Chapter SM 4: Heat and Mass Exchangers SM 4.1 Introduction In a number of HVAC components, water evaporates into or condenses out of an air stream. In an evaporative cooler, a warm and relatively dry air stream is cooled through evaporation from either a wet surface or water sprays. Such units are used for space cooling in the dry southern western areas of the country. In a humidifier, water or steam is sprayed into an air stream to increase the humidity level. Humidifiers are used to increase the humidity of dry and uncomfortable air that enters the building in very cold climates. Air washers are used to entrain particles and to clean the air flow through the spraying water into the air stream. These units are sometimes used instead of mechanical filters. Enthalpy exchangers are devices that exchange heat and moisture between two air streams, and often a desiccant is used as the exchange medium. In summer these units are used to remove the heat and moisture from incoming ventilation air and transfer it to exhaust air, which reduces the load on the cooling coil. In winter operation the exchanger is used to preheat and humidify the ventilation air. All of the devices described here fit specific niches in HVAC systems. The basic thermodynamic, heat, and mass transfer principles for these devices will be presented in this chapter. The performance of these heat and mass exchangers can usually be expressed in terms of the parameters used for heat exchangers (Chapter 13) and cooling coils (Chapter 14). SM 4.2 Evaporative Coolers An evaporative cooler is shown schematically in Figure 4.1. A warm and relatively dry air stream, usually from the ambient, enters the device and passes over wetted pads or surfaces. Evaporation of the water cools and humidifies the air stream. The exchange surfaces are maintained wet by a circulating water flow. An alternative to using wetted surfaces is to spray water into the air, but it is more difficult to control the degree of saturation in this method. The evaporative cooler process is shown on a psychrometric diagram in Figure 4.1. w Tw m a m Tin Tout 4.1 Figure 4.1 Schematic of evaporative cooler process The air outlet state can be related to the inlet state through application of mass and energy balances. A steady-state mass balance on the water is a w in m wm a w out 0 m (4.1) where ma and m w are the air and water flow rates, respectively, and win and wout are the inlet and outlet humidity ratios. Equation 4.1 relates the mass of water that evaporates to the humidity levels. The energy balance for the process incorporates the water mass flow rate from equation 4.1 (4.2) a h in h out m a w out w in h w 0 m where hin and hout are the enthalpies of the entering and leaving air /water vapor mixture, respectively, and hw is the enthalpy of the entering water stream. For evaporator cooler applications the last term in the energy balance is negligible (Section 4.4). The evaporative cooling process is then essentially a constant enthalpy process for the air stream. Evaporative cooling does not reduce the enthalpy of the air stream and thus would not reduce the load on a cooing coil if the unit were followed by a conventional air conditioner. Evaporative coolers are often used as the only source of cooling in very dry climates such as the Southwest. The air stream entering the space is then cooler and more comfortable and the outlet humidity is not so high that the air feels damp. Because enthalpy and wet bulb lines are essentially parallel on a psychrometric chart, it is also accurate to think of the process as occurring along a constant wet bulb line. An effectiveness parameter is useful in characterizing the performance of an evaporative cooler. It is convenient to define a temperature effectiveness in terms of the approach of the outlet temperature to the wet bulb. T T (4.3) in out Tin Twb where Twb is the wet-bulb temperature of the inlet air stream. The effectiveness depends on the transfer coefficients, the surface area, and air flow rate (the Ntu) in the same manner as for sensible heat exchangers and cooling coils. Typical values of the effectiveness range between 60 to 80 %. Evaporative coolers are discussed in Section 5.7. Evaporative coolers provide cooling at the expense of humidification of the air stream, but are limited by the wet-bulb temperature of the air. It is possible to provide another stage of cooling using an indirect evaporative cooler. In this device, an air stream is first cooled in an evaporative cooler and then used as the cold flow in a heat exchanger to cool another air stream. The cooled air stream can then be evaporatively cooled to provide a temperature lower than that with a single stage evaporative cooler. The arrangement is shown schematically and on psychrometric coordinates in Figure 4.2. 4.2 Water Inlet streams T1 Water T3 Ta Supply Tsupply T2 Figure 4.2 Schematic operation of an indirect evaporator cooler. The desired output is the cooled outlet air stream, which is at the humidity ratio of the incoming ambient but at a lower temperature. The performance of the system can be determined in terms of the effectivenesses of the evaporative cooler and heat exchanger, ec and hx, respectively. The cold outlet temperature of the evaporative cooler, Tc, is evaluated in terms of the effectiveness and wet bulb temperature using equation 4.3. The outlet temperature of the sensibly cooled stream, Tout, is then given in terms of the heat exchanger effectiveness and the temperature leaving the evaporative cooler, Tc. For equal capacitance rates for the heat exchanger, the outlet temperature can be expressed in terms of the inlet temperature, the wet bulb temperature, and the effectivenesses of evaporative cooler and heat exchanger as. (4.4) Tout Tin hx ec Tin Twb Commercially manufactured indirect evaporative coolers usually combine the evaporation and heat transfer effects into one unit. Water is brought in and flows down along sheets of plastic or metal that also form passages between which the air flows. This allows the heat transfer and evaporation to occur simultaneously. Example 4.2 illustrates the cooling that can be obtained through an indirect evaporative cooler. "Example 4.1 An indirect evaporative cooling system combines the evaporative cooler of example 4.1 (80 % effectiveness) with a heat exchanger of 70 % effectiveness. The air flow rate through both units is 2500 cfm and the ambient is 90 F and 5 % relative humidity. Determine the outlet state and the cooling potential." "Problem specifications" T_a = 90 “F” RH_a = 0.05 p_atm = 14.7 “psia” V_dot = 2500 “cfm” eff_EC = 0.8 eff_HX = 0.7 “Ambient temperature” “Ambient RH” “Ambient pressure” “Volume flow rate” “Evaporative cooler eff.” “Heat exchanger eff” "Determine the properties of the incoming air stream and the mass flow rate of the air streams" T_wb_a = WetBulb(AirH2O,t=T_a, p=p_atm, r=RH_a) “F” “Ambient wet-bulb” w_a = HumRat(AirH2O,t=T_a, p=p_atm, r=RH_a) “lbm/lbm” “Ambient humidity” rho_a = density(AirH2O,t=T_a, p=p_atm, r=RH_a) “lbm/ft3” “Ambient density” cp_a = specheat(AirH2O,t=T_a, p=p_atm, r=RH_a) “Btu/lbm-F” “Air specific heat” 4.3 m_dot = rho_a*V_dot*Convert(1/min,1/hr) “lbm/hr” “Mass flow rate” "For the first evaporative cooler, determine the outlet temperature. The outlet temperature will be the sink for cooling the second air stream from the ambient." eff_EC = (T_a -T_1)/(T_a - T_wb_a) “Evaporative cooler eff” "The humidity ratio of the coolant stream is" w_2 = humrat(AirH2O,T=T_1, p=p_atm, B=T_wb_a) “lbm/lbm” “Outlet humidity” "For the heat exchanger, determine the outlet temperatures of the supply stream (T_3) and the stream that was used to cool the exhaust stream (T_2). The capacitance rates of the supply and coolant stream are equal. The effectiveness based on the supply stream is" eff_HX = (T_a -T_3)/(T_a - T_1) “Heat exchanger eff” "The outlet humidity of the supply stream (w_3) equals that of the ambient since the supply stream is only cooled sensibly." w_3 =w_a “lbm/lbm” “Humidity ratio” "The outlet temperature of the coolant stream is determined. Because the supply and coolant stream capacitance ratios are equal the energy balance reduces to" (T_2- T_1) = (T_a - T_3) “F” “Energy balance” w_2 = w_1 “lbm/lbm” “Humidity ratio” "The supply stream is then evaporatively cooled in an evaporative cooler. The effectiveness is the same as for the first evaporative cooler. The wet-bulb temperature that of the supply stream at state 3." T_wb_3 = wetbulb(AirH2O,T=T_3, p=p_atm, w=w_3) “F” “Supply wet-bulb” eff_EC = (T_3 -T_supply)/(T_3 - T_wb_3) “Evaporative cooler eff” "The humidity of the supply state is" w_supply = humrat(AirH2O,T=T_supply, p=p_atm, B=T_wb_3) “lbm/lbm” “Supply humidity” RH_supply = RelHum(AirH2O,T=T_supply,P=p_atm,w=w_supply) “Supply RH” "The sensible cooling that could be achieved for a building with a temperature of 78 F with the supply flow is" T_z = 78 “F” “Zone temperature” Cool = m_dot*cp_a*(T_z - T_supply) “Btu/hr” “Cooling potential” Tons = Cool*convert(Btu/hr,tons) “tons” “Cooling potential” Results and Discussion The ambient has a wet bulb temperature of 55.4 F, and is cooled to 62.3 F in the first evaporative cooler. The air stream with this temperature is then used to sensibly cool the supply stream from the ambient from 90 F to 70.6 F. The wet-bulb temperature of this stream is reduced to 47.0 F. In the second evaporative cooler the supply stream is brought to a condition of 51.8 F and 70 % RH. The supply stream at this temperature could provide a cooling potential of 68,380 Btu/hr, or 5.7 tons. This is 70 % more cooling potential than that provided by the single stage evaporative cooler. If the cooling potential is greater than desired, the effectiveness of the second evaporative cooler can be decreased by reducing the water flow rate. This would increase the supply temperature and reduce the relative humidity, and possible make for more comfortable conditions. Examples 4.1 and 4.2 illustrate how evaporative coolers can be employed to provide air conditioning. The cooling cost is "free" in that only fan power is required. Fan power for an 4.4 evaporative cooler is generally small relative to the cooling benefit. Indirect evaporative coolers have higher fan power requirements due to the pressure drop in the heat exchanger, and two stages of evaporative cooling are the largest number of stages that is economically feasible. 4.3 Spray Dehumidifiers Spray dehumidifiers are occasionally used to both cool and dehumidify air. A water flow is cooled by a chiller and then introduced into the spray dehumidifier. The operation is similar to that for a cooling tower, with the difference that the entering water stream is cold. The spray dehumidifier differs from the evaporative cooler in that the water flow rate is high and only a small amount of water evaporates. Inside the dehumidifier, the air becomes saturated and cooled. A schematic of a spray dehumidifier and the psychrometric representation of the air and water processes are shown in Figure 4.3. Water Tw, in Inlet Air Tin Outlet Air Tout Tw, out Figure 4.3 Schematic operation of a spray dehumidifier An effectiveness is defined in terms of enthalpies. The coldest and driest possible exit state for the air stream is to leave in equilibrium with the water inlet state, which corresponds to saturation at the temperature of the incoming water. The effectiveness is then defined as the actual enthalpy change from inlet to outlet divided by the enthalpy difference between the air inlet and saturated air at the water inlet temperature. h in h out (4.5) h in h w,sat,in For the conditions illustrated in Figure 4.3, the air inlet enthalpy is greater than that of saturated air at the water inlet temperature. Energy will then be transferred from the air to the water stream, the air will be cooled, and the humidity level will drop. The water condensed out of the air will leave with the water flow. In this manner a cold water spray will actually dehumidify the air. Example 4.3 illustrates the performance of a spray dehumidifier. 4.5 "Example 4.2 An air flow of 5000 L/s and at 30 C and 75 % RH enters a spray dehumidifier with an effectiveness of 0.8 and an inlet water temperature of 10 C. Determine the outlet state of the air and the water flow rate required for a 2 C temperature rise of the water through the spray dehumidifier." "Problem Specifications" p_atm = 101.3 "kPa" T_in= 30 "C" RH_in = 0.75 V_dot = 5000 "L/s" eff = 0.8 T_w_in= 10 "C" T_w_out = 12 "C" "Atmospheric pressure" "Air inlet temperature" "Relative humidity" "Air volume flow rate" "Dehum. effectiveness" "Water inlet temp." "Water outlet temp" "Properties of the air flow at inlet conditions" m_dot_a = V_dot*rho_in*convert(L,m3) "kg/s" "Water mass flow rate" rho_in = density(AirH2O, T = T_in, p=p_atm, R=RH_in) "kg/m3""Air density" w_in = HumRat(AirH2O, T = T_in, p=p_atm, R=RH_in) "kg/kg""Humidity ratio" h_in = Enthalpy(AirH2O, T = T_in, p=p_atm, R=RH_in) "kJ/kg""Air enthalpy" "Properties of the air flow at outlet conditions" RH_out = 1 "Relative humidity" w_out = HumRat(AirH2O, T = T_out , p=p_atm, R=RH_out ) "kg/kg""Humidity ratio" h_out = Enthalpy(AirH2O, T = T_out , p=p_atm, R=RH_out ) "kJ/kg""Air enthalpy" "Properties of the water flow" h_w_in= Enthalpy(Water,T=T_w_in,P=p_atm) "kJ/kg" h_w_out = Enthalpy(Water,T=T_w_out,P=p_atm) "kJ/kg" "Water enthalpy" "Water enthalpy" "Spray dehumidifier effectiveness, equation 4.5" eff = (h_in- h_out)/(h_in- h_w_sat_in) "Defn of effectiveness" h_w_sat_in= Enthalpy(AirH2O, T = T_w_in, p=p_atm, R=1) "kJ/kg""Sat air enth. at T_w_in" "Mass balance on the dehumidifier to determine the rate at which moisture is condensed out of the air stream" m_dot_cond = m_dot_a*(w_in- w_out) "kg/s" "Condensation flow rate" "Energy balance on the dehumidifier to determine the water flow rate that will produce a 2 C rise in the water temperature. The energy of the condensed water is included in the energy balance and its temperature is taken as that of the inlet water." m_dot_a*(h_in- h_out) + m_dot_w*h_w_in- m_dot_w*h_w_out -m_dot_cond*h_w_out = 0 "kW" Results and Discussion: Solving the set of equations yields the amount of moisture condensed out of the air as 0.057 kg/s, an inlet water flow rate of 27.94 kg/s, and an outlet of 28.00 kg/s. The condensate flow rate is relatively small compared to the total water flow rate, but there still is some water addition to the flow stream. Ultimately this condensate flow will need to be drained off. The air temperature is dropped from 30 C to 14.2 C. Even though the air leaves at saturated conditions, the humidity ratio is reduced from 0.0202 kgw/kga to 0.0101 kgw/kga. The air is cooled enough and dried enough to be used for space conditioning. A modification of the spray cooling process is to use a cold liquid desiccant solution instead of a chilled water flow. The water in the air stream is condensed and goes into the desiccant solution. Because of its affinity for water, at the same temperature the liquid desiccant allows the 4.6 air to be dehumidified more than with the chilled water. The desiccant will eventually become saturated with water and must then be regenerated by heating to evaporate the absorbed water. A spray cooler uses a chilled water or liquid desiccant flow to provide a cold and dehumidified air stream. The end result is the same as if a conventional cooling coil were used. The advantage of the spray cooler is that the water does not need to be as cold as with a coil because the air does not need to be cooled to the dew point. This reduces the chiller power. However, the water flow rate is generally significantly larger than that through a chilled water coil, and the cooling power requirement might be more. The water flow removes particles from the air and acts as a filter, which is usually beneficial. Eliminators need to be placed downstream of the unit to prevent carry-over of the water, and the water quality needs to be maintained for health and safety reasons. Because the use of cooling coils for cooling buildings is well established, spray dehumidifiers are not widely used. 4.4 Evaporative Condensers An evaporative condenser is a heat exchanger that is continuously cooled by a flow of evaporating water at the same time that the refrigerant is condensed. Condensation of the refrigerant takes place inside tubes as in a normal condenser. Water sprayed over the tubes flows downward and evaporates into an air flow from the atmosphere that is induced by a fan and flows upward. A schematic of an evaporative condenser is shown in Figure 4.4. Refrigerant Water flow Air flow Makeup water Figure 4.4 Schematic of an evaporative condenser Because the air is cooled by the evaporation of water the air stream can approach the wet bulb temperature, providing a lower temperature for the heat rejection. Most of the energy transfer goes into evaporating the water flow and so the temperature of the air stream does not increase much. As a result, the refrigerant in an evaporative condenser is condensed at a lower temperature than in an air-cooled condenser, reducing the chiller power. An evaporative condenser is also a more compact device than a condenser-cooling tower combination that could provide the same benefits. The performance of the evaporative condenser can be represented in a manner similar to that for a cooling coil. The heat and mass transfer processes in an evaporative condenser are the same as in the cooling coil, with the difference that the heat and moisture flows are into the air 4.7 instead of out of the air. The detailed analysis of Section 15.3 and the analogy approach of Section 15.4 therefore apply to the evaporative condenser. An energy balance on a section of the evaporative condenser, similar to that of Figure 4.5, yields an equation similar to the energy balance relation for the coil. d hA d hr (4.6) mA mr d AA d Ar where m A and m r are the flow rates of ambient air and refrigerant, respectively, hA and hr are the enthalpies of the moist air and refrigerant, respectively, and AA and Ar are the heat transfer areas on the air and refrigerant side of the condenser, respectively. During the condensation process the refrigerant temperature is constant but the enthalpy decreases as vapor condenses. The heat transfer from the refrigerant to the air stream is related to the heat transfer conductance between the refrigerant and the condenser surface and the heat and mass transfer conductances between the water film and the air. The development parallels that of the cooling coil, and the energy change of the air stream is given by an equation similar to that for a cooling coil: d hA U* (4.7) h A h r,sat d AA mA where hr, sat is the enthalpy of saturated air at the refrigerant temperature and U* is the overall energy transfer conductance. To illustrate the similarity to the cooling coil, it is assumed that the amount of superheat and subcooling is small relative to the condensation. The effect of superheat can be included following the approach shown in Section 4.3. The similarity of the evaporative condenser to the cooling coil leads to a definition of effectiveness similar to that for the cooling coil: h A,out h A,in (4.8) h r,sat h A,in The heat transfer can then be computed as the product of effectiveness, air mass flow rate, and the enthalpy difference times the enthalpy difference between saturated air at the refrigerant temperature and that at the inlet: Q mA h A,sat h A,in (4.9) As with the cooling coil, the effectiveness is a function of the number of transfer units and capacitance rate ratio. The number of transfer units for a wet surface depends upon the overall conductance and is given by U* A A Ntu * (4.10) mA Because the refrigerant temperature is essentially constant the capacitance rate ratio is zero. Example 4.4 illustrates the determination of heat flow and refrigerant temperature for an evaporative condenser. "Example 4.3 A refrigeration system transfers 120,000 Btu/hr to the ambient using an evaporative condenser with an effectiveness of 0.75. The air flow is 10,000 cfm and the air enters at 80 F and 40 % RH. 4.8 Determine the temperature of the condensing refrigerant. Compare the refrigerant temperature for the evaporative condenser to that for an air-cooled condenser with the same air flow rate and effectiveness." “The EES equations are entered sequentially and the solution can be obtained directly.” "Problem Specifications" Q_dot = 120000 “Btu/hr” CFM= 10000 “cfm” T_a = 80 “F” RH_a= 0.4 p_atm = 14.7 “psia” “Heat flow rate” “Air Volume flow rate” “Air temperature” “Relative humidity” “Atmospheric pressure” "Air properties and mass flow rate" h_a_i = Enthalpy(AirH2O, T=T_a, P=p_atm, R=RH_a) “Btu/lbm” rho_a = density(AirH2O, T=T_a, P=p_atm,R=RH_a) “lbm/ft3” cp_a = SpecHeat(AirH2O, T=T_a, P=p_atm, R=RH_a) “Btu/lbm-F” T_wb = WetBulb(AirH2O, T=T_a, P=p_atm, R=RH_a) “F” m_dot_a = CFM*rho_a*convert(1/min,1/hr) “lbm/hr” “Air enthalpy” “Air density” “Specific heat” “Wet-bulb temperature” “Air mass flow rate” "Evaporative condenser performance. The heat flow rate is the condenser rejection rate. The condenser effectiveness is given by equation 4.9. This yields the enthalpy of saturated air at the refrigerant temperature, which in turn yields the refrigerant temperature." eff = 0.75 “Effectiveness” Q_dot = eff*m_dot_a*(h_r_sat - h_a_i) “Btu/hr” “Heat transfer rate” h_r_sat = Enthalpy(AirH2O, T=T_r_EC, P=p_atm, R=1) “Btu/lbm” “Sat air enthalpy” "Sensible heat exchanger performance. With the same effectiveness this yields the refrigerant temperature for the dry exchanger." Q_dot = eff*m_dot_a*cp_a*(T_r_HX - T_a) “Btu/hr” “Heat transfer rate” Results and Discussion For an evaporative condenser with an effectiveness of 0.75 transferring 120,000 Btu/hr to air at 80 F and 40 % RH, the enthalpy of saturated air at the refrigerant temperature must be 32.4 Btu/lbm. This corresponds to a temperature of 68.1 F, which is also then the temperature at which the refrigerant condenses. The thermal resistances between the refrigerant and air stream are assumed negligible. The refrigerant condensing temperature is lower than the air temperature due to the evaporation of the water from the coil surfaces into the air stream. It is higher, though, than the wet bulb temperature of 63.5 F, which is the lowest temperature that could be achieved with an evaporative cooler. For an air-cooled condenser, the refrigerant temperature would be determined from the expression for heat transfer for a sensible heat exchanger (Section 13.4). The refrigerant temperature is 95 F. The evaporative condenser reduces the condensing temperature of the refrigerant significantly over that for an air-cooled condenser. For the air-cooled temperature, the refrigerant condenses 15 F above the dry bulb air temperature, whereas with the evaporative condenser the condensing temperature is 12 F lower than the air temperature. The lower temperature would significantly increase the performance of the refrigerant system. Evaporative heat transfer is more effective than "dry" heat transfer. 4.9 4.5 Enthalpy Exchangers Enthalpy exchangers transfer both thermal energy and moisture between two air streams. Because both the temperature and humidity of the two streams change, these devices are termed enthalpy exchangers. Such units are commonly used for energy recovery in ventilation systems. For example, in winter time in Northern climates the incoming ventilation flow from the outdoors needs to be heated before it enters the space. Under very cold ambient conditions it is also common to add humidity to the air stream, usually after the air has been heated. Enthalpy exchangers transfer heat and moisture from the relatively warm and humid exhaust air to the incoming ventilation air, which increases both the temperature and the moisture levels and reduces the heating demand in winter. In a similar fashion, the enthalpy exchanger would cool down and dehumidify the ventilation air in summer time by transferring heat and moisture entering with the ventilation stream to the exhaust stream, which would reduce the load on the air conditioner. To successfully employ an enthalpy exchanger, the building must be “tight” to prevent infiltration and exfiltration. Many commercial buildings have installed enthalpy exchangers, and they are becoming more common in well-constructed residential buildings. There are two general classes of enthalpy exchangers, indirect and direct. Indirect enthalpy exchangers are desiccant wheels that rotate relatively fast. As discussed in relation to Figure 4.9, the state of the air that leaves the wheel before the fast wave exits is at the entering state of the other air stream. Thus, if the desiccant wheel is turned fast enough so that the first wave does not exit the bed, the state of the air exiting the wheel on the ventilation side will be at the temperature and humidity level of the exhaust state. The incoming ventilation air would enter the space at the same conditions as the exhaust air and would be fresh air from the ambient. Indirect enthalpy exchangers are constructed similar to desiccant dehumidifiers. One difference is that since the air is not dried to a very low humidity level the amount of desiccant can be much less than for a dehumidifier. Enthalpy exchangers are commonly made from aluminum sheets coated with a polymeric desiccant, and then wound spirally to form a matrix with triangular air passages. A section of a rotary enthalpy exchanger is shown schematically in Figure 4.13a. Aluminum sheet Desiccant-coated foil sheets Exhaust air stream Ventilation air stream Desiccant-coated partition a) Indirect enthalpy exchanger b) Direct enthalpy exchanger Figure 4.5a. Schematic of a rotary enthalpy exchanger surface. 4.5b. Schematic of a direct transfer enthalpy exchanger 4.10 Direct transfer enthalpy exchangers, shown in Figure 4.13b, are constructed similarly to indirect transfer heat exchangers, but the partition that separates the two streams allows both heat and moisture to be transferred. The separating surface is porous to water vapor and often treated with a desiccant. Moisture is adsorbed on the high humidity side, diffuses through the surface to the low humidity side, and then desorbs into the low humidity air stream. The pores allow moisture to transfer from one side to another but not air molecules. The processes that the air stream undergoes are the same for both direct and indirect enthalpy exchangers. For an exchanger with the same flow rates and transfer coefficients for both flows, the outlet states lie on a line connecting the two inlet states as shown on psychrometric coordinates in Figure 4.14 for an air-conditioning situation in which the ambient is hotter and more humid than the zone.. In an ideal exchanger, the outlet state of each stream equals the inlet of the other. In actual exchangers the heat and mass transfer coefficients are finite and less moisture and heat are transferred, producing a difference between the outlet and inlet states. Exhaust stream inlet State 3 Ventilation inlet State 1 Ventilation stream inlet State 1 Ventilation stream outlet State 2 4 2 Exhaust inlet State 3 Exhaust stream outlet State 4 Figure 4.6 Processes for an enthalpy exchanger For rotary wheels, the Lewis number is close to unity, and the convective heat and mass transfer coefficients are then directly related (Section 5.4). The process is then as shown in Figure 4.14. In a direct transfer device, the transfer coefficients are also equal, but the separating surface offers more resistance to mass transfer than to heat transfer. Thus the process lines are not along the line connecting the two inlets, but follow paths as shown in Figure 4.15. As the mass transfer resistance becomes very large, there is no moisture transfer and the device becomes a sensible heat exchanger only. 4.11 Mass transfer resistance of separating surface Infinite Ventilation inlet State 1 Large Zero Exhaust inlet State 3 Figure 4.7 Effect of mass transfer resistance on enthalpy exchanger processes The performance of an enthalpy exchanger is characterized by an enthalpy effectiveness, which is defined as the total enthalpy change of one of the streams relative to the maximum possible total enthalpy change. For a balanced exchanger in which the mass flow rates of the ventilation and exhaust streams are equal, the effectiveness is an enthalpy ratio only. Because the desired state is that of the ventilation flow into the building, the effectiveness is based on the enthalpy difference of the ventilation flow rate. h h h 1 2 (4.11) h1 h 3 When the Lewis number is unity the outlet states lie on a line connecting the inlet states and only the enthalpy effectiveness relation is needed to characterize the performance. However, when there is an added mass transfer resistance in the matrix another effectiveness is needed. It is conventional to define a sensible effectiveness to reflect the thermal energy exchange. The thermal effectiveness is defined as T T T 1 2 (4.12) T1 T3 The enthalpy effectiveness is always less than, or at best equal to, the sensible effectiveness. A mass transfer effectiveness that relates the humidity ratio change to the maximum possible change is also defined: w w2 (4.13) m 1 w1 w 3 For commercially available exchangers, the enthalpy and thermal effectiveness values are typically in the range of 0.50 to 0.75. 4.12 The enthalpy exchanger provides significant reductions in moisture as well as temperature, and is preferable to a sensible heat exchanger for energy recovery during the air conditioning season. The enthalpy recovery exchanger performance, in terms of reducing the load on the compressor, is three to four times that of a sensible heat exchanger. In addition, the reduction in design load can result in a significantly reduced installed capacity of the air conditioner, which produces additional savings (Steich et al., 1995). In the heating season the advantages of an enthalpy exchanger over a sensible exchanger are not as significant. The humidity levels in winter, both inside buildings and outdoors, are low and, relative to summer, there is not much to be gained by transferring moisture. In contrast the temperature differences between the building zones and the ambient are much larger than in summertime, and there can be significant savings due to heat transfer. The reduction in heating energy through the use of an enthalpy exchanger is only 10 to 20 % greater than that obtained using a sensible heat exchanger. In wintertime condensation or freezing may occur inside either an enthalpy or sensible heat exchanger. For an enthalpy exchanger, when the ambient temperature is very low the line connecting the ambient and building zone states may intersect the saturation line, as shown schematically in Figure 4.4. This means that at some point in the exchanger the exhaust stream is cooled below the local dew point, causing the moisture to condense. If the dew point is below freezing, ice will form. Although enthalpy exchangers can accommodate some amount of condensation and freezing, it is necessary to prevent an excessive amount of moisture from accumulating by lowering the effectiveness. In a rotary unit, the effectiveness is reduced by slowing the rotational speed. Point of condensation for a sensible heat exchanger Point of condensation for an enthalpy exchanger Zone state (exhaust inlet) Ambient state (ventilation inlet) Figure 4.8 Condensation in an enthalpy exchanger during wintertime operation The problem of condensation and freezing is accentuated in a sensible heat exchanger, as also shown in Figure 4.16, since the zone air is cooled at a constant humidity ratio and has a 4.13 higher dew point temperature. This further lowers the energy savings of the sensible heat recovery exchanger relative to the enthalpy exchanger, especially in very cold climates. Example 4.6 illustrates the calculation of the performance advantage of an enthalpy exchanger during the air-conditioning season. "Example 4.4 In a commercial building, 5000 cfm of outdoor air at 95 F dry bulb and 75 F wet bulb are brought into the space. The zone conditions are 75 F and 40 % RH. An exchanger is to be employed to precondition the outdoor air using exhaust air before it enters the cooling coil. The exchanger is a direct transfer type as shown in Figure 4.13b with passages one-eighth inch high and triangular in shape. The effectivenesses for temperature and mass transfer are 0.75 and 0.65, respectively. The exchanger is 4 ft long in the flow direction and 2.5 ft high. The same geometry can be used for a heat exchanger that only transfers heat or one that transfers both heat and moisture. Determine the ventilation load for a conventional system without an exchanger, a system using a heat recovery exchanger, and one using an enthalpy exchanger." "Problem specifications" p_atm = 14.7 "psia" V_dot = 5000 "cfm" T_a = 95 "F" Twb_a= 75 "F" Eff_T = 0.75 Eff_m = 0.65 "Atmospheric pressure" "Ventilation flow rate" "Ambient temperature" "Ambient wet-bulb" “Temperature eff.” “Humidity effectiveness” "Determine the properties of the ambient air and the mass flow rate of the ventilation air." h_a = Enthalpy(AirH2O,T=T_a,P=p_atm,B=Twb_a) "Btu/lbm" "Ambient enthalpy" w_a = HumRat(AirH2O,T=T_a,P=p_atm,B=Twb_a) "lbm/lbm" "Ambient humidity ratio" rho_a = density(AirH2O,T=T_a,P=p_atm,B=Twb_a) "lbm/ft3" "Ambient density" m_dot = V_dot*rho_a*convert(1/min,1/hr) "lbm/hr" "Mass flow rate" "Determine the zone air properties. " T_z = 75 "F" RH_z = 0.40 h_z = Enthalpy(AirH2O,T=T_z,P=p_atm,R=RH_z) "Btu/lbm" w_z = HumRat(AirH2O,T=T_z,P=p_atm,R=RH_z) "lbm/lbm" "Zone temperature" "Zone relative humidity" "Zone enthalpy" "Zone humidity ratio" Eff_T = (T_a - T_o)/(T_a - T_z) "Temperature eff" "For a heat recovery exchanger, the outlet state is at the temperature T_o and the inlet humidity ratio w_a" h_o_HX = Enthalpy(AirH2O,T=T_o,P=p_atm,w=w_a) "Btu/lbm" "Outlet enthalpy for HT" Eff_m = (w_a - w_o)/(w_a - w_z) "MT effectiveness" "For an energy recovery exchanger, the outlet enthalpy is at the temperature T_o and the humidity ratio w_o" h_o = Enthalpy(AirH2O,T=T_o,P=p_atm,w=w_o) "Outlet enthalpy for MT" "The enthalpy effectiveness is based on the outlet enthalpy of the energy recovery exchanger" Eff_h = (h_a - h_o)/(h_a - h_z) "Enthalpy effectivenss" "Determine the ventilation loads for the heat transfer and mass transfer exchangers. " AC_ht = m_dot*(h_o_HX - h_coil)*convert(Btu/hr,tons) "tons" "Vent load - HX exch." AC_mt = m_dot*(h_o - h_coil)*convert(Btu/hr,tons) "tons" "Vent load - MT exch." "For comparison, the ventilation load for a conventional system with a coil outlet temperature of 50 F is also determined." T_coil = 50 "F" "Outlet temp for coil" h_coil = Enthalpy(AirH2O,T=T_coil,P=p_atm,R=1) "Btu/lbm" "Outlet enthalpy for coil" AC_conv = m_dot*(h_a - h_coil)*convert(Btu/hr,tons) "tons" "Vent load - coil" 4.14 Results and Discussion Without any exchanger the ambient air would be cooled and dehumidified from ambient conditions to 50 F and saturated by passing through a coil. With a ventilation flow rate of 20,987 lbm/hr, the ventilation load without any exchanger is 31.5 tons. For the heat transfer only exchanger, the outlet temperature is dropped from the ambient temperature of 95 F to 80.0 F, but the humidity ratio is the same as the ambient at 0.01405 lbmw/lbma, yielding an outlet air enthalpy of 34.6 Btu/lbm. The ventilation load is 25.1 tons, which is about 80 % of that without an exchanger. With an enthalpy exchanger, both the temperature and humidity ratio are decreased. The outlet temperature is 80.0 F, which is the same as for heat transfer only. The humidity ratio is reduced from the ambient to 0.00970 lbmw/lbma, yielding an outlet air enthalpy of 29.9 Btu/lbm. This is significantly lower than that for a heat transfer only exchanger. The corresponding ventilation load is 4.8 tons, which is about 53 % of that without an exchanger. For a system that operated 4000 hours per year, the enthalpy exchanger would produce an energy cost savings of about $ 2,100 per year at electrical costs of $ 0.10/kWh. There is also a reduction in the required installed coil and air conditioner capacity of about 15 tons. At a representative incremental cost of $ 250/ton, this amounts to about $ 3,500. The savings in operating and equipment costs would probably pay for the added cost of the heat and mass exchanger in relatively short time. Enthalpy exchangers significantly reduce the cost of operating air conditioning equipment. Equally important, enthalpy exchangers allow the installed capacity of the air-conditioning equipment to be reduced. The cooling load met by the enthalpy exchanger truly reduces the load on the cooling coil, and the design of the system can take this into account. The reduction in cost of the conventional equipment is often greater than the added cost of the enthalpy exchanger. 4.6 Summary The evaporation of water into an air stream can be used to condition a building space. An evaporative cooler provides cooling of an air stream, although with a corresponding increase in humidity. This device is appropriate in locations such as the southwest where ambient humidity levels are low. Indirect evaporative coolers use evaporative cooled air as a heat rejection source, and produce cooling without humidification. These devices extend the climate range for which evaporation alone can be used for space conditioning. The cost of operation of these devices is roughly an order of magnitude less than cooling with conventional cooling units. In combination with conventional cooling systems, evaporative coolers reduce the maximum load on the system. This allows smaller capacity and lower cost cooling equipment to be installed. Evaporative condensers allow refrigeration equipment to reject heat to air at the wet bulb temperature instead of the higher dry bulb temperature as in dry condensers. Evaporative condensers thus allow the cooling equipment to operative more efficiently. The reduction in compressor power is less than the parasitic power for the extra fans and pumps of the evaporative condenser. 4.15 Enthalpy exchangers pre-condition incoming ventilation air by transferring heat and moisture to the exhaust air steam, significantly reducing the enthalpy of the incoming air. The corresponding ventilation load on the heating or cooling system is significantly reduced. The reduction in humidity level has a much larger impact on energy savings during the cooling seasons than the heating season. Enthalpy exchangers are more effective than sensible exchangers during the cooling system, while sensible heat exchangers are nearly as effective during winter and are somewhat less costly. Installing an enthalpy exchanger reduces the maximum load on the air-conditioning equipment and allows smaller equipment to be installed. 4.7 Nomenclature A h w W area specific enthalpy mass flow rate number of transfer units for heat transfer number of transfer units for mass transfer heat flow rate temperature overall unit mass transfer conductance humidity ratio moisture content effectiveness relative humidity m Ntu Ntu* Q T U* Subscripts A ambient state a air ec evaporative cooler f liquid phase g vapor phase h enthalpy hx heat exchanger in in, inlet m mass transfer out out, outlet r refrigerant sat saturation conditions T temperature w water wb wet-bulb z zone 4.8 References ASHRAE Handbook, HVAC Systems and Equipment, Chapter 19, ASHRAE, Atlanta GA, 2004 Duffie, J. A., W. A. Beckman, and J. W. Mitchell, “Solar Cooling,” in Solar Energy Technology Handbook, W.C. Dickenson (Ed.), Marcel Dekker, New York, 1980. Evaporative Cooling, Munters Corporation, Fort Meyers, FL, 1994. Hollands, K. G. T., "Analysis and Design of Evaporative Cooler Pads," Mechanical and Chemical Engineering Transactions, p 55 - 61, 1970 Indirect Evaporative Cooling, Vari-Cool, Santal Rosa, CA, 1980. Jalalzadeh-Azar, A., S. Slayzak, R. Judkoff, T. Schaffhauser, and R. DeBlasio, “Performance Assessment of a Desiccant Cooling System in a CHP Application Incorporating an IC Engine,” IJDER, 2005 Jurinak, J., J. W. Mitchell, W. A. Beckman, "Open-Cycle Desiccant Air Conditioning as an Alternative to Vapor Compression Cooling in Residential Applications," ASME Trans., 106, 252-260 (1984). 4.16 Klein, H., S.A. Klein, J. W. Mitchell, "Analysis of Regenerative Enthalpy Exchangers," International Journal of Heat Transfer, (1989). Lowenstein, A., S. Slayzak, and E. Kozubal, “A Zero Carryover Liquid-Desiccant Air Conditioner For Solar Applications,” Proceedings Of Isec2006 ASME International Solar Energy Conference July 8-13, 2006, Denver, Co Maclaine-Cross, I. L. and P. J. Banks, "Coupled Heat and Mass Transfer in RegeneratorsPredictions Using an Analogy with Heat Transfer," International Journal of Heat and Mass Transfer, Vol 15, no. 6, pg 1225 - 1242, 1972. Manley, D. L., K. L. Bowlen, and B. M. Cohen, "Evaluation of Gas-Fired Desiccant-Based Space Conditioning for Supermarkets," Trans. ASHRAE, V 91, Pt 1, 1985. Peterson, J. L., "An Effectiveness Model for Indirect Evaporative Coolers," Trans. ASHRAE, V 99, Pt 2, 1993. Steich, G., Mitchell, J.W., Klein, S.A., "Performance of Rotary Heat and Mass Exchangers" Int. J. of HVAC and Refrigerating Research, 308,17, (1995). SuperAire Design Manual, Cargocaire Corporation, Amesbury, MA. Tanaka, O., "An Analysis of Simultaneous Heat and Water Vapour Exchange through a Total Heat Exchanger of the Paper Plate Fin Type," report of Mitsubishi Corporation, 1982. 4.9 Problems Problems in English units 4.1 A supply air temperature lower than 65 F and a humidity ratio lower than 0.006 lbmw/lbma can provide satisfactory conditions in an occupied space. a. On a psychrometric chart show the region of ambient conditions for which an evaporative cooler would be suitable and the values of effectivenesses that are needed to achieve the desired supply state. b. On a psychrometric chart show the region of ambient conditions for which a single stage indirect evaporative cooler would be suitable and the values of effectivenesses that are needed to achieve the desired supply state. c. Draw some conclusions from your results. 4.2 A single stage indirect evaporative cooler consists of a 90 % effectiveness evaporative cooler and a 75 % effectiveness heat exchanger. The system is designed to be the sole cooling source for a building load of 10 tons of cooling with a SHR of 0.8 at ambient conditions of 80 F and 20 % RH. The zone set temperature is to be 75 F with the humidity within the ASHRAE comfort zone. a. Determine the air flow rate (cfm) and zone humidity level (RH and humidity ratio) at design conditions. b. For operating ambient conditions between 70 and 90 F and 20 and 40 % relative humidity, the system uses the indirect evaporative cooler to precool air that then enters the coil of a vapor compression system. Determine the energy savings of the combined system over a conventional air-conditioning system. 4.17 4.3 4.4 4.5 4.6 4.7 c. Draw some conclusions from your results. An air flow of 500 cfm and at 90 F and 65 % RH enters a spray dehumidifier with an effectiveness of 0.8. The chilled water temperature is 45 F and the flow rate is 6000 lbm/hr. a. Determine the outlet state of the air, the amount of water condensed, and the temperature rise of the water flow. b. Determine and plot on psychrometric coordinates the air outlet state as the spray dryer effectiveness is varied between 0 and 1.0. c. Draw some conclusions from your results. An evaporative condenser with an effectiveness of 0.7 operates with 30,000 cfm of air at a condition of 85/70 (dry bulb/wet bulb). a. Determine the condenser capacity (Btu/hr and tons) and the amount of water evaporated for a condensing temperature of 78 F. b. For the capacity found in part a, determine and plot the condensing temperature over the range of effectiveness of 0.2 to 0.9. c. Draw some conclusions from your results. An evaporative condenser is to be designed for an air conditioner that rejects 500,000 Btu/hr. The design conditions are 95/80 (dry bulb/wet bulb) and the design effectiveness is 0.7. The evaporative condenser is to be compared to a dry condenser with the same effectiveness. a. Determine the condensing temperatures and air flow rates for the evaporative and dry condensers at design conditions. b. At the design air flow rates, determine the condensing temperatures for the two units over an range of ambient temperature and humidity representative of operation. c. Draw some conclusions from your results. A commercial building application has an outdoor air requirement of 10,000 cfm. In summer time the average conditions are 85 F dry bulb, and 65 F wet bulb for 2000 hours per year. In winter the average conditions are 25 F and 80 % RH for 1000 hours. The zone is maintained at 75 F and 40 % RH in summer and 70 F and 20 % in winter. The air conditioner has a COP of 3.4 and electrical costs are $ 0.11/kWh, and heating costs are $ 10/106 Btu. Determine the seasonal energy savings for a. An enthalpy exchanger with a heat transfer effectiveness of 0.7 and a mass transfer effectiveness of 0.65 b. A sensible heat exchanger with an effectiveness of 0.7. c. Plot the processes for both exchangers and for both seasons on psychrometric coordinates. d. Draw some conclusions from your results. An exchanger is considered for a commercial building operation in Washington D.C. to recover exhaust heat in the air-conditioning season. The indoor conditions are 70 F and 45 % RH, the average summer ambient conditions are 85 F and 60 % RH, and the flow rate is 4000 cfm. There are 1900 hours of operation for the unit. A sensible heat exchanger 4.18 would cost $ 7000, and an enthalpy exchanger would cost $ 8000. Both would have an effectiveness of 0.7. Determine whether either exchanger is cost effective and, if so, which one is the more cost effective. The cooling system has a COP of 3 and electrical costs are $0.085/kWh. Problems in SI Units: 4.8 A supply air temperature lower than 18 C and a humidity ratio lower than 0.006 kgw/kga can provide satisfactory conditions in an occupied space. a. On a psychrometric chart show the region of ambient conditions for which an evaporative cooler would be suitable and the values of effectivenesses that are needed to achieve the desired supply state. b. On a psychrometric chart show the region of ambient conditions for which a single stage indirect evaporative cooler would be suitable and the values of effectivenesses that are needed to achieve the desired supply state. c. Draw some conclusions from your results. 4.9 A single stage indirect evaporative cooler consists of a 90 % effectiveness evaporative cooler and a 75 % effectiveness heat exchanger. The system is designed to be the sole cooling source for a building load of 40 kW of cooling with a SHR of 0.8 at ambient conditions of 27 C and 20 % RH. The zone set temperature is to be 24 C with the humidity within the ASHRAE comfort zone. a. Determine the air flow rate (L/s) and zone humidity level (RH and humidity ratio) at design conditions. b. For operating ambient conditions between 20 and 35 C and 20 and 40 % relative humidity, the system uses the indirect evaporative cooler to precool air that then enters the coil of a vapor compression system. Determine the energy savings of the combined system over a conventional air-conditioning system. c. Draw some conclusions from your results. 4.10 An air flow of 500 L/s and at 35 C and 60 % RH enters a spray dehumidifier with an effectiveness of 0.8. The chilled water temperature is 7 C and the flow rate is 1.5 kg/s. a. Determine the outlet state of the air, the amount of water condensed, and the temperature rise of the water flow. b. Determine and plot on psychrometric coordinates the air outlet state as the spray dryer effectiveness is varied between 0 and 1.0. c. Draw some conclusions from your results. 4.11 An evaporative condenser with an effectiveness of 0.7 operates with 20,000 L/s of air at a condition of 30/20 (dry bulb/wet bulb). a. Determine the condenser capacity and the amount of water evaporated for a condensing temperature of 25 C. b. For the capacity found in part a, determine and plot the condensing temperature over the range of effectiveness of 0.2 to 0.9. c. Draw some conclusions from your results. 4.19 4.12 An evaporative condenser is to be designed for an air conditioner that rejects 200 kW. The design conditions are 35/28 (dry bulb/wet bulb) and the design effectiveness is 0.7. The evaporative condenser is to be compared to a dry condenser with the same effectiveness. a. Determine the condensing temperatures and air flow rates for the evaporative and dry condensers at design conditions. b. At the design air flow rates, determine the condensing temperatures for the two units over an range of ambient temperature and humidity representative of operation. c. Draw some conclusions from your results. 4.13 A commercial building application has an outdoor air requirement of 5,000 L/s. In summer time the average conditions are 30 C dry bulb, and 20 C F wet bulb for 2000 hours per year. In winter the average conditions are -10 C and 80 % RH for 1000 hours. The zone is maintained at 24 C and 40 % RH in summer and 22 C and 20 % in winter. The air conditioner has a COP of 3.4 and electrical costs are $ 0.11/kWh, and heating costs are $ 0.035/kWh. Determine the seasonal energy savings for a. An enthalpy exchanger with a heat transfer effectiveness of 0.7 and a mass transfer effectiveness of 0.65 b. A sensible heat exchanger with an effectiveness of 0.7. c. Plot the processes for both exchangers and for both seasons on psychrometric coordinates. d. Draw some conclusions from your results. 4.14 An exchanger is considered for a commercial building operation in Washington D.C. to recover exhaust heat in the air-conditioning season. The indoor conditions are 22 C and 45 % RH, the average summer ambient conditions are 30 C and 60 % RH, and the flow rate is 2,000 L/s. There are 1900 hours of operation for the unit. A sensible heat exchanger would cost $ 7000, and an enthalpy exchanger would cost $ 8000. Both would have an effectiveness of 0.7. Determine whether either exchanger is cost effective and, if so, which one is the more cost effective. The cooling system has a COP of 3 and electrical costs are $0.085/kWh. 4.20