North Carolina State University Centennial Campus Communications/Internet Infrastructure Guidelines May 27, 1999 Version 1.0 Revised October 12, 2000 Version 1.1 Revised January 22, 2002 Version 1.2 Revised April 1, 2006 Version 1.3 Revised October 27, 2014 Version 1.4 Table of Contents Executive Summary .................................................................................................................................... 1 Section 1 – Building and Occupant Types ................................................................................................ 3 Section 2 - Service Policies .......................................................................................................................... 4 I. Infrastructure Installation/Maintenance II. Telephone Services III. Television Services IV. Data/Internet Services V. Wireless Services VI. Interconnection of Noncontiguous Spaces Section 3 - Infrastructure Policies .............................................................................................................. 7 I. Receipt Supported Office Buildings II. Third Party Developed Office Buildings III. Specialty Buildings Appendix 1 - Preferred Service Providers of Data Network Services .................................................. 16 Appendix 2 - Exceptions…………………………………………………………………………….…..17 Executive Summary Background The pace of development of Centennial Campus accelerated significantly during the 1990s. The completion of Research IV and Partners I buildings in 1996 and 1997 respectively marked an apparent realization of “critical mass” in the growth of the campus, especially in regards to the locating of corporate/government units (hereafter referred to as “Partners”) to NC State. Prior to the construction of these two buildings, the telecommunications infrastructure strategies in use on main campus seemed satisfactory to serve the voice, data, and video communication needs of Centennial Campus tenants. However, the shared infrastructure system in use in all university buildings proved less than ideal in those two facilities, especially in meeting the needs and desires of the non-university Partners located there. After these buildings were occupied, it became apparent that these Partners desired “private” infrastructure (e.g. telecom rooms, pathways, cabling systems, etc. which are not shared with other tenants) and customized infrastructure (not necessarily compliant with NC State’s University Wiring Standard). It also became apparent that these Partners desired much wider choice in the types of voice and data services than are provided to university departments by the Telecommunications (now “ComTech”) Office (part of the Office of Information Technology). The desire for customizable data services has led to the selection of outside service providers (called Preferred Service Providers or “PSP’s”) to provide a wide variety of such services to the Partners on Centennial Campus. The above inadequacies created the need to develop a set of communications and internet infrastructure and service strategies for tenant buildings on Centennial Campus. This document outlines the infrastructure strategies, policies, and mechanisms for procurement of services for both appropriated campus buildings and tenant buildings on the campus. The Approach The basic approach to the provision of communication and network services for university departments housed on Centennial Campus is to have their services and infrastructure mirror that on main campus as closely as possible. The only difference is that each department in a multi-tenant building will have a dedicated telecom room and wiring system within its space (as opposed to a shared system as they would have on main campus). Within the department’s space, the infrastructure will be installed according to the NCSU University Wiring Standard. These departments will obtain voice, data network, and CATV services from ComTech. The approach to providing services for non-university Partners is to isolate each Partner’s infrastructure from that of other tenants. The Partners are free to wire their spaces any way they see fit. The Partners will obtain traditional copper-based services from AT&T (either directly or via a third party provider of their choice), and they will obtain fiber-based services from one of the PSP’s. This will allow them maximum privacy, choice, and flexibility in meeting their connectivity needs in a manner closely resembling that available to them in high-end private commercial parks. Page 1 Version 1.4 Section 1 – Building and Occupant Types Centennial Campus consists of two major areas of the NC State University campus. The larger is the area between Centennial Parkway and I-440. The second, the Centennial Biomedical Campus is located between Hillsborough St. and Wade Ave. There are three basic types of occupants of Centennial Campus buildings: NCSU Departments This classification applies to any occupant who pays for services via a university OUC account. Corporate/Government Units (Partners) This classification applies to any occupant who pays for services via any means other than a university OUC account. (government agencies, private companies, etc.) Public Users of the Campus (condo and apartment residents, guests, etc.) In addition to traditional university facilities, there are several classifications of Centennial Campus buildings that house Partners: Receipt Supported Office Buildings (Research I, II, III, and IV, Partners I, II, and III, Poulton Innovation Center) Third Party Developed Office Buildings (Venture Center Complex, Keystone Science Center, Alliance Complex, 1801 Varsity) Specialty Buildings (North Shore Condominiums, The Greens Apartments, Poole Clubhouse) The policies and procedures governing infrastructure vary according to both the type of building and the type of occupant considered. This creates a matrix of combinations making provision of communications/internet services potentially complex and confusing. These guidelines attempt to simplify as much as possible the infrastructure requirements for each of these combinations. Page 3 Version 1.4 Section 2 - Service Policies Following are assumptions made regarding service policies that are drivers for the infrastructure policies outlined in these guidelines: I. Infrastructure Installation/Maintenance A. NCSU Departments. All spaces are required to be wired in compliance with the latest version of the NCSU University Wiring Standard (UWS). ComTech will maintain all infrastructure. B. Partners. Fiber optic cable and twisted pair copper cable will be required from the Building Distribution Frame (BDF) to an Intermediate Distribution Frame (IDF) in the Partner’s space. Costs for installation will be borne by the Partner. Partners are responsible for installation and maintenance of all wiring within their space (outward from their IDF). II. Telephone Services A. NCSU Departments. All telephone services will be required to be purchased from ComTech. B. Partners. ComTech will not provide any telephone services to the Partners. Partners will order traditional dial tone directly from AT&T. Partners may obtain VoIP telephone services from one of the PSP’s. III. Television Services A. NCSU Departments. CATV services will be required to be purchased from ComTech. B. Partners. CATV services are not currently available to Partners. Partners may procure satellite TV services from a satellite vendor. Installation must meet all physical and aesthetic requirements established by NCSU. Page 4 Version 1.4 IV. Data/Internet Services A. NCSU Departments. All data network services will be provided by ComTech. B. Partners. Partners may not obtain direct access to the NCSU campus data network. For lower speed (copper-based) services, they may procure services from AT&T or a third party provider who purchases services from AT&T. For higher speed (fiber-based) services, Partners have access to a wide array of services from the PSP’s. These providers have been granted special considerations (use of NCSU fiber) in order to serve Partners. See Appendix 1 for the current list of approved PSP’s. Partners may use other providers as they wish, but these will not be given the same special considerations as PSP’s, nor will they be allowed to install physical infrastructure to or between buildings on Centennial Campus. Other providers will be required to gain “last mile connectivity” from either AT&T (copper) or PSP’s (fiber). V. Wireless Services A. NCSU Departments. All wireless (WiFi) services will be provided by ComTech. B. Partners. Partners may access the NCSU wireless network by using the guest wireless network SSID. Partners may also install their own wireless access points in their space as long as the signal from these units do not negatively impact on the NCSU wireless network. VI. Interconnection of Noncontiguous Spaces A. NCSU Departments. Direct interconnection of departmental spaces will not be allowed. B. Partners. Two Spaces within One Building. Point to point interconnection of spaces within a single building will be the responsibility of the Partner. Partner spaces in two Centennial Campus buildings can be linked by the leasing of fiber pairs from ComTech from the BDF of one building to the BDF of another building. The Partner will be required to install fiber from their IDFs to each BDF. The current rate for leasing each fiber pair is $846.00/month. Fiber pair links may only be leased between Centennial Page 5 Version 1.4 Campus buildings, not from Centennial Campus buildings to main campus or to off campus locations. Ductbank cells will not be available for leasing. Page 6 Version 1.4 Section 3 - Infrastructure Policies I. Receipt Supported Office Buildings These buildings are usually constructed in two phases: base building and departmental/Partner space upfits. A. Base Building. 1. Components. The following components of this infrastructure will be constructed during the base building phase: Entrance ductbank to nearest ComTech manhole Building Distribution Frame (BDF) room Conduit and wiring for special use lines (elevator, blue light, fire alarm, etc.) Blue light telephone units on project site Stacked vertical “chase” closets for riser conduit installation Riser conduits from the BDF to chase closets Entrance telephone and fiber optic cables (by ComTech) Equipment racks and ladder racks in the BDF (by ComTech) 2. Access to the BDF. a. Partner and Departmental Access. Neither Partners nor university departments will have ongoing access to the BDF. Partners will have access to install riser cables only. Partners will not be allowed to install any equipment in the BDF. BDFs will be keyed to the ComTech telecom room master key. b. Service Provider Access. Only AT&T and the PSP’s will be allowed access to the BDF. 3. Design. The base building components should be designed in accordance with the University Wiring Standard with the following exceptions: a. BDF Equipment. Three standard equipment racks should be installed. One will be used for ComTech equipment and two for PSP equipment. b. Telephone Terminal Installation. AT&T will install their telephone terminal hardware on a designated wall. ComTech will install a demarcation board with associated hardware for NCSU telephone lines and special use (life safety) telephone lines, and will install a demarcation board for Partner telephone lines. Page 7 Version 1.4 c. Vertical “Chase” Closets. To provide for installation of riser conduits between the BDF and each departmental or Partner IDF, a series of small stacked closets should be constructed on each floor of the building. Ideally, these will be placed directly above the BDF. These rooms would be approximately 3' x 4' with a door to a corridor. This door should be keyed as mechanical rooms. These chase closets will be constructed in the base building phase. Also in that phase, a series of 2” EMT conduits will be installed from the BDF to each of the chase closets. The quantity of conduits will be determined during the building design based on the potential number of distinct tenants. 4. Base building connections. Horizontal cabling will be installed from the BDF to serve telephone and network connections that are generally not associated with the interior of specific tenant (department or Partner) spaces. These include common spaces (i.e. lobbies, vending areas, building conference rooms), life safety (i.e. blue lights, elevators, fire alarm dialers), security (i.e. card access – including door access to particular tenant suites, cameras), building system (i.e. electrical meters, building automation system controllers), and any other general building connection. Wireless access points that are part of the NCSU wireless network will also be wired back to the BDF. ComTech will install all equipment necessary in the BDF to facilitate connectivity for the above locations and systems. B. NCSU Departmental Space Upfits 1. Overview. The infrastructure for these buildings will be designed to provide isolation of a particular tenant’s infrastructure from the infrastructure serving other tenants. The infrastructure installed for spaces in these buildings that are occupied by NCSU departments will be virtually identical to that which is installed in appropriated campus buildings. The only difference is that no shared IDF and wireway system will be installed. Instead, an IDF will be built in each departmental space that will serve only that department. This infrastructure will be completely isolated from the infrastructure serving all other building tenants. 2. Components. The following components of this infrastructure will be constructed during the departmental upfits phase: One IDF in each departmental space Riser conduits connecting conduits in the nearest chase closet to each departmental IDF, and riser cables connecting each of the departmental IDFs to the BDF Page 8 Version 1.4 Equipment racks and ladder racks in the departmental IDF Cross-connect panels in the departmental IDF Wireways from the departmental IDF throughout the departmental space Station conduits from wireways to outlets Station wiring to outlets All required bonding and grounding of above 3. Design. With the exceptions noted above, the infrastructure installed during these upfits should comply with the University Wiring Standard (UWS 3.0). In smaller tenant upfits, the cabling and associated hardware may be installed by ComTech, with all IDF and pathway components installed by the contractor. C. Partners Space Upfits 1. Overview. The infrastructure serving spaces occupied by Partners will not be integrated into the infrastructure installed to serve NCSU departments. The Partners are responsible to install their own wiring within their space and copper and/or fiber riser cables from their space to the BDF. 2. Components. The following components of the infrastructure will be constructed during the Partner’s upfit phase: All voice and data wiring within their space. Riser cabling from the Partner’s space to the BDF. 3. Design and Construction. The design and construction of the infrastructure within the Partner’s space is the responsibility of and is at the discretion of the Partner. 4. Riser Cable Installation. The Partners are responsible to install any required riser cables connecting their space to the BDF as part of their space upfit. For Partners desiring copper-based connectivity services from AT&T, copper riser cable is required. For Partners desiring fiber-based connectivity services from one of the PSP’s, copper cable and/or fiber optic riser cable is required (depending on services desired). The Partners are responsible to coordinate connection of their cables to AT&T or the PSP in the BDF. Riser cables will be routed in the conduits referenced above from the BDF up through the chase closets to the floor where the Partner is located. The Partners must extend conduit from one of the existing riser conduits in the chase closet to their space for riser cabling. All cables outside of the Partner’s leased space must be in metallic conduit. Page 9 Version 1.4 5. Partner Work within the BDF. The Partner is responsible for any damage to existing cables or equipment in the BDF caused by them or any contractors working on their behalf. ComTech will retain final authority on the use of the BDF. No Partner or contractors/service providers working for the Partner (except the PSP’s) will be allowed to install any equipment, data electronics, telephone systems, etc. in the BDF. The Partners will not install any horizontal (station) wiring directly to the BDF. D. Receipt Supported Single Tenant Office Buildings. The infrastructure model for tenant office buildings housing only one Partner will be similar to the model presented above. The only difference is that except for the BDF itself, the type of intrabuilding infrastructure installed is at the discretion of and is the responsibility of the Partner. Page 10 Version 1.4 II. Third Party Developed Office Buildings These buildings are usually constructed in two phases: base building and departmental/Partner space upfits. A. Base Building. 1. Components. The following components of this infrastructure will be constructed during the base building phase: Entrance ductbank from nearest ComTech manhole. Building Distribution Frame room (BDF) Conduit and wiring for special use lines (elevator, blue light, fire alarm, etc.) Blue light telephone units on project site All required bonding and grounding of above Stacked vertical “chase” closets for riser conduit installation Floor sleeves from the BDF through the chase closets Entrance telephone and fiber optic cables (by ComTech – paid for by developer) Equipment racks and ladder racks in the BDF (by ComTech – paid for by developer) 2. Access to the BDF. a. Partner and Departmental Access. Neither Partners nor university departments will have ongoing access to the BDF. Partners will have access to install riser cables only. Partners will not be allowed to install any equipment in the BDF. BDFs will be keyed to the ComTech telecom room master key. b. Service Provider Access. Only AT&T and the PSP’s will be allowed access to the BDF. 3. Design. The base building components should be designed in accordance with the University Wiring Standard with the following exceptions: a. BDF Equipment. Three standard equipment racks should be installed. One will be used for ComTech equipment and two for PSP equipment. b. Telephone Terminal Installation. AT&T will install their telephone terminal hardware on a designated wall. ComTech will install a demarcation board with associated hardware for NCSU telephone lines and special use (life safety) telephone lines, and will install a demarcation board for Partner telephone lines. c. Vertical “Chase” Closets. Page 11 Version 1.4 To provide for installation of riser conduits between the BDF and each departmental or Partner IDF, a series of small stacked closets should be constructed on each floor of the building. Ideally, these will be placed directly above the BDF. These rooms would be approximately 3' x 4' with a door to a corridor. This door should not be keyed to the ComTech telecom room master key. These chase closets will be constructed in the base building phase. Also in that phase, a series of 2” EMT conduits will be installed from the BDF to each of the chase closets. The quantity of conduits will be determined during the building design based on the potential number of distinct tenants. 4. Base building connections. Horizontal cabling will be installed from the BDF to serve telephone and network connections that are generally not associated with the interior of specific tenant (department or Partner) spaces. These include common spaces (i.e. lobbies, vending areas, building conference rooms), life safety (i.e. blue lights, elevators, fire alarm dialers), security (i.e. card access – including door access to particular tenant suites, cameras), building system (i.e. electrical meters, building automation system controllers), and any other general building connection. Wireless access points that are part of the NCSU wireless network will also be wired back to the BDF. The developer may or may not elect to connect to NCSU services associated with the above systems. For all connections to NCSU services, ComTech will install all equipment necessary in the BDF to facilitate connectivity. B. NCSU Departmental Space Upfits. 1. Overview. The infrastructure for these buildings will be designed to provide maximum isolation of a particular tenant’s infrastructure from the infrastructure serving other tenants. The infrastructure installed for spaces in these buildings that are occupied by NCSU departments will be virtually identical to that which is installed in appropriated campus buildings. The only difference is that no shared IDF and wireway system will be installed. Instead, an IDF will be built in each departmental space that will serve only that department. This infrastructure will be completely isolated from the infrastructure serving all other building tenants. 2. Components. The following components of this infrastructure will be constructed during the departmental upfits phase: One IDF in each departmental space Page 12 Version 1.4 Riser conduits from each departmental IDF to the nearest chase closet, continuing down through the chase closets to the BDF, and riser cables connecting each of the departmental IDFs to the BDF Equipment racks and ladder racks in the departmental IDF Cross-connect panels in the departmental IDF Wireways from the departmental IDF throughout the departmental space Station conduits from wireways to outlets Station wiring to outlets All required bonding and grounding of above 3. Design. With the exceptions noted above, the infrastructure installed during these upfits should comply with the University Wiring Standard (UWS 3.0). In smaller tenant upfits, the cabling and associated hardware may be installed by ComTech, with all IDF and pathway components installed by the developer. C. Partners Space Upfits. 1. Overview. The infrastructure serving spaces occupied by Partners will not be integrated into the infrastructure installed to serve NCSU departments. The Partners are responsible to install their own wiring within their space and copper and/or fiber riser cables from their space to the BDF. 2. Components. The following components of the infrastructure will be constructed during the Partner’s upfit phase: All voice and data wiring within their space. Riser cabling from the Partner’s space to the BDF. 3. Design and Construction. The infrastructure within the Partner’s space is the responsibility of and is at the discretion of the Partner. 4. Riser Cable Installation. The Partners are responsible to install any required riser cables connecting their space to the BDF as part of their space upfit. For Partners desiring copper-based connectivity services from AT&T, copper riser cable is required. For Partners desiring fiber-based connectivity services from one of the PSP’s, copper cable and/or fiber optic riser cable is required (depending on services desired). The Partners are responsible to coordinate connection of their cables to AT&T or the PSP in the BDF. 5. Partner Work within the BDF. No Partner or contractors/service providers working for the Partner (except the PSP’s) will be allowed to install any equipment, data electronics, Page 13 Version 1.4 telephone systems, etc. in the BDF. The Partners will not install any horizontal (station) wiring directly to the BDF. Page 14 Version 1.4 III. Third Party Developed Specialty Buildings A. Overview. These are various new buildings that are to be built by outside developers. They generally house service providers who are providing a variety of services to NC State faculty, staff, students, and the general public. Examples include restaurants, hotels, condominium, retail, etc. Each building may house only one service provider or a multitude of providers. The current assumption is that all of these providers will be outside companies, agencies, etc. (not NCSU departments). Due to the uniqueness of each building, communications/internet infrastructure strategies may vary from building to building. However, following are some principles that should transcend all buildings within this classification. As with third party developed office buildings, these buildings are to be designed based on the goal of minimizing the amount of infrastructure, space, and cost required for the outside developer. B. Model. The infrastructure and services model for these buildings should mimic that used in third party developed office buildings. Page 15 Version 1.4 Appendix 1 - Service Providers for Partners Updated 6/1/14 Corporate and government partners located on Centennial Campus have several options for obtaining internet and communication services to meet their needs. These include: 1. Copper-based Services – AT&T offers a variety of telephone and lower speed (DSL) internet options using copper cables they have installed to each Centennial Campus building. Information on these services can be found at www.ATT.com under their “Small Business” offerings. 2. Fiber-based Services – NC State University has created a unique partnership with two top-tier internet service providers to provide impressive arrays of communication and high-speed internet services to Centennial partners. This partnership, termed the Preferred Service Provider (PSP) program, allows these two providers, Time Warner Cable and TW Telecom, to use university—owned, underground fiber optic cables to reach every building on the campus. There are no limits on the either the variety of services that can be offered or the bandwidth provided to a specific partner. 3. See the attached description of services sheets for more info on each PSP. In addition, each PSP has account representatives focused on Centennial Campus. If a partner is interested in having a representative visit them to explain their services and rates, they should reach out to the following contacts: TW Telecom Susan Poteat Senior Account Executive 919-573-7775 Susan.poteat@twtelecom.com Time Warner Cable Business Class Walter Hayes Major Account Executive 919-654-7694 Walter.hayes@twcable.com Note: Partners may elect to utilize secondary internet service providers other than those listed above. However, those secondary providers must procure network connectivity via one of the above PSP’s. Page 16 Version 1.4 Appendix 2 - Exceptions A. NCREN Connectivity (updated 6/1/2012) NCSU and MCNC technical staffs have determined that it is acceptable to provide NCREN connectivity to customers on NCSU Centennial Campus in certain circumstances. These special circumstances are as follows: 1. The requesting organization already has an existing connection elsewhere to NCREN, or is contractually committed to obtaining a connection to NCREN from another location; 2. The requesting organization is either a commercial or research affiliate with NCSU and the collaborative work of this affiliation would be better served if that organization were connected to NCREN; 3. The requesting organization has known potential to be a commercial or research affiliate with NCSU and it is anticipated that the collaborative work of this affiliation would be better served if the organization were connected to NCREN. Circumstances #2 or #3 require sponsorship of the appropriate Vice Chancellor or Dean highlighting the benefits of connectivity. Organizations meeting the criteria above and wishing to establish connectivity will need to engage both MCNC technical staff and NCSU ComTech staff to discuss specific network needs. The MCNC technical staff will coordinate such requests with the NCSU Comtech staff, and all such arrangements will require individual engineering by NCSU Comtech staff to ensure optimum utilization of scarce on-campus infrastructure. The cost of the use of the NCSU infrastructure shall become a part of the overall price quotation that MCNC will make to the customer and, upon agreement execution and subsequent implementation completion, will thereafter be collected by MCNC and paid to NCSU in normal fashion for such revenue sharing arrangements. NCREN connections approved under this plan shall require that the customer: Sign an Agreement with MCNC that includes both NCREN and NCSU costs and fees; and, Obtain and place appropriate fiber optic cabling from their space back to the main telecom room (BDF) for their building; and, Work with the building owner (NCSU or private developer) regarding requirements (i.e. electrical/fire code or NCSU's requirement that all Page 17 Version 1.4 cabling in building common spaces be in conduit); and, Coordinate with ComTech on where to terminate cables in the BDF room. Page 18 Version 1.4