Transmission Lines We have obtained the following solutions for the steady-state voltage and current phasors in a transmission line: Loss-less line + − jβ z − jβ z V (z) = V e Lossy line + −γz − γz +V e ( 1 I (z) = V + e − jβ z − V − e jβ z Z0 V (z) = V e ) ( +V e 1 I (z) = V + e− γ z − V −e γ z Z0 ) Since V (z) and I (z) are the solutions of second order differential + − (wave) equations, we must determine two unknowns, V and V , which represent the amplitudes of steady-state voltage waves, travelling in the positive and in the negative direction, respectively. Therefore, we need two boundary conditions to determine these unknowns, by considering the effect of the load and of the generator connected to the transmission line. © Amanogawa, 2006 – Digital Maestro Series 65 Transmission Lines Before we consider the boundary conditions, it is very convenient to shift the reference of the space coordinate so that the zero reference is at the location of the load instead of the generator. Since the analysis of the transmission line normally starts from the load itself, this will simplify considerably the problem later. ZR New Space Coordinate z d 0 We will also change the positive direction of the space coordinate, so that it increases when moving from load to generator along the transmission line. © Amanogawa, 2006 – Digital Maestro Series 66 Transmission Lines We adopt a new coordinate d = − z, with zero reference at the load location. The new equations for voltage and current along the lossy transmission line are Loss-less line + jβd − − jβ d V (d) = V e I (d) = 1 Z0 ( Lossy line + γd − −γ d +V e + jβd V e − − jβ d −V e V (d) = V e ) I (d) = 1 Z0 ( +V e + γd V e − −γd −V e ) At the load (d = 0) we have, for both cases, V (0) = V + + V − ( 1 I (0) = V + −V − Z0 © Amanogawa, 2006 – Digital Maestro Series ) 67 Transmission Lines For a given load impedance ZR , the load boundary condition is V (0) = Z R I (0) Therefore, we have ( ZR V +V = V + −V − Z0 + − ) from which we obtain the voltage load reflection coefficient V− Z R − Z0 ΓR = + = Z R + Z0 V © Amanogawa, 2006 – Digital Maestro Series 68 Transmission Lines We can introduce this result into the transmission line equations as Loss-less line Lossy line + jβ d V (d) = V e + jβ d I (d) = V e Z0 ( 1+ ΓR e ( 1 − Γ Re −2 jβ d −2 jβ d ) ) + γd V (d) = V e + γd I (d) = V e Z0 ( 1+ ΓR e ( 1 − Γ Re −2 γ d −2 γ d ) ) At each line location we define a Generalized Reflection Coefficient Γ (d) = Γ R e−2 jβ d Γ (d) = Γ R e−2 γ d and the line equations become V (d) = V + e jβ d (1 + Γ (d) ) V (d) = V + e γ d (1 + Γ (d) ) V + e jβ d I (d) = (1 − Γ (d) ) Z0 V +e γd I (d) = (1 − Γ (d) ) Z0 © Amanogawa, 2006 – Digital Maestro Series 69 Transmission Lines We define the line impedance as 1 + Γ(d) V (d) Z (d) = = Z0 1 − Γ(d) I (d) A simple circuit diagram can illustrate the significance of line impedance and generalized reflection coefficient: ΓReq = Γ(d) d © Amanogawa, 2006 – Digital Maestro Series ZR Zeq=Z(d) 0 70 Transmission Lines If you imagine to cut the line at location d, the input impedance of the portion of line terminated by the load is the same as the line impedance at that location “before the cut”. The behavior of the line on the left of location d is the same if an equivalent impedance with value Z(d) replaces the cut out portion. The reflection coefficient of the new load is equal to Γ(d) Γ Req = Γ(d ) = Z Req − Z 0 Z Req + Z 0 If the total length of the line is L, the input impedance is obtained from the formula for the line impedance as Vin V (L) 1 + Γ(L) = = Z0 Z in = 1 − Γ(L) I in I (L) The input impedance is the equivalent impedance representing the entire line terminated by the load. © Amanogawa, 2006 – Digital Maestro Series 71 Transmission Lines An important practical case is the low-loss transmission line, where the reactive elements still dominate but R and G cannot be neglected as in a loss-less line. We have the following conditions: ω L >> R ω C >> G so that γ = ( jω L + R )( jω C + G ) = R G jω L jω C 1 + 1+ j ω L j ω C R G RG ≈ jω LC 1 + + − jω L jω C ω2 LC The last term under the square root can be neglected, because it is the product of two very small quantities. © Amanogawa, 2006 – Digital Maestro Series 72 Transmission Lines What remains of the square root can be expanded into a truncated Taylor series 1 R G + γ ≈ jω LC 1 + 2 j L j C ω ω 1 C L = R +G + jω LC 2 L C so that 1 C L α = R +G L C 2 © Amanogawa, 2006 – Digital Maestro Series β = ω LC 73 Transmission Lines The characteristic impedance of the low-loss line is a real quantity for all practical purposes and it is approximately the same as in a corresponding loss-less line R + jω L L Z0 = ≈ G + jωC C and the phase velocity associated to the wave propagation is ω vp = ≈ β 1 LC BUT NOTE: In the case of the low-loss line, the equations for voltage and current retain the same form obtained for general lossy lines. © Amanogawa, 2006 – Digital Maestro Series 74 Transmission Lines Again, we obtain the loss-less transmission line if we assume R=0 G=0 This is often acceptable in relatively short transmission lines, where the overall attenuation is small. As shown earlier, the characteristic impedance in a loss-less line is exactly real L Z0 = C while the propagation constant has no attenuation term γ = ( jω L)( jω C ) = jω LC = jβ The loss-less line does not dissipate power, because α = 0. © Amanogawa, 2006 – Digital Maestro Series 75 Transmission Lines For all cases, the line impedance was defined as V (d) 1 + Γ (d) Z (d) = = Z0 I (d) 1 − Γ (d) By including the appropriate generalized reflection coefficient, we can derive alternative expressions of the line impedance: A) Loss-less line 1 + Γ R e−2 jβd Z R + jZ 0 tan(β d) Z (d) = Z 0 = Z0 −2 jβd jZ R tan(β d) + Z 0 1 − Γ Re B) Lossy line (including low-loss) 1 + Γ R e −2 γ d Z R + Z 0 tanh( γ d) Z (d) = Z 0 = Z0 −2 γ d Z R tanh( γ d) + Z 0 1 − Γ Re © Amanogawa, 2006 – Digital Maestro Series 76 Transmission Lines Let’s now consider power flow in a transmission line, limiting the discussion to the time-average power, which accounts for the active power dissipated by the resistive elements in the circuit. The time-average power at any transmission line location is { 1 〈 P(d , t ) 〉 = Re V (d) I * (d) 2 } This quantity indicates the time-average power that flows through the line cross-section at location d. In other words, this is the power that, given a certain input, is able to reach location d and then flows into the remaining portion of the line beyond this point. It is a common mistake to think that the quantity above is the power dissipated at location d ! © Amanogawa, 2006 – Digital Maestro Series 77 Transmission Lines The generator, the input impedance, the input voltage and the input current determine the power injected at the transmission line input. Iin ZG VG Vin Generator © Amanogawa, 2006 – Digital Maestro Series Zin Line Zin Vin = VG ZG + Zin 1 Iin = VG ZG + Zin 1 * 〈 Pin 〉 = Re Vin Iin 2 { } 78 Transmission Lines The time-average power reaching the load of the transmission line is given by the general expression { } 1 〈 P(d=0 , t ) 〉 = Re V (0) I * (0) 2 + 1 1 = Re V (1 + Γ R ) * V + (1 − Γ R ) 2 Z0 ( * ) This represents the power dissipated by the load. The time-average power absorbed by the line is simply the difference between the input power and the power absorbed by the load 〈 P line 〉 = 〈 P in 〉 − 〈 P (d = 0 , t ) 〉 In a loss-less transmission line no power is absorbed by the line, so the input time-average power is the same as the time-average power absorbed by the load. Remember that the internal impedance of the generator dissipates part of the total power generated. © Amanogawa, 2006 – Digital Maestro Series 79 Transmission Lines It is instructive to develop further the general expression for the time-average power at the load, using Z0=R0+jX0 for the characteristic impedance, so that R0 + jX 0 R0 + jX 0 = * = = 2 * 2 Z0 Z0 Z0 R0 + X 02 Z0 1 Z0 Alternatively, one may simplify the analysis by introducing the line characteristic admittance 1 Y0 = = G0 + jB0 Z0 It may be more convenient to deal with the complex admittance at the numerator of the power expression, rather than the complex characteristic impedance at the denominator. © Amanogawa, 2006 – Digital Maestro Series 80 Transmission Lines * 0 〈 P(d=0, t ) 〉 = 1 Re V + 1+Γ R 1 V + 1−Γ Z 2 = V+ 2 Z0 = V+ 2 Z0 = V+ 2 Z0 = V+ 2 Z0 2 2 Re R0 + jX 2 0 R + jX Re 0 0 2 2 1+ Re Γ + j Im Γ R 2 2 2 2 R0 − R0 Γ R − 2 X 0 Im Γ © Amanogawa, 2006 – Digital Maestro Series R = 1− Re Γ 2 2 1− Re Γ + Im Γ + R R Re + + 2Im R jX j 1− Γ Γ R 0 0 2 * R R R + j Im Γ R j 2Im Γ R = R 81 Transmission Lines Equivalently, using the complex characteristic admittance: * 0 〈 P(d=0, t ) 〉 = 1 Re V + 1+Γ R Y V + 1−Γ 2 = = = = V+ 2 2 2 2 1+ Re Γ + j Im Γ R 2 R = 1− Re Γ 2 2 1− Re Γ R + Im Γ R + 2 Re G0 − jB0 1− Γ R + j 2Im Γ 2 V+ Re G0 − jB0 2 V+ 0 Re G0 − jB 2 V+ * R 2 G0 − G0 Γ R + 2B0 Im Γ © Amanogawa, 2006 – Digital Maestro Series R R + j Im Γ R j 2Im Γ R = R 82 Transmission Lines The time-average power, injected into the input of the transmission line, is maximized when the input impedance of the transmission line and the internal generator impedance are complex conjugate of each other. Zin Generator Load ZG VG ZG = Z*in © Amanogawa, 2006 – Digital Maestro Series Transmission line ZR for maximum power transfer 83 Transmission Lines The characteristic impedance of the loss-less line is real and we can express the power flow, anywhere on the line, as 1 〈 P (d , t ) 〉 = Re{ V (d) I * (d) } 2 1 + jβ d 1 + Γ R e− j 2β d = Re V e 2 ( ) ( 1 (V + )* e− jβ d 1 − Γ R e− j 2β d Z0 1 +2 = V 2Z0 Incident wave ) * 1 +2 − V ΓR 2 2Z0 Reflected wave This result is valid for any location, including the input and the load, since the transmission line does not absorb any power. © Amanogawa, 2006 – Digital Maestro Series 84 Transmission Lines In the case of low-loss lines, the characteristic impedance is again real, but the time-average power flow is position dependent because the line absorbs power. { { } ( 1 〈 P (d , t ) 〉 = Re V (d) I * (d) 2 1 = Re V + eα d e jβ d 1 + Γ R e−2 γ d 2 1 (V + )* eα d e− jβ d 1 − Γ R e−2 γ d Z0 ) ( ) * 1 1 + 2 2α d + 2 −2α d = V e − V e ΓR 2 2Z0 2Z0 Incident wave © Amanogawa, 2006 – Digital Maestro Series Reflected wave 85 Transmission Lines Note that in a lossy line the reference for the amplitude of the incident voltage wave is at the load and that the amplitude grows exponentially moving towards the input. The amplitude of the incident wave behaves in the following way V + eα L ⇔ input V + eα d inside the line ⇔ V+ load The reflected voltage wave has maximum amplitude at the load, and it decays exponentially moving back towards the generator. The amplitude of the reflected wave behaves in the following way V + Γ R e−α L ⇔ input © Amanogawa, 2006 – Digital Maestro Series V + Γ R e−α d ⇔ inside the line V +ΓR load 86 Transmission Lines For a general lossy line the power flow is again position dependent. Since the characteristic impedance is complex, the result has an additional term involving the imaginary part of the characteristic admittance, B0, as { { } 1 〈 P (d , t ) 〉 = Re V (d) I * (d) 2 1 = Re V + eα d e jβ d (1 + Γ (d) ) 2 } Y0* (V + )* eα d e− jβ d (1 − Γ (d) )* G0 + 2 2α d G0 + 2 −2α d = V e − V e ΓR 2 2 2 + B0 V © Amanogawa, 2006 – Digital Maestro Series +2 e2α d Im(Γ (d)) 87 Transmission Lines For the general lossy line, keep in mind that Z 0* R0 − jX 0 R0 − jX 0 1 Y0 = = = = 2 = G0 + jB0 * 2 2 Z0 Z0 Z0 R0 + X 0 Z0 −X0 R0 = G0 = 2 B 0 R0 + X 02 R02 + X 02 Recall that for a low-loss transmission line the characteristic impedance is approximately real, so that B0 ≈ 0 and Z 0 ≈ 1 G0 ≈ R0 . The previous result for the low-loss line can be readily recovered from the time-average power for the general lossy line. © Amanogawa, 2006 – Digital Maestro Series 88 Transmission Lines To completely specify the transmission line problem, we still have to determine the value of V+ from the input boundary condition. ¾ The load boundary condition imposes the shape of the interference pattern of voltage and current along the line. ¾ The input boundary condition, linked to the generator, imposes the scaling for the interference patterns. We have Zin Vin = V (L) = VG ZG + Zin or with 1 + Γ (L) Zin = Z 0 1 − Γ (L) Z R + jZ 0 tan(β L) Zin = Z 0 jZ R tan(β L) + Z 0 loss - less line Z R + Z 0 tanh( γ L) Zin = Z 0 Z R tanh( γ L) + Z 0 lossy line © Amanogawa, 2006 – Digital Maestro Series 89 Transmission Lines For a loss-less transmission line: V (L) = V + e jβ L [1 + Γ (L) ] = V + e jβ L (1 + Γ R e− j 2β L ) ⇒ Zin 1 V = VG ZG + Zin e jβ L (1 + Γ R e− j 2β L ) + For a lossy transmission line: ( V (L) = V + e γ L [1 + Γ (L) ] = V + e γ L 1 + Γ R e−2 γ d ⇒ ) Zin 1 V = VG ZG + Zin e γ L (1 + Γ R e−2 γ L ) + © Amanogawa, 2006 – Digital Maestro Series 90 Transmission Lines In order to have good control on the behavior of a high frequency circuit, it is very important to realize transmission lines as uniform as possible along their length, so that the impedance behavior of the line does not vary and can be easily characterized. A change in transmission line properties, wanted or unwanted, entails a change in the characteristic impedance, which causes a reflection. Example: Z01 Z02 ZR Γ1 Z01 © Amanogawa, 2006 – Digital Maestro Series Zin Zin − Z01 Γ1 = Zin + Z01 91 Transmission Lines Special Cases ZR → 0 (SHORT CIRCUIT) ZR = 0 Z0 The load boundary condition due to the short circuit is V (0) = 0 ⇒ V (d = 0) = V + e jβ 0 (1 + Γ R e− j 2β 0 ) = V + (1 + Γ R ) = 0 ⇒ © Amanogawa, 2006 – Digital Maestro Series Γ R = −1 92 Transmission Lines Since ΓR = V− V+ ⇒ V − = −V + We can write the line voltage phasor as V (d) = V + e jβ d + V − e− jβ d = V + e jβ d − V + e− jβ d = V + ( e jβ d − e− jβ d ) = 2 jV + sin(β d) © Amanogawa, 2006 – Digital Maestro Series 93 Transmission Lines For the line current phasor we have 1 (V + e jβ d − V − e− jβ d ) I (d) = Z0 1 (V + e jβ d + V + e− jβ d ) = Z0 V + jβ d (e = + e− jβ d ) Z0 2V + cos(β d) = Z0 The line impedance is given by V (d) 2 jV + sin(β d) = = jZ0 tan(β d) Z(d) = + I (d) 2V cos(β d) / Z0 © Amanogawa, 2006 – Digital Maestro Series 94 Transmission Lines The time-dependent values of voltage and current are obtained as V (d, t ) = Re[V (d) e jω t ] = Re[2 j | V + | e jθ sin(β d) e jω t ] = 2| V + |sin(β d) ⋅ Re[ j e j (ω t +θ) ] = 2| V + |sin(β d) ⋅ Re[ j cos(ω t + θ) − sin(ω t + θ)] = −2| V + |sin(β d) sin(ω t + θ) I (d, t ) = Re[ I (d) e jω t ] = Re[2 | V + | e jθ cos(β d) e jω t ] / Z0 = 2| V + |cos(β d) ⋅ Re[ e j (ω t +θ) ] / Z0 = 2| V + |cos(β d) ⋅ Re[ (cos(ω t + θ) + j sin(ω t + θ)] / Z0 | V+ | =2 cos(β d) cos(ω t + θ) Z0 © Amanogawa, 2006 – Digital Maestro Series 95 Transmission Lines The time-dependent power is given by P(d, t ) = V (d, t ) ⋅ I (d, t ) | V + |2 =−4 sin(β d) cos(β d) sin(ω t + θ) cos(ω t + θ) Z0 | V + |2 =− sin(2β d) sin (2ω t + 2θ) Z0 and the corresponding time-average power is 1 T < P(d, t ) > = ∫ P(d, t ) dt T 0 | V + |2 1 T =− sin(2β d) ∫ sin (2ω t + 2θ) = 0 Z0 T 0 © Amanogawa, 2006 – Digital Maestro Series 96 Transmission Lines ZR → ∞ (OPEN CIRCUIT) ZR → ∞ Z0 The load boundary condition due to the open circuit is I (0) = 0 V + jβ 0 ⇒ I (d = 0) = e (1 − Γ R e− j 2β 0 ) Z0 V+ = (1 − Γ R ) = 0 Z0 ⇒ © Amanogawa, 2006 – Digital Maestro Series ΓR = 1 97 Transmission Lines Since ΓR = V− V+ ⇒ V− = V+ We can write the line current phasor as 1 I (d) = (V + e jβ d − V − e− jβ d ) Z0 1 = (V + e jβ d − V + e− jβ d ) Z0 V + jβ d − jβ d 2 jV + = −e (e )= sin(β d) Z0 Z0 © Amanogawa, 2006 – Digital Maestro Series 98 Transmission Lines For the line voltage phasor we have V (d) = (V + e jβ d + V − e− jβ d ) = (V + e jβ d + V + e− jβ d ) = V + ( e jβ d + e− jβ d ) = 2V + cos(β d) The line impedance is given by V (d) 2V + cos(β d) Z0 Z(d) = = =−j I (d) 2 jV + sin(β d) / Z0 tan(β d) © Amanogawa, 2006 – Digital Maestro Series 99 Transmission Lines The time-dependent values of voltage and current are obtained as V (d, t ) = Re[V (d) e jω t ] = Re[2 | V + | e jθ cos(β d) e jω t ] = 2| V + |cos(β d) ⋅ Re[ e j(ω t +θ) ] = 2| V + |cos(β d) ⋅ Re[ (cos(ω t + θ) + j sin(ω t + θ)] = 2| V + |cos(β d) cos(ω t + θ) I (d, t ) = Re[ I (d) e jω t ] = Re[2 j | V + | e jθ sin(β d) e jω t ] / Z0 = 2| V + |sin(β d) ⋅ Re[ j e j(ω t +θ) ] / Z0 = 2| V + |sin(β d) ⋅ Re[ j cos(ω t + θ) − sin(ω t + θ)] / Z0 | V+ | = −2 sin(β d) sin(ω t + θ) Z0 © Amanogawa, 2006 – Digital Maestro Series 100 Transmission Lines The time-dependent power is given by P(d, t ) = V (d, t ) ⋅ I (d, t ) = | V + |2 =−4 cos(β d) sin(β d) cos(ω t + θ) sin(ω t + θ) Z0 | V + |2 =− sin(2β d) sin (2ω t + 2θ) Z0 and the corresponding time-average power is 1 T < P(d, t ) > = ∫ P(d, t ) dt T 0 | V + |2 1 T =− sin(2β d) ∫ sin (2ω t + 2θ) = 0 Z0 T 0 © Amanogawa, 2006 – Digital Maestro Series 101 Transmission Lines ZR = Z0 (MATCHED LOAD) Z0 ZR = Z0 The reflection coefficient for a matched load is ZR − Z0 Z0 − Z0 ΓR = = =0 ZR + Z0 Z0 + Z0 no reflection! The line voltage and line current phasors are V (d) = V + e jβ d (1 + Γ R e−2 jβ d ) = V + e jβ d + V + jβ d V (1 − Γ R e−2 jβ d ) = I( d ) = e e jβ d Z0 Z0 © Amanogawa, 2006 – Digital Maestro Series 102 Transmission Lines The line impedance is independent of position and equal to the characteristic impedance of the line V (d) V + e jβ d Z(d) = = = Z0 + I (d) V jβ d e Z0 The time-dependent voltage and current are V (d, t ) = Re[| V + | e jθ e jβ d e jω t ] = | V + | ⋅ Re[e j(ω t +β d +θ) ] =| V + | cos(ω t + β d + θ) I (d, t ) = Re[| V + | e jθ e jβ d e jω t ] / Z0 + | V+ | | V | j (ω t +β d +θ) = ⋅ Re[e ]= cos(ω t + β d + θ) Z0 Z0 © Amanogawa, 2006 – Digital Maestro Series 103 Transmission Lines The time-dependent power is + | | V P(d, t ) = | V + | cos(ω t + β d + θ) cos(ω t + β d + θ) Z0 | V + |2 cos2 (ω t + β d + θ) = Z0 and the time average power absorbed by the load is 1 t | V + |2 < P(d) > = ∫ cos2 (ω t + β d + θ) dt T 0 Z0 | V + |2 = 2 Z0 © Amanogawa, 2006 – Digital Maestro Series 104 Transmission Lines ZR = jX (PURE REACTANCE) ZR = j X Z0 The reflection coefficient for a purely reactive load is ZR − Z0 jX − Z0 ΓR = = = ZR + Z0 jX + Z0 ( jX − Z0 )( jX − Z0 ) = = ( jX + Z0 )( jX − Z0 ) © Amanogawa, 2006 – Digital Maestro Series X 2 − Z02 Z02 + X 2 +2j XZ0 Z02 + X 2 105 Transmission Lines In polar form Γ R = Γ R exp( jθ) where ΓR = ( ( ) ) ( 2 2 X − Z0 4 X 2 Z02 + = 2 2 Z02 + X 2 Z02 + X 2 2 ) ( ( ) ) 2 2 2 Z0 + X =1 2 Z02 + X 2 −1 2 XZ0 θ = tan X 2 − Z2 0 The reflection coefficient has unitary magnitude, as in the case of short and open circuit load, with zero time average power absorbed by the load. Both voltage and current are finite at the load, and the time-dependent power oscillates between positive and negative values. This means that the load periodically stores power and then returns it to the line without dissipation. © Amanogawa, 2006 – Digital Maestro Series 106 Transmission Lines Reactive impedances can be realized with transmission lines terminated by a short or by an open circuit. The input impedance of a loss-less transmission line of length L terminated by a short circuit is purely imaginary 2π f 2π Zin = j Z0 tan ( β L ) = j Z0 tan L = j Z0 tan L v λ p For a specified frequency f, any reactance value (positive or negative!) can be obtained by changing the length of the line from 0 to λ/2. An inductance is realized for L < λ/4 (positive tangent) while a capacitance is realized for λ/4 < L < λ/2 (negative tangent). When L = 0 and L = λ/2 the tangent is zero, and the input impedance corresponds to a short circuit. However, when L = λ/4 the tangent is infinite and the input impedance corresponds to an open circuit. © Amarcord, 2006 – Digital Maestro Series 107 Transmission Lines Since the tangent function is periodic, the same impedance behavior of the impedance will repeat identically for each additional line increment of length λ/2. A similar periodic behavior is also obtained when the length of the line is fixed and the frequency of operation is changed. At zero frequency (infinite wavelength), the short circuited line behaves as a short circuit for any line length. When the frequency is increased, the wavelength shortens and one obtains an inductance for L < λ/4 and a capacitance for λ/4 < L < λ/2, with an open circuit at L = λ/4 and a short circuit again at L = λ/2. Note that the frequency behavior of lumped elements is very different. Consider an ideal inductor with inductance L assumed to be constant with frequency, for simplicity. At zero frequency the inductor also behaves as a short circuit, but the reactance varies monotonically and linearly with frequency as X = ωL (always an inductance) © Amarcord, 2006 – Digital Maestro Series 108 Transmission Lines Short circuited transmission line – Fixed frequency L Z in = 0 L= 0 0< L< L= λ 4 λ 2 4 λ 2 λ k p Im Z in > 0 in d u c ta n c e Z in → ∞ o p e n c irc u it k p c a p a c ita n c e Im Z in < 0 Z in = 0 2 < L< L= 4 λ < L< L= λ 3λ 4 3λ 4 3λ < L< λ 4 s h o rt c irc u it k p s h o rt c irc u it Im Z in > 0 in d u c ta n c e Z in → ∞ o p e n c irc u it k p Im Z in < 0 c a p a c ita n c e … © Amarcord, 2006 – Digital Maestro Series 109 Z(L)/Zo = j tan(β L) Transmission Lines Impedance of a short circuited transmission line (fixed frequency, variable length) 40 30 20 inductive Normalized Input Impedance 10 inductive inductive 0 -10 capacitive cap. -20 -30 -40 0 100 π/(2β)= λ/4 200 π/β =λ/2 300 3π/(2β)= 3λ/4 400 2π/β= λ 500 5π/(2β)= 5λ/4 θ L [deg] Line Length L © Amarcord, 2006 – Digital Maestro Series 110 Z(L)/Zo = j tan(β L) Transmission Lines Impedance of a short circuited transmission line (fixed length, variable frequency) 40 30 20 inductive Normalized Input Impedance 10 inductive inductive 0 -10 capacitive cap. -20 -30 -40 0 100 vp / (4L) 200 vp / (2L) 300 3vp / (4L) 400 vp / L 500 5vp / (4L) θ [deg] f Frequency of operation © Amarcord, 2006 – Digital Maestro Series 111 Transmission Lines For a transmission line of length L terminated by an open circuit, the input impedance is again purely imaginary Z0 Zin = − j =−j tan ( β L ) Z0 Z0 =−j 2π 2π f tan L tan L λ v p We can also use the open circuited line to realize any reactance, but starting from a capacitive value when the line length is very short. Note once again that the frequency behavior of a corresponding lumped element is different. Consider an ideal capacitor with capacitance C assumed to be constant with frequency. At zero frequency the capacitor behaves as an open circuit, but the reactance varies monotonically and linearly with frequency as 1 X= (always a capacitance) ωC © Amarcord, 2006 – Digital Maestro Series 112 Transmission Lines Open circuit transmission line – Fixed frequency L L= 0 0< L< L= λ 4 λ 2 4 λ 2 λ 2 < L< L= 4 λ < L< L= λ 3λ 4 3λ 4 3λ < L< λ 4 Z in → ∞ o p e n c irc u it Im Z in < 0 k p c a p a c ita n c e Z in = 0 s h o rt c irc u it k p Im Z in > 0 in d u c ta n c e Z in → ∞ o p e n c irc u it Im Z in < 0 k p c a p a c ita n c e Z in = 0 s h o rt c irc u it k p Im Z in > 0 in d u c ta n c e … © Amarcord, 2006 – Digital Maestro Series 113 Normalized Input Impedance Z(L)/ Zo = - j cotan(β L) Transmission Lines Impedance of an open circuited transmission line (fixed frequency, variable length) 40 30 20 inductive 10 inductive inductive 0 -10 capacitive capacitive capacitive -20 -30 -40 0 0 100 π/(2β) = λ/4 200 π/β = λ/2 300 3π/(2β) = 3λ/4 400 2π/β = 2λ 500 5π/(2β) = 5λ/4 θ [deg] L Line Length L © Amarcord, 2006 – Digital Maestro Series 114 Normalized Input Impedance Z(L)/ Zo = - j cotan(β L) Transmission Lines Impedance of an open circuited transmission line (fixed length, variable frequency) 40 30 20 inductive 10 inductive inductive 0 -10 capacitive capacitive capacitive -20 -30 -40 0 0 100 vp / (4L) 200 vp / (2L) 300 3vp / (4L) 400 vp / L 500 5vp / (4L) θ [deg] f Frequency of operation © Amarcord, 2006 – Digital Maestro Series 115 Transmission Lines It is possible to realize resonant circuits by using transmission lines as reactive elements. For instance, consider the circuit below realized with lines having the same characteristic impedance: I L1 short circuit Z0 V Zin1 Zin1 = j Z0 tan ( β L 1 ) © Amarcord, 2006 – Digital Maestro Series L2 Z0 short circuit Zin2 Zin2 = j Z0 tan ( β L 2 ) 116 Transmission Lines The circuit is resonant if L1 and L2 are chosen such that an inductance and a capacitance are realized. A resonance condition is established when the total input impedance of the parallel circuit is infinite or, equivalently, when the input admittance of the parallel circuit is zero 1 1 + =0 j Z0 tan ( β r L1 ) j Z0 tan ( β r L 2 ) or ωr ωr tan L1 = − tan L 2 vp vp with 2π ωr βr = = λ r vp Since the tangent is a periodic function, there is a multiplicity of possible resonant angular frequencies ωr that satisfy the condition above. The values can be found by using a numerical procedure to solve the trascendental equation above. © Amarcord, 2006 – Digital Maestro Series 117