4. 4.2.2-GB Motor protection - and switching unit Switching unit for 3~ motors with two speeds (Y/▲ change-over) Type: S-DT2S(K)T Examples of applications for switching 3~ fans in two steps Manual 2-step speed change-over (Y/▲) of one or more 3~ fans e. g. in: heat exchangers (as warm-air heaters), hoods, ventilation of rooms. - Via potential-free contact (e. g. of thermostat type SRE1G) the device can be switched ON / OFF in the preselected step. Thus simple temperature control is accomplished. - Type S-DT2SKT includes potential-free and 230 V power on contacts for the connection of damper control motors or gas valves (hoods application) (see connection example on back). Equipment Enclosed version IP 54 · Restart the drive unit after cooling by switching off and back on Type: S-DT2ST Part-No. 301024 Type: S-DT2SKT Part-No. 301034 (add. contacts) · Remote control (ON/OFF) via potential-free contact (terminals ”RT”-”RT”). · Motor protection using thermocontact connection (terminals "TK"-"TK"). Automatic switch-off by motor over-temperature. Restart after cooling the drive unit by switch-off and after that switch on the mains voltage or by step-switch ("reset"). · A power on lamp and a control fuse are integrated. · Automatic switch on after power failure. · Type S-DT2SKT (additional power on contacts) - Potential-free changer (terminals 11, 12, 14) - 230 V switched and constant voltage Technical data - Line voltage 3~ 400 V, 50/60 Hz - Max. contact load (type S-DT2SKT) × Potential-free changer (terminals 11, 12, 14) 250 V AC / 2 A × 230 V switched and constant voltage max. 1 A - Rated current 10 A - Max. power of motor 4 kW - Protection class IP54 - Max. line fuse 10 A - Weight approx. 1.1 kg - Internal equipment fuse T 2 A (5x 20 mm) - Max. ambient temperature + 40° C Dimension sheet Ziehl-Abegg AG Heinz-Ziehl-Straße D-74653 Künzelsau TIL02_47 (21.10.02) - Plastic housing (ABS) × top: light grey RAL 7035 × bottom: dark-grey marbled UN 7005 Connection diagram Tel.: +49 (0) 7940 16-0 Fax: +49 (0) 7940 16-200 info@ziehl-abegg.de http://www.ziehl-abegg.de Connection example for damper control motors Connection of damper control motors (different models) is possible via the potential-free contacts or via the 230 V contacts of the power on relay. This relay rises, if the device is activated and the fan is running. By switching off via remote control (terminals ”RT”-RT”) or in case of motor fault (interruption terminals ”TK”-”TK”) the relay falls off. For damper control motors with ”single-wire-control” connection with constant voltage (also in switch position ”0”) for ”damper CLOSE”. For motors with ”single-wirecontrol” - damper ”OPEN”: if fan is running, 230 V at terminal L - damper ”CLOSE”: constant voltage at terminal L, if fan is not running (also in switch position ”0”) AC 230 For motors with ”spring return” - damper ”OPEN”: if fan is running, 230 V at terminal L - damper ”CLOSE”: via spring return (if no voltage at L ) For motors with ”2-wire-control” - damper ”OPEN”: if fan is running, voltage at terminal 14 - damper ”CLOSE”: voltage at terminal 12, fan is not running (also in switch position ”0”) AC 230 N L L N L L N 11 12 AC 24 V...250 V M TIL02_47 (21.10.02) M M 14