A1033 Use existing Flame Rod Ultraviolet R7849A1015 R7849A1023 Order Honeywell flame detector C7027 or C7035 Infrared Self Check UV R7852A1001 Order Honeywell flame detector C7915 C7861A1034 R7861A1026 Order Honeywell flame detector C7061 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 10 FIREYE FOOTNOTES: Table 11. FIREYE® C SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. Amplifier Purge Timer Timing Type 10 10 R7847A1033 ST7800A1047 (40 seconds) 33 On-Off, X X LF Proving 7 X 24CJ5 3000 10 10 R7847A1033 ST7800A1039 30 On-Off, X X LF Proving 7 X 24CJ5 3010 10 10 R7847A1033 ST7800A1047 (40 seconds) 37 On-Off, X X LF Proving X 7 24CJ5 3011 10 10 R7847A1025 RM7840M1017 RM7840L1018 (0.8 FFRT) or R7847A1033 RM7840L1075 (3.0 FFRT) ST7800A1070 (2.5 minutes) 98 On-Off, X X LF Proving X 24CJ5 3014 10,14 10 R7847A1025 RM7840G1014 RM7840L1018 (0.8 FFRT) or or R7847A1033 RM7840G1022 RM7840L1075 (3.0 FFRT) ST7800A1054 60 3-wire, X X LHL, LF Proving RM7840M1017 RM7840L1018 or RM7840L1075 RM7840M1017 RM7840L1018 or RM7840L1075 Frequency Voltage Modulation Postpurge MFEP PFEP 24CJ5 1000 RM7840M1017 RM7840L1018 or RM7840L1075 Spark Term Interlocks INTM Pilot INTR Pilot Prepurge Start Running Lockout Preignition Hi-fire Lo-fire Replacement Control 7800 Series Current Replacement Current Plug Replacement to meet In to meet UL Insurance Device to be Replacement 1 4 5 7 8 12 1 4 5 7 9 11 Replaced 12 13 17 17 17 Comments 10 X 8 120 50/ 4 sec FFRT, 60 rectification type flame sensor, vacuum tube circuitry. 41 10 X 15 120 60 2-4 sec FFRT, rectification type flame sensor. X 10 X 15 120 60 2-4 sec FFRT, rectification type flame sensor. 7 X 10 X 25 120 60 1-4 sec FFRT, rectification type flame sensor. X 7 X 10 20 3-wire 120 60 1-4 sec FFRT, rectification type flame sensor. R7120D3007 10 10 R7847A1025 RM7840M1017 RM7840L1018 (0.8 FFRT) or R7847A1033 RM7840L1075 (3.0 FFRT) ST7800A1047 (40 seconds) 37 On-Off, X X LF Proving X 5 X 10 X 15 120 60 1-4 sec FFRT, rectification type flame sensor. 24CJ5 5011 R7120D3007 10 10 R7847A1025 RM7840M1017 RM7840L1018 (0.8 FFRT) or R7847A1033 RM7840L1075 (3.0 FFRT) ST7800A1070 (2.5 minutes) 98 On-Off, X X LF Proving X 5 X 10 X 25 120 60 1-4 sec FFRT, rectification type flame sensor. 24CJ5 5015 R7120D2000 14 RM7840L1018 R7847A1033 RM7840G1014 or or RM7840L1075 RM7840G1022 ST7800A1054 60 4-wire, LHL, LF Proving X X X 7 X 10, 15 15 4- wire 120 50/ 4 sec FFRT, 60 rectification type flame sensor. 24RJ8 1000 R7120D2000 14 RM7840L1018 R7847A1033 RM7840G1014 or or RM7840L1075 RM7840G1022 ST7800A1054 60 4-wire, LHL, LF Proving X X X 7 X 10, 15 15 4- wire 120 50/ 4 sec FFRT, 60 rectification type flame sensor. 10 ST7800A1039 30 On-Off, X X LF Proving 25CU6 1050 70-8313—02 See footnotes on page 44 10 18 RM7840M1017 RM7840L1018 R7849A1023 or RM7840L1075 7 X 10 X 15 120 60 4 sec FFRT, UV type flame detector. PROGRAMMER CONTROL CROSS REFERENCE 24CJ5 5010 Replacement Control Interlocks ST7800A1047 (40 seconds) 37 On-Off, X X LF Proving X 7 X 10 X 15 120 60 1-4 sec FFRT, UV type flame detector. 25CU6 1063 10 10 18 ST7800A1070 (2.5 minutes) 98 On-Off, X X LF Proving X 7 X 10 X 25 120 60 1-4 sec FFRT, UV type flame detector. 25CU6 1065 10 10 18 ST7800A1054 60 3-wire, X X LHL, LF Proving X 7 X 10 20 3-wire 120 60 1-4 sec FFRT, UV type flame detector. 120 60 1-4 sec FFRT, UV type flame detector. 120 60 1-4 sec FFRT, UV type flame detector. Amplifier RM7840M1017 RM7840L1018 R7849A1015 or (0.8 FFRT) RM7840L1075 R7849A1023 (3.0 FFRT) RM7840M1017 RM7840L1018 R7849A1015 or (0.8 FFRT) RM7840L1075 R7849A1023 (3.0 FFRT) RM7840G1014 RM7840L1018 R7849A1015 or or (0.8 FFRT) RM7840G1022 RM7840L1075 R7849A1023 (3.0 FFRT) Purge Timer Timing Type PFEP Frequency 18 Voltage 10 Modulation 10 INTM Pilot INTR Pilot 25CU6 1062 Start Running Lockout Preignition Hi-fire Lo-fire Postpurge Prepurge Spark Term 7800 Series Current Replacement Current Plug Replacement to meet In to meet UL Insurance Device to be Replacement 1 4 5 7 8 12 1 4 5 7 9 11 Replaced 17 12 13 17 17 MFEP Comments R7120D3007 10 10 18 ST7800A1047 (40 seconds) 37 On-Off, X X LF Proving X 7 X 10 X 25CU6 5063 R7120D3007 10 10 18 ST7800A1070 (2.5 minutes) 98 On-Off, X X LF Proving X 7 X 10 X 25CU6 5065 25CU6 5065A R7120D1002 18 RM7840L1018 10 RM7840L1018 R7849A1023 or RM7840L1075 or RM7840L1075 ST7800A1054 60 4-wire LHL, HF & LF Proving X 7 X 10, 15 20 4-wire 120 50/ 4 sec FFRT, UV 60 type flame detector. 25CU6 5066 25CU6 5066A R7120D1002 18 RM7840G1014 10 RM7840L1018 R7849A1023 or RM7840G1022 or RM7840L1075 ST7800A1054 60 3-wire, LHL, LF Proving X 7 X 10, 30 15 4-wire 120 50/ 4 sec FFRT, UV 60 type flame detector. 25CU6 RS-2 25CU6 RS-2D 10 10 18 ST7800A1039 30 On-Off, X X LF Proving X 10 X 15 120 60 Ray Burner special, 4 sec FFRT, UV type flame detector. 25CU6 RS-2RE R7120D3007 10 10 18 ST7800A1070 (2.5 minutes) 98 On-Off, X X LF Proving X 25 120 60 Ray Burner special, 1-4 sec FFRT, UV type flame detector. 26CF6 1000 10 10 18 ST7800A1039 30 On-Off, X X LF Proving 15 120 50/ 1-4 sec FFRT, IR 60 type flame detector. 42 25CU6 5062 See footnotes on page 44 RM7840M1017 RM7840L1018 R7849A1015 or (0.8 FFRT) RM7840L1075 R7849A1023 (3.0 FFRT) RM7840M1017 RM7840L1018 R7849A1015 or (0.8 FFRT) RM7840L1075 R7849A1023 (3.0 FFRT) RM7840M1017 RM7840L1018 R7849A1023 or RM7840L1075 RM7840M1017 RM7840L1018 R7849A1023 or RM7840L1075 RM7840M1017 RM7840L1018 R7852A1001 or (3.0 sec) RM7840L1075 X X X X X 7 X X 5 X 10 X 7 X 10 25 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 11. FIREYE® C SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Table 11. FIREYE® C SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Amplifier Purge Timer Timing Type PFEP MFEP Frequency Voltage Modulation Postpurge Spark Term Interlocks INTM Pilot INTR Pilot 7800 Series Current Replacement Current Plug Replacement to meet In to meet UL Insurance Device to be Replacement 1 4 5 7 8 12 1 4 5 7 9 11 Replaced 17 12 13 17 17 Prepurge Start Running Lockout Preignition Hi-fire Lo-fire Replacement Control Comments 26CF6 1010 10 10 18 ST7800A1047 (40 seconds) 37 On-Off, X X LF Proving X 7 X 10 X 15 120 50/ 1-4 sec FFRT, IR 60 type flame detector. 26CF6 1011 10 10 18 ST7800A1070 (2.5 minutes) 98 On-Off, X X LF Proving X 7 X 10 X 25 120 50/ 1-4 sec FFRT, IR 60 type flame detector. 26CF6 1012 10 14 10 18 ST7800A1054 60 X X 3-wire, LHL, LF Proving X 7 X 10 20 120 50/ 1-4 sec FFRT, IR 60 type flame detector. RM7840M1017 RM7840L1018 R7852A1001 or (3.0 sec) RM7840L1075 RM7840M1017 RM7840L1018 R7852A1001 or (3.0 sec) RM7840L1075 RM7840G1014 RM7840L1018 R7852A1001 or or (3.0 sec) RM7840G1022 RM7840L1075 10 10 18 ST7800A1047 (40 seconds) 37 On-Off, X X LF Proving X X 10 X 26CF6 5021 R7120D3007 10 10 18 ST7800A1070 (2.5 minutes) 98 On-Off, X X LF Proving X X 10 X 26CF6 5022 26CF6 5022A R7120D1002 NONE RM7840L1018 18 R7852B1009 or RM7840L1075 (3.0 sec) ST7800A1054 60 4-wire LHL, HF & LF Proving X 26CF6 5023 26CF6 5023A R7120D2000 14 RM7840L1018 18 RM7840G1014 or R7852A1001 or RM7840L1075 (3.0 sec) RM7840G1022 ST7800A1054 60 4-wire LHL, LF Proving X RM7840L1018 18 RM7840G1014 or R7852A1001 or RM7840L1075 (3.0 sec) RM7840G1022 ST7800A1054 60 4-wire LHL, LF Proving X 26CF6 RC-3A See footnotes on page 44 RM7840M1017 RM7840L1018 R7852A1001 or (3.0 sec) RM7840L1075 RM7840M1017 RM7840L1018 R7852A1001 or (3.0 sec) RM7840L1075 14 X X X 120 50/ 1-4 sec FFRT, IR 60 type flame detector. 25 120 50/ 1-4 sec FFRT, IR 60 type flame detector. 10, 15 20 120 50/ With 60 AUTOCHECK feature, same as Honeywell R7852B AMPLICHECK™. X 7 X X 7 X 10, 30 15 120 50/ 4 sec FFRT, IR 60 type flame detector. X X 7 X 10, 30 15 120 50/ Ray Burner 60 special, 2 sec FFRT. 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE R7120D3007 43 26CF6 5020 1 Refer to Modernization Wiring Information for conversion wiring information. Low Voltage controller will need to be upgraded to line voltage controller. 3 Replacement suggestion does not support dual IR detector feature, be sure to confirm application requirements. 4 Replacement control has 15 second postpurge. 5 Replacement control has 15 second postpurge, RM7840G1022 or RM7840L1075 have programmable postpurge option. 6 Replacement suggestion is 120 Vac, 50/60 Hz. 7 Requires Q7800A or Q7800B Wiring Subbase. 8 RM7840G,M meets current UL requirements. 9 RM7840L meets current insurance requirements. 10 Start interlocks become running interlocks using the replacment controls. (Required to start the equiment, and maintained throughout the call for heat). 11 Running Interlocks become lockout interlocks. (Opening interlock results in safety shutdown and control reset). 12 Replacement control has 10 second PFEP, 4 seconds available with JR1 clipped 13 Replacement has 10, 15 second MFEP. 14 Replacement has 10, 15, 30 second MFEP or intermittent pilot. 15 Replacement has 10 second MFEP or intermittent pilot. 16 5 second ignition early spark termination when ignition wired to terminal 10. 17 Display Module is available by ordering model shown in the table, or ordering seperately. 2 Suggestion Model Display Model 44 RM7840M1017 RM7800M1011 RM7840G1014 RM7800G1018 RM7840G1022 Order S7800A1142 seperately RM7840L1018 RM7800L1012 RM7840L1075 RM7800L1087 R7120D Order S7800A1001 seperately 18 Select appropriate flame detector and amplifier from table. FFRT Flame Detection Type 0.8 sec 3.0 sec Comments R.ectification R7847A1025 R7847A1033 Use existing Flame Rod Ultraviolet R7849A1015 R7849A1023 Order Honeywell flame detector C7027 or C7035 Infrared Self Check UV R7852A1001 Order Honeywell flame detector C7915 C7861A1034 R7861A1026 Order Honeywell flame detector C7061 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 11 FIREYE FOOTNOTES: Table 12. FIREYE® D SERIES PROGRAMMER TO HONEYWELL CROSS REFERENCE. Frequency Voltage Postpurge Early Spark Term Hi-fire RM7840L1018 R7847A1033 ST7800A1054 60 or RM7840L1075 4-wire LHL, HF & LF Proving X X X X 10 X 10, 15 X 15 120 50/ 4 sec FFRT, rectification 60 type flame detector, solid state circuitry. D10-5022 R7120D1002 ST7800A1054 60 RM7840L1018 18 R7852B1009 or RM7840L1075 4-wire LHL, HF & LF Proving X X X X 10 X 10, 15 X 15 120 50/ 4 sec FFRT, IR type 60 flame detector, auto check amplifier, solid state circuitry. D10-5065 R7120D1002 ST7800A1054 60 RM7840L1018 18 R7849A1023 or RM7840L1075 4-wire LHL, HF & LF Proving X X X X 10 X 10, 15 X 15 120 50/ 4 sec FFRT, UV type 60 flame detector, solid state circuitry. X X X 10 X 10, 15 X 15 120 50/ 4 sec FFRT, rectification 60 type flame detector, solid state circuitry. Start D10-5016 R7120D1002 Amplifier Purge Timer Timing Running Lo-fire INTR Pilot Interlocks Lockout Prepurge Preignition 7800 Series Functional Replacement to Meet Current Plug 7800 Series Device to Functional Insurance In be Needs Replacement Replacement Replaced 17 1 7 9 16 17 1 7 8 16 17 INTM Pilot Functional Replacement Type MFEP PFEP Comments 45 14 14 RM7840L1018 R7847A1033 ST7800A1054 60 RM7840G1014 or or RM7840L1075 RM7840G1022 4-wire LHL, LF Proving D20-5023 14 14 RM7840L1018 18 ST7800A1054 60 RM7840G1014 or R7852A1001 or RM7840L1075 RM7840G1022 4-wire LHL, LF Proving X X X X 10, 15 X 15 120 50/ 4 sec FFRT, IR type 60 flame detector, solid state circuitry. D20-5066 14 14 RM7840L1018 18 ST7800A1054 60 RM7840G1014 or R7849A1023 or RM7840L1075 RM7840G1022 4-wire LHL, LF Proving X X X X 10, 15 X 15 120 50/ 4 sec FFRT, UV type 60 flame detector, solid state circuitry. R7120D2000 R7120D2000 R7120D2000 D30-5010 R7120D3007 RM7840M1017 13 R7847A1033 ST7800A1039 30 On-Off, LF Proving X X X X X 10 X 15 120 50/ 4 sec FFRT, rectification 60 type flame detector, solid state circuitry. D30-5011 R7120D3007 RM7840M1017 13 R7847A1033 ST7800A1062 90 On-Off, LF Proving X X X X X 10 X 15 120 50/ 4 sec FFRT, rectification 60 type flame detector, solid state circuitry. See footnotes on page 47 RM7840L1018 or RM7840L1075 RM7840L1018 or RM7840L1075 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE D20-5015 Interlocks X X X 10 X 15 120 50/ 4 sec FFRT, IR type 60 flame detector, solid state circuitry. D30-5021 R7120D3007 RM7840M1017 13 18 ST7800A1062 90 On-Off, LF Proving X X X X X 10 X 15 120 50/ 4 sec FFRT, IR type 60 flame detector, solid state circuitry. D30-5062 R7120D3007 RM7840M1017 13 18 ST7800A1039 30 On-Off, LF Proving X X X X X 10 X 15 120 50/ 4 sec FFRT, IR type 60 flame detector, solid state circuitry. D30-5063 RM7840M1017 RM7840L1018 or RM7840L1075 X X 10 X 15 120 50/ 4 sec FFRT, IR type 60 flame detector, solid state circuitry. 46 See footnotes on page 47 RM7840L1018 R7852A1001 or RM7840L1075 RM7840L1018 R7852A1001 or RM7840L1075 RM7840L1018 R7852A1001 or RM7840L1075 PFEP 7 MFEP Frequency X Voltage X Type Postpurge On-Off, LF Proving Purge Timer Timing Hi-fire ST7800A1039 30 Amplifier Lo-fire 18 Lockout 13 Preignition RM7840M1017 Start D30-5020 R7120D3007 Running INTR Pilot Prepurge INTM Pilot 7800 Series Functional Replacement to Meet Current Plug 7800 Series Device to Functional Insurance In be Needs Replacement Replacement Replaced 1 7 8 16 17 17 1 7 9 16 17 Early Spark Term Functional Replacement Comments PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 12. FIREYE® D SERIES PROGRAMMER TO HONEYWELL CROSS REFERENCE. (Continued) Table 12 FIREYE FOOTNOTES: 1 Refer to Modernization Wiring Information for conversion wiring information. Low Voltage controller will need to be upgraded to line voltage controller. 3 Replacement suggestion does not support dual IR detector feature, be sure to confirm application requirements. 4 Replacement control has 15 second postpurge. 5 Replacement control has 15 second postpurge, RM7840G1022 or RM7840L1075 have programmable postpurge option. 6 Replacement suggestion is 120 Vac, 50/60 Hz. 7 Requires Q7800A or Q7800B Wiring Subbase. 8 RM7840G,M meets current UL requirements. 9 RM7840L meets current insurance requirements. 10 Start interlocks become running interlocks using the replacment controls. (Required to start the equiment, and maintained throughout the call for heat). 11 Running Interlocks become lockout interlocks. (Opening interlock results in safety shutdown and control reset). 12 Replacement control has 10 second PFEP, 4 seconds available with JR1 clipped 13 Replacement has 10, 15 second MFEP. 14 Replacement has 10, 15, 30 second MFEP or intermittent pilot. 15 Replacement has 10 second MFEP or intermittent pilot. 16 5 second ignition early spark termination when ignition wired to terminal 10. 17 Display Module is available by ordering model shown in the table, or ordering seperately. 2 Suggestion Model Display Model 47 RM7800M1011 RM7840G1014 RM7800G1018 RM7840G1022 Order S7800A1142 seperately RM7840L1018 RM7800L1012 RM7840L1075 RM7800L1087 R7120D Order S7800A1001 seperately 18 Select appropriate flame detector and amplifier from table FFRT Flame Detection Type 0.8 sec 3.0 sec Comments Rectification R7847A1025 R7847A1033 Use existing Flame Rod Ultraviolet R7849A1015 R7849A1023 Order Honeywell flame detector C7027 or C7035 Infrared Self Check UV R7852A1001 Order Honeywell flame detector C7915 C7861A1034 R7861A1026 Order Honeywell flame detector C7061 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE RM7840M1017 X X d R7120D1002 RM7840L1018 RM7840L1018 or or RM7840L1075 RM7840L1075 ST7800A1039 30 4-wire LHL, HF & LF Proving X X X k R7120D1002 RM7840L1018 RM7840L1018 or or RM7840L1075 RM7840L1075 k k 4-wire LHL, HF & LF Proving X X X X k d h i R7120D1002 RM7840L1018 RM7840L1018 or or RM7840L1075 RM7840L1075 ST7800A1039 30 4-wire LHL, HF & LF Proving I X X X 10 d R7120D1002 RM7840L1018 RM7840L1018 or or RM7840L1075 RM7840L1075 ST7800A1039 30 4-wire LHL, HF & LF Proving X X X X d j R7120D1002 RM7840L1018 RM7840L1018 or or RM7840L1075 RM7840L1075 ST7800A1039 30 4-wire LHL, HF & LF Proving X X X X d R7120D1002 RM7840L1018 RM7840L1018 or or RM7840L1075 RM7840L1075 ST7800A1039 30 4-wire LHL, HF & LF Proving X X X d 9 9 RM7840L1018 RM7840G1014 or or RM7840L1075 RM7840G1022 ST7800A1039 30 4-wire LHL, LF Proving X X d 9 9 8 ST7800A1039 30 4-wire LHL, LF Proving X d, h 9 9 8 ST7800A1039 30 4-wire LHL, LF Proving d 9 9 RM7840L1018 RM7840G1014 or or RM7840L1075 RM7840G1022 ST7800A1039 30 e f g R7120D3007 RM7840M1017 ST7800A1039 30 EP161 EPD161 EP163 EP165 EPD165 48 EP166 EPD166 EPD167 EP170 EPD170 EP260 EPD260 EP261 EPD261 EP265 EPD265 EP270 EPD270 EP380 EPD380 R7120D2000 R7120D2000 R7120D2000 R7120D2000 RM7840G1014 RM7840L1018 or or RM7840G1022 RM7840L1075 RM7840G1014 RM7840L1018 or or RM7840G1022 RM7840L1075 See footnotes on page 49 8 RM7840L1018 or RM7840L1075 Comments 10 X 10, 15 15 120 50/60 4 sec FFRT 10 X 10, 30 15 120 50/60 4 sec FFRT k 15 120 50/60 4 sec FFRT, Purge and Ignition timings are programmable using the ED Display Module. X 10 15 120 50/60 2 sec FFRT 10 X 15 15 120 50/60 2 sec FFRT, locks out on power inerruption 10 X 10, 15 15 120 50/60 4 sec FFRT 5, 10 X 10 15 120 50/60 4 sec FFRT, Waits indefinitely for Low Fire Switch to close., X 10 X 10, 15 15 120 50/60 4 sec FFRT X X 10 X 10, 30 15 120 50/60 4 sec FFRT X X X 10 X 10 15 120 50/60 2 sec FFRT 4-wire LHL, LF Proving X X X 5, 10 X 10 15 120 50/60 4 sec FFRT On-Off, LF Proving h X X X 10 15 120 50/60 4 sec FFRT X X Frequency X MFEP Voltage 4-wire LHL, HF & LF Proving PFEP Postpurge Hi-fire 30 Type Lo-fire Preignition ST7800A1039 Lockout RM7840L1018 RM7840L1018 or or RM7840L1075 RM7840L1075 Running R7120D1002 EP160 EPD160 Start d Early Spark Term Interlocks INTR Pilot Prepurge 7800 Series Functional Current Plug 7800 Series Replacement Device to Functional to Meet In be Timing Replacement Replacement Insurance Amplifier b Replaced Purge Timerb 12 1 3 5 11 12 13 b 1 3 4 11 12 INTM Pilot Functional Replacement f X 10 X X f X PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Table 13. FIREYE® E SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. Type PFEP MFEP 5, 10 10 e f g R7120D3007 RM7840M1017 8 ST7800A1039 (30 seconds) 15 On-Off, LF Proving h X X X e f g R7120D3007 RM7840M1017 8 ST7800A1005 (2 seconds) 0 On-Off, LF Proving h X X X g R7120D3007 RM7840M1017 8 l l On-Off, LF Proving X X m f g h R7120D3007 RM7840M1017 13 ST7800A1062 90 On-Off, LF Proving X X 5, 10 EP381 EPD381 EP382 EPD382 EP383 EP390 EPD390 RM7840L1018 or RM7840L1075 RM7840L1018 or RM7840L1075 RM7840L1018 or RM7840L1075 RM7840L1018 or RM7840L1075 h X f X e X m f X f X f X m 10 f X f X Frequency Voltage Postpurge INTR Pilot INTM Pilot Lo-fire Hi-fire Preignition Start 7800 Series Functional Current Plug 7800 Series Replacement Device to Functional to Meet In be Timing Replacement Replacement Insurance Amplifier Replacedb Purge Timerb 12 1 3 5 11 12 13 b 1 3 4 11 12 Interlocks Lockout Prepurge Running Functional Replacement Early Spark Term Table 13. FIREYE® E SERIES TO HONEYWELL PROGRAMMER CROSS REFERENCE. (Continued) Comments 15 120 50/60 4 sec FFRT 15 120 50/60 m 120 50/60 m 15 120 50/60 4 sec FFRT See footnotes on page 49 49 Table 13 FIREYE FOOTNOTES: Honeywell Solution Suggestion 70-8313—02 All programmers have selectable 3 to P "prove open on Start" feature using a dipswitch Clip JR3 if dipswitch feature is enabled. b Purge timings can be extended using the dipswitches located on the porgrammer module. Check dipswitches and select appropriate ST7800 Purge Timer c EPD programmers include a built in LED display. See display models suggestion in table I. d Programmer adds 30 seond after pre-purge to allow damper motor to drive to low fire position. Honeywell Model adds 30 seconds for jumpered or closed interlock e EP380, EM381, EP382 and EP390 have selectable intermittent or interrupted (15 sec PTFI) operation of terminal 6 using dipswitch. Honeywell suggestion dependant on terminals wired f These programmers can use terminal X for spark termination. Requires terminals 10 and 5 to be jumpered. Available when Ignition is wired to terminal 10. g EP380, EM381, EP382 and EP390 have selectable recycle or non recycle operation using a dipswitch. Honeywell suggestion DOES NOT offer non recycle, if required select an "L model. h During MTFI, terminal 6 is energized for 5 seconds before 10 second MTFI for EP165 and EP265; 15 second MTFI for EP166 only. Honeywell suggestion does not offer the energize the spark early. i EP165 locks out on power inerruption Honeywell suggestion DOES NOT offer this feature. PROGRAMMER CONTROL CROSS REFERENCE Fireye Notes a Honeywell Solution Suggestion The EPD167 waits indefinitely for the Low Fire Start Switch (M-D) to close. Honeywell suggestion DOES NOT offer this feature. k The EP163 Purge and Ignition timings are programmable using the ED Display Module. Honeywell suggestion DOES NOT offer feature to program Purge and Ignition l The EP383 Purge, Ignition, FFRT and Post Purge time are programmable using the Honeywell suggestion DOES NOT offer feature to program Purge, Ignition, FFRT ED Display Module. and Post Purge Time. m Intermittent or Interrupted Pilot opertion may be selected using a dipswitch (or using the ED Display Module with EP383) Honeywell suggestion offers feature based on the terminal the pilot valve is wired. Other Footnotes 1 Replacement control has 15 second postpurge. control has 15 second postpurge, RM7840G1022 or RM7840L1075 have programmable postpurge option. 3 Requires Q7800A or Q7800B Wiring Subbase. 4 RM7840G,M meets current UL requirements. 5 RM7840L meets current insurance requirements. 6 Start interlocks become running interlocks using the replacment controls. (Required to start the equiment, and maintained throughout the call for heat). 7 Replacement control has 10 second PFEP, 4 seconds available with JR1 clipped 8 Replacement has 10, 15 second MFEP. 9 Replacement has 10, 15, 30 second MFEP or intermittent pilot. 10Replacement has 10 second MFEP or intermittent pilot. 115 second ignition early spark termination when ignition wired to terminal 10. 12Display Module is available by ordering model shown in the table, or ordering seperately. 2 Replacement 50 Display Model Suggestions Suggestion Model Display Model RM7840M1017 RM7800M1011 RM7840G1014 RM7800G1018 RM7840G1022 Order S7800A1142 seperately RM7840L1018 RM7800L1012 RM7840L1075 RM7800L1087 13Select appropriate flame detector and amplifier from table Amplifier Selection Type FFRT (seconds) Replacement Comments 72D1R1 IR 2-4 R7852A1001 Select C7915 flame detector 72D1R1T IR 1 none available 72D1R3 IR 2-4 (For solid fuel) 72D1R3T IR 1 (For solid fuel) 72DRT1 Flame Rod 2-4 R7847A1033 72DRT1T Flame Rod 1 R7847A1025 72DUV1 UV 2-4 R7849A1023 Select C7027A1080 flame detector 72DUVS4 UV Self Check 2-4 R7861A1026 Select C7061 flame detector 72DUVS1T UV Self Check 1 R7861A1034 Select C7061 flame detector PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 Fireye Notes j 51 PROGRAMMER CONTROL CROSS REFERENCE 70-8313—02 PROGRAMMER CONTROL CROSS REFERENCE Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U.S. Registered Trademark © 2011 Honeywell International Inc. 70-8313—02 M.S. Rev. 09-11 Printed in United States