Nexans Cabling Solutions Field Testing Procedures of Optical Fibre Cabling Nexans Cabling Solutions Alsembergsesteenweg 2, b3 1501 Buizingen - Belgium Edition July 05, 2002 Revision 1.2 Table of Contents 1. INTRODUCTION ................................................................................................. 3 2. THE NEXANS CERTIFIED SYSTEM WARRANTY ............................................ 3 3. FIELD TEST PROCEDURES .............................................................................. 4 3.1. Background ......................................................................................................................................... 4 3.1.1. Acceptable link loss calculation ......................................................................................................... 4 3.1.2. Loss Parameters and limits................................................................................................................. 5 3.2. Field-testing equipment for Nexans Certified System installations ........................ 5 3.3. Loss testing methodologies .......................................................................................................... 7 3.3.1. Multimode fibre link ............................................................................................................................ 7 3.3.2. Singlemode fibre link ........................................................................................................................... 7 3.4. The material you need .................................................................................................................... 7 3.5. Test tool configuration ................................................................................................................... 8 3.6. Testing.................................................................................................................................................... 8 3.6.1. Single fibre measurement.................................................................................................................... 9 3.6.2. Dual fibre measurement .....................................................................................................................11 3.7. OF Warranty Application............................................................................................................13 3.7.1. Warranty certification procedure ....................................................................................................13 3.7.2. OF Warranty Application form .......................................................................................................13 4. TROUBLESHOOTING .......................................................................................15 5. ANNEXES ..........................................................................................................16 5.1. A1 - Normative references ..........................................................................................................16 5.2. A2 - Fibre Optic Loss Measurement .....................................................................................17 5.2.1. Definitions ..............................................................................................................................................17 5.2.2. Fibre Optic cabling compliance testing requirements ................................................................17 5.2.3. Loss Parameters and limits................................................................................................................18 5.2.4. Acceptable link loss calculation ........................................................................................................19 5.2.5. Other requirements and limitations ................................................................................................20 OF testing procedure ©Nexans Cabling Solutions 2002 Page 2 of 20 July 05, 2002 Rev 1.2 Field Testing Procedures of Optical Fibre Cabling 1. Introduction This document specifies the procedure for field-testing the transmission performance of Nexans installed optical fibres links in premises. The procedure complies with the ISO/IEC 14763-3 standard. The ISO/IEC 14763 standard specifies the implementation and operation of customer premises cabling. The part 3 of this ISO document (14763-3) details test procedures for optical fibre cabling designed in accordance with ISO/IEC 11801 and installed according to the recommendations of ISO/IEC 14763-2 (Planning and installation of customer premises cabling). The optical link test configuration as defined further in this document shall be used to verify the performance of permanently installed OF cabling. All 100 % of the installed OF links have to be tested and must pass the acceptance criteria in order to apply for the Nexans performance warranty certificate. Make sure that the operator doing the tests has been properly trained and that the field-test equipment and cords work properly. The tester has to be normalised in accordance with the manufacturer’s guidelines. Test limits and required results are specified further in this document. 2. The Nexans Certified System Warranty For a complete overview of the Nexans Cabling Solutions Warranty for the different systems and products, please refer to the respective warranty modules OF testing procedure ©Nexans Cabling Solutions 2002 Page 3 of 20 July 05, 2002 Rev 1.2 3. Field Test Procedures 3.1. Background Fibre-optic Tests applied to links and exclude equipment and work area cord. OF Attenuation testing is used to verify the initial performance of the installed link. The attenuation of the link is measured using the insertion loss method. This method uses an optical source and an optical power meter to compare the difference between two optical power levels: First measuring how much light is put into the link at the near end (P1) Then measuring how much light exits at the far end of the link (P2) These absolute optical power levels are measured in dBm. 0 dBm is equivalent to 1 mW of power. The attenuation values (in dB) are determined by subtraction of the two absolute power levels (in dBm). Attenuation or Loss (dB) = P1 (dBm) – P2 (dBm) If the measured attenuation of the links has a lower value than the acceptable link attenuation calculated, the subsystem is OK and can be certified. If not, additional actions to rectify the problem will have to be taken. 3.1.1. Acceptable link loss calculation The measured value of attenuation of a FO link should not exceed the sum of allowable attenuation of each component of the link. These components are The fibre-optic cable The termination OF connectors The splices (if any) The specifications within the ISO 11801 standard are representative of the following formulas Link loss (dB) = Cable loss + Connectors loss + Splices loss Cable loss (dB) = Cable length (km) x Loss coefficient (dB/km)* Connector loss (dB) = number of connector pairs x connector loss (dB)* Splice loss = number of splices x splice loss (dB)* *: from Table 1 – Attenuation criteria The Cable length shall be optically measured or calculated using cable sheath length markings. (Refer also to Annex 2) OF testing procedure ©Nexans Cabling Solutions 2002 Page 4 of 20 July 05, 2002 Rev 1.2 3.1.2. Loss Parameters and limits The attenuation of one link at specified wavelength shall not exceed the sum of the specified attenuation values for all the components of that link. Table 01 - Attenuation criteria Loss/km Optical Fibre type 850 nm 1310 nm 1550 nm (in dB) Multimode 62,5 µm 3,5 1,5 NA Multimode 50 µm 3,5 1,5 NA Singlemode NA 1,0 1,0 3.2. Loss Connector Splice (in dB) 0,75 0,3 0,75 0,3 0,75 0,3 Field-testing equipment for Nexans Certified System installations A stabilized light source and an optical power meter (Also known as Loss Test Set) are used to measure the attenuation of each terminated fibre link. Factory-terminated OF test cords shall be used to ensure accurate results. Test equipment shall be capable of measuring relative or absolute optical power in accordance with IEC 61280-4-1 for multimode fibres and IEC 61280-4-2 for singlemode fibres. Single fibre measurement test set can be used but Nexans Cabling Solutions recommends the use of enhanced measurement test set designed for testing of FO cabling subsystem in premise LAN. Pre-programmed OF field Certification tools Instrument manufacturers have introduced fibre test adapters to be attached to their standard balanced cabling test equipments. These cable testers comply with the standard specifications and provide features to ease and speed up the testing and the certification process: Test two fibres and two wavelengths at one time Measure optical loss, fibre length and propagation delay Save OF measurement results Utilize specific software to manage results and generate electronic reports Calculate the loss budget and report the “Pass/Fail” margin against the ISO standard (and Gigabit Ethernet standard for some adapters) Test certify and document fibre and copper with one tester OF testing procedure ©Nexans Cabling Solutions 2002 Page 5 of 20 July 05, 2002 Rev 1.2 The specific fibre test adaptors to be used are: Table 03 – Fibre test adaptors Brand name Fluke Microtest Agilent Ideal Balanced cable tester Multimode OM1 & OM2 OM3 DSP serie FTA410S/420S OMNIScanner OMNIFIBER MM SmartProbe WireScope 350 N2597A-030 Lantek 6 and 7 FiberKit+MM FTA440S ------------- Singlemode 1 test for both λ FTA430S OMNIFIBER SM SmartProbe N2597A-040 Yes Yes FiberKit+ALL No No 1 test for both λ (wavelengths): Fluke and Microtest OF test adaptors are able to test the attenuation for both wavelengths (850nm + 1310nm for MM – 1310nm + 1550nm for SM). Other adaptors (Agilent and Ideal) can only test one wavelength in each direction. In other words, it is necessary to swap the fibres during the testing process to have both fibres measured at both wavelengths. The use of dual wavelengths test adaptors is quicker and safer. Furthermore, the swap of the fires could become a problem when testing SFF terminated fibres: no swap possible at least for some of them (MT-RJ). Maintenance of the field instruments involves ensuring the adapters and connectors are maintained in good condition. Follow the manufacturer’s guidelines to keep the rechargeable batteries in good condition. Always store the instrument and equipment in a case. Software upgrades are relatively easy and often contain instrument performance improvements. Software upgrades are usually obtained directly by downloading new executable files into a computer and transferring the files to the field instruments. It is a good idea to check the manufacturer’s web site on a frequent basis to ensure the field tester has the latest software and is up-to-date with the revisions to standards limits. Optical Time Domain Reflectometer (OTDR) OTDR shall not be used to measure cable plant loss. No official standard regarding OTDR testing has been developed for general or LAN use Furthermore, the use of an OTDR in short LAN lengths is expensive and performance is usually slow. The limited distance resolution of the OTDR makes it very hard to use in a LAN or building environment. OTDR Loss measurements have to be carefully interpreted by a trained technician and are not as accurate as direct measurement of the attenuation. Therefore, OTDR can only be used for length measurement and for fault location. Nexans Cabling Solutions will not accept loss measurement performed with an OTDR. Warranty application If the loss test set doesn’t provide test results storage features, the measurements must be transmitted to Nexans Cabling Solutions (NCS) using the NCS OF data form. More information can be found in the chapter 3.7: OF Warranty Application OF testing procedure ©Nexans Cabling Solutions 2002 Page 6 of 20 July 05, 2002 Rev 1.2 3.3. Loss testing methodologies 3.3.1. Multimode fibre link The test procedure described bellow is based on the use of the “one-jumper method” specified by Method 2 of IEC 61280-4-1. This procedure is used for testing links for which the connector loss is a significant portion of the total link attenuation. This is the case for LAN premises links. This method is only valid for links terminated with single-fibre connectors such as SC and ST connectors. SC is the preferred connector specified in the ISO11801 standard. However, SFF connectors can also be used. Small Form Factor (SFF) connectors Adapted test solutions to be used to certify links terminated with SFF connectors will be issued. In particular, specific methodologies will be issued to match the unique characteristics of the SFF connectors: MT-RJ (dual-fibre connector and pinned + unpinned), LC, VF45 and OptiJack. 3.3.2. Singlemode fibre link The test procedure to be applied is the same and is based on the use of the “one-jumper method” specified by Method 1a of IEC 61280-4-2. This procedure is used for testing links for which the connector loss is a significant portion of the total link attenuation. This is the case for LAN premises links. This method is only valid for links terminated with single-fibre connectors such as SC and ST connectors. SC is the preferred connector specified in the ISO11801 standard. However, SFF connectors can also be used. Small Form Factor (SFF) connectors Adapted test solutions to be used to certify links terminated with SFF connectors will be issued. 3.4. The material you need To test fibre optic links, you will need the following items: Dual wavelength fibre-optic source and power meter Wavelengths: 850 & 1310 nm for MM fibres / 1310 & 1550 nm for SM fibres. Launch and Receive reference single fibre cords Connectors (ST, SC, FC, MT-RJ…) and fibre types (MM 50µ, MM 62.5µ, SM) compatible with the OF subsystem to be tested. These cords shall be factory terminated and maintained in perfect shape. Mating adapters for connectors (Coupling) Not necessary for most of the procedures but it could be useful to check the quality of the reference cords or to analyse a failed link. Lint free cleaning wipes and pure isopropyl alcohol. Airborne dirt (transported by the air) use to be as big as the core of a SM fibre and big enough to cause high loss in MM fibre. Always clean connectors before testing. A fibre scope This tool will be useful to inspect the connectors and for trouble-shooting NCS OF Warranty Application Data form if the loss test set doesn’t provide test results storage features OF testing procedure ©Nexans Cabling Solutions 2002 Page 7 of 20 July 05, 2002 Rev 1.2 3.5. Test tool configuration Check the loss test set to be sure it is fully functional, the battery is charged, and all the necessary equipment or adapters are available. Inspect the connectors of the reference cords for polish and cleanliness. Nexans Cabling Solutions recommend the use of a fibre scope to perform this inspection. Calibration and set-up Calibration and set-up procedures vary per field tester. Check with the field tester documentation for the correct procedure. When using Pre-programmed OF field-testing certification tools, the required settings also include the following items: test standard, fibre type, adapter type, adapter and splice numbers, index of refraction… 3.6. Testing To measure the loss of an OF link, we have to compare the difference between two optical power levels: First measuring how much light is put into the link at the near end (P1) Then measuring how much light exits at the far end of the link (P2) The attenuation value (in dB) is determined by subtraction of the two absolute power levels (in dBm). Attenuation or Loss (dB) = P1 (dBm) – P2 (dBm) OF testing procedure ©Nexans Cabling Solutions 2002 Page 8 of 20 July 05, 2002 Rev 1.2 3.6.1. Single fibre measurement This procedure has to be used when testing with basic optical source and power meter. Using a basic loss test set, fibres have to be tested one at a time. If the loss test set doesn’t provide test results storage features, the measurements must be transmitted to Nexans Cabling Solutions (NCS) using the NCS OF data form. Step 1: Reference – P1 measurement Fig.1 - Reference power mea surement Source Not to be disrupted once reference is set Reference launching cord P1 mea sure for both wavelengths (in dBm) Power Meter Disconnecting cord end Clean all fibre connections Dirt is harmful to connectors and causes loss which affect measurements. Always cover the connectors with a dust cap when not in use. Power Meter: Select the dBm range Source: Select the wavelength () 850 nm and 1310 nm for multimode loss test set 1310 nm and 1550 nm for singlemode loss test set For both wavelengths, measure the power at the power meter Record these values: P11 & P12 These are your two reference power levels for all loss measurements Significant notes Once the reference is set, do not disconnect the launching cord from the source. If the connection between the source output and the cord is disrupted, the reference is lost because the P1 value will most probably be different when you will reconnect the cord to the source. If you disconnect it, it is mandatory to repeat the step 1 to have a new reference before continuing the test of the links. To ensure the stability of the reference, we recommend installing the source at the Building Distributor side (OF backbone testing) to avoid any move of the source to a different location. We also recommend periodically re-establishing the reference, at least if you have to move the source or if situations indicate a need to do it. OF testing procedure ©Nexans Cabling Solutions 2002 Page 9 of 20 July 05, 2002 Rev 1.2 All optical power measurements shall be recorded to one significant digit after the decimal place (For example: -23.6 dBm) The power meter connection, the link connector and the launching cord free-end connector shall match together. If not, it will be impossible to stick to this procedure. Step 2: Test – P2 measurement Fig.2 - Test power mea surement Link under test Source Launching cord Receiving cord Adapter Adapter P2 mea sure for both wa velengths (in dBm) Link loss = (P1 - P2) Fibre + 2 connectors + splices (If a ny) Power Meter Move the power meter to the far end of the link Attach the receiving cord to the power meter Connect the free ends of the cords to the terminations of the link on both sides For both wavelengths, measure the power at the power meter Record these values: P21 & P22 Repeat the step 2 for all the fibres of the link Step 3: Test results evaluation Loss measurement calculation: o Loss1 = P11 - P21 o Loss2 = P12 - P22 Compare these results with the acceptable losses calculated in advance (refer to §3.1.1 and Annex A2) Measured loss values shall be lower or equal to the calculated ones Record the measurements values in the OF data form (Refer to §3.7: OF Warranty Application) OF testing procedure ©Nexans Cabling Solutions 2002 Page 10 of 20 July 05, 2002 Rev 1.2 3.6.2. Dual fibre measurement This procedure has to be used when testing with A dual optical loss test set OF LAN certification tools Using a dual-fibre loss test set, fibres are tested two at a time. If the loss test set doesn’t provide test results storage features, the measurements must be transmitted to Nexans Cabling Solutions (NCS) using the NCS OF data form and the evaluation of the results must be done according to the procedure described in the former chapter (3.6.1). Step 1: Reference – P1 measurement Fig.3 - Dua l reference power mea surement Not to be disrupted once reference is set Test Tool 2 reference launching cords IN OUT OUT IN Disconnecting cord ends Remote Unit P1: mea sure of the fibre pa ir for both wa velengths (in dBm) Clean all fibre connections Always cover the connectors with a dust cap when not in use Setting up for fibre tests Configure your test tool according to the users manual Select the remote unit configuration for fibre pair measurement Set the reference power levels The tester will record P11 & P12 for both fibres These are your two reference power levels for all loss measurements Significant notes Once the reference is set, do not disconnect the launching cords from the output ends (sources) of the testers. If the connection between the testers outputs and the cords is disrupted, the reference is lost because the P1 values will most probably be different when you will reconnect the cords to the sources. If you disconnect it, it is mandatory to repeat the step 1 to have new references before continuing the test of the links. OF testing procedure ©Nexans Cabling Solutions 2002 Page 11 of 20 July 05, 2002 Rev 1.2 Testing links terminated with Small Form Factor connectors (SFF) require the method to be adapted. Please refer to the specific method described in a separated document. All optical power measurements shall be recorded to one significant digit after the decimal place (For example: -23.6 dBm) The tester connections, the link connectors and the launching cords free-end connectors shall match together. If not, it will be impossible to stick to this procedure. Step 2: Test – P2 measurement Fig.4 - Fibre pa ir test power mea surement Lauching cords Not to be disrupted once reference is set OF pair Link under test Test Tool Receiving Launching IN Cords OUT Cords IN OUT Launching Adapters Link loss = (P1 - P2) Fibre + 2 connectors + splices (If a ny) Receiving Adapters Remote Unit P2 mea sure of the fibre pa ir for both wa velengths (in dBm) Move the remote unit to the far end of the link Attach the receiving cords to the test tool and the remote unit Connect the free ends of the cords to the terminations of the link on both sides Perform the test – Run the autotest When using single wavelength test heads, you have to swap the fibre during the autotest procedure. The swap shall be done on the patch panel side. Do not disconnect the launching cords from the output ends (sources) of the testers. Check the result: Pass: go to next step Fail: go to the troubleshooting chapter Save the results of the test Repeat the step 2 for all the fibre pairs of the link Step 3: Test results evaluation Check the result: Pass/Fail and headroom Pass: proceed to the measurement of the next dual OF link Fail: troubleshooting OF testing procedure ©Nexans Cabling Solutions 2002 Page 12 of 20 July 05, 2002 Rev 1.2 3.7. OF Warranty Application 3.7.1. Warranty certification procedure The procedure to be applied is similar to the one you must use to apply for a copper warranty certification. Only the new Warranty Application Form can be used to apply for a warranty and it will only be accepted in electronic format. This Warranty Application Form is similar to the previous warranty application form and the checklist that had to be used. The test results have to be saved and sent in electronic format. A hard copy may be added. Test results shall be exported from the certification tool in .fcm format from FLUKE, .mdb format from WIRESCOPE or .dat format from MICROTEST. .csv format is only accepted if the used tester tool (WAVETEK, …) does not support .fcm, .mdb or .dat formats. 3.7.2. OF Warranty Application form If the loss test set doesn’t provide test results storage features, the measurements must be transmitted to Nexans Cabling Solutions (NCS) using the NCS OF Warranty Application data form. OF Warranty Application data form explanation The data form includes 3 sheets: Data collection: legend, procedure summary and 11 data fields to be completed. Test report 1: measurement at the first wavelength (850nm for MM and 1310 for SM) Test report 2: measurement at the second wavelength (1310nm for MM and 1550 for SM) The file is foreseen to report the test of one complete OF link: 2 to 24 fibres. One report file has to be created and saved for every OF cable whatever the fibre quantity. The cells are coloured to highlight the ones that have to be filled up: Light turquoise cells: explanation / description Light Green cells: will be automatically filled up – do not type in these cells Tan cells: the value has to be chosen from the list: when the cell is selected, click on the arrow to see the list of values White cells: to be filled up On the first sheet (Data collection), there are 10 fields to be filled up: Tan and white cells. All these cells shall be filled up because these values are used to automatically fill up the TAN cells from the second and third sheet. On the two last sheets (Test reports 1 & 2), only white cells have to be filled up with the measured power values: reference value (P1) + far end measurement. The reference value is the same for all measurements performed on the same link (One value for each test report sheet: the reference value is different for each wavelength). OF testing procedure ©Nexans Cabling Solutions 2002 Page 13 of 20 July 05, 2002 Rev 1.2 If you set the reference measurement (P1) to zero in your tester, enter ‘0’ in the reference power measurement cell from sheet 2 and 3. When using the zero reference feature, your tool already perform the P1-P2 calculation. That’s why the reference power has to be set to 0. Power measurement expressed in dBm used to be negative (O dBm = 1 mW / Led output power used to be around –20 dBm). To ensure that the automatic calculation provide correct values, always type the figures with their minus sign. The calculation of the acceptable link loss is automatically done according to the fields filled up on the Data collection sheet. The margin and the Pass/Fail fields are also automatically calculated once the measured values have been typed in the corresponding cells. Fails are highlighted in red. When printing, if you select the 3 sheets beforehand (Click on the first one and shift + click on the third one), it will be numbered from 1/3 to 3/3. Not to be filled cells are locked to prevent accidental erasing of the formulas. The Excel file itself is also protected: Read only. To save your files, select File – Save as and change the file name. OF testing procedure ©Nexans Cabling Solutions 2002 Page 14 of 20 July 05, 2002 Rev 1.2 4. Troubleshooting A test failure is a measurement failure and could be caused by the cabling, the field instrument, poor installation practices, or a combination of these. Depending upon the test that failed, several diagnostic alternatives may be available. Before attempting any changes to the cabling, always ensure that the field tester is providing accurate results and the correct test configuration has been set up. The presence of dust, dirt and other contaminants at the interfaces to the cabling under test may produce misleading results and in some cases damage the cabling under test and/or the cabling interface adapter. The mating connector end faces of cabling interface adaptors and the cabling under test shall be cleaned in accordance with the connecting hardware manufacturers instructions prior to mating. Always clean the fibre end faces before making the connections. Use lint-free swabs or wipes moistened with pure isopropyl alcohol or pre-moistened wipes approved for use in fibre connectors. If no power is measured at the source, the optical source or the patch cords could be defective. If the power loss is more than expected o Fibres could be connected to the wrong port of the unit o Fibres could be swapped at one end of the link o One Patch cord could be broken o There could be one or more dirty connections in the link o Setting up of the parameters in the tester could be wrong o Patch cord(s) and fibre from the link could have a different core size If the measure of the length of cable is too long or too short, the index of refraction could have been set up correctly. DO NOT look into an active optical fibre (especially with a microscope) as harmful radiation that can cause eye damage may be present. OF testing procedure ©Nexans Cabling Solutions 2002 Page 15 of 20 July 05, 2002 Rev 1.2 5. ANNEXES 5.1. A1 - Normative references This testing procedure comply with the following International Standards: ISO/IEC 11801 - latest draft of the 2nd edition: Generic cabling for customer premises ISO/IEC 14763-3: Implementation and operation of customer premises cabling – Part 3: Testing of optical fibre cabling IEC 61280-4-1: Part 4-1: Test procedures for fibre optic cable plant and links –Multimode fibre optic cable plant attenuation measurement IEC 61280-4-2: Part 4-2: Test procedures for fibre optic cable plant and links - Single mode fibre optic cable plant attenuation measurement OF testing procedure ©Nexans Cabling Solutions 2002 Page 16 of 20 July 05, 2002 Rev 1.2 5.2. A2 - Fibre Optic Loss Measurement 5.2.1. Definitions A Link is the transmission circuit between any two telecommunications active devices not including the patch cords. Horizontal link extends from a patch panel located in the cabinet (Floor Distributor) to the telecommunications outlet (TO) at the user side. The link excludes equipment and work area cords, and cross-connections, but does includes the optional consolidation point. Intra-building primary backbone link extends from a patch panel (PP) located in the cabinet of the Building Distributor (BD) to a PP located in the Floor Distributor (FD). This link forms the main circuit between the BD and one FD. The BD is the head end of the intra-building backbone. Secondary backbone link forms a circuit between two FDs or a second (backup) circuit between the BD and the FD. Inter-building backbone link forms a circuit between the Campus Distributor (CD) and one Building Distributor. The CD is the head end of the inter-building backbone. A Channel represents the complete end-to-end path between any two pieces of telecom active equipment. The channel includes the link components, the work area cord, the equipment cord, and the cross-connect. Horizontal channel forms the end-to-end path between the user equipment (PC, phone, video equipment, printer…) and the active equipment at the cabinet side (switch, hub, PABX, video equipment). Backbone (vertical) channel forms the end-to-end path between any two pieces of active equipment located in both distributors rooms (FDs, BDs, CD). The Link and Channel definitions can be applied to both copper and optical fibre circuits. 5.2.2. Fibre Optic cabling compliance testing requirements After installation, links must be tested for compliance with the normative requirements in order to validate the installed cabling. To characterize a fibre optic (FO) circuit, we need to know its limits. One of the most important limitations for the performance of an optical fibre is the attenuation or loss. According to the applicable standards (Refer to §3.2), the end-to-end optical attenuation has to be tested for all installed FO links as a means of validating the FO cabling subsystem. End-to-end attenuation Measure of the optical power loss between cable termination points (Link measurement) Acceptable attenuation values are different for each link. The value is dependent upon the link length, the wavelength, and the number of connectors and splices. This value has to be calculated in accordance to the specifications within ISO/IEC 11801. OF testing procedure ©Nexans Cabling Solutions 2002 Page 17 of 20 July 05, 2002 Rev 1.2 To pass the test, the measured attenuation of a FO link should always be lower than the acceptable link loss value calculated for this link. Link performance If all the links pass the test, the FO subsystem will be validated but the warranted performance can vary according to the characteristics defined during the design phase. Channel performance Applications requiring a high bandwidth (example: Gigabit network applications) will only be warranted if the following elements have been chosen according to the specific needs of the customer: A: Optical fibre type: OM1, OM2, OM3, OS1 Core diameter 50µ or 62.5µ for OM types only B: Channel class: OF-300, OF-500 or OF-2000 For more information, please refer to clause 8, clause 9.4 and annex F from the second edition of the ISO 11801 standard. As the present procedure is related to field-testing we only focus on the OF measurement that will lead to the validation of the FO subsystem link performance. 5.2.3. Loss Parameters and limits The link attenuation or link loss shall be tested. The attenuation of one link at specified wavelength shall not exceed the sum of the specified attenuation values for all the components of that link. Table 01 - Attenuation criteria Loss/km Optical Fibre type 850 nm 1310 nm Loss 1550 nm (in dB) Connector Splice (in dB) Multimode 62,5 µm 3,5 1,5 NA 0,75 0,3 Multimode 50 µm 3,5 1,5 NA 0,75 0,3 Singlemode NA 1,0 1,0 0,75 0,3 OF testing procedure ©Nexans Cabling Solutions 2002 Page 18 of 20 July 05, 2002 Rev 1.2 5.2.4. Acceptable link loss calculation The measured value of attenuation of a FO link should not exceed the sum of allowable attenuation of each component of the link. These components are The fibre-optic cable The termination OF connectors The splices (if any) The specifications within the ISO 11801 standard are representative of the following formulas Link loss (dB) = Cable loss + Connectors loss + Splices loss Cable loss (dB) = Cable length (km) x Loss coefficient (dB/km)* Connector loss (dB) = number of connector pairs x connector loss (dB)* Splice loss = number of splices x splice loss (dB)* *: from Table 1 – Attenuation criteria Examples a) Link loss for 84 meters of 62.5/125µ OF terminated on field installable ST connectors Cable loss at 850nm: Connector loss: Splice loss: Acceptable Link Loss 0,084 km X 3,5 dB/km 2 X 0,75 dB 0 x 0.3 dB = 0.3 dB = 1,5 dB = 0,0 dB = 1,8 dB b) Link loss for 350 meters of 50/125µ OF terminated on SC pigtails Cable loss at 1310nm: Connector loss: Splice loss: Acceptable Link Loss 0,350 km X 1,5 dB/km 2 X 0,75 dB 2 x 0.3 dB = 0.5 dB = 1,5 dB = 0,6 dB = 2, 6 dB The Cable length shall be optically measured or calculated using cable sheath length markings. The length measurement can be performed with an Optical Time Domain Reflectometer (OTDR). The refractive index of the fibre to be tested has to be set to the right value. This parameter is used by the OTDR to calculate the length of the cable. It is so important to introduce the right value to retrieve the right length measurement from the OTDR tool. OF testing procedure ©Nexans Cabling Solutions 2002 Page 19 of 20 July 05, 2002 Rev 1.2 The refractive index of a fibre is a characteristic that may vary from one OF manufacturer to another. Here are the values to be used with the Nexans fibres. Table 02 – Index of refraction Index of refraction Optical Fibre type 850 nm 1310 nm 1550 nm Multimode 62,5 µm 1,4989 1,4935 NA Multimode 50 µm 1,4850 1,4840 NA NA 1,4710 1,4719 Singlemode 5.2.5. Other requirements and limitations Horizontal link Link length: a multimode horizontal optical fibre cabling subsystem is limited to 90 meter length Horizontal link shall be tested at 850 nm and 1310 nm in one direction Test method 2 of IEC 61280-4-1 shall be used (Refer to the testing procedure chapter) Multimode backbone link Link length: may vary upon Optical fibre type (OM1, OM2, OM3) and Channel class: OF-300, OF-500 or OF-2000 Multimode backbone link shall be tested at 850 nm and 1310 nm in one direction Test method 2 of IEC 61280-4-1 shall be used (Refer to the testing procedure chapter) Singlemode backbone link Singlemode backbone link shall be tested at 1310 nm and 1550 nm in one direction Test method A1 of IEC 61280-4-2 shall be used (Refer to the testing procedure chapter) All singlemode links shall be certified with test tools using laser light sources at 1310 nm and 1550 nm OF channel topology The models described in the ISO 11801 standard (clauses 7.2 & 7.3 – fig. 11 & 12) are applicable to horizontal and backbone cabling using copper AND fibre. That is why the same 90m-length limitation is applicable for both media. However the delivery of fibres to the TO (FTTD) will generally not require transmission equipment at the Floor Distributor. The standard allow the creation of a combined backbone/horizontal channel (Fig.13 – clause 8.4 from ISO 11801). ----------------------------- OF testing procedure ©Nexans Cabling Solutions 2002 Page 20 of 20 July 05, 2002 Rev 1.2