Volume 2 - Design Criteria

advertisement
Greenbank Leisure Centre, Swadlincote
PERFORMANCE SPECIFICATION
FOR
BUILDING SERVICES INSTALLATIONS
Volume 1 – Design Criteria
Prepared by
Yorkshire Building Services Ltd
Martin Street
Birstall,
Batley,
West Yorkshire,
WF17 9PJ.
Tel: 01924 471955
andy.sutcliffe@ybsltd.co.uk
Issue 1 – 28th June 2013
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Issue Record Sheet
Issue/revision
Issue 0
Revision 1
Remarks
Date
28th June 2013
Prepared by
A. Sutcliffe
Signature
Checked by
Signature
Authorised by
Signature
Project number
File reference
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Revision 2
Revision 3
Design Team
Client
Active Nation
Address
Quatro House,
Lyon Way,
Frimley Road,
Camberley,
Surrey,
GU16
Tel:
01283 216269
Contact:
John Oxley
Project Managers/ PQS
TBC
Address
Tel:
Contact:
Architect
-
Hadfield Cawkwell Davidson
Address
17 Broomgrove Road,
Sheffield,
S10 2LZ
Tel:
0114 2668181
Contact:
Mathew Bradbury
Structural Engineer –
TBC
Address
Tel:
Contact:
M&E Consulting Engineer – Yorkshire Building Services
Address
Martin Street,
Birstall,
Batley,
West Yorks, WF17 9PJ
Tel:
01924 471955
Contact:
Andy Sutcliffe
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Notes for Tenderers
This series of documents are issued for the Contractor to prepare the Mechanical & Electrical Designs for the
Project
The series of documents comprises the following:Volume 1
-
Contract Preliminaries
Volume 2
-
Design Criteria
Volume 3
-
Workmanship & Materials
This documentation must be read in conjunction with all other tender documentation – including, but not limited
to:Architects Outline Specification
Architects Drawings
Structural Engineers Drawings & Specifications
All Documents referred to in the above documents
The Room Data Sheets Document
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Introduction
The building, which is already in existence, was initially opened in 1978 as a leisure centre provided by the local
council to the people of the community.
The building was originally built in the 1977/78 and has undergone various extensions and refurbishments in a bid
to maintain the services to the community. One of the most recent areas of refurbishment which the centre has
undergone is that of the wet changing areas.
The proposal is to renovate the areas identified within the layout drawings including a variety of strip outs,
changes of use and refurbishments throughout the entire of the leisure centre. This will also involve a variety of
stripping out, reusing and replacing the existing building services to the areas which will be affected as part of the
refurbishment. The details of the mechanical and electrical installation are detailed in this series of documents.
The centre is currently serviced with electricity, gas & water; it is not envisaged that these need to be upgraded as
part of the scope of this project; however pressure checks of the incoming water main should be carried out to
confirm sufficient is available to cope with any additional load incurred by these works. The contractor must make
allowances within their tender for main cold water boosting if their design calculations find this to be required to
achieve sufficient water pressure throughout.
Allowances must be made for the inspection and making safe of all existing services within areas that are to be
affected to ensure that services comply with latest industry codes of practice even in instances where services
affected run out of the demise of the planned works. These include BS7671 2008 17th Edition Wiring Regulations
and ACOP Gas Safety Regulations 1998.
The tender should include for all costs in this respect. The contractor must visit site to establish the extent of the
strip-out. No claims for additional monies in this respect will be considered.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
CONTENTS
1.01
1.02
1.03
1.04
1.05
1.06
1.07
1.08
1.09
1.10
1.11
1.12
1.13
1.14
1.15
INTRODUCTION
GENERAL DESCRIPTION
DESIGN
DRAWINGS
CO-ORDINATION
DRAWING SCHEDULE
VISITING SITE
PROGRAMMING THE WORKS
COMMISSIONING
BUILDERSWORK
CONSTRUCTION DESIGN & MANAGEMENT REGULATIONS
PART L BUILDING REGULATIONS
STAFF TRAINING
STANDARDS OF WORKMANSHIP
EXISTING EXTERNAL SERVICES
ELECTRICAL INSTALLATION
2.01
2.02
2.03
2.04
2.05
2.06
2.07
2.08
2.09
2.10
2.11
2.12
2.13
2.14
2.15
2.16
INFRASTRUCTURE
LV DISTRIBUTION
UNDERFLOOR DUCTING
EARTHING AND BONDING INSTALLATION
LIGHTNING PROTECTION INSTALLATION
GENERAL LOW VOLTAGE POWER INSTALLATION
GENERAL LIGHTING INSTALLATION
EMERGENCY LIGHTING INSTALLATION
FIRE ALARM INSTALLATION
DISABLED CALL SYSTEMS
SPECIALIST SYSTEMS
TELEPHONE MAINS (Incoming)
TELEPHONE INSTALLATION
TV AERIALS
DATA SYSTEMS
CCTV INTRUDER SYSTEMS
MECHANICAL INSTALLATION
3.01
3.02
3.03
3.04
3.05
3.06
3.07
3.08
DESIGN PARAMETERS
SYSTEM DESCRIPTIONS
DOMESTIC WATER SERVICES
GAS MAIN SUPPLY
DUCTWORK INSTALLATION
HVAC CONTROLS
MISCELLANEOUS MECHANICAL VENTILATION
KITCHEN AREA VENTILATION & GAS SUPPLIES
3.09
3.10
POWER SUPPLIES TO MECHANICAL PLANT
ABOVE GROUND DRAINAGE
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
GENERAL
4.01
4.02
TESTING AND COMMISSIONING
AS FITTED DRAWINGS AND OPERATING MANUALS
DRAWINGS
A-04-100_Existing Floor Plan
A-04-110_Proposed Floor Plan
A-35-100_Existing Ceiling Plan
A-35-110_Proposed Ceiling Plan
A-35-111_Proposed Ceiling Details
A-67-100_Existing Fire Strategy Plan
A-67-110_Proposed Fire Strategy Plan
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
1.01
INTRODUCTION
The contractor shall be responsible for carrying out the electrical & mechanical services design
and installation in accordance with this performance specification.
The contractor shall install a fully co-ordinated services installation which meets the
requirements of this performance specification and is in accordance with all current statutory
regulations and codes of practice in particular the following:The IEE Wiring Regulations - 17thEdition Requirements for Electrical Installations BS7671:
The British Standard Specifications and Codes of Practice.
The Electricity at Work Regulations 1989.
The Electricity Supply Regulations 1988.
The Factories Act 1961.
Local Authority By-Laws and Regulations, including Local Petroleum Licensing Regulations
issued by the Local Fire or Petroleum Client.
The Health and Safety at Work Act 1974 and subsequent amendments.
The Control of Substances Hazardous to Health Regulations 1988.
The Consumer Protection Act 1987.
The Management of Health and Safety at Work Regulations 1992.
The Provision and Use of Work Equipment Regulations 1992.
The Workplace (Health, Safety and Welfare) Regulations 1992.
The Manual Handling Operations Regulations 1992.
Regulations and Requirements of the Electricity Supply Authority.
The Construction (Design and Management) Regulations 1994 and current amendments.
Year 2000 Compliance
The Building Regulations and all current amendments.
The Chartered Institute of Building Services Guides All current Volumes.
Control of Legionella in Health Care Premises – A Code of Practice
The clauses contained in this section of the specification shall be read in conjunction with the
Volume 3 Workmanship & Materials, of this series of documents and the Architect’s General
Arrangement drawings relating to the works and all NBS specifications.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
1.02
GENERAL DESCRIPTION
The services installation works referred to in this performance specification shall comprise the
complete design, supply, and installation, co-ordination, testing, commissioning and setting to
work including the provision of all handover documentation.
All documentation required for Building Regulation approval, including documentation required
to ascertain compliance with Part L 2006 shall be provided by the contractor.
The details of the construction are detailed on the architect’s drawings and within the NBS
specifications, all of which are issued under separate cover.
Internal room layouts and suspended ceiling details are also as detailed on the architects
drawings and NBS specifications.
All documentation shall be read in conjunction with the any room data sheets issued by the
client.
1.03
DESIGN
The contractor shall carry out all necessary design and drawing work required to ensure the
suitability, compatibility, and correct location within the various systems of components
selected, to meet the requirements of this performance specification.
The contractor shall produce such drawings, calculations and other documents for the detail
design of the works as may be required for examination. The contractor shall agree the location
of all plant and equipment with the client or their appointed representative.
Unless specific written dispensation is given all equipment selected for the works shall be from
reputable manufacturers who are part of a recognised quality assurance scheme.
All equipment selections shall be approved by the client or their appointed representative.
A schedule of proposed equipment suppliers shall be provided with the tender documentation.
Key parameters are given that are to be utilised for the design of each of the elements.
The Designer shall ensure full compliance with any requirements of the Local
Planning Authority and Building Control – The contractor shall be responsible for all
requirements in this respect. The early approval of external plant locations is recommended.
All plant shall be selected for a design life of 15 years.
The designer shall conform to all of the parameters as a minimum, and shall take
responsibility for the final design and selection of all systems.
The designer shall make available the full design for comment by the client and/or their
appointed representative.
The design shall be based on the criteria given and any applicable Building Regulations, British
Standards, CIBSE guidelines etc.
The designer shall utilise an industry standard software package.
A design review will be undertaken; the designers shall make themselves available to attend
all meetings required to attain full scheme approval.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
1.04
DRAWINGS
The contractor shall provide a full package of design information to enable the client and/or
their appointed representative to audit the design including but not limited to:(i) Drawings – Design, Co-ordination & Builderswork
(ii) Specifications and Schedule
(iii) Detail of Equipment Selections and any samples required
(iv) Calculations
The contractor shall issue a ‘Schedule of Design Information’ which shall be agreed with the
appointed representative to ensure the timely issue of design information for approval.
The approval process will be as follows
Status A - No further comment
Status B - Further information required. Information acceptable for installation.
Status C - Information not acceptable. Resubmit information in revised form.
The contractor shall produce complete design and detail drawings, production information,
design calculations and specifications as required. The contractor shall liaise with other
members of the design team to ensure co-ordination of the works with other building elements
and services.
The contractor shall provide 4 no. copies of all design and working drawings. The contractor
shall allow to amend all design and working drawings subject to comment.
The contractor shall provide 4 no. copies of final design and production information
The contractor shall produce all design and production in formation using the latest version of
AUTOCAD.
1.05
CO- ORDINATION
The contractor shall be responsible for the co-ordination of services with all building elements,
structure, all other services and specialist suppliers equipment
The contractor shall provide drawings and sections to demonstrate the co-ordination
detailed above.
1.06
DRAWING SCHEDULES
The contractor shall provide a complete schedule of proposed drawings when requested. The
schedule shall be agreed with the Client or their appointed representative and shall contain
drawing issue dates that shall be agreed and strictly adhered to.
1.07
VISITING SITE
The contractor is advised to visit the site to determine the extent and nature of the works and to
familiarise himself with local conditions and access.
No allowance of any kind will be allowed for matters arising from the contractor’s failure to
visit site.
1.08
PROGRAMMING THE WORKS
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
The Contractor shall compile a programme for carrying out the design and installation of the
works making due allowance for the production and approval of the scheme content, the whole
of which shall be integrated into the overall construction programme.
The programme shall be based on hours of working which is trade practice where applicable.
Should the nature of the work make it necessary for the Contractor to work at premium times in
order to undertake the works without inconvenience to other trades and the Client then he
should allow in his tender for such overtime.
1.09
COMMISSIONING
The Contractor shall provide full commissioning schedules for all installed services prior to
practical completion to ensure all systems are verified. The contractor shall ensure that all
commissioning is witnessed by the clients appointed representative.
1.10
BUILDERSWORK
The contractor shall supply and install all primary and secondary steelwork supports for all
new Plant & Equipment.
The contractor shall allow for lifting all Plant & Equipment into its final locations and for
securing plant to the structure.
The contractor shall provide all builders work necessary in connection with the services
installation, including holes, apertures, recesses and chases.
The contractor shall mark out in advance and shall be responsible for the accuracy and sizes of
all cut out holes and chases required and shall drill and plug all holes for securing services
which require screw or bolt fixing. Builder’s works requirements in sufficient detail to enable
accurate setting out of holes, built-in sleeves and bases shall be identified in advance so that the
exact position can be agreed.
All openings shall be weather sealed, and will be constructed using robust details such that they
do not compromise the ‘sealed building’ requirement.
All access to plant areas e.g. platforms, access ladders, walkways etc, shall be provided by
the Contractor, for future maintenance of engineering plant and in accordance with the
requirements of the CDM Regulations.
All plant areas internal or external to the building shall be provided with maintenance lighting &
emergency lighting.
All plant areas shall also be provided with weatherproof fire alarm call points smoke/heat
detection (where appropriate) and sounders.
1.11
CONSTRUCTION, DESIGN & MANAGEMENT REGULATIONS
All documentation required by the CDM co-ordinator shall be issued in a timely manner, the
Contractor shall include for all requirements in this respect.
1.12
PART L BUILDING REGULATIONS
The new mechanical & electrical installation shall be fully compliant with part L of the building
regulations.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
1.13
STAFF TRAINING
The Contractor shall ensure that the client’s managements nominated facilities maintenance
contractor is trained to operate all systems installed by the contractor.
The contractor shall liaise with the client to establish mutually agreeable dates for training and
shall prepare a document scheduling the system upon which training as been provided, the date
and the names of the personnel trained
The training schedules shall be signed by both parties to confirm an acceptable level of training
as been provided
The contractor shall include for all requirements in this respect.
1.14
STANDARD OF WORKMANSHIP
Materials employed and work carried shall be in accordance with the workmanship & materials
standards document.
1.15
EXISTING EXTERNAL SERVICES
The centre is currently serviced with electricity, gas & water and whilst preliminary unobtrusive
surveys suggest utility service upgrades are unlikely, the contractor must carry out investigative
work to assess that the existing services are sufficient to cope with the demands of the centre
following the refurbishment works. If mains water pressure is found to be insufficient the
contractor must allow for the installation of a boosted system to cope with demand.
The contractor shall be responsible for all costs associated with the modifications to all existing
statutory services in and around the development, necessitated by the works including all
associated builder’s work.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
ELECTRICAL INSTALLATION
2.01
INFRASTRUCTURE
The development is currently served from the Statutory Service Providers local LV
infrastructure. The existing supply is sized at 300A three phase. The local Grove Building
squash courts are served from this building.
It is not anticipated that the refurbishment works will require an increase in the electrical supply.
Electrical Supply Authorities
2.02
Host REC (DNO)
TBC
TBC
2nd Tier Electricity Supplier
TBC
TBC
Meter Operator
TBC
TBC
LV DISTRIBUTION
Existing Installation
From the incoming supply position in the boiler room pit a 185mm 2 4C armored sub main cable
serves the main distribution equipment located in the basement switch room.
The main equipment consists of an eight-way TP&N MCCB panel board with a 400A MCCB
incomer utilizing one of the ways. A newer twelve-way TP&N MCCB mounted directly above
is fed via a multi-core armored cable from a 200A TP&N MCCB in the main panel board.
Additional MCB distribution boards and contactor panels in the basement switch room provide
power supplies and controls to local services. Further MCB distribution boards are located
around the building to serve local equipment and services.
The electrical sub-contractor shall design the cable installation based on the following criteria:-
The Electrical Installation must be designed in accordance with 17 th Edition IEE wiring
Regulations and all Guidance notes.
-
The maximum demand of the installation shall be determined taking into account
diversity where appropriate and used for the sizing of cables and equipment.
-
Volt drop calculations shall be carried out and visually demonstrated to be in accordance
with the 17th Edition wiring regulations.
-
The method shown the 17th Edition IEE Wiring Regulations shall be used to assess the
current carrying capacity and voltage drop for the proposed cable installation.
-
Sub-main cables shall be XLPE/LSF/SWA/LSF and shall be supplied with a CPC, sized
in accordance with BS 7671.
-
Final circuit cables shall be supplied with a CPC, sized in accordance with BS 7671. The
final circuit cables shall have a minimum conductor size of 1.5mm2 for lighting and
2.5mm2 for power.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
-
Particular attention shall be given to ensure discrimination between all "upstream" and
"downstream" protective devices.
-
The Contractor shall provide computer originated reports verifying the cable installation
calculations.
The computer calculations shall be based on using
HEVACOMP/AMTECH or similar.
System Objectives
Generally the existing LV distribution system shall be retained with minor modifications with
the following exceptions:
2.03
2.02.1:
The existing sub main cables installed within the ceiling void of the existing crèche and adjacent
rooms shall be reinstated onto supporting cable tray to ensure an adequately and safely
supported cable installation for the proposed studios.
2.02.2:
Liaison with the architect/building contractor to provide boxing out for existing distribution
boards located in areas that would become visible / accessible to members of the public
following the refurbishment works i.e. the distribution boards in the existing bar cellar/store
area.
2.02.3:
Provision of accurate and up to date circuit charts for each distribution board affected by the
refurbishment works (non-affected outgoing circuits to be included on the new charts). The
charts should be typed charts enclosed in plastic wallets affixed inside the distribution board
cover & correspond with information provided by the electrical sub-contractor on new labels
adjacent each circuit breaker.
2.02.4:
Provision of new metering in compliance with the Building Regulations Document L, Part 2b
and CIBSE TM 39.
CONTAINMENT
The sub-contractor shall provide a cable containment system for all new cable installations. This
shall generally consist of basket trays above suspended ceilings and white finished galvanized
steel trunkings below ceilings.
All new cable installations shall be fully contained along their length utilizing discrete
galvanized conduit drops in wall constructions or in BOH areas where possible or white plastic
conduit drops FOH where surface installations are required.
The electrical sub-contractor shall supply and install new containment routes as required from
the local and main distribution boards around the building to create a main spine with
supplementary branches to serve individual rooms. The electrical sub-contractor shall supply
and install main containment routes for all systems however specialist system contractors shall
supply and install their own final containment requirements including conduit drops.
Where possible the existing cabling installations shall be reinstated onto the new cable
containment. The new cable containment systems shall be sized for the new cabling, the local
existing cabling plus a minimum of 25% spare capacity for future use.
2.04
EARTHING AND BONDING INSTALLATION
The existing main earth bar is located adjacent the main panel board in the basement switch
room. This is bonded to the main supply with bonds to the incoming water and gas supplies.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
2.04.1:
The existing earth bar shall be replaced with a new bar that has a removable link for testing
purposes. The new earth bar shall be sufficiently sized to allow each bond to be independently
bolted to the bar thus eliminating the possibility of isolating an earth connection reducing risks
to the members of the public. All of the earth bonds shall be identified and provided with a
traffolyte label.
Adjacent the main earthing bar shall be provided and permanently fixed a plastic label have a
yellow background and bearing in a black warning triangle, the wording "WARNING SAFETY ELECTRICAL CONNECTIONS - DO NOT REMOVE".
2.04.2:
The existing earthing conductors visually appear to be undersized however this couldn’t be
confirmed at the time of the survey. The electrical sub-contractor shall determine the size of the
existing conductors and confirm their suitability.
2.04.3:
The electrical sub-contractor shall ensure that all new plant, equipment, circuit cabling and
extraneous conductive parts are connected to earth and that all main equipotential bonding
conductors are installed. The Contractor shall ensure that all earthing is in accordance with
BS7671 and BS 7430.
A separate circuit protective conductor shall be provided throughout every part of every final
circuit. The size of the circuit protective conductor shall be at least in accordance with the
minimum requirements of Regulations
Supplementary bonding conductors shall be provided throughout to ensure equipotential
earthing. Extraneous conductive parts in any room which contain an electrical accessory shall
be bonded. All hot and cold pipework, showers, sinks and wastes shall be directly and
independently bonded to the protective conductor at the nearest socket outlet or accessory
earthing terminal.
Supplementary bonding conductors, to suspended ceiling systems, and the like, shall be sized in
accordance with BS7671 and comprise copper cables insulated with green/yellow LSF 6491B
which shall be mechanically protected throughout their length. All
supplementary
bonding
connections shall be made with lug connectors and brass nut, bolt, washer minimum size
2.5mm2 and earth clamp complying with BS 951. Final connections shall be made via conduit
of accessory boxes and cord grip outlets.
2.05
LIGHTNING PROTECTION INSTALLATION
The existing lightning protection system shall be retained with no modifications.
2.05.1:
2.06
New bonds to the existing roof air termination network shall be made for all new roof mounted
plant. The bonds shall be made using PVC covered copper tapes.
GENERAL LOW VOLTAGE POWER
The existing general low voltage power installation shall be partially stripped out, modified,
extended and replaced to provide socket outlets, fused connection units and other outlets as
required to serve fixed and portable equipment.
Where possible the new installation shall comprise of flush outlets with concealed wiring
however where this is not possible the electrical sub-contractor shall identify and seek approval
for the installation of surface mounted outlets served via white finished high impact plastic
conduits and back boxes.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
General front of house outlets shall be white plastic whilst back of house outlets and outlets
above ceiling voids etc. shall be metal clad. Where outlets are installed onto trunkings etc.
colored fillets shall be installed either side of the outlet to aid visibility in compliance with
Building Regulations Document M.
All fused connection units and socket outlets for dedicated items of equipment shall be engraved
as to its purpose.
All outlets shall be provided with a self-adhesive typed label denoting its full circuit reference.
All new MCB’s and RCBO’s shall be 10kA rated, suitably sized for the circuit and load they are
protecting.
Final connections to each hand dryer or hair dryer shall be from a switched fused connection
unit installed at high level with final connection shall being carried out using 85° rubber
insulated cables in a recessed conduit and box terminated at the rear of the unit. The electrical
sub-contractor shall include for all hand dryers Bobric. Hair dryers shall be free-issued by others
for installation by the electrical sub-contractor.
In addition to the full testing of all new circuitry, existing circuits modified with new outlets,
removal of outlets or relocation of outlets etc. shall be fully tested with any faults or failures
reported to the Project Engineer and rectified by the electrical sub-contractor.
Where possible the electrical sub-contractor shall reuse existing spare circuit breakers however
the sub-contractor is deemed to have included all necessary equipment including new protective
devices to provide a fully functional general low voltage power system as described in the
following sections.
Where cable installations pass through walls, partitions, ceilings or the roof the electrical subcontractor shall seal the opening following the installation of the final cables and containment.
All openings shall be appropriately sealed to the same fire rated performance as the wall.
External penetrations shall be suitably sealed against the impregnation of weather and vermin.
2.06.1:
Within the areas being refurbished and remodeled the general low voltage systems in the
following areas shall be stripped out:







Sauna along with associated stores, toilets and changing rooms.
Function suite.
Kitchen, server, bar cellar, stores and staff area.
Manager’s office.
Staff room.
Reception.
Crèche.
2.06.2:
Within the new entrance and café area new ring main circuits shall be installed to serve socket
outlets for general use. Separate circuits shall be installed for cleaner’s sockets, the sales area
and the new vending area. The cleaners and sales area circuits shall be protected by RCBO’s
whilst the dedicated, labeled sockets for the vending areas shall be protected by type B RCD’s.
The new circuits shall be installed from the local distribution board and wired using multicore
LSF insulated cables.
2.06.3:
A new ring main circuit shall be installed to the newly formed reception to serve twin switched
socket outlets installed within the reception counter for PC’s and other equipment. Socket
outlets shall be provided and wired on a new RCBO protected circuit from the local distribution
board using multicore LSF sheathed cabling. The cabling shall drop from the ceiling void of the
back office via surface mounted conduits with wiring in the counter construction protected from
damage via flexible conduits.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
New power supplies for fixed equipment located within the reception area such as the disabled
call system panel shall be provided on dedicated radial circuits from the local distribution board.
Existing supplies to items of retained equipment such as the intruder alarm system panels shall
be retained where possible.
2.06.4:
A new ring main circuit shall be installed to the newly formed back office to serve twin switched
socket outlets installed on dado trunking above the new benching for PC’s and other equipment.
Socket outlets shall be provided and wired on a new RCBO protected circuit from the local
distribution board using multicore LSF sheathed cabling.
New power supplies for fixed equipment such as the retained CCTV system, data cabinet,
telephone system, panic alarm system etc. shall be provided on dedicated radial circuits from the
local distribution board. Existing supplies to items of retained equipment shall be retained and
reused where possible.
2.06.5:
New switched socket outlets shall be provided in the crèche for general use. These shall be flush
installed at 1200mm AFFL and provided with safety caps to avoid accidental contact with the
room’s younger occupants. These shall be provided and wired on a new RCBO protected ring
circuit from the local distribution board using multicore LSF sheathed cabling.
2.06.6:
A new ring main circuit shall be installed to the newly formed multi-purpose/office/meeting
room to serve twin switched sockets. Sockets shall be installed around the perimeter of the room
in locations and at mounting heights suitable for use with projectors, laptops and tea making
facilities etc. likely to be used in a meeting/presentation. The sockets shall be provided and
wired on a new RCBO protected circuit from the local distribution board using multicore LSF
sheathed cabling.
2.06.7:
A new ring main circuit shall be installed to the newly formed multi-purpose room to serve twin
switched sockets. Sockets shall be installed around the perimeter of the room and wired on a
new RCBO protected circuit from the local distribution board using multicore LSF sheathed
cabling.
2.06.8:
New ring main and radial circuits shall be installed to the newly formed fitness suite extension
to serve switched socket outlets and fused connection units. The new socket outlets shall be
provided and wired on new RCBO protected circuits from the local distribution board using
multicore LSF sheathed cabling. The electrical sub-contractor shall provide sufficient outlets to
suit the proposed equipment layout.
2.06.9:
Within the studio, sockets shall be installed around the perimeter of the room and wired on a
new RCBO protected circuit from the local distribution board using multicore LSF sheathed
cabling.
2.06.10:
Within the spinning studio, sockets shall be installed around the perimeter of the room and wired
on a new RCBO protected circuit from the local distribution board using multicore LSF
sheathed cabling.
2.06.11:
New switched single socket outlets shall be provided in the corridor serving the changing rooms
for cleaning purposes to suit the existing sockets being removed with the new changing room
wall. These sockets shall be installed at 450mm AFFL and at locations suitable for the use of
cabled vacuum cleaners. These shall be installed onto a RCBO protected circuit from the local
distribution board using multicore LSF sheathed cabling.
2.06.12:
New switched single socket outlets shall be provided for cleaning purposes in the refurbished
areas either in the corridors or individual rooms. These sockets shall be installed at 450mm
AFFL and at locations suitable for the use of cabled vacuum cleaners. These shall be installed
onto RCBO protected circuits from the local distribution boards using multicore LSF sheathed
cabling. The electrical sub-contractor shall ensure that where cleaner’s sockets are installed in
individual rooms they are on the same phase as the main power systems in that room.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
2.07
2.06.13:
Existing power supplies for hand dryers and hair dryers etc. in the existing dry changing rooms
shall be relocated as necessary to suit the remodel and extension of the changing rooms.
2.06.14:
Existing power supplies for hand dryers etc. in the existing entrance toilets shall be relocated as
necessary to suit the remodel of the toilets. The circuits shall be modified as necessary to suit the
removal of the female toilets.
2.06.15:
New power supplies shall be installed for mechanical systems including fused connection units
within the ceiling voids or at high level for VAM and cassette units etc. These outlets shall be
installed on ring or radial circuits from MCB’s in the local distribution board using multicore
LSF sheathed cabling.
2.06.16:
New power supplies shall be installed for mechanical systems including external weatherproof
isolators for roof mounted external condensers and air handling units. These outlets shall be
installed on radial circuits from MCB’s in the local distribution board using armored multicore
LSF sheathed cabling. Dependent upon the size of the supply required the supply for the air
handling unit may need to be taken from an MCCB within the main distribution plant in the
basement electrical switch room.
2.06.17:
New power supplies shall be installed for general ancillary services such as disabled toilet
alarms, CCTV cameras, mechanical controls, fire alarm devices etc. These outlets shall be
provided by fused connection units installed on ring or radial circuits from MCB’s in the local
distribution board using multicore LSF sheathed cabling.
2.06.18:
During the general non-intrusive survey a number of suspect wiring points were noted which
have been highlighted separately to the Client. During the works on site, the electrical subcontractor shall note any damaged or dangerous electrical installations and prepare a report for
the project engineer.
GENERAL LIGHTING INSTALLATION
The existing general lighting installation shall be partially stripped out, modified, extended and
replaced to provide a new lighting installation designed to suit the new building use.
General front of house lighting switches shall be white plastic whilst back of house switches
shall be metal clad. Where outlets are installed onto trunkings etc. coloured fillets shall be
installed either side of the outlet to aid visibility in compliance with Building Regulations
Document M.
All switches shall be provided with a self-adhesive typed label denoting its full circuit reference.
The lighting installations shall be compatible with the ceiling type within which they are
installed. The Contractor shall provide all patresses required to correctly support luminaries
within the ceiling tiles. All luminaries shall be securely fixed to the structure i.e they will not
rely on the Ceiling support grid
All new MCB’s shall be 10kA rated, suitably sized for the circuit and load they are protecting.
New lighting circuits shall be taken from the local distribution board via type C MCB’s and
wired using multicore LSF sheathed cabling. Lighting circuits in shower or toilet areas shall be
protected by an RCD.
In addition to the full testing of all new circuitry, existing circuits modified with new luminaires,
removal of luminaires or relocation of luminaires and switches etc. shall be fully tested with any
faults or failures reported to the Project Engineer and rectified by the electrical sub-contractor.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Where possible the electrical sub-contractor shall reuse existing spare circuit breakers however
the sub-contractor is deemed to have included all necessary equipment including new protective
devices to provide a fully functional general lighting system as described in the following
sections.
Where cable installations pass through walls, partitions, ceilings or the roof the electrical subcontractor shall seal the opening following the installation of the final cables and containment.
All openings shall be appropriately sealed to the same fire rated performance as the wall.
External penetrations shall be suitably sealed against the impregnation of weather and vermin.
2.07.1:
Within the areas being refurbished and remodeled the general lighting systems in the following
areas shall be stripped out:













2.07.2:
Entrance Lobby.
Reception.
Café & store.
Reception toilets.
Office.
Manager’s office.
Staff room.
Function Suite.
Kitchen and associated servery, stores, beer cellar.
Sauna and associated stores, changing rooms.
Crèche.
Dry changing rooms.
Changing room corridor.
New lighting shall be installed to the reception, café and corridor areas in the form of recessed
circular down lights to areas with a ceiling. Down lights with wall washing optics shall be
installed to the retail and notice board areas to highlight the sales points. The circular down
lights shall be complete with high frequency control gear and fluorescent lamps.
Suspended pendants shall be installed within the café atrium. The pendants shall be complete
with high frequency control gear and fluorescent lamps.
Additional circular down lights shall be recessed into ceiling above the reception desk to create a
focal point and a higher illumination level.
Suspended pendants shall be installed within the entrance lobby. The pendants shall be complete
with high frequency control gear and fluorescent lamps.
The new reception lighting shall be controlled by a bank of switches behind the reception
counter with the lighting grouped in logical control circuits.
The suspended pendants in the café atrium shall be controlled by a local photocell with an
override facility at the reception desk.
The suspended pendants in the entrance lobby shall be controlled by a time-clock and local
photocell arrangement with an override switch behind the reception counter.
2.07.3:
New lighting shall be installed to the back office in the form of recessed modular luminaires
complete with high frequency control gear and T5 fluorescent lamps and prismatic diffusers.
The luminaires shall be selected to achieve the requirements of LG7.
The back office lighting shall be controlled by a ceiling mounted PIR with a key switch operated
override switch at the door for maintenance purposes.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
2.07.4:
New lighting shall be installed to the crèche in the form of recessed modular luminaires
complete with high frequency dimmable control gear and T5 fluorescent lamps and prismatic
diffusers.
The crèche lighting shall be controlled by a wall mounted rotary dimmer switch, located
adjacent the entrance.
2.07.5:
New lighting shall be installed to the multi-purpose / office / meeting room in the form of
recessed circular down lights. The luminaires shall be selected to achieve the requirements of
LG7.
The room lighting shall be controlled by a wall mounted rotary dimmer switch, located adjacent
the entrance. The lighting shall be split into a minimum of two control circuits to allow different
lighting levels to be achieved during a presentation for example.
2.07.6:
New lighting shall be installed to the multi-purpose room in the form of recessed modular
luminaires complete with high frequency control gear and T5 fluorescent lamps and prismatic
diffusers to reduce glare.
The room lighting shall be controlled by a group of wall mounted switches, located adjacent the
entrance.
2.07.7:
New lighting shall be installed to the fitness suite extension in the form of recessed modular
luminaires complete with high frequency control gear and fluorescent lamps.
The room lighting shall be controlled by a group of wall mounted switches, located adjacent the
entrance from the existing fitness suite with a two-way controlled illuminated route from the
entrance of the multi-purpose room and rear corridor.
2.07.8:
New lighting shall be installed to the studio in the form of recessed circular down lights with
high frequency control gear and fluorescent lamps. .
The room lighting shall be controlled by a group of wall mounted switches, located adjacent the
entrance from the existing fitness suite with a two-way controlled illuminated route from the
secondary entrance.
2.07.9:
New lighting shall be installed to the spinning studio in the form of recessed circular down lights
with high frequency control gear and fluorescent lamps.
The room lighting shall be controlled by a group of wall mounted switches, located adjacent the
entrance.
2.07.9:
New lighting shall be installed to the dry changing rooms, sauna, shower and toilets in the form
of recessed circular down lights complete with high frequency control gear, fluorescent lamps
and IP54 (minimum) glasses to reduce glare. Cubicles shall have their own luminaire and not
rely upon borrowed or reflected light.
The lighting shall be controlled by a ceiling mounted presence detectors, connected in parallel to
ensure movement in any area controls the entire room. Key switches shall be located outside of
the spaces adjacent the entrance for override and maintenance purposes.
2.07.10:
Lighting designs shall be carried out by the electrical sub-contractor and approved by the
project engineer prior to works beginning on site. Computer aided designs shall be provided for
each room i.e isolux plots
As a basis of the design the following shall be assumed:Reflection Factors:
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Ceiling 70%
}
Walls 50%
Floor 20%
Maintenance Factor:
}All Areas
}
To be determined, dependent upon
a) lamp lumen maintenance factor
b) lamp survival factor
c) luminaire maintenance factor and
d) room surface maintenance factor.
Floor to ceiling height: See Architects drawings.
Working plane height: See Architects drawings.
Lamp Design Lumens: LDL at 100 hours at an ambient temperature of 22°C.
2.07.11:
2.08
New lighting shall be designed in accordance with the illumination and glare levels as dictated
in BS EN 12464 and CIBSE Lighting Guide 4. The project engineer and client reserve the right
to approve all illumination levels during the design approval stage.
EMERGENCY LIGHTING INSTALLATION
New emergency lighting shall be provided to all the areas being refurbished in the form of
maintained bulkheads (ceiling recessed where possible) fed from the local lighting circuit. The
luminaires shall be arranged in accordance with BS5266 to highlight emergency and safety
equipment, escape routes, final exits, changes in direction, ramps and provide general escape
lighting.
Emergency lighting shall only be provided within the disabled/ambulant cubicles of toilets,
changing rooms and showers etc.
Internally illuminated exit signs shall be provided on all escape routes and at final exits from
publicly accessed rooms and spaces. The exit signs shall be located and sized in accordance with
BS5266 and BS5499.
The emergency lighting shall be designed with a three hour battery backup. The emergency
lighting shall be tested by key switches at the entrance to the space to aid future maintenance
and testing procedures.
The emergency lighting installation shall ensure the safe evacuation from the building and must
be agreed with the Local Authority Building Control Officer.
The Contractor shall test the Emergency lighting throughout including the existing and new
installation and issue a Completion Certificate.
2.09
FIRE ALARM INSTALLATION
The existing fire alarm system shall be retained and modified to suit the refurbishment.
The existing control panel located in the reception entrance is of an age where support may not
be achievable.
The electrical sub-contractor shall carefully strip out and retain all the existing detectors in the
refurbished areas. The existing detectors shall be reinstated on the new ceiling in locations to
suit the new layout in accordance with BS5839. The refurbished areas should be provided with
detection designed in accordance with category L1.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Voids of 800mm in depth or above in the areas where works are being undertaken shall be
provided with smoke detection.
The existing loop cabling shall be stripped out and replaced with new red sheathed multicore fire
rated cabling i.e. FP200 etc. in areas where works are undertaken and the existing cabling
installation is found to be non-compliant with current standards.
The new roof mounted ventilation equipment shall be provided with an interface unit
programmed to deactivate the unit in the event of a fire situation (if not controlled from a central
controller already).
Where indicated on the architect’s layout internal doors shall be provided with door hold open
devices that shall release, to close the door upon activation of the fire alarm via an interface unit.
New sounders shall be installed on the existing loops along the corridors and within individual
rooms as required. The audibility of the fire alarm shall be checked at practical completion with
a noise spectrum analyser i.e. when all works have been completed and furniture and the like is
installed. Where noise levels do not meet the requirements of BS 5839, then additional sounders
shall be provided at the cost of the electrical sub-contractor.
Fire Alarm detection and sounders shall be provided in all areas – All disabled access rooms
shall have visual indication of alarm in addition to the general audible provision. The fire alarm
design shall include for visual indication of fire alarm in accordance with BS 5839 & The
Disability Discrimination Act
The fire alarm design shall be agreed with project engineer, the Building Control Officer and the
local Fire Office prior to installation. The electrical sub-contractor shall allow for all liaisons and
costs in this respect.
Any power supply for AV equipment requires a fire alarm interface to shut the sound system off
in the event of an alarm.
2.10
DISABLED CALL SYSTEM
The electrical sub-contractor shall supply, install and commission a new toilet disabled call
system. The system shall pick up the inputs from existing retained call systems and incorporate
these onto a new display panel behind the reception counter.
Each new call point shall include the a pull cord with handles at 800mm and 100mm AFFL,
local reset button and a reassurance light.
All equipment shall be positioned in accordance with the requirements of Part M of the Building
Regulations
2.11
SPECIALIST SYSTEMS
2.12
TELEPHONE MAINS (INCOMING)
The existing main telephone system shall be retained with no modifications.
2.13
TELEPHONE INSTALLATION
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
The electrical sub-contractor shall employ a specialist installer to modify the existing internal
telephone communications systems to suit the refurbishment and layout changes.
The existing number of points shall be retained with the following minimum achieved:
-
2.14
Back office: 6no points
Reception desk – 4no points
TV AERIALS
The television distribution system shall be provided and installed by others.
The electrical sub-contractor shall liaise with the specialist contractor to provide all required
power supplies for distribution equipment etc. The electrical sub-contractor shall install an
additional twin switched socket outlet adjacent each TV connection point for the installation of a
TV etc. by others.
The electrical sub-contractor shall provide a main spine of cable containment to allow
installation of the system however the specialist contractor shall supply and install all secondary
and final containment requirements.
2.15
DATA SYSTEM
The electrical sub-contractor shall employ a specialist installer to modify the existing data
system as part of a structured wiring installation.
The existing number of points shall be retained with the following minimum achieved:
-
Back office: 10no points
Reception desk – 6no points
Meeting room – 2No
Sales area – 2No data, 2No telephone & 2No double sockets.
All main Containment Systems and Power supplies required by the specialist Data installer shall
be installed by the Contractor
All Structured cabling CAT 5E shall be supplied and installed by the contractor, including all
final connections. Each data point shall be cabled back to the existing wall mounted data rack
located in the back office.
Under no circumstances shall cables be loose laid or run parallel or within 300mm of power
cabling systems. Refer BS 7671.
2.16
CCTV, INTRUDER, ACCESS & INTERCOM SYSTEMS
The existing security systems shall be retained.
The electrical sub-contractor shall allow for protection of the systems during the works on site.
The electrical sub-contractor shall modify or relocate items of equipment as required to suit the
changes to internal partitions and ceilings.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
The electrical sub-contractor shall allow for the temporary disconnection and reinstatement of
all ceiling mounted equipment that is affected by the installation of a new ceiling.
The electrical sub-contractor shall be responsible for the full reinstatement of all systems to the
satisfaction of the client and project engineer. An initial survey and condition report would be
beneficial in this regard to highlight any existing issues before works commence.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
MECHANICAL SERVICES INSTALLATION
This section sets out the design parameters for the installation of the mechanical services
installation within the development.
Key parameters are given that are to be utilised for the design of each of the elements
All Equipment selections shall be approved by the client or their appointed representative
prior to installation.
3.01
DESIGN PARAMETERS
Environmental Criteria
300 C dry bulb @ 220C wet bulb
External Ambient (summer)
-40C dry bulb @ 100% saturation
External Ambient (winter)
Internal Design Condition (summer)
220C (where comfort cooling is provided)
Internal Design Condition (winter)
210C
NO NEW HUMIDITY CONTROL SHALL BE PROVIDED.
Miscellaneous Heat Gains
10W/m2
Lighting gains
Occupancy gains (per person)
Occupancy level
When seated
Active
95W Sensible
200W Sensible
70W Latent
100W Latent
TBC by the client within each area
Solar Gains
Solar gains shall be calculated using an industry Standard Computer selection programme – All
glazing details and shading/internal blinds shall be provided by the project Architect
Fabric Losses
Fabric lloss should be based on the environmental criteria set out previously and the U values
set out below: - (Project Specific U Values shall be confirmed with the Architect)
Fabric
Roof
Floor Slab
Walls
Glazing Vertical
U Value (W/m2K)
TBC by Architect prior to final design
TBC by Architect prior to final design
TBC by Architect prior to final design
TBC by Architect prior to final design
The building is existing and is not subject to Part L regulations as a new build and allowances
must be made for U-values and air infiltration in accordance with historical data where required
and the U-values available where provided. The designer shall allow for these infiltration rates
within their calculations for heating and cooling load.
The heating/cooling system shall be designed to achieve the desired room temperatures within 1
hour of activation.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Miscellaneous Data
Room Design Noise Levels
NR Value
Changing Areas
Corridor
Fitness Suite
Crèche
Office
Multi Purpose Room
Fitness Suite
Spinning Studio
Studio
Cafe
WC Areas
45
40
45
45
35
40
45
45
45
40
45
External noise criteria (plant)
55dB(A) at the site boundary (min)
Or to suit any local planning requirements, whichever is the more stringent the contractor shall
include for all attenuation requirements, both atmosphere and job side.
Attenuators shall be installed up and/or downstream of the plant being attenuated, these shall
generally comprise rectangular or circular pod type attenuator with stilted cores.
Duct Velocities
Duct velocities shall be as recommended in DW 144 and within CIBSE guidelines. The
velocities selected shall not exceed noise levels specified.
3.02
SYSTEM DESCRIPTIONS
Heating
LPHW
The mechanical services design shall be in accordance with the parameters stated above.
The existing LPHW boilers within the plant room are to remain. These are Remora 610 ECA
boilers which appear to have been installed recently.
Currently the heating to the development is provided by a variety of LPHW emitters to the
various areas. Many of the areas to be refurbished will omit the existing LPHW radiators and
pipework and be replaced with heat recovery ventilation air handling equipment and new heat
pump units.
Where LPHW heating is to be retained and relocated, heating shall be provided with heating via
wall mounted radiators on a LPHW 2 pipe circuit, with flow & return temperature 820C & 710C
respectively.
All radiators shall be low surface temperature type in all customer areas and flat panels in the
corridor/staff areas.
Existing heating plant within the plant room is to be retained.
The boiler rooms shall be vented in accordance with the 1999 Gas Safety Regulation
requirements.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
All radiators shall be provided with thermostatic radiator valves on the flow & lockshield valves
on the return for balancing purposes.
All connections shall be bottom opposite ends.
All pipework shall be mild steel shall be routed in ceiling voids to the radiator position – drops
down the face of walls shall be boxed in by others (all to be in the corners of rooms), all pipe
routes and final connections to Radiators shall be agreed with the Architect, client and their
appointed representative.
Heat Pump Air Conditioning
In areas where comfort cooling is to be installed which include the new studio, spinning studio,
fitness suite extension, back office and crèche heat pumps will also provide heating to these
areas via a variety of wall and ceiling mounted indoor units with external condensers mounted
on the roof plant level above the new fitness suit extension or externally to the rooms where
maximum pipe lengths are exceeded.
The reception and cafe areas are to be heated via the installation of a new recuperating air
handling unit to include a LPHW heating coil and frost coil fed from the LPHW system.
Comfort cooling & heating shall be provided to the new studio, spinning studio, fitness suite
extension & multi-purpose room. The contractor is to carry out heat loss and gain calculations to
ascertain the required heating and cooling loads to achieve the required internal conditions.
The indoor units, which shall be a variety of wall mounted and ceiling mounted units, shall be
served via external condensing units and 2 pipe distribution pipework.
Units shall be fitted with condensate pumps to lift condensate water to a gravity drainage system
in the ceiling void.
The condensers shall be located external to the rooms they serve and shall be provided with
protective cage to prevent vandalism where required.
The contractor shall provide single phase supplies to IP54 rated external isolators adjacent to the
outdoor units
Control shall be given by the local control unit mounted locally to the unit.
A master time enable shall be derived from the H&V control panel to ensure all units are
switched ‘Off’ outside normally occupancy times.
A setback temperature of 160C shall be maintained at all times.
3.03
DOMESTIC WATER SERVICES
Hot & cold water services shall be installed throughout the development to align with the
architects layouts i.e WC’s, showers, cleaner’s rooms, serverys etc. These shall be fed from the
existing DWS systems currently in place.
The local water authority shall be contacted by the contractor, to advise them that works are
being undertaken , as required by the Water Supply (Water Fittings) Regulations 1999. The
contractor shall issue all drawings to the local water authority for their comment and approval.
The contractor shall arrange to meet the representative of the local water authority on site prior
to practical completion and survey the development to ensure the whole development is
compliant with the Water Supply (Water Fittings) Regulations 1999. All remedial works
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
necessitated by the works shall be undertaken by the contractor and a compliance certificate
issued to the client.
Local Water Authority
-
TBC
Tel
TBC
All pipework shall be insulated in accordance with Volume 3b of this series of documents
Care shall be taken to ensure no ‘dead legs’ contained in the water pipework configuration
where existing services are affected and as part of the new installation on both hot and cold
water services.
Cold Water
Domestic cold water services shall be provided to all areas, either tanked or mains fed for
drinking purposes in accordance with the architect’s layout.
The existing incoming water supply shall be retained for reuse.
The contractor shall include a provision sum for Water Softening equipment that maybe
required if the levels of hardness in the area are above 7 Degrees Clark.
The contractor shall ensure that there is adequate water pressure to serve the new requirements
of the domestic water services.
Care shall be taken to ensure no ‘deadlegs’ contained in the water pipework configuration.
The whole installation shall be compliant with The Water Supply (Water Fittings) Regulations
1999.
The materials utilised for the cold water installation shall be Copper table X, where concealed or
in plant areas. All exposed pipework drops in general areas shall be chrome plated, and shall be
complete with ceiling rosettes where pipes drop out of ceiling voids.
Alternatives will be considered, but shall only be utilised with the express written approval of
the client and/or their appointed representative.
No water services shall be installed within any floor construction.
Hot Water
Domestic hot water services shall be provided to all areas.
2no. gas fired boilers within the plant room provide heat to an existing 1000l calorifier which is
stored at 60oC. This provides domestic water services to the leisure centre with the exception of
point of use water heaters and the sports hall changing areas.
Where the existing installation does not comply, the contractor must allow ensuring that all
areas containing gas fired equipment shall be vented in accordance with The 1999 Gas Safety
Regulation requirements. High and low ventilation must be present and operational within plant
rooms containing gas fired equipments.
Domestic hot water flow and return temperatures shall be 600C – 500C respectively.
All hot water outlets for hand washing & for bathing will be provided with mixers to give a
delivery temperature of 43oC – Thermostatic mixing valves shall be within 1.5m of the outlet it
is serving.
All hot water outlets for showers will be provided with mixers to give a delivery
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
temperature of 41oC. Thermostatic mixing valves shall be within 1.5m of the outlet tap it is
serving.
Hot water supplies to sinks and cleaners sinks are not to be thermostatically mixed and are to
deliver water up to 60oC.
The materials utilised for the hot water installation shall be Copper table X, where concealed or
in plant areas. All exposed pipework drops in general areas shall be chrome plated, and shall be
complete with ceiling rosettes where pipes drop out of ceiling voids.
Alternatives will be considered, but shall only be utilised with the express written approval of
the client and/or their appointed representative.
No water services shall be installed within any floor construction.
3.04
GAS MAINS SUPPLY
The existing gas supply to the development does not need to be modified due to these works. It
is not envisaged that a gas upgrade is required.
All existing pipework routes through the building shall be ventilated.
3.05
DUCTWORK INSTALLATIONS
All ductwork shall be selected and installed in accordance with DW144 and DW 171.
Alternatives to galvanised sheet steel ductwork shall be considered. The installation of
alternative systems must be approved by the client or their appointed representative prior to
installation.
Fire dampers shall be provided to align with the fire compartmentation strategy of the
building. The contractor shall allow for all items in this respect – refer to the Architect’s
drawings.
Ductwork systems shall be pressure tested in accordance with Part L of the building regulations.
3.06
HVAC CONTROLS
Whilst the majority of the new plant and equipment to be installed during the refurbishment can
be stand-alone, the additional air handling plant to the cafe will remain under the control of the
existing BMS system.
An HVAC Control System exists to control & monitor the HVAC installation and is located
within the building plant room.
The contractor shall be responsible for all liaison in this respect. System schematic drawings and
‘Point Schedules’ shall be issued to the client or their appointed representatives for comment
prior to installation panel facia layout detailing all hand/off/auto switches shall be issued for the
client or their appointed representatives approval.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
3.07
MISCELLANEOUS MECHANICAL VENTILATION SYSTEMS
The Contractor shall design, supply and install mechanical ventilation systems to the following
areas to comply with the Building Regulations and CIBSE guides.
Area
Air Change Rate/hr
WC’s
Shower
Cleaner’s Store
Staff Room
Plant Room
10 ACH
10 ACH
6 ACH
6 ACH
6 ACH
Café/Reception
8l/s/p
Back Office
Crèche
Multi-purpose/Office/Mtg
N/V
N/V
6 ACH
Multi Purpose Room
6 ACH
Fitness Suite Extension
12l/s/p
Studio
12l/s/p
Spinning Studio
15l/s/p
Control
Via PIR with run on timer (15mins)
Via PIR with run on timer (15mins)
Via PIR with run on timer (15mins)
Via PIR with run on timer (15mins)
Local thermostat switched on temperature
rise + combustion ventiltion
Roof mounted AHU -time controlled by
BMS equipment. Positive pressure.
Opening window
Opening windows
Heat recovery ventilation c/w pre-heat and
re-heat electric heater batteries
Heat recovery ventilation c/w pre-heat and
re-heat electric heater batteries
Heat recovery ventilation c/w pre-heat
battery switched via PIR
Heat recovery ventilation c/w pre-heat
battery switched via PIR
Heat recovery ventilation c/w pre-heat
battery switched via PIR
Client to provide room data sheets with occupancy levels included.
Make-up Air
Make up air systems shall be provided via AHU’s mounted in accessible/maintainable locations
such as within ceiling voids, store rooms etc.
Make up air shall be introduced via door transfer grilles with intumescent fire blocks where fire
barriers are penetrated. Door transfer grilles shall be sized to allow the correct make up air
volume at a velocity no greater than 2.5m/s.The colour of all door transfer grilles shall be
approved by the Architect.
The systems shall comprise of wall or duct mounted fans controlled as noted above, all power
supplies shall be derived from local distribution boards.
All fans shall be located in accessible & maintainable locations.
All ductwork shall be as previously described and shall be c/w fire dampers where they pass
through fire compartment walls – refer to fire strategy drawings for details of walls that a fire
rated.
Fans shall either be wall mounted or duct mounted and shall discharge through louvers/roof
cowls – louvres/roof cowls shall be provided by the contractor and shall be a colour approved
by the project Architect.
Extract grilles shall be egg crate type finished in white.
Supply grilles shall be 4 Way discharged finished in white.
All grilles shall be tamperproof.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
All openings above 300mm shall be fitted with burglar bars.
3.08
KITCHEN AREA VENTILATION
Servery supply and extract ventilation is to be via the air handling plant mounted on the roof
above the reception area.
3.09
POWER SUPPLIES TO MECHANICAL PLANT
Power supplies to mechanical plant, i.e. air handling equipment and ancillary equipment shall be
derived from the H&V control panel located in the first floor plantroom. As previously noted
power supplies to comfort cooling units and extract fans shall be derived from local distribution
boards.
3.10
ABOVE GROUND DRAINAGE
The contractor shall design, supply & install the above ground drainage system strictly in
accordance with BS EN 12056-2:2000.
All above ground drainage for WCs, showers, baths, sinks, WHBs, kitchen equipment &
specialist equipment noted on the architects layout.
All sanitary ware shall be included as per the HCD specification.
The contractor is responsible for all above ground drainage only.
All drainage shall be connected to soil & vent pipes terminating externally above roof level
under no circumstances shall AAV ‘Durgo’ valves be utilised. SVPs shall discharge at least
900mm from any opening and shall terminate with a proprietary wire cage.
All condensate connection from comfort cooling units shall be run to the nearest cleaner’s room
drain position and shall be insulated; final connections to drain shall be via a trapped tundish
Minimum trap sizes shall be as follows:Equipment
Sink
Urinals
WHB
Dishwasher/Washer
Min Trap Size
42mm
42mm
35mm
42mm
Depth of Seal
75mm
75mm
75mm
75mm
Rodding eyes shall be provided in readily accessible locations, i.e such that rods can easily be
inserted
Materials
Soil Stacks/Vent pipes
WC/Urinals
WHB Branch connections
Kitchens/Dishwashers/Washers /Cleaners
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
-
uPVC Solvent welded
uPVC Solvent welded
uPVC Solvent welded
uPVC Solvent welded
4.00
GENERAL
4.01
TESTING AND COMMISSIONING
The contractor shall include for the building services installation and specialist system to be
tested and commissioned strictly in accordance with the requirements of all the relevant British
Standards as appropriate to each elemental item of equipment or system.
The whole of the Electrical Services Installation shall be tested in accordance with the following
and issue the following appropriate test certificates:-
BS7671
BS5266
BS6651
BS5839
CIBSE
:
:
:
:
:
IEE Wiring Regulations
Emergency Lighting
Lightning Protection Systems
Fire Alarm
Commissioning codes
The Contractor shall submit on completion NICEIC, Emergency Lighting, Fire Alarm and
Electrical Installation Test Certificates.
The Contractor shall provide all test equipment and provide current calibration certificates.
4.02
AS FITTED DRAWINGS AND OPERATING AND MAINTENANCE
MANUALS
The Contractor shall provide a full package of ‘As Installed’ drawings and Operation &
Maintenance Manuals – These shall be vetted by the client’s appointed representative and any
comments incorporated
The Contractor shall prepare the Operation & Maintenance Manuals in accordance with
BSRIA’s code of practice for provision of Operation & Maintenance documentation
3no. copies of Operation & Maintenance manuals & drawings shall be provided 2no. in CD
format 2 No Hard Copies.
The full documentation (post audit and update) shall be issued at practical completion
The record documents shall comprise:1)
As Fitted Electrical & Mechanical Installation Drawings.
A separate set of information for each trade
2)
Specialist System Information. I.e BMS – I.T, Telephones - etc
3)
Operation and Maintenance Manuals.
The Operation and Maintenance Manuals shall be encased in A4 size plastic covered
loose leaf, 4 ring binders generally as follows:a)
b)
c)
Section 1
Section 2
Section 3
d)
e)
Section 4
Section 5
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Index
Description of Design Intent
Details of Equipment, Manufacturers Data
Sheets etc.
Description of Operation of Specialist Plant and Equipment.
Details of planned maintenance required to
f)
Section 6
g)
Section 7
plant and equipment including spare parts.
Set of Record Drawings and Specialist
Installation drawings.
Telephone numbers of Sub-Contractors,
Specialist Suppliers, Equipment Suppliers.
The Contractor shall submit the record drawings prepared using AUTOCAD.
The Contractor shall submit a draft of the Operating and Maintenance Manuals 4 weeks prior to
handover for comment.
Active Nation – Greenbank Leisure Centre
Volume 2 M&E Performance Specification – Design Criteria
Issue 1 – June 28th 2013
Download