C2 Full Factory Calibration Worksheet for Pressure

advertisement
#21 C2Sheets.doc
APPLICATION HELP
C2 Full Factory Calibration
Configuration Form Required
When you select the C2 option for a full factory calibration, it is necessary to submit a C2 Configuration Form.
IMPORTANT!!
The order will not be processed at the factory until the form is submitted. The
required forms are provided in the pages that follow.


Please submit the form that is appropriate for the electronics option selected.
It is only necessary to provide the information that differs from the default values shown on the form.
Blank spaces will automatically set the default value.
Configuration Forms Below
To print only the form you want, select:
 File > Print
 Select the “Pages” button and enter the pages indicated.
1. INTELLIGENT I/A SERIES PRESSURE TRANSMITTERS - FOXCOM “-D” VERSION
Pages 2 – 4
2. INTELLIGENT I/A SERIES PRESSURE TRANSMITTERS HART “-T” VERSION
Pages 5 - 7
3. I/A SERIES PRESSURE TRANSMITTERS
4 to 20 ma “-I” VERSION
Pages 8 - 9
4. ANALOG OUTPUT I/A SERIES PRESSURE TRANSMITTERS “-A” VERSION
Pages 10 - 11
5. ANALOG OUTPUT I/A SERIES PRESSURE TRANSMITTERS “-V” VERSION
Pages 12 - 13
Page 1 of 8
INTELLIGENT I/A SERIES PRESSURE TRANSMITTERS - FOXCOM “-D” VERSION
CONFIGURATION WORKSHEET FOR -C2 OPTION
Customer: ________________________
P.O. No.: __________________Item No. (on P.O.): _____________
Your Office Order No.: _____________________________
Your Name: ____________________
Foxboro S.O. No.: ___________________________
Your Branch or Company: ___________________
Date: ___________
MAKE ONE SELECTION FOR EACH AND EVERY PARAMETER. IF ANY ITEMS ARE LEFT BLANK, THE FACTORY
DEFAULT VALUES MAY BE USED FOR THE ENTIRE TRANSMITTER. REQUIRED: SEPARATE SHEET FOR EACH
TAG NUMBER, UNLESS ALL CONFIGURATION DATA IS IDENTICAL.
Category/Parameter
Information
Factory
Default
Optional Configuration
Requested
Descriptors:
Tag Number
12 Characters, max.
Tag Number
_________________________
Tag Name
14 Characters, max.
Owner Tag Name
_________________________
Location
14 Characters, max.
Instr Location
_________________________
Device Name
6 Characters, max.
DevNam
_________________________
Calibrated Range
LRV may be < or > URV.
If Sq. Rt., LRV must = 0.
See List B for
Default Calibrated
Range by model.
_____ to
_____ _____
LRV
URV Units
(See List A for available units)
Meas. #1 Mode
4-20 mA or Digital
4-20 mA
□ 4-20 mA
Measurement #1
Characteristic
If LRV>URV, select Linear.
Square root applicable to
IDP10.
Linear
□ Linear
□ Sq. Rt. w/Cutoff
□ Sq. Rt. w/Active Low End
Measurement #1
EGU's
If Sq.Rt., use % or Custom.
Std. Pressure Units
from Calibrated
Range, above.
□ Std. Press. Units from
Calib. Range, above.
(Requires Meas.#1 Linear)
Input:
Output:
If "Custom", specify LRV,
URV, & Units. For example,
0 to 100 GPM.
□ Digital
□ 0 to 100 %
□ Custom Units, Specify:
Specified EGU's will also
be used for optional LCD.
LIST A (Standard Pressure Units):
-psig
-ftH2O
-bar
-psia
-inH2O
-mbar
-inHg
-atm
-MPa
-Pa
-kg/cm2
-g/cm2
-dy/cm2
-cmHg
-mmHg
_____ to
LRV
_____ _____
URV Units
(6 Characters,
Maximum)
-torr
-cmH2O
-mmH2O
-kPa
1/30/97 Rev.
Page 2 of 8
WORKSHEET FOR -C2 OPTION ON -D INTELLIGENT VERSIONS (CONT.)
PAGE 2 OF 3
Data for Tag Number _______________, continued:
Category/Parameter
Factory
Default
Optional Configuration
Requested
Linear
□ Off
□ Linear
□ Sq. Rt. w/Cutoff
□ Sq. Rt. w/Active Low End
0 to 100 %
If "Custom", specify LRV,
□ Std. Press. Units from List A
Specify Units:_____Note (b)
(Meas. #2 must be Linear)
URV, & Units.
For example, 0 to 100 GPM.
□ 0 to 100 %
□ Custom Units, Specify:
Choices/Information
Output (Continued)
Measurement #2
Status and
Characteristic
Square root applicable to
IDP10.
Note (a)
Measurement #2
EGU's
If Sq.Rt., use % or Custom.
Specified EGU's will also
be used for optional LCD
Indicator. Note (c).
_____ to
LRV
_____ _____
URV Units
(6 Characters,
Maximum)
Failsafe Direction:
(4-20 mA, only)
High or Low mA on
certain faults
High
□ High
□ Low
Temp. Failure Strategy
Fail or Continue with
Default Temperature
Continue
□ Fail
□ Continue
External Zero
Adjust Security
For optional External
Zero adjustment
Enabled
□ Enabled
□ Disabled
Swap Meas. #1 & #2
Interchange configured outputs
No
□ Yes
□ No
Damping:
None, 0.25, 0.50, 1, 2, 4,
8, 16, or 32 seconds
None
Specify: ________________
WHERE TO SEND THIS FORM:
Until this form is included in SiebeStore for electronic transmission with the order, FAX or mail
Pages 1 & 2 to your Distribution Coordinator whenever the -C2 Option is specified on an order.
1/30/97 Rev.
Page 3 of 8
WORKSHEET FOR -C2 OPTION ON -D INTELLIGENT VERSIONS (CONT.)
PAGE 3 OF 3
NOTES:
(a) If Measurement #1 is configured "Square Root", which precludes use of pressure units, consider configuring
Measurement #2 "Linear" to provide a means of reading pressure units.
Also, if Measurement #1 is in "Square Root" mode, the pressure units for reranging from the optional LCD
indicator default to "Transmitter Default Units" (such as inH2O on a "B" Span IDP10) unless Measurement #2 is
"Linear", in which case they default to the standard pressure units specified for Measurement #2. This provides a
convenient way to rerange in preferred local pressure units, such as mbar or mmH2O.
(b) Units selected for Measurement #2 may be different from units selected for Measurement #1.
(c) The optional LCD Indicator normally displays Measurement #1. It will display Measurement #2 if the "Enter"
pushbutton is pressed once. It defaults to Measurement #1 upon removal of power and therefore can only be
selected after transmitter is installed and powered.
(d) Handheld Terminal (HHT) and optional LCD w/Pushbuttons can be used to configure most selections. A few
require the PC10 or I/A Series System Configurators.
(e) A Forward/Reverse selection can be used to achieve the requested calibration direction, based on LRV & URV.
LIST B (Default Calibrated Ranges)
The following calibrated ranges & units will be used if the Calibrated Range is left blank or is marked "Uncalibrated".
Model Span Code
Default Calibrated Range
IDP10 B
&
C
IGP20 D
E
0 to 200 inH2O
0 to 840 inH2O
0 to 300 psi
0 to 3000 psi
IGP10 C
D
E
0 to 30 psi
0 to 300 psi
0 to 3000 psi
IAP10 C
D
E
0 to 30 psia
0 to 300 psia
0 to 3000 psia
1/30/97 Rev.
Page 4 of 8
ANALOG OUTPUT I/A SERIES PRESSURE TRANSMITTERS “-A” VERSION
CONFIGURATION WORKSHEET FOR -C2 OPTION
Customer: ________________________
P.O. No.: __________________Item No. (on P.O.): _____________
Your Office Order No.: _____________________________
Your Name: ____________________
PAGE 1 OF 2
Foxboro S.O. No.: ___________________________
Your Branch or Company: ___________________
Date: _____________
MAKE ONE SELECTION FOR EACH AND EVERY PARAMETER. IF ANY ITEMS ARE LEFT BLANK, THE FACTORY
DEFAULT VALUES MAY BE USED FOR THE ENTIRE TRANSMITTER. REQUIRED: SEPARATE SHEET FOR EACH
TAG NUMBER, UNLESS ALL CONFIGURATION DATA IS IDENTICAL.
Factory
Default
See List B for
Default Calibrated
Range by model.
Optional Configuration
Requested
_____ to
_____ _____
LRV
URV Units
(See List A for available units)
Category/Parameter
Calibrated Range
Information
LRV may be < or > URV.
If Sq. Rt., LRV must = 0.
Characteristic
If LRV>URV, select Linear.
Square root applicable to
IDP10.
Linear
□ Linear
□ Sq. Rt. w/Cutoff
□ Sq. Rt. w/Active Low End
Failsafe Direction:
High
□ High
□ Low
External Zero
Adjust Security
Damping:
High or Low mA on
certain faults
For optional External
Zero adjustment
None, 2, 4, or 8 seconds
Enabled
□ Enabled
□ Disabled
None
□ None
□ 2 sec.
□ 4 sec.
□ 8 sec.
Temp. Failure
Strategy
Fail or Continue with
Default Temperature
Continue
□ Fail
□ Continue
LCD Indicator:
(LINEAR MODE)
If in Linear Mode there are no configuration choices; the display automatically shows the
measured pressure in the units previously selected for the Calibrated Range.
LCD Indicator:
(SQ. RT. MODE)
Label (Engr. Units
PERCENT
for Display – typically
the Flow Rate Units).
Select up to seven
alphanumeric characters.
Alpha’s are Upper Case Only.
Spaces are allowed.
Available symbols include:
], *, +, -, /, \, <, >, and [
LCD Indicator:
(SQ. RT. MODE)
(Continued)
Page 5 of 8
Display Upper Range Value,
(typically the Maximum
Flow Rate). Specify up to
four digits, a + or -, and
location of decimal point.
Write alphanumerics here
Write numbers here
100
Mark
*
+ or - Mark Decimal Point
here. in one of these 4 places.
* (dec.pt. at far rt. position not displayed on LCD)
6/18/98 Rev.
WORKSHEET FOR -C2 OPTION ON ANALOG OUTPUT “-A” VERSION (CONT.) PAGE 2 OF 2
LIST A – Available Standard Pressure Units (displayed in UPPER CASE only):
-psi
-inHg
-bar
-kg/cm2
-MPa
-inH2O
-mmH2O
-mbar
-Pa
-torr
-ftH2O
-mmHg
-g/cm2
-kPa
-atm
LIST B (Default Calibrated Ranges)
The following calibrated ranges & units will be used if the Calibrated Range is left blank or is marked "Uncalibrated".
Model
IDP10
&
IGP20
IGP10
&
IAP10
Span Code
A
B
C
D
E
Default Calibrated Range
0 to 30 inH2O
0 to 200 inH2O
0 to 840 inH2O
0 to 300 psi
0 to 3000 psi
C
D
E
0 to 30 psi
0 to 300 psi
0 to 3000 psi
Reranging:
The -A version supports reranging without pressure and can be reranged in the field. Reranging must be done in Linear
Mode. If there is a custom flow rate display (Square Root Mode only), it will have to be reconfigured following a
reranging.
LCD Indicator (Standard on –A Electronics Modules):
There are two lines for display of up to four numeric characters for the measurement on the top line (with plus or minus
& selectable decimal point position) and up to seven alphanumeric characters on the bottom line, referred to as the Label.
In Linear Mode the display shows the measured pressure in the units selected for the calibrated range and cannot be
changed.
In Square Root Mode the display defaults to 0 to 100 PERCENT. However, the display can be configured to show the
flow rate and flow rate units. When placed in Square Root Mode, the transmitter retains the calibrated range defined by
the pressure range LRV and URV, previously entered and saved.
When flow rate is to be displayed, the maximum flow rate corresponding to the 20 mA output signal must be entered. If
the maximum flow rate exceeds four digits, use a multiplier such as X10. For example, if the flow rate URV is 40000
SCFH, you could specify 4000 for the display URV and X10SCFH for the Label on the bottom line.
WHERE TO SEND THIS FORM
Until this form is included in SiebeStore for electronic transmission with the order, FAX or mail Page 1 to your
Distribution Coordinator whenever the -C2 Option is specified on an order.
6/18/98 Rev.
Page 6 of 8
ANALOG OUTPUT I/A SERIES PRESSURE TRANSMITTERS “-V” VERSION
CONFIGURATION WORKSHEET FOR -C2 OPTION
Customer: ________________________
P.O. No.: __________________Item No. (on P.O.): _____________
Your Office Order No.: _____________________________
Your Name: ____________________
PAGE 1 OF 2
Foxboro S.O. No.: ___________________________
Your Branch or Company: ___________________
Date: _____________
MAKE ONE SELECTION FOR EACH AND EVERY PARAMETER. IF ANY ITEMS ARE LEFT BLANK, THE FACTORY
DEFAULT VALUES MAY BE USED FOR THE ENTIRE TRANSMITTER. REQUIRED: SEPARATE SHEET FOR EACH
TAG NUMBER, UNLESS ALL CONFIGURATION DATA IS IDENTICAL.
Factory
Default
See List B for
Default Calibrated
Range by model.
Optional Configuration
Requested
_____ to
_____ _____
LRV
URV Units
(See List A for available units)
If LRV>URV, select Linear.
Square root applicable to
IDP10.
Linear
□ Linear
□ Sq. Rt. w/Cutoff
□ Sq. Rt. w/Active Low End
High
□ High
□ Low
External Zero
Adjust Security
Damping:
High or Low V on
certain faults
For optional External
Zero adjustment
None, 2, 4, or 8 seconds
Enabled
□ Enabled
□ Disabled
None
□ None
□ 2 sec.
□ 4 sec.
□ 8 sec.
Temp. Failure
Strategy
Fail or Continue with
Default Temperature
Continue
□ Fail
□ Continue
LCD Indicator:
(LINEAR MODE)
If in Linear Mode there are no configuration choices; the display automatically shows the
measured pressure in the units previously selected for the Calibrated Range.
LCD Indicator:
(SQ. RT. MODE)
Label (Engr. Units
PERCENT
for Display – typically
the Flow Rate Units).
Select up to seven
alphanumeric characters.
Alpha’s are Upper Case Only.
Spaces are allowed.
Available symbols include:
], *, +, -, /, \, <, >, and [
Category/Parameter
Calibrated Range
Information
LRV may be < or > URV.
If Sq. Rt., LRV must = 0.
Characteristic
Failsafe Direction:
LCD Indicator:
(SQ. RT. MODE)
(Continued)
Display Upper Range Value,
(typically the Maximum
Flow Rate). Specify up to
four digits, a + or -, and
location of decimal point.
Write alphanumerics here
Write numbers here
100
Mark
*
+ or - Mark Decimal Point
here. in one of these 4 places.
* (dec.pt. at far rt. position not displayed on LCD)
6/18/98 Rev.
Page 7 of 8
WORKSHEET FOR -C2 OPTION ON ANALOG OUTPUT “-V” VERSION (CONT.) PAGE 2 OF 2
LIST A – Available Standard Pressure Units (displayed in UPPER CASE only):
-psi
-inHg
-bar
-kg/cm2
-MPa
-inH2O
-mmH2O
-mbar
-Pa
-torr
-ftH2O
-mmHg
-g/cm2
-kPa
-atm
LIST B (Default Calibrated Ranges)
The following calibrated ranges & units will be used if the Calibrated Range is left blank or is marked "Uncalibrated".
Model
IDP10
&
IGP20
IGP10
&
IAP10
Span Code
A
B
C
D
E
Default Calibrated Range
0 to 30 inH2O
0 to 200 inH2O
0 to 840 inH2O
0 to 300 psi
0 to 3000 psi
C
D
E
0 to 30 psi
0 to 300 psi
0 to 3000 psi
Reranging:
The -V version supports reranging without pressure and can be reranged in the field. Reranging must be done in Linear
Mode. If there is a custom flow rate display (Square Root Mode only), it will have to be reconfigured following a
reranging.
LCD Indicator
There are two lines for display of up to four numeric characters for the measurement on the top line (with plus or minus
& selectable decimal point position) and up to seven alphanumeric characters on the bottom line, referred to as the Label.
In Linear Mode the display shows the measured pressure in the units selected for the calibrated range and cannot be
changed.
In Square Root Mode the display defaults to 0 to 100 PERCENT. However, the display can be configured to show the
flow rate and flow rate units. When placed in Square Root Mode, the transmitter retains the calibrated range defined by
the pressure range LRV and URV, previously entered and saved.
When flow rate is to be displayed, the maximum flow rate corresponding to the 5 V output signal must be entered. If the
maximum flow rate exceeds four digits, use a multiplier such as X10. For example, if the flow rate URV is 40000 SCFH,
you could specify 4000 for the display URV and X10SCFH for the Label on the bottom line.
WHERE TO SEND THIS FORM
Until this form is included in SiebeStore for electronic transmission with the order, FAX or mail Page 1 to your
Distribution Coordinator whenever the -C2 Option is specified on an order.
6/22/99 Rev.
Page 8 of 8