Chrysler LLC Construction Standards 12/17/04 SECTION 15410 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes plumbing fixtures and trim, fittings, and accessories, appliances, appurtenances, equipment, and supports associated with plumbing fixtures. B. Related Sections include the following: 1. Division 15 Section "Basic Mechanical Materials and Methods." 1.2 DEFINITIONS A. Accessory: Device that adds effectiveness, convenience, or improved appearance to a fixture but is not essential to its operation. B. Appliance: Device or machine designed and intended to perform a specific function. C. Appurtenance: Device or assembly designed to perform some useful function when attached to or used with a fixture. D. Fitting: Fitting installed on or attached to a fixture to control the flow of water into or out of the fixture. E. Fixture: Installed receptor connected to the water distribution system that receives and makes available potable water and discharges the used liquid or liquid-borne wastes directly or indirectly into the drainage system. The term "Fixture" means the actual receptor, except when used in a general application where terms "Fixture" and "Plumbing Fixture" include associated trim, fittings, accessories, appliances, appurtenances, support, and equipment. F. Roughing-In: Installation of piping and support for the fixture prior to the actual installation of the fixture. G. Support: Device normally concealed in building construction, for supporting and securing plumbing fixtures to walls and structural members. Supports for urinals, lavatories, and sinks are made in types suitable for fixture construction and the mounting required. Categories of supports are: 1. Carrier: Floor-mounted support for wall-mounted water closet, and support fixed to wall construction for wall-hung fixture. 2. Chair Carrier: Support for wall-hung fixture, having steel pipe uprights that transfer weight to the floor. 3. Reinforcement: Steel plate built into wall construction, for securing fixture to wall. 4. Trim: Hardware and miscellaneous parts, specific to a fixture and normally supplied with it as may be required to complete fixture assembly and installation. 1.3 1.4 SUBMITTALS A. Product data for each type of plumbing fixture specified, including fixture and trim, fittings, accessories, appliances, appurtenances, equipment, supports, construction details, dimensions of components, and finishes. B. Wiring diagrams for field-installed wiring of electrically operated units. QUALITY ASSURANCE PLUMBING FIXTURES 15410 - 1 of 11 Chrysler LLC Construction Standards 12/17/04 A. Energy Policy Act Requirements: Comply with requirements of Public Law 102-486 “Energy Policy Act,” regarding water flow rate and water consumption of plumbing fixtures. B. Listing and Labeling: Provide electrically operated fixtures specified in this Section that are listed and labeled. 1. The terms "listed" and "labeled" shall be as defined in the National Electrical Code, Article 100. 2. Listing and Labeling Agency Qualifications: A "Nationally Recognized Testing Laboratory" (NRTL) as defined in OSHA Regulation 1910.7. C. Design Concept: The drawings indicate types of plumbing fixtures and are based on the specific descriptions, manufacturers, models, and numbers indicated. Plumbing fixtures having equal performance characteristics by other manufacturers may be considered provided that deviations in dimensions, operation, color or finish, or other characteristics are minor and do not change the design concept or intended performance as judged by the Architect. Burden of proof for equality of plumbing fixtures is on the proposer. 1.5 DELIVERY, STORAGE, AND HANDLING A. Deliver plumbing fixtures in manufacturer's protective packing, crating, and covering. B. Store plumbing fixtures on elevated platforms in a dry location. PART 2 - PRODUCTS 2.1 PLUMBING FIXTURE STANDARDS A. 2.2 Comply with applicable standards below and other requirements specified. 1. Electric Water Coolers: ARI 1010 and UL 399. 2. Emergency Equipment: ANSI Z358.1. 3. Enameled, Cast-Iron Fixtures: ASME A112.19.1M. 4. National Sanitation Foundation Construction: NSF 2. 5. Porcelain-Enameled Fixtures: ASME A112.19.4M. 6. Stainless-Steel Fixtures: ASME A112.19.3M. 7. Vitreous-China Fixtures: ASME A112.19.2M. 8. Water-Closet, Flush Valve, Tank Trim: ASME A112.19.5. LAVATORY/SINK FAUCET STANDARDS A. Comply with ASME A112.18.1M and other requirements specified for lavatory, sink, and similartype-fixture faucet fittings. Include hot- and cold-water indicators; 2.0-gpm maximum flow rate; and polished, chrome-plated finish; except where otherwise indicated. Coordinate faucet inlets with supplies and fixture holes and outlet with spout and fixture receptor. 1. Faucet Hose: ASTM D 3901. 2. Hose-Connection Vacuum Breakers: ASSE 1011. 3. Hose-Coupling Threads: ASME B1.20.7. 4. Integral, Atmospheric Vacuum Breakers: ASSE 1001. 5. Pipe Threads: ASME B1.20.1. PLUMBING FIXTURES 15410 - 2 of 11 Chrysler LLC Construction Standards 12/17/04 2.3 SHOWER FAUCET STANDARDS A. 2.4 Comply with ASME A112.18.1M and other requirements specified for bathtub and shower faucet fittings. Include hot- and cold-water indicators; 2.5-gpm maximum flow rate; and polished, chrome-plated finish; except where otherwise indicated. Coordinate faucet inlets with supplies and outlet with diverter valve; and shower head, arm, and flange. MISCELLANEOUS FITTING STANDARDS A. 2.5 Comply with ASME A112.18.1M and other requirements specified for fittings, other than faucets. Include polished, chrome-plated finish, except where otherwise indicated. Coordinate fittings with other components and connectors. 1. Brass and Copper, Supplies and Tubular Brass: ASME A112.18.1M. 2. Fixed Flow Restrictors: ASSE 1034. MISCELLANEOUS COMPONENT STANDARDS A. 2.6 Comply with applicable standards below and other requirements specified for components for plumbing fixtures, equipment, and appliances. 1. Floor Drains: ASME A112.21.1M. 2. Hose-Coupling Threads: ASME B1.20.7. 3. Pipe Threads: ASME B1.20.1. 4. Supply and Drain Insulation Kits: CABO A117.1. 5. Supports: ASME A112.6.1M. FITTINGS A. Fittings for Plumbing Fixtures: Refer to plumbing fixture specifications in this Section for materials for supplies, supply stops, supply risers, traps, and other fittings. B. Fittings for Equipment Specified in Other Sections: Fittings include the following: 1. Supply Inlets: Brass pipe or copper tube, size required for final connection. 2. Supply Stops: Chrome-plated brass, angle or straight; compression, loose key type; same size as supply inlet and with outlet matching supply riser. 3. Supply Risers: 3/8-inch NPS rigid brass tube with 1/4-inch NPS straight, knob-end tailpiece. Use chrome-plated tube for exposed applications. 4. Traps: Tubular brass with 0.045-inch wall thickness, slip-joint inlet, cleanout, wall flange, escutcheons, and size to match equipment. Use chrome-plated tube for exposed applications. 5. Indirect Waste: Tubular brass, 0.045-inch wall thickness, and size to match equipment. 2.7 MANUFACTURERS A. Manufacturers: Unless otherwise directed by the Owner, products in each category, by one of the following listed for that category: 1. Water Closets: a. American Standard, Inc. b. Crane Plumbing/Fiat Products. c. Eljer; A Household International Co. d. Kohler Co. 2. Urinals: a. American Standard, Inc. b. Crane Plumbing/Fiat Products. c. Eljer; A Household International Co. d. Kohler Co. 3. Lavatories: a. American Standard, Inc. PLUMBING FIXTURES 15410 - 3 of 11 Chrysler LLC Construction Standards 12/17/04 4. 5. 6. 7. 8. 9. 10. 11. 12. b. Crane Plumbing/Fiat Products. c. Eljer; A Household International Co. d. Kohler Co. Sinks: a. American Standard, Inc. b. Crane Plumbing/Fiat Products. c. Eljer; A Household International Co. d. Elkay Manufacturing Co. e. Just Manufacturing Co. f. Kohler Co. Wash Fountain: a. Bradley Corp. b. Intersan Manufacturing Co. c. Acorn Engineering Co. Terrazzo Shower Receptor: a. Aqua Glass Corp. b. Fiat Products, Inc. c. Florestone Products Co. d. Precast Terrazzo Products, Inc. e. Stern-Williams Co., Inc. Terrazzo Mop-Service Basin: a. Fiat Products, Inc. b. Floretone Products Co. c. Mustee d. Precast Terrazzo Products, Inc. e. Stern-Williams Co., Inc. Emergency Shower and Eyewash: a. Bradley Corp. b. Encon Safety Products Co. c. Guardian Equipment. d. Haws Drinking Faucet Co. e. Murdock, Inc. f. Speakman Co. g. Western Emergency Equipment Water Coolers: a. EBCO Manufacturing Co. b. Elkay Manufacturing Co. c. Halsey Taylor; A Household International Co. d. Haws Drinking Faucet Co. e. Sunroc Corp. Toilet Seats: a. Bemis Mfg. Co. b. Beneke Div.; Sanderson Plumbing Products, Inc. c. Church Seat Co. d. Kohler Co. e. Olsonite Corp. f. Sperzel Industries, Inc. Flushometers: a. Cambridge Brass Div.; EMCO Products; Masco Corp. b. Coyne & Delany Co. c. Sloan Valve Co. d. Watrous Flush Valve Co.; Polaris Industries. e. Zurn Industries, Inc.; Flush Valve Operations. Commercial Cast-Brass and Cast-Brass Underbody Faucets: a. American Standard, Inc. b. Brass Craft Subsidiary; Masco Corp. c. Briggs Div.; Briggs Industries, Inc. PLUMBING FIXTURES 15410 - 4 of 11 Chrysler LLC Construction Standards 12/17/04 13. 14. 2.8 d. Central Brass Manufacturing Co. e. Chicago Faucet Co. f. Crane Plumbing/Fiat Products g. Delta Faucet Co.; Div. of Masco Corp. h. Eljer; A Household International Co. i. Elkay Manufacturing Co. j. Kohler Co. k. Moen Group; Stanadyne Corp. l. Royal Brass Mfg. Co. m. Speakman Co. n. T & S Brass and Bronze Works, Inc. Miscellaneous Fittings (Except Faucets): a. Aquaflo Corp. b. Beaton & Corbin Mfg. Co. c. Brass Craft Subsidiary; Masco Co. d. Central Brass Manufacturing Co. e. Chicago Faucet Co. f. Crane Plumbing/Fiat Products. g. Eljer; A Household International Co. h. Kohler Co. i. McGuire Manufacturing Co., Inc. j. Price Pfister, Inc. k. Royal Brass Mfg. Co. l. T & S Brass and Bronze Works, Inc. Supports: a. Ancon, Inc. b. Josam Co. c. Smith (Jay R.) Mfg. Co. d. Wade Div.; Tyler Pipe. e. Zurn Industries, Inc.; Hydromechanics Div. PLUMBING FIXTURES, GENERAL A. Water Closets: 1. WC-1: Wall hung back outlet vitreous china siphon jet water closet with elongated bowl, 1-1/2 inch top spud, 2-5/8 inch passageway and 1.6 gallon flush. Fixture: Kohler Kingston K-4430-ET. Fixture Color: White. Flush Valve: Sloan Royal Optima 8111-LH-MC, Battery powered, sensor operated low consumption, less handle, with metal cover, batteries, and manual over-ride button. Seat: Bemis 1655-SS/C black solid plastic open front. Carrier: Smith commercial grade adjusted for 15" bowl height. 2. WC-2: ADA compliant wall hung back outlet vitreous china siphon jet water closet with elongated bowl, 1-1/2 inch top spud, 2-5/8 inch passageway and 1.6 gallon flush. Fixture: Kohler Kingston K-4430-ET. Fixture Color: White. Flush Valve: Sloan Royal Optima 8111-LH-MC, Battery powered, sensor operated low consumption, less handle, with metal cover, batteries, and manual over-ride button. Seat: Bemis 1655-SS/C black solid plastic open front. Carrier: Smith commercial grade adjusted for ADA bowl height B. Urinals: 1. UR-1: Wall mount vitreous china siphon jet urinal with 3/4" top inlet spud, 2" outlet spud, extended high lip type, flushing rim, removable strainer, wall hanger, bolt caps, and 1 gallon flush. PLUMBING FIXTURES 15410 - 5 of 11 Chrysler LLC Construction Standards 12/17/04 Fixture: Fixture Color: Flush Valve: Strainer: Carrier: Kohler Freshman K-4989-T. White. Sloan Royal Optima 8186-1.0-LH-MC, Battery powered, sensor operated low 1.0 gpf consumption, less handle, with metal cover, batteries, and manual over-ride button. Kohler K-9183 stainless steel beehive. Smith commercial grade adjusted for 24" lip height. C. Lavatories: 1. L-1: Countertop mount white vitreous china lavatory with 4" on center faucet openings and self rimming. Fixture: American Standard Aqualun. Faucet: Reliant. Drain: Kohler K-13885 polished chrome perforated strainer and 1-1/4" offset tailpiece. Trap: 1-1/4”x1-1/2" 17 ga. cast brass trap and tubular wall bend, with cleanout plug. Supplies & Stops: Chicago Faucet No. 1006 with loose key. Carrier: Smith floor mounted concealed arm adjusted for 34" height. 2. L-2: Countertop mount white vitreous china lavatory with 4" on center faucet openings and self rimming; mounting to be ADA compliant. Fixture: American Standard Aqualun. Faucet: Reliant. Drain: Kohler K-13885 polished chrome perforated strainer and 1-1/4" offset tailpiece. Trap: 1-1/4”x1-1/2" 17 ga. cast brass trap and tubular wall bend, with cleanout plug. Supplies & Stops: Chicago Faucet No. 1006 with loose key. Carrier: Smith floor mounted concealed arm adjusted for 34" height. 3. L-3: Wall mount white vitreous china lavatory drilled for concealed arm carrier with 4" on center faucet openings. Fixture: American Standard. Faucet: Reliant. Drain: Kohler K-13885 polished chrome perforated strainer and 1-1/4" offset tailpiece. Trap: 1-1/4”"x1-1/2" 17 ga. cast brass trap and tubular wall bend, with cleanout plug. Supplies & Stops: Chicago Faucet No. 1006 with loose key. Carrier: Smith floor mounted concealed arm adjusted for 34" height. D. Sinks: 1. SK-1: Wall mounted 14 ga. type 304 (18-8) stainless steel single compartment sink with 1-3/4 inch Radius vertical and horizontal coved corners, 1-1/2 inch rolled rims, full-length backsplash, satin finish, undercoated underside, 2 faucet openings 8" on center. Fixture: Elkay EWS-2520-W6-C, 25”X19-1/2” overall with 22”x16”x101/2” deep compartment. Wall Hanger: Including stainless steel support brackets. Faucet: Elkay LK-393-BH-6, chrome plated with 6” wrist blade handles, 9” gooseneck spout and vandal-proof anti-hose aerator. Drain: Elkay LK-18-B stainless steel 3” grid drain fitting with 1-1/2” O.D. tailpiece. Trap: 1-1/2"x1-1/2" 17 ga. cast brass trap and tubular wall bend, with cleanout plug. Supplies & Stops: Chicago Faucet No. 993 w/ 1/2” riser, length as necessary. 2. SK-2: Counter mounted 18 ga. type 302 stainless steel single compartment sink with 13/4 inch Radius vertical and horizontal coved corners, 1-1/2 inch rolled rims, full-length backsplash, satin finish, undercoated underside, 2 faucet openings 8" on center. PLUMBING FIXTURES 15410 - 6 of 11 Chrysler LLC Construction Standards 12/17/04 Elkay BLR15 12”X9-3/4”, 6-1/2” deep compartment. Elkay LK-393-BH-6, chrome plated with 6” wrist blade handles, 9” gooseneck spout and vandal-proof anti-hose aerator. Drain: Elkay LK-18-B stainless steel 3” grid drain fitting with 1-1/2” O.D. tailpiece. Trap: 1-1/2"x1-1/2" 17 ga. cast brass trap and tubular wall bend, with cleanout plug. Supplies & Stops: Chicago Faucet No. 993 w/ 1/2” riser, length as necessary. Fixture: Faucet: E. Wash Fountains: 1. WF-1: Floor mounted, stainless steel, circular, 54-inch diameter, 54” high, vandal resistant, with soap dispenser system. Provide stainless steel pipe enclosure where supplies are from above. Fixture: Bradley Sentry Model 20084 Number of Stations: 4 Mounting Support: Manufacture’s standard. Faucet: Infrared sensor-actuated thermostatic mixing valve with check valves, strainers, flow restrictors, solenoid valves, and transformer. Drain: Stainless steel grid drain with 2-inch NPS tailpiece. Trap: 2” cast brass trap with slip-joint inlet, and cleanout plug. Vented trap where required. Supplies & Stops: 1-inch copper tubing with ball valves. 2. WF-2: Floor mounted, stainless steel, semi-circular, 54-inch diameter, 54” high, vandal resistant, with soap dispenser system. Fixture: Bradley Sentry Model 2004. Number of Stations: 4 Mounting Support: Manufacture’s standard. Faucet: Infrared sensor-actuated thermostatic mixing valve with check valves, strainers, flow restrictors, solenoid valves, and transformer. Drain: Stainless steel grid drain with 2-inch NPS tailpiece. Trap: 3. F. 2” cast brass trap with slip-joint inlet, cleanout plug, pipe nipple to wall, and wall flange. Supplies & Stops: 1-inch copper tubing with ball valves. WF-3: Wall mounted Terron Wash Fountain, 3 station wash fountain, 80 inches long by 21 inches deep, complete with soap dispenser system. Fixture: Bradley 3- Station Model SS-3/IR/WH97 Number of Stations: 3 Mounting Support: Manufacture’s standard. Faucet: Infrared sensor-actuated thermostatic mixing valve with check valves, strainers, flow restrictors, solenoid valves, and transformer. Drain: Stainless steel grid drain with 2-inch NPS tailpiece. Trap: 2” cast brass trap with slip-joint inlet, and cleanout plug. Vented trap where required. Supplies & Stops: 1-inch copper tubing with ball valves. Service Sinks: 1. SS-1: - Wall mounted enameled cast iron service sink, 24” x 20”, with stainless steel rim guard, plain back, wall hanger supports, and black under-surface. Fixture: Kohler Bannon K-6719. Faucet: Chicago Faucet No. 897 chrome plated with vacuum breaker, 3/4” hose threaded spout, pail hook, wall support, loose key stops, and lever handles. Drain: Kohler K-6673, 3" trap with strainer, cleanout plug and floorplate. PLUMBING FIXTURES 15410 - 7 of 11 Chrysler LLC Construction Standards 12/17/04 2.9 G. Electric Water Coolers: 1. EWC-1: Floor mounted water cooler with stainless steel basin, self-closing top-mounted push button, abrasion-resistant bubbler, removable front panel, and 1-1/4" tailpiece, rated for 8.9 GPH at 80 degree inlet water, 90 degree ambient and 50 degree leaving water, 260 watts maximum, 120/60/1. Color to be gray beige. Fixture: Elkay LPTE-8-C. Refrigerant: HFC-134a. Trap: 1-1/4" x 1-1/4" 17 ga. cast brass trap. Stop: Chicago Faucet No. 1004. H. Mop-Service Basin: 1. MB-1: 24” x 24” x 12” high, one piece ground and polished pre-cast terrazzo, with 2” Shoulders, stainless steel caps on all sides, 3” stainless steel drain with flat-type 16 Ga. grid strainer, heavy gauge stainless steel wall guards and wall mounted faucet. Fixture: American Standard. Faucet: Chicago Faucet No. 897 chrome plated with vacuum breaker, 3/4” hose threaded spout, pail hook, wall support, loose key stops, and lever handles. Drain Body: Stainless steel cast integral, caulked lead connection not less 1" deep to a 3" pipe. Accessories: 30 inch long x 5/8” flexible hose and stainless steel hose bracket. I. Showers: 1. SH-1: 36” x 36” x 6” high, one piece ground and polished pre-cast terrazzo shower base receptor with integral threshold, 1” high shoulders, 1” tiling flange Receptor: Fiat 36 MFT. Receptor Color: Black and white marble chips in white portland cement. Drain: Stainless steel cast integral body with 2” connection, removable stainless steel strainer plate. Fittings: Pressure balanced shower valve with ceramic valving, spring check stops, adjustable temperature limit, stop and volume control, chrome plated lever handle operated. Brass stationary showerhead with spray adjustment, flow rate meeting ANSI A112.18.1 Standard, supply pipe and stainless steel escutcheon. Valve: Speakman SM-1426-SCS. Shower Head: Speakman S-2252 AF. Shower Arm: Speakman S-2520, 5-1/2” chrome plated shower arm. J. Emergency Eyewash/Face Wash Fountains and Showers: 1. EEWS-1: Floor mounted combination eyewash and shower with 10” ABS safety green plastic deluge shower head, rigid stainless steel pull rod with a spring return chrome plated brass shower valve, 30 GPM flow control; 1-1/4” hot dipped galvanized standard with 9” diameter floor flange, cast air gap/ supply fitting, and self adhesive high visibility stripes in Safety Green and bright yellow; safety green ABS eyewash receptor with twin anti-surge eyewash heads, dust covers, stainless steel push flag operating a stay open chrome plated brass ball valve; universal emergency sign; safety green sign designating universal pictorial of eyewash and shower; automatic water pressure compensating device; eyewash strainer. Fixture: Haws 8226. Shower Head: Haws 8129. Sign: Haws SP178. Flow Control: Haws SP38. Trap: Haws SP95, chrome plated 1-1/4” x 1-1/2”. PLUMBING FIXTURE SUPPORTS PLUMBING FIXTURES 15410 - 8 of 11 Chrysler LLC Construction Standards 12/17/04 A. Supports: ASME A112.6.1M, categories and types as required for wall-hanging fixtures specified, and wall reinforcement. B. Support categories are: 1. Carriers: Supports for wall-hanging urinals and lavatories supported from wall construction. 2. Chair Carriers: Supports with steel pipe uprights for wall-hanging fixtures. Urinal chair carriers shall have bearing plates. C. Reinforcement: 1/4-inch by 6-inch steel plates attached to studs, in wall construction, to secure floor-mounted and special fixtures to wall. D. Support Types: Provide support of category specified, of type having features required to match fixture. E. Provide supports specified as part of fixture description, in lieu of category and type requirements above. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine roughing-in for potable cold water and hot water supplies and soil, waste, and vent piping systems to verify actual locations of piping connections prior to installing fixtures. B. Examine walls, floors, and cabinets for suitable conditions where fixtures are to be installed. C. Do not proceed until unsatisfactory conditions have been corrected. 3.2 APPLICATION A. Install plumbing fixtures and specified components, in accordance with designations and locations indicated on Drawings. B. Install supports for plumbing fixtures in accordance with categories indicated, and of type required: 1. Carriers for following fixtures: a. Wall-hanging fixtures supported from wall construction. 2. Chair carriers for the following fixtures: a. Wall-hanging urinals. b. Wall-hanging water closets. c. Wall-hanging lavatories. 3.3 INSTALLATION OF PLUMBING FIXTURES A. Install plumbing fixtures level and plumb, in accordance with fixture manufacturers' written installation instructions, roughing-in drawings, and referenced standards. B. Install wall-hanging, back-outlet urinals with gasket seals. C. Fasten wall-hanging plumbing fixtures securely to supports attached to building substrate when supports are specified, and to building wall construction where no support is indicated. D. Fasten wall-mounted fittings to reinforcement built into walls. E. Secure supplies behind wall or within wall pipe space, providing rigid installation. PLUMBING FIXTURES 15410 - 9 of 11 Chrysler LLC Construction Standards 12/17/04 F. Install stop valve in an accessible location in each water supply to each fixture. G. Install trap on fixture outlet except for fixtures having integral trap. H. Install escutcheons at each wall, floor, and ceiling penetration in exposed finished locations and within cabinets and millwork. Use deep pattern escutcheons where required to conceal protruding pipe fittings. Exposed traps, piping and escutcheons to be chrome plated brass. Cover exposed water closet bolts with bolt covers. I. Install each fixture with trap easily removable for servicing and cleaning. Install fixture stops in readily accessible location for servicing. J. Provide unions at water connections to electric water coolers. K. Seal fixtures to walls, floors, and counters using a sanitary-type, one-part, mildew-resistant, sealant in accordance with sealing requirements specified in Division 7 Section "Joint Sealers." Match sealant color to fixture color. L. Install toilet seats on water closets. M. Fasten wall-hanging plumbing fixtures securely to supports attached to building substrate when supports are specified, and to building wall construction where no support is indicated. N. Fasten counter-mounting plumbing fixtures to casework. Provide sealant. O. Secure supplies to supports or substrate within pipe space behind fixture. P. Set shower receptors and mop basins in leveling bed of cement grout. Q. Install individual stop valve in each water supply to fixture. Use gate or globe valve where specific stop valve is not specified. R. Exception: Omit stop valves on supplies to emergency equipment, except when permitted by authorities having jurisdiction. When permitted, install valve chained and locked in OPEN position. S. Install faucet, flow-control fittings with specified flow rates and patterns in faucet spouts when faucets are not available with required rates and patterns. Include adapters when required. T. Install shower, flow-control fittings with specified maximum flow rates in shower arms. 3.4 CONNECTIONS A. Piping installation requirements are specified in other sections of Division 15. The Drawings indicate general arrangement of piping, fittings, and specialties. The following are specific connection requirements: B. Install piping connections between plumbing fixtures and piping systems and plumbing equipment specified in other sections of Division 15. C. Install piping connections indicated between appliances and equipment specified in other sections, direct connected to plumbing piping systems. D. Rough-in schedule: FIXTURE Lavatory or Sink PLUMBING FIXTURES HOT 1/2” COLD 1/2” WASTE 1-1/2” VENT 1-1/2” 15410 - 10 of 11 Chrysler LLC Construction Standards 12/17/04 Water Closet with Flush Valve Urinals Service Sinks Showers Mop Basins Wash Fountains Electric Water Coolers E. 3.5 3/4” 1/2” 3/4” 1” - 1” 3/4” 3/4” 1/2” 3/4” 1” 1/2” 4” 2” 3” 2” 3” 2” 1-1/4” 2” 1-1/2” 1-1/2” 1-1/2” 1-1/2” 1-1/2” 1-1/4” Supply and Waste Connections to Equipment Specified in Other Sections: Connect equipment with supply inlets, supply stops, supply risers, and traps specified in this Section. Use fitting sizes required to match connected equipment, unless otherwise noted. Connect fittings to plumbing piping. FIELD QUALITY CONTROL A. Inspect each installed fixture for damage. Replace damaged fixtures and components. B. Test fixtures to demonstrate proper operation upon completion of installation and after units are water pressurized. Replace malfunctioning fixtures and components, then retest. Repeat procedure until all units operate properly. 3.6 ADJUSTING AND CLEANING A. Operate and adjust faucets and controls. Replace damaged and malfunctioning fixtures, fittings, and controls. B. Adjust water pressure at faucets, and flushometers having controls, to provide proper flow and stream. C. Replace washers of leaking and dripping faucets and stops. D. Clean fixtures, fittings, and spout and drain strainers with manufacturers' recommended cleaning methods and materials. 3.7 PROTECTION A. Provide protective covering for installed fixtures and fittings. B. Do not allow use of fixtures for temporary facilities, except when approved in writing by the Owner. END OF SECTION PLUMBING FIXTURES 15410 - 11 of 11