Republic of Iraq Ministry of Electricity General directorate of electrical energy production – BASRAH. E-mail: gdeep_comm_dept@yahoo.com جمهـوريـة العــراق وزارة الكهـربـــاء المديرية العامة ألنتاج الطاقة الكهربائية في البصرة Power Station: Hartha power station REF NO. 5/2/24/988 S أس الهارثة: المحطـة 988/24/2/5 : رقم الطلب Excitation System For Unit No. 1&4 Item 1 Qty. 2 Unit Set -Supply and installation: Static excitation system with digital automatic voltage regulator for synchronous machine and disassemble of old excitation system . Automatic Voltage Regulator The digital type controller consists of control board, analogue/digital interface board / Tow channel at least. Monitoring LCD Monitor for operation /control/interlock signals/alarm/indication, location in unit control room. Thyristor rectifier Converts AC power from excitation transformer to DC field. 3 phase full bridge type. Withdrawal (tray) type (thyristor elements fitted on removal tray) If ONE thyristor tray( per phase) put out of service should not effect on the system Field breaker On/off field current and interrupt fault current. DC type breaker is used.(2Poles) DC type breaker with discharge resistor (liner type). Rating: 4000A Initial excitation Build up generator voltage to approx. 10KV. DC power source from external system battery set. Field discharge circuit Absorb the energy when opening the field breaker (FCB). DC type FCB: discharge contact and resistor. {0.105Ω} Protection element Fuse to protect thyristor element from over current, with alarm C-R circuit to protect thyristor element from over Voltage. Field ground detector, cooler fan. AVR panel in unit control cubical room Thyristor panel in turbine power house 1st floor (open Area) Location Setting range at Auto. mode ±10% of generator rated voltage Setting range at Min. mode 10% of rated no load field current/voltage to 120% of rated field current/voltage at generator rated load Excitation system for unit No. 1&4 Deliver to: Electric department Provided that the origin of the: Mitsubishi, ABB, Alstom or Westinghouse. Item Qty. Unit Voltage accuracy ±0.5% or less Rating of the one Thyristor bridge Ceiling voltage 1000/750/500 Amps Ambient Condition Temperature:+55C Humidity: 95% PT/CT (burden) 2 3 2 Set PTPT 900V DC Power source PT 18KV/110V, 100VA CT 10000/5A, 100VA ,10P20 Control power: DC 220V Warranty Excitation power: Derived from excitation transformer 600V 3ph AC Initial excitation power: DC 220V external from DC battery set 1200A/10h 12 Months. -Digital AVR maintenance tool. Maintenance tool consist of PC(laptop). and software. Maintenance tool has following useful features. Setting of the control parameters Monitor of the operation . Monitor failure. Event /Signal trace. And all connection and cable. 4 5 - - -Spare part: Spare part 30% from the system -Training: Maintenance training for 7 specialists at least 4 weeks in the origin. -Generator Specification: 250MVA 18KV±5% 8019A, 0.8PF 3ph, 50Hz 3000rpm, 2pole Star connection Excitation Voltage: 440VDC Field Current: 3037A Slip ring Stator winding per phase (at 75ºC) : 0.0023 ohm Rotor winding per phase (at 75ºC) : 0.1050 ohm (Unsaturated) (xd) 198% Negative-sequence reactance (xa) 180% Zero- sequence reactance (xo) 13.0% (xd`) 34.3% (xd``) 25.8% -Excitation transformer available, the excitation transformer having the following specification: 3ph, 3.3MVA Y∆ / yd1 Pr.: 18KV /106A Sec.: 600V / 3180A. -18KV I.P.B From main bus (gen .output) To Excitation transformer are available. -Power cable from Excitation transformer to Thyristor panel to slip ring are available. -Estimated Cost = (4000000) $ USD . NOTE: Provided that the origin of the: Mitsubishi, ABB(Germany or Switzerland ) , Alstom (France) or Westinghouse(USA). المدير التجاري توقيع المستفيد