SIMULATION NO DEVICE 1 AC AIR CONDITIONER UTM NA 2 AHU AIR HANDLER UTM/TRANE TROUBLE ALARM UTM/TRANE SUPPLY FAN 1 FAIL 3 DFF DEWATERING FACILITY FAN UTM MOTOR OVERLOAD 4 TIT TEMPERATURE TRANSMITTER UTM NA 5 TSHL THERMOSTAT UTM NA 6 ULIT ULTRASONIC LEVEL TRANSMITTER HELIX/ZAK TANK FULL LEVEL Place a reflective surface at know distances from transmitter 6A HELIX/ZAK TROUBLE ALARM Simulate it from the Transmitter or breaking the analog loop by disconnecting wire 6B HELIX/ZAK A PROCESS VARIABLE 6C HELIX/ZAK TANK HIGH HIGH LEVEL CORTECH VFD FAIL CORTECH MOTOR HIGH TEMP Lower the setpoint trip temperature of the TSE relay module to below ambient temperature. Reset to 20-30 deg greater than ambient after test complete. CORTECH LOW SUCTION PRESSURE Option 1. If you can change trip pressure raise it to above the actual suction pressure until trips and then reset to desired trip pressure. Option 2. If you can't change (or won't), ensure there is liquid in the suction housing (can rig some flush water through cleanout port), run the pump at low speed and close the suction valve. If doesn't trip in 1-2 min (without flush), then reopen valve and investigate pressure switch. FACILITIES ENG LONG TRAVEL VFD TROUBLE 2A 7 IBPMP INDUSTRIAL WATER BOOSTER PMP 7A 7B 8 CRN BRIDGE CRANE PROVIDER RECOMMENDED SIMULATION ABBREV. FOR 8A FACILITIES ENG CROSS TRAVEL VFD TROUBLE 8B FACILITIES ENG HOIST MOTOR CONTROLLER TROUBLE SILO CAKE HANDLING HART Communicator Simulate using the transmitter or 4-20 ma loop generator or HART communicator Simulate using 4-20 ma loop or HART Simulate by removing the output wires from VFD LOW OIL LEVEL HPU HIGH OIL TEMP AT HPU 9B SCHWING SOFT START FAULT 9C SCHWING OIL HIGH PRESSURE AT HPU Change the set point to a lower value 9D SCHWING 24VDC TROUBLE Pull the fuse for 24VDC power supply 9E SCHWING DIRTY OIL FILTER #1 AT HPU Change the DP set point or simulate it with 4-20 ma loop 9F SCHWING DIRTY OIL FILTER #2 AT HPU Change the DP set point or simulate it with 4-20 ma loop 9G SCHWING SCREW FEEDER HIGH PRESSURE (JAMMED) Set the set point to a lower value 9H SCHWING SLIDE FRAME HIGH PRESSURE (JAMMED) Set the limit switch out of range 9I SCHWING AUTOMATIC GREASER FAULT Jumper the wires at Greaser 9J SCHWING PUMP S2 SPEED CHANGE Change the speed from HMI 9K SCHWING PUMP S3 SPEED CHANGE Change the speed from HMI 9L SCHWING 0% PUMP SPEED Change the speed from HMI 9M SCHWING 0% SCREW FEEDER SPEED COMMAND Change the speed from HMI 9N SCHWING 0% SLIDE FRAME SPEED COMMAND Change the speed from HMI 9O SCHWING SLIDE FRAME EXTENDED POSITION Manualy extend from the panel 9P SCHWING SLIDE FRAME RETRACTED POSITION Manulay Retract from the panel 9Q SCHWING SLIDE GATE OPENED Remote open and wait for feedback 9R SCHWING SLIDE GATE CLOSED Remote close and wait for feedback 9S SCHWING 0% PUMP INLET PRESSURE (AT PRESSURE TRANSMITTER) Use hand held programmer or transmitter itslef to simulate the displays 9T SCHWING 0% LEVEL AT RADAR LEVEL TRANSMITTER 1 Use hand held programmer or transmitter itself to simulate the displays 9U SCHWING 0% LEVEL AT RADAR LEVEL TRANSMITTER 2 Use hand held programmer or transmitter itself to simulate the displays 9V SCHWING RTD CPMP CENTRATE PUMP 10A 10B XYLEM VFD FAIL XYLEM MOTOR HIGH TEMP XYLEM LOW LOW WET WELL LEVEL UTM TROUBLE ALARM Jumper the wires on sensor Jumper the fault contact Verify that all RTD'S are reading close to each other. If one is different there is an issue. If possible remove the probe and apply heat, if not possible disconnect one wire and verify the loss of connection. Remove the output wires to simulate fault Unplug wire at controller Manually actuate the switch 11 CHR CHILLER 12 HTR HEATER COIL UTM NA 13 CVY CONVEYORS SCHWING VFD FAIL SCHWING MOTOR HIGH TEMP HELIX/ZAK GAS DETECTED ALARM Use manufacturer gas test kit HELIX/ZAK NO GAS DETECTED Use manufacturer gas test kit 13A 14 CGAT COMBUSTIBLE GAS DETECTOR 14A NO SIMULATION REQUIRED Remove the outgoing wires to motor from VFD and turn on VFD Disconnect the High Temp contact from MCC Use a hand pump calibrator 15 PDIT DIFFERENTIAL PRESSURE TRANSMITTER METPRO PROCESS VARIABLE (IF AVAILABLE) 16 ORPAIT ORP ANALOG TRANSMITTER METPRO TRANSMITTER TROUBLE Use ORP transmitter for simulation METPRO PROCESS VARIABLE (IF AVAILABLE) Use ORP transmitter for simulation METPRO TRANSMITTER TROUBLE Use ORP transmitter for simulation METPRO PROCESS VARIABLE (IF AVAILABLE) USE ph Transmitter for simulation MISCO OVERLOAD 18A MISCO REMOTE CURRENT TRIP 18B MISCO MOTOR HIGH TEMP 16A 17 PHAIT PH ANALOG TRANSMITTER 17A 18 GDR GRINDER By control panel manufacturer Remove the sensor from oil and verify the change of state SCHWING SCHWING 10 SCH Manually trip overload device in MCC bucket 9A 9 COMMENTS Manually trip overload device in MCC bucket Unplug wire at MCC By control panel manufacturer Lift L3 to create PHASE LOSS trouble. 19 MOVOC MOTOR OPERATED VALVES CSAMSCO TROUBLE 20 IF INLINE FAN DANIEL CO MOTOR OVERLOAD Manually trip overload device in MCC bucket 20A DANIEL CO MOTOR HIGH TEMP Unplug wire at controller 20B DANIEL CO LOW FLOW If possible manually activate switch. Jumper switch terminals Disconnect VFD output wires from terminal strip (current fail) 21 LPMP LUBRICATION PUMP SCHWING VFD FAIL 22 BCH BATTERY CHARGER HELIX/ZAK TROUBLE ALARM HELIX/ZAK LOW DC VOLTAGE 23 BSWI BATTERY DISCONNECT SWITCH HELIX/ZAK NA NO SIMULATION REQUIRED 24 MTS MANUAL TRANSFER SWITCH HELIX/ZAK NA NO SIMULATION REQUIRED 25 QC SWITCHGEAR QC HELIX/ZAK LINE A/B NORMAL 25A HELIX/ZAK LOW VOLTAGE 25B HELIX/ZAK BUS A TRIP 25C HELIX/ZAK BUS B TRIP 25D HELIX/ZAK TIE TRIP HELIX/ZAK TROUBLE ALARM 26A HELIX/ZAK LOW BATTERY VOLTAGE 26B HELIX/ZAK BYPASS 22A 26 UPS UNINTERRUPTABLE POWER SUPPLY 27 24F 24 VDC FAIL HELIX/ZAK NA NO SIMULATION REQUIRED 28 120F 120 VAC FAIL HELIX/ZAK NA NO SIMULATION REQUIRED 29 ATS AUTOMATIC TRANSFER SWITCH HELIX/ZAK NA NO SIMULATION REQUIRED 30 LT D/P LEVEL TRANSMITTER HELIX/ZAK PROCESS VARIABLE (IF AVAILABLE) 31 NGT NEUTROL GROUND TROUBLE HELIX/ZAK TROUBLE 32 RRA RIO REMOTE AND ALARMS HELIX/ZAK NA 33 PPMP T&D CAKE PISTON PUMP SCHWING LOW OIL LEVEL AT HPU Remove the sensor from oil and verify the change of state 33A SCHWING HIGH OIL TEMP AT HPU Jumper the wires on sensor 33B SCHWING SOFT START FAULT 33C SCHWING HIGH OIL PRESSURE Change the set point to a lower value 33D SCHWING 24 VDC TROUBLE Pull the fuse for 24VDC power supply 33E SCHWING HPU DIRTY OIL FILTER 1 Change the DP set point or simulate it with 4-20 ma loop 33F SCHWING HPU DIRTY OIL FILTER 2 Change the DP set point or simulate it with 4-20 ma loop 33G SCHWING SCREW FEEDER HIGH PRESSURE (JAMMED) Set the set point to a lower value 33H SCHWING AUTOMATIC GREASER FAULT Set the limit switch out of range 33I SCHWING PUMP S2 SPEED CHANGE Jumper the wires at Greaser 33J SCHWING PUMP S3 SPEED CHANGE Change the speed from HMI 33K SCHWING 0% PUMP SPEED COMMAND Change the speed from HMI 33L SCHWING 0% SCREW FEEDER SPEED COMMAND Change the speed from HMI 33M SCHWING DIVERTER GATE OPENED Simullate from HMI by open command 33N SCHWING DIVERTER GATE CLOSED Simulate from HMI by close command 33O SCHWING 0% PUMP INLET PRESSURE (AT PRESSURE TRANSMITTER) 33P SCHWING 0% LEVEL AT RADAR LEVEL TRANSMITTER 1 simulate using 4-20 ma loop generator or HART communicator or instrument 33Q SCHWING 0% LEVEL AT RADAR LEVEL TRANSMITTER 2 simulate using 4-20 ma loop generator or HART communicator or instrument WESTFALIA PROCESS VARIABLE (IF AVAILABLE) WESTFALIA TROUBLE 34 DAIT DENSITY ANALOG TRANSMITTER 34A Preferably use hand pump for pressure or Simulate from transmitter OR 4-20 ma loop simulator or HART NO SIMULATION REQUIRED Jumper the fault contact Use manual pressure source or simulate using HART Remote close and wait for feedback Use hand held programmer or transmitter itslef to simulate the displays Jumper flow switch contacts in field 35 FS FLOW SWITCH CORTECH & HELIX/ZAK FLOW SWITCH/CONTACT ON 36 PS PRESSURE SWITCH CORTECH & HELIX/ZAK PRESSURE SWITCH/CONTACT ON Use hand pump calibrator to raise pressure 37 PCPMP PROGRESSIVE CAVITY PUMPS CORTECH VFD TROUBLE Remove the output wires to simulate fault 37A CORTECH PRV FAIL TO CLOSE Prevent switch contact from being activated 37B CORTECH HIGH MOTOR TEMP Unplug wire at controller NO SIMULATION REQUIRED 38 ELP EMERGENCY LOADOUT PANEL HELIX/ZAK NA 39 DSPMP DUPLEX SUMP PUMP XYLEM OVERLOAD TRIP 39A XYLEM SEAL LEAK 39B XYLEM MOTOR HIGH TEMP Unplug wire at controller UTM MOTOR OVERLOAD Manually trip overload device in MCC bucket UTM LOW FLOW 40 OCF ODOR CONTROL FAN 40A if not available us a 4-20mA loop generator to simulate the signal from the field device wiring to the PLC module Join neutral with ground Manually trip overload device in MCC bucket Jumper contacts If possible manually activate switch. Jumper switch terminals NO SIMULATION REQUIRED 41 PSTFP POLYMER STORAGE TANK FILL PANEL HELIX/ZAK NA 42 PREF PUMP ROOM EXHAUST FAN OCSD FANS, HELIX TUB MOTOR OVERLOAD Manually trip overload device in MCC bucket EXISTING FANS, NEW TUB 43 PRSF PUMP ROOM SUPPLY FAN OCSD FANS, HELIX TUB MOTOR OVERLOAD Manually trip overload device in MCC bucket EXISTING FANS, NEW TUB 44 SD SMOKE DETECTOR HELIX/ZAK SMOKE DETECTION CONTACT ON Use spray can of smoke detector test aerosol 45 SFY SOLENOID OPERATED VALVE (OPEN/CLOSE) CSAMSCO NA 46 ULS ULTRASONIC LEVEL SWITCH HELIX/ZAK START LEAD PUMP LEVEL 47 BK BREAKER HELIX/ZAK TROUBLE 48 CPL CONTROL POWER LOST HELIX/ZAK CONTROL POWER LOST AT SW 49 ESL LOW VOLTAGE HELIX/ZAK LOW VOLTAGE AT SWITCHGEAR 50 XFMR TRANSFORMER HELIX/ZAK LOW OIL LEVEL HELIX/ZAK HIGH TEMP 50A Place a reflective surface at know distances from transmitter 50B HELIX/ZAK HIGH PRESSURE Use a hand pump calibrator 50C HELIX/ZAK SUDDEN PRESSURE Use a hand pump calibrator OCSD VFD FAULT OCSD LEAK DETECTION (IF APPLICABLE) 51 BPMP BLEACH PUMP 51A 52 LSL LEVEL SWITCH HELIX/ZAK SWITCH/CONTACT ON 53 MAG MAGNETIC FLOW METER HELIX/ZAK TROUBLE ALARM HELIX/ZAK PROCESS VARIABLE (IF AVAILABLE) 53A Disconnect VFD output wires from terminal strip (current fail) If possible add water in leak detection chamber to activate Level switch or Jumper contacts in the field Manually actuate the switch simulate from Flowmeter OR Disconnect 4-20 ma wires. Use a hart communicator OR simulate from Flowmeter itslef NO SIMULATION REQUIRED 54 MOVLOCFCP MOTOR OPERATED VALVE (LOCAL-OPEN-CLOSE-FCP) DANIEL CO NA 55 MOVOC-R MOTOR OPERATED VALVE (OPEN-CLOSE W/ REMOTE) CSAMSCO TROUBLE 56 PT PRESSURE TRANSMITTER SOME SCHWING AND SOME ZAK PROCESS VARIABLE (IF AVAILABLE) Use a hand pump calibrator 57 RLIT RADAR LEVEL TRANSMITTER SOME SCHWING AND SOME ZAK PROCESS VARIABLE (IF AVAILABLE) Place a reflective surface at know distances from transmitter 58 SFV SOLENOID OPERATED PNEUMATIC VALVE (O-C) SCHWING NA NO SIMULATION REQUIRED 59 ZS LIMIT SWITCH (OPEN-CLOSED) HELIX/ZAK CLOSE FIELD SWITCH/CONTACT ON Manually actuate the switch 60 CMAT CARBON MONOXIDE DETECTOR HELIX/ZAK NA NO SIMULATION REQUIRED 61 HGAT SOLENOID OPERATED PNEUMATIC HOPPER GATE SCHWING NA NO SIMULATION REQUIRED 62 TLC TRUCK LOADING CONSOLE HELIX/ZAK NA NO SIMULATION REQUIRED 63 SRPMP SCRUBBER RECIRCULATION PUMP METPRO MOTOR OVERLOAD Manually trip overload device in MCC bucket METPRO MOTOR HIGH TEMP Simulate High Temp alarm by disconnecting the high temp contact METPRO MOTOR OVERLOAD Manually trip overload device in MCC bucket METPRO MOTOR HIGH TEMP Simulate High Temp alarm by disconnecting the high temp contact HIGHLAND TANK PROCESS VARIABLE (IF AVAILABLE) 63A 64 FAEF FOUL AIR EXHAUST FAN 64A 65 FTLT FUEL TANK D/P LEVEL TRANSMITTER 66 DSFV DUAL SOLENOID PNEUMTIC VALVE 67 MTM MIXING TANK MIXERS (POLYMER) NA Philadelphia Mixing 67A 68 STM SLUDGE TANK MIXERS (BLEND TANKS) Philadelphia Mixing Simulate High Temp alarm by bdisconnecting the high temp contact VFD FAIL OVERTORQUE CONDITION 00 MAG EXISTING MAGNETIC FLOWMETER OCSD NO SIMULATION REQUIRED Simulate motor overload from MCC 68B SOLENOID OPERATED VALVE (CURRENT TO PRESSURE) Simulate from transmitter OR 4-20 ma loop simulator or HART MOTOR HIGH TEMP MOTOR HIGH TEMP SFVIP MAY BE OTHER SUPPLIERS MOTOR OVERLOAD 68A 69 Lift L3 to create PHASE LOSS trouble. Simulate the VFD trouble by disconnecting the outgoing power from VFD drive Simulate the High temp alarm by disconnecting the High temp contact. Simulate overtorque condition by changing overload current set point at vendor PLC/HMI TROUBLE ALARM PROCESS VARIABLE SUPPLIER RECOMMENDATION RECOMMENDATION STILL NEEDED