SECTION 26 09 00
INSTRUMENTATION AND CONTROL FOR ELECTRICAL SYSTEMS
[ALTERNATE] SECTION 23 09 00
INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS
Copyright 2011 – EnOcean Inc.
Section number and title complies with the Construction Specifications Institute’s (CSI’s) MasterFormat™.
Specification format conforms to recommendations in CSI’s SectionFormat™ and PageFormat™.
This guide specification section is intended to specify products that incorporate wireless devices manufactured by
EnOcean.
This guide specification will require appropriate evaluation by licensed design professionals. It is not intended to
serve as a replacement for the engagement of a registered professional, and should be used only by those
professional individuals competent enough to understand the significance and limitations of the devices and systems
specified. EnOcean Inc. or the EnOcean Alliance assume no liability, expressed or implied, resulting from the use of
this guide specification.
Visit the EnOcean (www.enocean.com) and the EnOcean Alliance (www.enocean-alliance.org) websites for latest
information. Email support: CSI-spec@enocean.com
PART 1 GENERAL
1.01 SUMMARY
A.
Section Includes: Self-powered wireless electrical devices including the following:
1. Switches.
2. Sensors.
3. Actuators, Relays and controllers.
4. Gateway systems.
1.02 DEFINITIONS
Note to Specifier: Retain definitions that are used in the specification text.
A.
BACnet: Building automation and controls network.
B.
DMX: Digital multiplex.
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 1
[Project No.]
[Date]
[Project Name]
[Project Location]
C.
IP: Internet protocol.
D.
VAV: Variable air volume.
1.03 ADMINISTRATIVE REQUIREMENTS
A.
Sequencing: Install wireless devices following or in conjunction with installation of electrical devices.
1.04 ACTION SUBMITTALS
A.
Product Data: Manufacturer’s printed literature describing devices system and components.
B.
Shop Drawings: Include the following:
1. Schematic of system.
2. Floor plans indicating locations of devices.
3. Schedule of devices using designations indicated in Drawings and Specifications.
1.05 INFORMATIONAL SUBMITTALS
A.
Qualification Statement: For installer.
B.
Field quality-control reports.
1.06 CLOSEOUT SUBMITTALS
A.
Operation and Maintenance Data: To include in operation and maintenance manuals. Include the
following:
1. Schematic of installed system.
2. User’s manuals for each device.
1.07 QUALITY ASSURANCE
A.
Radio Certification:
1. FCC Certified for wireless communication complying with FCC Part 15 [Class A] [or] [Class B].
Note to Specifier: Paragraph above is for applications in the United States. Class A devices are for commercial,
industrial, or business applications. Class B devices are generally for residential applications but may be used in
commercial, industrial, and business applications. Paragraph below is for applications in Canada.
2. I.C. Certified.
B.
Electrical Devices: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked
for intended location and application.
C.
Installer Qualifications: Installer should be a qualified electrician, Installation and Range Planning
Guidelines can be found at www.enocean.com.
1.08 FIELD CONDITIONS
A.
Install devices only when ambient air temperature can be maintained between 32 and 104 deg F (0 and
40 deg C).
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 2
[Project No.]
[Date]
[Project Name]
[Project Location]
1.09 WARRANTY
A.
Manufacturer’s Warranty: Standard limited warranty where manufacturer agrees to repair or replace
devices that fail in material or workmanship for the warranty period.
1. Warranty Period: [5] <Insert period> years.
PART 2 PRODUCTS
2.01 PERFORMANCE
A.
Provide radio frequency, wireless devices that are self-powered [and do not require the use of
batteries] [, but may use batteries for backup] [, and may have low voltage power for continuous
operation].
Note to Specifier: Retain 315 MHz for installations in the United States. For installations in Canada, retain either
315 MHz or 868 MHz, or retain both for contractor’s option.
1. Frequency Band: [315 MHz] [or] [868 MHz].
2. Range: [75 feet typical] <Insert range>
3. Material Range reduction vs. Line of Sight
Wood; plaster, glass uncoated, without metal
0 - 10%
Brick, press board
5 - 35%
Ferro concrete
10 - 90%
B.
Provide devices that are compatible with each other.
2.02 SWITCHES
Note to Specifier: If more than one type of lighting switch is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule.
A.
Switch <Insert type designator>: Switch [receiver] [transmitter] to control [lighting] [and] [HVAC]
systems.
Note to Specifier: Select one of the following switch types. Generally, switches for HVAC systems is limited to
rocker, key card, and handheld remote types. Only Echoflex Solutions provides a hospital bed-type switch. Retain
last option if dimming is required.
1. Type: [Rocker] [Pushbutton] [Key card] [Handheld remote] [Hospital bed] [with dimming
feature].
a. Number of Rockers: [Single, Euro Style] [Double, Euro Style] [1-gang, Decora/Decorator
Style] [2-gang, Decora/Decorator Style] [3-gang, Decora/Decorator Style].
Note to Specifier: Retain paragraph above and delete paragraph below for rocker-type switches and select the
number of rockers provided with the device. Retain paragraph below and delete paragraph above for pushbuttonand handheld remote-type switches and select the number of pushbuttons provided with the device.
b. Number of Pushbuttons: [One] [Two] [Four].
Note to Specifier: Not all lighting switches are available in the colors listed in the paragraph below. Check with
manufacturers’ product data to determine available color selections.
2. Color: [White] [Silver] [Almond] [Light almond] [Ivory] [Gray] [Black].
Note to Specifier: Only ILLUMRA and Leviton indicate they provide anti-theft, tamper resistant switches.
3. Mounting: [Electrical box] [Surface-mounted plate].
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 3
[Project No.]
[Date]
[Project Name]
[Project Location]
Note to Specifier: Only Dimonoff, Echoflex Solutions, ILLUMRA, and Magnum Energy Solutions indicate they
provide switches for HVAC systems.
4. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
5. Manufacturers:
a. Dimonoff.
b. Distech Controls.
c. Echoflex Solutions.
d. Functional Devices
e. ILLUMRA.
f.
Leviton.
g. Magnum Energy Solutions
h. Verve Living Systems.
2.03 SENSORS
Note to Specifier: If more than one type of temperature sensor is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule.
A.
Temperature[ and Humidity] Sensor <Insert type designator>: Solar powered[ with battery back-up]
[with setpoint adjustment] [for ductwork] [for surface temperature monitoring].
1. Location: [Indoor] [Outdoor].
2. Temperature Monitor Range: [32 to 100 deg F (0 to 40 deg C)] <Insert range>.
Note to Specifier: Delete paragraph and subparagraph below if setpoint adjustment is not a requirement.
3. Temperature Setpoint Range: [60 to 85 deg F (15 to 30 deg C)] <Insert range>.
a. Control: [Pushbutton] [Dial].
Note to Specifier: Typically, the first range option in the paragraph below is for indoor applications and the second
range option is for outdoor applications.
4. Transmission Range: 75 feet typical].
5. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
6. Manufacturers:
a. Distech Controls.
b. Echoflex Solutions.
c. ILLUMRA.
d. Leviton.
e. Magnum Energy Solutions.
f.
Reliable Controls.
g. Verve Living Systems.
Note to Specifier: If more than one type of occupancy sensor is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule.
B.
Occupancy Sensor <Insert type designator>: Solar-powered with a minimum of 48 hours of stored
power. [Provide unit with battery backup for uninterrupted operation.]
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 4
[Project No.]
[Date]
[Project Name]
[Project Location]
Note to Specifier: Room-type sensors provide 360 degrees of detection. Hallway-type sensors provide detection in
two directions. Only Verve Living Systems provides a hallway-type sensor.
1. Type: [Room] [Hallway].
2. Modes: [Auto-ON/Auto-OFF] [and] [Manual-ON/Auto-OFF].
3. Mounting: [Wall] [Ceiling].
Note to Specifier: Typically, the first range option in the paragraph below is for indoor applications and the second
range option is for outdoor applications.
4. Transmission Range: 75 feet typical
Note to Specifier: First three options are for room sensors. The last option is for hallway sensors.
5. Coverage: Minimum [450 sq. ft.] [1500 sq. ft.] [32 feet in each direction up to a height of 5 feet.]
6. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
7. Manufacturers:
a. Distech Controls.
b. Echoflex Solutions.
c. ILLUMRA.
d. Leviton.
e. Magnum Energy Solutions.
f.
Verve Living Systems.
Note to Specifier: If more than one type of light sensor is required, copy and paste paragraph and subparagraphs
below and provide a type designator that is used on the drawings or in a schedule.
C.
Light Sensor <Insert type designator>: Solar-powered with up to 8 hours of stored power.
1. Location: [Indoor] [Outdoor].
2. Measurable Light Range: [0 to 47 footcandles (0 to 512 lux)] [0 to 94 footcandles (0 to 1024 lux)]
<Insert range>.
Note to Specifier: Typically, the first range option in the paragraph below is for indoor applications and the second
range option is for outdoor applications.
3. Transmission Range: 75 feet typical
Note to Specifier: Paragraph below is only available with ILLUMRA light sensor.
4. Options: Ethernet antenna.
5. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
6. Manufacturers:
a. Distech Controls.
b. Echoflex Solutions.
c. ILLUMRA.
d. Magnum Energy Solutions.
Note to Specifier: If more than one type of position sensor is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule.
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 5
[Project No.]
[Date]
D.
[Project Name]
[Project Location]
Position Sensor <Insert type designator>: Two-piece unit consisting of contact switch and magnet for
use on [doors] [and] [windows]. Solar-powered with a minimum of 24 hours of stored power.
1. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
2. Manufacturers:
a. Distech Controls.
b. Echoflex Solutions.
c. Functional Devices
d. ILLUMRA.
e. Magnum Energy Solutions.
f.
Verve Living Systems.
Note to Specifier: If more than one type of position/temperature sensor is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule.
E.
Position/Temperature Sensor <Insert type designator>: Two-piece unit consisting of contact switch
and magnet for use on [doors] [and] [windows] with integrated temperature sensor.
1. Temperature Monitor Range: [32 to 100 deg F (0 to 40 deg C)] <Insert range>.
2. Temperature Setpoint Range: [60 to 85 deg F (15 to 30 deg C)] <Insert range>.
3. Manufacturer: Echoflex Solutions.
F.
Voltage Sensor: Detects presence of voltage.
1. Voltage [AC][DC]
2. Manufacturers:
a. Functional Devices
b. ILLUMRA
c. Leviton
G.
Current Sensor. Detects presence of current
1. Current [Amps]
2. Manufacturers:
a. Functional Devices
2.04 ACTUATORS AND CONTROLLERS
Note to Specifier: If more than one type of receiver actuator is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule.
Most actuators control electrical devices; however, ILLUMRA, Magnum Energy Solutions, and Spartan Peripheral
Devices provide actuators that control flow valves of radiators for hot water and steam heating systems.
A.
Actuator, Receiver <Insert type designator>: Wireless relay receiver to control [an electrical device]
[a valve] and respond up to [30] <Insert number> transmitters.
Note to Specifier: Retain paragraph below if actuator operates a valve and two-way communication is required.
Only Spartan Peripheral Devices provides valve actuators with two-way communication.
1. Provide actuator with two-way communication providing feedback on position and temperature.
Note to Specifier: The first option in paragraph below is used primarily for limited lighting or other small electrical
loads. The second option is for motor or large lighting loads. Plug-in types plug into an installed receptacle. DMX
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 6
[Project No.]
[Date]
[Project Name]
[Project Location]
types are used for theatrical and architectural lighting systems. Retain last option if the actuator is required to have
dimming capability; verify capability with manufacturers’ products. Delete paragraph if actuator controls a valve.
2. Type: [3-wire] [5-wire] [Plug-in] [1-channel] [2-channel] [4-channel] [8-channel] [Power Strip]
[DMX interface] [Transformer] [with dimming capability].
Note to Specifier: Retain 347VAC option only for applications in Canada. Retain battery-operated option for valve
actuators.
3. Power Supply: [9 to 24VDC] [24VAC] [110 to 125VAC] [120VAC] [240VAC] [277VAC] [347VAC]
[Battery-operated].
Note to Specifier: Retain paragraph below for transformer-type actuators.
4. Power Output: 24VDC.
Note to Specifier: Retain paragraph below for dimmable controllers.
5. Dimming Control: For [light fixtures] [fluorescent ballasts] [and] [LED power supplies].
6. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, to dim LEDs, or
0~10V dimming of fluorescent lights, or a comparable product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
7. Manufacturers:
a. Dimonoff.
b. Echoflex Solutions.
c. Functional Devices, Inc.
d. ILLUMRA.
e. Leviton.
f.
Magnum Energy Solutions.
g. Spartan Peripheral Devices.
Note to Specifier: If more than one type of transmitter actuator is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule.
B.
Actuator, Transmitter <Insert type designator>: Wireless switch leg transmitter to control [a single]
[multiple] electrical device[s].
1. Power Supply: [24VAC] [120VAC] [8 to 28 VDC] [240VAC][277VAC]
2. Channels: [One] [Four].
3. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
4. Manufacturers:
a. ILLUMRA.
b. Leviton.
c. Magnum Energy Solutions.
C.
Transmitter with Dry Contact Input and Voltage Control Input to control control [a single] [multiple]
electrical device[s].
1. Power supply: 24Vac/dc, 50-60 Hz
2. Control Input: 5-25 Vac/dc
3. Manfacturers:
a. Functional Devices
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 7
[Project No.]
[Date]
[Project Name]
[Project Location]
Note to Specifier: If more than one type of controller is required, copy and paste paragraph and subparagraphs
below and provide a type designator that is used on the drawings or in a schedule. A relay receiver will receive a
signal from a transmitter and control multiple devices using existing wiring. A transceiver will receive a signal from a
transmitter and transmit signals to multiple receivers actuators for electrical devices.
D.
Controller <Insert type designator>: Wireless [relay receiver] [transceiver] to control multiple
electrical devices.
Note to Specifier: Room controllers provide manual and automatic control for a variety of electrical devices, such
as lights, ceiling fans, and security panels. Shade controllers provide manual or automatic control for motorized
window shades, blinds, and other coverings. Tabletop controllers are portable units
1. Type: [Room] [Shade] [Tabletop].
2. Power Supply: [8 to 28VAC] [8 to 30VDC] [120VAC] [240VAC] [277VAC] [347VAC].
Note to Specifier: Retain paragraph below if controller is required to transform high voltage to low voltage to power
peripheral devices, such as occupancy sensors.
3. Power Output: 24VDC.
Note to Specifier: Retain paragraph below if more than one circuit is controlled by unit.
4. Channels: [Two] [Three] [Four] [Eight] [Ten].
5. Transmitter IDs: [30] <Insert number>
6. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
7. Manufacturers:
a. Dimonoff.
b. Echoflex Solutions.
c. Functional Devices
d. ILLUMRA
e. Leviton.
f.
Magnum Energy Solutions.
g. Verve Living Systems.
Note to Specifier: If more than one type of control panel is required, copy and paste paragraph and subparagraphs
below and provide a type designator that is used on the drawings or in a schedule.
2.05 GATEWAY SYSTEMS
Note to Specifier: If more than one type of controller/gateway is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule. Retain actuator
option for units that provide direct actuation of VAV.
A.
Gateway/[Actuator/]Controller <Insert type designator>: Wireless transceiver to control multiple
electrical devices with embedded gateway to Building Automation Systems such as BACnet , LONworks
, MS/TP, KNX, etc..
1. Type: [Room] [and] [VAV].
2. Power Supply: [24VAC] [24VDC].
3. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 8
[Project No.]
[Date]
[Project Name]
[Project Location]
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
4. Manufacturers:
a. Beckhoff Automation.
b. CAN2GO.
c. Distech Controls.
d. Magnum Energy Solutions.
e. Reliable Controls.
Note to Specifier: If more than one type of receiver is required, copy and paste paragraph and subparagraphs
below and provide a type designator that is used on the drawings or in a schedule.
Lighting Control and Design provides units that link to a control panel. Reliable Controls provides units that link to a
gateway/controller. Magnum Energy Solutions offers unlimited addressable access point.
B.
Receiver <Insert type designator>: Wireless unit that accepts addresses from up to [14] [18] [30]
<Insert number> transmitters and links with [control panel] [or] [gateway] using [RJ11] [RJ45] [or]
[RS-232 serial] connectors.
1. Power Supply: [8 to 28VAC] [8 to 30VDC].
2. Basis-of-Design Product: Provide <Insert product> by <Insert manufacturer>, or a comparable
product by one of the following manufacturers:
Note to Specifier: Retain either paragraph above or below. Use the “Basis-of-Design” paragraph when the design
is based on a specific product.
3. Manufacturers:
a. ILLUMRA.
b. Leviton.
c. Magnum Energy Solutions.
d. Reliable Controls.
2.06 ACCESSORIES
Note to Specifier: If more than one type of data interface is required, copy and paste paragraph and subparagraphs
below and provide a type designator that is used on the drawings or in a schedule.
A.
Data Interface <Insert type designator>: Wireless unit that transmits and receives signals to wireless
devices and links with computer using industry standard protocols such as RS-232/485 serial, TCP/IP,
BACnet, LON, KNX, Modbus, etc..
1. Power Supply: [8 to 28VAC] [8 to 30VDC] [24VAC] [120VAC] [240VAC] [277VAC].
2. Manufacturer: ILLUMRA, Leviton, Magnum Energy Solutions.
Note to Specifier: If more than one type of repeater is required, copy and paste paragraph and subparagraphs
below and provide a type designator that is used on the drawings or in a schedule.
B.
Repeater <Insert type designator>: Wired unit that [repeats] [amplifies] signal for out-of-range
sensors and switches.
Note to Specifier: Retain 120/347VAC option only for applications in Canada.
1. Power Supply: [24VAC] [120/277VAC] [240VAC] [8-28VDC] [120/347VAC].
2. Manufacturer: Distech Controls, ILLUMRA, Leviton.
Note to Specifier: If more than one type of transmitting power pack is required, copy and paste paragraph and
subparagraphs below and provide a type designator that is used on the drawings or in a schedule.
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 9
[Project No.]
[Date]
[Project Name]
[Project Location]
C. Transmitting Power Pack <Insert type designator>: Wired unit that transmits wireless signal on contact closure
status of a low voltage sensor or switch.
Note to Specifier: Retain 347VAC option only for applications in Canada.
3. Power Supply: [24VAC] [120VAC] [277VAC] [347VAC] [240VAC] [8-28VDC].
4. Power Output: [24VAC] [120VAC] [277VAC] [347VAC] [240VAC] [8-28VDC].
5. Manufacturer: Echoflex Solutions, ILLUMRA, Leviton
Note to Specifier: If more than one type of power pack is required, copy and paste paragraph and subparagraphs
below and provide a type designator that is used on the drawings or in a schedule.
C.
Power Pack <Insert type designator>: Wired transformer and relay unit that supplies low voltage power
to sensor, and controls an electrical load[ and slave Relay Packs].
Note to Specifier: Retain 347VAC option only for applications in Canada.
1. Power Supply: [120VAC] [277VAC] [347VAC].
2. Power Output: 24VDC
3. Manufacturer: ILLUMRA.
Note to Specifier: If more than one type of power pack is required, copy and paste paragraph and subparagraphs
below and provide a type designator that is used on the drawings or in a schedule.
E. Relay Pack <Insert type designator>: Wired relay unit that controls an electrical load triggered by signal from
Power Pack.
4. Power Supply: 24VDC
5. Manufacturer: ILLUMRA, Magnum Energy Solutions
D.
Software <Insert type designator>: Software operating on a PC, tablet, phone or handheld device
providing control and monitoring of Home or Commercial Building Automation, Energy Dashboard, Load
Shedding and Demand Response
1. Manufacturer: Magnum Energy Solutions
PART 3 EXECUTION
3.01 EXAMINATION
Note to Specifier: Delete this Article if flush-mounted control panels are not used.
A.
Examine walls and partitions where flush-mounted enclosures will be installed.
Note to Specifier: Retain paragraph below if self-powered devices are specified. If light levels are not sufficient,
then devices will not function properly in periods of darkness.
B.
Examine locations where self-powered devices are indicated to be installed and check ambient light
levels. Notify Architect if light levels are below manufacturer’s recommendations.
C.
Examine locations where radio-frequency devices are indicated to be installed using manufacturer’s field
intensity meter to test for signal strength. If range is insufficient, enable repeaters, or move devices to
closer locations. Installation and Range Planning Guidelines can be found at www.enocean.com.
1. Annotate Record Drawings with new locations if location of devices are modified due to radiofrequency strength.
EnOcean Alliance
[Author]
[File Name]
Instrumentation and Control for
Electrical Systems
26 09 00 - 10
[Project No.]
[Date]
[Project Name]
[Project Location]
3.02 INSTALLATION, GENERAL
A.
Install accessories in accordance with manufacturer’s printed instructions.
B.
Program devices to properly receive or transmit signals to other devices
3.03 DEVICE INSTALLATION
A.
Switch Installation:
1. Install switches in recessed boxes or on surface-mounted plates as indicated on Drawings.
Note to Specifier: Retain paragraph below if devices are not provided with cover plates. Delete option and insert
another section if cover plates are specified in a different section,
2. Install matching, non-metallic cover plates as specified in [Section 26 27 26 “Wiring Devices.”]
<Insert section number and title.>
B.
Sensor Installation:
1. [Position] [and] [Position/Temperature] Sensor Installation: Attach sensor to door or window using
[double-sided tape] [mounting plate and screws]. Place magnet in correct orientation, alignment,
and spacing with contact switch according to manufacturer’s instruction to ensure proper operation.
2. Occupancy Sensors: Attach sensor to wall or ceiling as indicated on Drawings.
a. Wall-Mounted Sensors: mount per manufacturer’s printed instructions <Insert height>.
C.
Gateway System Installation:
1. Link peripheral devices to gateway/controller.
2. Connect gateway/controller to building automation system.
Note to Specifier: Retain paragraph below if some devices require electrical power. Delete option and insert
another section if electrical wiring is specified in a different section,
D.
Connect devices requiring power supply to building electrical system as specified in [Section 26 05 23
“Low-Voltage Electrical Power Conductors and Cables.”] <Insert section number and title.>
3.04 FIELD QUALITY CONTROL
A.
Operational Tests: Ensure that each component operates properly.
1. Verify radio frequency strengths at installed locations of devices.
2.
Test actuators to ensure operations comply with manufacturer’s stated ranges.
B.
Components will be considered defective if they do not pass tests.
C.
Prepare test report.
3.05 ADJUSTING
A.
Adjust [light] [and] [occupancy] sensors to provide coverage of areas required for proper operation.
3.06 DEMONSTRATION
A.
Train Owner’s maintenance personnel to operate devices and to properly program components.
END OF SECTION