ECS – FLORIDA, LLC Geotechnical Construction Materials Environmental Facilities January 26, 2009 Mr. Rich Armstrong St. Joseph’s Women’s Hospital c/o Mr. Chet Emmett HKS, Inc. 1919 McKinney Avenue Dallas, Texas 75201 ECS Job No.: 25-3110 Reference: Report of Subsurface Exploration and Geotechnical Engineering Analysis, St. Joseph’s Women’s Hospital Bed Tower Addition, Florida Dear Mr. Armstrong: As authorized by acceptance of our proposal ECS 24-5826-GP, dated December 2, 2008, ECSFlorida, LLC (ECS) has completed the subsurface exploration and conducted geotechnical engineering analyses for the proposed St. Joseph’s Women’s Hospital Bed Tower Addition, located in Tampa, Florida. Our attached report includes the results of our subsurface exploration program, laboratory testing program, and geotechnical engineering analysis. We understand the project will consist of a 5-story, 115,000 square feet hospital bed tower addition with no allowance for future floors. Maximum column loads for the bed tower are estimated to be 960 kips, with 80 percent of the load from dead load. Allowable differential settlement between the proposed and existing buildings will be 0.5 inch. The planned final ground floor elevation for the hospital is 33.65 feet above mean sea level. This report provides recommendations on soil bearing pressures, foundation settlement estimates, placement and compaction of new fills, drainage, construction procedures, and other factors that may influence design and construction at the site. This geotechnical engineering study includes an evaluation of the subsurface soils and groundwater conditions of the site and general area, as described in the scope of services identified in our proposal. No other considerations or additional issues were investigated, requested or proposed during this evaluation. The conclusions and recommendations presented within this report are based upon a reasonable level of investigation within normal bounds and standards of professional practice for a site in this particular geographic and geologic setting. This report has been prepared to aid in the evaluation of this site and to assist the Owner and Engineer in the implementation of the project. The report scope is limited to the specific project and location described, and the project description represents our understanding of the significant aspects relevant to soil and foundation 2000 Avenue P, Suite 3, West Palm Beach, FL 33404 (561) 840-3667 FAX (561) 840-3668 www.ecslimited.com ECS Carolinas, LLP ECS Florida, LLC ECS Illinois, LLC ECS Mid-Atlantic, LLC ECS Southeast, LLC ECS Texas, LLP St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 Cover Letter January 26, 2009 Page 2 characteristics. Observations, conclusions and recommendations pertaining to geotechnical conditions at the subject site are necessarily limited to conditions observed, and/or materials reviewed at the time this study was undertaken. No warranty, express or implied, is made with regard to the conclusions and recommendations presented within this report. This report is provided for the exclusive use of HKS, Inc, and their successors or assigns. This report is not intended to be used or relied upon in connection with other projects or by other unidentified third parties. The use of this report by any undesignated third party or parties will be at such party's sole risk and ECS disclaims liability for any such third party use or reliance. We appreciate this opportunity to be of service to HKS, Inc, on this project. If you have any questions regarding the information and recommendations contained in the accompanying report, or if we may be of further assistance to you in any way during planning or construction of this project, please contact us. Respectfully, ECS-FLORIDA, LLC Florida Certificate of Authorization No. 26152 Sunil Sundaram Project Manager Anthony J. Fiorillo, P.E. Principal Engineer P.E. 58405 I:\Projects\3000-3999\3100-3199\3110 St. Joseph's Women's Hospital GEO\GEOTECH REPORT.doc TABLE OF CONTENTS PAGE PROJECT OVERVIEW Project Location and Proposed Construction Scope of Work Purposes of Exploration EXPLORATION PROCEDURES Subsurface Exploration Procedures Laboratory Testing Program Particle Size Analysis, Modified Proctor and LBR 1 1 1 2 3 3 4 4 EXPLORATION RESULTS 5 Current Site Conditions Regional Geology Soil Conditions Groundwater Observations 5 5 5 6 ANALYSES AND RECOMMENDATIONS Shallow Foundations Mat Foundations Deep Foundations Floor Slab Design Earthwork Operations Fill Placement Retaining Walls Pavement Considerations General Asphalt (Flexible) Pavements Layer Components Stabilized Subgrade Base Course Surface Course Effects of Groundwater Landscape Drains Construction Traffic Concrete (Rigid) Pavements Construction Considerations Closing APPENDIX 7 7 7 8 9 9 11 12 13 13 14 14 15 15 16 16 16 16 17 18 18 20 St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 1 of 19 PROJECT OVERVIEW Project Location and Proposed Construction The proposed St. Joseph’s Women’s Hospital Bed Tower site is located on the southeast corner of the intersection of Martin Luther King Boulevard and N. MacDill Avenue in Tampa, Florida. We understand the project will consist of a 5-story, 115,000 square feet hospital bed tower addition with no allowance for future floors. Maximum column loads for the bed tower are estimated to be 960 kips, with 85 percent of the load from dead load. Allowable differential settlement between the proposed and existing buildings will be 0.5 inches. The planned final ground floor elevation for the hospital is 33.65 feet above mean sea level. Scope of Work The conclusions and recommendations contained in this report are based on our field subsurface explorations, laboratory testing, and review of available geologic and/or geotechnical data. The recent subsurface exploration program included 5 soil borings, extended to depths of 6 to 75 feet below existing land surface (bls). Pressuremeter testing was performed at various depths in 2 borings using a CPT (Cone Penetration Test) rig. Additionally two (2) CPT borings were performed to depths of 25 to 30 feet in proximity to the pressuremeter tests. Laboratory tests were performed on selected soil samples to identify the soils and to assist in determination of the soil properties. We have also visited the site to conduct a site reconnaissance. The boring locations for the proposed St. Joseph’s Women’s Hospital Bed Tower were selected and located in the field by ECS. Consider the indicated locations and depths to be approximate. Our layout crew located the borings based upon the site plan provided, along with measuring distances and relationships to obvious landmarks. The Boring Location Plan is included in the Appendix. Our investigation was confined to the zone of soil likely to be stressed by the proposed construction. Our work did not address the potential for surface expression of deep geological conditions, such as sinkhole development related to karst activity. This evaluation requires a more extensive range of field services than performed in this study. We will be pleased to conduct an investigation to evaluate the probable effect of the regional geology upon the proposed construction, if you desire. This report presents an evaluation of site conditions on the basis of traditional geotechnical procedures for site characterization. The recovered samples were not examined, either visually or analytically, for chemical composition or environmental hazards. If requested, ECS would be pleased to perform these services. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 2 of 19 Purposes of Exploration The purposes of the exploration were to explore the soil and groundwater conditions at the site and to develop engineering recommendations to guide the Geotechnical design and construction of the current project. We accomplished these purposes by: 1. Drilling borings to explore the subsurface soil and groundwater conditions, 2. Performing laboratory tests on selected representative soil samples from the test borings to evaluate pertinent engineering properties and, 3. Evaluating the field and laboratory test results to develop appropriate engineering recommendations. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 3 of 19 EXPLORATION PROCEDURES Subsurface Exploration Procedures The soil borings were performed with a truck-mounted drill rig utilizing mud rotary drilling methods to advance the boreholes. Drilling fluid was used in this process. Representative soil samples were obtained by means of the split-barrel sampling procedure. The number of blows required to drive the sampler through a 12-inch interval with a 140 pound manual drop safety hammer is termed the Standard Penetration Test (SPT) value, or "N" value, and is indicated for each sample on the boring logs. This value can be used as a quanitative indication of the in-place relative density of non-cohesive soils. In a less reliable way, it also indicates the consistency of cohesive soils. This indication is qualitative, since many factors can significantly affect the standard penetration resistance value and prevent a direct correlation between drill crews, drill rigs, drilling procedures, and hammer-rod-sampler assemblies. A field log of the soils encountered in each boring was maintained by the drill crew. After recovery, each sample was removed from the sampler and visually classified. Representative portions of each sample were then sealed and delivered to ECS’ laboratory for further visual examination and laboratory testing. Pressuremeter testing was also performed, which is used to provide a direct measurement of the relative strength of the soil lying at and below the planned bottom of footing elevations at this site. The pressuremeter is a down borehole, stress volumetric strain device. Because it is performed in-situ, it provides a direct measurement of the soil. The pressuremeter provides two values that are fundamental in evaluating bearing capacity and settlement. First, it develops a modulus of elasticity, commonly referred to as the “pressuremeter modulus”. It also allows us to develop a limit pressure, which gives an indication as to the ultimate strength of the soil. More detailed pressuremeter data collected onsite is included in the Pressuremeter Logs within the Attachments of this report. Cone penetrometer testing (CPT) is performed by advancing a standard friction mantle cone into the soil. The pressure required to advance the cone is measured by a pressure cell attached to the "proving ring" to determine the tip resistance. The tip resistance is referred to as the Qc-value in units of kilograms per square centimeter. The tip resistance is an index of soil strength and density. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 4 of 19 Laboratory Testing Program Representative soil samples were selected and tested in our laboratory to confirm the field classifications and to determine pertinent engineering properties. The laboratory testing program included visual sample classifications, moisture content tests, washed sieve gradation tests, pH, resistivity and organic tests. Data obtained from the laboratory tests are included on the respective boring logs in the Appendix. A member of ECS’ Geotechnical staff classified each soil sample on the basis of texture and plasticity in accordance with the Unified Soil Classification System (USCS). The group symbols for each soil type are indicated in parentheses following the soil descriptions on the boring logs. A brief explanation of the USCS is included with this report. The Geotechnical Engineer grouped the various soil types into the major zones noted on the boring logs. The stratification lines designating the interfaces between earth materials on the boring logs and profiles are approximate; in the field, the transitions may be gradual. Particle Size Analysis, Modified Proctor and LBR Off-site borrow material samples were not evaluated because the general contractor has not chosen a supplier at this time. Please notify us when a borrow pit has been chosen, and ECS will perform these services. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 5 of 19 EXPLORATION RESULTS Current Site Conditions A site visit was conducted by ECS during the drilling operation to observe existing site conditions. The proposed site is currently used as driveway and parking areas. The boring locations were located in the existing asphalt parking lot east of the existing four-story building. Associated landscaped areas and curbing are present within the proposed addition area. Regional Geology The general hydrogeology of Hillsborough County includes the unconfined surficial aquifer of Pleistocene to recent age. This 50 to 150 feet thick sequence of sand and clay overlies the Miocene Hawthorne Formation, which measures approximately 0 to 250 feet in thickness in Hillsborough County. Small quantities of water are pumped from this artesian aquifer. Below the Hawthorn Formation are the Tampa and Suwannee Limestone. The majority of Hillsborough County’s municipal and commercial water supply is pumped from these limestone formations. Within the geological province including this portion of Hillsborough County, the surface of the water table approximately conforms to the ground surface topography with groundwater drainage in a down-slope direction towards the nearest surface water body. Surface streams typically drain in a direction that is in accordance with the regional surface slope. Perturbations in the surface drainage are usually due to man-induced changes in the surface topography. Soil Conditions Subsurface conditions within the project site were evaluated with 5 soil test borings. Borings S-1 through S-3 were drilled to depths of 75 feet below grade in the building areas; A-1 and A-2 were drilled to 6 feet below grade in the parking areas. Additionally 2 Pressuremeter test borings (P-1 and P-2) and 2 Cone Penetration Test borings (C-1 and C-2) were performed to evaluate the strength of the soil. The approximate boring locations are shown on the Boring Location Plan in the Appendix. Ground surface elevations were not available at the time of drilling or submittal of the report. In general, borings performed encountered alternate layers of fine sand (SP), fine sand with silt (SP-SM) and silty fine sand (SM) from the existing grade to a depth of 40 feet below grade, followed by very dense limerock to the termination depth of 75 feet below grade. For details at the individual boring locations, refer to the logs attached in the Appendix. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 6 of 19 Groundwater Observations On the basis of depth to water measurements made in the open boreholes, we estimate that the groundwater level was about 7.5 feet below existing grade at the time of drilling. The groundwater will fluctuate seasonally depending upon local rainfall. The rainy season in Central Florida is normally between June and September. Based upon our site specific field data, our review of the USDA Soils Survey of Hillsborough County, the USGS topographic map of the area, the expected regional hydrogeology and our experience in the area, we estimate the seasonal high groundwater levels could be on the order of 5 feet below the existing grade at the boring locations. Variations in the location of the long-term groundwater table may occur as a result of changes in precipitation, evaporation, surface water runoff, and other factors not immediately apparent at the time of this exploration. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 7 of 19 ANALYSES AND RECOMMENDATIONS Based on the soil conditions encountered at the anticipated foundation elevation, the results of our pressuremeter testing program, and the anticipated maximum loading conditions (960 kips column load), ECS recommends the following three foundation options: Shallow Foundation Mat Foundation Deep Foundation Considering all three foundation alternatives, shallow foundation is the most cost effective option, considering our experience and understanding of the risk tolerances. Detailed discussions of the foundation options are provided below. Shallow Foundations The most economical option is to use shallow foundations to support the five-story structure. The geotechnical analyses of the field data indicate the soils expected at subgrade levels should be suitable for a net allowable bearing pressure of 3,000 pounds per square foot (psf). The net allowable soil bearing pressure refers to that pressure which may be transmitted to the foundation bearing soils in excess of the final minimum surrounding overburdened pressure. Settlement of individual footings designed in accordance to recommendations outlined above is expected to be small and within tolerable limits for the proposed structure. Within the proposed building addition, total allowable and differential post-construction settlements of less than ½ inch are anticipated. These settlement estimates are based on our engineering experience with these soils and are provided to guide the structural engineer with their design. In order to prevent disproportionately small footing sizes, we recommend that continuous footings have a minimum width of 1½ feet and that isolated column footings have a minimum lateral dimension of 2½ feet. The minimum dimensions recommended above help reduce the possibility of foundation bearing failure and excessive settlement due to local shear or "punching" action. Embedment depths should be a minimum of 24 inches. Mat Foundations The second option is using a mat foundation to support the five-story structure. We recommend that the mat foundation be designed using a modulus subgrade reaction of k=125 tcf. This modulus of subgrade reaction is based upon an equivalent 12 inch square plate load test. Caution St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 8 of 19 should be used in determining the proper modulus of subgrade reaction to be input into any computerized solution to determine the thickness of the mat. Specifically, the modulus of subgrade reaction is a function of the size of the plate on which the test is based, and variations are a direct function of the size of the plate. The equivalent modulus of subgrade reaction for the entire mat would be significantly less than 125 tcf. However, the recommended value of 125 tsf should be used as the design input into the mat design computer program unless the program specifically includes assumptions different from those outlined above. We also recommend that the mat be designed for a maximum average contact stress of 2500 psf and maximum local contact pressure of 4,500 psf. During the mat foundation design, there may be areas where the maximum bearing pressure exceeds the recommended 4,500 psf. Where these conditions occur, they should be brought to the attention of ECS. Please note that some overstress across the mat footprint may be acceptable. We will specifically evaluate the bearing conditions based on the soil conditions in those areas of the mat. Depending on the localized soil conditions, a higher bearing pressure may be feasible. We recommend that the structural engineer provide us with a copy of the bearing pressure contour plan of the mat foundation for our review. Additionally, an allowable stress increase factor can be applied to the recommended bearing pressure for short term (wind) loading. The bearing capacity of the subgrade soils should be confirmed immediately prior to placement of a gravel or concrete working mat. The soils should be observed by an experienced soils technician working under the direct supervision of a registered professional geotechnical engineer. Any soils which are soft or which become loosened by construction activities or water intrusion should be removed and replaced with a gravel backfill or “lean” concrete. Proper dewatering of the subgrade soils may be required during construction to reduce difficulties during foundation installation. A detailed discussion of construction dewatering is included in a subsequent section of this report. During excavation operations, we recommend that large excavation equipment be permitted to excavate no deeper than 1 foot above the proposed subgrade elevations. Below this level, smaller excavation equipment or a GRADALL should be utilized for final grading which will reduce disturbance of the subgrade. Upon completion of the excavation, an 8 inch gravel mat or a 4 inch lean concrete mud mat should be placed as a working surface. Deep Foundations The third option is to support the five-story structure on a deep foundation system. Once structural load and foundation configurations are finalized, a pile type should be chosen based upon cost, ease, timing of construction, and quality control assurances. Based on these criteria the three options for piles are Driven Precast Concrete Piles, Auger Displacement Piles, and Auger Cast Piles. Based on the loading conditions, settlement criteria, and economics, ECS St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 9 of 19 recommends using a shallow foundation system (with bearing capacity of 3,000 psf). ECS will be glad to provide you with all the deep foundation recommendations if you decide to choose a deep foundation option. Floor Slab Design According to the test borings and recommendations included in this report, soils at the lowest floor slab subgrade should consist of medium dense sand (SP) soils, which should be suitable for floor slab support. The subgrade should be prepared in accordance with our recommendations outlined in the sections entitled “Earthwork Operations” and “Fill Placement”. The lowest slabs can then be designed as slab on grade with a modulus of subgrade reaction of 200 pounds per cubic inch (pci). The Florida Building Code 2007 requires the use of a 6-mil (0.006 inch) polyethylene vapor retarder, with joints lapped not less than 6 inches, beneath the floor slab to control moisture. This will help to minimize floor dampness and moisture intrusion into the structure through the slab. Care should be exercised during construction to prevent tearing or punching of the vapor retarder prior to slab placement. Any tears must be repaired immediately. Special attention should be given to the surface curing of the slabs to minimize uneven drying of the slabs, associated cracking, and/or slab curling. Please refer to ACI 302.1R96 Guide for Concrete Floor and Slab Construction and ASTM E 1643 Standard Practice for Installation of Water Vapor Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs for additional guidance on this issue. In order to minimize the crack width of any shrinkage cracks that may develop near the surface of the slab, we recommend mesh reinforcement, as a minimum, be included in the design of the floor slab. For maximum effectiveness, temperature and shrinkage reinforcements in slabs on ground should be positioned in the upper third of the slab thickness. The Wire Reinforcement Institute recommends the mesh reinforcement be placed 2 inches below the slab surface or upper one-third of slab thickness, whichever is closer to the surface. Adequate construction joints, contraction joints and isolation joints should also be provided in the slab to reduce the impacts of cracking and shrinkage. Please refer to ACI 302.1R96 Guide for Concrete Floor and Slab Construction for additional information regarding concrete slab joint design. Earthwork Operations We recommend normal, good practice site preparation procedures. These procedures include stripping the site of existing asphalt, concrete, construction debris, vegetation, topsoil, and any other soft or unsuitable material from the proposed building areas; proofrolling the subgrade; and backfilling to grade with engineered fill. Stripping depths on the order of 2 inches in the asphalt St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 10 of 19 pavement areas and 6 to 12 inches in the landscaped areas should be anticipated. The underlying limerock base may be left in place. Asphalt should either be recycled on/off site or disposed of properly. As per Florida Building Code 2007 Section 1803.3 Site Grading, stripping within the proposed structural areas should be extended at least 10 feet beyond the planned limits. A more detailed synopsis of this work is as follows: 1. Prior to construction, the location of existing underground utility lines within the construction area should be established. Provisions should be made to relocate interfering utilities to appropriate locations. It should be noted that if underground pipes are not properly removed or plugged, they might serve as conduits for subsurface erosion which may subsequently lead to excessive settlement of overlying structures. 2. Strip the proposed construction limits of existing asphalt, concrete, construction debris, vegetation, topsoil, and any other soft or unsuitable material from the proposed building areas within and 10 feet beyond the perimeter of the proposed building and paved areas. Expect stripping on the order of 2 inches in the asphalt pavement areas and 6 to 12 inches in the existing landscaped areas. Somewhat deeper stripping or undercutting may be required in isolated areas to the root system of trees. The underlying limerock base may be left in place and the topsoil may be reused in landscaped areas. 3. The groundwater level was encountered at a depth of 7.5 feet below existing land surface (bls). Seasonal high groundwater levels could occur at a depth of 5 feet bls over most of the site. The need for groundwater control is therefore not anticipated for the initial site stripping and fill placement. For deeper excavations where sustained, positive groundwater control is needed, a system of vacuum well points may be required. The groundwater level should be maintained at least one foot below the bottom of any excavations during construction and two feet below the surface of any vibratory compaction operations. Vibratory compaction efforts should only be perform beyond 30 feet from existing structures. Within 30 feet of existing structures equipment should be used in static mode. 4. Proofroll the compacted subgrade with a heavily loaded, rubber-tired vehicle under the observation of ECS’ geotechnical engineer or his representative. Proofrolling will help locate any zones of especially loose or soft soils not encountered in the soil test borings. Then undercut, or otherwise treat these zones as recommended by the engineer. 5. Place structural fill material, as required, in accordance with the “Fill Placement” section of this report, below. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 11 of 19 Fill Placement Any off-site borrow material to be placed on site should consist of soils classified SP per ASTM D-2487 and have less than 10 percent passing the No. 200 sieve. The near surface on-site soils should be suitable for reuse as compacted fill, provided that the moisture content is within an acceptable range to obtain compaction. Prior to the commencement of fill operations and/or utilization of any off-site borrow materials, the contractor should provide representative samples of the soil materials to the geotechnical engineer. The geotechnical engineer will determine the material’s suitability for use as an engineered fill and develop moisture-density relationships in accordance with the recommendations provided herein. Samples should be provided to the geotechnical engineer at least 3 to 5 days prior to their use in the field to allow for the appropriate laboratory testing to be performed. The footprint of the proposed building area should be well defined during fill placement. Grade controls should also be maintained throughout the filling operations. All filling operations should be observed on a full-time basis by the Geotechnical Engineer’s representative to determine that the required degrees of compaction are being achieved. Compliance tests should be performed at a rate of 1 test per 2,500 square feet per lift in the structure areas, 1 test per 10,000 square feet per lift in paved areas; or two tests, which ever is greater. The elevation and location of the tests should be accurately identified at the time of fill placement. Areas which fail to achieve the required degree of compaction should be re-compacted and re-tested until minimum compaction is achieved. Failing test areas may require moisture adjustments or other suitable remedial activities in order to achieve the required compaction. All fill materials placed within the building and pavement areas should be placed in lifts not exceeding 8 to 12 inch thick loose lifts, moisture conditioned to within 3 percent of the optimum moisture content, and compacted to a minimum of 95 percent of the Modified Proctor maximum dry density as determined in accordance with ASTM D 1557. The upper 1 foot of soils supporting slabs on grade, pavements or sidewalks should be compacted to 98 percent of the Modified Proctor maximum dry density. In parking areas the upper 1 foot of fill should consist of a stabilized subgrade with a Limerock Bearing Ratio (LBR) value of 40. Stabilize this zone with limerock if needed, unless laboratory testing indicates a soil with LBR value of 40 is present. In the building areas, test all footing cuts for compaction to a depth of 1 foot below bottom of footing elevation. We recommend testing every column footing, and conduct a minimum 1 test for every 100 lineal feet of wall footing. Footing bottoms must be compacted to a minimum of 95 percent of the Modified Proctor maximum dry density as determined in accordance with ASTM D 1557. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 12 of 19 Fill placed in non-structural areas (i.e. grassed areas) should be compacted to at least 90 percent of the maximum dry density according to ASTM D-1557, in order to avoid significant subsidence. If problems are encountered during the site grading operations, or if the actual site conditions differ from those encountered during our subsurface exploration, the ECS geotechnical engineer should be notified immediately. Retaining Walls We assume the retaining walls will be constructed of smooth concrete. We recommend using the parameters stated in the below table for retaining wall design utilizing the in-situ sand and crushed well-graded limestone as wall backfill. These backfill materials should be compacted to a minimum of 95% of the maximum dry density obtained in accordance with ASTM Specification D-1557, Modified Proctor Method. Behind the retaining wall, materials should be carefully placed and compacted so as not to damage the structure by the use of hand-operated compaction equipment. All fill operations should be observed on a full-time basis by a qualified soil technician to determine that minimum compaction requirements are being met. A minimum of one compaction test should be tested in each lift placed. The elevation and location of the tests should be clearly identified at the time of fill placement. Laboratory testing in accordance with ASTM D-1557, Modified Proctor Method, should be performed on a representative sample of the on-site soils in order to obtain the theoretical maximum dry density for use during backfilling operations. A uniform frictional resistance coefficient of 0.30 (tan) can be utilized for sliding resistance design for the site’s retaining walls. Based on the anticipated soil strength parameters for the insitu sand and crushed well-graded limestone, the following lateral earth pressure coefficients are provided for horizontal backfill. Soil Parameters and Lateral Earth Pressure (LEP) Coefficients Soil Type Moist Unit Weigh t (γtotal, pcf) Submerged Unit Weight (γ, pcf) Internal Angle of Friction (φ,º) Coefficient of Friction, Fine Sand 120 58 30 0.30 0 0.33 3.00 0.5 Crushed Limestone 145 80 36 0.30 0 0.26 3.85 0.4 Cohesion Intercept (c, psf) Active LEP Passive LEP Coefficien Coefficient t (Kp) (Ka) The table above does not include a factor of safety. Therefore, an appropriate factor of safety should be incorporated by the designer. Additionally, the recommendations contained above At-rest LEP Coeffici ent (Ko) St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 13 of 19 assume that the backfill behind the retaining walls is horizontal ( = 0 degrees), is properly drained and will not permit the buildup of hydrostatic pressures behind the wall. Retaining walls with adjacent sloping earth embankments, sloping backfill or structural loadings require special considerations. Similarly, the design should also account for any surcharge loads that are within a 45° slope from the base of the wall. In areas of the wall near corners where rigidity is required, at-rest equivalent fluid pressures should be utilized. Pavement Considerations General All pavement subgrades should be prepared in accordance with the recommendations in the sections entitled “Earthwork Operations” and “Fill Placement”. An important consideration with the design and construction of pavements is surface and subsurface drainage. Where standing water develops, either on the pavement surface or within the base course layer, softening of the subgrades and other problems related to the deterioration of the pavement can be expected. Furthermore, good drainage should reduce the possibility of the subgrade materials becoming saturated during the normal service period of the pavement. Regardless of the pavement type, a minimum separation of 18 inches should be maintained between the pavement base and the season high groundwater levels. No full depth asphalt or concrete sections are allowed. We recommend that drains be installed around the landscaped sections adjacent to the parking lots and driveways to protect the asphalt pavement from excess rainfall and over irrigation. Migration of irrigation water from the landscape areas to the interface between the asphalt and the base usually occurs unless landscape drains are installed. This migration often causes separation of the wearing surface from the base and subsequent rippling and pavement deterioration. The underdrains or strip drains should be routed to a positive outfall at the pavement area catch basins. Light duty roadways and incomplete pavement sections will not perform satisfactorily under construction traffic loadings. We recommend that construction traffic (construction equipment, concrete trucks, sod trucks, garbage trucks, moving vans, dump trucks, etc.) be re-routed away from these roadways or that the pavement section is designed for these loadings. Flexible pavement combines the strength and durability of several layer components to produce an appropriate and cost-effective combination of available construction materials. Rigid concrete pavement has the advantage of the ability to “bridge” over isolated soft areas, it requires less lighting, and it typically has a longer service life than asphalt pavement. Disadvantages of rigid pavement include an initial higher cost and more difficult patching of distressed areas than occurs with flexible pavement. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 14 of 19 Asphalt (Flexible) Pavements Layer Components As a reference Hillsborough County has divided their pavement requirements into four types of services: 1. Local Roads, 2. Subdivision Collector Roads, 3. Major Collector Roads, and 4. Industrial/Commercial Roads. We believe that the minimum county requirements may lead to more than normal periodic maintenance and may not meet typical life expectancies for some pavements. If projected traffic loads become available, we recommend that an appropriate pavement design be used and the component thicknesses be adjusted accordingly. Because traffic loadings are commonly unavailable, we have generalized our pavement design into the four groups as divided by Hillsborough County. The group descriptions and the recommended component thicknesses are presented in following table. For loading conditions greater than those presented in the following table, we recommend that you have a complete pavement design performed based on projected traffic data. Pavement Component Recommendations Component Thickness Traffic Group Stabilized Subgrade** Local Roads 6” 40 LBR Subdivision Collector Roads 8” 40 LBR Major Collector Roads 12” 40 LBR Base Course 6" Limerock 6" Soil Cement 6” Crushed Concrete 4” Asphalt (ABC III) or 6” Shell 8" Limerock 8" Soil Cement 8” Crushed Concrete 5” Asphalt (ABC III) or 8” Shell 8" Limerock 8" Soil Cement 8” Crushed Concrete 5” Asphalt (ABC III) or 8” Shell Surface Course*** 1¾” 1¾” 2” St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 15 of 19 Industrial Commercial Roads 12” 40 LBR 8" Limerock* 8" Soil Cement* 8” Crushed Concrete* 5” Asphalt (ABC III)* or 8” Shell * Local Roads 2¼” Collector Roads 2½“ Arterial Road 2½” * Base course can be reduced to 6 inches with design calculations ** Stabilized subgrade can be reduced to LBR 20 for 12 inches when using soil cement *** Add FC-3 friction course if speeds are greater than 45 mph Stabilized Subgrade We recommend that subgrade materials be compacted in place according to the requirements in the "Earthwork Operations" section of this report. Further, stabilize the subgrade materials should have a minimum Limerock Bearing Ratio (LBR) of 40 percent. All stabilized subgrade materials should be compacted to 98 percent of the Modified Proctor (AASHTO T-180) maximum dry density and meet specification requirements for Type B or Stabilized Subgrade by Florida Department of Transportation (FDOT). Further, the stabilized subgrade can be imported material or a blend of on-site soils and imported materials. If a blend is proposed, we recommend that the contractor perform a mix design to find the optimum mix proportions. Base Course We recommend that the base course be limerock, soil cement, crushed concrete, asphalt, or shell. If limerock is used it should have a minimum LBR of 100 percent and should be mined from an FDOT approved source. Place limerock in maximum 6-inch lifts and compact each lift to a minimum density of 98 percent of the Modified Proctor (AASHTO T-180) maximum dry density. For a soil-cement base, we recommend that the contractor perform a soil-cement design with a minimum seven-day strength of 300 pounds per square inch (psi) on the materials he intends to use. Place soil-cement in maximum 6-inch lifts and compact in place to a minimum density of 95 percent of the Standard Proctor maximum dry density according to specifications in ASTM D558. Place and finish the soil-cement according to Portland Cement Association requirements. Final review of the soil-cement base course should include manual "chaining" and/or "soundings" seven days after placement. Shrinkage cracks will form in the soil-cement mixture and you should expect reflection cracking on the surface course. Crushed concrete, asphalt base, or shell should follow the appropriate FDOT specifications. Perform compliance testing for the base course at a frequency of one test per 500 lineal feet of St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 16 of 19 roadway alternating between lanes, every 5,000 square feet of pavement, or at a minimum of two test locations, whichever is greater. Surface Course In residential light duty areas where there is occasional truck traffic, but primarily passenger cars, we recommend using an asphaltic concrete, FDOT Type S. A minimum of two lifts are required for pavement thickness greater than 2 inches. Asphaltic concrete mixes should be a current FDOT approved design of the materials actually used. Test samples of the materials delivered to the project should be checked to verify that the aggregate gradation and asphalt content satisfies the mix design requirements. Compact the asphalt to a minimum of 95 percent of the Marshall design density. After placement and field compaction, core the wearing surface to evaluate material thickness and to perform laboratory densities. Obtain cores at frequencies of at least one core per 500 lineal feet of placed pavement or a minimum of two cores per day's production. Effects of Groundwater One of the most critical influences on the pavement performance in Central Florida is the relationship between the pavement subgrade and the seasonal high groundwater level. Many roadways and parking areas have been destroyed as a result of deterioration of the base and the base/surface course bond. Regardless of the type of base selected, we recommend that the seasonal high groundwater and the bottom of the base course be separated by at least 18 inches. To maintain this separation, either raise the roadway grades or artificially lower the groundwater level with underdrains. Landscape Drains We recommend that drains be installed around the landscaped sections adjacent to the parking lots and driveways to protect the asphalt pavement from excess rainfall and over irrigation. Migration of irrigation water from the landscape areas to the interface between the asphalt and the base usually occurs unless landscape drains are installed. This migration often causes separation of the wearing surface from the base and subsequent rippling and pavement deterioration. The underdrains or strip drains should be routed to a positive outfall at the pavement area catch basins. Construction Traffic Light duty roadways and incomplete pavement sections will not perform satisfactorily under St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 17 of 19 construction traffic loadings. We recommend that construction traffic (construction equipment, concrete trucks, sod trucks, garbage trucks, moving vans, dump trucks, etc.) be re-routed away from these roadways or that the pavement section be designed for these loadings. Concrete (Rigid) Pavements Concrete pavement is a rigid pavement that transfers much lighter wheel loads to the subgrade soils than a flexible asphalt pavement. For a concrete pavement subgrade, a minimum 4 inch thick limerock base course should be placed beneath the concrete atop a 4 inch thick stabilized subgrade. The limerock base and stabilized subgrade should be densified to at least 98 percent of Modified Proctor test maximum dry density (ASTM D 1557). The surface of the subgrade soils must be smooth, and any disturbances or wheel rutting corrected prior to placement of concrete. The subgrade soils must be moistened prior to placement of concrete. Concrete pavement thickness should be uniform throughout, with exception to thickened edges (curb or footing). The bottom of the pavement should be separated from the estimated typical wet season groundwater level by at least 18 inches. Our recommendations for slab thickness for heavy-duty concrete pavements are based on the same factors as above. We recommend using concrete of unreinforced Portland cement concrete (Type I) providing a minimum 28-day compressive strength of 4,000 pounds per square inch (psi). In addition, the concrete should provide a minimum 28-day flexural strength (modulus of rupture) of 600 psi, based on the third point loading of concrete beam samples. Front-loading trash dumpsters frequently impose concentrated front-wheel loads on pavements during loading. This type of loading typically results in rutting of bituminous pavements and ultimately pavement failures and costly repairs. Therefore, we suggest that the pavements in trash pickup areas utilize a heavy duty Portland Cement Concrete (PCC) pavement section. Such a PCC section would typically consist of 6 inches of 4,000 psi concrete over a 6 inch thick compacted aggregate base course. Appropriate steel reinforcing and jointing should also be incorporated into the design of all PCC pavements. Concrete pavement is a rigid pavement that transfers reduced wheel pressures to the underlying subgrade soils. Control joints for crack control should be a maximum of 12 feet apart and 1.5 inches deep. Control joints should be provided in a uniform square or rectangular pattern. The joints should be submitted for review and approved prior to construction. Control joints should be sawed as soon as the concrete can withstand traffic, and concrete surface and aggregate raveling can be prevented. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 18 of 19 One of the most critical influences on the pavement performance in South Florida is the relationship between the pavement subgrade and the seasonal high groundwater level. It is recommended that the seasonal high groundwater and the bottom of the stabilized subgrade be separated by at least 18 inches. Construction Considerations Exposure to the environment may weaken the soils at the footing bearing level if the foundation excavations remain open for too long a time. Therefore, foundation concrete should be placed the same day that excavations are excavated during the rainy season or if rain is anticipated. If the bearing soils are softened by surface water intrusion or exposure, the softened soils must be removed from the foundation excavation bottom immediately prior to placement of concrete. If the excavation must remain open overnight, or if rainfall becomes imminent while the bearing soils are exposed, the geotechnical engineer should be contacted immediately. The soils at the proposed bearing elevations are moisture and disturbance sensitive. When wet, these soils will degrade quickly and create a soft condition that is not suitable to support the building loads without detrimental settlement. The contractor may need to dewater (sump pits and trenching) the site to two feet below the groundwater level at the time of construction, depending on foundation depth and time of year. Without dewatering the site soils prior to excavating footings, we anticipate that the foundations will need to be excavated and placed within two to three hours. If aggressive dewatering is not undertaken, then the footings will need to be excavated to within six inches of subgrade to maintain an overburden confinement. Once the footing excavations are tested by ECS, concrete placed in no more than two hours. If final concrete cannot be placed within that timeframe, then we recommend the use of a 2 to 3 inch thick concrete mudmat used with the same placement limitations. The contractor may elect to place the foundations in sections in order to limit the softening of soils, which should be removed The surficial soils are considered moderately erodible. The Contractor should provide and maintain good site drainage during earthwork operations to help maintain the integrity of the surface soils. The surface of the site should be kept properly graded in order to enhance drainage of the surface water away from the proposed construction areas during the earthwork phase. We recommend that surface drainage be diverted around the proposed building area without significantly interrupting its pattern. All erosion and sedimentation shall be controlled in accordance with sound engineering practice and current state and local requirements. Closing This report has been prepared to aid in the evaluation of this site and to assist the design team with the design of the proposed facility. The report scope is limited to this specific project and the location described. The project description represents our current understanding of the significant aspects of the proposed improvements relevant to the geotechnical considerations. St. Joseph’s Women’s Hospital Bed Tower Addition ECS Job No.: 24-3110 January 26, 2009 Page 19 of 19 The analysis and recommendations are, of necessity, based on the information made available to us at the time of the actual writing of the report and the on-site conditions, surface and subsurface that existed at the time the exploratory borings were drilled. Further assumptions have been made that the limited exploratory borings, in relation both to the aerial extent of the site and to depth, are representative of conditions across the site. If subsurface conditions are encountered which differ significantly from those reported herein, such as muck or silt, this office should be notified immediately so that the analyses and recommendations can be reviewed for validity. The earthwork and foundation construction operations for the site will be a primary consideration during development of this project. The placement of any new engineered fill will require adequate monitoring during construction in order to assure that the fill mass is installed properly to avoid future settlements. Because of our in-depth knowledge of the subsurface conditions at the site, we recommend that ECS observe all earthwork and construction operations to assure that the work is being performed in accordance with the project specifications. It is also recommended that ECS be allowed to prepare or at least review the project specifications with regard to the earthwork for this site. We would appreciate the opportunity to continue our involvement on the project during construction. ECS-Florida, LLC is capable of providing all Construction Materials Testing, Private Provider Inspections (mechanical, electrical, plumbing and building), Threshold Inspections and Resident Inspections; and we would be glad to prepare proposals to offer our services. APPENDIX Unified Soil Classification System Reference Notes for Boring Logs Boring Location Plan Boring Logs S-1 through S-3; A-1 and A-2: C-1 and C-2; Pressuremeter Tests P-1 (Sounding 1) and P-2 (Sounding 2) REFERENCE NOTES FOR BORING LOGS I. Drilling Sampling Symbols: SS Split Spoon Sampler RC Rock Core, NX, BX, AX DC Dutch Cone Penetrometer BS Bulk Sample of Cuttings HAS Hollow Stem Auger II. ST PM RD PA WS Shelby Tube Sampler Pressuremeter Rock Bit Drilling Power Auger (no sample) Wash Sample Correlation of Penetration Resistances to Soil Properties: Standard Penetration (Blows/Ft) refers to the blows per foot of a 140 lb. Hammer falling 30 inches on a 2-inch OD split spoon sampler, as specified in ASTM D-1586. The blow count is commonly referred to as the N value. A. Non-Cohesive Soils (Silt, Sand, Gravel and Combinations) Density Under 4 blows/ft Very Loose 4 to 10 blows/ft Loose 11 to 30 blows/ft Medium Dense 31 to 50 blows/ft Dense Over 51 blows/ft Very Dense Particle Size Identification 8 inches or larger 3 to 8 inches 1 to 3 inches ½ to 1 inch ¼ to ½ inch 2.00 mm to ¼ inch (dia. of lead pencil) 0.42 to 2.00 mm (dia. of broom straw) 0.074 to 0.42 mm (dia. of human hair) 0.0 to 0.074 mm (particles cannot be seen) Boulders Cobbles Gravel Coarse Medium Fine Sand Coarse Medium Fine Silt and Clay B. III. Relative Properties Adjective Form 12% to 49% With 5% to 12% Cohesive Soils (Clay, Silt, and Combinations) Blows/ft Consistency Unconfined Comp. Strength Qp (tsf) Under 2 2 to 4 4 to 8 9 to 15 16 to 30 Over 30 Very Soft Soft Med. Stiff Stiff Very Stiff Hard Under 0.25 0.25-0.49 0.50-0.99 1.00-1.99 2.00-3.00 Over 4.00 Degree of Plasticity Plasticity Index None to Slight Slight Medium High to Very High 0–4 5 -7 8 - 22 Over 22 Water Level Measurement Symbols: WL Water Level WS While Sampling WD While Drilling BCR Before Casing Removal DCI Dry Cave-In ACR After Casing Removal WCI Wet Cave-In Existing Groundwater Level ● Est. Seasonal High GWT The water levels are those water levels actually measured in the borehole at the times indicated by the symbol. The measurements are relatively reliable when augering, without adding fluids, in a granular soil. In clay and plastic silts, the accurate determination of water levels may require several days for the water level to stabilize. In such cases, additional methods of measurement are generally applied. REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL ANALYSIS ST. JOSEPH’S WOMEN’S HOSPITAL BED TOWER ADDITION TAMPA, FLORIDA FOR HKS, INC JANUARY 26, 2009