05-08-2015 - University of Engineering and Technology

advertisement
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Bakhtawar Amin Trust Hospital
Multan
Reference # CED/TFL 21440 (Engr. Rehan)
Reference of the request letter# Eng. 100
Tension Test Report
(Page -1/2)
Breaking
Load
Actual
(inch)
Nominal
Actual
(kg)
Nominal
Actual
Nominal
Actual
(inch)
1
0.354
3/8
0.364
0.11
0.104
3000
4500
60200
63590
90200
95400
1.20
15.0
2
0.357
3/8
0.365
0.11
0.105
3400
5000
68200
71470
100200
105100
1.20
15.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Yield Stress
(psi)
Ultimate Stress
(psi)
Note: only two samples for tensile and one sample for bend test
Bend Test
3/8" Dia Bar Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
Remarks
Yield load
Nominal
(inch)
(kg)
Area
(in2)
% Elongation
Diameter/
size
Sr. No.
Weight
Elongation
06-08-2015
8 inches
Deformed Steel Bar Tensile and Bend Test as per ASTM-A615
(lbs/ft)
Date of Test
Gauge length
Description
Dated: 05-08-2015
Dated: 05-08-2015
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Sdub Divisional Officer
Provincial Buildings Sub Division
Sahiwal
Reference # CED/TFL 21441 (Engr. Rehan)
Reference of the request letter# 83/S
Tension Test Report
(Page -1/1)
Breaking
Load
Actual
(inch)
Nominal
Actual
(kg)
Nominal
Actual
Nominal
Actual
(inch)
1
0.349
3/8
0.361
0.11
0.103
3100
4850
62200
66660
97200
104300
1.00
12.5
2
0.352
3/8
0.363
0.11
0.103
3200
5000
64200
68150
100200
106500
1.10
13.8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Yield Stress
(psi)
Ultimate Stress
(psi)
Note: only two samples for tensile and one sample for bend test
Bend Test
3/8" Dia Bar Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
Remarks
Yield load
Nominal
(inch)
(kg)
Area
(in2)
% Elongation
Diameter/
size
Sr. No.
Weight
Elongation
06-08-2015
8 inches
Deformed Steel Bar Tensile and Bend Test as per ASTM-A615
(lbs/ft)
Date of Test
Gauge length
Description
Dated: 05-08-2015
Dated: 03-08-2015
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Banu Mukhtar Contracting (Pvt) Ltd.
New Garden Town, Lahore
(Roshan Packages (Pvt) Limited, S.I.E.)
Reference # CED/TFL 21442 (Engr. Affifa Akram)
Dated: 05-08-2015
Reference of the request letter# BML/GM/ROSHAN PACKAGES/457Dated: 04-08-2015
Tension Test Report
(Page -1/2)
Breaking
Load
Actual
(inch)
Nominal
Actual
(kg)
Nominal
Actual
Nominal
Actual
(inch)
1
0.384
3
0.379
0.11
0.113
3600
4700
72200
70330
94200
91900
1.00
12.5
2
0.372
3
0.373
0.11
0.109
3300
4500
66200
66490
90200
90700
1.20
15.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Yield Stress
(psi)
Ultimate Stress
(psi)
Note: only two samples for tensile test
Bend Test
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
Remarks
Yield load
Nominal
(#)
(kg)
Area
(in2)
% Elongation
Diameter/
size
Sr. No.
Weight
Elongation
06-08-2015
8 inches
Deformed Steel Bar Tensile Test as per ASTM-A615
(lbs/ft)
Date of Test
Gauge length
Description
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Banu Mukhtar Contracting (Pvt) Ltd.
New Garden Town, Lahore
(Roshan Packages (Pvt) Limited, S.I.E.)
Reference # CED/TFL 21442 (Engr. Affifa Akram)
Dated: 05-08-2015
Reference of the request letter# BML/GM/ROSHAN PACKAGES/461Dated: 04-08-2015
Bend Test Report (Page -2/2)
Date of Test
Gauge length
Description
06-08-2015
8 inches
Deformed Steel Bar Bend Test as per ASTM-A615
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
Note: one sample for bend test
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Sukh Chayn Gardens (Pvt) Ltd.
25-Km Multan Road, Lahore
Reference # CED/TFL 21443 (Engr. Rehan)
Reference of the request letter# SCG/ComB/ST/04
Tension Test Report
(Page -1/1)
Breaking
Load
Actual
(inch)
Nominal
Actual
(kg)
Nominal
Actual
Nominal
Actual
(inch)
1
0.374
3/8
0.374
0.11
0.110
4700
5600
94200
94120
112300
112200
0.40
5.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Yield Stress
(psi)
Ultimate Stress
(psi)
Note: only two samples for tensile and one sample for bend test
Bend Test
3/8" Dia Bar Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
Remarks
Yield load
Nominal
(inch)
(kg)
Area
(in2)
% Elongation
Diameter/
size
Sr. No.
Weight
Elongation
06-08-2015
8 inches
Deformed Steel Bar Tensile and Bend Test as per ASTM-A615
(lbs/ft)
Date of Test
Gauge length
Description
Dated: 05-08-2015
Dated: 04-08-2015
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S S.J Steel Re-Rolling Mills
Lahore
Reference # CED/TFL 21444 (Engr. Rehan)
Reference of the request letter# Nil
Tension Test Report
(Page -1/1)
Breaking
Load
Actual
(inch)
Nominal
Actual
(kg)
Nominal
Actual
Nominal
Actual
(inch)
1
0.387
3
0.381
0.11
0.114
3600
5250
72200
69760
105200
101800
1.00
12.5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Yield Stress
(psi)
Ultimate Stress
(psi)
Note: only one sample for tensile and one sample for bend test
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
Remarks
Yield load
Nominal
(#)
(kg)
Area
(in2)
% Elongation
Diameter/
size
Sr. No.
Weight
Elongation
05-08-2015
8 inches
Deformed Steel Bar Tensile and Bend Test as per ASTM-A615
(lbs/ft)
Date of Test
Gauge length
Description
Dated: 05-08-2015
Dated: 04-08-2015
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To
M/S Defence Housing Scheme
Lahore Cantt
(Construction of SDS at Sector-V DHA Ph-VIII (M/s Inland Const. Co.)
Reference # CED/TFL 21445 (Dr. Asif)
Reference of the request letter # 408/241/E/Lab/362
Dated: 05-08-2015
Dated: 01-07-2015
Pressure Test (Page – 1/1)
Date of Test
05-08-2015
Description
GRP Pipe Pressure Test
Sr.
No.
Diameter
(inch)
Pressure Applied
(Bar)
Results
1
28
12
OK
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Only one Sample for Test
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Relacom Pakistan Pvt Ltd
Shahrah Faisal, Karachi
((Site ID # LMIR02)
Reference # CED/TFL 21446 (Engr. Rehan)
Reference of the request letter# 01
Tension Test Report
(Page -1/2)
Breaking
Load
Actual
(inch)
Nominal
Actual
(kg)
Nominal
Actual
Nominal
Actual
(inch)
1
0.365
10
0.369
0.11
0.107
3000
4600
60200
61680
92200
94600
1.20
15.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Yield Stress
(psi)
Ultimate Stress
(psi)
Note: only one sample for tensile and one sample for bend test
Bend Test
10mm Dia Bar Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
Remarks
Yield load
Nominal
(mm)
(kg)
Area
(in2)
% Elongation
Diameter/
size
Sr. No.
Weight
Elongation
06-08-2015
8 inches
Deformed Steel Bar Tensile and Bend Test as per ASTM-A615
(lbs/ft)
Date of Test
Gauge length
Description
Dated: 05-08-2015
Dated: 05-08-2015
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S Relacom Pakistan Pvt Ltd
Shahrah Faisal, Karachi
((Site ID # LBMR12)
Reference # CED/TFL 21446 (Engr. Rehan)
Reference of the request letter# 01
Tension Test Report
(Page -1/2)
Breaking
Load
Actual
(inch)
Nominal
Actual
(kg)
Nominal
Actual
Nominal
Actual
(inch)
1
0.358
10
0.366
0.11
0.105
3000
4600
60200
62810
92200
96300
1.30
16.3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Yield Stress
(psi)
Ultimate Stress
(psi)
Note: only one sample for tensile and one sample for bend test
Bend Test
10mm Dia Bar Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
Remarks
Yield load
Nominal
(mm)
(kg)
Area
(in2)
% Elongation
Diameter/
size
Sr. No.
Weight
Elongation
06-08-2015
8 inches
Deformed Steel Bar Tensile and Bend Test as per ASTM-A615
(lbs/ft)
Date of Test
Gauge length
Description
Dated: 05-08-2015
Dated: 05-08-2015
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer, JICA
AKERRRP, NESPAK Mansehra
Reference # CED/TFL 21447 (Dr. Asif)
Reference of the request letter # 3418/IUK/02/306
Tension Test Report
(Page – 1/4)
Nominal
Weight
Measured
weight
Yield
strength
clause (6.3)
Breaking
strength
clause
(6.2)
(mm)
(kg/km)
(kg/km)
(kg)
(kg)
E, GPa
Remarks / Coil No.
1
12.70
(1/2”)
775.0
789.0
17800
19900
199
>3.50
xx
2
12.70
(1/2”)
775.0
789.0
17900
20300
198
>3.50
xx
3
12.70
(1/2”)
775.0
787.0
17500
19700
199
>3.50
xx
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Sr. No.
Nominal
Diameter
% Elongation
07-08-2015
640 mm
Steel Strand Tensile Test as per ASTM A-416-94a
Young’s
Modulus of
Elasticity
Date of Test
Gauge length
Description
Dated: 05-08-2015
Dated: 03-08-2015
Only three samples for Test
Note:
1. Modulus of Elasticity is based on nominal steel area of the steel strand vide clause 13.3 of ASTM – A416a
2. Load versus percentage strain graphs are attached
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer, JICA
AKERRRP, NESPAK Mansehra
Reference # CED/TFL 21447 (Dr. Asif)
Reference of the request letter # 3418/IUK/02/306
Dated: 05-08-2015
Dated: 03-08-2015
Graph (Page – 2/4)
Stress Strain Relation -- Specimen No. W 1
300000
Stress (psi)
250000
200000
150000
100000
50000
0
0
0.2
0.4
0.6
0.8
Strain (% )
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
1
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer, JICA
AKERRRP, NESPAK Mansehra
Reference # CED/TFL 21447 (Dr. Asif)
Reference of the request letter # 3418/IUK/02/306
Dated: 05-08-2015
Dated: 03-08-2015
Graph (Page – 3/4)
Stress Strain Relation -- Specimen No. W 2
300000
Stress (psi)
250000
200000
150000
100000
50000
0
0
0.2
0.4
0.6
0.8
Strain (% )
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
1
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
Resident Engineer, JICA
AKERRRP, NESPAK Mansehra
Reference # CED/TFL 21447 (Dr. Asif)
Reference of the request letter # 3418/IUK/02/306
Dated: 05-08-2015
Dated: 03-08-2015
Graph (Page – 4/4)
Stress Strain Relation -- Specimen No. W 3
300000
Stress (psi)
250000
200000
150000
100000
50000
0
0
0.2
0.4
0.6
0.8
Strain (% )
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
1
STRUCTURAL ENGINEERING DIVISION
Test Floor Laboratory
Department of Civil Engineering
University of Engineering and Technology Lahore, 54890
Pakistan. Ph: 92-42-99029202
To,
M/S S.J Steel Re-Rolling Mills
Lahore
(AFCO Steel)
Reference # CED/TFL 21448 (Engr. Rehan)
Reference of the request letter# Nil
Tension Test Report
(Page -1/1)
Breaking
Load
Actual
(inch)
Nominal
Actual
(kg)
Nominal
Actual
Nominal
Actual
(inch)
1
0.378
3
0.376
0.11
0.111
4600
5900
92200
91340
118300
117200
1.00
12.5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Yield Stress
(psi)
Ultimate Stress
(psi)
Note: only one sample for tensile and one sample for bend test
Bend Test
#3 Bar Bend Test Through 180º is Satisfactory
I/C Testing Laboratoires
UET Lahore, Pakistan.
Note:
1-
You can See your reports On Internet in the following web site
http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports
2. The above results pertain to sample /samples supplied to this laboratory.
3Sealed sample / Unsealed sample / Marked sample/Signed Samples
Remarks
Yield load
Nominal
(#)
(kg)
Area
(in2)
% Elongation
Diameter/
size
Sr. No.
Weight
Elongation
06-08-2015
8 inches
Deformed Steel Bar Tensile and Bend Test as per ASTM-A615
(lbs/ft)
Date of Test
Gauge length
Description
Dated: 05-08-2015