Lutron Stanza Guestrom Light Control System CSI spec(260936 CSI

advertisement
SECTION 260936
MODULAR DIMMING CONTROLS
Lutron Stanza Wireless Guestroom Light Control System
This specification is dated October 1, 2011, and supersedes all previous Lutron Stanza Guestroom Light Control System
specifications.
This section includes editing notes to assist the user in editing the section to suit project requirements. These notes are
included as hidden text, and can be revealed or hidden by one of the following methods:
 Microsoft Word: From the pull-down menus select TOOLS, then OPTIONS. Under the tab labeled VIEW, select or
deselect the HIDDEN TEXT option.
 Corel WordPerfect: From the pull-down menus select VIEW, then select or deselect the HIDDEN TEXT option.
PART 1 - GENERAL
1.1
1.2
SUMMARY
A.
Section Includes:
1. Lighting Control Devices
B.
Related Sections:
1. Section [122000 - Window Treatments:] Window treatments controlled by central dimming
control system.
2. Section [262726 - Wiring Devices]
3. Section [265113 – Interior Lighting Fixtures, Lamps, and Ballasts:] Fluorescent lighting ballasts
controlled by central dimming control system.
4. Section [260923 – Lighting Control Devices:] Occupancy sensors used in conjunction with
central dimming control system.
REFERENCES
A.
American National Standards Institute/Institute of Electrical and Electronic Engineers (ANSI/IEEE) (
and )
1. C62.41-1991 – Recommended Practice for Surge Voltages in Low-Voltage AC Power Circuits.
B.
ASTM International (ASTM) ()
1. D4674 -02a Standard Test Method for Accelerated Testing for Color Stability of Plastics
Exposed to Indoor Fluorescent Lighting and Window-Filtered Daylight.
C.
Canadian Standards Association (CSA) ().
1. CSA C22.2 # 184 Solid-State Lighting Controls
D.
International Electrotechnical Commission ().
1. (IEC) 801-2 Electrostatic Discharge Testing Standard.
2. IEC/EN 60669-2-1 Switches for household and similar fixed electrical installations - electronic
switches.
E.
International Organization for Standardization (ISO)
1. 9001:2000 – Quality Management Systems.
F.
National Electrical Manufacturers Association (NEMA)
1. WD1 (R2005) - General Color Requirements for Wiring Devices.
G.
Norma Official Mexicana (NOM).
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 1
1.
2.
H.
1.3
1.5
1.7
Radio Frequency Light Control System (RFLCS)
1. Modular dimming and switching components.
2. Two-way Radio Frequency controlled wall-mounted dimmers and switches, lamp socket module
dimmers and switches, master controls, and interfaces without the use of a central processor.
SUBMITTALS
A.
Submit under provisions of Section [013300.] [______.]
B.
Specification Conformance Document: Indicate whether the submitted equipment:
1. Meets specification exactly as stated.
2. Meets specification via an alternate means and indicate the specific methodology used.
C.
Shop Drawings; include:
1. Load schedule indicating actual connected load, load type, and control zones.
2. Schematic of system.
D.
Product Data: Catalog cut sheets with performance specifications demonstrating compliance with
specified requirements.
CLOSEOUT SUBMITTALS
A.
1.6
Underwriters Laboratories, Inc. (UL) ():
1. 244A – Solid State Appliance Controls.
2. 1472 (1996) - Solid-State Dimming Controls.
SYSTEM DESCRIPTION
A.
1.4
NOM-001 Electronic Products – Safety Specifications
NOM-003-SCFI Electrical products - Safety Specifications
[Sustainable Design Closeout Documentation (LSC-LEED-DOC)
1. Lighting Control System Manufacturer to provide Enhanced Start-up documentation that details
the start-up procedure being performed including a process to follow, details on tests performed
and an area that documents any test results.]
QUALITY ASSURANCE
A.
Manufacturer: Minimum [10] [__] years experience in manufacture of architectural lighting controls
and Radio Frequency Light Control products.
B.
Manufacturer’s Quality System: Registered to ISO 9001:2000 Quality Standard, including in-house
engineering for product design activities.
C.
Radio Frequency Light Control System (RFLCS):
1. Listed by [CSA] [NOM] [UL] specifically for the required loads. Provide evidence of compliance
upon request.
2. Approval of local radio communications governing agency. Provide evidence of compliance
upon request.
PROJECT CONDITIONS
A.
Do not install equipment until following conditions can be maintained in spaces to receive equipment:
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 2
1.
2.
3.
1.8
Ambient temperature: 0 degrees to 40 degrees C (32 degrees to 104 degrees F).
Relative humidity: Maximum 90 percent, non-condensing.
Light control system must be protected from dust during installation.
WARRANTY
A.
Provide Manufacturer’s Warranty:
1. Standard 2-year warranty, Includes:
a. 100 Percent Replacement Parts for Manufacturer Lighting System Components
b. 100 Percent Manufacturer Labor Coverage to Troubleshoot and Diagnose a Lighting Issue
c. First –Available Onsite or Remote Response Time
d. 24 Hours Per Day, 7 Days Per Week Telephone Technical Support, Excluding
Manufacturer Holidays
e. Remote Diagnostics for Applicable Systems
f.
4-Hours of Remote Programming for Applicable Systems
2.
Enhanced 8-year Silver Level limited parts warranty, Includes:
a. Years 1-2:
1) 100 Percent Replacement Parts for Manufacturer Lighting System Components
2) 100 Percent Manufacturer Labor Coverage to Troubleshoot and Diagnose a Lighting
Issue
3) First-Available Onsite or Remote Response Time
4) Remote Diagnostics for Applicable Systems
5) 4-Hours of Remote Programming for Applicable Systems
b. Years 3-5: 50% Replacement Parts Coverage
c. Years 6-8: 25% Replacement Parts Coverage
d. 24 Hours Per Day, 7 Days Per Week Telephone Technical Support, Excluding
Manufacturer Holidays
3.
Enhanced 8-year Gold Level limited parts warranty, Includes:
a. Years 1-2:
1) 100 Percent Replacement Parts for Manufacturer Lighting System Components
2) 100 Percent Manufacturer Labor Coverage to Troubleshoot and Diagnose a Lighting
Issue
3) 72-Hour Onsite or Remote Response Time
4) Annual Scheduled Preventative Maintenance Visit
5) Remote Diagnostics for Applicable Systems
6) 4-Hours of Remote Programming for Applicable Systems
b. Years 3-5: 50% Replacement Parts Coverage
c. Years 6-8: 25% Replacement Parts Coverage
d. 24 Hours Per Day, 7 Days Per Week Telephone Technical Support, Excluding
Manufacturer Holidays
4.
Enhanced 8-year Platinum Level limited parts warranty, Includes:
a. Years 1-2:
1) 100 Percent Replacement Parts for Manufacturer Lighting System Components
2) 100 Percent Manufacturer Coverage to Troubleshoot and Diagnose a Lighting Issue
3) 24-Hour Onsite or Remote Response Time
4) Annual Scheduled Preventative Maintenance Visit
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 3
b.
c.
d.
B.
5) Remote Diagnostics for Applicable Systems
6) 4-Hours of Remote Programming for Applicable Systems
Years 3-5: 50% Replacement Parts Coverage
Years 6-8: 25% Replacement Parts Coverage
24 Hours Per Day, 7 Days Per Week Telephone Technical Support, Excluding
Manufacturer Holidays
[Provide Manufacturer’s Support and Maintenance Plan for [8] [__] years covering 100 percent parts
and 100 percent labor and additional benefits as described below beginning 2 years after system
startup completion.]
1.
Silver Level Support and Maintenance Plan, Includes:
a. 100 Percent Parts for Manufacturer Lighting System Components
b. 100 Percent Manufacturer Labor Coverage for Troubleshooting and Diagnosis of Lighting
Issues
c. 24 Hours Per Day, 7 Days Per Week Telephone Technical Support, Excluding Manufacturer
Holidays
d. First-Available Onsite or Remote Response Time
d. Remote Diagnostics for Applicable Systems
e. 4-Hours of Remote Programming for Applicable Systems
2.
Gold Level Support and Maintenance Plan, Includes:
a. 100 Percent Parts for Manufacturer Lighting System Components
b.
100 Percent Manufacturer Labor Coverage for Troubleshooting and Diagnosis of Lighting
Issues
c. 24 Hours Per Day, 7 Days Per Week Telephone Technical Support, Excluding Manufacturer
Holidays
d. 72-Hour On-Site or Remote Response Time
e. Annual Scheduled Preventative Maintenance Visit
f. Remote Diagnostics for Applicable Systems
g. 4-Hours Remote Programming for Applicable Systems
h. Includes Service Coverage Upgrade of the Initial 2-year 100 Percent Manufacturer Labor
Coverage to Gold Level Coverage.
3.
Platinum Level Support and Maintenance Plan, Includes:
a. 100 Percent Parts for Manufacturer Lighting System Components
b.
100 Percent Manufacturer Labor Coverage for Troubleshooting and Diagnosis of Lighting
Issues
c. 24 Hours Per Day, 7 Days per Week Telephone Technical Support, excluding Manufacturer
Holidays
d. 24-Hour On-Site or Remote Response Time
e. Annual Scheduled Preventative Maintenance Visit
f. Remote Diagnostics for Applicable Systems
g. 4-Hours Remote Programming for Applicable Systems
h. Includes Service Coverage Upgrade of the Initial 2-Year 100 Percent Manufacturer Labor
Coverage to Platinum Level Coverage.
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 4
1.9
C.
[For ballasts, see section 265113 – Interior Lighting Fixtures, Lamps, and Ballasts: Fluorescent
Electronic Dimming Ballasts.]
D.
[For Sivoia shades, see section 122413 – Roller Window Shades.]
MAINTENANCE MATERIAL SUBMITTALS
A.
Make ordering of new equipment for expansions, replacements, and spare parts available to end
user.
B.
Make new replacement parts available for minimum of ten years from date of manufacture.
PART 2 - PRODUCTS
2.1
2.2
MANUFACTURERS
A.
Acceptable Manufacturer: Lutron Electronics Co., Inc. – System: Lutron Stanza Radio Frequency
Light Control System
B.
[Basis of design product: Lutron Stanza Radio Frequency Light Control System or subject to
compliance and prior approval with specified requirements of this section, one of the following:]
1. Lutron Stanza Radio Frequency Light Control System
2. <Insert manufacturer’s name>
C.
Substitutions: [Not permitted.] [Under provisions of Division 1.]
1. All proposed substitutions (clearly delineated as such) must be submitted in writing for approval
by the design professional a minimum of 10 working days prior to the bid date and must be
made available to all bidders.
2. Proposed substitutes must be accompanied by a review of the specification noting compliance
on a line-by-line basis.
3. Any substitutions provided by the contractor shall be reviewed at the contractor’s expense by
the electrical engineer at a rate of [$200.00] per hour.
4. By using pre-approved substitutions, the contractor accepts responsibility and associated costs
for all required modifications to circuitry, devices, and wiring.
5. Provide complete engineered shop drawings (including power wiring) with deviations for the
original design highlighted in an alternate color to the engineer for review and approval prior to
rough-in.
GENERAL
A.
Provide system that is designed, tested, manufactured, and warranted by a single manufacturer.
B.
Radio Frequency communications to operate within 434 MHz band, free from interference from other
building and system frequencies.
C.
Light Controls: Ten-year operational life while operating continually at any temperature in an ambient
temperature range of 0 degrees C (32 degrees F) to 40 degrees C (104 degrees F) and 90 percent
non-condensing relative humidity.
D.
Designed and tested to withstand electrostatic discharges up to 15,000 V without impairment per IEC
801-2.
E.
Electrolytic capacitors to operate at least 20 degrees C below the component manufacturer's
maximum temperature rating when device is under fully-loaded conditions in 40 degrees C (104
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 5
degrees F) ambient temperature.
2.3
F.
Design and test line voltage devices to withstand line-side surges without impairment to
performance.
1. Power handling devices: Withstand surges without impairment of performance when subjected
to surges of 6,000 volts, 200 amps per ANSI/IEEE C62.41C.
G.
Power failure memory such that if power is interrupted and subsequently returned, lights will
automatically return to same levels (dimmed setting, full on, or off) prior to power interruption within 3
seconds.
1. All programmable information, including system identification codes, addresses, and master
control button programming to be retained in non-volatile memory and to remain intact in the
case of a 10 year power loss to the system.
H.
Color:
1. [Match NEMA WD1, Section 2.] [Custom color to be selected.]
2. Color variation in same product family: Maximum ΔE=1, CIE L*a*b color units.
3. Visible parts: Exhibit ultraviolet color stability when tested with multiple actinic light sources as
defined in ASTM D4674. Provide proof of testing upon request.
I.
Provide faceplates with concealed mounting hardware.
J.
Engrave keypad buttons with appropriate zone or scene engraving descriptions.All text, borders,
logos, and graduations to use graphic process that chemically bonds markings to faceplate or
buttons, resistant to removal by scratching and cleaning.
PERMANENTLY MOUNTED DIMMERS;
A.
Product: Lutron Model: [SZ-6D-color] [SZ-6ND-color]
B.
Description:
1. Provide local control:
a. To override master controls.
b. In the event that communication with other devices in the system is interrupted.
2. Capable of controlling MLV and Incandescent loads without a neutral wire
3. Capable of controlling interfaces to other loads when used with a neutral wire
4. Capable of providing smooth continuous dimming.
5. Operate and control lamps without integrated outlets when used in conjunction with an outlet
approved by UL for dimming.
6. Operate and control dimmable compact fluorescent lamps (CFLs).
C.
Load Handling Thyristors (SCRs and triacs), Field Effect Transistors (FETs), and Isolated Gate
Bipolar Transistors (IGBTs): Manufacturer’s maximum current rating minimum two times control’s
rated operating current.
D.
Capable of withstanding repetitive inrush current of 50 times operating current without impacting
lifetime of dimmer/switch.
E.
Utilize air gap off for permanently-mounted dimmers/switches to disconnect the load from line
supply.
F.
Dimmers to meet following load-specific requirements:
1. Magnetic Low Voltage (MLV) transformer:
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 6
a.
Contain circuitry designed to control and provide a symmetrical AC waveform to input of
magnetic low voltage transformers per UL 1472, Section 5.11.
b. Dimmers using unipolar load current devices (such as FETs or SCRs) to include DC
current protection in the event of a single device failure.
2. Fluorescent electronic dimming ballast: Refer to Section [265113] [______] for dimming ballast
specifications and performance.LAMP SOCKET DIMMERSProduct: Lutron Model: [SZ-1SDWH]Description:
1. Provide local control at lamp socket:
a. To override master controls.
b. In the event that communication with other devices in the system is interrupted.
2. Capable of dimming incandescent, halogen, and dimmable compact fluorescent bulbs
3. Capable of switching non-dimmable compact fluorescent bulbs without swapping device
4. Capable of providing smooth continuous dimming.
5. Operate and control lamps with integrated outlets
6. Operate and control dimmable compact fluorescent lamps (CFLs).
2.5
2.6
2.7
C.
Load Handling Thyristors (SCRs and triacs), Field Effect Transistors (FETs), and Isolated Gate
Bipolar Transistors (IGBTs): Manufacturer’s maximum current rating minimum two times control’s
rated operating current.
D.
Capable of withstanding repetitive inrush current of 50 times operating current without impacting
lifetime of dimmer/switch.
SWITCHES
A.
Product: Lutron Model: [SZ-6ANS-color]
B.
Description:
1. Provide local control:
a. To override master controls.
b. In the event that communication with other devices in the system is interrupted.
2. Capable of controlling incandescent, fluorescent, magnetic low-voltage, electronic low-voltage,
and high intensity discharge loads with a neutral wire
C.
Load Handling Thyristors (SCRs and triacs), Field Effect Transistors (FETs), and Isolated Gate
Bipolar Transistors (IGBTs): Manufacturer’s maximum current rating minimum two times control’s
rated operating current.
D.
Capable of withstanding repetitive inrush current of 50 times operating current without impacting
lifetime of dimmer/switch.
E.
Utilize air gap off to disconnect the load from line supply.
KEYPADS
A.
Product: Lutron Model: [SZ-2B-color] [SZ-3B-color] [SZ-4B-color] [SZ-5B-color] [SZ-3/1B-color]
B.
Functionality:
1. Control any single lighting load or combination of lighting loads, which are part of the RFLCS.
2. LEDs on each button to reflect the true system status.
3. Master control keypad to be field programmable.
CARD SWITCH GUEST ROOM CONTROL
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 7
2.8
2.9
A.
Product: Lutron Model [SZ-CS-CCO]
B.
Functionality:
1. Provide maintained contact closure output when card key is inserted to turn lights on.
2. Turns lights off when card key is removed.
C.
Accept standard size card keys: 54mm x 86 mm x 0.8 mm (2.125 inches x 3.375 inches x 0.03
inches)
D.
Provide flashing backlit slider when card key is not present.
POWER INTERFACES
A.
Product: [PHPM-PA.] [GRX-TVI.] [GRX-PWM] [HP-2.], [HP-4.], [HP-6.]
B.
Electrical:
1. Phase independent of control input.
C.
Diagnostics and Service: Replacing power interface does not require re-programming of system or
devices.
CONTROL INTERFACES
A. Contact Closure Interface; Lutron Model [SZ-IO]
1. The contact closure inputs will accept both momentary and maintained contact closures.
2. The contact closure outputs will provide “dry” closure outputs.
B.
2.10
Serial / Ethernet Interface; Lutron Model [SZ-CI-PRG]
1. The Serial / Ethernet interface must be used to change system programming
2. The Serial / Ethernet interface allows integration of the RFLCS to other room or building
systems
SOURCE QUALITY CONTROL
A.
Perform full-function testing on all completed assemblies at end of line. Statistical sampling is not
acceptable.
PART 3 - EXECUTION
3.1
3.2
INSTALLATION
A.
Install equipment in accordance with manufacturer’s installation instructions.
B.
Provide complete installation of system in accordance with Contract Documents.
C.
Define each dimmer's load type, assign each load to a zone, and set control functions.
D.
Provide equipment at locations and in quantities indicated on Drawings. Provide any additional
equipment required to provide control intent.
STARTUP AND PROGRAMMING
A.
Provide factory-certified field service engineer to a site visit to ensure proper system installation and
operation under following parameters:
1. Qualifications for factory-certified field service engineer:
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 8
2.
a. Minimum experience of 2 years training in the electrical/electronic field.
b. Certified by the equipment manufacturer on the system installed.
Make a visit upon completion of installation of RFLCS control system:
a. Verify connection and location of controls.
b. Verify system operation control by control, zone by zone.
c. Verify proper Radio Frequency communication.
d. Verify proper integration of manufacturers interfacing equipment.
e. Provide programming.
f.
Obtain sign-off on system functions.
g. Train owner on system operation.
END OF SECTION
__________________________________________________________________________________________
Lutron
Modular Dimming Controls
Stanza Radio Frequency Light Control System
10/1/2011
260936 - 9