9. 9.2.1-GB Transformer based controller for 3~ motors 5-step controller inclusive additional functions for voltage controllable fans R-DT1... 7KT(G) Type: Examples of applications for controlling 3~ fans in 5-steps Manual 5-step speed change-over of one or more 3~ fans e. g. in: heat exchangers (as warm-air heaters), hoods, ventilation of rooms. Via potential-free contact, e. g. of thermostat (type SRE1G), the device can be switched ON / OFF in the preselected step. Thus simple temperature control is accomplished. The device includes potential-free and 230 V power on contacts for the connection of gas valves (hoods application) or damper control motors (see connection example on back). Equipment Enclosed version IP21 / IP54 Transformer based controllers for voltage controllable 3~ fans • 5-step switch for manual speed control IP21 IP54 • Remote control (ON/OFF) via potential-free contact IP54 (terminals „RT”-„RT”). • Motor protection using thermal contact connection (terminals „TK"-„TK"). Automatic switch-off by motor overt temperature Restart after cooling the drive unit by switch-off and after that switch on the mains voltage or by step-switch („reset"). • Switch-off with interlock via potential-free contact (terminals FS - FS) e. g. for antifreezing thermostat (restart see motor failure) • A power on lamp is integrated • Automatic switch on after power failure • Additional power on contact R-DT-1KTG R-DT-2KTG - Potential-free changer (terminals 11, 12, 14) - 230 V switched and constant voltage (terminals N↓, L↓, L R-DT-4KT R-DT-7KT R-DT-3KTG R-DT-5.2KTG ) Technical data - Line voltage 3~ 400 V, 50/60 Hz Output voltage 95 V - 145 V - 190 V - 240 V - 400 V Max. load of the power on contacts: Potential-free changer (terminals 11, 12, 14) 250 V AC / 2 A 230 V switched and constant voltage max. 1 A (terminals N↓, L↓, L ) Type R-DT1KTG R-DT2KTG R-DT3KTG R-DT4KT R-DT5.2KTG R-DT7KT Part.-Nr. 302581 302582 302583 302584 302585 302586 Rated current 1A 2A 3A 4A 5.2 A 7A Dimension sheet max. ambient temperature +40° C - - Housing top ABS plastic, colour light grey, bottom aluminium die casting Max. line Fuse 4A 4A 6A 6A 13 A 16 A Max. heat dissipation approx. 40 W approx. 55 W approx. 60 W approx. 75 W approx. 85 W approx. 115 W Protection IP54 IP54 IP54 IP21 IP54 IP21 Weight 4.7 kg 7.4 kg 11.0 kg 11.0 kg 15.6 kg 15.6 kg Connection diagram R-DT...KT(G) R-DT1/2KTG (R-DT3/4/5.2/7KT(G)) 12 11 14 N L L RT RT FS 1* 250VAC max. 2A FS 1* TK TK N L1 L2 L3 U V W 1* 230VAC max. 1A 230V AC Kontaktbelastung contact rating pouvoir de coupure kontaktbelastning PE N L1 L2 L3 Netz / line / secteur Nätanslutning 3~400V 50/60Hz 0 1 J U V W PE M 3~ TK TK Y bzw. or D Vo r Ö ff n e n d e s D e c k e ls G e rä t s p a n n u n g s fre i s c h a lte n ! S w itc h o f f t h e m a in s u p p ly b e f o re re m o vin g t h e c o ve r! SR171K05 24.11.2004 AUS/EIN OFF/ON ARRET/MARCHE AV/PÅ AUS/EIN (nur über Reset) OFF/ON (only by reset) ARRET/MARCHE (lors d´un reset) AV/PÅ (bara över reset) 1* Wenn Funktion nicht benötigt wird, Klemmen brücken If function is not needed, terminals must be bridged Ziehl-Abegg AG Heinz-Ziehl-Straße D-74653 Künzelsau R-TIL03_24-GB 02/04 Tel.: +49 (0) 7940 16-0 Fax: +49 (0) 7940 16-504 info@ziehl-abegg.de http://www.ziehl-abegg.de 3~ Motor mit eingebauten Thermokontakten with internal thermocontacts à thermocontacts intégrés med integrerade termokontakter 1* Si la fonction n’est pas utile, les bornes doivent être reliées Om funktionen inte används, måste plintarna byglas Connection example for damper control motors Connection of damper control motors (different models) is possible via the potential-free contacts or via the 230 V contacts of the power on relay. This relay rises, if the device is activated and the fan is running. By switching off via remote control (terminals „RT”-„RT“) or in case of motor fault the relay falls off. For damper control motors with „single-wire-control” connection with constant voltage (also in switch position „0”) for „damper CLOSE”. For motors with „single-wirecontrol” - damper „OPEN”: if fan is running, 230 V at terminal L - damper „CLOSE”: constant voltage at terminal L, if fan is not running (also in switch position ”0”) AC 230 V For motors with „spring return” - damper „OPEN”: if fan is running, 230 V at terminal L - damper „CLOSE”: via spring return (if no voltage at L ) For motors with „2-wire-control” - damper „OPEN”: if fan is running, voltage at terminal 14 - damper „CLOSE”: voltage at terminal 12, fan is not running (also in switch position ”0”) AC 230 V N L L N L L N 11 12 AC 24 V...250 V M R-TIL03_24-GB 02/04 M M 14