PLANNING, INSTALLATION OPERATION AND MAINTENANCE COMPRESSOR DESICCATOR UNIT 3C BT ITEM CODE 074375 MANUFACTURERS TYPE NO. 12450 OPERATING HANDBOOK ISSUE 6 DRALLIM TELECOM (A DIVISION OF DRALLIM INDUSTRIES LTD.) MILLWOOD HOUSE, DRURY LANE, PONSWOOD INDUSTRIAL ESTATE, ST. LEONARDS ON SEA, EAST SUSSEX. TN38 9BA TELEPHONE: 44 (0) 01424 205140 FAX: 44 (0) 01424 202140 1 2 LIST OF CONTENTS SECTION 1 INTRODUCTION SECTION 2 PRODUCTION SPECIFICATION 2.1 2.2 2.3 2.4 2.5 2.6 SECTION 3 Environmental Considerations Operational Features Dry Air Output Alarm Indications. Monitoring/Control Features Test Facilities INSTALLATION DESIGN 3.1 3.2 3.4 3.5 Introduction Performance Suitability for High Flow Installations Outlet Connection SECTION 4 ACCOMMODATION REQUIREMENTS SECTION 5 EQUIPMENT SAFETY 5.1 5.2 5.3 5.4 5.5 SECTION 6 INSTALLATION INSTRUCTIONS 6.1 6.2 6.4 6.5 6.6 6.8 6.9 SECTION 7 WARNINGS Cautions Health and Safety & Factories Act Electricity At Work Regulations Manufacturers Declaration Of Conformity General Compressor Desiccator Unit 3C Installation Pneumatic Connections Electrical Connections Remote Monitoring of Alarms Commissioning the CDU 3C Completion of Installation COMMISSIONING 7.1 7.2 7.3 7.4 7.5 7.6 Visual Inspection Connection Humidity Detector Check Compressor Control Pressure Switch Check Air Receiver Relief Valve Check Remote Alarm Check 3 SECTION 8 OPERATING INSTRUCTIONS 8.1 8.2 8.3 8.4 8.5 SECTION 9 TEST FACILITIES 9.1 9.2 SECTION 10 11 12 General Electrical Description Test Facility Operation Pneumatic Description Test Switch Operation FAULT DIAGNOSIS AND CORRECTIVE MAINTENANCE 11.1 11.2 11.3 SECTION Introduction Use of the Test Facility OPERATING PRINCIPLES 10.1 10.3 10.6 10.11 10.17 SECTION General Switch on Procedures - Introduction Switch on After Commissioning or Long Periods of “Down Time” Switch on After Short Shutdown Periods Adjusting the Equipment Output Pressure Introduction Lamp Replacement Changing the Compressor Filter MAINTENANCE 12.2 Maintenance Schedule Functional Checks 12.3 12.4 12.5 12.6 12.7 12.8 12.9 12.10 12.11 12.12 12.13 12.15 12.16 12.18 12.19 12.20 Introduction Checking for Leaks Checking the Output Flowrate Checking the Compressor Maximum Pressure Checking the Purge Flowrate Checking the Air Receiver Checking the Electrical Wiring Checking the Humidity Detector System Testing the Sensing Element Testing the Circuit Board Changing the Desiccator Bed Filters Lower Filters Upper Filters Changing the Solenoid Valve Cores Servicing the Non-Return Valve Changing the Reactivation Orifice 4 SECTION 13 DIAGNOSTICS 13.1 SECTION 14 REPAIRS 14.1 14.2 14.3 14.4 14.5 14.6 14.7 14.8 14.9 14.10 14.11 SECTION 15 Introduction Introduction Fuse Replacement Compressor Replacement Fan Replacement Pressure Gauge Replacement Running Hours Meter Replacement Compressor Control Pressure Switch Replacement Compressor Control Pressure Switch Adjustment Minimum Pressure Regulating Valve Adjustment Air Receiver Safety Relief Valve Replacement Power OFF/ON Rocker Switch Replacement SPARE PARTS LIST OF FIGURES FIG 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 COMPRESSOR DESICCATOR UNIT 12450 (CDU 3C) FRONT VIEW COMPRESSOR DESICCATOR UNIT 3C - TOP VIEW COMPRESSOR PRESSURE GAUGE VENT VALVE CONTROL FEATURES ELECTRICAL DIAGRAM COMPONENT LAYOUT (CONTROL FEATURES) COMPONENT LAYOUT (DESICCATOR FEATURES) PNEUMATIC DIAGRAM USE OF FLOWMETER PORTABLE 2A TO CHECK OUTPUT FLOWRATE USE OF FLOWMETER PORTABLE 2A TO CHECK PURGE FLOWRATE DESICCATOR BED FILTER ASSEMBLY SOLENOID VALVE ASSEMBLY NON-RETURN VALVE ASSEMBLY COMPRESSOR REMOVAL COMPRESSOR CONTROL PRESSURE SWITCH LIST OF TABLES 1 2 3 4 FAULT DIAGNOSIS MAINTENANCE SCHEDULE MALFUNCTION DIAGNOSIS SPARE PARTS LIST OF DOCUMENT ISSUES 5 SECTION 1 - INTRODUCTION 1.1 The DRALLIM Compressor Desiccator Unit 12450 (CDU 3C) is an energy saving integrated unit for supplying dry air to pressurised cables. It has been designed to alleviate the need for gas bottles in smaller exchanges, and is quiet enough in operation to be sited in manned areas. 1.2 The CDU 3C consists of a small cabinet housing the compressor, desiccator, humidity detector and all electrical and pneumatic control circuits. An air receiver forms an integral part of the unit, obviating the requirement for additional components. However, a pressure regulating panel (Panel Pressure Regulating 3A) is necessary to control the output from the CDU 3C. 1.3 The CDU 3C can be installed to be either wall or rack mounted using its alternative bracket positions, or can equally be sited as a floor standing unit if preferred. In some cases the cabinet may be sited some distance from the Equipment Cable Pressurisation (ECP) rack. This will not affect the operation of the unit and all details given in this manual will still be applicable. No on-site installation adjustments are necessary. 1.4 The CDU 3C has been designed for simple installation and requires little routine maintenance. Up to 8000 running hours, the only part serviced is the compressor intake filter which is changed by the operator. To maintain optimum efficiency however, a number of functional checks should be carried out at 4000 hour intervals. These checks are detailed in Section 12 of this manual. 1.5 This manual provides information in Sections 11, 12, 13,14 and 15 to allow personnel to maintain and repair all parts of the system. The only notable exception is the compressor which is normally replaced as a unit if faulty. 1.6 The pressure figures quoted in this manual are, in general, purely nominal and must be treated as such. This is because the figures achieved for individual installations will vary due to design tolerances and other external factors. Note Assuming that the equipment is being serviced as detailed in Section 12 of this manual, any gross deviations from the given figures should be reported to the manufacturer. 6 Fig 1 - Compressor Desiccator Unit 12450 (CDU3C) - Front View SECTION 2 - PRODUCT SPECIFICATION 2.1 Environmental Considerations: h Operating Voltage - 230V A.C. 50HZ single phase Plug and 2 metre lead supplied Rating plate affixed to unit Current consumption 2.1A h Temperature - Ambient operating temp. 0 to 35°C h Dimensions - 440mm wide x 800mm high x 330mm deep 7 2.2 - Fixing brackets enable either wall or 19in. rack mounting h Mass - 55kg h Noise Level - 56 to 59 dBA at 1 metre, all planes - 1 Operational Features: h Compressor /3 HP rocking single cylinder piston pump (100 psi) Stop/start pressure 32-65 psi Minimal transmission of vibration, compressor fitted via rubber mounts. Safety relief valve fitted to protect against overpressure Intake filter fitted with replaceable element - - h Air Drier - Twin bed heatless pressure reactivated adsorption type. Each bed on line 1 min/regenerating l min. Automatic changeover by electro-mechanical process timer with memory Desiccant, grade 4A molecular sieve, 3-5mm Inlet and outlet filtration by sintered 35 micron bronze filters at each drier bed port Output dewpoint detection circuit with associated indication & test facilities Automatic bypass to atmosphere of any insufficiently dried air. Set to operate at -20ºC/reset at -25ºC “Brown” colour coded humidity Sensing Element Fail safe operation - - - h Humidity Detection - h Dry Air Storage - Welded air storage reservoir to provide reserve of dry air Capacity 15 litres Safety relief valve set at 102 psi with integral ring pull Fitted with ¼ turn drain ball valve - 8 2.3 2.4 Dry Air Output: h Pressure - Unregulated 32/65 psi intended to be controlled by a separate remote pressure regulating panel h Flow - Exceeds 35 cu ft./hr (16.5 litres/min) Free air delivery h Dewpoint - Better than -40ºC h Connection - Single “quick release” bulkhead coupling to suit ¼“ OD tube, situated at top rear of equipment. - (Multichip Leds) with integral current limiting resistors. Receiver Filling (Green)/Dry Receiver not filling (Red)/Wet ie output being bypassed to atmosphere Alarm Indication: h Visual - h Extended - 15 Way “D” connector provided to enable remote indication of alarms, both normally open and normally closed volt free contacts provided (2 sets each) for: Mains fail Low output pressure. - 2.5 Monitoring/Control h Electrical - Combined illuminated on/off switch and circuit breaker. Total running hour meter to indicate compressor usage. “Running command” lamp indicating when compressor should be operating. - h Pneumatic - 63mm dia. “Compressor” pressure gauge (liquid damped) 63mm dia. “Receiver” pressure gauge 0-160psi. - 9 2.6 Test Facilities h Element Check - A momentary pushbutton switch introduces un-dried compressor air to the sensing element h Circuit Check - “Wet” and “Dry” circuit check pushbuttons to electrically test humidity detector circuitry Tester Humidity Detector 1A compatible via test jack sockets located internally - h Override - Momentary pushbutton to run compressor continually enabling tests to be carried out on the humidity detector. SECTION 3 - INSTALLATION DESIGN INTRODUCTION 3.1 In order to establish the suitability of the CDU 3C for a particular installation, the following data and information must be considered. PERFORMANCE 3.2 The unit is capable of delivering in excess of 35 cu. ft/hr (16.5 litres/min.) of dry air at free air delivery (FAD). It is recommended that for most applications the unit should run at a maximum duty cycle of 50% (12 hrs/day); this means that the total flow should ideally not exceed 13 cu. ft/hr (6 litres/min) at 620 mbar supply pressure. 3.3 To find total cable flow of an existing installation, add together the flow readings of the individual rack mounted flowmeters. Note No harm will occur to the equipment if the 50% duty cycle is exceeded, but at these higher levels, the reserve capacity (which may be required to deal with faults or emergencies)is reduced and the frequency of routine maintenance increased. SUITABILITY FOR HIGH FLOW INSTALLATIONS 3.4 The CDU 3C is not recommended for installations where cable flow is likely to exceed 25 cu. ft/hr (12 litres/min) at 620 mbar. For higher flow installations, the use of either the CDU 1A or CDU2A is recommended depending on capacity. 10 OUTLET CONNECTIONS 3.5 Dry air stored in the air receiver is at a pressure of 32-65 psi (2.2 - 4.5 bar) and is reduced to an output pressure of 9 psi (620 mbar) cable pressure at the Panel Pressure Regulating 3A, which can be fitted to the ECP rack, or the CDU 3C itself using mounting brackets. 3.6 The Panel Pressure Regulating 3A is fitted with a non-return valve to prevent air being drained from the cables in the event of disconnection of the air supply. An air valve is also provided as an entry point for cylinder or mobile desiccator supply in emergencies. 3.7 An alternative panel is available which has all the features of the PPR 3A, but also incorporates a 5-way flowmeter, with provision to increase by a further five. This panel can be obtained directly from Drallim (Part No. 13854) and is supplied complete with brackets to fit above the CDU 3C in a floor standing situation. Fig 2 - Compressor Desiccator Unit 3C - Top View 11 SECTION 4 - ACCOMMODATION REQUIREMENTS 4.1 The CDU 3C is supplied complete with a 2 metre mains lead terminated with a 3 pin 13A plug. 4.2 The dry air outlet is via a quick-release coupling at the top of the cabinet. The mating connector is supplied terminating in an elbow to which ¼“ OD tubing can be connected and run to the Panel Pressure Regulating 3A. 4.3 Physical data for the cabinet is as follows: Height Width Depth Weight 4.4 800mm 440mm 330mm 55 kg When selecting a site for the CDU 3C, observe the following conditions : i) Avoid siting the equipment in locations which experience : a) b) c) ii) High ambient temperatures - ideal operating conditions are 0-35ºC - below zero, the compressor may experience difficulty in starting and the diaphragm of the Minimum Pressure Regulating Valve may become inflexible. Acidic fumes which may damage the internal seals of the compressor. Excessive dust will decrease the performance of the equipment and increase the amount of maintenance required due to filter restrictions. Site the equipment within the exchange or repeater station building. The power room will often provide the most suitable site. 4.5 The equipment must not be sited in a cable chamber. 4.6 The Panel Pressure Regulating 3A should be installed adjacent to the CDU 3C where possible, but extended distances should not cause any operational problems. 4.7 If necessary, arrange for the installation of a wall-mounted mains socket local to the proposed equipment position. Supply requirements are 230V A.C. 50 Hz 13A. 4.8 The CDU 3C can be either floor standing, wall or 19” rack mounted. No rear or side access is required, although some free space must be allowed above the unit to allow the exhaust air to escape. Alternative positions are provided to allow the fixing brackets to be mounted to the cabinet sides to suit either rack or wall mounting (Fig 1). 4.9 Much of the installation work can be completed without disturbing the existing equipment, however at some stage it will be necessary to interrupt the existing air supply to the cables and arrangements for a temporary supply will be required. 12 SECTION 5 - EQUIPMENT SAFETY 5.1 WARNINGS COMPRESSED AIR: THE COMPRESSOR DESICCATOR UNIT 12450 IS CHARGED WITH AIR AT PRESSURES UP TO 100 PSI. UNDER NO CIRCUMSTANCES SHOULD PERSONNEL ATTEMPT TO DISCONNECT PIPEWORK, VALVES, ETC. UNTIL THE SYSTEM HAS BEEN FULLY DEPRESSURISED. VOLTAGES: THE COMPRESSOR DESICCATOR UNIT 12450 OPERATES USING POTENTIALLY LETHAL VOLTAGES OF UP TO 230V AC. ALL NORMAL PRECAUTIONS REGARDING ELECTRICAL EQUIPMENT MUST BE OBSERVED WHEN OPERATING OR WORKING ON THE UNIT. ENSURE THAT ALL ELECTRICAL SUPPLIES ARE ISOLATED BEFORE OPENING THE EQUIPMENT TO DISCONNECT SUPPLY WIRES. 5.2 CAUTIONS Ensure that the air intake/outlet orifices forming part of the casing are unobstructed. The compressor becomes hot in operation if prolonged running is encountered. This may cause localised heating of the equipment casing in the vicinity of the compressor head. Mind your fingers! 5.3 HEALTH AND SAFETY AND FACTORIES ACT. THE COMPRESSOR DESICCATOR UNIT 12450 IS FITTED WITH A PRESSURE VESSEL, REFERRED TO IN THE TEXT AS AN AIR RECEIVER. THE RELEVANT CERTIFICATE OF TESTING IS INCLUDED WITH EACH INDIVIDUAL EQUIPMENT PERFORMED AFTER MANUFACTURE AND VALID FOR 12 MONTHS THEREAFTER. THE AIR RECEIVER IS MANUFACTURED IN ACCORDANCE WITH BS EN286 / BS5169 CLASS 3E. IT SHOULD BE RE-INSPECTED ON A REGULAR BASIS IN ACCORDANCE WITH THE PRESSURE SYSTEMS AND TRANSPORTABLE GAS CONTAINERS REGULATIONS 1989. 5.4 ELECTRICITY AT WORK REGULATIONS IN ACCORDANCE WITH THE ABOVE REGULATIONS THIS EQUIPMENT IS TO BE TREATED AS A PORTABLE ELECTRICAL APPLIANCE AND SHOULD AS SUCH BE INCLUDED IN ANY PLANNED ROUTINE ELECTRICAL TESTING TO ENSURE EMPLOYEE SAFETY. 13 5.5 MANUFACTURERS DECLARATION OF CONFORMITY This equipment is CE marked, indicating that the following Directives have been considered during its design and manufacture. Where relevant, all necessary controls have been applied to ensure compliance. 5.5.1 Low Voltage Directive (73/23/EEC) Implemented in the UK by the Electrical Equipment (Safety) Regulations 1994 (SI 1994 No.3260) which came into effect on 9 January 1995. Most electrical equipment designed to be used with voltages of 501000V a.c. and 75-1500V d.c. is covered. It provides for the equipment to be constructed following good engineering practice so as not to endanger the safety of people, domestic animals or property. 5.5.2 Electromagnetic Compatibility Directive (89/336/EEC) as amended by Directive (92/31/EEC) Implemented in the UK by the Electromagnetic Compatibility Regulations 1992 (SI 1992 No.2372) applicable in full as from 1 January 1996. Covering almost all electrical and electronic appliances, intended to cover the non-generation of electromagnetic disturbances and immunity from such disturbances. 5.5.3 Simple Pressure Vessels Directive (87/404/EEC) Implemented in the UK by the Simple Pressure Vessels (Safety) Regulations 1991 (SI 1991 No.2749) as amended, which came into effect on 31 December 1991. Welded vessels intended to contain air or nitrogen at gauge pressures above 0.5 bar (7.3 psi) are covered. Vessels intended for export outside the EEC are excluded however. A copy of the relevant certificate for the air receiver fitted to this equipment is supplied with the unit. 5.5.4 Pressure Equipment Directive (97/23/EC) Implemented in the UK by the Pressure Equipment Regulations 1999 (SI 1999 No.2001) applicable in full as from 29 November 1999. 14 Applies to equipment, be it components or assemblies forming an integral functional system, subjected to pressures exceeding 0.5 bar. This equipment forms a “Pressure Equipment Assembly” requiring this manufacturers declaration to be made. The applicable conformity assessment procedure is Category 1 Module A. All DRALLIM divisions are accredited with either ISO9001 or ISO9002 and therefore capable of categorisation to either Module H or Module D1 respectively, exceeding the necessary requirements. It is worthwhile noting that “Pressurised pipes for the containment of transmission systems, for example electrical power and telephone cables” are excluded from the Regulations as a whole, reference Article 13 of Schedule 1 of the regulations. This equipment is supplied primarily for use as part of such a system. 15 SECTION 6 INSTALLATION INSTRUCTIONS GENERAL 6.1 Installation of the Compressor Desiccator Unit 3C (CDU 3C) necessitates the interruption of the air supply to the cables. It may therefore be necessary to arrange for a temporary air supply to be used to pressurise the cables. However, if there is sufficient space, the CDU 3C can be installed before existing equipment is recovered. Note Ensure that a mains socket outlet is installed in a position adjacent to the CDU 3C location. COMPRESSOR DESICCATOR UNIT 3C INSTALLATION 6.2 Unpack and prepare the unit as follows: i) ii) iii) iv) Remove and discard the packaging. Detach the cabinet door keys from their stowed position on the cabinet and place in the lock of the front door. Remove the compressor transit screws and pillars and retain for possible future use. The unit is equipped with a glycerine filled 0-150psi compressor pressure gauge of 63mm diameter. This offers the following advantages over a conventional gauge: The liquid absorbs vibration and pressure spikes. The dampening action of the liquid enables the operator to take readings during conditions of rapid dynamic loading and vibration – ideally suited to applications where pulsating situations are encountered, such as a reciprocating compressor. The liquid lubricates all moving elements, dramatically reducing wear in the movement. This gauge is fitted with a venting valve, which has been closed to prevent escape of the liquid during transit. It is important that this valve be opened before use. Temperature fluctuations during shipment and in the process application cause the liquid to expand and contract, which in turn increases/decreases case pressure. Move the valve to the ‘open’ position, which will release any pressure (or vacuum) which has built up in the case. The valve can be left in this ‘open’ position. Fig 3 – Compressor Pressure Gauge Vent Valve. Valve on compressor pressure gauge shown in ‘closed’ position as shipped. Move the orange lever through 180° to the ‘open’ position. 16 v) Ensure that a copy of the manual and the air receiver test certificate have been included in the package. vi) Ensure that the mating connector for the quick release air coupling, a copy of the CDU 3C manual, the air receiver test certificate and a copy of the factory test results have been included in the package together with the four mounting brackets and associated screws. 6.3 Position the CDU 3C ensuring that there is sufficient clearance at the side of the unit to give access to the transit handles. A space of 100mm should be allowed for air circulation above the extractor fan outlet. The unit can be installed to be either free-standing, or wall or rack mounted using the brackets provided. Pneumatic connections 6.4 The mating connector for the quick release coupling is terminated in an elbow to accommodate ¼“ OD tubing. The tubing should be routed from this point to the inlet of the Panel Pressure Regulating 3A. Use Tubing Polyethylene ¼“ PVC sheathed from the CDU3C to the Panel Pressure Regulating 3A. If the adaptor is unsuitable for local requirements, an alternative can be obtained from the Manufacturer. The pressure available at the outlet is between 32 and 65 psi (unregulated), as indicated by the “Receiver” Gauge. Electrical Connections 6.5 A wall mounted socket outlet should be available adjacent to the proposed position. Supply requirements are 230V A.C. 50 HZ 13A. The unit is supplied with a fixed lead terminated in a 13A 3 pin plug to BS1363, fitted with a 13A fuse. A thermal/magnetic overload circuit breaker is incorporated in the illuminated on/off rocker switch, rated at 10A. CAUTION Do not re-use any of the existing tubing as it will possibly be contaminated with water, oil or other debris. NOTE Do not remove or make pipework connections to the ECP rack or cables at this stage. 17 Remote Monitoring of Alarms 6.6 The CDU 3C is provided with facilities to enable external connections to monitor important alarm functions as under: i) Low Output Pressure Indicating that the unit is failing to respond to dry air demands due to either fault with the equipment itself or through increase in air requirements. This could result in inadequate protection being given to the network being supplied. The alarm is set to operate when stored pressure within the receiver reduces to 1.7 bar (25 psi) ii) Mains Failure Connected to the output side of the on/off switch to provide an alarm should the power supply to the unit be disrupted, or the equipment switched off or disconnected from the socket outlet for any reason. 6.7 The alarms can be monitored as either normally open or normally closed, or could be commoned to provide a single “prompting” alarm. The output is provided by a 15 way “D” Connector sited at the top left of the cabinet. To monitor these alarms, connections must be made as follows: PIN NUMBER FUNCTION 1 2 3 Mains Fail (1) Normally Closed Common Normally Open 4 5 6 Mains Fail (2) Normally Closed Common Normally Open 7 8 9 Spare 10 11 12 Low Output (1) Normally Closed Common Normally Open 13 14 Low Output (2) Normally Closed Common 18 15 Normally Open These are volt free clean contacts rated at 5A maximum. Refer to the electrical diagram (12450/B), Fig 5 of this manual COMMISSIONING THE CDU 3C 6.8 Commission the CDU 3C as detailed in Section 7 - COMMISSIONING WARNING VOLTAGES: THE COMPRESSOR, DESICCATOR AND HUMIDITY DETECTOR OPERATE USING POTENTIALLY LETHAL VOLTAGES OF UP TO 230V AC. ALL NORMAL PRECAUTIONS REGARDING ELECTRICAL EQUIPMENT MUST BE OBSERVED. ENSURE THAT ALL ELECTRICAL SUPPLIES ARE ISOLATED BEFORE OPENING THE EQUIPMENT TO DISCONNECT WIRES. WARNING COMPRESSED AIR: THE COMPRESSOR AND ASSOCIATED EQUIPMENT ARE CHARGED WITH HIGH PRESSURE AIR. UNDER NO CIRCUMSTANCES SHOULD PERSONNEL ATTEMPT TO DISCONNECT PIPEWORK, VALVES, ETC, UNTIL THE SYSTEM HAS BEEN FULLY DEPRESSURISED. COMPLETION OF INSTALLATION 6.9 Complete the installation by carrying out the following steps: i) Disconnect any temporary air supply from the cables and re-connect the cable air pipework. ii) Set the POWER OFF/ON switch of the CDU 3C to ON. iii) Adjust the PRESSURE REGULATOR on the PPR 3A to give the desired output pressure reading, usually 9 psi (620 mbar), indicated on the outlet pressure gauge. 19 SECTION 7 - COMMISSIONING The following procedures are to be carried out consecutively unless otherwise stated. VISUAL INSPECTION 7.1 Perform the following checks: i) Visually inspect all pipework and check nuts on pipe couplings for tightness. CONNECTION 7.2 i) The mating elbow connector should be plugged into the quick release coupling at the air outlet of the CDU 3C. Ensure that no tubing is connected from this to the PPR 3A at this stage, so that the output is effectively open to atmosphere. ii) Check that the external 230V AC electrical supply for the equipment is connected and switched on. Plug the mains lead into the supply socket. iii) Set the POWER OFF/ON switch to ON. The amber power and running command lamps will be illuminated and the compressor will start immediately, causing the compressor gauge to rise to about 60-65 psi (4.1 4.5 bar). The Receiver gauge indication will be zero. iv) The red NOT FILLING/WET lamp will probably be lit at this stage, indicating that the desiccant material in the dryer beds has absorbed moisture from the atmosphere. The compressor output air will be directed through the desiccant beds and the excess moisture will be purged to atmosphere. The air will be heard exhausting through the desiccator dump solenoid valve. v) When the desiccant beds have been dried (which could take up to four hours), the NOT FILLING/WET lamp will be extinguished and the green FILLING /DRY lamp will light. The unit will change over to direct the compressor output air via the desiccant beds to the air receiver. All air will consequently be exhausted to atmosphere via the output quick release coupling. Note When running, the sound of a ‘blast’ of escaping air will be heard at regular intervals and the COMPRESSOR gauge reading will drop back to about 25 psi (1.7 bar) and then quickly rise back to 60 psi (4.1 bar). This is not a fault, but the air being switched from one desiccant bed to the other to effect the purging of moisture from the desiccant, thus keeping the output air dry at all times. vi) Run the unit with the green FILLING/DRY lamp lit for at least 10 minutes before checking the operation of the Humidity Detector. 20 HUMIDITY DETECTOR CHECK 7.3 Carry out the following checks on the humidity detector: i) With the FILLING/DRY lamp lit, press the CIRCUIT CHECK/WET push-button. The NOT FILLING/WET lamp should light and the FILLING/DRY lamp extinguish, indicating that the associated electrical circuit is functioning correctly. When the CIRCUIT CHECK/WET push-button is released, check that the NOT FILLING/DRY lamp lights. ii) With the FILLING/DRY lamp lit, press the ELEMENT CHECK pushbutton very briefly. The NOT FILLING/WET lamp should light and the Compressor gauge reading should drop to about 49 - 52 psi (3.4-3.6 Bar). After a short time, the WET lamp should extinguish, the FILLING/DRY lamp being lit in its place. The COMPRESSOR gauge reading should rise to about 60 - 65 psi (4.1 - 4.5 Bar). This test confirms that the humidity detector and associated equipment is functioning correctly. Note The length of time taken for the equipment to dry out the desiccant beds (hence lighting the DRY lamp) is directly proportional to the length of the time that the ELEMENT CHECK button is held depressed. For this reason, do not hold the button for longer than a few seconds. COMPRESSOR CONTROL PRESSURE SWITCH CHECK 7.4 i) Remove the mating elbow connector from the socket of the quick release coupling at the top of the CDU 3C cabinet. This will prevent compressed air from the reservoir escaping to atmosphere. The pressure shown on the RECEIVER gauge will rise to 63 - 67 psi (4.3 - 4.6 Bar) and the compressor will stop. ii) Replace the elbow connector to allow air to be released from the air receiver. The receiver gauge should slowly fall and the compressor restart at 33 - 37 psi (2.3 - 2.6 Bar). This test confirms that the compressor control pressure switch is functioning correctly. AIR RECEIVER RELIEF VALVE CHECK 7.5 Note To check for the correct operation of the receiver relief valve, it is necessary to override the compressor control pressure switch which normally has a maximum setting of 65 psi (4.5 Bar). This is done by depressing and holding in the OVERRIDE switch. Proceed as follows to check the air receiver relief valve : i) The mating elbow connector should be removed from the quick release coupling at the air outlet of the CDU 3C. ii) Open the hinged front door of the cabinet 21 iii) Hold the OVERRIDE button in until the air receiver relief valve opens. Check that the reading on the air receiver pressure gauge is approx 92 - 112 PSI (6.4 – 7.7 Bar). REMOTE ALARM CHECK 7.6 Confirm correct operation of the remote alarm monitoring facility either at the remote site, or directly at the alarm output socket at the top left of the cabinet. Refer back to Sections 6.6 - 6.7 to identify the pin numbers and their function. Checking should be carried out as follows: I) Confirmation of the Low Output Pressure alarm function can be made by plugging the mating elbow connector into the quick release coupling at the air outlet of the CDU 3C. This will exhaust all stored air from the dry air storage reservoir. The compressor will restart when Receiver pressure drops to 33 - 37 psi (2.3 - 2.6 Bar), but the pressure will continue to fall, and at 22 - 28 psi (1.5 - 1.9 Bar) the Low Output Pressure alarm will be activated. ii) The Mains Failure alarm operation can be checked by switching the equipment off at the mains socket outlet, or operating the POWER OFF/ON switch. Note Commissioning has now been completed and the POWER OFF/ON switch should be switched to the OFF position. 22 SECTION 8 - OPERATING INSTRUCTIONS GENERAL 8.1 The design of the CDU 3C is such that it can be left operating for long periods of time with a minimum of operator intervention. SWITCH ON PROCEDURES Introduction 8.2 Depending on the length of time since the unit was last used, one of two differing sequences of events may be observed at switch-on. Although the operating procedure is substantially the same in both situations, both of the sequences are described in the following text. The operator should decide which test is applicable to his situation and read the instructions given therein. Switch-on After Commissioning or Long Periods of ‘Down Time’ 8.3 If the equipment has been commissioned and then left idle for some time or has not been operating due to, say, repair work, the following procedure must be adopted. i) Check that the quick release pneumatic connection at the top of the cabinet has been made. ii) Check that the external 230V AC electrical supply for the equipment is connected and switched on. iii) Set the POWER OFF/ON switch to ON. The amber POWER switch and RUNNING COMMAND lamps will be illuminated and the compressor will start immediately, causing the COMPRESSOR gauge on the panel to rise to about 60 psi (4.1 Bar). iv) It is probable that the red NOT FILLING/WET lamp will be lit at this stage. Under these circumstances, this is not a fault indication but is due to the desiccant material in the dryer beds absorbing moisture from the atmosphere. Leave the unit running; the compressor output air will be directed through the desiccant beds and the excess moisture will be purged to atmosphere. When the desiccant beds have been dried (which could take up to four hours), the lamp will be extinguished and the green FILLING/DRY lamp will light. v) When the FILLING/DRY lamp is lit, the unit will change over to direct the compressor output air via the desiccant beds to the air receiver. The gauge labeled RECEIVER will be seen to rise slowly until a pressure of 65 psi (4.5 Bar) is obtained, the compressor will then be switched off. 23 Note When running, the sound of a ‘blast’ of escaping air will be heard at regular intervals and the COMPRESSOR gauge will drop to about 25 psi (1.7 Bar) and then quickly rise back to 60 psi (4.1 Bar). This is not a fault, but is the air being switched from one desiccant bed to the other to effect the purging of moisture from the desiccant, thus keeping the receiver air dry at all times. vi) Check for any leaks in the interconnecting pipework and connectors and rectify as necessary. vii) Check that the visual indicator of the RUNNING HOURS meter is revolving, indicating that the meter is operating correctly. viii) Carry out the test procedure detailed in Section 9. Fig 4 - Control Features 24 Switch on After Short Shutdown Periods 8.4 If the equipment has been switched off for only a short time, perhaps to allow routine maintenance, the following procedure must be adopted. i) Check that the quick release pneumatic connection has been made at the top rear of the cabinet. ii) Check that the external 230V AC electrical supply for the equipment is connected and switched on. iii) Set the POWER OFF/ON switch to ON. The amber POWER switch lamp will be illuminated. If the air receiver is below 35 psi (2.4 Bar), the compressor will start and the COMPRESSOR pressure will rise to 60 psi (4.1. Bar). If the compressor does not start, this usually means that the pressure at the receiver is already adequate. Note When running, the sound of a ‘blast’ of escaping air will be heard at regular intervals and the COMPRESSOR gauge will drop to about 25 psi (1.7 Bar) and then quickly rise back to 60 psi (4.1 Bar). This is not a fault, but is the air being switched from one desiccant bed to the other to effect the purging of moisture from the desiccant, thus keeping the receiver air dry at all times. iv) Check for any leaks in the interconnecting pipework and connectors and rectify as necessary. v) Check that the visual indicator of the RUNNING HOURS meter is revolving, indicating that the meter is operating correctly. vi) Carry out the test procedure detailed in Section 9. ADJUSTING THE EQUIPMENT OUTPUT PRESSURE 8.5 From time to time, it may become necessary to adjust the system output pressure if the flow demand has been radically altered in some way. In the majority of applications, the pressure regulating panel should be adjusted to provide an output pressure of 9 psi (620 mbar) indicated by the output pressure gauge. This pressure will then be maintained irrespective of the pressure in the air receiver, provided that the receiver pressure is greater than 20 psi (1.4 Bar). 25 SECTION 9 - TEST FACILITIES INTRODUCTION 9.1 The CDU 3C is provided with a test facility which may be used by the operator to check that the system is functioning correctly. It is good practice to operate this facility at regular intervals as a “confidence check”, even if the equipment is apparently working normally. USE OF THE TEST FACILITY 9.2 At the prescribed intervals, initiate a test of the equipment as detailed below. 9.2.1 If the compressor is not running, hold in the OVERRIDE switch. This will bypass the pressure switch and cause the compressor to start. 9.2.2 If the FILLING/DRY lamp is lit, press the CIRCUIT CHECK/WET pushbutton. The NOT FILLING/WET lamp should light and the FILLING/DRY lamp extinguish, indicating that the associated electrical circuit is functioning correctly. 9.2.3 If the NOT FILLING/WET lamp is lit, press CIRCUIT CHECK/DRY. The FILLING/DRY lamp should light and the NOT FILLING/WET lamp extinguish, testing the circuit as in 9.2.2 above. If the NOT FILLING/WET lamp remains on for a long period this is indicative of a fault. 9.2.4 If condition 9.2.2 exists, press the ELEMENT CHECK pushbutton momentarily. The NOT FILLING/WET lamp should light and the COMPRESSOR gauge should drop to about 50 PSI (3.4 Bar). After a short time the WET lamp should extinguish, the FILLING/DRY lamp being lit in its place. The COMPRESSOR gauge should rise to about 60 psi (4.1 Bar). The test confirms that the humidity detector and associated equipment is functioning correctly. NOTE The length of time taken for the equipment to dry out the desiccant beds (hence lighting the DRY lamp) is directly proportional to the length of time that the ELEMENT CHECK button is held depressed. For this reason, do not hold the button for longer than a few seconds. 26 SECTION 10 - OPERATING PRINCIPLES GENERAL 10.1 The CDU 3C serves to supply dry, compressed air to pressurised cables. Air is drawn into the cabinet through the louvres in the front door and pressurised by the compressor. The air is subsequently dried by desiccator beds fitted to a panel on the inside face of the door and directed to the air receiver. This is fitted at the base of the cabinet and stores air at between 35 psi (2.4 Bar) and 65 psi (4.5 Bar), allowing the compressor to operate intermittently in order to maintain this pressure. It also provides a (15 litre) reserve capacity of air allowing cable pressure to be maintained for short periods in the event of the CDU 3C being switched off for maintenance. 10.2 The Pressure Regulating Panel (PPR 3A) regulator ensures that the equipment provides a substantially constant air pressure to the cables irrespective of flow rate. Notes 1) Although the electrical and pneumatic diagrams are separated, the two are obviously inter related. In the following text, references to pneumatic equipment are found in the electrical description and vice versa. 2) The descriptions below assume that, at switch on, the CDU 3C operates correctly and is running dry. ELECTRICAL DESCRIPTION 10.3 Mains power is applied to the unit by setting the POWER OFF/ON rocker (CBR) to ON. This switch is a combined thermal/magnetic circuit breaker (giving 10A overload protection) and neon. The neon is automatically illuminated on operation. 10.4 Assuming that the compressor is required to run, the compressor pressure switch is closed and the RUNNING COMMAND lamp (LP1) is illuminated. 10.4.1 Power is provided to the compressor and extraction fan. 10.4.2 The compressor RUNNING HOURS meter (HCR) starts and runs continuously at all times that the compressor is switched on. 10.4.3 Power is provided to the motor of the process timer (PT1). Depending on the cam position of the timer, power is routed via the wiper to either bed changeover solenoid valve (SV1 or SV2). 27 Fig 5 - Electrical Diagram 28 10.4.4 10.5 Power is routed to supply the humidity detector (HD) printed circuit board. According to the condition detected by the sensing element, the board provides an output to illuminate the NOT FILLING/WET lamp (LP3) or the FILLING/DRY lamp (LP2) as appropriate. If the humidity detector senses a “wet” condition, relay contacts are opened to deenergise the by-pass solenoid valve (SV3), expelling the moist air from the desiccator beds to atmosphere. TEST FACILITY OPERATION 10.6 When the OVERRIDE switch (SW4) is closed, ie held depressed, the compressor pressure switch is effectively short circuited, causing the compressor and associated equipment to operate continuously. 10.7 When the ELEMENT CHECK switch (SW1) is subsequently operated, the wet air test solenoid (SV4) is energised. As detailed in the pneumatic description (Para 10.11), this causes wet air direct from the compressor to be routed to the sensing element (HS) simulating a NOT FILLING/WET situation and thus testing the humidity detector circuit. 10.8 When the DRY CIRCUIT CHECK switch (SW2) is operated, two resistors are connected in series within the humidity detector board. This simulates the high impedance normally measured across the dry sensing element. Providing that the detector circuit is operating correctly, the FILLING/DRY lamp (LP2) will be illuminated. 10.9 When the WET CIRCUIT CHECK switch (SW3) is operated, only one resistor is connected within the detector board, presenting the much lower impedance normally measured across a wet sensing element. Providing that the detector circuit is operating correctly, the NOT FILLING/WET lamp (LP3) will be illuminated. 10.10 The Humidity Detector Board is fitted with two Jack sockets, JK1 and JK2, which are used in conjunction with a Tester Humidity Detector 1A as detailed in Section 12 of this manual. Inserting the plug of the tester into JK1 and JK2 disconnects the sensing element or the circuit board respectively from the equipment, thus allowing simulated inputs to be applied to test the element and board. 29 Fig 6 - Component Layout (Control Features) 30 Fig 7 - Component Layout (Desiccator Features) 31 PNEUMATIC DESCRIPTION Notes 1) The following text assumes that the compressor is running as described in Para 10.4. 2) A typical situation when the CDU 3C is first switched on for normal operation is shown in Fig. 8. The text describing fault and test conditions assumes that the reader is able to visualise the diagram with the solenoids SV1 and SV2 in their alternative positions. 10.11 Under normal operating conditions, the filtered high pressure outlet air from the compressor is routed to an aftercooler, before entering the input solenoid valves to the two desiccator beds. 10.12 The two input solenoid valves SV1 and SV2 assume opposite positions, i.e. one energised and the other de-energised. Assuming that the situation is that shown in Fig. 8, the pressurised air passes through solenoid valve SV1 and into the bottom of the corresponding desiccator bed (BED 1), where it is filtered and dried. 10.13 At the outlet of the desiccator bed, most of the air passes through the associated non-return valve into the humidity sensing unit housing (HS). However, a proportion of the air passes via the reactivation orifice (which is essentially a small bore restrictor) into the top of the right hand desiccator bed (BED 2). This dry air passes down through the bed carrying most of the moisture from the molecular sieve desiccant with it. At the bottom of the bed, the moist air is routed through the solenoid valve (SV 2) to be discharged to atmosphere. 10.14 Dependent on the operational environment the amount of moisture discharged from the desiccator will vary. Small amounts of moisture discharged into the cabinet will be evaporated by the internal heat of the unit. 10.15 The air that has passed through the humidity sensor is next routed to a pressure maintaining valve (PMV) which maintains a pre-set minimum outlet pressure. If the humidity sensor has not detected a “wet” condition, the air is directed to the air receiver. If, however, wet air is detected, the bypass solenoid valve (SV 3) is deenergised, releasing the air to atmosphere. 10.16 After one minute, the electrical process timer (PT 1) changes over the solenoid valves such that the main air is now routed via the right hand desiccator bed (BED 2) whilst the left hand bed (BED 1) is purged of moisture. One minute later the timer changes over the valves again and this procedure is repeated indefinitely for the whole period that the compressor is running. TEST SWITCH OPERATION 10.17 When the control panel ELEMENT CHECK (SW 1) button is pressed the two way test solenoid valve (SV 4) is energised. The compressor outlet air will then be routed directly to the humidity sensing unit housing (HS). Assuming that the electrical detection system is operating correctly the NOTFILLING/WET indicator (LP 3) will illuminate and the wet air is dumped as described in para 10.15. 32 Fig. 8 Pneumatic Diagram 33 SECTION 11 - FAULT DIAGNOSIS AND CORRECTIVE MAINTENANCE Introduction 11.1 In the event that a fault occurs on the equipment, reference should first be made to table 1. Having diagnosed the fault, refer to the relevant text indicated in the ‘Remedy’ column of table 1. Notes 1) If table 1 does not provide a solution for the fault or if the fault recurs, the manufacturer should be consulted as the fault will probably be beyond user repair. 2) In some cases a cross reference is not given in the ‘Remedy’ column if the work requires no specialist knowledge. e.g. changing a fuse. TABLE 1 - FAULT DIAGNOSIS SYMPTOMS POSSIBLE FAULT REMEDY Relevant lamp does not light. Lamp failed Replace lamp (see paragraph 11.2) Compressor runs continuously Failed or incorrectly set pressure switch Replace/adjust pressure switch (see paragraph 14.7 14.8). Unit does not run and POWER switch not lit a) Mains blown in plug or b) Main supply failed a) Replace fuse (13A) in mains plug b) Consult relevant maintenance authority Humidity Detection Circuit not operational Fuse blown a) Replace fuse (see para. 14.2) 34 Lamp replacement 11.2 If it is necessary to replace a failed lamp, the following procedure must be adopted: I) Set the POWER OFF/ON switch to OFF. ii) Unscrew the lens of the relevant lamp unit and withdraw the bulb. The fitting of a new lamp is a reverse operation. The lamps are multichip l.e.ds with integral current limiting resistors, coloured red or green according to function. Changing the Compressor Filter 11.3 i) Set the POWER OFF/ON switch to OFF. ii) Unlock and open the hinged front door of the cabinet to give access to the compressor. iii) Remove the filter unit cover by twisting anti-clockwise and pulling it off. iv) Take off the felt filter and discard it. v) Using a soft lint-free cloth, wipe out any dust from inside the filter unit cover. Take care that the nylon disc inside the cover is not lost or damaged. vi) Fit a new felt filter and re-fit the cover, ensuring that it is correctly locked on. vii) Close and lock the front door and set the POWER OFF/ON switch to ON. 35 SECTION 12 - MAINTENANCE 12.1 The maintenance procedures required on the CDU 3C mainly consist of replacing items which may have mechanically worn or deteriorated due to age. In order to maintain the unit operating at full efficiency, the servicing intervals and tasks detailed in Table 2 should be strictly adhered to. Note Before carrying out maintenance on the unit, it is advisable to arrange for a temporary alternative dry air source to ensure continuity of supply to the cables. MAINTENANCE SCHEDULE 12.2 Table 2 below is the full routine maintenance schedule for the CDU 3C. TABLE 2 - MAINTENANCE SCHEDULE TIME INTERVAL (HOURS) TASK 4000 8000 12000 16000 Functional check (Paragraphs 12.3 - 12.12) * * Change desiccant bed filters (Paragraphs 12.13 - 12.17) * * Change solenoid valve cores 1 (Paragraph 12.18) * Service non-return valve (Paragraph 12.19) * * Change reactivation orifice (Paragraph 12.20) Change compressor filter (Paragraph 11.3) 1 * * * * * The frequency of replacement of the wet air test (SV 4) and bypass (SV 3) solenoid valves is less than that for the desiccator bed changeover valves (SV 1 and SV 2) 36 FUNCTIONAL CHECKS Introduction 12.3 At the specified time intervals, all of the following functional checks should be carried out in the order given. If the result of a check is not necessary, refer to Section 13 - DIAGNOSTICS. Checking for Leaks WARNING THE FOLLOWING TEST REQUIRES THE UNIT TO BE INSPECTED WHILST IT IS OPERATING. TAKE GREAT CARE AS VOLTAGES OF UP TO 230V AC AND COMPRESSED AIR AT UP TO 100 PSI ARE PRESENT. 12.4 All pneumatic pipework and unions should be checked for leakage as follows: i) The POWER OFF/ON switch should be set to OFF. ii) Unlock and open the hinged front door to allow access to the desiccator and compressor assemblies. iii) Set the POWER OFF/ON switch to ON. Confirm that the cooling fan is running by placing a hand over the louvres in the cabinet top. However this will only operate whilst the compressor is running and therefore the OVERRIDE button should be operated if the compressor does not run. Note Discharge the air receiver by using the safety relief valve ringpull which will allow the unit to operate. This may need to be repeated several times. WARNING TAKE GREAT CARE. THE ASSEMBLY WILL NOW BE ELECTRICALLY LIVE AND PRESSURISED iv) Inspect all pipework and fittings for leaks, paying particular attention to flexible pipework. Larger leaks will usually be audible and self evident. If a leak is suspected but cannot be confirmed audibly, apply a small quantity of Leak Detecting Solution. WARNING TAKE GREAT CARE WHEN USING LEAK DETECTING SOLUTION NEAR ELECTRICAL TERMINALS AND WIRING 37 Checking the Output Flowrate 12.5 The Flowmeter Portable 2A is used to check the overall flowrate at the output of the CDU 3C. To use the flowmeter, proceed as follows: i) Refer to Fig 9. Remove the tubing connecting the unit to the Panel Pressure Regulating 3A. Connect the flowmeter to the output connector on top of the unit using ¼“ OD tubing. Fig 9 - Use of Flowmeter Portable 2A to Check Output Flowrate ii) Set the POWER OFF/ON switch to ON and, holding the flowmeter upright, note the reading obtained. It should be a minimum of 32 cu. ft./hr (15 litres/min.) iii) Set the POWER OFF/ON switch to OFF, remove the flowmeter and reconnect the normal outlet pipework. 38 Checking the Compressor Maximum Pressure 12.6 Although the compressor is capable of running at higher pressures, the back pressure of the desiccator is set at 60 - 65 psi (4.1 - 4.5 Bar) to maintain efficiency. The compressor is controlled such that maximum flow is obtained whilst overcoming this back pressure. To check the correct running pressure of the compressor, proceed as follows : i) Set the POWER OFF/ON switch to ON. If the compressor does not start, discharge the air receiver by using the safety relief valve. ii) Compressor pressure will rise to 60 psi (4.2 Bar) at which point air will begin to enter the receiver. The RECEIVER gauge can be seen to rise at this point. COMPRESSOR pressure should maintain at approximately 60 psi whilst RECEIVER pressure is increasing. iii) A safety relief valve is fitted to the compressor head which is set to exhaust at 120 - 130 psi (8.3 - 9 Bar) Checking the Purge Flowrate 12.7 A portable flowmeter 2A is used to check the purge air flowrate at the base of the desiccator beds. To use the flowmeter, proceed as follows: i) With the power still switched off, unlock and open the door. ii) Connect the flowmeter inlet pipe (refer to Fig. 10) to the spigot adapter at the exhaust port of the right hand bed changeover solenoid (SV 2) and ensure that it is tightened securely. iii) Set the POWER OFF/ON switch to ON. If the compressor does not start immediately, discharge the air receiver by using the safety relief valve. With the flowmeter held upright, the reading obtained should be in the range 16 20 cu. ft./hr (7.7 - 9.6 litres/min) at NTP. Note It may be necessary to wait for up to one minute before it is possible to take a reading. This is because the desiccator beds are purged alternately under control of the electrical timer. If more than one minute elapses and the bed has not purged, this is indicative of a fault in the solenoid and/or timer. v) Disconnect the flowmeter. vi) Repeat ii) - v) on the left hand bed/changeover solenoid (SV 1) 39 Checking the Air Receiver 12.8 Check that the receiver relief valve is not ‘lifting’ allowing pressurised air to escape. A serious leak can usually be detected audibly but if in doubt, use a suitable leak detecting solution. Replace the valve if it is found to be leaking. Checking the Electrical Wiring 12.9 Check the electrical wiring as follows: i) Switch the power OFF at the wall socket outlet. ii) With the power OFF, open the hinged door. iii) Examine the wiring harness for signs of overheating such as charring or discoloration. iv) Examine the tags on the terminals to ensure that they are secure. v) Close and re-secure the door. vi) Switch the power ON at the wall socket outlet. Checking the Humidity Detector System 12.10 When available, a Tester Humidity 1A can be used to test the CDU 3C internal humidity detection system and can be used in two different modes. In one mode it tests the humidity sensing element; in the second mode it tests the circuit board and wiring associated with the element. The use of the meter in both applications is detailed below. The front door must be open to access the jack sockets, which are fitted to the Humidity detector circuit board, identified on its cover as JK1 and JK2. 12.11 Testing the Sensing Element To test the sensing element, proceed as follows : i) Turn the Tester on and connect the small jack plug of the tester lead to the tester socket marked ELEMENT. Connect the other end of the lead to Test Jack Socket JK1 (large) of the CDU 3C’s Humidity Detector circuit board. ii) Note the reading given on the front panel OHMS meter, which should be in excess of 50 M ohms. iii) If a significantly lower reading is obtained, it may well be that the unit genuinely being subjected to moist air, switch the CDU 3C on and leave it to run for 30 minutes before repeating the test. If the element subsequently gives a reading of less than 50 M ohms when dry, it is faulty and should be replaced. iv) Disconnect the lead from Test Jack socket JK1. 40 is 12.12 Testing the Circuit Board To test the humidity sensing circuit board and wiring, proceed as follows : i) Connect the large jack plug of the tester lead to the tester socket labelled HUMIDITY DETECTOR. Connect the other end of the tester lead to Test Jack socket JK2 (small) of the CDU 3C’s Humidity Detector circuit board. ii) Set the tester thumbwheel controls to 150, representing a resistance of 15 M ohms. Note The maximum resolution of the thumbwheel resistance controls is 0.1 M ohms. iii) Set the CDU 3C POWER OFF/ON switch to ON. If the compressor is not running depress and hold the OVERRIDE pushbutton. This will override the pressure switch and cause the compressor to start. Irrespective of the actual moisture content in the desiccator beds, the front panel FILLING/DRY (LP 2) lamp should be illuminated. iv) Set the thumbwheel controls to 099 (9.9 M ohms) and then progressively reduce the resistance in 0.1 M ohm steps until the front panel lamps change to indicate NOT FILLING/WET (LP 3 illuminated). Note the value at which the lamps change over. v) Reset the thumbwheel controls to 199 (this will reset the circuit) and repeat (iv) twice, noting the changeover value on each occasion. The average value of the three readings obtained should not be less than 7 M ohms (070). vi) Set the thumbwheel controls to 050 (5 M ohms) and check that the NOT FILLING/WET lamp illuminates. Progressively increase the resistance in 0.1M ohm steps until the front panel lamps change to indicate FILLING/DRY. Note the value at which the lamps change over. vii) Reset the thumbwheel controls to 050 and repeat (vi) twice, noting the changeover value on each occasion. The average value of the three readings obtained should not be greater than 14 M ohms. viii) If the readings listed above cannot be obtained alter the Potentiometer marked R17 on the electronic circuit board, turn the Potentiometer in 90 degree steps clockwise or anti-clockwise repeating Sections (iii) to (vii) until correct readings are obtained. The cover must be removed to gain access to this potentiometer. 41 Note If the correct readings cannot be obtained the electronic circuit board may be faulty and will need changing. Drallim Reference for the electronic circuit board is 13970/110AC/240AC. ix) Switch off the CDU 3C and Tester. CHANGING THE DESICCATOR BED FILTERS Introduction 12.13 To change the desiccator bed filters, proceed as follows: i) Set the POWER OFF/ON switch to OFF. ii) Release the air outlet coupling from the quick release connector at the top of the cabinet. WARNING THE AIR RECEIVER AND ASSOCIATED FITTINGS AND TUBING ARE NOW PRESSURISED AT UP TO 100 PSI. CAUTION SHOULD BE EXERCISED WHILST CARRYING OUT THE FOLLOWING. iii) Pull on the ringpull of the safety relief valve fitted to the air receiver thus causing it to de-pressurise. Hold it out until the RECEIVER gauge falls to zero and then release. 12.14 In order to replace the desiccator bed filters, it is first necessary to remove the desiccator bed as follows. i) Fully slacken the ¼" union nuts at the base of the desiccator beds to release the lower tubing branch, complete with solenoid valves. ii) Slacken the two banding strips securing the right hand desiccator bed to its mounting brackets. 42 Fig 10 - Use of Flowmeter Portable 2A to check Purge Flowrate Filter Adaptor 12500/19 O Ring 200-112-4490 Spigot Adaptor 12500/18 Desiccator Bed 12500/15/3 Filter 1225501 O Ring 200-019-9775 Fig 11 - Desiccator Bed Filter Assembly 43 iii) Undo the right hand ¼“ union nut of the tee coupling connected to the upper filter carrier whilst supporting the desiccator bed. Once the nut has fully withdrawn from the thread, the desiccator bed can be removed from the assembly. Lower Filters 12.15 To change the desiccator bed lower filter, proceed as follows: i) Invert the desiccator bed assembly and remove the spigot adapter, leaving the threaded filter adapter bush complete with filter attached to the bed. ii) The filter is a threaded fit in the brass filter adapter bush and can be removed using a flat bladed screwdriver. Take care as the filter is made of brittle material. iii) Fit a new filter, ensuring that it is tightened fully ’home’ and replace the spigot adapter. iv) Re-invert the desiccator bed assembly. Note If any molecular sieve pellets inadvertently escaped, these should be replaced whilst changing the upper filter. Upper Filters Note The same care should be exercised as detailed for the lower filter. 12.16 To change the desiccator bed upper filter, proceed as follows: i) The desiccator bed should be removed as described under Para 12.14 ii) Place the bed on its side to prevent the escape of molecular sieve pellets and remove the spigot adapter revealing the filter, which can be removed using a flat bladed screwdriver, leaving the filter adapter bush in place in the desiccator bed. iii) Screw a new filter into the threaded bush, replace the spigot adapter into the desiccator bed and tighten. Note If difficulty is experienced in refitting the assembly due to the molecular sieve, gently tapping the desiccator bed will usually cause the pellets to settle. The assembly should fit without further problems. iv) Return the desiccator bed to its upright position. 44 v) Replace the desiccator bed by inserting it back through the banding strips, ensuring that it mates with the union nuts. Tighten the nuts finger tight and then refit the bed to the panel, tightening up the lockscrews of each band. Finally ensure that the union nuts and screws are securely tightened. 12.17 Repeat procedures as described in Paras 12.15 and 12.16 for the left hand desiccator bed. Changing the Solenoid Valve Cores 12.18 It is often expedient to replace the complete valve. However, to change the core of the solenoid valve, proceed as follows: i) Ensure that the POWER OFF/ON switch is set OFF. Unlock and open the hinged front door. ii) Pull on the ringpull of the safety relief valve fitted to the air receiver thus causing it to de-pressurise. Hold it out until the RECEIVER gauge falls to zero and then release. Disconnect the purge pipe connector from the exhaust port of the solenoid valve. iii) Remove the securing nut from the end of the core tube. Take off the washer and remove the solenoid coil. iv) Whilst holding the valve body with a suitable spanner, remove the core tube assembly. 45 Fig 12 - Solenoid Valve Assembly Caution The core tube may be very tight. It is essential that the valve body be held securely whilst the core tube is removed as the connecting pipework will otherwise be damaged. v) Separate the core and spring from the core tube. Retain the core tube for subsequent replacement. vi) Check that the core seating in the valve body and the core tube itself are clean and undamaged; clean as necessary. Assemble the new core and spring in the core tube and screw the assembly into position on the body. Tighten securely, ensuring that the body is adequately supported. vii) Fit the solenoid coil, and washer onto the core tube. Fit and tighten the securing nut and replace the purge pipe connector. 46 SERVICING THE NON-RETURN VALVE 12.19 To service the non-return valve, proceed as follows: i) Ensure that the POWER OFF/ON switch is set OFF. Unlock and open the hinged front door. ii) Pull on the ringpull of the safety relief valve fitted to the air receiver thus causing it to de-pressurise. Hold it out until the RECEIVER gauge falls to zero and then release. iii) Remove the right hand desiccator bed as described under Para 12.14. iv) Slacken the union nut connecting the humidity sensing unit housing to the non-return valve assembly. Support the regulating valve/humidity sensing unit housing assembly whilst releasing the union nut. v) Release the left hand union nut of the reactivation orifice and the lefthand connector nut of the non-return valve. The non-return valve assembly can then be removed from the desiccator panel. Fig 13 - Non-Return Valve Assembly vi) vii) viii) Undo the right hand connector nut of the non-return valve to enable removal of the tee coupling attached to it. Remove the right hand seat housing and withdraw the valve stem and spring. Remove and discard the old sealing washer. Clean the housing seat as necessary and re-assemble the valve using the new components from the service kit. In order to ease re-assembly, insert a screwdriver through the seat housing nut to hold the valve stem in the body whilst tightening the nut. 47 Caution If resistance is felt as the nut is tightened, the stem is not correctly located in the valve body. Remove the nut and re-commence assembly as the valve stem can be easily damaged. xi) Repeat steps vii) and viii) for the left hand section of the valve. Note Section 12.19 details only the right hand section of the valve. The left side is however identical in all respects. xii) Assembly is a reversal of the process described under iii) to vi) xi) Check the assembly for leaks as described in Para 12.4. CHANGING THE REACTIVATION ORIFICE 12.20 To change the reactivation orifice, proceed as follows: i) Ensure that the POWER OFF/ON switch is set to OFF. Unlock and open the hinged front door. ii) Undo the pipe connector nuts of the tee couplings in the upper branch of the desiccator assembly and remove the copper tubing branch complete with reactivation orifice. iii) Use a spanner to disconnect the two pipe connector nuts on the reactivation orifice, using a second spanner to hold the component. iv) Carefully locate the two copper tubing pieces into the new reactivation orifice and tighten the two pipe connector nuts. v) Replace this assembly into the tee couplings in the upper branch of the desiccator and tighten the union nuts. vi) Check the purge flowrate as described in Para 12.7. 48 SECTION 13 - DIAGNOSTICS INTRODUCTION 13.1 In the event that a fault occurs on the equipment, reference should first be made to Table 3. Having diagnosed the malfunction, refer to the relevant text as indicated in the ‘Remedy’ column of Table 3. Notes 1) In some cases a cross reference is not given in the ‘Remedy’ column if the work requires no specialist knowledge, e.g. - changing a fuse. 2) The diagnosis given in Table 3 is obviously not fully exhaustive, but details the common faults which practical experience has shown to occur most often. If the information in this table does not help cure the fault, reference should be made to the electrical circuit diagram Fig. 5 or the pneumatic diagram Fig. 8. TABLE 3 - MALFUNCTION DIAGNOSIS SYMPTOMS Relevant lamp does not light when circuit check (wet or dry) pressed. Compressor runs continually POSSIBLE FAULT a) Lamp failed a) Replace lamp (see Para. 11.2) b) Faulty printed circuit board b) Test board using Tester Humidity 1A (see Para. 12.12) a) Replace switch (see Para 14.7) a) Contacts of compressor pressure switch permanently closed. b) Unit undersized Receiver gauge never rises above zero although compressor operates normally. Unit continuously gives NOT FILLING WET indication. REMEDY a) Minimum pressure regulating valve setting incorrect. b) Check total cable flow (see Paras 3.2-3.4) a) Adjust valve setting (see Para 14.9) b) Receiver relief valve faulty. b) Replace receiver safety relief valve (see Para 14.10) c) Non-return valve faulty c) Service non-return valve (see Para 12.19) d) ‘Dump’ solenoid permanently open to atmosphere d) Check the humidity detector system (see Para 12.10) a) Unblock or replace reactivation orifice (see Para 12.20).. a) Reactivation orifice blocked or restricted. Check purge with flowmeter. 49 Unit does not run and POWER lamp not lit Mains Fail external alarm activated ‘Running Hours’ meter does not revolve when compressor running. Compressor cuts in and/or out at wrong pressure Outlet flowrate low or decreasing markedly b) Sensing element faulty. b) Replace as necessary. c) Non-return valve faulty. c) Service non-return valve (see Para 12.19) d) Faulty process timer d) Replace as necessary e) Bed changeover solenoid faulty. e) Repair/replace valve (see Para 12.18) f) Desiccator bed filter(s) blocked. f) Replace filters (see Para 12.13 - 12.17). g) Faulty printed wiring board. g) Check the humidity detector system (see Para. 12.10) a) Connect to supply a) Unit not connected to mains supply b) Mains supply failed b) Investigate supply problem c) Fuse blown c) Replace fuse (see Para 14.2) d) Power switch faulty d) Replace power switch (see Para 14.11) a) Check wiring (see Para 12.9) a) Damaged wiring b) Meter faulty b) Replace meter (see Para 14.6) a) Compressor pressure switch requires adjustment a) Adjust switch (see Para 14.8) b) Compressor pressure switch faulty b) Replace switch (see Para 14.7) a) Desiccator bed filter(s) blocked a) Change filters (see Paras 12.13 - 12.17) b) Compressor worn or faulty. b) Replace compressor (see Para 14.3) 50 Fan running but compressor not cutting in, FILLING/DRY lamp lit FILLING/DRY lamp lit but compressor cooling fan not running FILLING/DRY lamp lit, compressor running but fan not running Unit runs normally but neither FILLING/DRY nor NOT FILLING/WET lamps light when CIRCUIT CHECK button depressed c) Compressor filter blocked. c) Replace filter (see Para 11.3) d) Internal Pipework leaking d) Check for leaks and repair as necessary (See Para 12.4) a) Replace compressor (see Para 14.3) a) Compressor faulty a) Compressor control pressure switch faulty a) Replace switch (see Para 14.7) a) Fan burnt out or faulty a) Replace fan (See Para 14.4) a) Lamp failed a) Replace lamp (See Para 11.2) b) Printed circuit board fuse blown b) Replace on-board fuse (See Para 14.2) c) Printed circuit board faulty c) Test pcb using Tester Humidity 1A (See Para 12.12). 51 SECTION 14 - REPAIRS INTRODUCTION 14.1 This section is for use in conjunction with Section 13 which covers fault diagnosis. However, rather than unnecessary duplicate information under this heading, details of how to carry out several ‘repairs’ which also fall into the ‘maintenance’ category can be found in the preceding sections referred to in Table 3. Fuse Replacement NOTE Two fuses are used within the equipment. One is situated within the mains plug, the other fitted to the Humidity Detector printed circuit board. It is essential that the correct value fuse be fitted as a replacement as follows: Mains Plug Printed Circuit Board 14.2 13A QB 250mA AS Ceramic Quick Blow 1¼“ Anti Surge 20 mm If it is necessary to replace a blown printed circuit board fuse, proceed as follows: i) Set the POWER OFF/ON switch to OFF ii) Open the hinged front door. iii) Remove the four screws securing the printed circuit board cover to enable access to the board itself. iv) Withdraw the suspect fuse from its holder and test using a suitable instrument such as a multimeter. If the fuse has blown, proceed from Step v) below. v) Ensure that the fuse clips are clean and undamaged. Clean and carefully bend them to improve contact if necessary. vi) Fit the fuse in the holder vii) Refit the printed circuit board cover, close the door and set the POWER OFF/ON switch to ON. viii) Carry out a system test. If the fuse immediately blows again, further fault diagnosis must be carried out and the fault repaired before fitting another fuse. 52 Fig 14 - Compressor Removal Compressor Replacement 14.3 In the event that the compressor requires replacement, proceed as follows: i) Set the POWER OFF/ON switch to OFF. ii) Unlock and open the hinged front door. iii) Disconnect the electrical lead from the compressor. The terminal cover is removed by loosening the two hexagon headed screws at the left hand end of the compressor. Note the position of the crimp terminal connections before disconnecting as you will require this information to enable replacement. iv) Disconnect the braided outlet hose at the union on the head of the compressor. v) Undo and remove the two hexagon headed bolts securing the compressor support plate to the air receiver. vi) Carefully withdraw the compressor assembly complete with its mounting and support plates. 53 vii) Place the compressor on its side and remove the four hexagon headed bolts securing the compressor to its mounting plate. The anti-vibration mountings need not be disturbed. viii) Correctly position the replacement compressor on the mounting plate and secure with the four hexagon headed bolts. ix) Remove the union from the head of the defective compressor and fit to the replacement compressor together with the intake filter assembly. Use PTFE tape on the threads. x) Re-position the compressor complete with mounting and support plates onto the air receiver and secure with the two hexagon headed bolts removed in v). xi) Connect the compressor lead and replace the terminal cover. xii) Re-connect the braided outlet hose to the union fitted to the compressor head. xii) Close and lock the hinged front door. xiv) Set the POWER OFF/ON switch to ON. Fan Replacement 14.4 If the fan should need replacement, proceed as follows: I) Switch the POWER OFF at the wall socket outlet. ii) Open the hinged front door. iii) Disconnect the three wires from the terminals on the fan assembly, marking the wires carefully for subsequent reconnection. iv) The fan and grille are fitted to the inside top face of the cabinet. Remove the four screws, nuts and washers and withdraw the fan and grille, noting the orientation. v) Fit the new fan in position with the air flow arrow pointing uppermost and the grille underneath it. Secure with the four screws, nuts and washers. vi) Reconnect the three wires to the corresponding fan terminals. vii) Close and re-secure the hinged front door. Set the power ON at the wall socket outlet. 54 Pressure Gauge Replacement 14.5 In the event that either of the pressure gauges require replacement, proceed as follows: i) Set the POWER OFF/ON switch to OFF. ii) Open the hinged front door. iii) Pull on the ringpull of the safety valve fitted to the air receiver thus causing it to de-pressurise. Hold it out until the RECEIVER gauge falls to zero and no more air can be heard escaping, then release. iv) If the RECEIVER gauge is being replaced, release the union nut securing the cross coupling to the pipe fitting at the rear of the gauge. If the COMPRESSOR gauge is being replaced, loosen the pipe nut at the rear of the gauge and withdraw the tubing itself from the fitting. v) Remove the pipe fitting from the rear of the gauge, holding the gauge to prevent it from rotating. In the case of the RECEIVER gauge, release the securing nut and bridge piece and withdraw the gauge through the front of the door panel. The clamp fixing the COMPRESSOR gauge is released by slackening the e two slotted screws fixed through the clamp at either end. vi) Check that the replacement gauge to be fitted is of the correct type. The RECEIVER gauge is of 0 - 160 psi range, whilst the COMPRESSOR gauge is 0 - 150 psi, and liquid filled. vii) Fit the new gauge in the panel cutout and position the bridge piece behind. Secure this with the backnut in the case of the RECEIVER gauge, or by tightening the two slotted screws of the COMPRESSOR gauge. Refit the union and secure all remaining couplings and tubing removed during steps iv) - v) above. viii Close the hinged front door and set the POWER OFF/ON switch to ON. Running Hours Meter Replacement 14.6 In the event that the ‘Running Hours’ meter requires replacement, proceed as follows: i) Switch the POWER OFF at the wall socket outlet. ii) Open the hinged front. iii) Disconnect the wires from the terminals at the rear of the meter, noting their respective positions for subsequent replacement. iv) Press the plastic clips on either side of the meter inwards and push it through the panel. Remove the meter. 55 v) Push the replacement meter into position and reconnect the wires. vi) Close the hinged front door. vii) Set the POWER OFF/ON switch to ON. Compressor Control Pressure Switch Replacement 14.7 If the compressor control pressure switch requires replacement, proceed as follows: i) Switch the POWER OFF at the wall socket outlet. ii) Open the hinged front door. iii) Pull on the ringpull of the safety valve fitted to the air receiver thus causing it to de-pressurise. Hold it out until the RECEIVER gauge falls to zero and then release. iv) Slacken the two screws on top of the compressor control pressure switch and remove the front cover. Fig 15 - Compressor Control Pressure Switch 56 v) Disconnect the wires from their internal terminal block, noting their positions for subsequent reconnection. Withdraw the cables carefully through the grommet. vi) Disconnect the fitting from the pressure port on the base of the pressure switch. vii) Remove the two screws securing the unit to the inner door panel. viii) Tighten the fitting (using PTFE tape) on the pressure port. Do not overtighten. ix) Position the replacement pressure switch and fit and tighten the securing screws. x) Pierce a suitable hole through the grommet and carefully thread the wires through into the unit. Connect the wires to the correct terminals on the terminal block. xi) Slide the plastic cover onto the pressure switch and tighten the two retaining screws. xii) Adjust the pressure settings as detailed in Para 14.8 Compressor Control Pressure Switch Adjustment 14.8 To adjust the pressure switch settings, proceed as follows:i) Set the POWER OFF/ON switch to OFF. ii) Unlock and open the hinged front door. WARNING THE AIR RECEIVER AND ASSOCIATED FITTINGS AND TUBING ARE NOW PRESSURISED AT UP TO 100 PSI. CAUTION SHOULD BE EXERCISED WHILST CARRYING OUT THE FOLLOWING. iii) Pull on the ringpull of the safety valve fitted to the air receiver thus causing it to de-pressurise. Hold it out until the RECEIVER gauge falls to zero then release. iv) Turn the left hand square on top of the pressure switch until the START range scale reads 4.5 Bar. v) Turn the right hand hexagon on the top of the pressure switch until the DIFF range reads 2.3 Bar. vi) Switch on the unit and check the pressure at which the compressor cuts out. This should be 65 psi (4.5 Bar). To alter this setting, repeat steps i) to iii) above and adjust the left hand square on top of the pressure switch as necessary. 57 Note Although labelled START, the left hand range shows the pressure at which the compressor stops. This setting must always be adjusted accurately before adjusting the DIFF scale. The DIFF scale indicates the difference between start and stop pressures, not the start pressure itself. vii) When the required setting has been achieved, reduce air pressure in the receiver by pulling the pullring such that the safety relief valve just opens. Observe the RECEIVER gauge, which should indicate 32 psi (2.2 Bar) when the compressor re-starts. If necessary, adjust the right hand hexagon on top of the pressure switch. viii) With both the cut-out pressures correctly set, close and lock the front door of the CDU 3C. Minimum Pressure Regulating Valve Adjustment 14.9 To maintain drying efficiency, the back pressure of the desiccator is set at 4.3 Bar. This can be checked and adjusted as follows: i) Set the POWER OFF/ON switch to ON. If the compressor does not start, discharge the air receiver by using the safety relief valve. ii) The COMPRESSOR gauge should rise to 62 psi (4.3 Bar) at which point air will begin to enter the air receiver. The receiver gauge can be seen to rise at this point. If, however, this requires adjustment, alter the setting of the minimum pressure regulating valve. iii) Slacken the locknut of the adjusting screw, which should be turned clockwise to increase pressure. After adjustment, re-tighten the locknut and check the gauge readings. Air Receiver Safety Relief Valve Replacement 14.10 The safety relief valve is set to open at 102 psi (7.0 Bar). It is factory set and should not require adjustment. If however, during the routine checking for leaks, it is found that this valve does leak, it is likely to be worn seat necessitating replacement. This should be carried out as follows: i) Set the POWER OFF/ON switch to OFF. ii) Unlock and open the hinged front door. iii) Pull on the ringpull of the safety valve fitted to the air receiver thus causing it to de-pressurise. Hold it out until the RECEIVER gauge falls to zero then release. 58 WARNING UNDER NO CIRCUMSTANCES MUST ANY ATTEMPT BE MADE TO REMOVE THE RELIEF VALVE UNTIL THE RECEIVER IS COMPLETELY DEPRESSURISED. iv) Fit the new relief valve, using 3 or 4 turns of PTFE tape on the pipe thread before fitting. Caution Do not over-tighten the relief valve; the air receiver has to be returned to the manufacturer for replacement of a damaged socket. vi) Set the POWER OFF/ON switch to ON and when the air receiver has become pressurised, perform a leak test around the area of the relief valve using a suitable detecting solution. Tighten the valve further if necessary. Power Off/On Rocker Switch Replacement. 14.11 The POWER OFF/ON rocker is rated at 10A and is combined with a neon indicator. The unit is replaced as an assembly as follows: i) Disconnect the CDU 3C from the mains power source at the socket outlet. ii) Open the control hinged front door. iii) Pull back the shrouded terminal cover to allow access to the connectors and remove the connectors from the rear of the switch, noting their respective positions for subsequent replacement. iv) Press the plastic clips at the top and bottom rear of the switch to release and withdraw the assembly through the front of the panel. v) Push the new switch assembly through the front of the control panel, ensuring that the clips are fully engaged at the rear. vi) Reconnect the wires, and close the hinged front door. vii) Reconnect power at the socket outlet and set the POWER OFF/ON switch to ON to verify correct operation. 59 SECTION 14 SPARES PARTS All spares can be obtained from the manufacturer. Please contact the sales or service department at the following address: DRALLIM TELECOM MILLWOOD HOUSE, DRURY LANE, PONSWOOD INDUSTRIAL ESTATE, ST. LEONARDS ON SEA, EAST SUSSEX TN38 9BA Telephone 01424 205140 Fax 01424 202140 Product development may change details and specifications. TABLE 4 - SPARE PARTS ITEM Compressor Compressor Safety Relief Valve Flexible Compressor Hose Compressor Pressure Gauge Receiver Pressure Gauge Solenoid Valve 3 way Desiccator Changeover (High Humidity By Pass) Solenoid Valve 2 way Element Check Reactivation Orifice Non Return Valve Service Kit *1 Non Return Valve Complete Solenoid Valve Service Kit (Core) Solenoid Valve Service Kit (Core) Humidity Sensing CIRCUIT REF - MANUFACTURER DRALLIM (PT. NO) PART NO. GAST (71R142 - 6500240 POO1B - D301X) GAST (AF592S) 6520450 - DRALLIM 13629/2 PG 2 WIKA (213.53.063) 1300496 PG 1 WIKA (111.12.063) 1300528 SV1, SV2, SV3 PARKER LUCIFER (131 M14) 1805569 SV4 1805525 NRV PARKER LUCIFER (121 M13) DRALLIM DRALLIM SK303/CP/GW 1410474 NRV DRALLIM 13671/S/B PARKER LUCIFER (488877) PARKER LUCIFER (488878) OHMIC (HS - 1) 1606271 SV1, SV2, SV3 SV4 HS 60 1606270 1210264 ITEM Element *2 Humidity Detector Printed Circuit Board Pressure Maintaining Valve Compressor Control Pressure Switch Low Output Pressure Switch Air Receiver Safety Relief Valve On-Off Circuit Breaker Fan CIRCUIT REF MANUFACTURER (PT. NO) HD DRALLIM PMV IMI NORGREN (V06-222-NNKD) DANFOSS (KP35) PSW 1 PSW 2 SUCO 0180 45803 1 006 BAMBI COMPRESSORS ETA (3120-F451) ZIEHL - EBM (W25S107-AA01-40) OMRON (G2R-2 230VAC) CROUZET (88-611-3) CURTIS INSTRUMENTS ARCOLECTRIC (CO911NB/BLACK/ BLACK) CBR - Mains Fail Relay Low Output Relay Process Timer RLA RLB PT1 Running Hours Meter HCR Element Check Pushbutton Switch Override Pushbutton Switch Dry Circuit check Pushbutton Switch SW1 Wet Circuit Check Pushbutton Switch SW3 Running Command Lamp & Holder Filling Lamp (LED Cluster) Not Filling Lamp (LED Cluster) Filling Lamp Lampholder Not Filling Lamp Lampholder Dry Air Outlet Plug (Quick Release Desiccant Molecular Sieve Desiccator Bed Filter SW4 SW2 DRALLIM PART NO. 13970/110AC/ 240AC 1805396 1706636 1706568 1805264 1705874 1122570 1626260 1715628 1122868 1707076 LP1 ARCOLECTRIC (CO911NB/BLACK/ GREEN) ARCOLECTRIC (CO911NB/BLACK/ RED) ARCOLECTRIC 1425675 LP2 RS (585-668) 1425474 LP3 RS (585-652) 1425473 LP2 ARCOLECTRIC (T0063/AO/GREEN) ARCOLECTRIC (T0063/AO/RED) A.V.S. (5350 - 1/8) LAPORTE (4A-8/2 2.5 - 5mm) PORVAIR (AEL1050/B30 1425677 LP3 61 1707077 1707078 1425676 1123006 1205033 1225501 ITEM Solenoid Valve Exhaust Fitting Fuse (20 mm) Humidity Detector Board 250mA A/S Compressor Anti-Vibration Mount Air Receiver Drain Valve “O” Ring Sensing Element Cover “O” Ring Desiccator Bed Filter Adaptor Compressor Filter *3 CIRCUIT REF SV1, SV2, SV3 F1 MANUFACTURER (PT. NO) MICROPLASTICS (011032 FB 12N) - DRALLIM PART NO. 1225450 AVA LTD (AVM191) 1500862 VALVESTOCK (33) 4300020 DOWTY 200-021-7770 DOWTY 200-112-4490 GAST (B344A) 6520650 3956002 NOTES The following items can be obtained through BT Central Stores:*1 Kit Repair 10A Item code 072077 *2 Element Humidity Sensing Item code 310945 *3 Filter Compressor 1A Item Code 072490 DOCUMENT ISSUE ISSUE 01 02 03 04 05 06 DATE 21 July 2000 02 July 2001 22 October 2001 10 January 2003 26 August 2009 62 RFD/DCR DCR T4942 DCR T4975 DCR T5195 DCR T6329