DO97-6T Conductivity transmitter f or in f ield installations and f or panel mounting data sheet DS-DO97-6T-i.49.1 SERIES Transmitters Conductivity transmitters Series DO97-6T receive the signal from a conductivity cell and from a Pt100 temperature sensor. The signal from the conductivity cell is thermocompensated and converted into a 420 mA output signal proportional to the measured value. The output is galvanically isolated from the input. An LCD display allows to locally indicate conductivity value and temperature value. The functional parameters of the instrument can be configured Using the display and the keyboard. The careful choice of the components make the instrument accurate and reliable. Applications: - drinking water plants - wastewater treatment plants - swimming pools - wherever conductivity is to be measured Automatic thermocompensation Input/output galvanic isolation Displayed indication of conductivity and temperature 24 Vac power supply or 24 Vdc two wire transmitter version Current output 0/420 mA Two programmable set points with relay output Operating principle Mod.DO97-6T transmitters receive the signal from a conductivity cell and a signal from a temperature sensing element (Pt100). The transmitter operate temperature compensation of the signal and give local indication of pH (ORP) value and temperature value. The measured value is also retransmitted on a 0/420 mA proportional output, which is galvanically isolated from the input. Two programmable set points drive two relay outputs. Relays status is indicated on display. Realization Mod.DO9766T transmitter is supplied with IP64 housing, suitable for in field installation. Mod.DO9786T transmitter is supplied with IP44 housing, suitable for panel mounting. FURTHER INFORMATION on Instruction Manual n.139. Available versions Mod.DO9766T ................................. Conductivity transmitter with IP64 housing, suitable for in field installation. Mod.DO9786T ................................... Conductivity transmitter with IP44 housing, suitable for panel mounting. DO97-6T TECHNICAL DATA Conductivity input Measuring range 2/4 electrodes Transducer supply Input impedance Cable length Accuracy Temperature input Pt100 2/4 wires Transducer supply Cable length Accuracy 0.0 199.9 mS cell constant 0.01199.9 cm-1 configurable square wave 101000 mV, according to f.s. 2001600 Hz, according to f.s. >100 M up to 10 m if not shielded, up to 50 m if shielded (apprx. 2 nF) 0.5 % of reading, 2 digit , thermal drift 0.01%/°C -50199,9°C 0.5 mA dc up to 10 m for non shielded cable, up to 50 m for shielded cable (2 nF apprx.) 0.1 % of reading, 0.2°C, thermal drift 0.01%/°C Mod.DO9766T Temperature compensation none manual linear 0.004.00%/°C -50+200°C automatic linear 0.004.00%/°C -50+200°C reference temperature 20°C or 25°C, configurable Current output 420 mA programmable and proportional to conductivity 0.5 % of reading, 0.02 mA 2500 Vca, 1 minute accuracy isolation Realys output A and B SPDT, 3A/230 Vac, voltage free Power supply passive 1035 V, 420 mA, two wire transmitter 24 Vac active Housing Mod.DO9766T external dimensions 120 x 122 x 56 mm protection IP64 Housing Mod.DO9786T esternal dimensions 96 x 96 x 126 mm protection IP44 CE compliance Mod.DO9786T according to perinent rules Calibration The instrument is factory calibrated. At start up it is only needed to verify the calibration of the measuring chain, using a solution with known conductivity value. More details on Instruction Manual. Order information for calibration solutions Mod. T/401– A Specify desired conductivity value: 1 mS, 12 mS, 100 mS. Via del Luisetto,4 20040 Cavenago Brianza –MI- Tel 0039 02 95339721 Fax 0039 02 95339659 Em a i l clrmail@tin.it I n t e r n e t a d d r e s s : www. c l r i t a l i a . c o m CLR reserves the right to make modifications without previous notice