Specification Clause Dwellings: Continuous Mechanical Ventilation (Passivent iMEV) Passivent iMEV ventilation system Provide a Passivent ventilation system complying with Building Regulations (England and Wales) Approved Document F OR Building (Scotland) Regulations Technical Handbook Domestic Section 3 OR Building Regulations (Northern Ireland) Technical Booklet K OR Building Regulations (Republic of Ireland) Technical Guidance Documents Part F by means of a whole house intelligent mechanical extract ventilation (iMEV) system comprising: Inlets Either manual or humidity controlled wall / window inlet vents. All vents to be sited in habitable rooms as follows: TVES4 / A101 ~ Energy Saver Window Vent - Automatic Humidity Sensitive Window Inlet operating between 47 - 65% Relative Humidity and external Canopy Grille, allowing 2,760mm2 equivalent area in the fully open position. One vent to be located in each habitable room. TVES4dB / A101dB ~ Acoustic Energy Saver Window Vent - Automatic Humidity Sensitive Window Inlet operating between 47 - 65% Relative Humidity and external Canopy Grille, allowing 2,760mm2 equivalent area in the fully open position, and offering up to 39dB Dn,e,w acoustic attenuation. One vent to be located in each habitable room. DV4 ~ Delta Vent window tricklevent and grille with sliding manual control to allow 2,800mm2 equivalent area of ventilation, and optional trickle facility for when in closed position. One vent to be located in each habitable room. FV4 ~ Frame Vent window tricklevent and grille with manual control to allow 3,120mm2 equivalent area of ventilation, and optional trickle facility for when in closed position. One vent to be located in each habitable room. Passivent Fresh 80 ~ Manually controlled wall ventilator, allowing 2,220mm2 equivalent area of ventilation in the fully open position. One vent to be located in each habitable room. Passivent Fresh 90 ~ Manually controlled wall ventilator, allowing 2,630mm2 equivalent area of ventilation in the fully open position. One vent to be located in each habitable room. Passivent Fresh 100 ~ Manually controlled wall ventilator, allowing 3,200mm2 equivalent area of ventilation in the fully open position. One vent to be located in each habitable room. Passivent Fresh 99H ~ Humidity controlled wall vent to vary ventilation rate in line with relative humidity, allowing 3,350mm2 equivalent area in the fully open position. One vent to be located in each habitable room. Specification Clause Passivent Fresh TLF ~ Manually controlled wall ventilator, allowing 2,540mm2 equivalent area of ventilation in the fully open position. One vent to be located in each habitable room. TVALdB 450 ~ Manually controlled acoustic window ventilator, allowing 2,500mm2 equivalent area of ventilation, and offering up to 40dB Dn,e,w acoustic attenuation. One vent to be located in each habitable room. TVALdB 800 ~ Manually controlled acoustic window ventilator, allowing 2,012mm2 equivalent area of ventilation, and offering up to 42dB Dn,e,w acoustic attenuation. One vent to be located in each habitable room. Passivent Fresh 80dB ~ Manually controlled wall ventilator, allowing 2,220mm2 equivalent area of ventilation in the fully open position, and offering up to 50dB Dn,e,w acoustic attenuation. One vent to be located in each habitable room. Passivent Fresh 90dB ~ Manually controlled wall ventilator, allowing 2,630mm2 equivalent area of ventilation in the fully open position, and offering up to 45dB Dn,e,w acoustic attenuation. One vent to be located in each habitable room. Passivent Fresh 100dB ~ Manually controlled wall ventilator, allowing 3,200mm2 equivalent area of ventilation in the fully open position, and offering up to 42dB Dn,e,w acoustic attenuation. One vent to be located in each habitable room. Passivent Fresh 99HdB ~ Acoustic Humidity controlled wall vent to vary ventilation rate in line with relative humidity, allowing 3,350mm2 equivalent area in the fully open position, and offering up to 45dB Dn,e,w acoustic attenuation. One vent to be located in each habitable room. Passivent Fresh TLFdB ~ Manually controlled wall ventilator, allowing 2,540mm2 equivalent area of ventilation in the fully open position, and offering up to 44dB Dn,e,w acoustic attenuation. One vent to be located in each habitable room. Extracts One extract grille to be located in each wet room as follows. Kitchen A121 ~ Automatic Humidity Sensitive extract providing 15m³/hr (min) to 75 m³/hr (max) @ 80Pa when operating between 30-75% relative humidity. Extract Diameter: 160mm. Spigot size: Ø 125mm. Bathroom A121 ~ Automatic Humidity Sensitive extract providing 15m³/hr (min) to 75 m³/hr (max) @ 80Pa when operating between 30-75% relative humidity. Extract Diameter: 160mm. Spigot size: Ø 125mm. En-suite A121 ~ Automatic Humidity Sensitive extract providing 15m³/hr (min) to 75 m³/hr (max) @ 80Pa when operating between 30-75% relative humidity. Extract Diameter: 160mm. Spigot size: Ø 125mm. Utility Room A121 ~ Automatic Humidity Sensitive extract providing 15m³/hr (min) to 75 m³/hr (max) @ 80Pa when operating between 30-75% relative humidity. Extract Diameter: 160mm. Spigot size: Ø 125mm. Specification Clause WC A121 ~ Automatic Humidity Sensitive extract providing 15m³/hr (min) to 75 m³/hr (max) @ 80Pa when operating between 30-75% relative humidity. Extract Diameter: 160mm. Spigot size: Ø 125mm. Other A121 ~ Automatic Humidity Sensitive extract providing 15m³/hr (min) to 75 m³/hr (max) @ 80Pa when operating between 30-75% relative humidity. Extract Diameter: 160mm. Spigot size: Ø 125mm. Fan Remotely located central A151DCH extract fan ~ Humidity Controlled Central Extract Fan designed to run continuously, providing varying levels of extraction from a number of grilles relative to humidity levels. Dimensions: H 326mm x W 303mm x L 271mm. Weight: 3.4kg Voltage: 230V. Appendix Q: up to 0.4 w/l/s. Spigot size: Inlet: 4 x Ø 125mm. Exhaust: Ø150mm.Humidity controlled central extract fan ducted to a roof terminal. Fan to be Energy Savings Trust Best Practice compliant and have the following specific fan powers in line with Appendix Q test methodology: Kitchen + 1 additional wet room: Kitchen + 2 additional wet rooms: Kitchen + 3 additional wet rooms: 0.36w/l/s 0.30w/l/s 0.29w/l/s Ducting All ducting in roof spaces and other unheated spaces to be fully insulated with 25mm insulation. The system to be Passivent iMEV Whole House system supplied by Passivent Limited, 2 Brooklands Road, Sale, Cheshire, M33 3SS. Telephone: 0161 905 5700, fax: 0161 969 5346, email: technical@passivent.com. Installation to be in accordance with the manufacturer’s instructions and to be carried out by a Passivent Mastercare trained installer holding a current certificate. Layout and installation must comply with any design recommendations supplied.