VIPERCON ELECTRIC CABLE
PVC Sheathed, Unarmoured Power Cables - 0.6/1kV
Applications
WW VIPERCON 0.6/1kV PVC sheathed power cables are mostly used for buildings, industrial plants, gantry wiring, and road transport depots where not subject to mechanical damage. The cables are suitable for installation indoor/outdoor, enclosed in conduit, in underground duct
Configuration
Conductor:
Insulation:
Laying-up:
Sheath: plain annealed copper or plain aluminium of the type specified in AS/NZS 1125.
1.5mm
2 ~ 70mm 2 , polyvinylchloride compound PVC V90.
95mm 2 and above, cross-linked polyethylene compound XLPE cores are laid up together with a right-hand direction of lay, with non-hygroscopic filler where necessary to form a substantially compact and circular cross-section core assembly.
The laid-up core is sheathed with a continuous flame retardant polyvinylchloride compound PVC V90
Core identification
2C+E cable:
3C+E cable:
4C+E cable:
Phase core colour: Red,
Phase core colour: Red, White, and Blue
Phase core colour: Red, White, and Blue
Neutral core colour: Black
Neutral core colour: Black
Earth core colour: Green/Yellow
Earth core colour: Green/Yellow
Earth core colour: Green/Yellow
Sheath colour: Standard - Orange
Optional - Black (Ultraviolet radiation stabilised)
Technical data
Rated voltage: 0.6 / 1 kV
Conductor operating range: PVC insulated, -25 o
C ~ 75 o
C, MAX 90 o
C, short circuit temperature 160 o
C for 5 sec
Temperature at surface:
Minimum ambient temp:
XLPE insulated, -40 o
C ~ 90 o
C, short circuit temperature 250 o
C for 5 sec
In operation, -25 o
C ~ 90 o
C
0 o
C, after installation and only when cable is in a fixed position
Minimum bending radius: Stranded conductors 9 x cable O.D during installation
6 x cable O.D after installation
Compacted conductors 12 x cable O.D during installation
8 x cable O.D after installation
--The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
--When installed in tunnels, they should be fixed on brackets and cannot bear large pulling tension or pressure.
--Thermoplastic PVC V90 insulation is subject to deformation at temperatures above 75 o
C.
Standards:
International
Australian/New Zealand
- IEC 60502, IEC 60228, IEC 60332
- AS/NZS 5000.1, AS/NZS 3808, AS/NZS 1125, AS/NZS 1660
2 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
PVC Sheathed, Unarmoured Power Cables - 0.6/1kV
Type
Phase Cond.
Area mm²
Phase
Cond.
Type
Core
Dia.
mm
Earth Cond.
Area mm²
Core
Dia mm
Avg.
Cable Dia.
mm
Copper conductor
Product Approx Weight
Code kg/km
70
95
120
150
185
240
300
10
16
25
35
50
1.5
2.5
4
6
150
185
240
300
50
70
95
120
10
16
25
35
1.5
2.5
4
6
10
16
25
35
1.5
2.5
4
6
50
70
95
120
150
185
240
300
1015UA
1025UA
1004UA
1006UA
1010UA
1016UA
1125UA
1035UA
1050UA
1070UA
1095UA
1120UA
1150UA
1185UA
1124UA
1130UA
1305UA
1307UA
1309UA
1312UA
1350UA
1318UA
1324UA
1330UA
1301UA
1302UA
1304UA
1306UA
1310UA
1316UA
1325UA
1335UA
1505UA
1502UA
1504UA
1506UA
1510UA
1516UA
1525UA
1535UA
1550UA
1570UA
1595UA
1520UA
1515UA
1585UA
1524UA
1530UA
35.0
37.0
41.4
46.6
52.2
58.7
65.1
10.6
11.8
13.3
14.4
17.0
19.5
23.0
26.0
30.5
26.4
30.5
31.9
35.7
40.4
45.2
50.9
56.4
9.7
10.8
11.8
12.7
15.1
17.2
20.0
22.6
11.5
12.9
14.7
16.1
18.9
21.8
26.0
29.3
34.5
39.5
42.0
47.0
52.9
59.2
66.6
73.8
9.1
8.5
9.7
11.4
13.4
15.2
17.1
4.6
5.2
5.2
6.2
7.3
3.2
3.7
3.5
3.5
11.4
13.4
15.2
17.1
7.3
9.1
8.5
9.7
4.6
5.2
5.2
6.2
3.2
3.7
3.5
3.5
4.6
5.2
5.2
6.2
3.2
3.7
3.5
3.5
7.3
9.1
8.5
9.7
11.4
13.4
15.2
17.1
Compact
Compact
Compact
Compact
Compact
Compact
Compact
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Compact
Compact
Compact
Compact
Compact
Compact
Compact
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Compact
Compact
Compact
Compact
Compact
Compact
Compact
14.0
15.2
17.1
19.2
21.4
24.1
26.8
6.2
7.3
9.1
10.3
12.2
3.2
3.7
4.6
5.2
12.2
14.0
15.2
17.1
19.2
21.4
24.1
26.8
6.2
7.3
9.1
10.3
3.2
3.7
4.6
5.2
6.2
7.3
9.1
10.3
3.2
3.7
4.6
5.2
12.2
14.0
15.2
17.1
19.2
21.4
24.1
26.8
25
25
35
50
70
95
120
6
10
4
6
16
1.5
2.5
2.5
2.5
50
70
95
120
16
25
25
35
6
10
4
6
1.5
2.5
2.5
2.5
6
10
4
6
1.5
2.5
2.5
2.5
16
25
25
35
50
70
95
120
Aluminium conductor
Product
Code
Approx Weight kg/km
-
-
1120AUA
1150AUA
1185AUA
1124AUA
1130AUA
-
-
-
-
-
-
-
-
-
-
-
-
1312AUA
1350AUA
1318AUA
1324AUA
1330AUA
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1520AUA
1515AUA
1585AUA
1524AUA
1530AUA
-
-
-
1364
1705
2132
2711
3336
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1843
2327
2898
3688
4542
-
-
-
-
-
-
-
-
-
-
-
2373
2991
3719
4735
5832
2813
3392
4287
5420
6765
8730
10852
148
200
278
351
523
752
1084
1459
2057
1478
2029
2406
3047
3870
4854
6268
7791
119
159
213
263
390
554
779
1049
178
243
346
444
661
956
1398
1881
2653
3619
4403
5559
7013
8731
11262
13999
3 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
PVC Sheathed, Unarmoured Control Cables - 0.6/1kV
Applications
WW VIPERCON 0.6/1kV PVC sheathed multi-core control cables are mostly used for control circuit in buildings, industrial plants, gantry wiring, and road transport depots where not subject to mechanical damage. The cables are suitable for installation indoor/outdoor, enclosed in conduit, in underground duct,
Configuration
Conductor:
Insulation:
Laying-up:
Sheath: plain annealed copper (class 2 strands) of the type specified in AS/NZS 1125.
polyvinylchloride compound PVC V90.
cores are laid up together with a right-hand direction of lay, with non-hygroscopic filler where necessary to form a substantially compact and circular cross-section core assembly.
the laid-up core is sheathed with a continuous flame retardant polyvinylchloride compound PVC V90
Core identification
Core:
Earth core:
Sheath colour:
Active core: White core with black numbering
Green/Yellow
Standard - Orange
Optional - Black (Ultraviolet radiation stabilised)
Technical data
Rated voltage:
Conductor operating range:
Temperature at surface:
Minimum ambient temp:
Minimum bending radius:
0.6 / 1 kV
-25 o
C ~ 75 o
C, MAX 90 o
C, short circuit temperature 160 o
C for 5 sec
In operation, -25 o
C ~ 90 o
C
0 o
C after installation and only when cable is in a fixed position
9 x cable O.D during installation
6 x cable O.D after installation
--The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
--When installed in tunnels, they should be fixed on brackets and cannot bear large pulling tension or pressure.
--Thermoplastic PVC V90 insulation is subject to deformation at temperatures above 75 o
C.
Standards:
International
Australian/New Zealand
- IEC 60502, IEC 60228, IEC 60332
- AS/NZS 5000.1, AS/NZS 3808, AS/NZS 1125, AS/NZS 1660
Type
2C+E
3C+E
4C+E
6C+E
8C+E
10C+E
12C+E
15C+E
20C+E
25C+E
30C+E
40C+E
50C+E
Product
Code
1031UA
1041UA
1051UA
1701UA
1901UA
1111UA
1131UA
1161UA
1211UA
1261UA
1311UA
1411UA
1511UA
Conductor
Area mm²
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Core
Dia.
mm
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
Avg.
Cable Dia.
mm
9.7
10.6
11.5
12.6
15.4
16.0
17.5
18.5
20.6
23.0
25.4
28.7
30.4
Approx
Weight kg/km
119
148
178
231
300
351
409
486
621
758
898
1164
1410
Product
Code
1032UA
1042UA
1052UA
1702UA
1902UA
1112UA
1132UA
1162UA
1212UA
1262UA
1312UA
1412UA
1512UA
Conductor
Area mm²
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
Core
Dia.
mm
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
Avg.
Cable Dia.
mm
10.8
11.8
12.9
14.1
17.3
18.1
19.7
20.8
23.3
26.0
28.8
32.6
34.5
Approx
Weight kg/km
159
200
243
319
414
488
570
681
874
1071
1272
1655
2012
4 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
PVC Sheathed, Steel Wire Armoured Power Cables - 0.6/1kV
Applications
WW VIPERCON 0.6/1kV armoured power cables are mostly used for buildings, industrial plants, mining and petroleum industry where extra mechanical protection is required. The cables are suitable for installation indoor/outdoor, enclosed in conduit, in underground duct, and buried directly in earth.
Configuration
Conductor:
Insulation:
Laying-up:
Bedding:
Armour:
Sheath:
Core identification
2C+E cable:
3C+E cable:
4C+E cable: plain annealed copper or plain aluminium (class 2 strands) of the type specified in AS/NZS 1125.
1.5mm
2
~ 70mm
2
, polyvinylchloride compound PVC V90.
95mm
2 and above, cross-linked polyethylene compound XLPE cores are laid up together with a right-hand direction of lay, with non-hygroscopic filler where necessary to form a substantially compact and circular cross-section core assembly.
flame retardant polyvinylchloride compound PVC V90 single layer galvanized (Mild) steel wires helically applied over bedding.
The laid-up core is sheathed with a continuous flame retardant polyvinylchloride compound PVC V90 to AS/NZS 3808.
Phase core colour: Red,
Phase core colour: Red, White, and Blue
Phase core colour: Red, White, and Blue
Neutral core colour: Black
Neutral core colour: Black
Earth core colour: Green/Yellow
Earth core colour: Green/Yellow
Earth core colour: Green/Yellow
Sheath colour: Standard - Orange
Optional - Black (Ultraviolet radiation stabilised)
Technical data
Rated voltage:
Conductor operating range:
Temperature at surface:
Minimum ambient temp:
Minimum bending radius:
0.6 / 1 kV
PVC insulated, -25 o
C ~ 75 o
C, MAX 90 o
C
XLPE insulated, -40 o
C ~ 90 o
C
In operation, -25 o
C ~ 90 o
C
0 o
C after installation and only when cable is in a fixed position
18 x cable O.D during installation
12 x cable O.D after installation
--The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
--When installed in tunnels, they should be fixed on brackets and cannot bear large pulling tension or pressure.
--Thermoplastic PVC V90 insulation is subject to deformation at temperature above 75 o
C.
Standards:
International
Australian/New Zealand
- IEC 60502, IEC 60228, IEC 60332
- AS/NZS 5000.1, AS/NZS 3808, AS/NZS 1125, AS/NZS 1660, AS/NZS 3863
5 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
3C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
4C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
2C+E
PVC Sheathed, Steel Wire Armoured Power Cables - 0.6/1kV
Type
Phase Cond.
Area mm²
Phase
Cond.
Type
Core
Dia.
mm
Earth Cond.
Area mm²
Core
Dia mm
Over
Bedding Dia.
mm
Avg.
Copper conductor Aluminium conductor
Cable Dia.
Product Approx Weight Product Approx Weight mm Code kg/km Code kg/km
150
185
240
300
50
70
95
120
10
16
25
35
1.5
2.5
4
6
1.5
2.5
4
35
50
70
95
6
10
16
25
120
150
185
240
300
10
16
25
35
1.5
2.5
4
6
50
70
95
120
150
185
240
300
Strand
Compact
Compact
Compact
Compact
Compact
Compact
Compact
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Compact
Compact
Compact
Compact
Compact
Compact
Compact
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Strand
Compact
Compact
Compact
Compact
Compact
Compact
Compact
12.2
14.0
15.2
17.1
19.2
21.4
24.1
26.8
6.2
7.3
9.1
10.3
3.2
3.7
4.6
5.2
3.2
3.7
4.6
10.3
12.2
14.0
15.2
5.2
6.2
7.3
9.1
17.1
19.2
21.4
24.1
26.8
6.2
7.3
9.1
10.3
3.2
3.7
4.6
5.2
12.2
14.0
15.2
17.1
19.2
21.4
24.1
26.8
50
70
95
120
16
25
25
35
6
10
4
6
1.5
2.5
2.5
2.5
1.5
2.5
2.5
10
16
25
25
2.5
4
6
6
35
50
70
95
120
6
10
4
6
1.5
2.5
2.5
2.5
16
25
25
35
50
70
95
120
11.4
13.4
15.2
17.1
7.3
9.1
8.5
9.7
4.6
5.2
5.2
6.2
3.2
3.7
3.5
3.5
3.2
3.7
3.5
6.2
7.3
9.1
8.5
3.5
4.6
5.2
5.2
9.7
11.4
13.4
15.2
17.1
4.6
5.2
5.2
6.2
3.2
3.7
3.5
3.5
7.3
9.1
8.5
9.7
11.4
13.4
15.2
17.1
29.45
33.84
35.81
40.08
45.20
50.58
56.94
63.11
9.3
10.5
12.74
13.86
16.36
18.81
22.20
25.10
10.2
11.5
14.17
15.50
18.26
21.07
25.10
28.37
33.35
38.24
40.69
45.54
51.31
57.35
64.58
71.57
8.4
9.5
11.35
12.24
14.51
16.60
19.29
21.82
25.56
29.49
30.89
34.59
39.08
43.84
49.34
54.70
38.2
42.9
45.0
50.7
56.1
61.9
68.7
76.7
14.1
15.3
18.7
19.9
23.4
26.0
29.6
32.7
15.1
16.5
20.3
21.7
25.4
28.4
32.7
37.1
42.4
47.6
51.3
56.5
62.7
69.1
78.3
85.8
13.1
14.3
17.2
18.2
20.6
22.9
26.5
29.2
33.2
37.4
39.8
43.7
49.6
54.7
60.6
66.3
1050
1070
1095
1120
1150
1185
1124
1130
1015
1025
1004
1006
1010
1016
1125
1035
1505
1502
1504
1506
1510
1516
1525
1535
1550
1570
1595
1520
1515
1585
1524
1530
1301
1302
1304
1306
1310
1316
1325
1335
1305
1307
1309
1312
1350
1318
1324
1330
3401
4425
5118
6634
8087
9774
12151
15495
360
442
681
789
1156
1481
1947
2439
413
512
745
874
1176
1547
2230
2836
3778
4924
6075
7444
9557
11605
14569
17703
313
379
586
663
861
1091
1548
1918
2494
3204
3914
4739
6205
7480
9237
11099
-
-
-
1120A
1150A
1185A
1124A
1130A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1520A
1515A
1585A
1524A
1530A
-
-
-
-
-
-
-
-
-
-
-
1312A
1350A
1318A
1324A
1330A
-
-
-
4190
4993
5907
7109
9185
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4257
5536
6593
8042
9536
-
-
-
-
-
-
-
-
-
-
-
3038
4040
4758
5680
6644
6 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
PVC Sheathed, Steel Wire Armoured Multi-Core Control Cables - 0.6/1kV
Applications
WW VIPERCON 0.6/1kV armoured multi-core control cables are mostly used for control circuit in buildings, industrial plants, mining and petroleum industry where extra mechanical protection is required. The cables are suitable for installation indoor/outdoor, enclosed in conduit, in underground duct, and buried directly in earth.
Configuration
Conductor:
Insulation:
Laying-up:
Bedding:
Armour:
Sheath: plain annealed copper (class 2 strands) of the type specified in AS/NZS 1125.
polyvinylchloride compound PVC V90.
cores are laid up together with a right-hand direction of lay, with non-hygroscopic filler where necessary to form a substantially compact and circular cross-section core assembly.
flame retardant polyvinylchloride compound PVC V90 single layer galvanized (Mild) steel wires helically applied over bedding.
the laid-up core is sheathed with a continuous flame retardant polyvinylchloride compound PVC V90 to AS/NZS 3808.
Core identification
Core:
Sheath colour:
Active core:
Earth:
White core with black numbering,
Green/Yellow
Standard - Orange
Optional - Black (Ultraviolet radiation stabilised)
Technical data
Rated voltage:
Conductor operating range:
Temperature at surface:
Minimum ambient temp:
Minimum bending radius:
0.6 / 1 kV
-25 o
C ~ 75 o
C, MAX 90 o
C, short circuit temperature 160 o
C for 5 sec
In operation, -25 o
C ~ 90 o
C
0 o
C after installation and only when cable is in a fixed position
18 x cable O.D during installation
12 x cable O.D after installation
--The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
--When installed in tunnels, they should be fixed on brackets and cannot bear large pulling tension or pressure.
--Thermoplastic PVC V90 insulation is subject to deformation at temperature above 75 o
C.
Standards:
International
Australian/New Zealand
Type
2C+E
3C+E
4C+E
6C+E
8C+E
10C+E
12C+E
15C+E
20C+E
25C+E
30C+E
40C+E
50C+E
Product
Code
1031
1041
1051
1701
1901
1111
1131
1161
1211
1261
1311
1411
1511
- IEC 60502, IEC 60228, IEC 60332
- AS/NZS 5000.1, AS/NZS 3808, AS/NZS 1125, AS/NZS 1660, AS/NZS 3863
Conductor
Area mm²
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Core Over Avg.
Dia.
Bedding Dia. Cable Dia.
mm
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
mm
8.4
9.3
10.2
11.2
13.9
14.6
15.9
16.9
19.0
21.3
23.6
26.8
28.4
mm
13.1
14.1
15.1
16.6
20.0
20.7
22.2
23.2
26.2
28.6
31.1
34.6
37.1
Approx
Weight kg/km
313
360
413
528
771
835
949
1049
1392
1640
1910
2340
2837
Product
Code
1032
1042
1052
1702
1902
1112
1132
1162
1212
1262
1312
1412
1512
Conductor
Area mm²
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
Core
Dia.
mm
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
Over Avg.
Bedding Dia. Cable Dia.
mm mm
9.5
10.5
11.5
12.7
15.8
16.5
18.1
19.2
21.6
24.2
26.9
30.6
32.4
14.3
15.3
16.5
18.7
22.0
22.8
25.2
26.4
29.0
31.7
34.6
39.4
41.4
Approx
Weight kg/km
379
442
512
705
940
1028
1294
1439
1737
2038
2425
3228
3629
7 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
SDI Power Cable
Configuration
Conductor:
Inner Insulation:
Outer insulation:
Outer Insulation colour: plain annealed copper or plain aluminium (class 2 strands) of the type specified in AS/NZS 1125.
cross-linked polyethylene (XLPE).
flame retardant polyvinyl chloride PVC V90.
Standard - Orange
Optional - Black (Ultraviolet radiation stabilised)
Technical data
Rated voltage:
Conductor operating temp:
Minimum bending radius:
0.6 / 1 kV
- 40 o
C ~ 90 o
C, short circuit: 250 o
C for 5 sec
Stranded conductors 9 x cable O.D during installation
6 x cable O.D after installation
--The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
--The cables should not be flexed when either the ambient or cable temperature is below 0 o
C
Standards:
International:
Australian/New Zealand
Nominal
CSA mm²
70
95
120
150
185
240
300
6
10
16
25
35
50
- IEC 60228, IEC 60332-1
- AS/NZS 5000.1, AS 1955, AS/NZS 3808, AS/NZS 1125, AS/NZS 1660
Cable
Dia.
mm
17.4
19.8
21.6
23.9
26.2
29.4
32.4
7.7
9.1
10.3
12.2
13.5
15.6
Product
Code
7806XV
7810XV
7816XV
7825XV
7835XV
7850XV
7870XV
7895XV
7812XV
7815XV
7818XV
7824XV
7830XV
Copper conductor
Weight kg/km
98.2
148.8
213.6
316.2
419.4
582.0
782.9
1044.1
1290.7
1600.4
1959.6
2514.1
3117.2
Aluminium conductor
Product Weight
Code kg/km
-
-
-
-
SMAL35
SMAL50
SMAL70
SMAL95
SMAL120
SMAL150
SMAL185
SMAL240
SMAL300
320
410
505
624
762
961
1176
-
-
-
-
180
241
9 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
Earth Wire
Configuration
Conductor:
Insulation:
Insulation colour: plain annealed copper or plain aluminium (class 2 strands) of the type specified in AS/NZS 1125.
polyvinylchloride compound PVC V90.
Green/Yellow
Technical data
Rated voltage:
Conductor operating temp:
Minimum bending radius:
0.6 / 1 kV
- 25 o
C ~ 90 o
C, short circuit: 160 o
C for 5 sec
12 x cable O.D
--The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
--The cables should not be flexed when either the ambient or cable temperature is below 0 o
C
--Thermoplastic 90 o
C PVC insulation is subject to deformation at temperature above 75 o
C.
Standards:
International
Australian/New Zealand
- IEC 60502, IEC 60228, IEC 60332
- AS/NZS 5000.1, AS/NZS 3808, AS/NZS 1125, AS/NZS 1660
Nominal
Conductor Area
(mm²)
70
95
120
150
185
240
300
16
25
35
50
4
6
10
Insulation
Thickness
(mm)
1.4
1.6
1.6
1.8
2.0
2.2
2.4
1.0
1.0
1.0
1.0
1.2
1.2
1.4
Cable
Dia.
(mm)
14.0
16.2
17.9
20.0
22.2
25.1
28.0
4.6
5.2
6.2
7.3
9.1
10.3
12.2
Copper
Product
Code
E2V70
E2V95
E2V120
E2V150
E2V185
E2V240
E2V300
E2V4
E2V6
E2V10
E2V16
E2V25
E2V35
E2V50
Approximate
Weight
(kg/km)
703
952
1186
1484
1830
2366
2949
52
73
113
171
266
361
514
Aluminium
Product
Code
-
-
-
-
E2V25A
E2V35A
E2V50A
E2V70A
E2V95A
E2V120A
E2V150A
E2V185A
E2V240A
E2V300A
Approximate
Weight
(kg/km)
270
364
444
556
686
881
1093
-
111
145
205
-
-
-
10 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
Supplementary Technical Information
A. Rated voltage designation
Voltage rating for low voltage power cable is expressed in the form Uo/U (Um), the voltage designation takes into consideration the fact that the system voltage may vary up to
9.1% from the designated voltage.
0.6/1kV (1.2kV): Uo = 0.6kV, U = 1kV, Um = 1.2kv
Uo
U
Um is the R.M.S power frequency voltage between phase conductor and earth conductor of the supply system.
is the R.M.S power frequency voltage between phases conductor of the supply system.
is the maximum R.M.S power frequency voltage between any two phases conductor for which cables are designed. It is the highest voltage that can be sustained under normal operating conditions at any time and at any point in a system. It excludes transient voltage variation due to fault condition and sudden disconnection of large load.
The rated voltage of the cable for a given application shall be suitable for the operating condition in the system.
B. Conductor materials characteristics:
Conductor Material
Type
Copper:
Conductivity
%
100
Resistivity at 20ºC n ¡ .m
17.07~17.24
Aluminium 61 28.264
Density g/cm
3
8.92
2.73
Temperature Constant
ºC
234.5
228.1
C. Conductor maximum d.c resistance at 20ºC and a.c resistance at 90ºC (Multi-core):
Nominal
Area mm²
Max. d.c resistance of conductor at 20ºC
Copper Aluminium
] / km ] / km a.c resistance of conductor at 90ºC
Copper Aluminium
] / km ] / km
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
13.6
7.41
4.61
3.08
1.83
1.15
0.7270
0.5238
0.3661
0.2604
0.1931
0.1528
0.1222
0.0991
0.0761
0.0611
-
-
-
-
-
-
1.20
0.8670
0.6061
0.4310
0.3196
0.2529
0.2023
0.1641
0.1260
0.1012
17.3
9.45
5.88
3.93
2.33
1.47
0.927
0.669
0.494
0.343
0.248
0.197
0.160
0.129
0.0998
0.0812
*Further conductor types and stranding configuration on request. Conductor compacted index is not less than 0.9.
-
-
-
-
-
-
-
1.11
0.822
0.569
0.411
0.325
0.265
0.212
0.162
0.131
D. Conversion factor for conductor temperatures:
Temperature Rating
ºC
20
Conversion Factor
Copper Aluminium
1.000
1.000
90
105
130
250
1.275
1.334
1.432
1.904
1.282
1.343
1.443
1.927
Conversion Example
50mm 2 Cable (Copper)
Max d.c resistance at 20ºC = 0.3661
¡ / km.
Conversion factor for 50mm 2 at 90ºC = 1.275
Max d.c resistance at 90ºC = 0.3661
¡ / km * 1.275 = 0.4668
¡ / km
1.5
1.4
1.3
1.2
1.1
1
2
1.9
1.8
1.7
1.6
Conversion Factor vs. Conductor Temperature
Copper
Aluminium
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 105 130 250
Temperature ºC
11 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
E. Conductor three phase voltage drop* at 50Hz. 90ºC (mV/A.m)
Nominal Area mm 2
150
185
240
300
50
70
95
120
10
16
25
35
1.5
2.5
4
6
Max
0.87
0.61
0.45
0.37
0.31
0.26
0.22
0.19
30.0
16.4
10.2
6.8
4.05
2.55
1.61
1.17
Copper
0.8 power factor
-
-
0.22
0.19
-
-
-
-
-
-
-
-
-
-
-
-
*Single phase voltage drop is multiplying the three phase values by 1.155.
Max
1.43
0.993
0.723
0.577
0.476
0.388
0.307
0.258
-
-
-
1.93
-
-
-
-
Aluminium
0.8 power factor
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
F. Cable reactance at 50Hz ( ¡ /km)
Nominal Area mm 2
150
185
240
300
50
70
95
120
10
16
25
35
1.5
2.5
4
6
PVC insulated
Max
-
-
-
-
0.0797
0.0770
-
-
0.111
0.102
0.102
0.0967
0.0906
0.0861
0.0853
0.0826
XLPE insulated
Max
-
-
0.0725
0.0713
0.0718
0.0720
0.0709
0.0704
-
-
-
-
-
-
-
-
12 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
G. Current carrying capacity
The current rating given in this catalogue has been calculated using the method described in IEC 60287 - Calculation of the current rating (All parts), and based on typical Australia installation condition:
Lay in air:
Lay in ground:
Lay in conduits:
Other conditions:
Ambient air temperature 40 o
C
Ambient soil temperature 25 o
C,
Specific thermal resistivity 1.2 K.m/W, Buried depth 0.75 ~ 0.8m
The current carrying capacity will be reduced by approximate 15 ~ 25%.
Balance load, Unexposed to the direct sunlight.
Multi - Core cables current rating
Nominal
Phase
CSA mm 2
120
150
185
240
300
35
50
70
95
6
10
16
25
1.5
2.5
4
Insulated
Material
PVC
PVC
PVC
XLPE
XLPE
XLPE
XLPE
XLPE
XLPE
PVC
PVC
PVC
PVC
PVC
PVC
PVC
360
410
475
560
640
130
160
200
310
18
26
34
44
60
80
105
Cu
A
Unenclosed
Touching
Al
A
280
320
370
440
510
100
125
155
240
-
-
-
-
-
-
-
3G(2C+E) - 2 loaded
Buried direct
Cu
A
Al
A
410
460
520
600
680
180
210
260
360
28
40
52
65
87
115
145
320
355
405
470
530
140
165
200
280
-
-
-
-
-
-
-
325
375
425
500
570
140
165
205
285
22
31
40
51
68
88
115
Cu
A
Buried in conduit
Al
A
255
290
330
390
450
110
130
160
220
-
-
-
-
-
-
-
305
350
405
480
550
110
135
170
265
37
51
68
91
15
22
29
4G(3C+E) or 5G(3C+N+E) - 3 loaded
Unenclosed Buried Buried touching direct in conduit
Cu
A
Al
A
Cu
A
Al
A
Cu
A
Al
A
240
270
315
375
430
87
105
135
205
-
-
-
-
-
-
-
345
385
435
500
570
150
180
220
300
24
34
44
55
74
96
125
265
300
340
395
445
115
140
170
235
-
-
-
-
-
-
-
275
310
355
420
475
115
140
175
240
43
57
74
96
19
26
34
215
240
280
330
375
91
110
135
185
-
-
-
-
-
-
-
Fault Current
Rating
Cu kA
Al kA
5.01
7.15
10.02
13.59
17.17
21.46
26.47
34.34
42.93
0.21
0.36
0.57
0.86
1.43
2.29
3.58
3.31
4.73
6.62
8.98
11.35
14.18
17.49
22.69
28.37
-
-
-
-
-
-
-
Single - Core & SDI cables current rating
Copper conductor
Nominal Area
Touching (laid flat) mm²
A
6
40
10
54
Enclosed in duct (trefoil)
Touching (laid flat)
Enclosed in duct (trefoil)
A
A
A
34
47
42
47
65
58
62
86
78
16
72
25
97
87
115
110
35
120
100
145
125
50
145
70
185
125
175
155
155
225
190
95
230
185
280
230
120
265
220
325
270
150
310
185
355
250
375
310
285
435
355
240
425
300
490
340
520
420
390
600
485
Aluminium conductor
Nominal Area
Touching (laid flat)
Enclosed in duct (trefoil) mm²
A
A
6
-
-
10
-
-
16
-
-
25
-
-
35
110
105
50
135
125
70
175
160
95
215
195
120
255
230
150
290
260
185
340
300
240
405
360
300
470
415
13 www.wwcables.com.au
World Wire Cables
VIPERCON ELECTRIC CABLE
H. Current rating factor.
1. Depth of laying rating factor
Nominal Area
0.8m
1m
Conductor area vs. Depth (Laid direct in ground)
1.25m
1.5m
1.75m
2m
300 mm² 1 0.98
0.96
0.95
0.94
0.92
2.5m
0.91
+3m
0.90
2. The current carrying capacity of a cable will vary dependent on the installation condition and the cable surrounding condition.
(I) ambient air temperature conversion factor (II) ambient soil temperature conversion factor
Conversion Factor vs. Air Ambient Temperature
90ºC conductor temp.
80ºC conductor temp.
70ºC conductor temp.
Conversion Factor vs. Soil Ambient Temperature
90ºC conductor temp.
80ºC conductor temp.
70ºC conductor temp.
1.4
1.2
1.20
1.10
1
1.00
0.8
0.90
0.6
0.4
0.80
0.2
0.70
0 0.60
15 20 25 30 35 40 45
Temperature ºC
50 55 60 65 70 10 15 20 25
Temperature ºC
30 35 40
Note: the current rating and the derating factor is referenced from AS/NZS 3008.1, please refer to AS/NZS 3008.1 or AS/NZS 3000 for current rating on other installation condition.
I. Cable testing criterias
The following test will be conducted at manufacturer's work, and testing method is in accordance with AS/NZS 1660 a. Cable construction test, sample test b. Conductor resistance test, routine test c. Insulation spark test (6kV a.c) d. Cable A.C withstand voltage test (3.5kV a.c /5 min.) e. Cable mechanical test, sample test on tensile strength, bending radius.
14 www.wwcables.com.au
World Wire Cables
CONFLEX ELECTRIC CABLE
Flexible SDI Power/Welding Cables
Applications
WW Cables' SDI Power / Welding Cables are for use in switchboard wiring, load banks, welding, battery leads, battery chargers, jumper leads, etc
Configuration
Conductor:
Inner Insulation:
Outer insulation:
Outer Insulation colour: plain annealed copper (class 5 strands) of the type specified in AS/NZS 1125.(Available in tinned copper on request) cross-linked polyethylene (XLPE). or flame retardant polyvinyl chloride PVC V90.
thermoplastic elastomer (TPE)
Standard - Orange
Optional - Black (Ultraviolet radiation stabilised)
Technical Data
Voltage Ranges:
Conductor operating temp:
0.6 / 1 kV
XLPE insulated: - 40 o
C ~ 90 o
C, short circuit: 250 o
C for 5 sec
V90 insulated: - 25 o
C ~ 75 o
C, Max 90 o
C, short circuit: 140 o
C for 5 sec
Minimum bending radius:
Maximum pulling tension:
7.5xcable O.D
20N/mm
2 x total cross-sectional area of phase conductor
-The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
--The cables should not be flexed when either the ambient or cable temperature is below 0 o
C
--Thermoplastic PVC V90 insulation is subject to deformation at temperature above 75 o
C.
Standards:
International:
Australian/New Zealand
Nominal Insulation
CSA mm²
Thickness mm
95
120
150
185
240
300
400
500
630
16
25
35
50
70
2.2
2.2
2.8
3.0
3.0
2.0
2.0
2.2
2.2
1.5
1.8
1.8
1.8
2.0
Cable
Dia.
mm
10.3
12.2
13.5
15.6
17.4
19.8
21.6
23.9
26.2
29.4
32.4
36.7
40.5
44.5
- IEC 60228, IEC 60332-1
- AS/NZS 5000.1, AS 1995, AS/NZS 3808, AS/NZS 1125, AS/NZS 1660
Product
Code
7816
7825
7835
7850
7870
7895
7812
7815
7818
7824
7830
7840
7850
7863
V90
Weight kg/km
216.8
328.5
431.2
582.0
794.0
1044.2
1286.5
1594.3
1929.6
2452.2
3018.0
4597.3
5696.7
7069.0
Current rating for fix installation
Product
Code
7816XT
7825XT
7835XT
7850XT
7870XT
7895XT
7812XT
7815XT
7818XT
7824XT
7830XT
7840XT
7850XT
7863XT
XLPE
Weight kg/km
201.6
305.9
405.4
552.0
754.9
999.7
1237.3
1533.9
1863.2
2377.5
2935.4
4329.5
5374.0
6684.6
3-phase voltage drop
(trefoil) mV/A.m
2.68
1.63
1.23
0.906
0.612
0.490
0.392
0.323
0.282
0.239
0.211
0.186
0.175
0.168
Max conductor
Resist.
At 20ºC
/km
1.21
0.780
0.554
0.386
0.272
0.206
0.161
0.129
0.106
0.0801
0.0641
0.0486
0.0384
0.0287
Currentrating of welding cables for 30sec period duty cycle
100%
A
60%
A
30%
A
25%
A
390
455
535
600
715
-
-
-
-
125
165
205
260
325
505
585
690
775
920
-
-
-
-
160
210
265
335
415
715
830
975
1095
1305
-
-
-
-
225
300
375
475
590
245
330
410
520
645
780
910
1070
1200
1430
-
-
-
-
Nominal Area
Touching (laid flat)
Enclosed in duct (trefoil)
Touching (laid flat)
Enclosed in duct (trefoil) mm²
A
A
A
A
16
72
62
86
78
25
97
87
115
110
35
120
100
145
125
50
145
125
175
155
70
185
155
225
190
95
230
185
280
230
120
265
220
325
270
150
310
250
375
310
185
355
285
435
355
240
425
340
520
420
300
490
390
600
485
400
570
455
700
560
500
660
530
810
650
630
760
620
940
760
20 www.wwcables.com.au
World Wire Cables
CONFLEX ELECTRIC CABLE
300/500V Flexible Control Cables
Applications
WW Cables' CONFLEX PVC Flexible Control Cables are manufactured for use as control and connecting cables in machine tools, machinery production lines, conveyer belts, airconditioning, and in all general production lines. The cables can be installed in dry, moist and wet indoor area and handling apparatus for low mechanical stress (ensuring the freemovement without tensile stress or forced movements).
The copper braiding screened EMC control cable is suitable for installation in the internal electric circuits and the environment where the protection from electromagnetic inferences is required.
Standard references
IEC 60228
VDE 0245
VDE 0295
VDE0293
AS/NZS 1125
AS/NZS 3808
- Conductors of insulated cables
- Flexible PVC-insulated control cable
- Conductors of cables, wires and flexible cords for power installation
- Core identification for cables and flexible cords used in power installation
- Conductor in insulated electric cables and flexible cords
- Insulating and sheathing materials for electric cables
Configurations
Conductor:
Insulation:
Filler:
Bedding:
Screen:
Sheath:
Sheath identification
Unscreened Control Cable plain annealed copper, class 5 fine wires stranded flame retardant polyvinyl chloride PVC V75 non-hygroscopic material flame retardant polyvinyl chloride PVC V75
flame retardant polyvinyl chloride PVC V75
Grey
- Also available with PUR or Low Smoke & Halogen Free sheath.
EMC Control Cable plain annealed copper, class 5 fine wires stranded flame retardant polyvinyl chloride PVC V75 non-hygroscopic material flame retardant polyvinyl chloride PVC V75 tinned annealed copper braid ( 82%) flame retardant polyvinyl chloride PVC V75
Transparent
Core identification: Phase core: Black core with white numbering, Earth: Green/Yellow
Technical data:
Rated voltage:
Test voltage:
Conductor operating temp:
Short circuit temp:
Minimum bending radius:
300 / 500V
1500V rms between conductors, between conductors and screen
4000V rms spark test
Static:
Flexing:
During installation:
140 o
C for 5 sec
-25 o
C ~ 75 o
C
-5 o
C ~ 70 o
C
-5 o
C ~ 70 o
C
Flexing - 7.5xcable O.D
Static - 5xcable O.D
Nominal
Area mm²
0.5
0.75
1
1.5
2.5
Max. wires Dia.
Fine-wire strand mm
0.20
0.20
0.20
0.25
0.25
Conductor
Diameter mm
0.85
1.16
1.34
1.64
2.12
Core
Diameter mm
1.8
1.9
2.3
2.6
3.1
Conductor d.c.
resistance at 20ºC
¡ / km
39.0
26.0
19.5
13.3
7.98
Specific insulation
Resistance
G ¡ .cm
>20
>20
>20
>20
>20
Current carrying
Capacity
A
8
11
13
16
23
-- Further conductor types and stranding configuration on request.
-- Current rating is calculated based on ambient air temperature at 25 o
C.
-- The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
-- The cables should not be flexed when either the ambient or cable temperature is below 0 o
C.
-- Thermoplastic PVC V75 insulation is subject to deformation at temperature above 70 o
C.
21 www.wwcables.com.au
World Wire Cables
CONFLEX ELECTRIC CABLE
2C
2C
2C+E
11C+E
13C+E
15C+E
17C+E
19C+E
20C+E
24C+E
29C+E
31C+E
33C+E
3C
4C
4C+E
5C+E
6C+E
7C+E
8C+E
9C+E
35C+E
2C+E
3C
4C
4C+E
7C
6C+E
11C+E
17C+E
2275
7301
2375
1275
1475
1675
1875
2075
2175
2575
3075
3275
3475
7304
7309
9575
2607
9775
2807
2907
1007
3675
2310
7305
7310
9510
7312
9710
1210
1810
300/500V Flexible Control Cables
Unscreened PVC flexible control cable
Product
Code
2550
3005
3205
3405
3605
4005
2905
1005
1250
1405
1605
1850
2005
2105
7303
7308
9550
2605
9750
2805
No. of
Core
3C
4C
4C+E
5C+E
6C+E
7C+E
8C+E
9C+E
11C+E
13C+E
15C+E
17C+E
19C+E
20C+E
24C+E
29C+E
31C+E
33C+E
35C+E
39C+E
Nominal Area mm²
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Cable Diameter mm
13.1
13.1
14.6
14.6
16.7
16.7
10.2
11.6
11.6
11.6
8.3
8.7
9.6
9.6
5.2
5.6
6.1
6.8
6.8
8.3
Cable Weight kg/km
270.1
305.2
342.6
356.6
405.1
433.2
101.1
112.2
135.3
149.4
170.4
201.0
215.0
222.1
40.5
48.0
56.9
69.5
76.5
94.1
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.6
5.6
5.6
11.4
11.4
12.1
13.8
13.8
13.8
15.5
15.5
17.3
17.3
7.7
9.8
9.8
10.3
5.6
6.2
7.0
7.7
19.2
8.5
8.5
12.4
15.0
6.1
6.1
6.8
7.6
36.9
36.9
46.8
190.2
210.0
239.5
282.5
302.3
312.2
379.7
429.1
481.6
501.4
46.8
61.1
76.3
92.5
102.3
132.2
142.1
157.8
542.1
57.9
57.9
75.7
94.4
126.9
126.9
235.2
349.5
No. of
Core
24C+E
35C+E
8C+E
9C+E
11C+E
13C+E
15C+E
17C+E
19C+E
2C
2C+E
3C
3C+E
4C+E
5C+E
6C+E
7C+E
20C+E
24C+E
29C+E
31C+E
33C+E
35C+E
39C+E
40C+E
49C+E
2C+E
3C
3C+E
13C+E
15C+E
17C+E
19C+E
20C+E
24C+E
29C+E
31C+E
33C+E
35C+E
4C
4C+E
5C+E
6C+E
7C+E
8C+E
9C+E
11C+E
39C+E
49C+E
Product
Code
2510
3610
2925
1024
1224
1425
1625
1824
1925
7302
2325
7307
2452
9525
2625
2726
2825
2125
2526
2925
3225
3425
3625
3925
4125
4925
2315
7306
2415
1415
1615
1815
1915
2115
2515
3014
3215
3415
3615
7311
9515
2615
9715
2815
2915
1014
1215
3915
4916
Nominal Area mm²
1.0
1.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Cable Weight kg/km
448.5
694.1
395.8
439.4
529.6
587.5
670.2
787.2
845.2
101.6
130.6
130.6
170.7
213.1
258.0
287.0
366.8
874.2
1061.1
1206.0
1347.0
1405.0
1593.2
1709.2
1738.2
2070.0
79.3
79.3
103.6
356.7
406.9
478.1
513.2
530.7
644.3
732.0
817.9
853.0
967.7
103.6
129.4
156.7
174.2
222.8
240.4
266.9
321.6
1037.9
1256.7
Cable Diameter mm
16.9
21.6
14.7
15.3
16.7
16.7
17.7
19.8
19.8
11.0
12.0
12.0
14.7
8.9
8.9
8.9
9.7
19.8
22.0
22.0
24.3
24.3
27.6
27.6
27.6
29.2
7.3
7.3
7.9
13.5
14.3
15.2
15.9
15.9
17.6
17.6
19.5
19.5
22.0
11.9
11.9
12.4
13.5
7.9
8.6
9.5
9.5
22.0
23.2
22 www.wwcables.com.au
World Wire Cables
CONFLEX ELECTRIC CABLE
8221
8222
8224
8225
8226
8227
8228
8229
8230
8231
8232
8233
8234
8223
8216
8217
8218
8219
8220
300/500V Flexible control cables
Screened PVC flexible EMC control cable
8206
8207
8208
8209
8210
8211
8212
8213
8214
8215
Product
Code
8200
8201
8202
8203
8204
8205
3C+E
6C+E
11C+E
17C+E
2C+E
3C+E
6+E
11C+E
17C+E
24C+E
No. of
Core
2C+E
3C+E
4C+E
6C+E
11C+E
24C+E
1.0
1.0
1.0
1.0
1.0
1.0
0.75
0.75
0.75
0.75
Nominal Area mm²
0.5
0.5
0.5
0.5
0.5
0.5
2C+E
3C+E
4C+E
6C+E
11C+E
24C+E
2C+E
3C+E
4C+E
5C+E
6C+E
7C+E
8C+E
9C+E
11C+E
13C+E
15C+E
17C+E
19C+E
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.5
1.5
1.5
1.5
1.5
1.5
7.9
8.7
9.6
10.5
10.5
13.2
13.2
13.9
15.3
15.3
16.2
18.6
18.6
6.5
7.1
7.8
8.5
11.9
16.0
Over bedding Diameter mm
4.8
5.2
5.7
6.2
8.5
11.1
5.9
7.1
9.8
11.6
5.8
6.4
7.6
10.6
12.6
14.2
10.7
11.9
13.0
14.0
14.0
16.8
16.8
17.5
19.1
19.1
20.0
22.5
22.5
9.1
9.7
10.4
11.1
15.3
19.6
Cable Diameter mm
7.6
8.1
8.6
9.1
11.6
14.4
8.5
9.7
13.0
15.0
8.0
8.6
10.0
13.4
15.4
17.7
153.3
180.9
211.1
262.6
480.9
837.6
206.4
262.1
313.2
364.9
383.5
511.2
529.9
576.9
704.7
742.0
827.4
977.7
1015.0
Cable Weight kg/km
89.5
105.8
119.7
147.9
228.9
383.6
121.2
163.0
292.6
393.2
125.9
146.4
201.2
343.4
479.5
604.8
23 www.wwcables.com.au
World Wire Cables
CONFLEX ELECTRIC CABLE
0.6/1kV Flexible Heavy Duty PVC Cable
Application
WW CABLES' Heavy Duty PVC flexible cables are manufacture based on AS 3191 with Electrical approval No. V99412. The cables are mainly for use as extension leads or light appliance leads.
Standard references
AS/NZS 3191:
AS/NZS 1125:
AS/NZS 3808:
IEC 60228:
Electric flexible cords
Conductor in insulated electric cables and flexible cords
Insulating and sheathing materials for electric cables
Conductors of insulated cables
Configuration
Conductor
Insulation
Sheath
- Fine wire stranded (Class 5) plain annealed copper to AS1125, IEC 60228
- The conductor is insulated with a continuous self-extinguish and flame retardant heavy duty PVC type V75 sheath to AS 3808.
- Continuous self-extinguish and flame retardant heavy duty PVC type V75 sheath to AS 3808.
Cable marking Imprint on cable
Technical data
Temperature at conductor:
Short circuit temperature
Temperature at surface:
Rated voltage:
Minimum bending radius:
Pulling tension strength:
Core colour code:
-25 o
C ~ 75 o
C
160 o
C
+5 o
C ~ 75 o
C
0.6 / 1kV
4 x Cable O.D for fixed used
6 x Cable O.D for flexible used (not under tension)
The safety pulling tension should be limited to 20N/mm
2 of the total cross-sectional area of conductor
Brown, Blue, Green/Yellow
Part
No
1315
Nominal CSA mm²
1.5
Conductor Strands mm
30/0.25
Core Dia.
mm
3.01
Cable Dia.
mm
10.05
Cable Weight kg/100m
14.50
Max. d.c Resistance
¡ /km
13.3
Current rating
A
16
Cable Sheath Colour:
22 - Red, 24 - Yellow, 26 - Violet, 28 - Grey, 30 - Orange,
Note: Thermoplastic PVC V75 insulation is subject to deformation at temperature above 75 o
C.
32 - Pink, 34 - Dark Blue.
24 www.wwcables.com.au
World Wire Cables
CONFLEX ELECTRIC CABLE
Flexible Automotive Cables
Application
WW Cables' Automotive Cables are manufactured for general purpose automotive applications. They are suitable for Low Voltage, High Current use.
Temperature at conductor: -25 o
C ~ 75 o
C
Temperature at surface: +5 o
C ~ 75 o
C
FIGURE 8 AUTOMOTIVE CABLE
Configuration
Flexible stranded plain or tinned annealed copper conductor covered with PVC V75 sheath.
Core identifications - Red/Red with trace or Red/Black (other by request)
Product
Code
2163
2263
Industry Standard
Size mm
3
4
Cond.
Strands
No./mm
16 / 0.30
25 / 0.30
Insulation
Thickness mm
0.6
0.6
Cable Avg
Dia.
mm
2.8 x 6.0
3.2 x 6.6
Approx
Weight kg/km
32.5
49.1
Max. d.c.
Resistance
/ km
15.76
9.70
Current
Rating
A
10
15
TWIN SHEATHED AUTOMOTIVE / MARINE CABLE
Configuration
Flexible stranded plain or tinned annealed copper conductor covered with PVC V75 sheath
Core identifications - Red/Black.
Product
Code
3163
3263
3413
3653
Industry Standard
Size mm
5
6
3
4
Cond.
Strands
No./mm
16 / 0.30
26 / 0.30
41 / 0.30
65 / 0.30
Insulation
Thickness mm
0.4
0.4
0.6
0.6
Cable Avg
Dia.
mm
6.6 x 3.2
7.3 x 3.5
8.6 x 4.2
9.8 x 4.7
Approx
Weight kg/km
40.3
60.5
86.5
138.5
Max. d.c.
Resistance
/ km
15.76
9.70
6.15
3.88
Current
Rating
A
10
15
27
31
TRAILER CABLE
Configuration
Flexible stranded plain or tinned annealed copper conductor covered with PVC V75 sheath.
Product
Code
3593
5163
3793
7163
Number
Of
Core
7
7
5
5
Cond.
Insulation
Strands Thickness
No./mm mm
9 / 0.30
16 / 0.30
9 / 0.30
16 / 0.30
0.4
0.4
0.4
0.4
Sheath
Thickness
Mm
0.6
0.6
0.6
0.6
Cable Avg
Dia.
mm
6.2
7.2
7.0
8.2
Approx
Weight kg/km
63.3
90.2
81.2
119.7
Max. d.c.
Resistance
/ km
28.02
15.76
28.02
15.76
Current
Rating
A
5
10
5
10
Core Identifications: 5 Core - White, Yellow, Brown, Red, Green,
7 Core - White, Yellow, Brown, Red, Green, Black, Blue
Note: WW Cables' Automotive Cables are not to be regarded as power cables or for the direct connection of equipment to main power supplies or low impedance source.
25 www.wwcables.com.au
World Wire Cables
CONFLEX ELECTRIC CABLE
Flexible Single Core Cables
Application
WW Cables' single core flexible cables are mainly used for the wiring of communication electronic and allied equipment, as well as the internal wiring of switchboards.
Configuration
Conductor:
Insulation: plain annealed copper or tinned annealed (class 5 strands) of the type specified in AS/NZS 1125.
polyvinylchloride compound PVC V90.
-- Full range of sheath colours and striping available on request
Technical data
Rated voltage:
Conductor operating temp:
Minimum bending radius:
0.5mm
2
1.5mm
2
~ 1mm
2
~ 10mm
: 240 V
2
: 0.6 / 1 kV
- 25 o
C ~ 90 o
C, short circuit: 160 o
C for 5 sec
5 x cable O.D
--The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions.
--The cables should not be flexed when either the ambient or cable temperature is below 0 o
C
--Thermoplastic PVC V90 insulation is subject to deformation at temperature above 75 o
C.
Standards:
International
Australian/New Zealand
Code
- IEC 60502, IEC 60228, IEC 60332
- AS/NZS 5000.1, AS/NZS 3808, AS/NZS 1125, AS/NZS 1660
Nominal
Conductor Area mm²
Conductor
Strands
No. / mm
Cable
Dia.
mm
Approx.
Weight kg/km
Current
Rating
A
7005
7075
7100
7150
7250
7400
7600
7700
0.50
0.75
1.00
1.50
2.50
4.00
6.00
10.00
16 / 0.20
24 / 0.20
32 / 0.20
30 / 0.25
50 / 0.25
56 / 0.30
84 / 0.30
77 / 0.40
2.1
2.4
2.5
3.0
3.7
4.6
5.2
6.2
10
13
15
22
33
53
73
113
3
7
9
12
20
25
40
65
Conductor d.c.
resistance at 20ºC
/ km
40.1
26.7
20.0
13.7
8.21
5.09
3.39
1.95
Cable
Packing
100m / spool or 500m / drum
100m / spool or 500m / drum
100m / spool or 500m / drum
100m / spool or 500m / drum
100m / spool or 500m / drum
100m / spool or 500m / drum
100m / spool or 500m / drum
100m / spool or 500m / drum
Cable Sheath Colour:
20 – Green/Yellow
21 – Black
22 - Red
23 – Blue
24 – Yellow
25 – Green
26 – Violet
27 – Brown
28 – Grey
29 – White
30 – Orange
31 – Dark Blue
32 – Pink
33 – Light Pink
34 – Dark Blue
26 www.wwcables.com.au
World Wire Cables
VIPERHITEMP HALOGEN-FREE CABLE
Single Core (Glass Braid) Single Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth
Standard references
IEC 60228
VDE 0295
AS/NZS 1125
AS/NZS 3808
- Conductors of insulated cables
- Conductors of cables, wires and flexible cords for power installation
- Conductor in insulated electric cables and flexible cords
- Insulating and sheathing materials for electric cables
34 www.wwcables.com.au
World Wire Cables
VIPERHITEMP HALOGEN-FREE CABLE
300 / 500V Silicone Flexible Halogen Free Cables: Single-Core (180 o
C)
Applications
WW Cables' VIPERHITEMP Silicone Flexible Cables are manufactured for use as wiring of domestic electrical heating application, lighting or industrial wiring for hot environments.
Silicone flexible cables with coated synthetic reinforcing braid have excellent mechanical strength.
Configuration
Conductor:
Insulation:
Sheath:
Sheath identification
Cables without braid reinforcement plain annealed copper, class 5 fine wires stranded
Silicone rubber
All colour
Cable with braid reinforcement plain annealed copper, class 5 fine wires stranded
Silicone rubber
Coated fibre glass reinforcing braid
All colour
Technical data*:
Voltage Ranges:
Test voltage:
Conductor operating temp:
Short circuit temp:
300V / 500V
1500V
-60 o
C ~ +180 o
C
+200 o
C
Minimum bending radius: 5 x cable O.D
*Further conductor types and stranding configuration on request.
*The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions
Product
Code
8805
8810
8815
8825
8805NB
8810NB
8815NB
8825NB
Nominal
Area mm²
0.5
1
1.5
2.5
0.5
1
1.5
2.5
Max. wires Dia.
Fine-wire strand mm
0.20
0.20
0.25
0.25
0.20
0.20
0.25
0.25
Conductor
Diameter mm
0.85
1.34
1.64
2.12
0.85
1.34
1.64
2.12
Insulation
Thickness mm
0.6
0.6
0.7
0.8
0.6
0.6
0.7
0.8
Cable Overall
Diameter mm
2.0
2.8
3.1
3.5
2.4
2.8
3.3
3.9
Cable Approx.
Weight kg/km
8.6
14.0
20.3
31.9
8.1
15.6
21.0
31.4
Conductor d.c.
resistance at 20ºC
¡ / km
39.0
19.5
13.3
7.98
39.0
19.5
13.3
7.98
Reinforcing braid
-
-
-
-
Cable Sheath Colour:
20 – Green/Yellow
21 – Black
22 – Red
23 – Blue
24 – Yellow
25 – Green
26 – Violet
27 – Brown
28 – Grey
29 – White
30 – Orange
31 – Dark Blue
32 – Pink
33 – Light Pink
34 – Dark Blue
35 www.wwcables.com.au
World Wire Cables
VIPERHITEMP HALOGEN-FREE CABLE
300 / 500V Nickel-plated Core Flexible Cables: Single-Core (500 o
C)
Applications
WW Cables' VIPERHITEMP Flexible Nickel-plated Cables are manufactured for use as wiring of heating elements, cartridges, bands and hot plates or heavy industry: foundries, steelwork and glassworks, etc.
Configurations
Conductor:
Insulation:
Sheath:
Sheath identification
Cable with braid reinforcement
Class 5 strands Nickel -plated copper
Several mineral-impregnated glass lapping tapes
Silicone -coated mineral fibre braid
Standard colour: White
Any colour is available on request
Product
Code
8810N5
8815N5
8825N5
8804N5
8806N5
Nominal
Area mm²
1
1.5
2.5
4
6
Max. wires Dia.
Fine -wire strand mm
0.20
0.25
0.25
0.30
0.30
Conductor
Diameter mm
1.34
1.64
2.12
2.66
3.39
Cable Overall
Diameter mm
3.98
4.17
4.77
5.32
5.81
Cable Approx.
Weight kg/km
17.9
25.9
37.8
57.7
83.2
Conductor d.c.
resistance at 20ºC
¡ / km
20.0
13.9
8.21
5.09
3.40
Technical data:
Rated voltage:
Test voltage:
300 / 500V
2000V
Conductor operating temp: -60 o
C ~ +450 o
C, Peaks at: 500
-- Further conductor types and stranding configuration on request.
o
C
-- The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions
36 www.wwcables.com.au
World Wire Cables
VIPERHITEMP HALOGEN-FREE CABLE
Silicone Flexible Halogen Free Cables (Cords): Multi-Core
Applications
WW Cables' VIPERHITEMP Silicone Flexible Cables are manufactured for use as wiring in metal industry, glassworks, lighting, and in hot environment up to 180 o
C.
Configuration
Conductor:
Insulation:
Sheath:
Sheath identification
Tinned annealed copper, class 5 fine wires stranded
Silicone rubber
Silicone rubber
Black
Core identification:
2 core and earth, 3 Core and earth, 4 core and earth:
Cords (0.75mm
2 ~ 2.5mm
2 ) to AS/NZS 3191:
Active cores: Brown, White, Black
Cables (4.0 mm 2 and above) to VDE0293:
Neutral core:
Active cores: Brown, Grey, Black
6 cores and above:
Active cores: Black core with white numbering
Neutral core:
Blue
Blue
Earth core:
Earth core:
Green/Yellow
Green/Yellow
Earth core: Green/Yellow
6875
6975
6675
6810
6910
6710
6610
6615
6815
6915
6715
6515
6215
6219
6825
6925
6625
6725
6225
6226
Technical data*:
Voltage Ranges:
Test voltage:
Conductor operating temp:
Short circuit temp:
Minimum bending radius:
Cords: 450V / 750V, Cables: 600V / 1000V
2000V
-60 o
C ~ +180 o
C
+200 o
C
5 x cable O.D
*The maximum conductor temperatures specified are based on the properties of the insulation material but in practice may need to be derated to take account of joints and terminations and environmental conditions
Product
Code
Nominal
Area mm²
Number of cores
Max. wires
Diameter mm
Core
Diameter mm
Cable Overall
Diameter mm
Cable Approx.
Weight kg/km
Conductor d.c.
Resistance at 20ºC
¡ / km
6840
6640
6540
6659
6660
6661
4
6
4
4
6
6
1
1
1.5
1.5
1.5
1.5
1.5
0.75
0.75
0.75
1
1
1.5
1.5
2.5
2.5
2.5
2.5
2.5
2.5
2C
2C+E
3C+E
2C
2C+E
3C+E
4C+E
2C
2C+E
3C+E
4C+E
6C+E
11C+E
18C+E
2C+E
3C+E
4C+E
6C+E
11C+E
18C+E
2C+E
3C+E
4C+E
2C+E
3C+E
4C+E
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.30
0.30
0.30
0.30
0.30
0.30
Conductor
Diameter mm
CORDS
1.34
1.34
1.64
1.64
1.64
1.64
1.64
1.16
1.16
1.16
1.34
1.34
1.64
1.64
2.12
2.12
2.12
2.12
2.12
2.12
CABLES
2.68
2.68
2.68
3.28
3.28
3.28
4.7
4.7
4.7
5.3
5.3
5.3
2.5
2.5
3.0
3.0
3.0
3.0
3.0
2.4
2.4
2.4
2.5
2.5
3.0
3.0
3.7
3.7
3.7
3.7
3.7
3.7
12.8
14.1
15.5
14.2
15.7
17.3
7.9
8.6
7.7
8.2
9.4
10.4
12.7
6.3
6.7
7.3
6.7
7.1
17.4
17.4
10.2
11.2
12.4
15.2
21.0
21.0
268.3
336.6
411.9
354.9
448.1
550.1
53.9
64.4
78.9
62.6
75.6
96.6
116.4
84.1
103.7
136.8
169.9
247.4
451.8
533.4
169.9
211.4
262.0
383.2
703.1
837.8
5.09
5.09
5.09
3.39
3.39
3.39
20.0
20.0
13.7
13.7
13.7
13.7
13.7
26.7
26.7
26.7
20.0
20.0
13.7
13.7
8.21
8.21
8.21
8.21
8.21
8.21
37 www.wwcables.com.au
World Wire Cables