GE Global Research - Niskayuna Site Electrical Standards DEFINITIONS Accessible – Capable of being operated without unbolting covers or having services disconnect and/or material moved out of the way in a manner other than rolling it on its own wheels. Low Voltage – Nominal voltages from 0 to and including 600. Medium Voltage – Nominal voltages of 1000 to 35,000. High Voltage – Nominal voltages greater than or equal to 35,000. GENERAL REQUIREMENTS Boxes And Condulets 1. All “FS” type boxes shall include factory installed ground screws. In addition, all wall and floor mounted “FS” type boxes will include integral mounting lugs. 2. Condulet bodies of the “C”, “LB”, “LL”, “LR”, “T”, etc. types shall not be used for splicing. 3. All pendant hung boxes shall have integral threaded hubs. Conduit And Connectors 1. Flexible steel conduit and liquidtight flexible steel conduit shall only be used where flexibility is required. They shall not be used in lengths longer than three feet without permission of a GE Global Research – Niskayuna “ Facilities Services Operation” electrical engineer. 2. All conduit and cable connectors that are not equipped with a factory nylon insulator shall have a conduit bushing installed on the end of the connector after the locknut. 3. Rigid steel conduit nipples, not chase nipples, shall be used when connecting a conduit coupling or a condulet directly to an enclosure. 4. Rigid steel conduit nipples, not chase nipples, shall be used when close coupling enclosures through knockouts. 5. Double locknuts shall be used when connecting conduit to an enclosure through a knockout. Equipment Ratings 1. Heavy duty industrial rated devices shall be used for all safety switches and other electrical equipment. NEMA rated devices shall be the preference for all contactor/motor starter applications. 2. Unless installed for a specific item of equipment, all 120 volt convenience receptacles and their circuits shall be 20 amps. 1 Fill 1. Condulet and box fill markings shall be strictly adhered to. Where factory markings are not present, fill shall be determined using National Electrical Code Article 314. Flexible Cord, Cable And Their Connectors 1. Flexible cord and cable shall only be used were portability is required. Unless supplied by a factory as the connection means for an item of equipment, it shall always be used with a plug on one end. Where it is supplied by a factory as the connection means for an item of equipment, it can be used with or without a plug depending if movement on wheels or ease of disconnect is required or not. 2. Except for cable tray applications, Type SO/SOW-A cord shall be used for all flexible cord requirements through 80 amps. Above 80 amps, Type W cable shall be used. For cable tray applications, Type TC cable shall be used. 3. Only copper conductors shall be used in wire, cords and cables. 4. Size (AWG) of Type SO/SOW-A cord to use shall be determined according to the following: OVERCURRENT PROTECTION (AMPS) 15 20 25 30 35 40 45 50 60 70 80 NUMBER OF CURRENT CARRYING CONDUCTORS 2 3 4 14 14 12 12 12 10 12 10 8 10 8 6 8 8 6 8 6 4 6 6 4 6 4 2 4 4 2 4 2 2 2 - TREAT NEUTRALS OF 3 PHASE, 4 WIRE WYE CIRCUITS WHERE THE MAJOR PORTION OF THE LOAD CONSISTS OF NONLINEAR LOADS AS CURRENT CARRYING CONDUCTORS. FOR MORE THAN 4 CURRENT CARRYING CONDUCTORS, SEE NATIONAL ELECTRICAL CODE ARTICLE 400, PARAGRAPH 400.5. 5. All conduit and cable connectors that are not equipped with a factory nylon insulator shall have a conduit bushing installed on the end of the connector after the locknut. 2 GFCI Requirements 1. All receptacles within six (6) feet of a sink (excluding a cup sink) or water fountain shall be GFCI protected and shall be so marked. All water fountains shall be fed from a GFCI circuit breaker or receptacle. 2. All receptacles mounted on a wet hood shall be on a GFCI protected circuit. Grounding 1. Conduits containing conductors carrying an open circuit voltage of 50 volts or more shall include a separate copper equipment grounding conductor. This conductor shall be sized according to the following: CONDUCTOR OVERCURRENT EQUIPMENT GROUNDING PROTECTION RATING CONDUCTOR SIZE (in AMPS) (in AWG) 15 14 20 12 30 10 50 10 65 8 100 6 200 4 300 3 400 2 500 1 600 1/0 800 2/0 1000 3/0 1200 4/0 Any overcurrent protection falling between the values shown will require the next higher ground conductor size. 2. All non-current-carrying conductive material enclosing conductors of 50 volts or more, ie. junction boxes, pull boxes, switch boxes, receptacle boxes, etc., shall be grounded using the equipment grounding conductor. 3. Bonding and grounding bushings shall be used on the conduit of feeders and branch circuits with an overcurrent protection of 100 amps or more. They shall be install on all box entries and exits of these services. 4. Safety switches shall be equipped with the appropriate factory equipment grounding kit and, if required, the appropriate factory neutral kit. 5. Listed grounding devices shall be used in all equipment, pull boxes and junction boxes not supplied with a factory grounding lug or a factory threaded hole designated for grounding. GE manufactured equipment grounding kits shall be used in GE manufactured distribution equipment where such kits are available for the item of equipment being installed. The listed grounding devices and grounding kits shall be used in lieu of drilling holes in the sheet metal enclosure and/or using standard screws or bolts and nuts. 3 6. One leg of all control power transformer secondaries greater than 24 volts shall be grounded at the transformer. 7. All buildings with a footprint of 1000 square feet or more shall have a building ground grid. Building grounding conductors shall be 4/0. Exothermic welding shall be the preferred method for connecting and terminating building ground conductors. Ground rods shall be copper-clad solid steel with a minimum size of 5/8” diameter by 8 feet long. Triads of ground rods on ten foot centers at building corners is the preferred arrangement. Systems shall be tested to insure that the resistance to ground is 3 ohms or less. If the building grounding system tests to more than 3 ohms before being tied to the cold water service and the building steel, additional ground rods shall be added until the loop resistance requirement of 3 ohms or less is met. Additional ground rods shall be spaced no less than 10 feet from existing ground rods. 8. Double locknuts shall be used when connecting conduit to an enclosure through a knockout. 9. Where a wireway contains conductors of various sizes, but only one equipment grounding conductor, the size of the equipment grounding conductor shall be determined first based on the largest overcurrent device setting for the conductors, and then, if necessary, based on voltage drop. Installation 1. All pendant hung receptacles and switches will be mounted in boxes with integral threaded hubs. Wiremesh grips shall be used at the top and bottom of the pendant where flexible steel conduit, liquidtight flexible steel conduit or flexible cord is used. 2. All conduit and cable connectors that are not equipped with a factory nylon insulator shall have a conduit bushing installed on the end of the connector after the locknut. 3. All suspended ceiling drop-in lighting troffers shall be separately supported from the deck at a minimum of two opposite corners unless the ceiling is classified as a “listed assembly”. 4. All above-the-ceiling wiring shall be supported so that it is off of the ceiling and off of mechanical piping and electrical conduit. Supports shall extend to the deck. Where ceiling hanging wire is used to support the wiring, the wire shall be independent of that used to support the ceiling and shall be tied down on the bottom. 5. Every effort shall be made to bring conduits containing the line side conductors to motor starters and safety switches into the top third of the enclosure and to take the conduits containing the load side conductors from motor starters and safety switches out the bottom third of the enclosure. 6. EMT conduit shall not be used to support light fixtures either as a pendant mount or as a support from which to hang fixture chain. 7. Rigid steel conduit nipples, not chase nipples, shall be used when connecting a conduit coupling or a condulet directly to an enclosure through a knockout. 4 8. Rigid steel conduit nipples, not chase nipples, shall be used when close coupling enclosures through knockouts. 9. Double locknuts shall be used when connecting conduit to an enclosure through a knockout. 10. Clearances around and above electrical equipment shall be maintained according to National Electrical Code Article 110, Paragraph 110.26. 11. Equipment control wiring, as DDC wiring, shall not share the same raceway as power wiring. 12. Wiring to VFD controllers shall be per the manufacturer’s recommendation. Lockout Means 1. All motor starters, manual or magnetic, shall be equipped with a means to lock out the starter other than the branch circuit breaker. 2. Unless the equipment for which the receptacles are being installed has an accessible main breaker capable of being locked out, all single phase and three phase receptacles over 30 amps shall be equipped with a disconnecting lockout means other than their branch circuit breakers. Marking, Labelling And Color Coding 1. All panelboards shall be marked with the panelboard designation, as LP2B23 for 208 or 240 volt panelboards and PP1C13 for 480 volt panelboards, where 2B23 and 1C13 are room designations for the panelboard location. In addition, they shall also be marked with the highest voltage of the panelboard, the phase color coding and the source from where the panelboard is fed. Finally, lighting relay panelboards shall have the prefixes LRC- and PRC- in place of the LP- and PP- for 208/240 volt and 480 volt panelboards, respectively. 2. All safety switches shall be marked with a safety switch number (if group mounted), the name or designation of the equipment that it feeds, the highest voltage in the switch, whether the safety switch is fused or unfused and the source from where the switch is fed. 3. All motor control center (MCC) cubicles shall be marked with a reference designation, as 3C, where 3 is the MCC section number from left to right and C is the cubicle designation from top to bottom. Each cubicle shall also be marked with its purpose and/or the GE Global Research designation for the piece of equipment or motor that the cubicle feeds or controls. Other markings, such as “CAUTION – THIS EQUIPMENT MAY START AT ANY TIME” or “FED WITH POWER FROM “X” SEPARATE SOURCES”, may be required. Where multiple sources of power are present in a cubicle, all sources shall be listed on the front of that cubicle. 4. All separately mounting motor starters/contactors shall be marked with the highest voltage in the starter/contactor, the GE Global Research designation for the motor or equipment that the starter/contactor controls 5 5. 6. 7. 8. 9. and the source from where the starter/contactor is fed. Other markings may be required (See Item No. 3 above). All separate sources of power found inside of an item of electrical equipment shall be listed on the front of the equipment enclosure. All receptacles shall be marked with the panelboard designation and circuit number from where they are fed. The isolated ground conductor of an isolated ground circuit shall be green with a yellow tracer. All light switches shall be marked with the source of the wiring to the switch. The insulation of all 208Y/120 and 480Y/277 wire through 750 KCM shall be factory color coded per the coding shown under Wire in this section. Neutrals (Grounded Conductor) 1. Safety switches shall be equipped with the appropriate factory equipment grounding kit and, if required, the appropriate factory neutral kit. 2. All receptacle strips with 120 volt outlets fed from more than one circuit shall have a separate neutral for each circuit. 3. Neutrals for all multi-pole, non-linear computer and electronic loads shall be sized at least 1.732 times the overcurrent protection of the circuit they are feeding. 4. All ballasted and electric-discharge lighting circuits shall be installed with a separate neutral for each circuit. 5. All single-pole branch circuits shall have a separate neutral for that branch circuit. Overcurrent Protection 1. Both the primaries and the secondaries of all control power transformers shall be overcurrent protected. Protection shall be per NEC Article 450. Fuses or circuit breakers shall be coordinated between the primaries and the secondaries so that the secondary protection will blow or trip before the primary protection. 2. Unless installed for a specific item of equipment, all 120 volt convenience receptacles and their circuits shall be 20 amps. 3. For overcurrent protection of flexible cords and cables, see “Flexible Cords, Cables And Their Connectors” above. Panelboards 1. Panelboards 24” and over in height shall have their covers hinged to the backbox. 6 Receptacles 1. GE Global Research - Niskayuna has a receptacle standard that shall be followed for all receptacle applications referenced in said standard. 2. All receptacles within six (6) feet of a sink (excluding a cup sink) or water fountain shall be GFCI protected and shall be so marked. All water fountains shall be fed from a GFCI circuit breaker or receptacle. 3. Unless installed for a specific item of equipment, all 120 volt convenience receptacles and their circuits shall be 20 amps. 4. All single phase and three phase receptacles over 30 amps shall be equipped with a disconnecting lockout means other than their branch circuit breakers. 5. All single and duplex receptacles are to be mounted with the ground hole in the face above the other holes. 6. When available for the NEMA configuration being installed, receptacles on emergency power shall be red. Safety Switches 1. Safety switches shall be equipped with the appropriate factory equipment grounding kit and, if required, the appropriate factory neutral kit. 2. All single phase and three phase receptacles over 30 amps shall be equipped with a disconnecting lockout means other than their branch circuit breakers. Supporting 1. All suspended ceiling drop-in lighting troffers shall be separately supported from the deck at a minimum of two opposite corners unless the ceiling is classified as a “listed assembly”. 2. All above-the-ceiling wiring shall be supported so that it is off of the ceiling and off of mechanical piping and electrical conduit. Supports shall extend to the deck, shall be tied down on both ends and shall be distinguished from ceiling support wires by a tag or by color. 3. Outlet and switch boxes recessed in metal stud walls shall be supported by both the stud to the left and the stud to the right of the box. Support shall be with a Caddy Cat. No. HBS16 bracket or equal. Where there is not a full 16” center between studs, a Caddy Cat. No. H23 bracket or equal shall be used. 4. Wooden backboards installed on walls to support electrical equipment shall be made of flame resistant lumber or shall be interior grade lumber painted with flame resistant paint. 7 Voltage Drop Allowance Size homerun branch circuit conductors from the panelboard to the first outlet in accordance with the following maximum circuit length limits using the center of the load served as the basis for computing circuit lengths. CIRCUIT VOLTAGE 120 VOLT (20 AMP CIRCUIT) 277 VOLT (20 AMP CIRCUIT) CONDUCTOR SIZE (AWG) 12 10 8 65 FEET 110 FEET 165 FEET 150 FEET 250 FEET 380 FEET PROVIDE MINIMUM #12 AWG CONDUCTORS BEYOND THE FIRST OUTLET Wire 1. Standard phase color codes shall be as follows: 120, 208, 240 volts Phase A – black Phase B – red Phase C – blue Neutral - white 277, 480 volts Phase A – brown Phase B – orange Phase C – yellow Neutral – white or gray* 4160 volts Phase A – violet & violet Phase B – violet & red Phase C – violet & blue 34,500 volts Phase A – violet & brown Phase B – violet & orange Phase C – violet & yellow *Gray shall be used for the neutral in a 277/480 application when both the 120/208 volt and 277/480 volt neutrals are present in the same wireway. 2. Only copper conductors shall be used in permanently installed wire, cords and cables. 8 3. Fire alarm wiring shall be per the system manufacturer’s requirements. It shall have no splices. 4. The isolated ground conductor of an isolated ground circuit shall be green with a yellow tracer. 5. Wire Ampacity Derating Where more than three current carrying conductors are installed in a raceway, the ampacity of the conductors shall be derated according to the following table: MINIMUM PERMISSIBLE WIRE SIZE (AWG) (MAX. 20 AMP CIRCUITS) 12 10 8 NUMBER OF CURRENT CARRYING CONDUCTORS FOUR TO SIX SEVEN TO NINE TEN TO TWENTY TREAT NEUTRALS OF 3 PHASE, 4 WIRE WYE CIRCUITS WHERE THE MAJOR PORTION OF THE LOAD CONSISTS OF NONLINEAR LOADS AS CURRENT CARRYING CONDUCTORS. NOTE: The above paragraphs are enhancements to the National Electrical Code, which shall be followed for all applications not mentioned above. The owner’s Authority Having Jurisdiction shall be consulted on any questions or if any exceptions are taken. MATERIALS 1. Insulated grounds of Type AC and Type MC cable assemblies shall be green in color. 2. Strings of temporary lighting shall be of the factory assembled molded cable type with guards. Strings shall be suspended by the loops on the lighting fixtures, not by the cord. 3. Unless a larger capacity is required, all metal surface raceway used for convenience outlets shall be the Wiremold 3000 Series. 4. All plastic surface raceway and its accessories used in offices for convenience outlets and communications shall be the Panduit PAN-WAY Type T Surface Raceway in the TG-70 Series. 5. Only copper conductors shall be used in permanently installed wire, cords and cables. 6. Compression connectors used on wire and cable terminations and splices shall be the “COPPER ONLY” type. 7. All motor control centers, starters or other equipment requiring indicator lights shall use LED-type lamps. 9 8. Wet chemical hoods shall not have switches or receptacles mounted below the face of the hood. 9. All lighted exit signs and lighted information signs, as “CAUTION – LASER ON”, shall be of the LED type. 10. Variable frequency drives installed for Facilities owned pumps and HVAC units shall be per the specifications developed by GE GRC - Niskayuna Facilities Engineering. 11. Emergency power transfer switches installed for Facilities owned infrastructure shall be per the specifications developed by GE GRC – Niskayuna Facilities Engineering. 12. All lighting control panels installed in the support of infrastructure lighting shall be GE TLC Level 3 panels with the Controller Card installed. The correct number of Input/Output Cards for the number of relays present in the panel shall also be supplied at the time of installation of the panel. 13. When manufactured by GE, GE motors and controls, to include motor starters, equipment control devices such as relays, push buttons and programmable controllers, variable frequency drives, etc., shall be used. Package manufacturers shall be strongly encouraged to supply GE controls in their equipment. Where delivery becomes an issue, the owner’s Authority Having Jurisdiction shall be consulted. 14. All motor starters and safety switches installed out-of-doors shall have a NEMA 4 rated enclosure. 15. Trip programmers of main breakers and tie breakers of 480 volt load center unit substations shall have long time, short time and ground fault functions. Trip programmers of feeder breakers of 480 volt load center unit substations shall have long time, short time, instantaneous and ground fault functions. 16. Delta secondary transformers are prohibited. 17. The insulation of all 208Y/120 and 480Y/277 wire through 750 KCM shall be factory color coded per the coding shown under Wire in the GENERAL REQUIREMENTS section. OPERATIONS 1. All condensate pumps shall be backed up with emergency power. 2. All fire alarm panels and their associated peripheral equipment, whether equipped with battery back-up or not, shall be backed up with emergency power. 3. All motors 40 horsepower or more that are not controlled with a variable frequency drive shall be equipped with power factor correction capacitors that correct the power factor to better than 95 percent, but less than or equal to the maximum shown on the motor nameplate. 4. Automated control features for HVAC equipment, such as START or PURGE, shall not override the “OFF” position of an “OFF-ON” or “HANDOFF-AUTO” switch. 5. Switching orders shall be written for the opening or closing of one or more low voltage load center unit substation breakers, medium voltage substation breakers or load interrupting switches or high voltage substation breakers or 10 load interrupting switches. These orders shall be written by one member and approved by a second member of the GE Global Research’s Facilities Operation salaried electrical staff. 6. All rooms housing infrastructure type electrical equipment shall have a minimum of one light fixture and one convenience outlet on emergency power. 7. Wooden backboards installed on walls to support electrical equipment shall be made of flame resistant lumber or shall be interior grade lumber painted with flame resistant paint. Last Revised: 4/27/09 8:27 am 11