SECTION 123XX - WOOD LABORATORY CASEWORK AND EQUIPMENT SHELDON STANDARD SERIES PART 1 GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of contract, including General and Supplementary Conditions and Division-1 specification sections, apply to work of this section. 1.02 1.03 1.04 QUALIFICATIONS A. All laboratory equipment covered by this specification and accompanying drawings shall be manufactured or furnished by one manufacturer and supplied under their direction to eliminate any divided responsibility. B. Owner reserves the right to reject any or all bids and award contract to other than lowest bidder if, in their opinion, such action would insure better performance and a higher level of function, quality, and value. QUALITY ASSURANCE A. Products of Sheldon Laboratory Systems are specified as a basis of design, quality, and layout. The specifications and drawings define and show the essential minimum requirements. Where a definite material or manufacturer is specified, it is not the intent to discriminate against any product of another manufacturer. However, it is the intent of this specification to provide for the Owner a quality and educationally functional installation of laboratory equipment and casework, and to exclude inadequate or inferior laboratory equipment and casework. B. Minimum standards are set forth herein to comply with this intent. Laboratory equipment and casework manufacturer(s)/bidders are cautioned that ONLY EQUIPMENT MEETING THE STANDARDS SET FORTH IN THE SPECIFICATION WILL BE ACCEPTABLE. C. To insure that all bidders are bidding equal equipment, all requests for changes, modifications, substitutions, approvals, etc., will be set forth in an addendum. Any item not receiving prior approval will rightfully be construed as based on supplying the educational function, essential requirements, design, construction, and materials as called for in this specification. Bidders shall not rely upon approvals made in any other manner. D. Cabinet construction and associated components are approved and listed with SEFA to SEFA 8-2010 4TH Edition, Version 1.0 Specification. WORK BY LABORATORY EQUIPMENT CONTRACTOR 1 1.05 A. Furnishing, delivering to the building, uncrating, setting in place, leveling, and anchoring all casework and equipment listed in the specifications or equipment schedule and/or shown on the drawings. B. Furnishing plumbing fixtures and fittings only as defined in the specifications, complete with tank nipples and lock nuts for mounting fixtures and fittings on tops or curbs. Installation will be by other respective trades as a part of their final connections. C. Furnishing electrical service fixtures directly attached to the casework or equipment as called for in the specifications, equipment list and/or shown on the drawings. Fixtures supplied only, not attached or assembled. Installation will be by other respective trades as a part of their final connections. D. Furnishing sink bowls and cup sinks, complete with required overflows, plugs and strainers as called for in the specifications, equipment list and/or shown on the drawings. Sinks supplied, not attached or assembled. Installation will be by other respective trades as a part of their final connections. E. Furnishing and installing filler panels and scribes as required for finished installation. F. Removal of all debris, dirt, and rubbish accumulated as a result of installation of this equipment, leaving premises broom clean and orderly. WORK BY OTHERS A. Furnishing, installing, and connecting of all service lines, drain lines, piping, and conduit within equipment and fume hoods, in service turrets or tunnels, through, under, or along the backs of working surfaces, and in reagent racks above counter tops as required by specifications and/or drawings. B. Furnishing, installing, and connecting all ductwork from fume hoods to blowers and from blowers to final point of discharge to atmosphere. Blower furnished by mechanical contractor. C. Furnishing, installing, and connecting of all vents, revents, steam fittings and special plumbing fixtures or piping to meet local codes, even though not specifically called for in the specifications and/or shown on the drawings. D. Furnishing and installation of all rigid or flexible conduit, wire, pulling of wire, fittings, special electrical equipment and accessories including boxes, receptacles; flush plates sent loose. Included are those in box curbs or tops which are not installed at Equipment Contractor's plant due to inconvenience of shipping. All shall be in accordance with local codes even though not specifically called for in specifications and/or shown on drawings. Wiring and connection of switch to fume hood lights and blower motors. 2 1.06 E. Providing all framing and reinforcements of walls, floors, and ceilings necessary to adequately support the equipment and all bucks and plaster grounds required for proper installation of equipment. F. Furnishing any miscellaneous materials generally classified as maintenance or supply items. G. Providing protection and security by General Contractor during and after laboratory equipment installation. H. Hoisting or elevator service by General Contractor at no charge to Equipment Contractor. DRAWINGS This contractor shall furnish to the Owner, five (5) sets of shop drawings showing in detail all proposed materials, equipment, and scope of work. 1.07 MAINTENANCE AND OPERATING INSTRUCTIONS This contractor shall include in its bid, the cost of providing a technically qualified representative for a period of one (1) day to thoroughly instruct the Owner's personnel in correct procedures of operating and maintaining this contract. 1.08 GUARANTEE This contractor shall guarantee all materials and workmanship of equipment provided on this contract for a period of one (1) year from the date of final acceptance. Any defective materials or faulty workmanship occurring within that time shall be replaced or corrected without charge. PART 2 PRODUCTS 2.01 MATERIALS (WOOD CASEWORK) A. General 1. B. All casework shall be of modern design and shall be constructed in accordance with the best woodworking practices of the cabinet making industry. First class quality casework shall be established by use of machinery, tools, fixtures, and skilled workmanship. Tolerances for components per various equipment used to manufacture components. Definitions 1. The following definitions apply to wood laboratory casework units. Casework unit size and type are indicated on the drawings and/or equipment list. 3 C. a. Exposed portions of casework include surfaces visible when doors and drawers are closed. Bottoms of cases more than 4'-0" above floor shall be considered as exposed. Visible members in open cases or behind glass doors also shall be considered as exposed portions. b. Unexposed portions of casework shall include sleepers, web frames, dust panels, and other surfaces not usually visible after completed installation. c. Semi exposed portions of casework shall include interior spaces only exposed to view when doors and drawers are open. Materials Materials used for construction of cabinets, cases and tables as specified herein shall meet or exceed the minimum standards as specified. 1. Wood species required shall be: Maple 2. All wood materials used shall meet applicable standards for CARB 2. 3. Exposed Woods 4. 5. a. Solid Wood: Flat sawn lumber, clear and free from defects. All lumber thoroughly and properly air dried to a uniform moisture content of 4%-6% by weight, tempered to 7%-8% during fabrication. b. Plywood: Plywood shall be thickness as specified herein, faced with surface veneer secured with highly waterresistant glue. Wood veneer shall be plain sliced. Wood veneer shall be "Premium Grade A", face smooth, tight cut and full length of exposed face. Unexposed Woods a. Solid Lumber: Dry, sound, selected to eliminate appearance defects. Any species of hardwood. b. Plywood: Uniform hardwood face veneer. Hardboard: (Tempered) Shall be 1/4" thick. All hardboard shall be composed of wood fibers and resinous binder compressed under heat and pressure. 4 D. Construction - General 1. Cabinets, cases, tables, and other units shall be of the size and configuration indicated on the drawings and/or equipment list. General construction is bored, doweled, dadoed and glued. 2. Base Cabinet Construction 3. a. Cabinet end panels shall be 3/4" thick, 7-ply, hardwood plywood. b. Vertical partitions (as required) shall be 3/4" thick, 7-ply, hardwood plywood. c. Exposed edges of end panels, bottoms, partitions, shelves shall be edged with 3mm solid wood banding. d. Two Piece Top Frame: 1" X 3" solid hardwood front rail, back grooved to receive cross rails, and similar 1” X 3” solid hardwood back rail, both set flush with cabinet ends; doweled and glued into place. e. (Optional) Cross rails are 1" X 2-1/4" solid hardwood fully housed into front and back rails with mortised and tenoned joints to form a full four-sided top frame. f. Intermediate rails are provided on all base cabinets between drawer/drawer configurations and drawer/door configurations. Rails are 1” X 3” solid hardwood rails, back grooved to receive security panels (as required). Rails shall be set flush with cabinet ends; doweled and glued into place. g. Cabinet bottoms shall be 3/4”, 7 -ply hardwood plywood. Set flush with cabinet ends; doweled and glued into place. h. Security panel (as required) is 1/4" thick hardboard. Panel is provided between drawers/drawers and drawers/doors base cabinets only when specified. Wall Cabinet Construction a. Cabinet end panels shall be 3/4" thick, 7-ply, hardwood plywood. b. Vertical partitions (as required) shall be 3/4" thick, 7-ply, hardwood plywood. c. Exposed edges of end panels, top and bottom panels, partitions, shelves shall be edged with 3mm solid wood banding. d. Cabinet tops and bottoms shall be 1”, 11 -ply hardwood plywood. 5 Set flush with cabinet ends; doweled and glued into place. 4. 5. e. Back panel shall be ¼” hardwood plywood when cabinet interior is exposed and ¼” hardboard when semi exposed. f. Top and bottom back rail shall be 1/2” hardwood plywood. g. Each wall case will be provided two heavy duty steel angled mounting brackets screwed to the interior of the cabinet end panels and shall be used for mounting cabinets to wall structure. Tall Cabinet Construction a. Cabinet end panels shall be 3/4" thick, 7-ply, hardwood plywood. b. Vertical partitions (as required) shall be 3/4" thick, 7-ply, hardwood plywood. c. Exposed edges of end panels, top and bottom panels, partitions, shelves shall be edged with 3mm solid wood banding. d. Intermediate rails (as required) or back rails are 1” X 3” solid hardwood rails, back grooved to receive security panels as required, set flush with cabinet ends; doweled and glued into place. e. Cabinet bottoms shall be 3/4”, 7 -ply hardwood plywood. Set flush with cabinet ends; doweled and glued into place. f. Cabinet tops shall be 1”, 11 -ply hardwood plywood. Set flush with cabinet ends; doweled and glued into place. g. Top Back Rail and Center Back Rail shall be 1" X 3" solid hardwood doweled and glued into end panels. Bottom Back Rail shall be ¾” X 4” hardwood plywood doweled and glued into end panels. h. Back panel shall be ¼” hardwood plywood when cabinet interior is exposed and ¼” hardboard when semi exposed. Drawers – Classic Series, Square Edge partial Overlay, Wood Edge Band, Vertical Match Grained Front(s) cut from one panel a. Classic Front: Shall be 3/4" thick 45 lb. industrial grade particle board core, 5 ply panel with both faces surfaced with hardwood veneer. Edges banded with 3 mm solid hardwood with a slight radius. Grain is vertically matched cut from one panel as a set 6 b. 6. Doors - Base and Wall Cabinets - Classic Series, Square Edge partial Overlay, Wood Edge Band, Vertical Match Grained Front(s) cut from one panel a. 7. 10. Shall be 3/4" X 3” solid hardwood rails, doweled and glued together; sanded for smooth fit and edge detailed to match door selection. Cabinet Backs a. Exposed interior - 1/4" thick hardwood plywood b. Unexposed interior - 1/4" thick hardboard (Removable at sink cabinets) Cabinet Shelves a. E. Estate front: Shall be 3/4" thick constructed door with 45 lb industrial grade core, 3/4" X 7/8” solid hardwood banding, Overlaid with 1/8” solid hardwood veneer, radius all edges. Grain direction is vertical. Doors - Framed Glass a. 9. Estate front: Shall be 3/4" thick constructed door with 45 lb industrial grade core, 3/4" X 7/8” solid hardwood banding, Overlaid with 1/8” solid hardwood veneer, radius all edges. Grain direction is vertical. Doors - Tall Cabinets - Classic Series, Square Edge partial Overlay, Wood Edge Band, Vertical Match Grained Front(s) cut from one panel a. 8. Drawer Box Body: Back, sides, and front shall be 1/2” thick 9-ply birch plywood, chuck and bore joinery with 1 /4” thick hardboard white melamine bottom. Set in groove all around, pinned and glued, clear chemical resistant finish with top edges finished. Shelves in cabinets shall be 1” thick 11-ply hardwood plywood. Front edge banded with 3mm solid hardwood. Shelves are adjustable on 1-1/4" centers, supported by four (4) nickel-plated steel pin and socket type shelf clips. Partial depth shelves are standard. Laboratory Grade Wood Finish 1. Exposed wood parts of all laboratory equipment shall be finished SEFA approved finish. Standard colors or clear finish available 7 2. All parts shall be carefully sanded and buffed in preparation for the finishing processes. The first coat shall be a stain and sealer coat of synthetic resin. The product is then cured at elevated temperatures. After the first sealer coat, the product shall be sanded, wiped clean and then two (2) more coats of an acid resisting synthetic resin shall be applied and cured at elevated temperatures. a. 3. Cabinet Finish Chemical Test and Evaluation a. 2.02 Interior of cabinets with solid doors receive one (1) sealer coat and one (1) coat of an acid resisting synthetic resin. Chemical Test and Evaluation shall be in accordance with SEFA8-W-2010. Independent test reports available upon request. CASEWORK HARDWARE AND ACCESSORIES A. Hinges: Institutional type, ground tip, five-knuckle, with pins of not less than .177" in diameter and leaves of not less than .095" thick. Hinges shall be wrought steel with chemical resistant epoxy powder coating. Two (2) hinges shall be provided on doors under 36" in height and three (3) hinges for doors 36" and over. B. Pulls: Solid metal, wire type, 4" long mounted with two (2) screws fastened from back. Pulls shall be chemical resistant epoxy powder coated to match hinges. Provide two (2) pulls for drawers over 24" wide. C. Drawer Slide System: ¾ extension drawer runners shall be powder coated, cold roll steel, featuring a captive roller system with in and out stop and out position keeper. Drawer runners shall be side and bottom mount with 100 lb. load rating per BHMA, BIFMA test procedure. D. Door Catches: Provide two (2), top and bottom. Dual, self-aligning magnetic catch. E. Elbow Catches: Brass with latch held by coiled compressing spring. Catch plates of 16 gauge plated steel. F. Slam Latch: Supplied on tall cases with double doors where locks are specified, 4-5/8" bevel slide bolt with 2-1/4 lb./in. actuated spring. G. Leg Shoes: Molded vinyl or rubber, black, coved bottom type to match radius of base molding. H. Glass: Type I, Class I, float glass. I. Locks: Lock is laboratory grade, cylinder cam lock, with 5-disc tumbler mechanism, and a dull chrome-plated face. Tumblers and keys are brass, while plug and cylinder are die cast zinc alloy. There are 500 key changes standard. 8 Locks are keyed differently, master-keyed and furnished with 2 keys per lock. Lock is equipped with RemovaCoreTM keying control. If needed, with the use of a control key, the key core of the lock assembly can be removed and a new key core inserted, changing the entire locking system in a matter of minutes. Locks are provided only when specifically shown on drawings, equipment list, or indicated by catalog number. 2.03 J. Sliding Doors - (Frameless Glass) - .218" thick float plate glass with seamed edges. Operate on metal track applied at top and bottom front horizontal rails of cabinet. Doors easily removable for cleaning. Locks, when indicated, showcase type. K. Sliding Doors - (Framed Glass/Wood Tall Cases) - operate in overhead metal track with ball bearing rollers and nylon wheels. Plastic tracks applied to bottom and sized to allow cleaning space at each end. Locks, when indicated, plunger bolt type. L. Sliding Doors - (Framed Glass/Wood Wall Cases) - operate in overhead plastic track. Plastic tracks applied to bottom and sized to allow cleaning space at each end. Locks, when indicated, plunger bolt type. M. Tote Tray - High impact plastic tray with high gloss. TOPS, SINKS, AND ACCESSORIES A. General 1. Comply with physical and chemical resistance requirements for materials for tops and sinks as specified herein. 2. Tops: Provide smooth, clean, exposed tops and edges, in uniform plane free of defects. Splash and curbs shall be 4" high x 1" thick, unless otherwise noted on the drawings, and shall be located at the backs of all counter tops. a. B. Top sizes: Furnish tops in maximum practicable lengths, in configuration indicated on the drawings. Counter Tops 1. Shelresin (epoxy resin) - especially blended to produce a high chemical resistant material. Tops shall be one inch (1") thick. Physical and mechanical properties: Tensile strength, psi Compressive strength, psi Flexural strength, psi Hardness, Rockwell "M" Density, gr/cc 9 10,700 PSI 30,600 PSI 12,800 PSI 105 2.03 G/CC C. D. 2. Glass fiber reinforced structural polyester - acid resistant surface coating, semi-gloss sheen, to resist moderate chemicals, solvents, biological stains, heat and moisture. Non-burning when submitted to the ASTM D635 test. POLYESTER OR PLASTIC NOT MEETING THIS TEST FOR NON-BURNING WILL NOT BE ACCEPTABLE. 3. Plastic laminate top - thermosetting plastic laminate sheet 1/16" thick, cemented to underlayment with a highly water resistant resin adhesive. Underlayment shall have smooth surface, free of wood grain or other defects that would "telegraph" through to the top surface. Top shall be edge banded with same material as top, set under edge of top and cemented with a highly water resistant adhesive. Top thickness to be 11/4" unless noted otherwise. Sinks, Troughs, and Service Turrets 1. Shelresin (epoxy resin) - one-piece construction. Sinks to be “drop-in” style with inside corners and bottoms coved for easy cleaning. Epoxy sinks furnished with polypropylene sink outlets. 2. Glass fiber reinforced structural polyester - one-piece formed construction 3/4" radius on all exterior surfaces. Acid resistant surface coating, semigloss sheen, to resist moderate chemicals, solvents, biological stains, heat and moisture. Non-burning when submitted to the ASTM D-635 test. (Bidder must furnish notarized certificate that polyester or plastic material furnished meets this test.) Laboratory Service Fixtures and Fittings 1. Vandal-Resistant Fittings. Provide Vandal- Resistant Faucets and Fittings specifically designed to prevent student damage and provide extra protection from student vandalism. All Service Fittings shall conform to SEFA 7-2010, Recommended Practices for Laboratory Service Fittings, Para 14.0 - 14.3 for Vandal Resistant Fittings. Each fitting shall resist turning, bending, breakage, and unintended disassembly through acts of vandalism or physical abuse. Vandal- Resistant Construction features shall include: All threaded connections that will not require field service shall be secured with a suitable adhesive so as to be non-removable. 10 All Goosenecks and spouts shall be constructed of heavy duty pipe or tubing that is sufficient to resist bending and breakage. Faucet bodies and turret bases shall be provided with locking pins or other means to prevent the fixture from being turned on the work surface. Outlet fittings (such as aerators or serrated hose ends) shall either be of Vandal-Resistant design or shall be secured in place with an adhesive. Index buttons shall be tamperproof. Water fittings provided with serrated hose ends shall be furnished with vacuum breakers to prevent contamination of the potable water system through backflow or back-siphonage. Fittings for laboratory gases shall be furnished with ball valves. Water fittings shall have valve packing nuts secured with set screws. Integral Vacuum Breaker covers shall be secured with screws that may be removed only by maintenance personnel. 2. Gas Fixtures. Provide gas fittings in multiple service faucets, deck mounted turrets, or panel mounted flanges with ball valve, forged brass lever handle, nonremovable serrated hose end, and color coded index button. Provide ball valve with chrome plated ball and PTFE seals. Handle shall require no more than 5 ft-lbf to operate. Valve is factory tested at 125 PSI. Maximum working pressure is 75 PS. 3. Water Faucets and Valves. Provide units that comply with SEFA 7 - 2010, Laboratory Service Fittings - Recommended Practices, and also complying with ANSI/ASME A112.18.1 - 2005 and certified by CSA International under CAN/CSA B.125.1 - 05. Provide units fabricated from cast or forged red brass unless otherwise indicated. Provide fittings complete with threaded mounting shanks, locknuts, and washers. Include necessary flanges, escutcheons, extension rods, etc. Provide units complying with ADA accessible requirements where indicated on Drawings or Equipment List. One Faucet shall be provided with 4" wrist-blade handles at ADA sinks. 11 All Water faucets shall be provided with Aerators unless specifically noted to have Serrated Hose Ends. If Serrated Hose Ends are required on Water Faucets, provide unit with Vacuum Breaker. Water Faucets shall have self-contained renewable compression valve units with stainless steel valve seats. Compression unit valve stem shall be sealed with molded TFE stem packing to prevent leakage. Provide color coded index buttons. 4. Quality Assurance All water faucets and gas fixtures shall be fully assembled and factory tested prior to shipment. 5. All Water and Gas Service Fixtures shall have Black Powder Coat Epoxy Finish. 6. Multiple Service Water/Gas Fixture Combination Faucets. Sheldon Unicast Faucet No. 80020 Combination Cold Water/Gas Fixture with Aerator Black powder coat epoxy finish Color coded Nylon Handles for cold water Vandal- Resistant Sheldon Unimix Faucet No. 80030 Combination Hot Water/Cold Water /Gas Fixture with Aerator Black powder coat epoxy finish Color coded Nylon Handles for hot and cold water Vandal-Resistant Approved Equal Watersaver Faucet Co. No. VR5300WSA Combination Cold Water/Gas Fixture with Aerator Black powder coat epoxy finish Color coded Nylon Handles for cold water Vandal-Resistant Watersaver Faucet Co. No. VR5800WSA Combination Hot Water/Cold Water/Gas Fixture with Aerator 12 E. Black powder coat epoxy finish Color coded Nylon Handles for hot and cold water Vandal-Resistant Drain Fittings 1. Sink Fittings Sinks shall be provided with 1-1/2" Dia. x 3" threaded Polypropylene Sink Outlet with Locknut, Removable Disc Strainer, and Sink Stopper. F. 2.04 Electrical Fixtures 1. Electrical Fixtures that are a part of, or installed in the Lab Equipment shall be approved by the National Board of Underwriters and must conform to City and State Building Codes. 2. Knock-out Boxes when indicated, shall be installed in the Lab Equipment. 3. Receptacles shall be grounded type, 20-amp heavy-duty industrial grade. TECHNICAL PRODUCTS A. General 1. The following Equipment List is provided to accurately describe specific Technical Products shown on the Drawings and Equipment List PART 3 EXECUTION 3.01 COORDINATION The casework contractor shall coordinate all deliveries and installation of this equipment with the General Contractor and associated trades. A. Lab casework shall not be delivered to the jobsite until the following conditions have occurred. 1. Overhead ceiling work - ductwork, lighting, acoustical ceiling, etc. is complete. 2. Windows and exterior doors are installed. Building is secure and weather tight. 13 3. B. 3.02 3.03 Air circulation control system is functioning and maintaining relatively constant temperature and humidity conditions closely approximating those to be maintained by the Owner. It is recommended that all painting be completed in the areas in which casework is to be installed prior to such installation. CABINET INSTALLATION A. The casework shall be delivered to the building in prefinished modular units. It shall be set in place, leveled, secured to walls or floors as necessary, trimmed or scribed to make a neat installation. Installation shall be under the direction of a factory approved superintendent. B. Provide filler panels where required to close spaces between casework and walls. C. The casework contractor shall deliver to the appropriate contractor all sinks, troughs, service fixtures, etc., as supplied in this section, for installation and connection by the appropriate trades. CLEANING AND PROTECTION A. Remove all debris, dirt, rubbish and excess material accumulated as a result of the installation of this equipment and leave casework clean and orderly. B. Advise contractor of procedures for protection of installed material from damage from work of other trades. 14