Greenbank Leisure Centre, Swadlincote PERFORMANCE SPECIFICATION FOR BUILDING SERVICES INSTALLATIONS Volume 1 – Design Criteria Prepared by Yorkshire Building Services Ltd Martin Street Birstall, Batley, West Yorkshire, WF17 9PJ. Tel: 01924 471955 andy.sutcliffe@ybsltd.co.uk Issue 1 – 28th June 2013 Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Issue Record Sheet Issue/revision Issue 0 Revision 1 Remarks Date 28th June 2013 Prepared by A. Sutcliffe Signature Checked by Signature Authorised by Signature Project number File reference Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Revision 2 Revision 3 Design Team Client Active Nation Address Quatro House, Lyon Way, Frimley Road, Camberley, Surrey, GU16 Tel: 01283 216269 Contact: John Oxley Project Managers/ PQS TBC Address Tel: Contact: Architect - Hadfield Cawkwell Davidson Address 17 Broomgrove Road, Sheffield, S10 2LZ Tel: 0114 2668181 Contact: Mathew Bradbury Structural Engineer – TBC Address Tel: Contact: M&E Consulting Engineer – Yorkshire Building Services Address Martin Street, Birstall, Batley, West Yorks, WF17 9PJ Tel: 01924 471955 Contact: Andy Sutcliffe Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Notes for Tenderers This series of documents are issued for the Contractor to prepare the Mechanical & Electrical Designs for the Project The series of documents comprises the following:Volume 1 - Contract Preliminaries Volume 2 - Design Criteria Volume 3 - Workmanship & Materials This documentation must be read in conjunction with all other tender documentation – including, but not limited to:Architects Outline Specification Architects Drawings Structural Engineers Drawings & Specifications All Documents referred to in the above documents The Room Data Sheets Document Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Introduction The building, which is already in existence, was initially opened in 1978 as a leisure centre provided by the local council to the people of the community. The building was originally built in the 1977/78 and has undergone various extensions and refurbishments in a bid to maintain the services to the community. One of the most recent areas of refurbishment which the centre has undergone is that of the wet changing areas. The proposal is to renovate the areas identified within the layout drawings including a variety of strip outs, changes of use and refurbishments throughout the entire of the leisure centre. This will also involve a variety of stripping out, reusing and replacing the existing building services to the areas which will be affected as part of the refurbishment. The details of the mechanical and electrical installation are detailed in this series of documents. The centre is currently serviced with electricity, gas & water; it is not envisaged that these need to be upgraded as part of the scope of this project; however pressure checks of the incoming water main should be carried out to confirm sufficient is available to cope with any additional load incurred by these works. The contractor must make allowances within their tender for main cold water boosting if their design calculations find this to be required to achieve sufficient water pressure throughout. Allowances must be made for the inspection and making safe of all existing services within areas that are to be affected to ensure that services comply with latest industry codes of practice even in instances where services affected run out of the demise of the planned works. These include BS7671 2008 17th Edition Wiring Regulations and ACOP Gas Safety Regulations 1998. The tender should include for all costs in this respect. The contractor must visit site to establish the extent of the strip-out. No claims for additional monies in this respect will be considered. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 CONTENTS 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 INTRODUCTION GENERAL DESCRIPTION DESIGN DRAWINGS CO-ORDINATION DRAWING SCHEDULE VISITING SITE PROGRAMMING THE WORKS COMMISSIONING BUILDERSWORK CONSTRUCTION DESIGN & MANAGEMENT REGULATIONS PART L BUILDING REGULATIONS STAFF TRAINING STANDARDS OF WORKMANSHIP EXISTING EXTERNAL SERVICES ELECTRICAL INSTALLATION 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 INFRASTRUCTURE LV DISTRIBUTION UNDERFLOOR DUCTING EARTHING AND BONDING INSTALLATION LIGHTNING PROTECTION INSTALLATION GENERAL LOW VOLTAGE POWER INSTALLATION GENERAL LIGHTING INSTALLATION EMERGENCY LIGHTING INSTALLATION FIRE ALARM INSTALLATION DISABLED CALL SYSTEMS SPECIALIST SYSTEMS TELEPHONE MAINS (Incoming) TELEPHONE INSTALLATION TV AERIALS DATA SYSTEMS CCTV INTRUDER SYSTEMS MECHANICAL INSTALLATION 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 DESIGN PARAMETERS SYSTEM DESCRIPTIONS DOMESTIC WATER SERVICES GAS MAIN SUPPLY DUCTWORK INSTALLATION HVAC CONTROLS MISCELLANEOUS MECHANICAL VENTILATION KITCHEN AREA VENTILATION & GAS SUPPLIES 3.09 3.10 POWER SUPPLIES TO MECHANICAL PLANT ABOVE GROUND DRAINAGE Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 GENERAL 4.01 4.02 TESTING AND COMMISSIONING AS FITTED DRAWINGS AND OPERATING MANUALS DRAWINGS A-04-100_Existing Floor Plan A-04-110_Proposed Floor Plan A-35-100_Existing Ceiling Plan A-35-110_Proposed Ceiling Plan A-35-111_Proposed Ceiling Details A-67-100_Existing Fire Strategy Plan A-67-110_Proposed Fire Strategy Plan Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 1.01 INTRODUCTION The contractor shall be responsible for carrying out the electrical & mechanical services design and installation in accordance with this performance specification. The contractor shall install a fully co-ordinated services installation which meets the requirements of this performance specification and is in accordance with all current statutory regulations and codes of practice in particular the following:The IEE Wiring Regulations - 17thEdition Requirements for Electrical Installations BS7671: The British Standard Specifications and Codes of Practice. The Electricity at Work Regulations 1989. The Electricity Supply Regulations 1988. The Factories Act 1961. Local Authority By-Laws and Regulations, including Local Petroleum Licensing Regulations issued by the Local Fire or Petroleum Client. The Health and Safety at Work Act 1974 and subsequent amendments. The Control of Substances Hazardous to Health Regulations 1988. The Consumer Protection Act 1987. The Management of Health and Safety at Work Regulations 1992. The Provision and Use of Work Equipment Regulations 1992. The Workplace (Health, Safety and Welfare) Regulations 1992. The Manual Handling Operations Regulations 1992. Regulations and Requirements of the Electricity Supply Authority. The Construction (Design and Management) Regulations 1994 and current amendments. Year 2000 Compliance The Building Regulations and all current amendments. The Chartered Institute of Building Services Guides All current Volumes. Control of Legionella in Health Care Premises – A Code of Practice The clauses contained in this section of the specification shall be read in conjunction with the Volume 3 Workmanship & Materials, of this series of documents and the Architect’s General Arrangement drawings relating to the works and all NBS specifications. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 1.02 GENERAL DESCRIPTION The services installation works referred to in this performance specification shall comprise the complete design, supply, and installation, co-ordination, testing, commissioning and setting to work including the provision of all handover documentation. All documentation required for Building Regulation approval, including documentation required to ascertain compliance with Part L 2006 shall be provided by the contractor. The details of the construction are detailed on the architect’s drawings and within the NBS specifications, all of which are issued under separate cover. Internal room layouts and suspended ceiling details are also as detailed on the architects drawings and NBS specifications. All documentation shall be read in conjunction with the any room data sheets issued by the client. 1.03 DESIGN The contractor shall carry out all necessary design and drawing work required to ensure the suitability, compatibility, and correct location within the various systems of components selected, to meet the requirements of this performance specification. The contractor shall produce such drawings, calculations and other documents for the detail design of the works as may be required for examination. The contractor shall agree the location of all plant and equipment with the client or their appointed representative. Unless specific written dispensation is given all equipment selected for the works shall be from reputable manufacturers who are part of a recognised quality assurance scheme. All equipment selections shall be approved by the client or their appointed representative. A schedule of proposed equipment suppliers shall be provided with the tender documentation. Key parameters are given that are to be utilised for the design of each of the elements. The Designer shall ensure full compliance with any requirements of the Local Planning Authority and Building Control – The contractor shall be responsible for all requirements in this respect. The early approval of external plant locations is recommended. All plant shall be selected for a design life of 15 years. The designer shall conform to all of the parameters as a minimum, and shall take responsibility for the final design and selection of all systems. The designer shall make available the full design for comment by the client and/or their appointed representative. The design shall be based on the criteria given and any applicable Building Regulations, British Standards, CIBSE guidelines etc. The designer shall utilise an industry standard software package. A design review will be undertaken; the designers shall make themselves available to attend all meetings required to attain full scheme approval. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 1.04 DRAWINGS The contractor shall provide a full package of design information to enable the client and/or their appointed representative to audit the design including but not limited to:(i) Drawings – Design, Co-ordination & Builderswork (ii) Specifications and Schedule (iii) Detail of Equipment Selections and any samples required (iv) Calculations The contractor shall issue a ‘Schedule of Design Information’ which shall be agreed with the appointed representative to ensure the timely issue of design information for approval. The approval process will be as follows Status A - No further comment Status B - Further information required. Information acceptable for installation. Status C - Information not acceptable. Resubmit information in revised form. The contractor shall produce complete design and detail drawings, production information, design calculations and specifications as required. The contractor shall liaise with other members of the design team to ensure co-ordination of the works with other building elements and services. The contractor shall provide 4 no. copies of all design and working drawings. The contractor shall allow to amend all design and working drawings subject to comment. The contractor shall provide 4 no. copies of final design and production information The contractor shall produce all design and production in formation using the latest version of AUTOCAD. 1.05 CO- ORDINATION The contractor shall be responsible for the co-ordination of services with all building elements, structure, all other services and specialist suppliers equipment The contractor shall provide drawings and sections to demonstrate the co-ordination detailed above. 1.06 DRAWING SCHEDULES The contractor shall provide a complete schedule of proposed drawings when requested. The schedule shall be agreed with the Client or their appointed representative and shall contain drawing issue dates that shall be agreed and strictly adhered to. 1.07 VISITING SITE The contractor is advised to visit the site to determine the extent and nature of the works and to familiarise himself with local conditions and access. No allowance of any kind will be allowed for matters arising from the contractor’s failure to visit site. 1.08 PROGRAMMING THE WORKS Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 The Contractor shall compile a programme for carrying out the design and installation of the works making due allowance for the production and approval of the scheme content, the whole of which shall be integrated into the overall construction programme. The programme shall be based on hours of working which is trade practice where applicable. Should the nature of the work make it necessary for the Contractor to work at premium times in order to undertake the works without inconvenience to other trades and the Client then he should allow in his tender for such overtime. 1.09 COMMISSIONING The Contractor shall provide full commissioning schedules for all installed services prior to practical completion to ensure all systems are verified. The contractor shall ensure that all commissioning is witnessed by the clients appointed representative. 1.10 BUILDERSWORK The contractor shall supply and install all primary and secondary steelwork supports for all new Plant & Equipment. The contractor shall allow for lifting all Plant & Equipment into its final locations and for securing plant to the structure. The contractor shall provide all builders work necessary in connection with the services installation, including holes, apertures, recesses and chases. The contractor shall mark out in advance and shall be responsible for the accuracy and sizes of all cut out holes and chases required and shall drill and plug all holes for securing services which require screw or bolt fixing. Builder’s works requirements in sufficient detail to enable accurate setting out of holes, built-in sleeves and bases shall be identified in advance so that the exact position can be agreed. All openings shall be weather sealed, and will be constructed using robust details such that they do not compromise the ‘sealed building’ requirement. All access to plant areas e.g. platforms, access ladders, walkways etc, shall be provided by the Contractor, for future maintenance of engineering plant and in accordance with the requirements of the CDM Regulations. All plant areas internal or external to the building shall be provided with maintenance lighting & emergency lighting. All plant areas shall also be provided with weatherproof fire alarm call points smoke/heat detection (where appropriate) and sounders. 1.11 CONSTRUCTION, DESIGN & MANAGEMENT REGULATIONS All documentation required by the CDM co-ordinator shall be issued in a timely manner, the Contractor shall include for all requirements in this respect. 1.12 PART L BUILDING REGULATIONS The new mechanical & electrical installation shall be fully compliant with part L of the building regulations. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 1.13 STAFF TRAINING The Contractor shall ensure that the client’s managements nominated facilities maintenance contractor is trained to operate all systems installed by the contractor. The contractor shall liaise with the client to establish mutually agreeable dates for training and shall prepare a document scheduling the system upon which training as been provided, the date and the names of the personnel trained The training schedules shall be signed by both parties to confirm an acceptable level of training as been provided The contractor shall include for all requirements in this respect. 1.14 STANDARD OF WORKMANSHIP Materials employed and work carried shall be in accordance with the workmanship & materials standards document. 1.15 EXISTING EXTERNAL SERVICES The centre is currently serviced with electricity, gas & water and whilst preliminary unobtrusive surveys suggest utility service upgrades are unlikely, the contractor must carry out investigative work to assess that the existing services are sufficient to cope with the demands of the centre following the refurbishment works. If mains water pressure is found to be insufficient the contractor must allow for the installation of a boosted system to cope with demand. The contractor shall be responsible for all costs associated with the modifications to all existing statutory services in and around the development, necessitated by the works including all associated builder’s work. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 ELECTRICAL INSTALLATION 2.01 INFRASTRUCTURE The development is currently served from the Statutory Service Providers local LV infrastructure. The existing supply is sized at 300A three phase. The local Grove Building squash courts are served from this building. It is not anticipated that the refurbishment works will require an increase in the electrical supply. Electrical Supply Authorities 2.02 Host REC (DNO) TBC TBC 2nd Tier Electricity Supplier TBC TBC Meter Operator TBC TBC LV DISTRIBUTION Existing Installation From the incoming supply position in the boiler room pit a 185mm 2 4C armored sub main cable serves the main distribution equipment located in the basement switch room. The main equipment consists of an eight-way TP&N MCCB panel board with a 400A MCCB incomer utilizing one of the ways. A newer twelve-way TP&N MCCB mounted directly above is fed via a multi-core armored cable from a 200A TP&N MCCB in the main panel board. Additional MCB distribution boards and contactor panels in the basement switch room provide power supplies and controls to local services. Further MCB distribution boards are located around the building to serve local equipment and services. The electrical sub-contractor shall design the cable installation based on the following criteria:- The Electrical Installation must be designed in accordance with 17 th Edition IEE wiring Regulations and all Guidance notes. - The maximum demand of the installation shall be determined taking into account diversity where appropriate and used for the sizing of cables and equipment. - Volt drop calculations shall be carried out and visually demonstrated to be in accordance with the 17th Edition wiring regulations. - The method shown the 17th Edition IEE Wiring Regulations shall be used to assess the current carrying capacity and voltage drop for the proposed cable installation. - Sub-main cables shall be XLPE/LSF/SWA/LSF and shall be supplied with a CPC, sized in accordance with BS 7671. - Final circuit cables shall be supplied with a CPC, sized in accordance with BS 7671. The final circuit cables shall have a minimum conductor size of 1.5mm2 for lighting and 2.5mm2 for power. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 - Particular attention shall be given to ensure discrimination between all "upstream" and "downstream" protective devices. - The Contractor shall provide computer originated reports verifying the cable installation calculations. The computer calculations shall be based on using HEVACOMP/AMTECH or similar. System Objectives Generally the existing LV distribution system shall be retained with minor modifications with the following exceptions: 2.03 2.02.1: The existing sub main cables installed within the ceiling void of the existing crèche and adjacent rooms shall be reinstated onto supporting cable tray to ensure an adequately and safely supported cable installation for the proposed studios. 2.02.2: Liaison with the architect/building contractor to provide boxing out for existing distribution boards located in areas that would become visible / accessible to members of the public following the refurbishment works i.e. the distribution boards in the existing bar cellar/store area. 2.02.3: Provision of accurate and up to date circuit charts for each distribution board affected by the refurbishment works (non-affected outgoing circuits to be included on the new charts). The charts should be typed charts enclosed in plastic wallets affixed inside the distribution board cover & correspond with information provided by the electrical sub-contractor on new labels adjacent each circuit breaker. 2.02.4: Provision of new metering in compliance with the Building Regulations Document L, Part 2b and CIBSE TM 39. CONTAINMENT The sub-contractor shall provide a cable containment system for all new cable installations. This shall generally consist of basket trays above suspended ceilings and white finished galvanized steel trunkings below ceilings. All new cable installations shall be fully contained along their length utilizing discrete galvanized conduit drops in wall constructions or in BOH areas where possible or white plastic conduit drops FOH where surface installations are required. The electrical sub-contractor shall supply and install new containment routes as required from the local and main distribution boards around the building to create a main spine with supplementary branches to serve individual rooms. The electrical sub-contractor shall supply and install main containment routes for all systems however specialist system contractors shall supply and install their own final containment requirements including conduit drops. Where possible the existing cabling installations shall be reinstated onto the new cable containment. The new cable containment systems shall be sized for the new cabling, the local existing cabling plus a minimum of 25% spare capacity for future use. 2.04 EARTHING AND BONDING INSTALLATION The existing main earth bar is located adjacent the main panel board in the basement switch room. This is bonded to the main supply with bonds to the incoming water and gas supplies. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 2.04.1: The existing earth bar shall be replaced with a new bar that has a removable link for testing purposes. The new earth bar shall be sufficiently sized to allow each bond to be independently bolted to the bar thus eliminating the possibility of isolating an earth connection reducing risks to the members of the public. All of the earth bonds shall be identified and provided with a traffolyte label. Adjacent the main earthing bar shall be provided and permanently fixed a plastic label have a yellow background and bearing in a black warning triangle, the wording "WARNING SAFETY ELECTRICAL CONNECTIONS - DO NOT REMOVE". 2.04.2: The existing earthing conductors visually appear to be undersized however this couldn’t be confirmed at the time of the survey. The electrical sub-contractor shall determine the size of the existing conductors and confirm their suitability. 2.04.3: The electrical sub-contractor shall ensure that all new plant, equipment, circuit cabling and extraneous conductive parts are connected to earth and that all main equipotential bonding conductors are installed. The Contractor shall ensure that all earthing is in accordance with BS7671 and BS 7430. A separate circuit protective conductor shall be provided throughout every part of every final circuit. The size of the circuit protective conductor shall be at least in accordance with the minimum requirements of Regulations Supplementary bonding conductors shall be provided throughout to ensure equipotential earthing. Extraneous conductive parts in any room which contain an electrical accessory shall be bonded. All hot and cold pipework, showers, sinks and wastes shall be directly and independently bonded to the protective conductor at the nearest socket outlet or accessory earthing terminal. Supplementary bonding conductors, to suspended ceiling systems, and the like, shall be sized in accordance with BS7671 and comprise copper cables insulated with green/yellow LSF 6491B which shall be mechanically protected throughout their length. All supplementary bonding connections shall be made with lug connectors and brass nut, bolt, washer minimum size 2.5mm2 and earth clamp complying with BS 951. Final connections shall be made via conduit of accessory boxes and cord grip outlets. 2.05 LIGHTNING PROTECTION INSTALLATION The existing lightning protection system shall be retained with no modifications. 2.05.1: 2.06 New bonds to the existing roof air termination network shall be made for all new roof mounted plant. The bonds shall be made using PVC covered copper tapes. GENERAL LOW VOLTAGE POWER The existing general low voltage power installation shall be partially stripped out, modified, extended and replaced to provide socket outlets, fused connection units and other outlets as required to serve fixed and portable equipment. Where possible the new installation shall comprise of flush outlets with concealed wiring however where this is not possible the electrical sub-contractor shall identify and seek approval for the installation of surface mounted outlets served via white finished high impact plastic conduits and back boxes. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 General front of house outlets shall be white plastic whilst back of house outlets and outlets above ceiling voids etc. shall be metal clad. Where outlets are installed onto trunkings etc. colored fillets shall be installed either side of the outlet to aid visibility in compliance with Building Regulations Document M. All fused connection units and socket outlets for dedicated items of equipment shall be engraved as to its purpose. All outlets shall be provided with a self-adhesive typed label denoting its full circuit reference. All new MCB’s and RCBO’s shall be 10kA rated, suitably sized for the circuit and load they are protecting. Final connections to each hand dryer or hair dryer shall be from a switched fused connection unit installed at high level with final connection shall being carried out using 85° rubber insulated cables in a recessed conduit and box terminated at the rear of the unit. The electrical sub-contractor shall include for all hand dryers Bobric. Hair dryers shall be free-issued by others for installation by the electrical sub-contractor. In addition to the full testing of all new circuitry, existing circuits modified with new outlets, removal of outlets or relocation of outlets etc. shall be fully tested with any faults or failures reported to the Project Engineer and rectified by the electrical sub-contractor. Where possible the electrical sub-contractor shall reuse existing spare circuit breakers however the sub-contractor is deemed to have included all necessary equipment including new protective devices to provide a fully functional general low voltage power system as described in the following sections. Where cable installations pass through walls, partitions, ceilings or the roof the electrical subcontractor shall seal the opening following the installation of the final cables and containment. All openings shall be appropriately sealed to the same fire rated performance as the wall. External penetrations shall be suitably sealed against the impregnation of weather and vermin. 2.06.1: Within the areas being refurbished and remodeled the general low voltage systems in the following areas shall be stripped out: Sauna along with associated stores, toilets and changing rooms. Function suite. Kitchen, server, bar cellar, stores and staff area. Manager’s office. Staff room. Reception. Crèche. 2.06.2: Within the new entrance and café area new ring main circuits shall be installed to serve socket outlets for general use. Separate circuits shall be installed for cleaner’s sockets, the sales area and the new vending area. The cleaners and sales area circuits shall be protected by RCBO’s whilst the dedicated, labeled sockets for the vending areas shall be protected by type B RCD’s. The new circuits shall be installed from the local distribution board and wired using multicore LSF insulated cables. 2.06.3: A new ring main circuit shall be installed to the newly formed reception to serve twin switched socket outlets installed within the reception counter for PC’s and other equipment. Socket outlets shall be provided and wired on a new RCBO protected circuit from the local distribution board using multicore LSF sheathed cabling. The cabling shall drop from the ceiling void of the back office via surface mounted conduits with wiring in the counter construction protected from damage via flexible conduits. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 New power supplies for fixed equipment located within the reception area such as the disabled call system panel shall be provided on dedicated radial circuits from the local distribution board. Existing supplies to items of retained equipment such as the intruder alarm system panels shall be retained where possible. 2.06.4: A new ring main circuit shall be installed to the newly formed back office to serve twin switched socket outlets installed on dado trunking above the new benching for PC’s and other equipment. Socket outlets shall be provided and wired on a new RCBO protected circuit from the local distribution board using multicore LSF sheathed cabling. New power supplies for fixed equipment such as the retained CCTV system, data cabinet, telephone system, panic alarm system etc. shall be provided on dedicated radial circuits from the local distribution board. Existing supplies to items of retained equipment shall be retained and reused where possible. 2.06.5: New switched socket outlets shall be provided in the crèche for general use. These shall be flush installed at 1200mm AFFL and provided with safety caps to avoid accidental contact with the room’s younger occupants. These shall be provided and wired on a new RCBO protected ring circuit from the local distribution board using multicore LSF sheathed cabling. 2.06.6: A new ring main circuit shall be installed to the newly formed multi-purpose/office/meeting room to serve twin switched sockets. Sockets shall be installed around the perimeter of the room in locations and at mounting heights suitable for use with projectors, laptops and tea making facilities etc. likely to be used in a meeting/presentation. The sockets shall be provided and wired on a new RCBO protected circuit from the local distribution board using multicore LSF sheathed cabling. 2.06.7: A new ring main circuit shall be installed to the newly formed multi-purpose room to serve twin switched sockets. Sockets shall be installed around the perimeter of the room and wired on a new RCBO protected circuit from the local distribution board using multicore LSF sheathed cabling. 2.06.8: New ring main and radial circuits shall be installed to the newly formed fitness suite extension to serve switched socket outlets and fused connection units. The new socket outlets shall be provided and wired on new RCBO protected circuits from the local distribution board using multicore LSF sheathed cabling. The electrical sub-contractor shall provide sufficient outlets to suit the proposed equipment layout. 2.06.9: Within the studio, sockets shall be installed around the perimeter of the room and wired on a new RCBO protected circuit from the local distribution board using multicore LSF sheathed cabling. 2.06.10: Within the spinning studio, sockets shall be installed around the perimeter of the room and wired on a new RCBO protected circuit from the local distribution board using multicore LSF sheathed cabling. 2.06.11: New switched single socket outlets shall be provided in the corridor serving the changing rooms for cleaning purposes to suit the existing sockets being removed with the new changing room wall. These sockets shall be installed at 450mm AFFL and at locations suitable for the use of cabled vacuum cleaners. These shall be installed onto a RCBO protected circuit from the local distribution board using multicore LSF sheathed cabling. 2.06.12: New switched single socket outlets shall be provided for cleaning purposes in the refurbished areas either in the corridors or individual rooms. These sockets shall be installed at 450mm AFFL and at locations suitable for the use of cabled vacuum cleaners. These shall be installed onto RCBO protected circuits from the local distribution boards using multicore LSF sheathed cabling. The electrical sub-contractor shall ensure that where cleaner’s sockets are installed in individual rooms they are on the same phase as the main power systems in that room. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 2.07 2.06.13: Existing power supplies for hand dryers and hair dryers etc. in the existing dry changing rooms shall be relocated as necessary to suit the remodel and extension of the changing rooms. 2.06.14: Existing power supplies for hand dryers etc. in the existing entrance toilets shall be relocated as necessary to suit the remodel of the toilets. The circuits shall be modified as necessary to suit the removal of the female toilets. 2.06.15: New power supplies shall be installed for mechanical systems including fused connection units within the ceiling voids or at high level for VAM and cassette units etc. These outlets shall be installed on ring or radial circuits from MCB’s in the local distribution board using multicore LSF sheathed cabling. 2.06.16: New power supplies shall be installed for mechanical systems including external weatherproof isolators for roof mounted external condensers and air handling units. These outlets shall be installed on radial circuits from MCB’s in the local distribution board using armored multicore LSF sheathed cabling. Dependent upon the size of the supply required the supply for the air handling unit may need to be taken from an MCCB within the main distribution plant in the basement electrical switch room. 2.06.17: New power supplies shall be installed for general ancillary services such as disabled toilet alarms, CCTV cameras, mechanical controls, fire alarm devices etc. These outlets shall be provided by fused connection units installed on ring or radial circuits from MCB’s in the local distribution board using multicore LSF sheathed cabling. 2.06.18: During the general non-intrusive survey a number of suspect wiring points were noted which have been highlighted separately to the Client. During the works on site, the electrical subcontractor shall note any damaged or dangerous electrical installations and prepare a report for the project engineer. GENERAL LIGHTING INSTALLATION The existing general lighting installation shall be partially stripped out, modified, extended and replaced to provide a new lighting installation designed to suit the new building use. General front of house lighting switches shall be white plastic whilst back of house switches shall be metal clad. Where outlets are installed onto trunkings etc. coloured fillets shall be installed either side of the outlet to aid visibility in compliance with Building Regulations Document M. All switches shall be provided with a self-adhesive typed label denoting its full circuit reference. The lighting installations shall be compatible with the ceiling type within which they are installed. The Contractor shall provide all patresses required to correctly support luminaries within the ceiling tiles. All luminaries shall be securely fixed to the structure i.e they will not rely on the Ceiling support grid All new MCB’s shall be 10kA rated, suitably sized for the circuit and load they are protecting. New lighting circuits shall be taken from the local distribution board via type C MCB’s and wired using multicore LSF sheathed cabling. Lighting circuits in shower or toilet areas shall be protected by an RCD. In addition to the full testing of all new circuitry, existing circuits modified with new luminaires, removal of luminaires or relocation of luminaires and switches etc. shall be fully tested with any faults or failures reported to the Project Engineer and rectified by the electrical sub-contractor. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Where possible the electrical sub-contractor shall reuse existing spare circuit breakers however the sub-contractor is deemed to have included all necessary equipment including new protective devices to provide a fully functional general lighting system as described in the following sections. Where cable installations pass through walls, partitions, ceilings or the roof the electrical subcontractor shall seal the opening following the installation of the final cables and containment. All openings shall be appropriately sealed to the same fire rated performance as the wall. External penetrations shall be suitably sealed against the impregnation of weather and vermin. 2.07.1: Within the areas being refurbished and remodeled the general lighting systems in the following areas shall be stripped out: 2.07.2: Entrance Lobby. Reception. Café & store. Reception toilets. Office. Manager’s office. Staff room. Function Suite. Kitchen and associated servery, stores, beer cellar. Sauna and associated stores, changing rooms. Crèche. Dry changing rooms. Changing room corridor. New lighting shall be installed to the reception, café and corridor areas in the form of recessed circular down lights to areas with a ceiling. Down lights with wall washing optics shall be installed to the retail and notice board areas to highlight the sales points. The circular down lights shall be complete with high frequency control gear and fluorescent lamps. Suspended pendants shall be installed within the café atrium. The pendants shall be complete with high frequency control gear and fluorescent lamps. Additional circular down lights shall be recessed into ceiling above the reception desk to create a focal point and a higher illumination level. Suspended pendants shall be installed within the entrance lobby. The pendants shall be complete with high frequency control gear and fluorescent lamps. The new reception lighting shall be controlled by a bank of switches behind the reception counter with the lighting grouped in logical control circuits. The suspended pendants in the café atrium shall be controlled by a local photocell with an override facility at the reception desk. The suspended pendants in the entrance lobby shall be controlled by a time-clock and local photocell arrangement with an override switch behind the reception counter. 2.07.3: New lighting shall be installed to the back office in the form of recessed modular luminaires complete with high frequency control gear and T5 fluorescent lamps and prismatic diffusers. The luminaires shall be selected to achieve the requirements of LG7. The back office lighting shall be controlled by a ceiling mounted PIR with a key switch operated override switch at the door for maintenance purposes. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 2.07.4: New lighting shall be installed to the crèche in the form of recessed modular luminaires complete with high frequency dimmable control gear and T5 fluorescent lamps and prismatic diffusers. The crèche lighting shall be controlled by a wall mounted rotary dimmer switch, located adjacent the entrance. 2.07.5: New lighting shall be installed to the multi-purpose / office / meeting room in the form of recessed circular down lights. The luminaires shall be selected to achieve the requirements of LG7. The room lighting shall be controlled by a wall mounted rotary dimmer switch, located adjacent the entrance. The lighting shall be split into a minimum of two control circuits to allow different lighting levels to be achieved during a presentation for example. 2.07.6: New lighting shall be installed to the multi-purpose room in the form of recessed modular luminaires complete with high frequency control gear and T5 fluorescent lamps and prismatic diffusers to reduce glare. The room lighting shall be controlled by a group of wall mounted switches, located adjacent the entrance. 2.07.7: New lighting shall be installed to the fitness suite extension in the form of recessed modular luminaires complete with high frequency control gear and fluorescent lamps. The room lighting shall be controlled by a group of wall mounted switches, located adjacent the entrance from the existing fitness suite with a two-way controlled illuminated route from the entrance of the multi-purpose room and rear corridor. 2.07.8: New lighting shall be installed to the studio in the form of recessed circular down lights with high frequency control gear and fluorescent lamps. . The room lighting shall be controlled by a group of wall mounted switches, located adjacent the entrance from the existing fitness suite with a two-way controlled illuminated route from the secondary entrance. 2.07.9: New lighting shall be installed to the spinning studio in the form of recessed circular down lights with high frequency control gear and fluorescent lamps. The room lighting shall be controlled by a group of wall mounted switches, located adjacent the entrance. 2.07.9: New lighting shall be installed to the dry changing rooms, sauna, shower and toilets in the form of recessed circular down lights complete with high frequency control gear, fluorescent lamps and IP54 (minimum) glasses to reduce glare. Cubicles shall have their own luminaire and not rely upon borrowed or reflected light. The lighting shall be controlled by a ceiling mounted presence detectors, connected in parallel to ensure movement in any area controls the entire room. Key switches shall be located outside of the spaces adjacent the entrance for override and maintenance purposes. 2.07.10: Lighting designs shall be carried out by the electrical sub-contractor and approved by the project engineer prior to works beginning on site. Computer aided designs shall be provided for each room i.e isolux plots As a basis of the design the following shall be assumed:Reflection Factors: Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Ceiling 70% } Walls 50% Floor 20% Maintenance Factor: }All Areas } To be determined, dependent upon a) lamp lumen maintenance factor b) lamp survival factor c) luminaire maintenance factor and d) room surface maintenance factor. Floor to ceiling height: See Architects drawings. Working plane height: See Architects drawings. Lamp Design Lumens: LDL at 100 hours at an ambient temperature of 22°C. 2.07.11: 2.08 New lighting shall be designed in accordance with the illumination and glare levels as dictated in BS EN 12464 and CIBSE Lighting Guide 4. The project engineer and client reserve the right to approve all illumination levels during the design approval stage. EMERGENCY LIGHTING INSTALLATION New emergency lighting shall be provided to all the areas being refurbished in the form of maintained bulkheads (ceiling recessed where possible) fed from the local lighting circuit. The luminaires shall be arranged in accordance with BS5266 to highlight emergency and safety equipment, escape routes, final exits, changes in direction, ramps and provide general escape lighting. Emergency lighting shall only be provided within the disabled/ambulant cubicles of toilets, changing rooms and showers etc. Internally illuminated exit signs shall be provided on all escape routes and at final exits from publicly accessed rooms and spaces. The exit signs shall be located and sized in accordance with BS5266 and BS5499. The emergency lighting shall be designed with a three hour battery backup. The emergency lighting shall be tested by key switches at the entrance to the space to aid future maintenance and testing procedures. The emergency lighting installation shall ensure the safe evacuation from the building and must be agreed with the Local Authority Building Control Officer. The Contractor shall test the Emergency lighting throughout including the existing and new installation and issue a Completion Certificate. 2.09 FIRE ALARM INSTALLATION The existing fire alarm system shall be retained and modified to suit the refurbishment. The existing control panel located in the reception entrance is of an age where support may not be achievable. The electrical sub-contractor shall carefully strip out and retain all the existing detectors in the refurbished areas. The existing detectors shall be reinstated on the new ceiling in locations to suit the new layout in accordance with BS5839. The refurbished areas should be provided with detection designed in accordance with category L1. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Voids of 800mm in depth or above in the areas where works are being undertaken shall be provided with smoke detection. The existing loop cabling shall be stripped out and replaced with new red sheathed multicore fire rated cabling i.e. FP200 etc. in areas where works are undertaken and the existing cabling installation is found to be non-compliant with current standards. The new roof mounted ventilation equipment shall be provided with an interface unit programmed to deactivate the unit in the event of a fire situation (if not controlled from a central controller already). Where indicated on the architect’s layout internal doors shall be provided with door hold open devices that shall release, to close the door upon activation of the fire alarm via an interface unit. New sounders shall be installed on the existing loops along the corridors and within individual rooms as required. The audibility of the fire alarm shall be checked at practical completion with a noise spectrum analyser i.e. when all works have been completed and furniture and the like is installed. Where noise levels do not meet the requirements of BS 5839, then additional sounders shall be provided at the cost of the electrical sub-contractor. Fire Alarm detection and sounders shall be provided in all areas – All disabled access rooms shall have visual indication of alarm in addition to the general audible provision. The fire alarm design shall include for visual indication of fire alarm in accordance with BS 5839 & The Disability Discrimination Act The fire alarm design shall be agreed with project engineer, the Building Control Officer and the local Fire Office prior to installation. The electrical sub-contractor shall allow for all liaisons and costs in this respect. Any power supply for AV equipment requires a fire alarm interface to shut the sound system off in the event of an alarm. 2.10 DISABLED CALL SYSTEM The electrical sub-contractor shall supply, install and commission a new toilet disabled call system. The system shall pick up the inputs from existing retained call systems and incorporate these onto a new display panel behind the reception counter. Each new call point shall include the a pull cord with handles at 800mm and 100mm AFFL, local reset button and a reassurance light. All equipment shall be positioned in accordance with the requirements of Part M of the Building Regulations 2.11 SPECIALIST SYSTEMS 2.12 TELEPHONE MAINS (INCOMING) The existing main telephone system shall be retained with no modifications. 2.13 TELEPHONE INSTALLATION Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 The electrical sub-contractor shall employ a specialist installer to modify the existing internal telephone communications systems to suit the refurbishment and layout changes. The existing number of points shall be retained with the following minimum achieved: - 2.14 Back office: 6no points Reception desk – 4no points TV AERIALS The television distribution system shall be provided and installed by others. The electrical sub-contractor shall liaise with the specialist contractor to provide all required power supplies for distribution equipment etc. The electrical sub-contractor shall install an additional twin switched socket outlet adjacent each TV connection point for the installation of a TV etc. by others. The electrical sub-contractor shall provide a main spine of cable containment to allow installation of the system however the specialist contractor shall supply and install all secondary and final containment requirements. 2.15 DATA SYSTEM The electrical sub-contractor shall employ a specialist installer to modify the existing data system as part of a structured wiring installation. The existing number of points shall be retained with the following minimum achieved: - Back office: 10no points Reception desk – 6no points Meeting room – 2No Sales area – 2No data, 2No telephone & 2No double sockets. All main Containment Systems and Power supplies required by the specialist Data installer shall be installed by the Contractor All Structured cabling CAT 5E shall be supplied and installed by the contractor, including all final connections. Each data point shall be cabled back to the existing wall mounted data rack located in the back office. Under no circumstances shall cables be loose laid or run parallel or within 300mm of power cabling systems. Refer BS 7671. 2.16 CCTV, INTRUDER, ACCESS & INTERCOM SYSTEMS The existing security systems shall be retained. The electrical sub-contractor shall allow for protection of the systems during the works on site. The electrical sub-contractor shall modify or relocate items of equipment as required to suit the changes to internal partitions and ceilings. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 The electrical sub-contractor shall allow for the temporary disconnection and reinstatement of all ceiling mounted equipment that is affected by the installation of a new ceiling. The electrical sub-contractor shall be responsible for the full reinstatement of all systems to the satisfaction of the client and project engineer. An initial survey and condition report would be beneficial in this regard to highlight any existing issues before works commence. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 MECHANICAL SERVICES INSTALLATION This section sets out the design parameters for the installation of the mechanical services installation within the development. Key parameters are given that are to be utilised for the design of each of the elements All Equipment selections shall be approved by the client or their appointed representative prior to installation. 3.01 DESIGN PARAMETERS Environmental Criteria 300 C dry bulb @ 220C wet bulb External Ambient (summer) -40C dry bulb @ 100% saturation External Ambient (winter) Internal Design Condition (summer) 220C (where comfort cooling is provided) Internal Design Condition (winter) 210C NO NEW HUMIDITY CONTROL SHALL BE PROVIDED. Miscellaneous Heat Gains 10W/m2 Lighting gains Occupancy gains (per person) Occupancy level When seated Active 95W Sensible 200W Sensible 70W Latent 100W Latent TBC by the client within each area Solar Gains Solar gains shall be calculated using an industry Standard Computer selection programme – All glazing details and shading/internal blinds shall be provided by the project Architect Fabric Losses Fabric lloss should be based on the environmental criteria set out previously and the U values set out below: - (Project Specific U Values shall be confirmed with the Architect) Fabric Roof Floor Slab Walls Glazing Vertical U Value (W/m2K) TBC by Architect prior to final design TBC by Architect prior to final design TBC by Architect prior to final design TBC by Architect prior to final design The building is existing and is not subject to Part L regulations as a new build and allowances must be made for U-values and air infiltration in accordance with historical data where required and the U-values available where provided. The designer shall allow for these infiltration rates within their calculations for heating and cooling load. The heating/cooling system shall be designed to achieve the desired room temperatures within 1 hour of activation. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Miscellaneous Data Room Design Noise Levels NR Value Changing Areas Corridor Fitness Suite Crèche Office Multi Purpose Room Fitness Suite Spinning Studio Studio Cafe WC Areas 45 40 45 45 35 40 45 45 45 40 45 External noise criteria (plant) 55dB(A) at the site boundary (min) Or to suit any local planning requirements, whichever is the more stringent the contractor shall include for all attenuation requirements, both atmosphere and job side. Attenuators shall be installed up and/or downstream of the plant being attenuated, these shall generally comprise rectangular or circular pod type attenuator with stilted cores. Duct Velocities Duct velocities shall be as recommended in DW 144 and within CIBSE guidelines. The velocities selected shall not exceed noise levels specified. 3.02 SYSTEM DESCRIPTIONS Heating LPHW The mechanical services design shall be in accordance with the parameters stated above. The existing LPHW boilers within the plant room are to remain. These are Remora 610 ECA boilers which appear to have been installed recently. Currently the heating to the development is provided by a variety of LPHW emitters to the various areas. Many of the areas to be refurbished will omit the existing LPHW radiators and pipework and be replaced with heat recovery ventilation air handling equipment and new heat pump units. Where LPHW heating is to be retained and relocated, heating shall be provided with heating via wall mounted radiators on a LPHW 2 pipe circuit, with flow & return temperature 820C & 710C respectively. All radiators shall be low surface temperature type in all customer areas and flat panels in the corridor/staff areas. Existing heating plant within the plant room is to be retained. The boiler rooms shall be vented in accordance with the 1999 Gas Safety Regulation requirements. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 All radiators shall be provided with thermostatic radiator valves on the flow & lockshield valves on the return for balancing purposes. All connections shall be bottom opposite ends. All pipework shall be mild steel shall be routed in ceiling voids to the radiator position – drops down the face of walls shall be boxed in by others (all to be in the corners of rooms), all pipe routes and final connections to Radiators shall be agreed with the Architect, client and their appointed representative. Heat Pump Air Conditioning In areas where comfort cooling is to be installed which include the new studio, spinning studio, fitness suite extension, back office and crèche heat pumps will also provide heating to these areas via a variety of wall and ceiling mounted indoor units with external condensers mounted on the roof plant level above the new fitness suit extension or externally to the rooms where maximum pipe lengths are exceeded. The reception and cafe areas are to be heated via the installation of a new recuperating air handling unit to include a LPHW heating coil and frost coil fed from the LPHW system. Comfort cooling & heating shall be provided to the new studio, spinning studio, fitness suite extension & multi-purpose room. The contractor is to carry out heat loss and gain calculations to ascertain the required heating and cooling loads to achieve the required internal conditions. The indoor units, which shall be a variety of wall mounted and ceiling mounted units, shall be served via external condensing units and 2 pipe distribution pipework. Units shall be fitted with condensate pumps to lift condensate water to a gravity drainage system in the ceiling void. The condensers shall be located external to the rooms they serve and shall be provided with protective cage to prevent vandalism where required. The contractor shall provide single phase supplies to IP54 rated external isolators adjacent to the outdoor units Control shall be given by the local control unit mounted locally to the unit. A master time enable shall be derived from the H&V control panel to ensure all units are switched ‘Off’ outside normally occupancy times. A setback temperature of 160C shall be maintained at all times. 3.03 DOMESTIC WATER SERVICES Hot & cold water services shall be installed throughout the development to align with the architects layouts i.e WC’s, showers, cleaner’s rooms, serverys etc. These shall be fed from the existing DWS systems currently in place. The local water authority shall be contacted by the contractor, to advise them that works are being undertaken , as required by the Water Supply (Water Fittings) Regulations 1999. The contractor shall issue all drawings to the local water authority for their comment and approval. The contractor shall arrange to meet the representative of the local water authority on site prior to practical completion and survey the development to ensure the whole development is compliant with the Water Supply (Water Fittings) Regulations 1999. All remedial works Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 necessitated by the works shall be undertaken by the contractor and a compliance certificate issued to the client. Local Water Authority - TBC Tel TBC All pipework shall be insulated in accordance with Volume 3b of this series of documents Care shall be taken to ensure no ‘dead legs’ contained in the water pipework configuration where existing services are affected and as part of the new installation on both hot and cold water services. Cold Water Domestic cold water services shall be provided to all areas, either tanked or mains fed for drinking purposes in accordance with the architect’s layout. The existing incoming water supply shall be retained for reuse. The contractor shall include a provision sum for Water Softening equipment that maybe required if the levels of hardness in the area are above 7 Degrees Clark. The contractor shall ensure that there is adequate water pressure to serve the new requirements of the domestic water services. Care shall be taken to ensure no ‘deadlegs’ contained in the water pipework configuration. The whole installation shall be compliant with The Water Supply (Water Fittings) Regulations 1999. The materials utilised for the cold water installation shall be Copper table X, where concealed or in plant areas. All exposed pipework drops in general areas shall be chrome plated, and shall be complete with ceiling rosettes where pipes drop out of ceiling voids. Alternatives will be considered, but shall only be utilised with the express written approval of the client and/or their appointed representative. No water services shall be installed within any floor construction. Hot Water Domestic hot water services shall be provided to all areas. 2no. gas fired boilers within the plant room provide heat to an existing 1000l calorifier which is stored at 60oC. This provides domestic water services to the leisure centre with the exception of point of use water heaters and the sports hall changing areas. Where the existing installation does not comply, the contractor must allow ensuring that all areas containing gas fired equipment shall be vented in accordance with The 1999 Gas Safety Regulation requirements. High and low ventilation must be present and operational within plant rooms containing gas fired equipments. Domestic hot water flow and return temperatures shall be 600C – 500C respectively. All hot water outlets for hand washing & for bathing will be provided with mixers to give a delivery temperature of 43oC – Thermostatic mixing valves shall be within 1.5m of the outlet it is serving. All hot water outlets for showers will be provided with mixers to give a delivery Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 temperature of 41oC. Thermostatic mixing valves shall be within 1.5m of the outlet tap it is serving. Hot water supplies to sinks and cleaners sinks are not to be thermostatically mixed and are to deliver water up to 60oC. The materials utilised for the hot water installation shall be Copper table X, where concealed or in plant areas. All exposed pipework drops in general areas shall be chrome plated, and shall be complete with ceiling rosettes where pipes drop out of ceiling voids. Alternatives will be considered, but shall only be utilised with the express written approval of the client and/or their appointed representative. No water services shall be installed within any floor construction. 3.04 GAS MAINS SUPPLY The existing gas supply to the development does not need to be modified due to these works. It is not envisaged that a gas upgrade is required. All existing pipework routes through the building shall be ventilated. 3.05 DUCTWORK INSTALLATIONS All ductwork shall be selected and installed in accordance with DW144 and DW 171. Alternatives to galvanised sheet steel ductwork shall be considered. The installation of alternative systems must be approved by the client or their appointed representative prior to installation. Fire dampers shall be provided to align with the fire compartmentation strategy of the building. The contractor shall allow for all items in this respect – refer to the Architect’s drawings. Ductwork systems shall be pressure tested in accordance with Part L of the building regulations. 3.06 HVAC CONTROLS Whilst the majority of the new plant and equipment to be installed during the refurbishment can be stand-alone, the additional air handling plant to the cafe will remain under the control of the existing BMS system. An HVAC Control System exists to control & monitor the HVAC installation and is located within the building plant room. The contractor shall be responsible for all liaison in this respect. System schematic drawings and ‘Point Schedules’ shall be issued to the client or their appointed representatives for comment prior to installation panel facia layout detailing all hand/off/auto switches shall be issued for the client or their appointed representatives approval. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 3.07 MISCELLANEOUS MECHANICAL VENTILATION SYSTEMS The Contractor shall design, supply and install mechanical ventilation systems to the following areas to comply with the Building Regulations and CIBSE guides. Area Air Change Rate/hr WC’s Shower Cleaner’s Store Staff Room Plant Room 10 ACH 10 ACH 6 ACH 6 ACH 6 ACH Café/Reception 8l/s/p Back Office Crèche Multi-purpose/Office/Mtg N/V N/V 6 ACH Multi Purpose Room 6 ACH Fitness Suite Extension 12l/s/p Studio 12l/s/p Spinning Studio 15l/s/p Control Via PIR with run on timer (15mins) Via PIR with run on timer (15mins) Via PIR with run on timer (15mins) Via PIR with run on timer (15mins) Local thermostat switched on temperature rise + combustion ventiltion Roof mounted AHU -time controlled by BMS equipment. Positive pressure. Opening window Opening windows Heat recovery ventilation c/w pre-heat and re-heat electric heater batteries Heat recovery ventilation c/w pre-heat and re-heat electric heater batteries Heat recovery ventilation c/w pre-heat battery switched via PIR Heat recovery ventilation c/w pre-heat battery switched via PIR Heat recovery ventilation c/w pre-heat battery switched via PIR Client to provide room data sheets with occupancy levels included. Make-up Air Make up air systems shall be provided via AHU’s mounted in accessible/maintainable locations such as within ceiling voids, store rooms etc. Make up air shall be introduced via door transfer grilles with intumescent fire blocks where fire barriers are penetrated. Door transfer grilles shall be sized to allow the correct make up air volume at a velocity no greater than 2.5m/s.The colour of all door transfer grilles shall be approved by the Architect. The systems shall comprise of wall or duct mounted fans controlled as noted above, all power supplies shall be derived from local distribution boards. All fans shall be located in accessible & maintainable locations. All ductwork shall be as previously described and shall be c/w fire dampers where they pass through fire compartment walls – refer to fire strategy drawings for details of walls that a fire rated. Fans shall either be wall mounted or duct mounted and shall discharge through louvers/roof cowls – louvres/roof cowls shall be provided by the contractor and shall be a colour approved by the project Architect. Extract grilles shall be egg crate type finished in white. Supply grilles shall be 4 Way discharged finished in white. All grilles shall be tamperproof. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 All openings above 300mm shall be fitted with burglar bars. 3.08 KITCHEN AREA VENTILATION Servery supply and extract ventilation is to be via the air handling plant mounted on the roof above the reception area. 3.09 POWER SUPPLIES TO MECHANICAL PLANT Power supplies to mechanical plant, i.e. air handling equipment and ancillary equipment shall be derived from the H&V control panel located in the first floor plantroom. As previously noted power supplies to comfort cooling units and extract fans shall be derived from local distribution boards. 3.10 ABOVE GROUND DRAINAGE The contractor shall design, supply & install the above ground drainage system strictly in accordance with BS EN 12056-2:2000. All above ground drainage for WCs, showers, baths, sinks, WHBs, kitchen equipment & specialist equipment noted on the architects layout. All sanitary ware shall be included as per the HCD specification. The contractor is responsible for all above ground drainage only. All drainage shall be connected to soil & vent pipes terminating externally above roof level under no circumstances shall AAV ‘Durgo’ valves be utilised. SVPs shall discharge at least 900mm from any opening and shall terminate with a proprietary wire cage. All condensate connection from comfort cooling units shall be run to the nearest cleaner’s room drain position and shall be insulated; final connections to drain shall be via a trapped tundish Minimum trap sizes shall be as follows:Equipment Sink Urinals WHB Dishwasher/Washer Min Trap Size 42mm 42mm 35mm 42mm Depth of Seal 75mm 75mm 75mm 75mm Rodding eyes shall be provided in readily accessible locations, i.e such that rods can easily be inserted Materials Soil Stacks/Vent pipes WC/Urinals WHB Branch connections Kitchens/Dishwashers/Washers /Cleaners Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 - uPVC Solvent welded uPVC Solvent welded uPVC Solvent welded uPVC Solvent welded 4.00 GENERAL 4.01 TESTING AND COMMISSIONING The contractor shall include for the building services installation and specialist system to be tested and commissioned strictly in accordance with the requirements of all the relevant British Standards as appropriate to each elemental item of equipment or system. The whole of the Electrical Services Installation shall be tested in accordance with the following and issue the following appropriate test certificates:- BS7671 BS5266 BS6651 BS5839 CIBSE : : : : : IEE Wiring Regulations Emergency Lighting Lightning Protection Systems Fire Alarm Commissioning codes The Contractor shall submit on completion NICEIC, Emergency Lighting, Fire Alarm and Electrical Installation Test Certificates. The Contractor shall provide all test equipment and provide current calibration certificates. 4.02 AS FITTED DRAWINGS AND OPERATING AND MAINTENANCE MANUALS The Contractor shall provide a full package of ‘As Installed’ drawings and Operation & Maintenance Manuals – These shall be vetted by the client’s appointed representative and any comments incorporated The Contractor shall prepare the Operation & Maintenance Manuals in accordance with BSRIA’s code of practice for provision of Operation & Maintenance documentation 3no. copies of Operation & Maintenance manuals & drawings shall be provided 2no. in CD format 2 No Hard Copies. The full documentation (post audit and update) shall be issued at practical completion The record documents shall comprise:1) As Fitted Electrical & Mechanical Installation Drawings. A separate set of information for each trade 2) Specialist System Information. I.e BMS – I.T, Telephones - etc 3) Operation and Maintenance Manuals. The Operation and Maintenance Manuals shall be encased in A4 size plastic covered loose leaf, 4 ring binders generally as follows:a) b) c) Section 1 Section 2 Section 3 d) e) Section 4 Section 5 Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013 Index Description of Design Intent Details of Equipment, Manufacturers Data Sheets etc. Description of Operation of Specialist Plant and Equipment. Details of planned maintenance required to f) Section 6 g) Section 7 plant and equipment including spare parts. Set of Record Drawings and Specialist Installation drawings. Telephone numbers of Sub-Contractors, Specialist Suppliers, Equipment Suppliers. The Contractor shall submit the record drawings prepared using AUTOCAD. The Contractor shall submit a draft of the Operating and Maintenance Manuals 4 weeks prior to handover for comment. Active Nation – Greenbank Leisure Centre Volume 2 M&E Performance Specification – Design Criteria Issue 1 – June 28th 2013