MFPE 2014 CHAPTER 4 MAINTENANCE Scope 4.1. This chapter specifies Defence requirements for the maintenance of fire safety measures in all Defence owned and occupied buildings. Aim 4.2. The aim of this chapter is to detail the minimum maintenance requirements of building active and passive fire safety measures. References 4.3. Reference is necessary to the following documents: a. National Construction Code Volume One – Building Code of Australia (BCA); b. National Fire Protection Association (NFPA) 11—Standard for low-,medium-, and high-expansion Foam; c. Relevant State / Territory building legislation related to building fire safety system maintenance; d. AS 1851-2012—Routine service of fire protection systems and equipment; e. AS 2293.2—Maintenance and testing of emergency evacuation lighting in buildings; f. AS 2304—Water storage tanks for fire protection systems; and g. Guidelines for testing fixed aqueous film forming fire suppression systems – refer to fire protection section on http://www.defence.gov.au/estatemanagement/policy/technical/main.htm. h. Policy for Defence emergency management and incident response located at http://intranet.defence.gov.au/emergencymanagement. Requirements 4.4. A building’s active and passive fire safety measures must perform to a standard not less than they were originally required to achieve. 4.5. Maintenance must be undertaken in accordance with the applicable legislation, standards and codes in paragraph 4.3. 4.6. 2012. Defence buildings are to be maintained in accordance with the requirements of AS 1851Notes. (1) The 2012 edition of AS 1851 may be applied to fire systems and equipment regardless of building age. Adopting the 2012 edition will meet relevant State and Territory maintenance legislation which may refer to previous editions without substantial change to existing maintenance regimes. (2) The full adoption of the new edition is considered important for Defence to meet its duty of care obligations. 4.7. Fire safety measures within an approved Alternative Solution or Dispensation must be maintained in accordance with the requirements specified therein. 4.8. The maintenance of the fire safety measures in any Defence leased building or part of a building not on Crown land must comply with the applicable State or Territory legislation. MFPE 2014 4-2 4.9. Fire safety measures installed to comply with the MFPE in any Defence occupied building or part must be maintained in accordance with the applicable design and maintenance standard. For example, specialist foam Installations in aircraft Hangars shall be maintained/tested in accordance with the standards referenced in AS 2304 and NFPA 11. 4.10. Maintenance of foam fire suppression systems shall be in accordance with NFPA 11— Standard for low-,medium-, and high-expansion Foam. Further Defence requirements related to foam suppression systems are detailed in the ‘Guidelines for Testing Fixed Aqueous Film Forming Fire Protection System’ – located in the fire protection section located at http://www.defence.gov.au/estatemanagement/policy/technical/main.htm. 4.11. Maintenance of emergency evacuation lighting in buildings shall be in accordance with AS 2293.2. Yearly condition report 4.12. For the purpose of compliance with clause 1.17.2 of AS 1851-2012 – which requires a yearly condition report – the Regional Director is the responsible entity. The Regional Director or their representative shall also ensure that the yearly condition report is attached to the relevant structure in DEMS. Exit doors and doors in paths of travel to exits 4.13. All required exits and doors in the path of travel to a required exit shall be inspected at least annually to ensure that the door opens and closes freely. This includes, but is not limited to a functional test of any electronic or mechanical hardware and the operation of any door latching hardware. Any deficiencies shall be rectified. Solid core doors in Living-in-Accommodation 4.14. All solid core doors bounding public corridors or other units – required by the BCA or other building legislation – shall be inspected at least annually to ensure that the door opens and closes freely. This includes, but is not limited to a functional test of the mechanical hardware, self-closers and the operation of any door latching hardware. The doors are to come to the fully closed and latched position after each manual opening. Any deficiencies shall be rectified. Emergency planning 4.15. For compliance with AS 1851-2012 Section 14, Emergency Planning in Facilities – refer to Defence Emergency Management and Incident Response requirements located at http://intranet.defence.gov.au/emergencymanagement.