Elevator Hoist Beam.JVA Response

advertisement

GH Phipps Construction Co.

5995 Greenwood Plaza Blvd. Suite 100

Greenwood Village CO 80111-4710

Subject: Elevator Hoist Beam

Project: Metro CareRing-Hunger Relief Center

Address: 1100 E 18th St

Denver CO 80203 Denver County

Phone: Fax:

To:

Joel Hermann

Barker Rinker Seacat & Architecture

From: GH Phipps Construction Co.

Brady McQuinn

Contact: Co-Author:

Reference:

Drawing:

Spec Section:

Discipline: All

Detail:

Page:

Request For Information

RFI-13J2024-0023

Printed On: 07/28/2014

Page 1 of 1

Date:

Job:

Required:

Est.Cost Impact: $

Est. Days Impact:

07/28/2014

13J2024

08/04/2014

Co-Author RFI Number:

Request

REF: S103 and Elevator Submittal (Otis)

On drawing S103 the elevator W 8x24 hoist beam is shown running North and South. The elevator submittal shows the elevator hoist beam running East and West. After speaking with Tim Thompson (Otis Elevator) it was confirmed that the hoist beam must run East and West to set the elevator side rails. Please provide new hoist beam size and any additional supporting details/embeds.

Suggestion

Answer Accept Suggestion

JVA Response:

Changing beam size is not necessary, a W8x24 will still work. The connections at bearing ends remain the same. Coordinate new dimensions with steel fabricator and/or Otis and also with the now perpendicular 10K1 (not 8K1) joist at roof.

Steve Carpenter - JVA, Inc. 07/28/14

Answered By:

Signed:

Date:

Distribution:

Subcontractors/Suppliers - Please respond back to GH Phipps Construction Co. within 7 calendar days from date of receipt regarding any cost or schedule impacts that are a result of this RFI.

pm3010

RFI 023- Elevator Hoist Beam

7'-10" min. rough opening at upper floor. 7'-0" clear opening.

7'-10" min. rough opening at lower floor. 7'-0" clear opening.

OK. No change to shaft dims. Otis concurs.

-BRS

- Elevator to be 8'-4" Clear

-

by 6'-0"

- Otis - please provide a sump pit location

Reference RFI #8 for sump pit.

-BRS

Sump pit 24"x24", centered in elevator pit.

Does the plate have to be continuous?

Does there need to be a plate if the walls are reinforced CMU?

Does the plate have to recessed into the wall?

Otis' answer is: No tube steel needed.

No plate is needed, but

CMU cells at sides of elevator to be grouted solid to accommodate attachments.

GHP: Please issue an RFI for these the new door and a change in the opening size for the elevator door itself.

Access door to be Type H, Hollow metal frame, 45 minute rated, with hardware group 9. Group 9 has been updated at the right:

Elevator door to be 3'-6" clear in lieu of 3'-0" as shown on drawings 4 & 8 on A501.

-BRS

HW 9

DOOR 202,

3 HINGE BB5000 450 652 BO

1 CLOSER 8616 AF86 FC 689(mount onDO

pull side)

1 STOREROOM LOCK C848D LRC 626 DO

1 STOP 1270WV 630 TR

1 KICKPLATE K0050 10x34 630 TR

1 SMOKE SEAL 5050B 17’ NG

Is a hatch better or a door?

Otis' answer is: It must be a door.

RFI 023- Elevator Hoist Beam