EC Type Examination Schedule (ATEX)

advertisement
Annex No. 2 to: IECEx ULD 06.0017X
Manufacturer: Detector Electronics Corporation
Electrical apparatus:
Multispectrum IR Flame Detectors models X3301,
X3302 and X33AF
Nomenclature for type X3301 (or X33AF) abcde:
where
a =
Enclosure material:
A = Aluminium
b
Type, and number of threaded locations:
S = Stainless steel
=
4M = 4 Port, Metric M25
4N = 4 Port, ¾” NPT
c =
Outputs:
11 = Relay
13 = Relay & 4-20mA
14 = LON Eagle Quantum Premier
15 = Relay & Pulse
16 = Addressable module (third party type, for Ex d version only)
17 = RS485
19 = POWER LOOP (AUTRONICA ONLY)
21 = Relay Automotive
22 = EQP Automotive
23 = Relay / 4-20mA & HART
d =
Approvals:
A = FM & CSA
B = Brazil
C = CSA
E = ATEX/CE
R = RUSSIA
T = SIL2/FM/CSA/ATEX/CE
U = UKRAINE
V = Vds/ATEX/CE/CNBOP
W = FM/CSA/ATEX/CE
Y = CHINA
e =
Classification:
1 = DIVISION/ZONE Ex d e
2 = DIVISION/ZONE Ex d
Nomenclature for type X3302 abcde:
where:
a =
Enclosure material:
A = Aluminium
b
Type, and number of threaded locations:
S = Stainless steel
=
4M = 4 Port, Metric M25
4N = 4 Port, ¾” NPT
c =
Outputs:
11 = Relay
13 = Relay & 4-20mA
14 = LON Eagle Quantum Premier
15 = Relay & Pulse
16 = Addressable module (third party type, for Ex d version only)
17 = RS485
Certificate: IECEx ULD 06.0017X
Report: 139309-02
This Annex is valid only in combination with certificate IECEx ULD 06.0017X and
may only be reproduced in its entirety and without any change
Annex No. 2 to: IECEx ULD 06.0017X
Manufacturer: Detector Electronics Corporation
Electrical apparatus:
Multispectrum IR Flame Detectors models X3301,
X3302 and X33AF
23 = Relay / 4-20mA & HART
Page 1 of 3
Nomenclature for type X3302 abcde (continued):
d =
Approvals:
E = ATEX/CE
T = SIL2/FM/CSA/ATEX/CE
V = Vds/ATEX/CE/CNBOP
W = FM/CSA/ATEX/CE
e =
Classification:
1 = DIVISION/ZONE Ex d e
2 = DIVISION/ZONE Ex d
Note:
The name and address of the manufacturer shall always be marked on the label.
Temperature range for X3301, X3302 and X33AF.
The relation between ambient temperature and the assigned temperature class is as follows:
For Ex d e:
Ambient temperature range
Temperature class
-50°C to +60°C
T6
-50°C to +75°C
T5
For Ex d:
Ambient temperature range
-55°C to +60°C
-55°C to +75°C
Temperature class
T6
T5
Electrical data
Rated voltage:
Power consumption:
18- 30Vdc
max. 17W
Optional third party addressable module:
Rated voltage:
30Vdc
Rated current:
30mA
Installation instructions
The field wiring connections in the terminal compartment are ATEX certified and accept wiring diameters from 12 AWG to 22 AWG.
The Multispectrum infrared (IR) flame detectors type X3301, X3302 and X33AF shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the terminal
compartment in type of explosion protection flameproof enclosure “d”, or in type of explosion protection increased safety “e” for use
with the terminal compartment in type of explosion protection increased safety “e”. They shall be IP66 rated, suitable for the conditions
of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector types X3301, X3302 and X33AF, must be electrically connected
to earth ground.
For ambient temperatures below –10 C and above +60 C use field wiring suitable for both minimum and maximum ambient
temperature.
Certificate: IECEx ULD 06.0017X
Report: 139309-02
This Annex is valid only in combination with certificate IECEx ULD 06.0017X and
may only be reproduced in its entirety and without any change
Annex No. 2 to: IECEx ULD 06.0017X
Manufacturer: Detector Electronics Corporation
Electrical apparatus:
Multispectrum IR Flame Detectors models X3301,
X3302 and X33AF
Routine tests
Routine tests for dielectric strength according to IEC 60079-7 cl. 7.1 are required for the increased safe ‘e’ terminal compartment
circuits.
Page 2 of 3
Documents:
Description:
Drawing No.:
Rev. Level:
Date:
Drawing, design reference X3301, X3302 and X33AF
“DEMKO”
Enclosure Machined SS
007288-001
P
2010-04-12
007247-002
G
2006-06-06
Enclosure, AL, D.C. (Mach)
008086-XXX
C
2008-07-29
Bulkhead Mach SST Herm Seal
010069-XXX
A
2009-09-17
Bulkhead Mach AL Herm Seal
010068-XXX
A
2009-09-17
Heatsink AL MACH ATEX
010056-001
C
2010-04-12
Window Sapphire
Cover Elect Module
010057-XXX
010055-XXX
C
D
2010-04-12
2010-04-12
Retainer Ring Mach FRGD AL
010206-001
A
2009-08-25
Installation Instructions
95-8527 / 95-8576 /
95-8625
4/10
-
Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with IEC60079-1 clause 5.1.c, all
inspections, repair and/or adjustments to this front window assembly, shall be done by Detector Electronics Corporation only.
The EOL resistor can only be used within the flameproof terminal compartment.
The Multispectrum infrared (IR) flame detector types X3301, X3302 and X33AF are to be installed in places where there is a low risk of
mechanical damage.
Additional information
The Multispectrum infrared (IR) flame detector types X3301, X3302 and X33AF have in addition passed the tests for
Ingress Protection to IP66 in accordance with IEC60529:1991/A1 2001.
Certificate: IECEx ULD 06.0017X
Report: 139309-02
This Annex is valid only in combination with certificate IECEx ULD 06.0017X and
may only be reproduced in its entirety and without any change
Annex No. 2 to: IECEx ULD 06.0017X
Manufacturer: Detector Electronics Corporation
Electrical apparatus:
Multispectrum IR Flame Detectors models X3301,
X3302 and X33AF
Page 3 of 3
Certificate: IECEx ULD 06.0017X
Report: 139309-02
This Annex is valid only in combination with certificate IECEx ULD 06.0017X and
may only be reproduced in its entirety and without any change
Download