T echnical Valve Sizing Calculations (Traditional Method) Introduction Fisher® regulators and valves have traditionally been sized using equations derived by the company. There are now standardized calculations that are becoming accepted worldwide. Some product literature continues to demonstrate the traditional method, but the trend is to adopt the standardized method. Therefore, both methods are covered in this application guide. Improper valve sizing can be both expensive and inconvenient. A valve that is too small will not pass the required flow, and the process will be starved. An oversized valve will be more expensive, and it may lead to instability and other problems. Sizing for Liquid Service Using the principle of conservation of energy, Daniel Bernoulli found that as a liquid flows through an orifice, the square of the fluid velocity is directly proportional to the pressure differential across the orifice and inversely proportional to the specific gravity of the fluid. The greater the pressure differential, the higher the velocity; the greater the density, the lower the velocity. The volume flow rate for liquids can be calculated by multiplying the fluid velocity times the flow area. By taking into account units of measurement, the proportionality relationship previously mentioned, energy losses due to friction and turbulence, and varying discharge coefficients for various types of orifices (or valve bodies), a basic liquid sizing equation can be written as follows Q = CV ∆P / G (1) where: Q = Capacity in gallons per minute Cv = Valve sizing coefficient determined experimentally for each style and size of valve, using water at standard conditions as the test fluid ∆P = Pressure differential in psi G = Specific gravity of fluid (water at 60°F = 1.0000) Thus, Cv is numerically equal to the number of U.S. gallons of water at 60°F that will flow through the valve in one minute when the pressure differential across the valve is one pound per square inch. Cv varies with both size and style of valve, but provides an index for comparing liquid capacities of different valves under a standard set of conditions. 626 FLOW INLET VALVE TEST VALVE LOAD VALVE Figure 1. Standard FCI Test Piping for Cv Measurement The days of selecting a valve based upon the size of the pipeline are gone. Selecting the correct valve size for a given application requires a knowledge of process conditions that the valve will actually see in service. The technique for using this information to size the valve is based upon a combination of theory and experimentation. PRESSURE INDICATORS ∆P ORIFICE METER To aid in establishing uniform measurement of liquid flow capacity coefficients (Cv) among valve manufacturers, the Fluid Controls Institute (FCI) developed a standard test piping arrangement, shown in Figure 1. Using such a piping arrangement, most valve manufacturers develop and publish Cv information for their products, making it relatively easy to compare capacities of competitive products. To calculate the expected Cv for a valve controlling water or other liquids that behave like water, the basic liquid sizing equation above can be re-written as follows CV = Q G ∆P (2) Viscosity Corrections Viscous conditions can result in significant sizing errors in using the basic liquid sizing equation, since published Cv values are based on test data using water as the flow medium. Although the majority of valve applications will involve fluids where viscosity corrections can be ignored, or where the corrections are relatively small, fluid viscosity should be considered in each valve selection. Emerson Process Management has developed a nomograph (Figure 2) that provides a viscosity correction factor (Fv). It can be applied to the standard Cv coefficient to determine a corrected coefficient (Cvr) for viscous applications. Finding Valve Size Using the Cv determined by the basic liquid sizing equation and the flow and viscosity conditions, a fluid Reynolds number can be found by using the nomograph in Figure 2. The graph of Reynolds number vs. viscosity correction factor (Fv) is used to determine the correction factor needed. (If the Reynolds number is greater than 3500, the correction will be ten percent or less.) The actual required Cv (Cvr) is found by the equation: Cvr = FV CV (3) From the valve manufacturer’s published liquid capacity information, select a valve having a Cv equal to or higher than the required coefficient (Cvr) found by the equation above. T echnical Valve Sizing Calculations (Traditional Method) INDEX 0.01 1 2 3 4 0.02 INDEX 0.01 1 2 3 4 6 8 100.03 20 30 40 60 0.04 Q 2,000800 4,000 1,000 3,000 800 600 600 2,000 1,000400 800 300 400 1000 300 1,000 400 300 100 400 300 200 200 80 200 80 100 40 80 30 60 60 20 30 10 20 8 6 10 4 8 6 4 3 2 3 1 0.8 0.6 2 1 0.80.4 0.3 0.6 0.2 100 80 40 60 30 40 20 30 10 8 4 6 4 3 4 2 3 3 2 2 1 1 0.8 0.8 0.3 0.2 0.2 0.1 0.08 0.02 0.04 0.1 0.06 0.08 0.03 0.04 0.06 0.01 0.02 0.03 0.004 0.003 0.002 0.4 0.3 0.2 0.1 0.08 0.06 0.03 0.04 0.03 0.01 0.004 0.008 0.003 0.006 0.004 0.0006 0.003 0.001 0.0008 0.0004 0.0006 0.0003 0.0004 0.0002 0 .001 0.0003 0.0008 0.0001 0.6 0.04 0.002 0 .001 0.0008 1 0.8 0.02 0.01 0.008 0.006 0.02 0.01 0.008 0.006 30 10 8 0.4 0.4 0.3 0.03 0.06 40 6 0.6 0.6 0.1 0.04 0.08 100 80 60 6 10 8 0.3 0.08 0.06 100 80 60 20 20 0.4 0.20.1 200 100 60 40 400 300 1000 800 600 800 600200 400 300 600 2,000 200 600 LIQUID FLOW COEFFICIENT, CV C 10,000 2,000 8,000 6,000 4,000 3,000 0.002 0.002 0.0004 0.0001 0.0003 0.0004 0.0002 0.0003 0.3 200 0.6 30 10 8 4 6 3 4 2 3 0.6 0.4 0.6 0.3 0.4 0.2 0.3 200,000 3 20,000 20,000 100,000 80,000 60,000 100,000 80,000 60,000 0.06 0.1 0.08 0.04 0.06 0.03 0.04 0.02 0.03 0.004 0.01 0.008 0.006 0.003 0.004 0.002 0.003 0.0006 0.001 0.0008 0.0004 0.0006 0.0003 0.0004 0.0002 0.0003 0.0002 0.0001 0.0001 20,000 2,000 10,000 8,000 6,000 1,000 800 600 4,000 3,000 400 300 2,000 200 1,000 800 600 100 80 60 400 300 40 30 200 20 100 80 10 8 6 60 4 3 40 2 1 35 32.6 60 80 100 0.3 0.4 0.2 0.6 0.3 0.8 1 4 10,000 8,000 8 6,000 10 4,000 3,000 1,000 800 600 40 60 80 100 300 400 600 800 1,000 2,000 40 2,000 200 1,000 800 600 30 60 200 40 30 200 300 20 100 80 10 8 6 60 4 3 4,000 2 6 8 10 20,000 2,000 10,000 8,000 6,000 20 4,000 3,000 40 30 2,000 60 1,000 FOR 200 PREDICTING 800 FLOW RATE 600 100 80 100 400 80 60 400 300 200 40 30 200 300 20 100 80 10 8 6 60 600 800 1,000 35 32.6 2 800 1,000 400 40 4 3 600 2,000 3,000 1 4,000 40 35 32.6 1 8,000 10,000 4 4,000 3,000 400 300 80 100 400 300 3,000 6,000 4,000 3,000 400 300 100 80 60 200 10,000 8,000 6,000 20 3 40,000 30,000 1,000 800 600 20,000 2,000 30 8 10 2 200,000 100,000 80,000 60,000 10,000 8,000 6,000 6 40,000 30,000 6 20 4 400,000 300,000 2,000 6,000 3,000 8,000 10,000 4,000 20,000 6,000 20,000 8,000 10,000 30,000 30,000 40,000 40,000 60,000 80,000 100,000 20,000 60,000 30,000 80,000 100,000 40,000 200,000 60,000 200,000 300,000 80,000 100,000 300,000 400,000 400,000 600,000 800,000 1,000,000 600,000 200,000 1 2 3 4 6 8 10 300,000 20 30 40 60 80 100 200 CV CORRECTION FACTOR, FV 400,000 0.0002 0.0001 Figure 2. Nomograph for Determining Viscosity Correction 0.0001 0.08 0.1 200 0.2 3 40,000 30,000 40,000 30,000 40 0.08 0.1 2 200,000 4,000 3,000 30 0.06 400,000 300,000 40,000 2 30,000 10,000 8,000 6,000 0.0420 20,000 60,000 0.2 0.1 0.08 10 100,000 0.6 80,000 60,000 0.8 1 40,000 30,000 400,000 300,000 100,000 80,000 60,000 2 1 0.8 8 0.4 20 6 6 FOR SELECTING VALVE SIZE 0.4 0.8100,000 1 80,000 40 4 0.2 400 300 20 0 .001 0.0008 0.003 0.0006 1000 800 600 30 1 0.8 3 FOR PREDICTING PRESSURE DROP 0.08 0.1 0.002 0.004 0.0006 0.06 40 0.01 0.008 0.006 0.01 0.008 0.006 0.001 0.0008 2,000 100 80 60 10 8 2 0.04 0.02 0.02 0.0002 0.03 FV 0.03 1 0.02 4,000 3,000 REYNOLDS NUMBER - NR 2000 4,000 3,000 4,000 3,000 C 10,000 8,000 6,000 VISCOSITY - SAYBOLT SECONDS UNIVERSAL 10,000 8,000 3000 6,000 1,000 800 LIQUID FLOW RATE (SINGLE PORTED ONLY), GPM CV 2,000 10,000 8,000 6,000 0.02 CV CORRECTION FACTOR, FV HR 0.01 KINEMATIC VISCOSITY VCS - CENTISTOKES 10,000 8,000 6,000 4,000 3,000 INDEX INDEX LIQUID FLOW RATE (DOUBLE PORTED ONLY), GPM 10,000 8,000 6,000 0.06 800,000 1,000,000 1 2 800,000 1,000,000 1 2 3 4 6 8 10 20 Nomograph Instructions Nomograph Procedure Use this nomograph to correct for the effects of viscosity. When assembling data, all units must correspond to those shown on the nomograph. For high-recovery, ball-type valves, use the liquid flow rate Q scale designated for single-ported valves. For butterfly and eccentric disk rotary valves, use the liquid flow rate Q scale designated for double-ported valves. 1. Lay a straight edge on the liquid sizing coefficient on Cv scale and flow rate on Q scale. Mark intersection on index line. Procedure A uses value of Cvc; Procedures B and C use value of Cvr. Nomograph Equations Q 1. Single-Ported Valves: N = 17250 R CV νCS 2. Double-Ported Valves: N 3 4 600,000 2. Pivot the straight edge from this point of intersection with index line to liquid viscosity on proper n scale. Read Reynolds number on NR scale. 3. Proceed horizontally from intersection on NR scale to proper curve, and then vertically upward or downward to Fv scale. Read Cv correction factor on Fv scale. Q = 12200 R CV νCS 627 30 40 60 T echnical Valve Sizing Calculations (Traditional Method) Predicting Flow Rate Select the required liquid sizing coefficient (Cvr) from the manufacturer’s published liquid sizing coefficients (Cv) for the style and size valve being considered. Calculate the maximum flow rate (Qmax) in gallons per minute (assuming no viscosity correction required) using the following adaptation of the basic liquid sizing equation: Qmax = Cvr ΔP / G FLOW RESTRICTION VENA CONTRACTA Figure 3. Vena Contracta (4) Then incorporate viscosity correction by determining the fluid Reynolds number and correction factor Fv from the viscosity correction nomograph and the procedure included on it. P1 Q Qpred = Fmax V P2 FLOW P1 Calculate the predicted flow rate (Qpred) using the formula: P2 P1 (5) P2 HIGH RECOVERY P2 LOW RECOVERY Predicting Pressure Drop Select the required liquid sizing coefficient (Cvr) from the published liquid sizing coefficients (Cv) for the valve style and size being considered. Determine the Reynolds number and correct factor Fv from the nomograph and the procedure on it. Calculate the sizing coefficient (Cvc) using the formula: C CVC = Fvr v (6) Calculate the predicted pressure drop (∆Ppred) using the formula: ΔPpred = G (Q/Cvc)2 (7) Flashing and Cavitation The occurrence of flashing or cavitation within a valve can have a significant effect on the valve sizing procedure. These two related physical phenomena can limit flow through the valve in many applications and must be taken into account in order to accurately size a valve. Structural damage to the valve and adjacent piping may also result. Knowledge of what is actually happening within the valve might permit selection of a size or style of valve which can reduce, or compensate for, the undesirable effects of flashing or cavitation. 628 Figure 4. Comparison of Pressure Profiles for High and Low Recovery Valves The “physical phenomena” label is used to describe flashing and cavitation because these conditions represent actual changes in the form of the fluid media. The change is from the liquid state to the vapor state and results from the increase in fluid velocity at or just downstream of the greatest flow restriction, normally the valve port. As liquid flow passes through the restriction, there is a necking down, or contraction, of the flow stream. The minimum cross-sectional area of the flow stream occurs just downstream of the actual physical restriction at a point called the vena contracta, as shown in Figure 3. To maintain a steady flow of liquid through the valve, the velocity must be greatest at the vena contracta, where cross sectional area is the least. The increase in velocity (or kinetic energy) is accompanied by a substantial decrease in pressure (or potential energy) at the vena contracta. Farther downstream, as the fluid stream expands into a larger area, velocity decreases and pressure increases. But, of course, downstream pressure never recovers completely to equal the pressure that existed upstream of the valve. The pressure differential (∆P) that exists across the valve T echnical Valve Sizing Calculations (Traditional Method) is a measure of the amount of energy that was dissipated in the valve. Figure 4 provides a pressure profile explaining the differing performance of a streamlined high recovery valve, such as a ball valve and a valve with lower recovery capabilities due to greater internal turbulence and dissipation of energy. PLOT OF EQUATION (1) Q(gpm) Km CHOKED FLOW Regardless of the recovery characteristics of the valve, the pressure differential of interest pertaining to flashing and cavitation is the differential between the valve inlet and the vena contracta. If pressure at the vena contracta should drop below the vapor pressure of the fluid (due to increased fluid velocity at this point) bubbles will form in the flow stream. Formation of bubbles will increase greatly as vena contracta pressure drops further below the vapor pressure of the liquid. At this stage, there is no difference between flashing and cavitation, but the potential for structural damage to the valve definitely exists. If pressure at the valve outlet remains below the vapor pressure of the liquid, the bubbles will remain in the downstream system and the process is said to have “flashed.” Flashing can produce serious erosion damage to the valve trim parts and is characterized by a smooth, polished appearance of the eroded surface. Flashing damage is normally greatest at the point of highest velocity, which is usually at or near the seat line of the valve plug and seat ring. However, if downstream pressure recovery is sufficient to raise the outlet pressure above the vapor pressure of the liquid, the bubbles will collapse, or implode, producing cavitation. Collapsing of the vapor bubbles releases energy and produces a noise similar to what one would expect if gravel were flowing through the valve. If the bubbles collapse in close proximity to solid surfaces, the energy released gradually wears the material leaving a rough, cylinder like surface. Cavitation damage might extend to the downstream pipeline, if that is where pressure recovery occurs and the bubbles collapse. Obviously, “high recovery” valves tend to be more subject to cavitation, since the downstream pressure is more likely to rise above the vapor pressure of the liquid. Choked Flow Aside from the possibility of physical equipment damage due to flashing or cavitation, formation of vapor bubbles in the liquid flow stream causes a crowding condition at the vena contracta which tends to limit flow through the valve. So, while the basic liquid sizing equation implies that there is no limit to the amount of flow through a valve as long as the differential pressure across the valve increases, the realities of flashing and cavitation prove otherwise. P1 = CONSTANT Cv ∆P (ALLOWABLE) ΔP Figure 5. Flow Curve Showing Cv and Km ACTUAL FLOW PREDICTED FLOW USING ACTUAL ∆P Q(gpm) ACTUAL ∆P ∆P (ALLOWABLE) Cv ΔP Figure 6. Relationship Between Actual ∆P and ∆P Allowable If valve pressure drop is increased slightly beyond the point where bubbles begin to form, a choked flow condition is reached. With constant upstream pressure, further increases in pressure drop (by reducing downstream pressure) will not produce increased flow. The limiting pressure differential is designated ∆Pallow and the valve recovery coefficient (Km) is experimentally determined for each valve, in order to relate choked flow for that particular valve to the basic liquid sizing equation. Km is normally published with other valve capacity coefficients. Figures 5 and 6 show these flow vs. pressure drop relationships. 629 T echnical Valve Sizing Calculations (Traditional Method) 1.0 CRITICAL PRESSURE RATIO—rc CRITICAL PRESSURE RATIO—rc 1.0 0.9 0.8 0.7 0.6 0.9 0.8 0.7 0.6 0.5 0 0.5 0 500 1000 1500 2000 2500 3000 0.20 0.40 0.60 0.80 1.0 VAPOR PRESSURE, PSIA CRITICAL PRESSURE, PSIA 3500 VAPOR PRESSURE, PSIA Use this curve for water. Enter on the abscissa at the water vapor pressure at the valve inlet. Proceed vertically to intersect the curve. Move horizontally to the left to read the critical pressure ratio, rc, on the ordinate. Use this curve for liquids other than water. Determine the vapor pressure/critical pressure ratio by dividing the liquid vapor pressure at the valve inlet by the critical pressure of the liquid. Enter on the abscissa at the ratio just calculated and proceed vertically to intersect the curve. Move horizontally to the left and read the critical pressure ratio, rc, on the ordinate. Figure 7. Critical Pressure Ratios for Water Figure 8. Critical Pressure Ratios for Liquid Other than Water Use the following equation to determine maximum allowable pressure drop that is effective in producing flow. Keep in mind, however, that the limitation on the sizing pressure drop, ∆Pallow, does not imply a maximum pressure drop that may be controlled y the valve. ∆Pallow = Km (P1 - rc P v) (8) where: ∆Pallow = maximum allowable differential pressure for sizing purposes, psi Km = valve recovery coefficient from manufacturer’s literature P1 = body inlet pressure, psia rc = critical pressure ratio determined from Figures 7 and 8 Pv = vapor pressure of the liquid at body inlet temperature, psia (vapor pressures and critical pressures for many common liquids are provided in the Physical Constants of Hydrocarbons and Physical Constants of Fluids tables; refer to the Table of Contents for the page number). After calculating ∆Pallow, substitute it into the basic liquid sizing equation Q = CV ∆P / G to determine either Q or Cv. If the actual ∆P is less the ∆Pallow, then the actual ∆P should be used in the equation. 630 The equation used to determine ∆Pallow should also be used to calculate the valve body differential pressure at which significant cavitation can occur. Minor cavitation will occur at a slightly lower pressure differential than that predicted by the equation, but should produce negligible damage in most globe-style control valves. Consequently, initial cavitation and choked flow occur nearly simultaneously in globe-style or low-recovery valves. However, in high-recovery valves such as ball or butterfly valves, significant cavitation can occur at pressure drops below that which produces choked flow. So although ∆Pallow and Km are useful in predicting choked flow capacity, a separate cavitation index (Kc) is needed to determine the pressure drop at which cavitation damage will begin (∆Pc) in high-recovery valves. The equation can e expressed: ∆PC = KC (P1 - PV) (9) This equation can be used anytime outlet pressure is greater than the vapor pressure of the liquid. Addition of anti-cavitation trim tends to increase the value of Km. In other words, choked flow and incipient cavitation will occur at substantially higher pressure drops than was the case without the anti-cavitation accessory. T echnical Valve Sizing Calculations (Traditional Method) Liquid Sizing Equation Application Equation 1 2 Q = Cv ΔP / G CV = Q G ∆P Cvr = FV CV 3 4 Application Qmax = Cvr ΔP / G 5 Qpred = 6 CVC = Qmax FV Basic liquid sizing equation. Use to determine proper valve size for a given set of service conditions. (Remember that viscosity effects and valve recovery capabilities are not considered in this basic equation.) Use to calculate expected Cv for valve controlling water or other liquids that behave like water. Use to find actual required Cv for equation (2) after including viscosity correction factor. Use to find maximum flow rate assuming no viscosity correction is necessary. Use to predict actual flow rate based on equation (4) and viscosity factor correction. Cvr Fv 7 ΔPpred = G (Q/Cvc)2 8 ∆Pallow = Km (P1 - rc P v) 9 ∆PC = KC (P1 - PV) Use to calculate corrected sizing coefficient for use in equation (7). Use to predict pressure drop for viscous liquids. Use to determine maximum allowable pressure drop that is effective in producing flow. Use to predict pressure drop at which cavitation will begin in a valve with high recovery characteristics. Liquid Sizing Summary The most common use of the basic liquid sizing equation is to determine the proper valve size for a given set of service conditions. The first step is to calculate the required Cv by using the sizing equation. The ∆P used in the equation must be the actual valve pressure drop or ∆Pallow, whichever is smaller. The second step is to select a valve, from the manufacturer’s literature, with a Cv equal to or greater than the calculated value. Accurate valve sizing for liquids requires use of the dual coefficients of Cv and Km. A single coefficient is not sufficient to describe both the capacity and the recovery characteristics of the valve. Also, use of the additional cavitation index factor Kc is appropriate in sizing high recovery valves, which may develop damaging cavitation at pressure drops well below the level of the choked flow. Cv = valve sizing coefficient for liquid determined experimentally for each size and style of valve, using water at standard conditions as the test fluid Cvc = calculated Cv coefficient including correction for viscosity Cvr = corrected sizing coefficient required for viscous applications ∆Pallow=maximum allowable differential pressure for sizing purposes, psi ∆Pc = pressure differential at which cavitation damage begins, psi Fv = viscosity correction factor G = specific gravity of fluid (water at 60°F = 1.0000) Kc = dimensionless cavitation index used in determining ∆Pc Liquid Sizing Nomenclature ∆P = differential pressure, psi Km = valve recovery coefficient from manufacturer’s literature P1 = body inlet pressure, psia Pv = vapor pressure of liquid at body inlet temperature, psia Q = flow rate capacity, gallons per minute Qmax= designation for maximum flow rate, assuming no viscosity correction required, gallons per minute Qpred= predicted flow rate after incorporating viscosity correction, gallons per minute rc = critical pressure ratio 631 T echnical Valve Sizing Calculations (Traditional Method) Sizing for Gas or Steam Service A sizing procedure for gases can be established based on adaptions of the basic liquid sizing equation. By introducing conversion factors to change flow units from gallons per minute to cubic feet per hour and to relate specific gravity in meaningful terms of pressure, an equation can be derived for the flow of air at 60°F. Because 60°F corresponds to 520° on the Rankine absolute temperature scale, and because the specific gravity of air at 60°F is 1.0, an additional factor can be included to compare air at 60°F with specific gravity (G) and absolute temperature (T) of any other gas. The resulting equation an be written: QSCFH = 59.64 CVP1 ∆P P1 520 GT (A) The equation shown above, while valid at very low pressure drop ratios, has been found to be very misleading when the ratio of pressure drop (∆P) to inlet pressure (P1) exceeds 0.02. The deviation of actual flow capacity from the calculated flow capacity is indicated in Figure 8 and results from compressibility effects and critical flow limitations at increased pressure drops. Critical flow limitation is the more significant of the two problems mentioned. Critical flow is a choked flow condition caused by increased gas velocity at the vena contracta. When velocity at the vena contracta reaches sonic velocity, additional increases in ∆P by reducing downstream pressure produce no increase in flow. So, after critical flow condition is reached (whether at a pressure drop/inlet pressure ratio of about 0.5 for glove valves or at much lower ratios for high recovery valves) the equation above becomes completely useless. If applied, the Cv equation gives a much higher indicated capacity than actually will exist. And in the case of a high recovery valve which reaches critical flow at a low pressure drop ratio (as indicated in Figure 8), the critical flow capacity of the valve may be over-estimated by as much as 300 percent. The problems in predicting critical flow with a Cv-based equation led to a separate gas sizing coefficient based on air flow tests. The coefficient (Cg) was developed experimentally for each type and size of valve to relate critical flow to absolute inlet pressure. By including the correction factor used in the previous equation to compare air at 60°F with other gases at other absolute temperatures, the critical flow equation an be written: 632 Qcritical = CgP1 520 / GT (B) ∆P = 0.5 P1 LOW RECOVERY ∆P = 0.15 P1 Q HIGH RECOVERY Cv ∆P / P1 Figure 9. Critical Flow for High and Low Recovery Valves with Equal Cv Universal Gas Sizing Equation To account for differences in flow geometry among valves, equations (A) and (B) were consolidated by the introduction of an additional factor (C1). C1 is defined as the ratio of the gas sizing coefficient and the liquid sizing coefficient and provides a numerical indicator of the valve’s recovery capabilities. In general, C1 values can range from about 16 to 37, based on the individual valve’s recovery characteristics. As shown in the example, two valves with identical flow areas and identical critical flow (Cg) capacities can have widely differing C1 values dependent on the effect internal flow geometry has on liquid flow capacity through each valve. Example: High Recovery Valve Cg = 4680 Cv = 254 C1 = Cg/Cv = 4680/254 = 18.4 Low Recovery Valve Cg = 4680 Cv = 135 C1 = Cg/Cv = 4680/135 = 34.7 T echnical Valve Sizing Calculations (Traditional Method) So we see that two sizing coefficients are needed to accurately size valves for gas flow­—Cg to predict flow based on physical size or flow area, and C1 to account for differences in valve recovery characteristics. A blending equation, called the Universal Gas Sizing Equation, combines equations (A) and (B) by means of a sinusoidal function, and is based on the “perfect gas” laws. It can be expressed in either of the following manners: QSCFH= 59.64 520 Cg P1 SIN C1 GT OR 3417 520 QSCFH= Cg P1 SIN C1 GT ∆P P1 rad (C) ∆P P1 Deg (D) Special Equation Form for Steam Below 1000 psig If steam applications do not exceed 1000 psig, density changes can be compensated for by using a special adaptation of the Universal Gas Sizing Equation. It incorporates a factor for amount of superheat in degrees Fahrenheit (Tsh) and also a sizing coefficient (Cs) for steam. Equation (F) eliminates the need for finding the density of superheated steam, which was required in Equation (E). At pressures below 1000 psig, a constant relationship exists between the gas sizing coefficient (Cg) and the steam coefficient (Cs). This relationship can be expressed: Cs = Cg/20. For higher steam pressure application, use Equation (E). CS P1 Qlb/hr = SIN 1 + 0.00065Tsh 3417 C1 ∆P P1 Deg (F) In either form, the equation indicates critical flow when the sine function of the angle designated within the brackets equals unity. The pressure drop ratio at which critical flow occurs is known as the critical pressure drop ratio. It occurs when the sine angle reaches π/2 radians in equation (C) or 90 degrees in equation (D). As pressure drop across the valve increases, the sine angle increases from zero up to π/2 radians (90°). If the angle were allowed to increase further, the equations would predict a decrease in flow. Because this is not a realistic situation, the angle must be limited to 90 degrees maximum. Gas and Steam Sizing Summary Although “perfect gases,” as such, do not exist in nature, there are a great many applications where the Universal Gas Sizing Equation, (C) or (D), provides a very useful and usable approximation. Most commonly, the Universal Gas Sizing Equation is used to determine proper valve size for a given set of service conditions. The first step is to calculate the required Cg by using the Universal Gas Sizing Equation. The second step is to select a valve from the manufacturer’s literature. The valve selected should have a Cg which equals or exceeds the calculated value. Be certain that the assumed C1 value for the valve is selected from the literature. General Adaptation for Steam and Vapors The density form of the Universal Gas Sizing Equation is the most general form and can be used for both perfect and non-perfect gas applications. Applying the equation requires knowledge of one additional condition not included in previous equations, that being the inlet gas, steam, or vapor density (d1) in pounds per cubic foot. (Steam density can be determined from tables.) Then the following adaptation of the Universal Gas Sizing Equation can be applied: 3417 Qlb/hr = 1.06 d1 P1 Cg SIN C1 ∆P Deg P1 The Universal Gas Sizing Equation can be used to determine the flow of gas through any style of valve. Absolute units of temperature and pressure must be used in the equation. When the critical pressure drop ratio causes the sine angle to be 90 degrees, the equation will predict the value of the critical flow. For service conditions that would result in an angle of greater than 90 degrees, the equation must be limited to 90 degrees in order to accurately determine the critical flow. It is apparent that accurate valve sizing for gases that requires use of the dual coefficient is not sufficient to describe both the capacity and the recovery characteristics of the valve. Proper selection of a control valve for gas service is a highly technical problem with many factors to be considered. Leading valve manufacturers provide technical information, test data, sizing catalogs, nomographs, sizing slide rules, and computer or calculator programs that make valve sizing a simple and accurate procedure. (E) 633 T echnical Valve Sizing Calculations (Traditional Method) Gas and Steam Sizing Equation Application Equation QSCFH = 59.64 CVP1 A ∆P P1 520 GT Use only at very low pressure drop (DP/P1) ratios of 0.02 or less. Qcritical = CgP1 520 / GT B C Application QSCFH= 59.64 520 Cg P1 SIN C1 GT Use only to determine critical flow capacity at a given inlet pressure. ∆P P1 rad Universal Gas Sizing Equation. Use to predict flow for either high or low recovery valves, for any gas adhering to the perfect gas laws, and under any service conditions. OR D E F QSCFH= 3417 520 Cg P1 SIN C1 GT Qlb/hr = 1.06 d1 P1 Cg SIN Qlb/hr = CS P1 1 + 0.00065Tsh 3417 C1 SIN 3417 C1 ∆P P1 Deg ∆P Deg P1 ∆P P1 Use to predict flow for perfect or non-perfect gas sizing applications, for any vapor including steam, at any service condition when fluid density is known. Deg Use only to determine steam flow when inlet pressure is 1000 psig or less. Gas and Steam Sizing Nomenclature C1 = Cg/Cv Cg = gas sizing coefficient Qcritical = critical flow rate, SCFH Cs = steam sizing coefficient, Cg/20 QSCFH = gas flow rate, SCFH Cv = liquid sizing coefficient d1 = density of steam or vapor at inlet, pounds/cu. foot G = gas specific gravity (air = 1.0) P1 = valve inlet pressure, psia 634 ∆P = pressure drop across valve, psi Qlb/hr = steam or vapor flow rate, pounds per hour T = absolute temperature of gas at inlet, degrees Rankine Tsh = degrees of superheat, °F Technical Valve Sizing (Standardized Method) Introduction Fisher® regulators and valves have traditionally been sized using equations derived by the company. There are now standardized calculations that are becoming accepted world wide. Some product literature continues to demonstrate the traditional method, but the trend is to adopt the standardized method. Therefore, both methods are covered in this application guide. Use N1, if sizing the valve for a flow rate in volumetric units (gpm or Nm3/h). Use N6, if sizing the valve for a flow rate in mass units (pound/hr or kg/hr). 3. Determine Fp, the piping geometry factor. Fp is a correction factor that accounts for pressure losses due to piping fittings such as reducers, elbows, or tees that might be attached directly to the inlet and outlet connections of the control valve to be sized. If such fittings are attached to the valve, the Fp factor must be considered in the sizing procedure. If, however, no fittings are attached to the valve, Fp has a value of 1.0 and simply drops out of the sizing equation. Liquid Valve Sizing Standardization activities for control valve sizing can be traced back to the early 1960s when a trade association, the Fluids Control Institute, published sizing equations for use with both compressible and incompressible fluids. The range of service conditions that could be accommodated accurately by these equations was quite narrow, and the standard did not achieve a high degree of acceptance. In 1967, the ISA established a committee to develop and publish standard equations. The efforts of this committee culminated in a valve sizing procedure that has achieved the status of American National Standard. Later, a committee of the International Electrotechnical Commission (IEC) used the ISA works as a basis to formulate international standards for sizing control valves. (Some information in this introductory material has been extracted from ANSI/ISA S75.01 standard with the permission of the publisher, the ISA.) Except for some slight differences in nomenclature and procedures, the ISA and IEC standards have been harmonized. ANSI/ISA Standard S75.01 is harmonized with IEC Standards 5342-1 and 534-2-2. (IEC Publications 534-2, Sections One and Two for incompressible and compressible fluids, respectively.) For rotary valves with reducers (swaged installations), and other valve designs and fitting styles, determine the Fp factors by using the procedure for determining Fp, the Piping Geometry Factor, page 637. 4. Determine qmax (the maximum flow rate at given upstream conditions) or ∆Pmax (the allowable sizing pressure drop). The maximum or limiting flow rate (qmax), commonly called choked flow, is manifested by no additional increase in flow rate with increasing pressure differential with fixed upstream conditions. In liquids, choking occurs as a result of vaporization of the liquid when the static pressure within the valve drops below the vapor pressure of the liquid. The IEC standard requires the calculation of an allowable sizing pressure drop (∆Pmax), to account for the possibility of choked flow conditions within the valve. The calculated ∆Pmax value is compared with the actual pressure drop specified in the service conditions, and the lesser of these two values is used in the sizing equation. If it is desired to use ∆Pmax to account for the possibility of choked flow conditions, it can be calculated using the procedure for determining qmax, the Maximum Flow Rate, or ∆Pmax, the Allowable Sizing Pressure Drop. If it can be recognized that choked flow conditions will not develop within the valve, ∆Pmax need not be calculated. In the following sections, the nomenclature and procedures are explained, and sample problems are solved to illustrate their use. Sizing Valves for Liquids Following is a step-by-step procedure for the sizing of control valves for liquid flow using the IEC procedure. Each of these steps is important and must be considered during any valve sizing procedure. Steps 3 and 4 concern the determination of certain sizing factors that may or may not be required in the sizing equation depending on the service conditions of the sizing problem. If one, two, or all three of these sizing factors are to be included in the equation for a particular sizing problem, refer to the appropriate factor determination section(s) located in the text after the sixth step. 5. Solve for required Cv, using the appropriate equation: 1. Specify the variables required to size the valve as follows: • For volumetric flow rate units: • Desired design • Process fluid (water, oil, etc.), and • Appropriate service conditions q or w, P1, P2, or ∆P, T1, Gf, Pv, Pc, and υ. Cv = The ability to recognize which terms are appropriate for a specific sizing procedure can only be acquired through experience with different valve sizing problems. If any of the above terms appears to be new or unfamiliar, refer to the Abbreviations and Terminology Table 3-1 for a complete definition. 2. Determine the equation constant, N. N is a numerical constant contained in each of the flow equations to provide a means for using different systems of units. Values for these various constants and their applicable units are given in the Equation Constants Table 3-2. q N1Fp P1 - P2 Gf • For mass flow rate units: Cv= w N6Fp (P -P ) γ 1 2 In addition to Cv, two other flow coefficients, Kv and Av, are used, particularly outside of North America. The following relationships exist: Kv= (0.865) (Cv) Av= (2.40 x 10-5) (Cv) 6. Select the valve size using the appropriate flow coefficient table and the calculated Cv value. 635 Technical Valve Sizing (Standardized Method) Symbol Cv d D Table 3-1. Abbreviations and Terminology Symbol P1 P2 Pc Fd Valve style modifier, dimensionless Pv Upstream absolute static pressure Downstream absolute static pressure Absolute thermodynamic critical pressure Vapor pressure absolute of liquid at inlet temperature FF Liquid critical pressure ratio factor, dimensionless ∆P Pressure drop (P1-P2) across the valve Fk Ratio of specific heats factor, dimensionless FL FLP FP Gf Gg Valve sizing coefficient Nominal valve size Internal diameter of the piping Rated liquid pressure recovery factor, dimensionless Combined liquid pressure recovery factor and piping geometry factor of valve with attached fittings (when there are no attached fittings, FLP equals FL), dimensionless q Volume rate of flow Maximum flow rate (choked flow conditions) at given upstream conditions Liquid specific gravity (ratio of density of liquid at flowing temperature to density of water at 60°F), dimensionless Gas specific gravity (ratio of density of flowing gas to density of air with both at standard conditions(1), i.e., ratio of molecular weight of gas to molecular weight of air), dimensionless T1 Absolute upstream temperature (deg Kelvin or deg Rankine) w Mass rate of flow Ratio of pressure drop to upstream absolute static pressure (∆P/P1), dimensionless Rated pressure drop ratio factor, dimensionless k Ratio of specific heats, dimensionless x K Head loss coefficient of a device, dimensionless xT M Molecular weight, dimensionless Y Expansion factor (ratio of flow coefficient for a gas to that for a liquid at the same Reynolds number), dimensionless N Numerical constant Z γ1 Compressibility factor, dimensionless Specific weight at inlet conditions N1 N2 N5 N6 Normal Conditions TN = 0°C Standard Conditions Ts = 16°C Standard Conditions Ts = 60°F υ N 0.0865 0.865 1.00 0.00214 890 0.00241 1000 2.73 27.3 63.3 3.94 394 4.17 417 Table 3-2. Equation Constants(1) Kinematic viscosity, centistokes w ---------------------kg/hr kg/hr pound/hr ------------- q Nm3/h Nm3/h gpm ---------------------Nm3/h Nm3/h Nm3/h Nm3/h p(2) kPa bar psia ------------kPa bar psia kPa bar kPa bar γ ---------------------kg/m3 kg/m3 pound/ft3 ------------- T ------------------------------deg Kelvin deg Kelvin deg Kelvin deg Kelvin d, D ---------mm inch mm inch ---------------------- 1360 ---- scfh psia ---- deg Rankine ---- Normal Conditions TN = 0°C 0.948 94.8 19.3 21.2 2120 kg/hr kg/hr pound/hr ------- ---------Nm3/h Nm3/h kPa bar psia kPa bar ---------------- deg Kelvin deg Kelvin deg Rankine deg Kelvin deg Kelvin ---------------- Standard Conditions TS = 16°C 22.4 2240 ------- Nm3/h Nm3/h kPa bar ------- deg Kelvin deg Kelvin ------- N8 N9(3) ∆Pmax(LP) qmax Piping geometry factor, dimensionless 1. Standard conditions are defined as 60°F and 14.7 psia. N7(3) Maximum allowable liquid sizing pressure drop Maximum allowable sizing pressure drop with attached fittings ∆Pmax(L) Standard Conditions 7320 ---scfh psia ---deg Rankine ---TS = 60°F 1. Many of the equations used in these sizing procedures contain a numerical constant, N, along with a numerical subscript. These numerical constants provide a means for using different units in the equations. Values for the various constants and the applicable units are given in the above table. For example, if the flow rate is given in U.S. gpm and the pressures are psia, N1 has a value of 1.00. If the flow rate is Nm3/h and the pressures are kPa, the N1 constant becomes 0.0865. 2. All pressures are absolute. 3. Pressure base is 101.3 kPa (1,01 bar) (14.7 psia). 636 Technical Valve Sizing (Standardized Method) Determining Piping Geometry Factor (Fp) Determine an Fp factor if any fittings such as reducers, elbows, or tees will be directly attached to the inlet and outlet connections of the control valve that is to be sized. When possible, it is recommended that Fp factors be determined experimentally by using the specified valve in actual tests. • For an outlet reducer: Calculate the Fp factor using the following equation: • For a valve installed between identical reducers: ∑K C Fp= 1 + N d2v 2 2 K2= 1.0 1- d 2 D -1/2 where, N2 = Numerical constant found in the Equation Constants table d = Assumed nominal valve size Cv = Valve sizing coefficient at 100% travel for the assumed valve size In the above equation, the ∑K term is the algebraic sum of the velocity head loss coefficients of all of the fittings that are attached to the control valve. ∑K = K1 + K2 + KB1 - KB2 where, K1 = Resistance coefficient of upstream fittings K2 = Resistance coefficient of downstream fittings KB1 = Inlet Bernoulli coefficient KB2 = Outlet Bernoulli coefficient The Bernoulli coefficients, KB1 and KB2, are used only when the diameter of the piping approaching the valve is different from the diameter of the piping leaving the valve, whereby: KB1 or KB2 = 1- d D 2 2 4 2 2 K1 + K2= 1.5 1- d 2 D Determining Maximum Flow Rate (qmax) Determine either qmax or ∆Pmax if it is possible for choked flow to develop within the control valve that is to be sized. The values can be determined by using the following procedures. FF = 0.96 - 0.28 If the inlet and outlet piping are of equal size, then the Bernoulli coefficients are also equal, KB1 = KB2, and therefore they are dropped from the equation. The most commonly used fitting in control valve installations is the short-length concentric reducer. The equations for this fitting are as follows: • For an inlet reducer: 2 PV PC Values of FL, the recovery factor for rotary valves installed without fittings attached, can be found in published coefficient tables. If the given valve is to be installed with fittings such as reducer attached to it, FL in the equation must be replaced by the quotient FLP/FP, where: 2 d = Nominal valve size D = Internal diameter of piping P1 - FF PV Gf Values for FF, the liquid critical pressure ratio factor, can be obtained from Figure 3-1, or from the following equation: where, d2 K1= 0.5 1- D 2 qmax = N1FLCV -1/2 1 K CV FLP = 1 d2 + F 2 N2 L and K1 = K1 + KB1 where, K1 = Resistance coefficient of upstream fittings KB1 = Inlet Bernoulli coefficient (See the procedure for Determining Fp, the Piping Geometry Factor, for definitions of the other constants and coefficients used in the above equations.) 637 Technical Valve Sizing (Standardized Method) ABSOLUTE VAPOR PRESSURE-bar 1.0 34 69 103 138 172 207 241 500 1000 1500 2000 2500 3000 3500 LIQUID CRITICAL PRESSURE RATIO FACTOR—FF 0.9 0.8 0.7 0.6 0.5 0 ABSOLUTE VAPOR PRESSURE-PSIA A2737-1 USE THIS CURVE FOR WATER, ENTER ON THE ABSCISSA AT THE WATER VAPOR PRESSURE AT THE VALVE INLET, PROCEED VERTICALLY TO INTERSECT THE CURVE, MOVE HORIZONTALLY TO THE LEFT TO READ THE CRITICAL PRESSURE RATIO, Ff, ON THE ORDINATE. Figure 3-1. Liquid Critical Pressure Ratio Factor for Water Determining Allowable Sizing Pressure Drop (∆Pmax) ∆Pmax (the allowable sizing pressure drop) can be determined from the following relationships: For valves installed without fittings: ∆Pmax(L) = FL2 (P1 - FF PV) For valves installed with fittings attached: 2 F ∆Pmax(LP) = LP (P1 - FF PV) FP where, P1 = Upstream absolute static pressure P2 = Downstream absolute static pressure Pv = Absolute vapor pressure at inlet temperature Values of FF, the liquid critical pressure ratio factor, can be obtained from Figure 3-1 or from the following equation: FF = 0.96 - 0.28 PV Pc An explanation of how to calculate values of FLP, the recovery factor for valves installed with fittings attached, is presented in the preceding procedure Determining qmax (the Maximum Flow Rate). Once the ∆Pmax value has been obtained from the appropriate equation, it should be compared with the actual service pressure differential (∆P = P1 - P2). If ∆Pmax is less than ∆P, this is an 638 indication that choked flow conditions will exist under the service conditions specified. If choked flow conditions do exist (∆Pmax < P1 - P2), then step 5 of the procedure for Sizing Valves for Liquids must be modified by replacing the actual service pressure differential (P1 - P2) in the appropriate valve sizing equation with the calculated ∆Pmax value. Note Once it is known that choked flow conditions will develop within the specified valve design (∆Pmax is calculated to be less than ∆P), a further distinction can be made to determine whether the choked flow is caused by cavitation or flashing. The choked flow conditions are caused by flashing if the outlet pressure of the given valve is less than the vapor pressure of the flowing liquid. The choked flow conditions are caused by cavitation if the outlet pressure of the valve is greater than the vapor pressure of the flowing liquid. Liquid Sizing Sample Problem Assume an installation that, at initial plant startup, will not be operating at maximum design capability. The lines are sized for the ultimate system capacity, but there is a desire to install a control valve now which is sized only for currently anticipated requirements. The line size is 8-inch (DN 200) and an ASME CL300 globe valve with an equal percentage cage has been specified. Standard concentric reducers will be used to install the valve into the line. Determine the appropriate valve size. Technical Valve Sizing (Standardized Method) 1.0 LIQUID CRITICAL PRESSURE RATIO FACTOR—FF 0.9 0.8 0.7 0.6 0.5 0 0.10 0.20 0.30 0.40 0.50 0.60 0.80 0.70 0.90 1.00 Pv absolute vapor pressure absolute thermodynamic critical pressure Pc use this curve for liquids other than water. determine the vapor pressure/ critical pressure ratio by dividing the liquid vapor pressure at the valve inlet by the critical pressure of the liquid. enter on the abscissa at the ratio just calculated and proceed vertically to intersect the curve. move horizontally to the left and read the critical pressure ratio, ff, on the ordinate. Figure 3-2. Liquid Critical Pressure Ratio Factor for Liquids Other Than Water 1. Specify the necessary variables required to size the valve: • Desired Valve Design—ASME CL300 globe valve with equal percentage cage and an assumed valve size of 3-inches. • Process Fluid—liquid propane • Service Conditions—q = 800 gpm (3028 l/min) P1 = 300 psig (20,7 bar) = 314.7 psia (21,7 bar a) P2 = 275 psig (19,0 bar) = 289.7 psia (20,0 bar a) ∆P = 25 psi (1,7 bar) T1 = 70°F (21°C) Cv d2 ∑K Fp = 1 + N2 2 -1/2 where, N2 = 890, from the Equation Constants table d = 3-inch (76 mm), from step 1 Cv = 121, from the flow coefficient table for an ASME CL300, 3-inch globe valve with equal percentage cage Gf = 0.50 To compute ∑K for a valve installed between identical concentric reducers: Pv = 124.3 psia (8,6 bar a) ∑K = K1 + K2 Pc = 616.3 psia (42,5 bar a) = 1.5 1 - d 2 D 2 2 2. Use an N1 value of 1.0 from the Equation Constants table. 3. Determine Fp, the piping geometry factor. (3)2 = 1.5 1 - (8)2 Because it is proposed to install a 3-inch valve in an 8-inch (DN 200) line, it will be necessary to determine the piping geometry factor, Fp, which corrects for losses caused by fittings attached to the valve. 2 = 1.11 639 Technical Valve Sizing (Standardized Method) where, and D = 8-inch (203 mm), the internal diameter of the piping so, 2 Fp = 1 + -1/2 1.11 121 890 32 ∑K Cv Fp = 1.0 + N d2 2 0.84 203 = 1.0 + 890 2 4 = 0.90 q N1Fp P1 - P2 Gf The required Cv of 125.7 exceeds the capacity of the assumed valve, which has a Cv of 121. Although for this example it may be obvious that the next larger size (4-inch) would be the correct valve size, this may not always be true, and a repeat of the above procedure should be carried out. Recalculate the required Cv using an assumed Cv value of 203 in the Fp calculation. This solution indicates only that the 4-inch valve is large enough to satisfy the service conditions given. There may be cases, however, where a more accurate prediction of the Cv is required. In such cases, the required Cv should be redetermined using a new Fp value based on the Cv value obtained above. In this example, Cv is 121.7, which leads to the following result: Fp = 1.0 + = 0.84 640 2 = 0.97 -1/2 2 -1/2 The required Cv then becomes: q Cv = N1Fp P1 - P2 Gf 800 = 2 ∑K Cv N2 d2 0.84 121.7 = 1.0 + 890 42 where, 2 25 0.5 = 121.7 6. Select the valve size using the flow coefficient table and the calculated Cv value. ∑K = K1 + K2 800 (1.0) (0.93) = 125.7 Assuming a 4-inches valve, Cv = 203. This value was determined from the flow coefficient table for an ASME CL300, 4-inch globe valve with an equal percentage cage. P1 - P2 Gf N1Fp = 800 (1.0) (0.90) 25 0.5 16 = 1.5 1 - 64 -1/2 q Cv = 5. Solve for Cv, using the appropriate equation. d2 = 1.5 1 - 2 D 2 and Based on the small required pressure drop, the flow will not be choked (∆Pmax > ∆P). = -1/2 = 0.93 4. Determine ∆Pmax (the Allowable Sizing Pressure Drop.) Cv = 2 (1.0) (0.97) 25 0.5 = 116.2 Because this newly determined Cv is very close to the Cv used initially for this recalculation (116.2 versus 121.7), the valve sizing procedure is complete, and the conclusion is that a 4-inch valve opened to about 75% of total travel should be adequate for the required specifications. T echnical Valve Sizing (Standardized Method) Gas and Steam Valve Sizing Sizing Valves for Compressible Fluids Following is a six-step procedure for the sizing of control valves for compressible flow using the ISA standardized procedure. Each of these steps is important and must be considered during any valve sizing procedure. Steps 3 and 4 concern the determination of certain sizing factors that may or may not be required in the sizing equation depending on the service conditions of the sizing problem. If it is necessary for one or both of these sizing factors to be included in the sizing equation for a particular sizing problem, refer to the appropriate factor determination section(s), which is referenced and located in the following text. to the valve, the Fp factor must be considered in the sizing procedure. If, however, no fittings are attached to the valve, Fp has a value of 1.0 and simply drops out of the sizing equation. Also, for rotary valves with reducers and other valve designs and fitting styles, determine the Fp factors by using the procedure for Determining Fp, the Piping Geometry Factor, which is located in Liquid Valve Sizing Section. 4. Determine Y, the expansion factor, as follows: Y=1- x 3Fk xT where, Fk = k/1.4, the ratio of specific heats factor 1. Specify the necessary variables required to size the valve as follows: k = Ratio of specific heats x = P/P1, the pressure drop ratio • Desired valve design (e.g. balanced globe with linear cage) xT = The pressure drop ratio factor for valves installed without attached fittings. More definitively, xT is the pressure drop ratio required to produce critical, or maximum, flow through the valve when Fk = 1.0 • Process fluid (air, natural gas, steam, etc.) and • Appropriate service conditions— q, or w, P1, P2 or P, T1, Gg, M, k, Z, and γ1 The ability to recognize which terms are appropriate for a specific sizing procedure can only be acquired through experience with different valve sizing problems. If any of the above terms appear to be new or unfamiliar, refer to the Abbreviations and Terminology Table 3-1 in Liquid Valve Sizing Section for a complete definition. If the control valve to be installed has fittings such as reducers or elbows attached to it, then their effect is accounted for in the expansion factor equation by replacing the xT term with a new factor xTP. A procedure for determining the xTP factor is described in the following section for Determining xTP, the Pressure Drop Ratio Factor. Note 2. Determine the equation constant, N. N is a numerical constant contained in each of the flow equations to provide a means for using different systems of units. Values for these various constants and their applicable units are given in the Equation Constants Table 3-2 in Liquid Valve Sizing Section. Conditions of critical pressure drop are realized when the value of x becomes equal to or exceeds the appropriate value of the product of either Fk xT or Fk xTP at which point: Use either N7 or N9 if sizing the valve for a flow rate in volumetric units (SCFH or Nm3/h). Which of the two constants to use depends upon the specified service conditions. N7 can be used only if the specific gravity, Gg, of the following gas has been specified along with the other required service conditions. N9 can be used only if the molecular weight, M, of the gas has been specified. y=1- Although in actual service, pressure drop ratios can, and often will, exceed the indicated critical values, this is the point where critical flow conditions develop. Thus, for a constant P1, decreasing P2 (i.e., increasing P) will not result in an increase in the flow rate through the valve. Values of x, therefore, greater Use either N6 or N8 if sizing the valve for a flow rate in mass than the product of either FkxT or FkxTP must never be substituted in the expression for Y. This means that Y can never be less units (pound/hr or kg/hr). Which of the two constants to use than 0.667. This same limit on values of x also applies to the flow depends upon the specified service conditions. N6 can equations that are introduced in the next section. be used only if the specific weight, γ1, of the flowing gas has been specified along with the other required service 5. Solve for the required Cv using the appropriate equation: conditions. N8 can be used only if the molecular weight, M, of the gas has been specified. For volumetric flow rate units— 3. Determine Fp, the piping geometry factor. x = 1 - 1/3 = 0.667 3Fk xT Fp is a correction factor that accounts for any pressure losses due to piping fittings such as reducers, elbows, or tees that might be attached directly to the inlet and outlet connections of the control valves to be sized. If such fittings are attached • If the specific gravity, Gg, of the gas has been specified: Cv = q N7 FP P1 Y x Gg T1 Z 641 T echnical Valve Sizing (Standardized Method) • If the molecular weight, M, of the gas has been specified: Cv = q N7 FP P1 Y x M T1 Z For mass flow rate units— • If the specific weight, γ1, of the gas has been specified: Cv = w N6 FP Y • If the molecular weight, M, of the gas has been specified: w Cv = xM N8 FP P1 Y T1 Z In addition to Cv, two other flow coefficients, Kv and Av, are used, particularly outside of North America. The following relationships exist: Kv = (0.865)(Cv) Av = (2.40 x 10-5)(Cv) 6. Select the valve size using the appropriate flow coefficient table and the calculated Cv value. Determining xTP, the Pressure Drop Ratio Factor If the control valve is to be installed with attached fittings such as reducers or elbows, then their effect is accounted for in the expansion factor equation by replacing the xT term with a new factor, xTP. xTP = xT 1+ xT Ki Cv N5 d2 Compressible Fluid Sizing Sample Problem No. 1 Determine the size and percent opening for a Fisher® Design V250 ball valve operating with the following service conditions. Assume that the valve and line size are equal. 1. Specify the necessary variables required to size the valve: x P1 γ1 2 KB1 = Inlet Bernoulli coefficient (see the procedure for Determining Fp, the Piping Geometry Factor, which is contained in the section for Sizing Valves for Liquids). -1 • Desired valve design—Design V250 valve • Process fluid—Natural gas • Service conditions— P1 = 200 psig (13,8 bar) = 214.7 psia (14,8 bar) P2 = 50 psig (3,4 bar) = 64.7 psia (4,5 bar) P = 150 psi (10,3 bar) x = P/P1 = 150/214.7 = 0.70 T1 = 60°F (16°C) = 520°R M = 17.38 Gg = 0.60 k = 1.31 q = 6.0 x 106 SCFH 2. Determine the appropriate equation constant, N, from the Equation Constants Table 3-2 in Liquid Valve Sizing Section. N5 = Numerical constant found in the Equation Constants table d = Assumed nominal valve size 3. Determine Fp, the piping geometry factor. Fp 2 where, Cv = Valve sizing coefficient from flow coefficient table at 100% travel for the assumed valve size Fp = Piping geometry factor xT = Pressure drop ratio for valves installed without fittings attached. xT values are included in the flow coefficient tables where, K1 = Resistance coefficient of upstream fittings (see the procedure for Determining Fp, the Piping Geometry Factor, which is contained in the section for Sizing Valves for Liquids). 642 Since valve and line size are assumed equal, Fp = 1.0. 4. Determine Y, the expansion factor. k Fk = 1.40 = In the above equation, Ki, is the inlet head loss coefficient, which is defined as: Ki = K1 + KB1 Because both Gg and M have been given in the service conditions, it is possible to use an equation containing either N7 or N9. In either case, the end result will be the same. Assume that the equation containing Gg has been arbitrarily selected for this problem. Therefore, N7 = 1360. 1.31 1.40 = 0.94 It is assumed that an 8-inch Design V250 valve will be adequate for the specified service conditions. From the flow coefficient Table 4-2, xT for an 8-inch Design V250 valve at 100% travel is 0.137. x = 0.70 (This was calculated in step 1.) T echnical Valve Sizing (Standardized Method) Since conditions of critical pressure drop are realized when the calculated value of x becomes equal to or exceeds the appropriate value of FkxT, these values should be compared. The appropriate flow coefficient table indicates that xT is higher at 75 degrees travel than at 80 degrees travel. Therefore, if the problem were to be reworked using a higher xT value, this should result in a further decline in the calculated required Cv. FkxT = (0.94) (0.137) = 0.129 Reworking the problem using the xT value corresponding to 78 degrees travel (i.e., xT = 0.328) leaves: Because the pressure drop ratio, x = 0.70 exceeds the calculated critical value, FkxT = 0.129, choked flow conditions are indicated. Therefore, Y = 0.667, and x = FkxT = 0.129. x = Fk xT = (0.94) (0.328) = 0.308 and, 5. Solve for required Cv using the appropriate equation. q Cv = x N7 FP P1 Y Gg T1 Z The compressibility factor, Z, can be assumed to be 1.0 for the gas pressure and temperature given and Fp = 1 because valve size and line size are equal. So, Cv = 6.0 x 106 (1360)(1.0)(214.7)(0.667) 0.129 (0.6)(520)(1.0) = 1515 6. Select the valve size using the flow coefficient table and the calculated Cv value. Cv = = q N7 FP P1 Y x Gg T1 Z 6.0 x 106 (1360)(1.0)(214.7)(0.667) 0.308 (0.6)(520)(1.0) = 980 The above Cv of 980 is quite close to the 75 degree travel Cv. The problem could be reworked further to obtain a more precise predicted opening; however, for the service conditions given, an 8-inch Design V250 valve installed in an 8-inch (203 mm) line will be approximately 75 degrees open. Compressible Fluid Sizing Sample Problem No. 2 The above result indicates that the valve is adequately sized (rated Cv = 2190). To determine the percent valve opening, note that the required Cv occurs at approximately 83 degrees for the 8-inch Design V250 valve. Note also that, at 83 degrees opening, the xT value is 0.252, which is substantially different from the rated value of 0.137 used initially in the problem. The next step is to rework the problem using the xT value for 83 degrees travel. The FkxT product must now be recalculated. x = Fk xT a. Desired valve design—ASME CL300 Design ED valve with a linear cage. Assume valve size is 4 inches. = (0.94) (0.252) b. Process fluid—superheated steam = 0.237 c. Service conditions— The required Cv now becomes: q Cv = x N7 FP P1 Y Gg T1 Z P1 = 500 psig (34,5 bar) = 514.7 psia (35,5 bar) P2 = 250 psig (17 bar) = 264.7 psia (18,3 bar) P = 250 psi (17 bar) x = P/P1 = 250/514.7 = 0.49 = 6.0 x 106 (1360)(1.0)(214.7)(0.667) = 1118 0.237 (0.6)(520)(1.0) Assume steam is to be supplied to a process designed to operate at 250 psig (17 bar). The supply source is a header maintained at 500 psig (34,5 bar) and 500°F (260°C). A 6-inch (DN 150) line from the steam main to the process is being planned. Also, make the assumption that if the required valve size is less than 6-inch (DN 150), it will be installed using concentric reducers. Determine the appropriate Design ED valve with a linear cage. 1. Specify the necessary variables required to size the valve: w = 125 000 pounds/hr (56 700 kg/hr) T1 = 500°F (260°C) The reason that the required Cv has dropped so dramatically 3 3 is attributable solely to the difference in the xT values at rated γ1 = 1.0434 pound/ft (16,71 kg/m ) and 83 degrees travel. A Cv of 1118 occurs between 75 and (from Properties of Saturated Steam Table) 80 degrees travel. k = 1.28 (from Properties of Saturated Steam Table) 643 T echnical Valve Sizing (Standardized Method) 2. Determine the appropriate equation constant, N, from the Equation Constants Table 3-2 in Liquid Valve Sizing Section. Because the 4-inch valve is to be installed in a 6-inch line, the xT term must be replaced by xTP. Because the specified flow rate is in mass units, (pound/hr), and the specific weight of the steam is also specified, the only sizing equation that can be used is that which contains the N6 constant. Therefore, where, N6 = 63.3 N5 = 1000, from the Equation Constants Table xTP = xT Fp2 1+ 3. Determine Fp, the piping geometry factor. d = 4 inches ΣK Fp = 1 + N2 where, N2 = 890, determined from the Equation Constants Table d = 4 inches Cv = 236, which is the value listed in the flow coefficient Table 4-3 for a 4-inch Design ED valve at 100% total travel. Cv = 1.5 1 - Fp = 1 + 0.463 890 Cv = 236, from step 3 and Ki = K1 + KB1 d2 = 0.5 1 - 2 D 2 42 2 where, 62 (1.0)(236) (4)2 2 where D = 6-inch so: = 644 4 6 4 1.28 1.40 x = 0.49 (As calculated in step 1.) 2 -1 = 0.67 Finally: Y=1- x 3 Fk xTP 0.49 (3) (0.91) (0.67) =1- x 3FkxTP = 0.91 + 1- 2 4 (0.69)(0.96) 236 0.69 xTP = 1+ 42 1000 0.952 -1/2 k Fk = 1.40 + 1- d D = 0.96 4. Determine Y, the expansion factor. 42 62 2 D2 = 0.95 Y=1- d2 = 0.5 1 - = 0.463 Finally, N5 -1 2 Fp = 0.95, determined in step 3 ΣK = K1 + K2 d2 Cv xT = 0.688, a value determined from the appropriate listing in the flow coefficient table d2 = 1.5 1 - -1/2 2 xT Ki = 0.73 5. Solve for required Cv using the appropriate equation. Cv = = w N6 FP Y x P1 γ1 125,000 (63.3)(0.95)(0.73) = 176 (0.49)(514.7)(1.0434) T echnical Valve Sizing (Standardized Method) Table 4-1. Representative Sizing Coefficients for Type 1098-EGR Regulator linear cage Body size, INCHES (dn) Line Size Equals Body Size 2:1 Line Size to Body Size Cv Cv XT FD 18.1 0.806 0.43 62.8 0.820 0.35 128 135 0.779 0.30 213 198 209 0.829 0.28 418 381 404 0.668 0.28 XT FD Regulating Wide-Open Regulating Wide-Open 1 (25) 16.8 17.7 17.2 2 (50) 63.3 66.7 59.6 3 (80) 132 139 4 (100) 202 6 (150) 397 FL 0.84 whisper trimTM cage Body size, INCHES (dn) Line Size Equals Body Size Piping 2:1 Line Size to Body Size Piping Cv Cv Regulating Wide-Open Regulating Wide-Open 1 (25) 16.7 17.6 15.6 16.4 0.753 0.10 2 (50) 54 57 52 55 0.820 0.07 3 (80) 107 113 106 110 0.775 0.05 4 (100) 180 190 171 180 0.766 0.04 6 (150) 295 310 291 306 0.648 0.03 FL 0.89 Table 4-2. Representative Sizing Coefficients for Rotary Shaft Valves VALVE SIZE, INCHES 1 1-1/2 VALVE STYLE V-Notch Ball Valve V-Notch Ball Valve V-Notch Ball Valve 2 High Performance Butterfly Valve V-Notch Ball Valve 3 High Performance Butterfly Valve V-Notch Ball Valve 4 High Performance Butterfly Valve V-Notch Ball Valve 6 High Performance Butterfly Valve V-Notch Ball Valve 8 High Performance Butterfly Valve V-Notch Ball Valve 10 High Performance Butterfly Valve V-Notch Ball Valve 12 High Performance Butterfly Valve V-Notch Ball Valve 16 High Performance Butterfly Valve DEGREES OF VALVE OPENING 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 60 90 CV FL XT FD 15.6 34.0 28.5 77.3 59.2 132 58.9 80.2 120 321 115 237 195 596 270 499 340 1100 664 1260 518 1820 1160 2180 1000 3000 1670 3600 1530 3980 2500 5400 2380 8270 3870 8600 0.86 0.86 0.85 0.74 0.81 0.77 0.76 0.71 0.80 0.74 0.81 0.64 0.80 0.62 0.69 0.53 0.80 0.58 0.66 0.55 0.82 0.54 0.66 0.48 0.80 0.56 0.66 0.48 0.78 0.63 ------0.80 0.37 0.69 0.52 0.53 0.42 0.50 0.27 0.53 0.41 0.50 0.44 0.50 0.30 0.46 0.28 0.52 0.22 0.32 0.19 0.52 0.20 0.33 0.20 0.54 0.18 0.31 0.19 0.47 0.19 0.38 0.17 0.49 0.25 ------0.45 0.13 0.40 0.23 ------------------0.49 0.70 0.92 0.99 0.49 0.70 0.92 0.99 0.49 0.70 0.91 0.99 0.49 0.70 0.91 0.99 0.49 0.70 0.91 0.99 0.49 0.70 0.92 0.99 0.49 0.70 0.92 1.00 ------- 645 T echnical Valve Sizing (Standardized Method) Table 4-3. Representative Sizing Coefficients for Design ED Single-Ported Globe Style Valve Bodies Valve Size, Inches 1/2 3/4 1 VALVE PLUG STYLE Post Guided Post Guided Micro-FormTM FLOW CHARACTERISTICS Equal Percentage Equal Percentage Equal Percentage Cage Guided Linear Equal Percentage Equal Percentage Micro-FormTM 1-1/2 Cage Guided PORT DIAMETER, INCHES (mm) 0.38 (9,7) 0.56 (14,2) 3/8 (9,5) 1/2 (12,7) 3/4 (19,1) 1-5/16 (33,3) 1-5/16 (33,3) 3/8 (9,5) 1/2 (12,7) 3/4 (19,1) 1-7/8 (47,6) 1-7/8 (47,6) 2-5/16 (58,7) 2-5/16 (58,7) 3-7/16 (87,3) ---- FL XT FD 2.41 5.92 3.07 4.91 8.84 20.6 17.2 3.20 5.18 10.2 39.2 35.8 72.9 59.7 148 136 0.90 0.84 0.89 0.93 0.97 0.84 0.88 0.84 0.91 0.92 0.82 0.84 0.77 0.85 0.82 0.82 0.54 0.61 0.66 0.80 0.92 0.64 0.67 0.65 0.71 0.80 0.66 0.68 0.64 0.69 0.62 0.68 0.61 0.61 0.72 0.67 0.62 0.34 0.38 0.72 0.67 0.62 0.34 0.38 0.33 0.31 0.30 0.32 2 Cage Guided 3 Cage Guided 4 Cage Guided Linear Equal Percentage 4-3/8 (111) ---- 2 (50,8) ---- 236 224 0.82 0.82 0.69 0.72 0.28 0.28 6 Cage Guided Linear Equal Percentage 7 (178) ---- 2 (50,8) ---- 433 394 0.84 0.85 0.74 0.78 0.28 0.26 8 Cage Guided Linear Equal Percentage 8 (203) ---- 3 (76,2) ---- 846 818 0.87 0.86 0.81 0.81 0.31 0.26 Refer to the flow coefficient Table 4-3 for Design ED valves with linear cage. Because the assumed 4-inch valve has a Cv of 236 at 100% travel and the next smaller size (3-inch) has a Cv of only 148, it can be surmised that the assumed size is correct. In the event that the calculated required Cv had been small enough to have been handled by the next smaller size, or if it had been larger than the rated Cv for the assumed size, it would have been necessary to rework the problem again using values for the new assumed size. 7.1 Turbulent flow 7.1.1 Non-choked turbulent flow 7.1.1.1 Non-choked turbulent flow without attached fittings [Applicable if x < FγxT] The flow coefficient shall be calculated using one of the following equations: Eq. 6 7. Sizing equations for compressible fluids. The equations listed below identify the relationships between flow rates, flow coefficients, related installation factors, and pertinent service conditions for control valves handling compressible fluids. Flow rates for compressible fluids may be encountered in either mass or volume units and thus equations are necessary to handle both situations. Flow coefficients may be calculated using the appropriate equations selected from the following. A sizing flow chart for compressible fluids is given in Annex B. The flow rate of a compressible fluid varies as a function of the ratio of the pressure differential to the absolute inlet pressure ( P/P1), designated by the symbol x. At values of x near zero, the equations in this section can be traced to the basic Bernoulli equation for Newtonian incompressible fluids. However, increasing values of x result in expansion and compressibility effects that require the use of appropriate factors (see Buresh, Schuder, and Driskell references). 646 CV Linear Equal Percentage Linear Equal Percentage Linear Equal Percentage 6. Select the valve size using flow coefficient tables and the calculated Cv value. RATED TRAVEL, INCHES (mm) 0.50 (12,7) 0.50 (12,7) 3/4 (19,1) 3/4 (19,1) 3/4 (19,1) 3/4 (19,1) 3/4 (19,1) 3/4 (19,1) 3/4 (19,1) 3/4 (19,1) 3/4 (19,1) 3/4 (19,1) 1-1/8 (28,6) 1-1/8 (28,6) 1-1/2 (38,1) ---- W C= N6Y Eq. 7 xP1ρ1 C= W N8P1Y T1Z xM C= Q N9P1Y MT1Z x C= Q N7P1Y GgT1Z x Eq. 8a Eq. 8b NOTE 1 Refer to 8.5 for details of the expansion factor Y. NOTE 2 See Annex C for values of M. 7.1.1.2 Non-choked turbulent flow with attached fittings [Applicable if x < FγxTP]