{Instruction to Consultants: The Master Specification must only be considered to be general guidelines as it is not prepared for a Specific Project. If the items described in the Master
Specification do not match the items actually going to be used in a Specific Project, then the
Consultant must add new text or modify the existing text so that the final Specification is fully coordinated and consistent with the Contract Drawings. The Master Specification must not be considered complete. Additions and deletions necessary to make it Project specific are required from the Consultant. Items that are not part of the scope of the Specific Project must be deleted.
The Consultant must add to and/or delete paragraphs, items, etc. to the Master Specification
Section as required by the scope and nature of the Specific Project. The general format and general statements of the various Sections must remain unchanged. The Consultant must modify and finalize the footer to identify the Specific Project as to name of Project, Project number, and issued for/issue date.}
PART 1 GENERAL
1.01 SUMMARY
A. This Section includes the following conventional plumbing fixtures and related components:
1. Faucets for lavatories, showers, and sinks
2. Laminar-flow faucet-spout outlets
3. Flushometers
4. Toilet seats
5. Protective shielding guards
6. Fixture supports
7. Interceptors
8. Shower receptors
9. Dishwasher air-gap fittings
10. Disposers
11. Hot-water dispensers
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-1 PLUMBING FIXTURES
12. Water closets
13. Urinals
14. Lavatories
15. Commercial sinks
16. Wash fountains
17. Bathtubs
18. Individual showers
19. Group showers
20. Kitchen sinks
21. Service sinks
22. Service basins
B. Related Sections include the following:
1. Division 2 Section "Water Distribution" for exterior plumbing fixtures and hydrants.
2. Division 10 Section "Toilet and Bath Accessories."
3. Division 15 Section "Emergency Plumbing Fixtures."
4. Division 15 Section "Drinking Fountains and Water Coolers."
5. Division 15 Section "Plumbing Specialties" for backflow preventers, floor drains, and specialty fixtures not included in this Section.
6. Division 15 Section "Water Filtration Equipment" for water filters
1.02 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-2 PLUMBING FIXTURES
1.03 DEFINITIONS
A. ABS: Acrylonitrile-butadiene-styrene plastic.
B. Accessible Fixture: Plumbing fixture that can be approached, entered, and used by people with disabilities.
C. Cast Polymer: Cast-filled-polymer-plastic material. This material includes cultured-marble and solid-surface materials.
D. Cultured Marble: Cast-filled-polymer-plastic material with surface coating.
E. Fitting: Device that controls the flow of water into or out of the plumbing fixture. Fittings specified in this Section include supplies and stops, faucets and spouts, shower heads and tub spouts, drains and tailpieces, and traps and waste pipes. Piping and general-duty valves are included where indicated.
F. FRP: Fiberglass-reinforced plastic.
G. PMMA: Polymethyl methacrylate (acrylic) plastic.
H. PVC: Polyvinyl chloride plastic.
I. Solid Surface: Nonporous, homogeneous, cast-polymer-plastic material with heat-, impact-, scratch-, and stain-resistance qualities.
1.04 SUBMITTALS
A. Product Data: For each type of plumbing fixture indicated, include selected fixture and trim, fittings, accessories, appliances, appurtenances, equipment, and supports. Indicate materials and finishes, dimensions, construction details, and flow-control rates.
B. Leadership in Energy and Environmental Design (LEED) and Chicago
Department of Aviation Sustainable Airport Manual (SAM) Submittal:
1. Product Data for LEED Credit WE [ 2 ] [ 3.1
] [ 3.2
] [ 2 and 3.1
] [ 2,
3.1, and 3.2
]: Documentation indicating flow and water consumption requirements.
2. Product Data for SAM Credit [ 3.1
] [ 3.1, and 3.2
]:
Documentation indicating flow and water consumption requirements.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-3 PLUMBING FIXTURES
C. Shop Drawings: Diagram power, signal, and control wiring.
D. Operation and Maintenance Data: For plumbing fixtures to include in emergency, operation, and maintenance manuals.
E. Warranty: Special warranty specified in this Section.
1.05 QUALITY ASSURANCE
A. Source Limitations: Obtain plumbing fixtures, faucets, and other components of each category through one source from a single manufacturer.
1. Exception: If fixtures, faucets, or other components are not available from a single manufacturer, obtain similar products from other manufacturers specified for that category.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to
The City of Chicago Building Code, and marked for intended use.
C. Regulatory Requirements: Comply with requirements in ICC A117.1,
"Accessible and Usable Buildings and Facilities"; Public Law 90-480,
"Architectural Barriers Act"; and Public Law 101-336, "Americans with
Disabilities Act"; for plumbing fixtures for people with disabilities.
D. Regulatory Requirements: Comply with requirements in Public
Law 102-486, "Energy Policy Act," about water flow and consumption rates for plumbing fixtures.
E. NSF Standard: Comply with NSF 61, "Drinking Water System
Components--Health Effects," for fixture materials that will be in contact with potable water.
F. Select combinations of fixtures and trim, faucets, fittings, and other components that are compatible.
G. Comply with the following applicable standards and other requirements specified for plumbing fixtures:
1. Enameled, Cast-Iron Fixtures: ASME A112.19.1M.
2. Plastic Lavatories: ANSI Z124.3.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
3. Plastic Laundry Trays: ANSI Z124.6.
15410-4 PLUMBING FIXTURES
4. Plastic Mop-Service Basins: ANSI Z124.6.
5. Plastic Shower Enclosures: ANSI Z124.2.
6. Plastic Sinks: ANSI Z124.6.
7. Plastic Urinal Fixtures: ANSI Z124.9.
8. Porcelain-Enameled, Formed-Steel Fixtures:
ASME A112.19.4M.
9. Slip-Resistant Bathing Surfaces: ASTM F 462.
10. Solid-Surface-Material Lavatories and Sinks: ANSI/ICPA SS-1.
11. Stainless-Steel Commercial, Handwash Sinks: NSF 2 construction.
12. Stainless-Steel Residential Sinks: ASME A112.19.3.
13. Vitreous-China Fixtures: ASME A112.19.2M.
14. Water-Closet, Flush Valve, Tank Trim: ASME A112.19.5.
15. Water-Closet, Flushometer Tank Trim: ASSE 1037.
16. Whirlpool Bathtub Fittings: ASME A112.19.8M.
H. Comply with the following applicable standards and other requirements specified for lavatory and sink faucets:
1. Backflow Protection Devices for Faucets with Side Spray:
ASME A112.18.3M.
2. Backflow Protection Devices for Faucets with Hose-Thread
Outlet: ASME A112.18.3M.
3. Diverter Valves for Faucets with Hose Spray: ASSE 1025.
4. Faucets: ASME A112.18.1.
5. Hose-Connection Vacuum Breakers: ASSE 1011.
6. Hose-Coupling Threads: ASME B1.20.7.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
7. Integral, Atmospheric Vacuum Breakers: ASSE 1001.
15410-5 PLUMBING FIXTURES
I.
8. NSF Potable-Water Materials: NSF 61.
9. Pipe Threads: ASME B1.20.1.
10. Sensor-Actuated Faucets and Electrical Devices: UL 1951.
11. Supply Fittings: ASME A112.18.1.
12. Brass Waste Fittings: ASME A112.18.2.
Comply with the following applicable standards and other requirements specified for shower faucets:
1. Backflow Protection Devices for Hand-Held Showers:
ASME A112.18.3M.
2. Combination, Pressure-Equalizing and Thermostatic-Control
Antiscald Faucets: ASSE 1016.
3. Faucets: ASME A112.18.1.
4. Hand-Held Showers: ASSE 1014.
5. High-Temperature-Limit Controls for Thermal-Shock-Preventing
Devices: ASTM F 445.
6. Hose-Coupling Threads: ASME B1.20.7.
7. Manual-Control Antiscald Faucets: ASTM F 444.
8. Pipe Threads: ASME B1.20.1.
9. Pressure-Equalizing-Control Antiscald Faucets: ASTM F 444 and ASSE 1016.
10. Sensor-Actuated Faucets and Electrical Devices: UL 1951.
11. Thermostatic-Control Antiscald Faucets: ASTM F 444 and
ASSE 1016.
J. Comply with the following applicable standards and other requirements specified for miscellaneous fittings:
1. Atmospheric Vacuum Breakers: ASSE 1001.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-6 PLUMBING FIXTURES
2. Brass and Copper Supplies: ASME A112.18.1.
3. Dishwasher Air-Gap Fittings: ASSE 1021.
4. Manual-Operation Flushometers: ASSE 1037.
5. Plastic Tubular Fittings: ASTM F 409.
6. Brass Waste Fittings: ASME A112.18.2.
7. Sensor-Operation Flushometers: ASSE 1037 and UL 1951.
K. Comply with the following applicable standards and other requirements specified for miscellaneous components:
1. Disposers: ASSE 1008 and UL 430.
2. Dishwasher Air-Gap Fittings: ASSE 1021.
3. Flexible Water Connectors: ASME A112.18.6.
4. Floor Drains: ASME A112.6.3.
5. Grab Bars: ASTM F 446.
6. Hose-Coupling Threads: ASME B1.20.7.
7. Off-Floor Fixture Supports: ASME A112.6.1M.
8. Pipe Threads: ASME B1.20.1.
9. Plastic Shower Receptors: ANSI Z124.2.
10. Plastic Toilet Seats: ANSI Z124.5.
PART 2
11. Supply and Drain Protective Shielding Guards: ICC A117.1.
PRODUCTS
2.01 LAVATORY FAUCETS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following:
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
1. American Standard Companies, Inc.
15410-7 PLUMBING FIXTURES
2. Bradley Corporation.
3. Chicago Faucets.
4. Delta Faucet Company.
5. Eljer.
6. Elkay Manufacturing Co.
7. Grohe America, Inc.
8. Just Manufacturing Company.
9. Kohler Co.
10. Moen, Inc.
11. Royal Brass Mfg. Co.
12. Sayco; a Briggs Plumbing Products, Inc. Company.
13. Speakman Company.
14. T & S Brass and Bronze Works, Inc.
15. Zurn Plumbing Products Group; Commercial Brass Operation.
B. Description: Refer to schedule on Drawings. Include hot- and coldwater indicators; coordinate faucet inlets with supplies and fixture holes; coordinate outlet with spout and fixture receptor.
1. Drain: Grid.
2. Tempering Device: Thermostatic Pressure balance
2.02 SHOWER FAUCETS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following. Select from list below for pressure-balance faucets:
1. American Standard Companies, Inc.
2. Chicago Faucets.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-8 PLUMBING FIXTURES
3. Delta Faucet Company.
4. Eljer.
5. Gerber Plumbing Fixtures LLC.
6. Kohler Co.
7. Leonard Valve Company.
8. Moen, Inc.
9. Powers; a Watts Industries Co.
10. Royal Brass Mfg. Co.
11. Sayco; a Briggs Plumbing Products, Inc. Company.
12. Speakman Company.
13. Sterling Plumbing Group, Inc.
14. Symmons Industries, Inc.
15. T & S Brass and Bronze Works, Inc.
16. Zurn Plumbing Products Group; Aqua Spec Commercial Faucet
Operation.
17. Zurn Plumbing Products Group; Wilkins Operation.
18. Lawler Manufacturing Co., Inc.
B. Description: Refer to schedule on Drawings. Include hot- and coldwater indicators; check stops; and shower head, arm, and flange.
Coordinate faucet inlets with supplies and outlet with diverter valve.
1. Maximum Flow Rate: 2.0 gpm (7.6 L/min.) or less , unless otherwise indicated.
2. Diverter Valve: [ Not required ] [ Integral with mixing valve ]
[ Not integral with mixing valve ].
3. Mounting: [ Exposed ] [ Concealed ].
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-9 PLUMBING FIXTURES
4. Backflow Protection Device for Hand-Held Shower: [ Required ]
[ Not required ].
5. Antiscald Device: [ Integral with mixing valve ] [ Separate unit ]
[ Not required ].
6. Check Stops: Check-valve type, integral with or attached to body; on hot- and cold-water supply connections.
7. Supply Connections: [ NPS 1/2 (DN 15) ] [ NPS 1/2 (DN 15) , union] [Sweat]
2.03 SINK FAUCETS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following. Select from list below for commercial, solid-brass faucets:
1. American Standard Companies, Inc.
2. Bradley Corporation.
3. Broadway Collection.
4. Chicago Faucets.
5. Delta Faucet Company.
6. Eljer.
7. Elkay Manufacturing Co.
8. Grohe America, Inc.
9. Just Manufacturing Company.
10. Kohler Co.
11. Moen, Inc.
12. Royal Brass Mfg. Co.
13. Sayco; a Briggs Plumbing Products, Inc. Company.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-10 PLUMBING FIXTURES
14. Speakman Company.
15. T & S Brass and Bronze Works, Inc.
16. Zurn Plumbing Products Group; Commercial Brass Operation.
B. Description: Refer to schedule on Drawings. Include hot- and coldwater indicators; coordinate faucet inlets with supplies and fixture holes; coordinate outlet with spout and fixture receptor.
1. Maximum Flow Rate: 1.8 gpm (6.8 L/min.) or less , unless otherwise indicated. For metering faucets, 0.2 gallons per cycle.
2. Backflow Protection Device for Hose Outlet: [ Required ] [ Not required ].
3. Backflow Protection Device for Side Spray: [ Required ] [ Not required ].
4. Mounting: [ Deck ] [ Back/wall ], [ exposed ] [ concealed ].
5. Vacuum Breaker: [ Required ] [ Not required ].
2.04 LAMINAR-FLOW FAUCET-SPOUT OUTLETS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following:
1. Chronomite Laboratories, Inc.
2. NEOPERL, Inc.
B. Description: Chrome-plated-brass faucet-spout outlet that produces non-aerating, laminar stream. Include male or female thread that mates with faucet outlet for attachment to faucets where indicated and flow-rate range that includes flow of faucet.
2.05 FLUSHOMETERS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following. Select from list below for diaphragm or piston flushometers:
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-11 PLUMBING FIXTURES
1. Coyne & Delany Co.
2. Delta Faucet Company.
3. Hydrotek International, Inc.
4. Sloan Valve Company.
5. TOTO USA, Inc.
6. Zurn Plumbing Products Group; Commercial Brass Operation.
B. Description: Refer to schedule on Drawings.
1. Internal Design: Diaphragm or piston operation.
2. Style: Exposed Concealed.
2.06 TOILET SEATS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following. Select from list below for residential and lightcommercial toilet seats, standard and heavy-duty, commercial toilet seats:
1. Bemis Manufacturing Company.
2. Centoco Manufacturing Corp.
3. Church Seats.
4. Kohler Co.
5. Olsonite Corp.
6. Pressalit A/S.
7. Sanderson Plumbing Products, Inc.; Beneke Div.
8. Sperzel.
B. Description: Toilet seat for water-closet-type fixture.
1. Material: Molded, solid plastic[ with antimicrobial agent ].
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-12 PLUMBING FIXTURES
2. Configuration: [ Closed ] [ Open ] front [ with ] [ without ] cover.
3. Size: [ Elongated ] [ Regular ].
4. Class: Standard commercial Heavy-duty commercial.
5. Color: White.
2.07 PROTECTIVE SHIELDING GUARDS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Engineered Brass Co.
2. Insul-Tect Products Co.; a Subsidiary of MVG Molded Products.
3. McGuire Manufacturing Co., Inc.
4. Plumberex Specialty Products Inc.
5. TCI Products.
6. TRUEBRO, Inc.
7. Zurn Plumbing Products Group; Tubular Brass Plumbing
Products Operation.
B. Description: Manufactured plastic wraps for covering plumbing fixture hot- and cold-water supplies and trap and drain piping. Comply with
Americans with Disabilities Act (ADA) requirements.
2.08 FIXTURE SUPPORTS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Josam Company.
2. MIFAB Manufacturing Inc.
3. Smith, Jay R. Mfg. Co.
4. Tyler Pipe; Wade Div.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
5. Watts Drainage Products Inc.; a div. of Watts Industries, Inc.
15410-13 PLUMBING FIXTURES
6. Zurn Plumbing Products Group; Specification Drainage
Operation.
B. Water-Closet Supports:
1. Description: Combination carrier designed for [ accessible ]
[ standard ] mounting height of wall-mounting, water-closet-type fixture. Include single or double, vertical or horizontal, hub-andspigot or hubless waste fitting as required for piping arrangement; faceplates; couplings with gaskets; feet; and fixture bolts and hardware matching fixture. Include additional extension coupling, faceplate, and feet for installation in wide pipe space.
C. Urinal Supports:
1. Description: Type [I, urinal carrier with fixture support plates and coupling with seal and fixture bolts and hardware matching fixture] [II, urinal carrier with hanger and bearing plates] for wallmounting, urinal-type fixture. Include steel uprights with feet.
2. Accessible-Fixture Support: Include rectangular steel uprights.
D. Lavatory Supports:
1. Description: Type II, lavatory carrier with concealed arms and tie rod III, lavatory carrier with hanger plate and tie rod for wallmounting, lavatory-type fixture. Include steel uprights with feet.
2. Accessible-Fixture Support: Include rectangular steel uprights.
E. Sink Supports:
1. Description: Type I, sink carrier with exposed arms and tie rods, sink carrier with hanger plate, bearing studs, and tie rod for sink-type fixture. Include steel uprights with feet.
2.09 INTERCEPTORS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Josam Company.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-14 PLUMBING FIXTURES
2. MIFAB Manufacturing Inc.
3. Smith, Jay R. Mfg. Co.
4. Tyler Pipe; Wade Div.
5. Watts Drainage Products Inc.; a div. of Watts Industries, Inc.
6. Zurn Plumbing Products Group; Specification Drainage
Operation.
B. Hair Interceptors:
1. Material: [ Brass ] [ or ] [ stainless-steel ] body.
2. Pipe Connections: [ NPS 1-1/4 (DN 32) ] [ NPS 1-1/2 (DN 40) ].
C. Sediment Interceptors:
1. Description: Manufactured unit with removable screens or strainer and removable cover; designed to trap and retain waste material. a. Material: [Cast-iron or steel body with acid-resistant lining and coating] [or] [carbon-steel body with acidresistant lining and coating] [stainless-steel]. b. Pipe Connections: [ NPS 1-1/2 (DN 40) ] [ NPS 2 (DN 50) ]
2.10 SHOWER RECEPTORS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or as otherwise specified by
Architect.
2.11 DISHWASHER AIR-GAP FITTINGS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. B & K Industries, Inc.
2. Brass Craft Mfg. Co.; a Subsidiary of Masco Corporation.
3. Brasstech Inc.; Newport Brass Div.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-15 PLUMBING FIXTURES
4. Dearborn Brass; a div. of Moen, Inc.
5. Geberit Manufacturing, Inc.
6. JB Products; a Federal Process Corporation Company.
7. Sioux Chief Manufacturing Company, Inc.
8. Watts Brass & Tubular; a division of Watts Regulator Co.
B. Description: Fitting suitable for use with domestic dishwashers and for deck mounting; with plastic body, chrome-plated brass cover; and capacity of at least 5 gpm (0.32 L/s) ; and inlet pressure of at least 5 psig (35 kPa) at a temperature of at least 140 deg F (60 deg C) .
Include 5/8-inch (16-mm-) ID inlet and 7/8-inch (22-mm-) ID outlet hose connections.
C. Hoses: Rubber and suitable for temperature of at least 140 deg F (60 deg C) .
1. Inlet Hose: 5/8-inch (16-mm) ID and 48 inches (1219 mm) long.
2. Outlet Hose: 7/8-inch (22-mm) ID and 48 inches (1219 mm) long
2.12 DISPOSERS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following. Select from list below for batch-feed disposers and continuous-feed disposers:
1. American Standard Companies, Inc.
2. Anaheim Manufacturing, Inc.; a Subsidiary of Western
Industries, Inc.
3. In-Sink-Erator; a div. of Emerson Electric Co.
4. KitchenAid.
5. Maytag Co.
B. Description: Continuous-feed household, food-waste disposer.
Include reset button; wall switch; corrosion-resistant chamber with jamresistant, cutlery- or stainless-steel grinder or shredder; NPS 1-1/2
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-16 PLUMBING FIXTURES
(DN 40) outlet; quick-mounting, stainless-steel sink flange; antisplash guard; and combination cover/stopper.
1. Type: Continuous-feed household.
2. Motor: 115-V ac, 1725 rpm, [ 1/3 ] [ 1/2 ] [ 3/4 ] [ 1 ] hp with overload protection.
2.13 WATER CLOSETS [ Select any or all of the following or modify accordingly ]
A. Water Closets – Wall Mounted
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Crane Plumbing, L.L.C./Fiat Products b. American Standard. c. Toto. d. American Standard Companies, Inc. e. Briggs Plumbing Products, Inc. f. Crane Plumbing, L.L.C./Fiat Products. g. Kohler Co. h. TOTO USA, Inc. i. Caroma USA, Inc.
2. Description [ Accessible, wall ] [ Wall ]-mounting, back-outlet, vitreous-china fixture designed for flushometer valve operation.
3. Style: Flushometer valve. a. Bowl Type: Elongated with siphon-jet design. b. Design Consumption: 1.28 gal/flush (4.8 L/flush) or less . c. Color: White.
4. Style: Dual flush valve. a. Bowl Type: Elongated with siphon-jet design.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-17 PLUMBING FIXTURES
b. Design Consumption: 1.6/1.1 gal/flush (6.0/4.2 L/flush) or less . c. Color: White.
5. Fixture Support: Water-closet support combination carrier.
B. Water Closets – Floor Mounted
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. American Standard Companies, Inc. b. Briggs Plumbing Products, Inc. c. Crane Plumbing, L.L.C./Fiat Products. d. Kohler Co. e. Mansfield Plumbing Products, Inc. f. TOTO USA, Inc.
2. Description: [Accessible, floor] [Floor-mounting] , floor-outlet, vitreous-china fixture designed for flushometer valve operation.
3. Style: Flushometer valve. a. Bowl Type: [Elongated] [Round] front with [siphon-jet]
[reverse-trap siphon-vortex] [siphon-wash] washdown design. Include bolt caps matching fixture. b. Height: Refer to schedule on Drawings. c. Design Consumption: 1.28 gal/flush (4.8 L/flush) or less . d. Color: [ White ] < Insert color >.
4. Style: Dual flush valve. a. Bowl Type: [Elongated] [Round] front with [siphon-jet]
[reverse-trap siphon-vortex] [siphon-wash] washdown design. Include bolt caps matching fixture.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-18 PLUMBING FIXTURES
b. Design Consumption: 1.6/1.1 gal/flush (6.0/4.2 L/flush) or less . c. Color: [ White ] < Insert color >.
2.14 URINALS
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following:
1. American Standard Companies, Inc.
2. Briggs Plumbing Products, Inc.
3. Crane Plumbing, L.L.C./Fiat Products.
4. Kohler Co.
5. Mansfield Plumbing Products, Inc.
6. TOTO USA, Inc.
B. Description: Refer to schedule on Drawings.
1. Design Consumption: 0.8 gal/flush (3.0 L/flush) or less.
2. Color: White.
3. Supply Spud Size: NPS 3/4 (DN 20 NPS 1-1/4 (DN 32) .
4. Outlet Size: NPS 1-1/2 (DN 40) NPS 2 (DN 50) NPS 3 (DN 80) .
5. Fixture Support: Urinal chair carrier.
2.15 LAVATORIES
A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following:
1. Select from list below for vitreous-china lavatories: a. American Standard Companies, Inc. b. Briggs Plumbing Products, Inc.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-19 PLUMBING FIXTURES
c. Crane Plumbing, L.L.C./Fiat Products. d. Gerber Plumbing Fixtures LLC. e. Kohler Co. f. Mansfield Plumbing Products, Inc. g. Sterling Plumbing Group, Inc. h. TOTO USA, Inc.
2. Select from list below for solid-surface lavatories: a. American Standard Companies, Inc. b. Avonite, Inc. c. Bradley Corporation. d. DuPont, Corian Products. e. Formica Corporation. f. Franke Consumer Products, Inc., Kitchen Systems Div. g. Lippert Corporation. h. Rynone Manufacturing Corp. i. Swan Corporation (The). j. Wilsonart International.
3. [Add list of manufacturers for enameled, cast-iron, or stainless steel, as needed]
4. Description: Refer to schedule on Drawings. a. [If basis-of-design product manufacturer's name, product name or designation, and description above are explicit enough, requirements in subparagraphs and associated subparagraphs below may be reduced or omitted]. b. Color: White c. Faucet: Lavatory for separate drain for each bowl. d. Faucet Hole Location: Countertop e. Supplies: NPS 3/8 (DN 10) chrome-plated copper with stops. f. Drain: Grid ] [ Grid with offset waste .
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-20 PLUMBING FIXTURES
g. Drain Piping: NPS 1-1/4 by NPS 1-1/2 (DN 32 by DN 40) chrome-plated, cast-brass P-trap; NPS 1-1/2 (DN 40) ,
[0.032 inch – (0.8-mm)] [0.045-inch (1.1-mm-)] thick tubular brass waste to wall; and wall escutcheon. h. [Retain subparagraph above or below] . i. Protective Shielding Guard(s) j. Fixture Support: Lavatory
2.16 COMMERCIAL SINKS
A. Commercial Sinks:
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Advance Tabco. b. Elkay Manufacturing Co. c. Just Manufacturing Company.
2. Description: Refer to schedule on Drawings. a. Compartment:
1) Drain: Grid with NPS 1-1/2 (DN 40) tailpiece and twist drain. b. Faucet(s): Sink. c. Supplies: NPS 1/2 (DN 15 chrome-plated copper with stops or shutoff valves. d. Drain Piping: NPS 1-1/2 (DN 40 chrome-plated, castbrass P-trap; copper pipe waste to wall; and wall escutcheon(s).
2.17 WASH FOUNTAINS
A. Wash Fountains:
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Acorn Engineering Company.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-21 PLUMBING FIXTURES
b. Bradley Corporation. c. Intersan Manufacturing Company.
2. Description: Refer to schedule on Drawings. a. Arrangement: Wash-up stations facing central spray heads. b. Receptor Color or Finish: [ Not applicable ] < Insert if required >. c. Control: [ Collective ] [ Individual ], [ push-button ] [ footpedal ] [ sensor ] actuation with thermostatic valve and check stops or field-installed check valves. d. Mounting: [Floor] [Floor mounting with bracket for attaching to wall]. e. Faucet(s): [Not applicable] [Sensor-actuated mixing valve with check stops]. f. Supplies: [Not applicable] [NPS 1/2 (DN 15) copper tubing with ball, gate, or globe valves]. g. Drain : [Grid with NPS 1-1/2 (DN 40) tailpiece]. [Grid with NPS2 (DN 50) tailpiece]. h. Drain/Trap Piping: [NPS 1-1/2 (DN 40) P-trap, waste to wall and wall flange]. [Trap Fitting: NPS2 (DN50) trap with waste and vent connections].
2.18 INDIVIDUAL SHOWERS [ Select any or all of the following or modify accordingly ]
A. Individual Showers – Single Unit Enclosure, <Insert drawing designation>:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
3. Basis-of-Design Product: Subject to compliance with requirements, provide [ the product indicated on Drawings ]
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-22 PLUMBING FIXTURES
< Insert manufacturer's name; product name or designation > or a comparable product by one of the following: a. Acryline USA, Inc. b. Aker Plastics Co., Inc. c. Aqua Bath Company, Inc. d. Aquatic Industries, Inc. e. Clarion Bathware. f. Crane Plumbing, L.L.C./Fiat Products. g. Florestone Products Co., Inc. h. Jacuzzi, Inc. i. Kohler Co. j. LASCO Bathware. k. Praxis Industries, Inc.; Aquarius Products. l. Sterling Plumbing Group, Inc. m. Swan Corporation (The). n. < Insert manufacturer's name.
>
4. Description: [ Accessible, ] [ FRP ] [ PMMA ] shower enclosure with slip-resistant bathing surface and shower rod with curtain. a. Size: [ 36 by 34 inches (915 by 865 mm) ] [ 42 by 36 inches (1065 by 915 mm) ] [ 43 by 39 inches (1090 by
990 mm) ] [ 48 by 34 inches (1220 by 865 mm) ] [ 52 by
36 inches (1320 by 915 mm) ] [ 60 by 36 inches (1525 by 915 mm) ] [ 72 by 36 inches (1830 by 915 mm) ]
< Insert dimensions >. b. Surround: One piece[ or sealed, multiple piece ]. c. Surround: One piece. d. Color: [ White ] < Insert color >. e. Drain Location: [ Left side ] [ Center ] [ Right side ]. f. Accessibility Options: Include grab bar and bench. g. Faucet: Shower < Insert designation >. h. Drain: Grid, NPS 2 (DN 50) .
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-23 PLUMBING FIXTURES
B. Individual Showers
– Built-in-Place, <Insert drawing designation>:
1. Description: Components for built-up shower. a. Shower Faucet: < Insert designation >. b. Receptor: [ Not required ] < Insert shower receptor designation >.
C. Individual Showers – Prefabricated, <Insert drawing designation>:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
3. Basis-of-Design Product: Subject to compliance with requirements, provide [ the product indicated on Drawings ]
< Insert manufacturer's name; product name or designation > or a comparable product by one of the following: a. Crane Plumbing, L.L.C./Fiat Products. b. Mustee, E. L. & Sons, Inc. c. Stern-Williams Co., Inc. d. Swan Corporation (The). e. < Insert manufacturer's name.
>
4. Description: Factory-fabricated, [ accessible, ]cabinet type with faucet and receptor. a. Size: [ 30 by 30 inches (760 by 760 mm) ] [ 32 by 32 inches (815 by 815 mm) ] [ 36 by 36 inches (915 by 915 mm) ] [ 36 by 39 inches (915 by 990 mm) ] [ 45 by 39 inches (1145 by 990 mm) ] < Insert dimensions >. b. Material: [ Steel ] [ Composite ] [ Plastic ], [ front ] [ corner ]
[ front and rear ] access. c. Color: [ Not applicable ] < Insert color >. d. Accessibility Options: Grab bar and bench. e. Faucet: Shower < Insert designation >.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-24 PLUMBING FIXTURES
f. Supplies: NPS 1/2 (DN 15) copper tubing[ with ball, gate, or globe valves ]. g. Drain: Grid, NPS 2 (DN 50) .
2.19 GROUP SHOWERS [ Select any or all of the following or modify accordingly ]
A. Group Showers
– Column-Mounted Fixture, <Insert drawing designation>:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
3. Basis-of-Design Product: Subject to compliance with requirements, provide [ the product indicated on Drawings ]
< Insert manufacturer's name; product name or designation > or a comparable product by one of the following: a. Acorn Engineering Company. b. Bradley Corporation. c. < Insert manufacturer's name.
>
4. Description: Stainless-steel column fixture with [ two ] [ three ]
[ four ] [ five ] [ six ] individual showers. a. Height to Shower Heads: [ 66 inches (1675 mm) ] [ 72 inches (1830 mm) ] < Insert dimension >. b. Control: [ Thermostatic ] [ Pressure-balance ] valve with individual hot- and cold-water mixing valve operation. c. Retain and edit subparagraph above or first subparagraph below. There are many possible combinations of options. d. Control: Thermostatic valve with individual temperedwater supply and [ push-button ] [ sensor ] operation. e. Flow Control: 2 gpm (7.6 L/min.) or less for each shower head.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-25 PLUMBING FIXTURES
f. Liquid Soap Dispenser: For each shower. g. Mounting: Floor flange. h. Supplies: [ NPS 3/4 (DN 20) ] [ NPS 1 (DN 25) ] copper tubing with ball, gate, or globe valves from [ bottom ]
[ top ]. i. j.
Shroud: [ Not required ] [ Stainless steel of size to cover supplies and vent piping ].
Drain Fitting: [ NPS 3 (DN 80) ] [ NPS 4 (DN 100) ] outlet with NPS 2 (DN 50) vent, integral with base of column. k. Vent Piping: [ Not required ] [ NPS 2 (DN 50) to ceiling ].
B. Group Showers – Wall-Mounted with Enclosure:
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Acorn Engineering Company. b. Bradley Corporation.
2. Description: Wall-mounting fixture with stainless-steel surface enclosure with [ two ] [ three ] individual showers. a. Control: Thermostatic valve with individual temperedwater supply and [ push-button ] [ sensor ] operation. b. Flow Control: 2 gpm (7.6 L/min.) or less for each shower head. c. Liquid Soap Dispenser: For each shower. d. Mounting: Wall bracket. e. Supplies: NPS 3/4 (DN 20) copper tubing with ball, gate, or globe valves.
2.20 KITCHEN SINKS
A. Kitchen Sinks :
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-26 PLUMBING FIXTURES
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Retain one of five lists below. b. Select from list below for enameled, cast-iron kitchen sinks. c. Select from list below for stainless-steel kitchen sinks. d. Dayton Products, Inc. e. Elkay Manufacturing Co. f. Franke Consumer Products, Inc., Kitchen Systems Div. g. Just Manufacturing Company. h. Kohler Co. i. Moen, Inc. j. Sterling Plumbing Group, Inc.
2. Description: Refer to schedule on Drawings. a. Drain: 3-1/2-inch (89-mm) crumb cup or as otherwise indicated on drawings. b. Sink Faucet: Refer to schedule on Drawings. c. Supplies: NPS 1/2 (DN 15) chrome-plated copper with stops. d. Drain Piping: NPS 1-1/2 (DN 40) chrome-plated, castbrass P-trap; 0.045-inch (1.1-mm-) thick tubular brass waste to wall; continuous waste ; and wall escutcheon(s). e. Retain subparagraph above or first subparagraph below. f. Disposer: [ Not required ] < Insert designation >. g. Dishwasher Air-Gap Fitting: [ Required ] [ Not required ].
B. Bar Sinks :
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Dayton Products, Inc. b. Elkay Manufacturing Co.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-27 PLUMBING FIXTURES
c. Franke Consumer Products, Inc.; Kitchen Systems Div. d. Just Manufacturing Company. e. Kohler Co. f. Moen, Inc. g. Sterling Plumbing Group, Inc.
2. Description: Refer to schedule on Drawings. a. Supplies: NPS 1/2 (DN 15) chrome-plated copper with stops. b. Drain: grid or as otherwise indicated on drawings. c. Drain Piping: NPS 1-1/2 (DN 40) chrome-plated, castbrass P-trap; 0.045-inch (1.1-mm-) thick tubular brass waste to wall; and wall escutcheon. d. Retain subparagraph above or first subparagraph below. e. Protective Shielding Guard(s): at ADA locations.
2.21 SERVICE SINKS
A. Service Sinks :
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. American Standard Companies, Inc. b. Commercial Enameling Company. c. Eljer. d. Kohler Co. e. Select from list below for vitreous-china service sinks. f. Crane Plumbing, L.L.C./Fiat Products. g. Eljer. h. Kohler Co.
2. Description: Trap-standard- and wall-mounting. Refer to schedule on Drawings. a. Faucet: Service/Mop Sink.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-28 PLUMBING FIXTURES
b. Drain: Grid with NPS 3 (DN 80) outlet. c. Trap Standard: NPS 3 (DN 80) enameled, cast iron with cleanout and floor flange. d. Fixture Support: Sink .
2.22 SERVICE BASINS
A. Service Basins :
PART 3
1. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated on Drawings or a comparable product by one of the following: a. Acorn Engineering Company. b. Crane Plumbing, L.L.C./Fiat Products. c. Florestone Products Co., Inc. d. Precast Terrazzo Enterprises, Inc. e. Stern-Williams Co., Inc. f. Select from list below for plastic (cast-polymer) service basins. g. Crane Plumbing, L.L.C./Fiat Products. h. Florestone Products Co., Inc. i. j.
Mustee, E. L. & Sons, Inc.
Swan Corporation (The). k. Zurn Plumbing Products Group; Light Commercial
Operation.
2. Description: Flush-to-wall, floor-mounting, fixture with rim guard. Refer to schedule on Drawings. a. Tiling Flange: [ Not required ] [ On one side ] [ On two sides ] [ On three sides ]. b. Rim Guard: On [ front ] [ all ] top surfaces. c. Faucet: Service/Mop Sink . d. Drain: Grid with NPS 3 (DN 80) outlet.
EXECUTION
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-29 PLUMBING FIXTURES
3.01 EXAMINATION
A. Examine roughing-in of water supply and sanitary drainage and vent piping systems to verify actual locations of piping connections before plumbing fixture installation.
B. Examine cabinets, counters, floors, and walls for suitable conditions where fixtures will be installed.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 INSTALLATION
A. Assemble plumbing fixtures, trim, fittings, and other components according to manufacturers' written instructions.
B. Install off-floor supports, affixed to building substrate, for wall-mounting fixtures.
1. Use carrier supports with waste fitting and seal for back-outlet fixtures.
2. Use carrier supports without waste fitting for fixtures with tubular waste piping.
3. Use chair-type carrier supports with rectangular steel uprights for accessible fixtures.
C. Install back-outlet, wall-mounting fixtures onto waste fitting seals and attach to supports.
D. Install floor-mounting fixtures on closet flanges or other attachments to piping or building substrate.
E. Install wall-mounting fixtures with tubular waste piping attached to supports.
F. Install floor-mounting, back-outlet water closets attached to building floor substrate and wall bracket and onto waste fitting seals.
G. Install counter-mounting fixtures in and attached to casework.
H. Install fixtures level and plumb according to roughing-in drawings.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-30 PLUMBING FIXTURES
I. Install water-supply piping with stop on each supply to each fixture to be connected to water distribution piping. Attach supplies to supports or substrate within pipe spaces behind fixtures. Install stops in locations where they can be easily reached for operation.
1. Exception: Use ball, gate, or globe valves if supply stops are not specified with fixture. Valves are specified in Division 15
Section "Valves."
J. Install trap and tubular waste piping on drain outlet of each fixture to be directly connected to sanitary drainage system.
K. Install tubular waste piping on drain outlet of each fixture to be indirectly connected to drainage system.
L. Install flushometer valves for accessible water closets and urinals with handle mounted on wide side of compartment. Install other actuators in locations that are easy for people with disabilities to reach.
M. Install toilet seats on water closets.
N. Install faucet-spout fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required.
O. Install water-supply flow-control fittings with specified flow rates in fixture supplies at stop valves.
P. Install faucet flow-control fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required.
Q. Install shower flow-control fittings with specified maximum flow rates in shower arms.
R. Install traps on fixture outlets.
1. Exception: Omit trap on fixtures with integral traps.
2. Exception: Omit trap on indirect wastes, unless otherwise indicated.
S. Install disposer in outlet of each sink indicated to have disposer.
Install switch where indicated or in wall adjacent to sink if location is not indicated.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-31 PLUMBING FIXTURES
T. Install dishwasher air-gap fitting at each sink indicated to have air-gap fitting. Install in sink deck . Connect inlet hose to dishwasher and outlet hose to disposer.
U. Install escutcheons at piping wall ceiling penetrations in exposed, finished locations and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding fittings. Escutcheons are specified in Division 15 Section "Escutcheons for Plumbing
Piping."
V. Set service basins in leveling bed of cement grout. Grout is specified in Division 15 Section "Basic Mechanical Materials and Methods."
W. Seal joints between fixtures and walls, floors, and countertops using sanitary-type, one-part, mildew-resistant silicone sealant. Match sealant color to fixture color. Sealants are specified in Division 7
Section "Joint Sealants."
3.03 CONNECTIONS
A. Piping installation requirements are specified in other Division 15
Sections. Drawings indicate general arrangement of piping, fittings, and specialties.
B. Connect fixtures with water supplies, stops, and risers, and with traps, soil, waste, and vent piping. Use size fittings required to match fixtures.
C. Ground equipment according to Division 16 Section "Grounding and
Bonding."
D. Connect wiring according to Division 16 Section "Conductors and
Cables."
3.04 FIELD QUALITY CONTROL
A. Verify that installed plumbing fixtures are categories and types specified for locations where installed.
B. Check that plumbing fixtures are complete with trim, faucets, fittings, and other specified components.
C. Inspect installed plumbing fixtures for damage. Replace damaged fixtures and components.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-32 PLUMBING FIXTURES
D. Test installed fixtures after water systems are pressurized for proper operation. Replace malfunctioning fixtures and components, then retest. Repeat procedure until units operate properly.
E. Install fresh batteries in sensor-operated mechanisms.
3.05 ADJUSTING
A. Operate and adjust faucets and controls. Replace damaged and malfunctioning fixtures, fittings, and controls.
B. Operate and adjust disposers and controls. Replace damaged and malfunctioning units and controls.
C. Adjust water pressure at faucets and flushometer valves to produce proper flow and stream.
D. Replace washers and seals of leaking and dripping faucets and stops.
E. Install fresh batteries in sensor-operated mechanisms.
3.06 CLEANING
A. Clean fixtures, faucets, and other fittings with manufacturers' recommended cleaning methods and materials. Do the following:
1. Remove faucet spouts and strainers, remove sediment and debris, and reinstall strainers and spouts.
2. Remove sediment and debris from drains.
B. After completing installation of exposed, factory-finished fixtures, faucets, and fittings, inspect exposed finishes and repair damaged finishes.
3.07 PROTECTION
A. Provide protective covering for installed fixtures and fittings.
B. Do not allow use of plumbing fixtures for temporary facilities unless approved in writing by Owner.
CHICAGO DEPARTMENT OF AVIATION/
O’HARE MODERNIZATION PROGRAM
MASTER SPECIFICATIONS
VOLUME IIIA
REV. 1, ISSUED 7/30/10
15410-33 PLUMBING FIXTURES