SHELF UNIT - GUIDE SPECIFICATIONS 2, 3, and 4 ton GENERAL Provide and install a split type air conditioning system designed specifically for use in smallcomputer or electronic equipment areas. The unit shall be capable of cooling, humidifying, dehumidifying and filtering air. Provide quantities and system configurations as shown on the project drawings. Units shall be ETL listed. CONTROLS Precise temperature regulation shall be provided by a built-in control system. All electrical components, including capacitors, contactors, relays and control transformers shall be pre-wired and contained in an electrical box. A factory installed micro-switch will disable the unit prior to condensate pan overflow should the drain become plugged with debris. CABINET and FRAME The frame shall be constructed of 14 gauge welded tubular steel and coated with a heavy corrosion inhibiting finish. The outer steel casing shall have removable panels for servicing. The panels shall be insulated with ½” inch thick, closed cell insulation for quiet and efficient operation. An integral unit filter section with a 20" x 25" x 4" pleated filter shall be provided. The filters shall be 30% efficient (based on A.S.H.R.A.E. Std. 52.1-1992). WATER COOLED SYSTEMS Provide a self-contained water cooled unit. The cabinet shall house the evaporator section, evaporator blower assembly and filter section. Evaporator coil shall be constructed with copper tubes and aluminum fins and mounted in a stainless steel drain pan. The single refrigeration circuit shall include a scroll compressor with internal protection and crankcase heater. The refrigeration circuit shall include an expansion valve with external equalizer, filter drier, sight-glass and high and low pressure safety switches. In addition, a high efficiency plate-fin condenser with head pressure activated 2-way water regulating valve shall be built into the refrigeration system and contained in the evaporator section. The blower assembly shall be a draw-through type with a centrifugal, forward curved, double width, and double inlet blower configuration engineered for quiet, reliable operation. The belt driven variable pitch drive shall provide adjustable air flow capability to match the requirements of the controlled space. The draw-through design shall insure even air distribution across the coil, low internal cabinet losses, and static sealing of the filter section. The evaporator motor shall have internal overload protection and shall be mounted on an adjustable slide base. Note: A fluid cooler or water cooling source is required. OPTIONS MINI DATA ALARM PROCESSOR-II™ Provide a Mini Data Alarm Processor-II. The microprocessor shall be a wall mounted and, one row, 16-character control that will monitor the controlled environment’s humidity, air flow and cleanliness, but also provides alarm history and an automatic self-test of the microprocessor on system start-up. Multiple messages shall be displayed by automatically scrolling from each message to the next. All messages shall be presented in a clear vernacular format on the liquid crystal display (LCD). Multiple alarms shall be displayed sequentially in order of occurrence. OPERATION - A slide switch shall allow unit on/off operation. Push buttons shall allow menu selection for programming, operational information, diagnostics and historical data. The two-level password feature shall prevent unauthorized access. Menu programmed information for basic system operation and alarm parameters shall be non-volatile. PROGRAMMABLE FUNCTIONS - The user friendly MENU and SELECT push buttons shall permit step-by-step programming of the following selections: • Temperature setpoint: 60-80° F/18.3-29.4° C • Temperature deadband: ± 1-5° F/C • Temperature alarm points • Calibrate temperature sensor • Unit start time delay • Password - 1st level • Audio alarm level • Firestat trip temperature • Humidity setpoint: 30-70% RH • Humidity deadband: ± 1-15% RH • Humidity alarm points • Calibrate humidity sensor • Interstage time delay • Password 2nd - level • Restart mode • Local alarm DISPLAYED CONDITIONS, DATA, and FUNCTIONS - The Mini Data Alarm Processor-II shall display and monitor the following conditions, data, and functions: • Temperature setpoints • Current temperature • Cooling • Humidification • Date and time • Humidity setpoint • Current humidity • Reheat • Dehumidification • Occupied/unoccupied period ALARMS - Alarm conditions shall be displayed and monitored on the microprocessor LCD along with an audible alarm. The alarm silence switch shall quiet the audible alarm but the display shall continue to indicate the alarm condition until it is corrected. The following alarms shall be capable displaying: • High temperature warning • Low temperature warning • No air flow • Power failure restart • Low voltage warning • Humidity sensor error • Change filter* • No water flow* • Smoke alarm* • Local alarm 1* • High pressure compressor 1* • High humidity warning • Low humidity warning • Firestat tripped • Compressor short cycle • Temperature sensor error • Condensate pan high level • Humidifier failure* • Fan overload* • Low pressure 1* • Local alarm 2* HISTORICAL DATA - Temperature and humidity, with the minimum and maximum readings since the last power on shall be recalled and displayed. Alarm history shall be maintained in sequential order (last 5 alarms). DIAGNOSTICS - Automatic and manual diagnostics shall simplify troubleshooting. In addition, the Mini Data Alarm Processor-II shall have an inclusive seven-day programming format for unoccupied or low demand periods. This secondary schedule shall minimize equipment runtimes, reducing energy consumption and provide user cost savings. The following selections shall be adjusted to match the requirements needed for the unoccupied or low demand periods: • Cooling Setpoint for Secondary Schedule Adjustment range: 1-30° F above the "occupied" temperature setpoint • Reheat Setpoint for Secondary Schedule Adjustment range: 1-30° F below the "occupied" temperature setpoint • Dehumidification Setpoint for Secondary Schedule Adjustment range: 1-30% RH above the "occupied" humidity setpoint • Humidification Setpoint for Secondary Schedule Adjustment range: 1-30% RH below the "occupied" humidity setpoint • Day Schedule Scheduling for each day of the week or any combination of days • "Unoccupied" Adjusted Setpoint Operation Adjusts to temperature and humidity setpoints to secondary schedule • "Unoccupied" ON/OFF Operation During "unoccupied" schedule Cooling: off Heating: off Humidification: off Dehumidification: off Fan: off • Override Request (Overrides Secondary Schedule) Adjustment range: 1-12 hours *Alarm displays require additional components or sensors and programmable selections. Some alarm messages are selected in three optional alarm menus. STEAM GENERATOR HUMIDIFIER - Provide an electric steam generator humidifier with disposable cylinder and self-regulating auto flush. Units with steam generator humidifier shall require the Mini Data Alarm Processor-II. DISCONNECT SWITCH - Provide a unit mounted disconnect switch with 1/4 turn latch. The switch must be in the "OFF" position to remove panel and access electrical compartment. EXTENDED COMPRESSOR WARRANTY - Provide an additional two-year or four-year extended compressor warranty.