Fuel Cell Power Generators - A Guide For Implementation

advertisement
Fuel Cell Power Electrical Generators Permitting Guide For Telecom Providers
Installation & Permitting ..................................................................................................................................................... 4
Reference Documents ................................................................................................................................................... 4
Organizations: ............................................................................................................................................................ 4
Relevant Documents for Compliance (mandated by code or law): ............................................................................ 4
Other Referenced Documents for Compliance: ......................................................................................................... 4
International Fire Code (IFC)- implementation by state governments: ...................................................................... 5
International Fuel & Gas Code (IFGC)- implementation by state governments: ....................................................... 5
General Safety Requirements (independent of fuel or fuel cell type): ........................................................................... 6
Specific Requirements for the Fuel Cell Power System (power generator) ..................................................................... 7
Federal Communication Commission (FCC) ............................................................................................................. 7
 Definitions ......................................................................................................................................................... 7
 Components & Systems Certifications ............................................................................................................. 7
 Labeling & Signage .......................................................................................................................................... 7
NFPA 2 Hydrogen Technologies Code - 2011 edition - (reference only) .................................................................. 8
 Components & Systems Certifications ............................................................................................................. 8
NFPA 853 Installation of Stationary Fuel Cell Power Systems -2010 edition ............................................................ 8
 Components & Systems Certifications ............................................................................................................. 8
 Location, Capacity, Siting, & Setbacks ............................................................................................................ 8
 Piping, Valves, Regulators, Fuel Controls ....................................................................................................... 9
 Vents & Ventilation ........................................................................................................................................... 9
 Fire & Emergency Response ......................................................................................................................... 10
 Fire Prevention & Emergency Plan: ............................................................................................................... 10
NFPA 70 National Electric Code -2014 edition ........................................................................................................ 10
 Definitions ....................................................................................................................................................... 10
 Components & Systems Certifications ........................................................................................................... 11
 Piping, Valves, Regulators, Fuel Controls (including pressure relief devices) .............................................. 11
 Labeling & Signage ........................................................................................................................................ 11
ANSI FC 1-2012 Stationary Fuel Cell Power Systems ............................................................................................ 12
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 12
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 12
ANSI FC 3-2004 Portable Fuel Cell Power Systems ............................................................................................... 12
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 12
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 12
Specific Requirements for the Fuel Supply (including storage and delivery) .................................................................. 13
OSHA (29CFR1910): Subpart H - Hazardous Materials .......................................................................................... 13
 Definitions ....................................................................................................................................................... 13
29CFR1910.101 Compressed gases (general requirements). .............................................................................. 14
 Container types & design & storage construction .......................................................................................... 14
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 14
29CFR1910.103(b) Gaseous hydrogen systems ..................................................................................................... 15
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 15
 Container types & design & storage construction .......................................................................................... 16
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 16
 Labeling & Signage ........................................................................................................................................ 16
29CFR1910.103(c) Liquified hydrogen systems ...................................................................................................... 16
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 16
 Container types & design & storage construction .......................................................................................... 17
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 17
 Labeling & Signage ........................................................................................................................................ 17
Safe Transportation of Gaseous Hydrogen, Methane, & gas mixtures - Identified by 49CFR172.101 Hazardous
Materials Table ......................................................................................................................................................... 18
Page 1 of 43
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
Safe Transportation of Liquified Hydrogen, Liquified Methane or Natural Gas - Identified by 49CFR172.101
Hazardous Materials Table ...................................................................................................................................... 19
International Fire Code (IFC)- hydrogen & other flammable gases: ........................................................................ 20
 Definitions:...................................................................................................................................................... 20
 Components & Systems Certifications ........................................................................................................... 20
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 20
 Container types & design & storage construction .......................................................................................... 20
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 21
 Labeling & Signage ........................................................................................................................................ 21
 Fire & Emergency Response ......................................................................................................................... 21
International Fire Code (IFC)- additional requirements for hydrogen-generating and refueling operations ............ 21
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 21
International Fuel Gas Code (IFGC) - Gaseous Hydrogen Systems ....................................................................... 21
 Components & Systems Certifications ........................................................................................................... 21
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 22
 Container types & design & storage construction .......................................................................................... 22
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 22
 Labeling & Signage ........................................................................................................................................ 23
International Fuel Gas Code (IFGC) - Liquified Hydrogen Systems ........................................................................ 23
 Components & Systems Certifications ........................................................................................................... 23
International Fuel Gas Code (IFGC) - additional requirements for indoor hydrogen-generating and refueling
operations ................................................................................................................................................................. 23
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 23
 Vents & Ventilation ......................................................................................................................................... 23
NFPA 2 Hydrogen Technologies Code - 2011 edition (reference only) ................................................................... 24
 Container types & design & storage construction .......................................................................................... 24
 Labeling & Signage ........................................................................................................................................ 24
NFPA 55 Compressed Gases and Cryogenic Fluids Code - 2013 edition .............................................................. 24
 Definitions ....................................................................................................................................................... 24
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 25
 Labeling & Signage ........................................................................................................................................ 25
NFPA 55 Compressed Gases and Cryogenic Fluids Code - additional requirements for hydrogen-generating and
refueling operations .................................................................................................................................................. 26
 Definitions ....................................................................................................................................................... 26
 Components & Systems Certifications ........................................................................................................... 26
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 26
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 26
 Vents & Ventilation ......................................................................................................................................... 27
 Fire & Emergency Response ......................................................................................................................... 27
Fuel: Flammable Liquids - Methanol ............................................................................................................................ 28
OSHA (29CFR1910): Subpart H - Hazardous Materials Methanol ...................................................................... 28
29CFR1910.106 Flammable Liquids ........................................................................................................................ 28
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 28
 Vents & Ventilation ......................................................................................................................................... 29
29CFR1926.152 Flammable Liquids (Safety & Health Regulations for Construction) ............................................ 30
 Container types & design & storage construction .......................................................................................... 30
Safe Transportation of Methanol - Identified by 49CFR172.101 Hazardous Materials Table ................................. 30
 Fuel Transportation & Site Refueling ............................................................................................................. 31
 Fire & Emergency Response ......................................................................................................................... 31
Hazardous Substances - Reportable Quantity (RQ) - Methanol .............................................................................. 31
International Fire Code (IFC)- methanol & other flammable liquids: ........................................................................ 32
 Definitions ....................................................................................................................................................... 32
 Components & Systems Certifications ........................................................................................................... 33
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 33
 Container types & design & storage construction .......................................................................................... 33
 Piping, Valves, Regulators, Fuel Controls (including pressure relief devices) .............................................. 33
Page 2 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
 Vents & Ventilation ......................................................................................................................................... 34
 Labeling & Signage ........................................................................................................................................ 34
 Fuel Transportation & Site Refueling ............................................................................................................. 36
 Fire & Emergency Response ......................................................................................................................... 36
International Fuel Gas Code (IFGC) - Liquid Fuel ................................................................................................... 37
 Components & Systems Certifications ........................................................................................................... 37
NFPA 30 Flammable & Combustible Liquids Code - 2012 edition .......................................................................... 37
 Definitions ....................................................................................................................................................... 37
 Components & Systems Certifications ........................................................................................................... 38
 Location, Capacity, Siting, & Setbacks .......................................................................................................... 38
 Container types & design & storage construction .......................................................................................... 39
 Piping, Valves, Regulators, Fuel Controls ..................................................................................................... 40
 Vents & Ventilation ......................................................................................................................................... 40
 Labeling & Signage ........................................................................................................................................ 41
 Fuel Transportation & Site Refueling ............................................................................................................. 41
 Fire & Emergency Response ......................................................................................................................... 42
By application: .............................................................................................................................................................. 43
Telecom Use.................................................................................................................................................................... 43
Page 3 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
Installation & Permitting
Where public safety is under control of a local Authority Having Jurisdiction (AHJ), the fuel cell will require a permit to
be installed and connected. The AHJ may be a federal, state, local, or other regional department or individual such as
a fire chief, fire marshal, or permitting agency. The AHJ has responsibility and authority for permitting and defines the
requirements as dictated by local codes, state and federal law.
The fuel cell power system (power generator) and the fuel supply (including storage and delivery) have separate
compliance requirements.
The fuel cell type determines the fuel used, either gas (pure hydrogen, or a mixture of hydrogen-containing flammable
gases) or liquid (methanol, or methanol/water mixture).
Reference Documents
Organizations:
ANSI - American National Standards Institute - responsible for approval of US standards
ASTM - American Society for Testing and Materials - standards writing organization for materials testing.
CSA - Canadian Standards Association - a Nationally Recognized Test Laboratory & standards writing organization.
FCC - Federal Communications Commission - responsible for control and use of RF spectrum.
FCC regulations for controlling and limiting equipment RF emissions are part of the US Code of Federal
Regulations, Title 47, Part 15 (47CFR15) - Radio Frequency Devices.
ICC - International Code Council - international standards writing organization.
IEC - International Electrotechnical Committee - international standards writing organization.
OSHA - Occupational Safety & Health Administration - part of the US Department of Labor.
OSHA regulations are part of the US Code of Federal Regulations, Title 29, Part 1910 (29CFR1910).
NFPA - National Fire Protection Agency - US national standards writing organization.
UL - Underwriters Laboratories, Inc. - a Nationally Recognized Test Laboratory & standards writing organization
Relevant Documents for Compliance (mandated by code or law):
ANSI FC 1
ANSI FC 3
IFC
IFGC
enforced)
NFPA 30
NFPA 54
NFPA 55
NFPA 70
NFPA 853
29CFR1910
47CFR15
49CFR172
Standard for Stationary Fuel Cell Power Systems (2012 edition)
Standard for Portable Fuel Cell Power Systems (2004 edition)
International Fire Code (2012 edition most recent; prior editions 2009, 2006, 2003 are still enforced)
International Fuel Gas Code (2012 edition most recent; prior editions 2009, 2006, 2003 are still
Flammable and Combustible Liquids Code (2012 edition)
National Fuel Gas Code (2012 edition)
Compressed Gases and Cryogenic Fluids Code (2013 edition; prior editions are still enforced)
National Electrical Code (2014 edition)
Installation of Stationary Fuel Cell Power Systems (2010 edition)
Occupational Health and Safety (OSHA)
Federal Communication Commission (FCC)
Department of Transportation (DOT)
Other Referenced Documents for Compliance:
ASME/ANSI B31.3
ANSI/IEC 60529
ANSI Z21.21/CSA 6.5
ASTM E 108
IBC
IMC
NFPA 2
NFPA 24
NFPA 80
NFPA 90A
NFPA 101
NFPA 220
NFPA 251
Process Piping
Degrees of protection provided by enclosures
Standard for Automatic Valves for Gas Appliances
With Distributed Energy Resources
Standard Test Methods for Fire Tests of Roof Coverings
International Building Code
International Mechanical Code
Hydrogen Technologies Code (2011 edition)
Standard for the Installation of Private Fire Service Mains and Their Appurtenances
Standard for Fire Doors and Other Opening Protectives
Standard for the Installation of Air-Conditioning and Ventilating Systems
Life Safety Code
Standard Types of Building Construction
Standard Methods of Tests of Fire Resistance of Building Construction and Materials
Page 4 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
ANSI/UL 991
UL 429
UL 790
UL1741
Standard for Tests for Safety-Related Controls Employing Solid-State Devices
Electrically Operated Valves
Standard Test Methods for Fire Tests of Roof Coverings
Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use
Fuel cell power systems and their fuel supplies must meet a number of compliance requirements for safe and legal
operation. Below is a detailed list of compliance requirements for the power system and fuel supplies, covering
hydrogen gas (H2), liquid hydrogen, biogas (e.g.; methane & hydrogen mix), and liquid fuels (e.g.; methanol).
This list is not intended to replace existing code; consult referenced standards for exact language and requirements.
Order of Precedence for Code Compliance:
1. Code of Federal Regulations; specifically, OSHA (Title 29), FCC (Title 47), DOT (Title 49)
2. State government-approved safety & design codes - typically adopted from International Code Council (ICC);
these include the International Fire Code (IFC), International Fuel & Gas Code (IFGC), International Building Code
(IBC), etc.
3. State, county, or local municipality approved standard or code.
4. ANSI-approved standards invoked by CFR, state, or local codes; including NFPA, ASME, UL, etc.
Codes & standards relevant for Fuel Cell Power Systems (power generator):
NFPA 853
Installation of Stationary Fuel Cell Power Systems (2010 edition)
NFPA 70
National Electrical Code (2014 edition)
ANSI FC 1
Standard for Stationary Fuel Cell Power Systems (2012 edition)
ANSI FC 3
Standard for Portable Fuel Cell Power Systems (2004 edition)
Codes & standards relevant for Fuel Storage:
29CFR1910
Occupational Health and Safety (OSHA)
49CFR172
Department of Transportation (DOT)
IFC
International Fire Code (2012 edition most recent; 2009, 2006, 2003 are still enforced)
IFGC
International Fuel Gas Code (2012 edition most recent; 2009, 2006, 2003 are still enforced)
NFPA 30
Flammable and Combustible Liquids Code (2012 edition)
NFPA 54
National Fuel Gas Code (2012 edition)
NFPA 55
Compressed Gases and Cryogenic Fluids Code (2013 edition; prior editions are still enforced)
NFPA 853
Installation of Stationary Fuel Cell Power Systems (2010 edition)
International Fire Code (IFC)- implementation by state governments:
- enacted as state and/or local law, versions (released by date) adopted by each state (as of Oct 2013):
IFC2012 - 2012 edition (most recent): CA, MS, SC, UT, WA, WY
IFC2009 - 2009 edition: AL, AK, ID, IL, IA, NC, OH, OK, OR, PA, SD, VA
IFC2006 - 2006 edition: AZ, AR, CO, D.C., GA, IN, KS, KY, MN, NV, NJ, NY, TN, TX
IFC2003 - 2003 edition: CT, NM
International Fuel & Gas Code (IFGC)- implementation by state governments:
- enacted as state and/or local law, versions (released by date) adopted by each state (as of Oct 2013):
IFGC2012 - 2012 edition (most recent): MS, RI, SC, UT, WA, WV, WY
IFGC2009 - 2009 edition: AL, AK, AZ, CO, FL, ID, IL, LA, MI, MT, NJ, NC, ND, OH, OK, OR, PA, VA, WI
IFGC2006 - 2006 edition: AR, D.C., GA, IN, KY,MN, NY, TX,
IFGC2000 - 2000 edition: MO
Page 5 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
General Safety Requirements (independent of fuel or fuel cell type):
 Noise:
The US National Institute for Occupational Safety and Health (NIOSH) establishes recommendations for public health
(recommendation only):
Centers for Disease Control and Prevention/NIOSH publication 98-126 Section 1.1.2 Time-Weighted Average (TWA) Recommended Exposure Level (REL) of 85dBA over 8hrs; exposure time is reduced by 50% for every 3dB above
85dBA. Section 1.3 Noise Exposure Assessment (method for compliance) per ANSI Standard Measurement of
Occupational Noise Exposure S12.19-1996.
OSHA limits the maximum noise (sound level) exposure in an occupational (workplace) environment.
29CFR1910.95 Occupational noise exposure
A-weighted sound level, slow response filter, permissible noise exposures are limited by level and duration.
Per Table G-16 Permissible Noise Exposures, the sound level is 90dBA over 8hrs (Table allows for higher levels for
shorter durations, not to exceed 115dBA for 15 minutes or less).
The following categories for compliance are used:
 Definitions
 Components & Systems Certifications
 Location, Capacity, Siting, & Setbacks
 Container types & design & storage construction
 Piping, Valves, Regulators, Fuel Controls (including pressure relief devices)
 Vents & Ventilation
 Labeling & Signage
 Fuel Transportation & Site Refueling
 Fire & Emergency Response
Page 6 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
Specific Requirements for the Fuel Cell Power System
(power generator)
Compliance Notes:
1. Fuel cell power systems (power generators) do not require 3rd party safety certification per OSHA (Code of Federal
Requirements 29, Section 1910) directives.
2. The International Mechanical Code 2012, 2009, 2006 editions - Section 924 Stationary Fuel Cell Power Systems
require testing to ANSI FC 1, and installation per NFPA 853 (for systems <10MW output).
3. NFPA 2 & NFPA 853 requires safety certification to ANSI FC 1 for AHJ approval (permit) of the installation.
4. NFPA 2 has not been adopted as code (regardless of the use of 'code' in its title) - the NFPA created this
document as a single source for hydrogen safety, but at present is not legally adopted by any state legislature.
Requirements for NFPA 2 are provided here for reference only (e.g.; if an AHJ chooses to invoke it; this standard
may be adopted in future code revisions). NFPA 853 is used for the fuel cell power system installation, NFPA 55 is
used for the compressed & flammable gas fuel (e.g.; hydrogen), and NFPA 30 is used for flammable liquid fuel
(e.g.; methanol) per the ICC and incorporated into state laws.
5. It is the responsibility of the fuel cell power system manufacturer to prove compliance to all legal
requirements prior to deploying these products into telecom applications.
Certified approval to ANSI FC 1 is provided by a National Recognized Testing Laboratory (NRTL) in the USA.
OSHA has established the NRTL program in compliance with 29CFR 1910.7 for US third-party certification of products
to safety standards.
For a list of approved NRTLs and details of the program, refer to:
https://www.osha.gov/dts/otpca/nrtl/index.html
Compliance requirements identified for each relevant document.
Federal Communication Commission (FCC)
 Definitions
Compliance is mandated in the USA by federal law.
per 47CFR Part 15 - Radio Frequency Devices - Subpart B: Unintentional Radiators.
o Radiated and AC conducted RF emission limits by type of application/installation
o Class A for industrial/commercial (non-residential),
o Class B for residential;
o limits per 47CFR15.107 & 109.
 Components & Systems Certifications
In compliance with US Code of Federal Regulations 47 Part 15, fuel cell power systems are electrical generators and
require verification testing by a test laboratory accredited by the National Voluntary Laboratory Accreditation Program
(NVLAP); the American Association of Laboratory Accreditation (A2LA); or an accredited laboratory designated by the
Commission under the terms of a negotiated Mutual Recognition Agreement (MRA).
For information on FCC-approved laboratories:
https://apps.fcc.gov/oetcf/eas/reports/TestFirmSearch.cfm
Following a successful test with report from the accredited laboratory, the manufacturer issues a Declaration of
Conformity (DoC) for each model successfully tested. A successful test report from the accredited laboratory meets the
requirements for verification testing and the DoC is the manufacturer's resulting claim for compliance.
o Compliance is required per model number;
o be rated for the Class of installation, and
o must carry the FCC logo and warnings on the nameplate and on the inside cover of the product manuals
per 47CFR15.19(a)(3).
 Labeling & Signage
- Nameplate:
o The product nameplate for each model of power generator must carry the NRTL Mark (in compliance with
FC 1), FCC Mark, and compliance warnings (per FCC by law and FC 1 by code).
Page 7 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
NFPA 2 Hydrogen Technologies Code - 2011 edition - (reference only)

Components & Systems Certifications
o Requires listing (certified approval) of the stationary fuel cell power system to ANSI FC 1 [NFPA2-2011
12.3.1.1.1.1]
o Modular (engineered and field-constructed) systems shall meet intent of ANSI FC 1 [NFPA2-2011
12.3.1.1.2.1]
NFPA 853 Installation of Stationary Fuel Cell Power Systems -2010 edition


Components & Systems Certifications
o Requires listing (certified approval) of the stationary fuel cell power system to ANSI FC 1 [NFPA853-2010
4.2 & 4.3]
o Modular (engineered and field-constructed) systems require a fire risk evaluation by a registered engineer
or AHJ-acceptable 3rd party. [NFPA853-2010 4.4]
Location, Capacity, Siting, & Setbacks
- Siting:
[NFPA853-2010 5.1.1]
o anchored to a foundation, physically protected,
o above base flood elevation,
o resistant to rain, snow, ice, freezing temperatures, wind, seismic events, and lightning,
o accessible to service & fire department personnel,
o locate exhaust vents away from building openings,
o located 5 ft. (1.5m) from other flammable or hazardous chemicals
- Outdoor Installations
[NFPA853-2010 5.2]:
o do not direct exhaust vents onto walkways or pedestrian paths
o fuel-bearing components located 15 ft. (4.6m) from building openings, including HVAC intakes,
- or - If fuel cell power system is 50kW or less, this is modified by Section 9.2 to:
o fuel-bearing components located 10 ft. (3m) from building openings, including HVAC intakes, and
o exhaust outlets not directed onto pedestrian walkways.
- Indoor Installations
[NFPA853-2010 5.3]:
o power system in a room separated from the rest of the building by floor, wall, and ceiling (including piping
seals and joints) with 1-hour fire resistance rating (per NFPA 251 Standard Methods of Tests of Fire
Resistance of Building Construction and Materials),
o with fire doors (per NFPA 80 Standard for Fire Doors and Other Opening Protectives),
o dampers (per NFPA 90A Standard for the Installation of Air-Conditioning and Ventilating Systems),
o and egress (per NFPA 101 Life Safety Code) or the locally adopted building code.
- or - If fuel cell power system is 50kW or less, this is modified by Section 9.3 to:
 fuel cells supplied by natural gas, propane, or fuel oil and located in residences do not require
fire-rated separations [NFPA853-2010 9.3.1];
 fuel cells supplied by methanol or other alcohol fuels and located in residences do not require
fire-rated separations if meet requirements of Sections 9.3.6.1 through 9.3.6.4 [NFPA853-2010
9.3.2]
For liquid fuel:
 <0.019 m3 (5 gal) of liquid fuel within the entire system including piping, during all modes of
operation, standby, and shutdown [NFPA853-2010 9.3.6.1],
 bulk fuel storage located outside [NFPA853-2010 9.3.6.2],
 solid pipe or tube or all-welded, soldered, or brazed construction for indoor piping up to and
through the fuel cell power system enclosure [NFPA853-2010 9.3.6.3],
 requires leakage detection and automatic isolation of the indoor fuel piping from the outdoor bulk
fuel supply upon detection of fuel leakage (using pump stoppage, valve closure, or other
manufacturer supplied control).
 Requires an automatic isolation valve at the tank for outdoor bulk fuel storage located at an
elevation above the fuel cell power system. [NFPA853-2010 9.3.6.4]
o Liquid fuel systems shall be provided with curbing, diking, or drainage in accordance with NFPA 30,
Flammable and Combustible Liquids Code. [NFPA853-2010 8.1.5.2]
- Rooftop Installations
[NFPA853-2010 5.4]:
o roofing material below and within 12 inches (30.5cm) horizontally from the power system, or
 components shall be non-combustible, or
 have Class A rating per either
- ASTM E 108 Standard Test Methods for Fire Tests of Roof Coverings or
Page 8 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers



- UL 790 Standard Test Methods for Fire Tests of Roof Coverings
- Electrical:
o Electrical connections and grounding per NFPA 70 National Electrical Code; specifically, Article 692 Fuel
Cell Systems. [NFPA853-2010 5.5.1]
o dry type transformers in use around/inside fuel cell; installed per NFPA 70 National Electric Code.
o oil-filled transformers >500 gallons (>1892 L) require protection from one of the following:
1. 25 ft (7.6 m) minimum spacing between transformer containment & other structures, or
2. 2-hr-rated fire barrier, extending 1ft (30.5cm) above and 2ft (61cm) beyond the sides of transformer
and other adjacent structures or equipment, or
3. automatic deluge water spray system per NFPA 15 Standard for Water Spray Fixed Systems for Fire
Protection; 0.25 gpm/ft2 (10.2 L/min*m2) minimum spray density over all transformer surfaces.
Container types & design & storage construction
- Fuel Storage:
o Gas Hydrogen storage per NFPA 55 Compressed Gases and Cryogenic Fluids Code. [NFPA853-2010
6.4.1]
o Liquid Hydrogen storage per NFPA 55 Compressed Gases and Cryogenic Fluids Code. [NFPA853-2010
6.4.2]
o Liquid fuel storage & piping per NFPA 30 Flammable and Combustible Liquids Code [NFPA853-2010
6.5.4]
o Natural gas (methane) storage & piping per NFPA 54 National Fuel Gas Code
[NFPA853-2010
6.2.1]
o Compressed natural gas (CNG) piping & valves per NFPA 52 Vehicular Fuel Systems Code
[NFPA853-2010 6.2.2]
o Biogas (from decomposition of organic matter) storage, piping, valves, & regulators per NFPA 54 National
Fuel Gas Code
[NFPA853-2010 6.5.3]
o Liquified Petroleum Gas (LP-Gas) storage & piping per NFPA 58 Liquified Petroleum Gas Code
[NFPA853-2010 6.3]
Piping, Valves, Regulators, Fuel Controls
o Hydrogen piping per ASME/ANSI B31.3 Process Piping. [NFPA853-2010 6.4.3]
o requires an accessible manual shutoff valve located within 6 ft. (1.8m) of the storage container.
[NFPA853-2010 6.4.3.1]
o requires a 2nd accessible manual shutoff valve located within 6 ft. (1.8m) of the storage container
[NFPA853-2010 6.4.3.2]
- unless:
 power system is enclosed by a room with 1-hour fire resistance rating per NFPA 251 Standard
Methods of Tests of Fire Resistance of Building Construction and Materials,
 with fire doors per NFPA 80 Standard for Fire Doors and Other Opening Protectives
 and dampers per NFPA 90A Standard for the Installation of Air-Conditioning and Ventilating
Systems,
- or  hydrogen storage is within 6 ft. (1.8m) of the fuel cell power system.
o requires the manual shutoff valve be located outside the 1-hour fire resistance-rated room. [NFPA8532010 6.4.3.3]
o requires an automatic shutoff valve interlocked with gas detection for fuel sources located outdoors and
serving an indoor fuel cell power system. [NFPA853-2010 6.4.3.4]
o requires ventilation to the outdoors for Class I Division 2 areas due to hydrogen piping. [NFPA853-2010
6.4.3.6]
- Biogas fuel supplies:
o gas storage, piping, valves, and regulators designed and installed per NFPA 54 National Fuel Gas Code.
[NFPA853-2010 6.5.3]
- Power & Ground:
o containers & piping requires electrical grounding per NFPA 70 National Electrical Code. [NFPA853-2010
6.4.3.7]
Vents & Ventilation
o natural ventilation is allowed (by verification). [NFPA853-2010 7.2.2]
o requires a cover or filter on the inlet vent to prevent foreign matter from entering the system. [NFPA8532010 7.2.3]
Page 9 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
o


control interlock to shut down the system upon loss of mechanical ventilation if required. [NFPA853-2010
7.1.4]
o control interlock to shut down the system upon loss of mechanical exhaust if required. [NFPA853-2010
7.3.4]
o requires ventilation and exhaust system to provide negative or neutral pressure in the room with respect to
the building (implies indoor application). [NFPA853-2010 7.1.2]
- Ventilation for Indoor Installations:
 requires room exhaust rate not less that 150 CFM (45 m 3/min.) and not less than 1 CFM/ ft.2 (0.3
m3/min. per square meter) of floor area. [NFPA853-2010 7.3.3]
 requires venting of sources of gas to outside building at least 15 ft (4.6m) from building openings.
[NFPA853-2010 7.4.1]
 requires vents to prevent entry of water or foreign objects. [NFPA853-2010 7.4.2]
Fire & Emergency Response
- For liquid fuel supplies:
o liquid fuel storage sites require fire hydrants [NFPA853-2010 8.1.1]
 per NFPA 30 Flammable and Combustible Liquids Code &
 NFPA 24 Standard for the Installation of Private Fire Service Mains and Their Appurtenances
 supplying water of at least 250 GPM (946 L/min.) for 2 hours.
- or  be protected in accordance with a fire risk evaluation.
o engineered and field-constructed fuel cells (per Section 4.4) require automatic fire detection and alarm
system per NFPA 72 National Fire Alarm and Signaling Code.
[NFPA853-2010 8.1.2]
o
Indoor:
o automatic fire suppression system that shuts off the fuel supply when activated is required for liquid fuel
pumps,
[NFPA853-2010 8.1.5.2 & 8.1.5.3]
o liquid fueled systems require leak detection
[NFPA853-2010 8.1.5.9]
o Combustible gas detector(s) required in the fuel cell power system enclosure, the exhaust system, or the
room containing the fuel cell power system, including all indoor or separately enclosed gas compressors.
[NFPA853-2010 8.1.5.4 & 8.1.5.5]
 except if used for a fuel cell power system <50kW where the fuel is either odorized natural gas or
LP-gas, or listed for indoor use.
[NFPA853-2010 9.5.1]
o hydrogen detector required in room when gaseous or liquefied hydrogen is piped into the room from
outside.
[NFPA853-2010 8.1.5.6]
o criteria for combustible gas detection systems, including detection specific to hydrogen:
(1) leakage sources and fuel type determines where to locate the detection device(s).
(2) The combustible gas detection system shall activate an alarm at 25% of the lower flammable limit
(LFL) and shut down the power system fuel supply at 60% LFL,
(3) using the lowest LFL of the gas or gas mixture. [NFPA853-2010 8.1.5.7]
o Where leak detection is provided, fuel cell power systems that do not use gaseous fuels and do not
generate flammable gas mixtures in any part of their systems shall not be required to have combustible
gas detection to be installed.
[NFPA853-2010 8.1.5.8]
Fire Prevention & Emergency Plan:
o see Section 8.2 for specific details required for Fire Prevention and Emergency Plan.
NFPA 70 National Electric Code -2014 edition

specifically - Article 692 Fuel Cell Systems
Definitions
o Fuel Cell System defined as a complete aggregate of equipment used to convert chemical fuel into usable
electricity; with power conditioners and auxiliary equipment; including a reformer if present. [NFPA70-2014
692.2]
o Classification of Locations:
 Class I locations (i.e. Division 1, Division 2; flammable concentrations likely to ignite) same as
29CFR1910.307.
 Class I Group Classifications (flammable gas or vapor): [NFPA70-2014 500.6]
 Group B: (hydrogen)
 Group C: (ethylene)
 Group D: (propane, methane, methanol, ethanol)
Page 10 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers



Components & Systems Certifications
o Fuel Cell System shall be evaluated and listed for its intended application prior to installation. [NFPA702014 692.6]
Piping, Valves, Regulators, Fuel Controls (including pressure relief devices)
- Power:
o Disconnecting means using a readily accessible circuit breakers or manually operated switches required to
connect all current carrying conductors from the fuel cell power source to all the other conductors in a
building or structure. [NFPA70-2014 692.13 & 692.17]
o Overcurrent protection required for the fuel cell; overcurrent devices readily accessible. [NFPA70-2014
692.9]
o Fuel cell is permitted to supply AC power to a building or structure. [NFPA70-2014 692.10]; transfer
switch required if connected to non-grid-interactive systems that use utility backup. [NFPA70-2014
692.59]
o Wiring per Chapter 3 of NFPA70. [NFPA70-2014 692.31]; for guidance on ampacity for conductors, see
Table 310.15(B)(16).
- Ground:
o AC & DC output systems require grounding; DC ground bonded to AC ground; grounding conductor sized
based on overcurrent device rating…see Table 250.122 Minimum Size Equipment Grounding Conductors
for Grounding Raceway & Equipment. [NFPA70-2014 692.41]
Labeling & Signage
o A permanent plaque or directory installed at each service equipment location noting all electrical power
sources on or in the premises. [NFPA70-2014 692.4(B)]
o Nameplate identifies the rated circuit current. [NFPA70-2014 692.8]
o If the fuel cell power system employs an AC inverter for generating single-phase 120V, and is connected
to a 3-wire 120/240V service with no 240V loads and no multiwire branch circuits, and the overcurrent
device connected to the fuel cell output must be rated less than the load - then the equipment must be
marked as follows:
" WARNING
SINGLE 120-VOLT SUPPLY. DO NOT CONNECT MULTIWIRE BRANCH CIRCUITS!"
[NFPA70-2014 692.10(C)]
- At the disconnecting means for the fuel cell power generator:
o Disconnecting means for ungrounded conductors - where terminals may be energized in the open position
requires a warning sign with the following words (or equivalent):
"DANGER
ELECTRIC SHOCK HAZARD
DO NOT TOUCH LIVE TERMINALS.
TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION"
[NFPA70-2014 692.17]
o Rated Output: Marking at the disconnecting means for the fuel cell power source specifying the fuel cell
system, the output voltage, the output power rating, and continuous output current rating. [NFPA70-2014
692.53]
o Fuel Shut Off: manual fuel shutoff valve location must be marked at the disconnecting means. [NFPA702014 692.54]
o Electrical Energy Storage within the fuel cell power system: if the fuel cell power system stores
electric energy (i.e.; battery or transient power module), warnings required at disconnecting means as
follows (or equivalent):
"WARNING
FUEL CELL POWER SYSTEM CONTAINS ELECTRICAL ENERGY STORAGE DEVICES"
[NFPA70-2014 692.56]
Page 11 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
ANSI FC 1-2012 Stationary Fuel Cell Power Systems


Location, Capacity, Siting, & Setbacks
o no Fuel Storage requirements
Piping, Valves, Regulators, Fuel Controls
o FC 1 requires the fuel supplied to the fuel cell power system pass through at least two automatic valves, in
series, each of which serves as an operating valve and safety shutoff valve. Typical fuel control design
places one valve inside the fuel cabinet or compartment (primary valve) and the other within the fuel cell
power generator (secondary valve).
o The valves must be compliant to UL 429 Electrically Operated Valves, or ANSI Z21.21/CSA 6.5 Standard
for Automatic Valves for Gas Appliances. [ANSI FC1-2012 1.11.2.2.a]
- Power & Ground:
o Grounding and power connections in compliance with NFPA 70 National Electric Code - Article 692 Fuel
Cell Systems.
ANSI FC 3-2004 Portable Fuel Cell Power Systems


Location, Capacity, Siting, & Setbacks
- Fuel Storage:
o Cylinders containing hazardous compressed gases shall comply with the requirements of the ASME Boiler
and Pressure Vessel Code, Section VIII or Title 49 of the US Code of Federal Regulations, Title 49 CFR,
Hazardous Materials Regulations, Chapter 1, Subchapter C, Part 178 - Specifications for Packagings.
o Removable compressed gas fuel containers shall be equipped with a cylinder valve compliant with the
applicable requirements in CGA V-9, Standard for Compressed Gas Cylinder Valves and include a
connection fixture that will not allow the flow of gas until a positive seal has been achieved.
o Fuel containers require mechanical restraint; can't displace more than an inch (25.4mm) when a lateral
force equal to the weight of the container is applied from any direction at the center of the vertical height of
the cylinder. [ANSI FC1-2012 1.2.3]
Piping, Valves, Regulators, Fuel Controls
o FC 3 requires the fuel supplied to the fuel cell power system pass through at least one automatic valve.
o A second automatic valve in series with the first is required if the fuel supply quantity exceeds 25% of LFL
if fully released into a volume of 500ft3 (14.1 m3). This does not apply if the fuel cell power system is
intended and marked for outdoor use only (single valve only required). [hydrogen supply: 25% of LFL =
1% by volume; > 5ft3 (0.14 m3) of H2 supply requires a second valve].
o The valves must be compliant to UL 429 Electrically Operated Valves, ANSI Z21.21/CSA 6.5 Standard for
Automatic Valves for Gas Appliances, FMRC 7400 Liquid & Gas Safety Shutoff Valve, or other nationally
recognized standards. [ANSI FC1-2012 1.29.1]
- Power & Ground:
o Power wiring in compliance with NFPA 70 National Electric Code - Articles 110 & 400
o Grounding in compliance with NFPA 70 National Electric Code - Articles 250.20 & 240.34
Page 12 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
Specific Requirements for the Fuel Supply (including storage and
delivery)
Fuel Supply Compliance Notes:
Determining Code Compliance:
Different requirements exist for placement and storage the fuel by type; e.g., gaseous hydrogen, liquid hydrogen,
flammable gas (methane or other hydrogen-rich gas), and flammable liquids (methanol).
1. Fuel supplies and fuel storage locations are defined by OSHA directives; the setback distances were derived from
the 1969 edition of NFPA 50A - which was made obsolete and replaced by the NFPA as an updated NFPA 55.
2. AHJs have the authority to chose compliance to NFPA 55 in place of default OSHA setback requirements if
allowed by local code.
3. Local jurisdictions (state, county, township, borough, etc.) may (by legislation) adopt other safety standards as
local code in place of OSHA directives. Federal law (OSHA, other Codes of Federal Regulations) are legally
mandated unless other standards or codes are adopted by the state legislature.
4. Each state or local agency within the state makes use of the International Code Council (ICC) international codes
for fire safety (International Fire Code - IFC) and fuel & gas safety (International Fuel & Gas Code - IFGC) by
incorporating these safety standards into state code. Other ICC international codes for safety are also used, but
the IFC and IFGC are specifically relevant for fuel use and storage.
5. Each state ratifies the version (by year of release) of ICC standards and continue to use prior versions until the
state legislatures update their state law; this requires evaluation of prior editions to address compliance nationwide.
A list of ICC standards and the state & local adoption of versions of each ICC standard can be found at ICC's website
(select "ADOPTIONS" tab for adoptions of Plumbing Mechanical, Fuel Gas - PMG - codes):
http://www.iccsafe.org/cs/PMG/Pages/default.aspx
For access to the text of each ICC document::
http://publicecodes.cyberregs.com/icod/
simply stated - for fuel storage & use: comply to OSHA, or by state legal adoption of IFC & IFGC
- which invoke compliance to NFPA 55 (and other standards).
Notes for the following compliance review:
1. Evaluation for gaseous and liquid hydrogen, methane, and methanol. Does not cover ammonia or petroleum gases
(i.e.; propane, butane, etc.)
2. Evaluation for transportation by road, train, airplane; does not include transportation by sea.
These requirements are specific to the fuel, capacities, and methods of storage, and location
Fuel:
Flammable Gases - Hydrogen & Liquified Hydrogen
Flammable Gases - Methane or other hydrogen-rich gases
Flammable & Hazardous Liquid - Methanol
OSHA (29CFR1910): Subpart H - Hazardous Materials
OSHA defines liquid hydrogen as liquefied hydrogen with separate requirements (compared to either gaseous
hydrogen or flammable liquids).
 Definitions
o Hydrogen gas - Class I (Flammable gases, vapors, liquids), Group B: Hydrogen,
o Methane gas - Class I (Flammable gases, vapors, liquids), Group D: Hydrocarbons,
other:
Hazardous (classified) locations (29CFR1910.307; definition of terms: 29CFR1910.399)
o "Class I, Division 1: Normally explosive and hazardous
Page 13 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
(i) In which ignitable concentrations of flammable gases or vapors may exist under normal operating
conditions; or
(ii) In which ignitable concentrations of such gases or vapors may exist frequently because of repair or
maintenance operations or because of leakage; or
(iii) In which breakdown or faulty operation of equipment or processes might release ignitable
concentrations of flammable gases or vapors, and might also cause simultaneous failure of electric
equipment.
Note to the definition of “Class I, Division 1:” This classification usually includes ….all other locations
where ignitable concentrations of flammable vapors or gases are likely to occur in the course of normal
operations."
o
"Class I, Division 2: Not normally present in an explosive concentration (but may accidently exist).
(i) In which volatile flammable liquids or flammable gases are handled, processed, or used, but in which
the hazardous liquids, vapors, or gases will normally be confined within closed containers or closed
systems from which they can escape only in the event of accidental rupture or breakdown of such
containers or systems, or as a result of abnormal operation of equipment; or
(ii) In which ignitable concentrations of gases or vapors are normally prevented by positive mechanical
ventilation, and which might become hazardous through failure or abnormal operations of the ventilating
equipment; or
(iii) That is adjacent to a Class I, Division 1 location, and to which ignitable concentrations of gases or
vapors might occasionally be communicated unless such communication is prevented by adequate
positive-pressure ventilation from a source of clean air, and effective safeguards against ventilation failure
are provided.
Note to the definition of “Class I, Division 2:” This classification usually includes locations where volatile
flammable liquids or flammable gases or vapors are used, but which would become hazardous only in
case of an accident or of some unusual operating condition. The quantity of flammable material that might
escape in case of accident, the adequacy of ventilating equipment, the total area involved, and the record
of the industry or business with respect to explosions or fires are all factors that merit consideration in
determining the classification and extent of each location.
Piping without valves, checks, meters, and similar devices would not ordinarily introduce a hazardous
condition even though used for flammable liquids or gases. Locations used for the storage of flammable
liquids or liquefied or compressed gases in sealed containers would not normally be considered hazardous
unless also subject to other hazardous conditions.
Electrical conduits and their associated enclosures separated from process fluids by a single seal or
barrier are classed as a Division 2 location if the outside of the conduit and enclosures is a nonhazardous
location."
29CFR1910.101 Compressed gases (general requirements).


Container types & design & storage construction
- (Fuel Storage) Containers:
o Inspection of compressed gas cylinders "…Visual and other inspections shall be conducted as prescribed
in the Hazardous Materials Regulations of the Department of Transportation (49 CFR parts 171-179 and
14 CFR part 103). Where those regulations are not applicable, visual and other inspections shall be
conducted in accordance with Compressed Gas Association Pamphlets C-6-1968 and C-8-1962…"
[29CFR1910.101(a)]
o Compressed gases. "The in-plant handling, storage, and utilization of all compressed gases in cylinders,
portable tanks, rail tankcars, or motor vehicle cargo tanks shall be in accordance with Compressed Gas
Association Pamphlet P-1-1965..." [29CFR1910.101(b)]
Piping, Valves, Regulators, Fuel Controls
- Safety relief (overpressure release) devices:
o Safety relief devices for compressed gas containers. Compressed gas cylinders, portable tanks, and cargo
tanks shall have pressure relief devices installed and maintained in accordance with Compressed Gas
Association Pamphlets S-1.1-1963 and 1965 addenda and S-1.2-1963…"
[29CFR1910.101(c)]
Page 14 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
29CFR1910.103(b) Gaseous hydrogen systems

Location, Capacity, Siting, & Setbacks
- Location: [29CFR1910.103(b)(2)]
system shall be located such that:
o shall be readily accessible to delivery equipment and to authorized personnel;
o shall be located above ground;
o not located beneath electric power lines;
o not close to flammable liquid piping or other flammable gas piping;
o and not higher than flammable liquid storage except where dikes, diversion curbs, grading, or separating
solid walls are used to prevent accumulation of flammable liquids under the system.
o The area within 15 feet of any hydrogen container shall be kept free of dry vegetation and combustible
material. [29CFR1910.103(b)(5)]
- Capacity & setback distances:
29CFR1910.103(b)(2)(ii)(a) Table H-1 limits
o >15,000 CF gas storage to separate buildings or outdoors;
o 3,000-15,000 CF is limited to outdoors, in a separate building, or in a special room,
o and allows <3000 CF to be stored inside building exposed to other occupancies.
29CFR1910.103(b)(2)(ii)(d) defines requirements for H2 storage <3000 CF inside a building:
o adequately ventilated per 29CFR1910.103(b)(3)(ii)(b),
o inlet opening located near the floor in exterior walls only,
o outlet openings at high point in room in exterior walls or roof,
o inlet & outlet openings shall have a minimum total area of 1 sq. ft. per 1000 CF of room volume,
o discharge from outlet directed to a safe location.
 20 feet from stored flammable materials or oxidizing gases,
 25 feet from open flames, ordinary electrical equipment, or other sources of ignition,
 25 feet from concentrations of people,
 50 feet from ventilation intakes for air-conditioning equipment and air compressors,
 50 feet from other flammable gas storage,
 protected from damage or injury due to falling objects or working activity in the area;
o also, more than one system of 3000 CF or less may be installed in the same room, separated by at least
50 feet, and each meeting the requirements above.
Table H2 defines the setback distances by storage capacity:
type of outdoor exposure
example
1. Building or structure
- see NFPA 220 Standard
Types of Building Construction
(1969 ed.)
2. Wall openings
3. Flammable liquids
above ground
4. Flammable liquids
below ground <1000 gallons
5. Flammable liquids
below ground >1000 gallons
6. Flammable gas storage, High
& Low pressure
7. Oxygen storage
[29CFR1910.103(b)(2)(ii)(c)]
<3,000
3,000 CF
15,000 CF
a. Wood frame construction
a. 10 ft.
a. 25 ft.
b. Heavy timber, or ordinary construction
b. 0 ft.
b. 10 ft.
c. Fire-resistive construction
c. 0 ft.
c. 0 ft.
a. Not above any part of a system
b. Above any part of a system
a. 0 to 1000 gallons
b. >1000 gallons
a. Tank
b. Vent or fill opening of tank
a. Tank
b. Vent or fill opening of tank
a. low pressure: 0-15,000 CF
b. high pressure: >15,000 CF
a. 0 - 12,000 CF - see NFPA 51 (1969 ed.)
b. > 12, 000 CF - see NFPA 566 (1969 ed.)
8. Fast-burning solids
9. Slow-burning solids
10. Open flame or sources of ignition
11. Inlets to air compressors, ventilation, or air conditioning equip.
12. Concentrations of people
Page 15 of 43
a. 10 ft.
b. 25 ft.
a. 10 ft.
b. 25 ft.
a. 10 ft.
b. 25 ft.
a. 20 ft.
b. 25 ft.
a. 10 ft.
b. 25 ft.
50 ft.
25 ft.
25 ft.
50 ft.
25 ft.
a. 10 ft.
b. 25 ft.
a. 25 ft.
b. 50 ft.
a. 10 ft.
b. 25 ft.
a. 20 ft.
b. 25 ft.
a. 25 ft.
b. 50 ft.
50 ft.
25 ft.
25 ft.
50 ft.
50 ft.
>15,000
CF
a. 50 ft.
b. 25 ft.
c. 0 ft.
a. 10 ft.
b. 25 ft.
a. 25 ft.
b. 50 ft.
a. 10 ft.
b. 25 ft.
a. 20 ft.
b. 25 ft.
a. 25 ft.
b. 50 ft.
50 ft.
25 ft.
25 ft.
50 ft.
50 ft.
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
The distances in Table H-2 type of outdoor enclosure Items 1 and 3 to 10 inclusive do not apply where protective
structures such as adequate fire walls are located between the system and the exposure.
Refer to OSHA 29CFR1910.103(b)(3) for additional definitions and requirements for building construction types.

Container types & design & storage construction
- (Fuel Storage) Containers:
o containers designed, constructed, tested to ASME Boiler & Pressure Vessel Code, Section VIII, Unfired
Pressure Vessels 1968 (per Sec. 29CFR1910.6)
[29CFR1910.103(b)(1)(i)(a)(1)],
- or o containers designed, constructed, and tested in accordance with US Dept. of Transportation (DOT)
Specifications and Regulations.
[29CFR1910.103(b)(1)(i)(a)(2)]
 Piping, Valves, Regulators, Fuel Controls
- Safety relief (overpressure release) devices:
Hydrogen containers shall be equipped with safety relief devices as required by
o ASME Boiler & Pressure Vessel Code, Section VIII, Unfired Pressure Vessels 1968, or
o by DOT Specifications and Regulations.
[29CFR1910.103(b)(1)(ii)(a)]
 Labeling & Signage
o each portable container shall be legibly marked with the name "Hydrogen" per Sec. 1910.253(b)(1)(ii);
each manifolded hydrogen supply shall be legibly marked with the name "Hydrogen" or a legend such as
"This unit contains hydrogen". [29CFR1910.103(b)(1)(i)(c)]
o The hydrogen storage location shall be permanently placarded as follows:
"HYDROGEN - FLAMMABLE GAS - NO SMOKING - NO OPEN FLAMES" or equivalent.
[29CFR1910.103(b)(1)(v)]
29CFR1910.103(c) Liquified hydrogen systems

Location, Capacity, Siting, & Setbacks
- Location:
system shall be located such that:
o shall be readily accessible to mobile supply equipment and to authorized personnel;
o not located beneath electric power lines;
o not close to flammable liquid lines, flammable gas lines, or lines carrying oxidizing materials;
o and not higher than flammable liquid storage except where dikes, diversion curbs, grading, or separating
solid walls are used to prevent accumulation of liquids within 50 feet of the liquefied hydrogen container.
o Storage sites shall be fenced and posted to prevent entrance by unauthorized personnel.
[29CFR1910.103(c)(2)(i)]
o Adequate lighting shall be provided for nighttime transfer operation. [29CFR1910.103(c)(3)(i)(e)]
- Capacity & setback distances:
Table H-3 limits [29CFR1910.103(c)(2)(ii)(a)]
o 51 to 300 gallons is limited to outdoors, a separate building, or in a special room,
o 301 to 600 gallons is limited to outdoors, or in a separate building,
o >600 gallons liquid hydrogen storage to outdoors only,
o and allows 39.63 (150 liters) to 50 gallons to be stored inside building exposed to other occupancies.
o does not apply to storage of dewars used in laboratories for experimental purposes.
liquid H2 storage 50 gallons or less inside a building:
[29CFR1910.103(c)(2)(iii)]
o adequately ventilated per 29CFR1910.103(c)(1)(iv)(b) and 29CFR1910.103(c)(2)(i)(f):
 designed and located so that moisture cannot collect and freeze in a manner that would interfere
with proper operation,
Page 16 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers

o
o
o
o
o
o
o
o
safety relief devices vented unobstructed to the outdoors at a minimum elevation of 25 feet above
grade to a safe location.
20 feet from stored flammable liquids or materials,
25 feet from open flames, ordinary electrical equipment, or other sources of ignition,
25 feet from concentrations of people,
50 feet from ventilation intakes for air-conditioning equipment and air compressors,
50 feet from other flammable gas storage or storage oxidizing gases,
protected from damage or injury due to falling objects or working activity in the area,
containers are firmly secured and stored in an upright position,
no smoking, welding, or cutting operations while hydrogen is in the room.
29CFR1910.103(b)(2)(ii)(c) Table H4 defines the setback distances by storage capacity:
type of exposure
39.63
3,501 to
15,001 to
(150 liters)
15,000
30,000
to 3500 gallons
gallons
gallons
1. Fire-resistive building and fire walls
5 ft.
5 ft.
5 ft.
2. Noncombustible building
25 ft.
50 ft.
75 ft.
3. Other buildings
50 ft.
75 ft.
100 ft.
4. Wall openings, air-compressor intakes, inlets for air75 ft.
75 ft.
75 ft.
conditioning or ventilating equipment
5. Flammable liquids (above ground and vent or fill openings if
50 ft.
75 ft.
100 ft.
below ground)
6. Between stationary liquefied hydrogen containers
5 ft.
5 ft.
5 ft.
7. Flammable gas storage
50 ft.
75 ft.
100 ft.
8. Liquid oxygen storage and other oxidizers
100 ft.
100 ft.
100 ft.
9. Combustible solids
50 ft.
75 ft.
100 ft.
10. Open flames, smoking and welding
50 ft.
50 ft.
50 ft.
11. Concentrations of people
75 ft.
75 ft.
75 ft.
(for types of building construction, refer to NFPA No. 220 Standard Types of Building Construction -1969)



Container types & design & storage construction
- Containers:
o containers designed, constructed, tested to
 ASME Boiler & Pressure Vessel Code, Section VIII, Unfired Pressure Vessels 1968, or
 API Standard 620 Recommended Rules for Design and Construction of Large, Welded, LowPressure Storage Tanks, Second Edition (June 1963) and appendix R (April 1965),
[29CFR1910.103(c)(1)(i)(a)] - or  portable containers designed, constructed, and tested in accordance with US Dept. of
Transportation (DOT) Specifications and Regulations.
[29CFR1910.103(c)(1)(i)(b)]
Piping, Valves, Regulators, Fuel Controls
- Safety relief (overpressure release) devices:
o Stationary liquefied hydrogen containers shall be equipped with safety relief devices sized in accordance
with CGA Pamphlet S-1, Part 3, Safety Relief Device Standards for Compressed Gas Storage Containers;
[29CFR1910.103(c)(1)(iv)(a)(1)]
o Portable liquefied hydrogen containers complying with the U.S. Department of Transportation Regulations
shall be equipped with safety relief devices as required in the U.S. Department of Transportation
Specifications and Regulations.
o Safety relief devices shall be sized in accordance with the requirements of CGA Pamphlet S-1, Safety
Relief Device Standards, Part 1, Compressed Gas Cylinders and Part 2, Cargo and Portable Tank
Containers.
[29CFR1910.103(c)(1)(iv)(a)(2)]
Labeling & Signage
o Sites shall be placarded as follows:
"Liquefied Hydrogen - Flammable Gas - No Smoking - No Open Flames".[29CFR1910.103(c)(2)(i)(e)]
Page 17 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
Safe Transportation of Gaseous Hydrogen, Methane, & gas mixtures - Identified by
49CFR172.101 Hazardous Materials Table
(2)
Hazardous
(3)
(1)
materials
(4)
Hazard
(5)
Sym descriptions
Identification
class or
PG
bols and proper
Numbers
Division
shipping
names
(6)
Label
Codes
(7)
Special
provisions
(§172.102)
(8)
(9)
Packaging
(§173.***)
Quantity limitations
(see §§173.27 and
175.75)
Exceptions
Non-bulk Bulk
Passenger
aircraft/rail
Cargo
aircraft
only
Hydrogen,
compressed
2.1 UN1049
2.1
N89 306
302
302,
314
Forbidden
150kg
Methane or
natural gas,
compressed
2.1 UN1971
2.1
306
302
302
Forbidden
150kg
Hydrogen
and
Methane
mixtures,
compressed
2.1 UN2034
2.1
N89 306
302
302,
314,
315
Forbidden
150kg
(3) Hazard class or Division "2.1" :
flammable gas per 49CFR173.115(a) definitions
(4) Identification Numbers :
United Nations (international) material designation for shipping identification number
(6) Label Codes :
Flammable Gas [see 49CFR172.417 for labeling]
(7) Special provisions :
N89 = When steel UN pressure receptacles are used, only those bearing the “H” mark are authorized.
(8) Packaging :
Exceptions [49CFR173.306] = Limited quantities of compressed gases.
Non-bulk [49CFR173.302] = Filling of cylinders with nonliquefied (permanent) compressed gases.
per 49CFR173.301b(f) Hydrogen bearing gases: A steel UN pressure receptacle bearing an “H” mark must be
used for hydrogen bearing gases...
per 49CFR173.302a(a)(4): DOT 3AX, 3AAX, and 3T cylinders are authorized for Division 2.1…materials and
for carbon monoxide. DOT 3T cylinders are not authorized for hydrogen. When used in methane service, the
methane must be a nonliquefied gas with a minimum purity of 98.0% methane and commercially free of corroding
components.
Bulk
[49CFR173.314] = Compressed gases in tank cars and multi-unit tank cars.
[49CFR173.315] = Compressed gases in cargo tanks and portable tanks. Container Types approved for Div.
2.1 material (hydrogen, etc.): DOT-51, MC-330, MC-331
(9) Quantity limitations : Forbidden to ship on passenger aircraft or passenger rail, limit of 150kg for cargo aircraft.
Page 18 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
Safe Transportation of Liquified Hydrogen, Liquified Methane or Natural Gas - Identified by
49CFR172.101 Hazardous Materials Table
(2) Hazardous
(3)
(1)
materials
(4)
(6)
Hazard
(5)
Sym descriptions and
Identification
Label
class or
PG
bols proper shipping
Numbers
Codes
Division
names
(7)
Special
provisions
(§172.102)
(8)
(9)
Packaging
(§173.***)
Quantity limitations
(see §§173.27 and
175.75)
Exceptions
Non-bulk
Bulk
Passenger
aircraft/rail
Cargo
aircraft only
Hydrogen,
refrigerated liquid
(cryogenic liquid)
2.1 UN1966
2.1
T75, TP5 None
316
318,
319
Forbidden
Forbidden
Methane or
Natural Gas,
refrigerated liquid
(cryogenic liquid)
2.1 UN1972
2.1
T75, TP5 None
None
318
Forbidden
Forbidden
(3) Hazard class or Division "2.1" :
flammable (liquefied) gas per 49CFR173.115(a) definitions
(4) Identification Numbers :
United Nations (international) material designation for shipping identification number
(6) Label Codes :
Flammable Gas [see 49CFR172.417 for labeling]
(7) Special provisions :
T75 = "…refrigerated liquefied gases are authorized to be transported in portable tanks in accordance
with the requirements of §178.277 of this subchapter."
TP5 = " For a portable tank used for the transport of flammable refrigerated liquefied gases…the
maximum rate at which the portable tank may be filled must not exceed the liquid flow capacity of the primary pressure
relief system rated at a pressure not exceeding 120 percent of the portable tank's design pressure…a portable tank
shall have an outage of at least two percent below the inlet of the pressure relief device or pressure control valve,
under conditions of incipient opening, with the portable tank in a level attitude."
(8) Packaging :
Non-bulk [49CFR173.316] = Cryogenic liquids in cylinders.
(a)(3) "The jacket covering the insulation on a cylinder used to transport any flammable cryogenic liquid must
be made of steel."
(a)(5) No aluminum valves, pipe, or fittings.
(c) "…Specification DOT-4L cylinders (§178.57 of this subchapter) are authorized for the transportation of
cryogenic liquids when carried in the vertical position as follows:
(i) Each cylinder must be constructed, insulated and maintained so that during transportation the total rate of
venting shall not exceed 30 SCF of hydrogen per hour.
(ii) In addition to the marking requirements in §178.35 of this subchapter, the total rate of venting in SCF per
hour (SCFH) shall be marked on the top head or valve protection band in letters at least one-half inch high as follows:
“VENT RATE**SCFH” (with the asterisks replaced by the number representing the total rate of venting, in SCF per
hour)."
Bulk
[49CFR173.318] = Cryogenic liquids in cargo tanks. See section 318 for detailed requirements.
[49CFR173.319] = Cryogenic liquids in tank cars. See section 319 for detailed requirements.
(9) Quantity limitations : Forbidden to ship on passenger aircraft, passenger rail, or cargo aircraft.
Page 19 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
International Fire Code (IFC)- hydrogen & other flammable gases:
Hazard definition & safety performance criteria:
IFC2012: Chapter 50 Hazardous Materials - General Provisions
IFC2009: Chapter 50 Hazardous Materials - General Provisions
IFC2006: Chapter 50 Hazardous Materials - General Provisions
IFC2003: Chapter 27 Hazardous Materials - General Provisions
Code Requirements for Flammable Gases (including Liquid Hydrogen):
IFC2012: Chapter 58 Flammable Gases & Flammable Cryogenic Fluids
- including H2, methane, and CO shall comply with NFPA 55
IFC2009: Chapter 35 Flammable Gases & Flammable Cryogenic Fluids
- including H2, methane, and CO shall comply with NFPA 55
IFC2006: Chapter 35 Flammable Gases
& Chapter 32 Flammable Cryogenic Fluids
- including H2, methane, and CO shall comply with NFPA 55
IFC2003: Chapter 35 Flammable Gases;
& Chapter 32 Flammable Cryogenic Fluids
- including H2, methane, and CO shall comply with NFPA 50B

Definitions:
o all IFC editions define hydrogen gas or liquid as a Physical Hazard, Flammable gas, either Gaseous or
Liquified. [IFC2012: Chapter 50; IFC2009, IFC2006, IFC2003: Chapter 27]
 Components & Systems Certifications
- Permitting:
Compressed gases. IFC2012, 2009, 2006 [Section 105.6.8]; IFC2003 [Section 105.6.9]
o An operational permit is required for the storage, use, or handling at normal temperature & pressure (NTP)
of compressed gases in excess of…200 cubic feet (ft.3) per Table 105.6.8.
Cryogenic fluids. IFC2012, 2009, 2006 [Section 105.6.10]; IFC2003 [Section 105.6.11]
o An operational permit is required to produce, store, transport on site, use, handle, or dispense cryogenic
fluids in excess of…more than 1 gallon inside building or 60 gallons outside building for flammable
cryogenic fluid per Table 105.6.10.
 Location, Capacity, Siting, & Setbacks
- Fuel Storage:
Indoor:
IFC2012 Table 5003.1.1(1) Maximum Allowable Quantity [MAQ] per Control Area of Hazardous Materials
Posing a Physical Hazard
o MAQ: Storage & Closed-System Use - restricts Flammable Gas to 1000 ft3 and Liquified Flammable
Gas to 150 lbs per control area, or else control area is classified as Occupancy Group H-2 (fire
suppression required).
o Maximum quantities increased by 100% if an approved sprinkler system is in place; limit: Flammable Gas
to 2000 ft3 and Liquified Flammable Gas to 300 lbs per control area. [note d]
o Maximum quantities increased by 100% if stored in approved gas cabinet or storage cabinet; limit:
Flammable Gas to 2000 ft3 and Liquified Flammable Gas to 300 lbs per control area. [note e]
o If both an approved gas cabinet and approved sprinkler system are used, the 100% increase in MAQ is
applied accumulatively; limit: Flammable Gas to 4000 ft3 and Liquified Flammable Gas to 600 lbs per
control area. [note d & e]
Outdoor:
IFC2012 Table 5003.1.1(3) Maximum Allowable Quantity [MAQ] per Control Area of Hazardous Materials
Posing a Physical Hazard in an Outdoor Control Area:
o MAQ: Storage - restricts Flammable Gas to 3000 ft3 and Liquified Flammable Gas to 300 lbs per control
area. Total quantities for storage & use must not exceed Storage amounts.
o MAQ: Closed-System Use - restricts Flammable Gas to 1500 ft3 and Liquified Flammable Gas to 150
lbs per control area.
 Container types & design & storage construction
o "Compressed gas containers, cylinders and tanks shall be designed, fabricated, tested, marked with the
specifications of manufacture and maintained in accordance with the regulations of DOTn 49 CFR Parts
100-185 or the ASME Boiler and Pressure Vessel Code, Section VIII." [IFC2012 5303.2]
Page 20 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
 Piping, Valves, Regulators, Fuel Controls
IFC2012 Sec. 5003.2.2.1 & IFC2009,2006,2003 [Sec. 2703.2.2.1]
o Pressure-handling components designed to withstand pressure, structural, seismic stress & exposure.
o Readily accessible manual or automatic remotely activated fail-safe emergency shutoff valves installed at
point of use and the tank, cylinder, or bulk source; clearly identified and indicated by a sign.
o Approved leak detection and emergency shutoff or excess flow control required.
- Pressure Relief Devices:
o pressure relief devices sized and selected per CGA S-1.1, S-1.2, and S-1.3 or the ASME Boiler and
Pressure Vessel Code, Section VIII. [IFC2012 5303.3.2]
o "Pressure relief devices shall be arranged to discharge upward and unobstructed to the open air in such a
manner as to prevent any impingement of escaping gas upon the container, adjacent structures or
personnel.
Exception: DOTn specification containers having an internal volume of 30 cubic feet
(0.855 m3) or less." [IFC2012 5303.3.4]
o pressure relief devices protected from freeze [IFC2012 5303.3.5]
 Labeling & Signage
o Piping & tubing identified per ASME A13.1 to indicated the material conveyed.
 Fire & Emergency Response
o Performance requirements (for Performance-based design alternative) - if chosen by mfg.
[IFC2012
5001.3.3]
o Hazardous Materials Management Plan (HMMP) - if required by AHJ
[IFC2012 5001.5.1]
o Hazardous Materials Inventory Statement (HMIS) - if required by AHJ
[IFC2012 5001.5.2]
o Fire Suppression required in Gas rooms [IFC2012 5003.8.4.1]
International Fire Code (IFC)- additional requirements for hydrogen-generating and
refueling operations
[IFC2012.2309]
 Location, Capacity, Siting, & Setbacks
Outdoors:
o allowed per IFC Chapter 58, [IFC2012.2309.3.1.1]
Indoors:
o "Generation, compression, storage and dispensing equipment shall be located in indoor rooms or areas
constructed in accordance with the requirements of the International Building Code, the International Fuel
Gas Code and the International Mechanical Code and one of the following:
1. Inside a building in a hydrogen cutoff room designed and constructed in accordance with Section
421 of the International Building Code.
2. Inside a building not in a hydrogen cutoff room where the gaseous hydrogen system is listed and
labeled for indoor installation and installed in accordance with the manufacturer’s installation
instructions.
3. Inside a building in a dedicated hydrogen fuel-dispensing area having an aggregate hydrogen
delivery capacity no greater than 12 standard cubic feet per minute (SCFM) and designed and
constructed in accordance with Section 703.1 of the International Fuel Gas Code."
[IFC2012.2309.3.1.2]
International Fuel Gas Code (IFGC) - Gaseous Hydrogen Systems

Components & Systems Certifications
o Installation of gaseous hydrogen systems per IFGC Chapter 7 & IFC Chapters 53 & 58 [IFGC2012.701.1]
o Permits per IFC Section 106. [IFGC2012.701.2]
o Gaseous hydrogen systems, equipment and machinery shall be listed or approved [IFGC2012.704.1]
o "Stationary fuel-cell power systems having a power output not exceeding 10 MW shall be tested in
accordance with ANSI CSA America FC 1 and shall be installed in accordance with the manufacturer’s
installation instructions, NFPA 853, the International Building Code and the International Fire Code."
[IFGC2012.633.1]
"This code shall not apply to the following:…
5. Industrial gas applications using gases such as acetylene and acetylenic compounds, hydrogen, ammonia,
carbon monoxide, oxygen and nitrogen…."
IFGC2012.101.2.4]
Page 21 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers



- Pressure Testing requirement:
o "Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to
determine that the materials, design fabrication and installation practices comply with the requirements of
this code."
[IFGC2012.705.1]
o "Inspections shall consist of a visual examination of the entire piping system installation and a pressure
test. Hydrogen piping systems shall be inspected in accordance with this code. Inspection methods such
as outlined in ASME B31.3 shall be permitted where specified by the design engineer and approved by the
code official. Inspections shall be conducted or verified by the code official prior to system operation."
[IFGC2012.705.2]
o "A hydrostatic or pneumatic leak test shall be performed. Testing of hydrogen piping systems shall utilize
testing procedures identified in ASME B31.3 or other approved methods…"
 See IFGC2012 Section 705.3 for additional piping test criteria & methods.
Location, Capacity, Siting, & Setbacks
o Indoor limitation: "Flammable gas cylinders in occupancies regulated by the International Residential
Code shall not exceed 250 cubic feet (7.1 m3) at normal temperature and pressure (NTP)."
[IFGC2012.703.2.1]
o pressure relief devices arranged to discharge unobstructed per IFC Section 2309
[IFGC2012.703.3.8]
Container types & design & storage construction
o compressed gas containers, cylinders, and tanks per IFC Chapter 53 & 58 [IFGC2012.703.2] & designed,
constructed, and tested per IFC Chapter 50, AMSE Boiler & Pressure Vessel Code (Section VIII) or DOTn
49CFR Parts 100-180
[IFGC2012.703.2.2].
o handling of compressed gas containers, cylinders, and tanks per IFC Chapter 50.
[IFGC2012.704.4]
o "Compressed gas containers, cylinders and tanks, except those with a water volume less than 1.3 gallons
(5 L) and those designed for use in a horizontal position, shall be used in an upright position with the valve
end up. An upright position shall include conditions where the container, cylinder or tank axis is inclined as
much as 45 degrees (0.79 rad) from the vertical."
[IFGC2012.704.2]
Piping, Valves, Regulators, Fuel Controls
- Pressure Relief Devices
o containers & vessel pressure relief devices per ASME Boiler and Pressure Vessel Code (Section VIII),
DOTn 49CR Parts 100-180
[IFGC2012.703.3.3 & 703.3.4],
o sized and selected per CGA S-1.1, S-1.2, and S-1.3
[IFGC2012.703.3]
o no valves or mechanical restrictions between container and pressure relief devices [IFGC2012.703.3.1]
o pressure relief devices protected from debris & environment [IFGC2012.703.3.6]
o pressure relief devices readily accessible for inspection
[IFGC2012.703.3.7]
- Piping design
o "Piping and tubing materials shall be 300 series stainless steel or materials listed or approved for
hydrogen service and the use intended through the full range of operating conditions to which they will be
subjected."
[IFGC2012.704.1.2.3]
o "Piping passing through concrete or masonry walls shall be protected against differential settlement."
[IFGC2012.704.1.2.3.7]
o "Underground piping shall not penetrate the outer foundation or basement wall of a building."
[IFGC2012.704.1.2.3.4]
o "Piping shall not be installed in or through a circulating air duct; clothes chute; chimney or gas vent;
ventilating duct; dumbwaiter; or elevator shaft.
o Piping shall not be concealed or covered by the surface of any wall, floor or ceiling."
[IFGC2012.704.1.2.3.1]
o Valves, regulators and piping components shall be listed or approved for hydrogen service, shall be
provided with access and shall be designed and constructed to withstand the maximum pressure to which
such components will be subjected.
[IFGC2012.704.1.2.5]
- Joint construction:
o "Joints in piping and tubing in hydrogen service shall be listed as complying with ASME B31.3 to include
the use of welded, brazed, flared, socket, slip and compression fittings.
o Gaskets and sealants used in hydrogen service shall be listed as complying with ASME B31.3.
o Threaded and flanged connections shall not be used in areas other than hydrogen cutoff rooms and
outdoors."
[IFGC2012.704.1.2.4]
o "Brazing alloys shall have a melting point greater than 1,000°F (538°C)."
[IFGC2012.704.1.2.4.1]
o "Mechanical joints shall maintain electrical continuity through the joint or a bonding jumper shall be
installed around the joint." [IFGC2012.704.1.2.4.2]
Page 22 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers

- Indoor gas piping:
o "Where piping other than stainless steel piping, stainless steel tubing or black steel is installed through
holes or notches in wood studs, joists, rafters or similar members less than 11/2 inches (38 mm) from the
nearest edge of the member, the pipe shall be protected by shield plates. Shield plates shall be a
minimum of 1/16-inch-thick (1.6 mm) steel, shall cover the area of the pipe where the member is notched
or bored and shall extend a minimum of 4 inches (102 mm) above sole plates, below top plates and to
each side of a stud, joist or rafter." [IFGC2012.704.1.2.3.5]
o "Except for through penetrations, piping located inside of buildings shall be installed in exposed locations
and provided with ready access for visual inspection."
[IFGC2012.704.1.2.3.2]
- Outdoor gas piping:
o "Piping installed above ground, outdoors, shall be securely supported and located where it will be
protected from physical damage.
o Piping passing through an exterior wall of a building shall be encased in a protective pipe sleeve.
o The annular space between the piping and the sleeve shall be sealed from the inside such that the sleeve
is ventilated to the outdoors.
o Where passing through an exterior wall of a building, the piping shall also be protected against corrosion
by coating or wrapping with an inert material.
o Below-ground piping shall be protected against corrosion."
[IFGC2012.704.1.2.3.6]
- Shutoff Valves:
o Shutoff valves shall be provided on all storage container and tank connections except for pressure relief
devices. Shutoff valves shall be provided with ready access.
[IFGC2012.704.1.2.5.1]
Labeling & Signage
o "Hydrogen piping systems shall be marked in accordance with ANSI A13.1. Markings used for piping
systems shall consist of the name of the contents and shall include a direction-of-flow arrow. Markings
shall be provided at all of the following locations:
1. At each valve.
2. At wall, floor and ceiling penetrations.
3. At each change of direction.
4. At intervals not exceeding 20 feet (6096 mm)."
[IFGC2012.704.1.2.2]
International Fuel Gas Code (IFGC) - Liquified Hydrogen Systems

Components & Systems Certifications
o The design of liquefied hydrogen systems shall comply with Chapter 55 of the International Fire Code.
[IFGC2012.708.1]
International Fuel Gas Code (IFGC) - additional requirements for indoor hydrogengenerating and refueling operations
[IFGC2012.703.1]
 Location, Capacity, Siting, & Setbacks
o limited to 850 ft2 (79 m2) maximum floor area, [IFGC2012.703.1.1]
 Vents & Ventilation
o must be vented outdoors,
o not exceed 4 SCFM (0.00189 m 3/s) H2 generation for each 250 ft2 floor area,
o 3 in. (76 mm) minimum cross-sectional area of air openings,
o ignition sources (appliance or equipment) not within 12 in. (305 mm) of ceiling.
o two permanent vent openings in the same exterior wall:
o upper opening within 12 in. (305 mm) of ceiling &
o lower opening within 12 in. (305 mm) of the floor;
o vent minimum free area of 1/2 ft2 per 1000 ft3 (1 m2 per 610 m3) of garage volume
o ventilation louvers & grilles fixed in open position,
o Indoor locations require ventilation per International Mechanical Code (IMC) Section 502.16.
[IFGC2012.703.1.2]; ignition sources located below mechanical vent outlets.
o Alternately, an approved engineered system is allowed. [IFGC2012.703.1.3]
Page 23 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
NFPA 2 Hydrogen Technologies Code - 2011 edition (reference only)
Note: NFPA 2 is not specified or invoked by any legal compliance requirement. NFPA requirements may be invoked by
a local AHJ at their discretion, but not supported by law. NFPA 2 requirements are for reference only.
 Container types & design & storage construction
[NFPA 2-2011 7.1.5]
designed, fabricated, tested, and marked (stamped) in accordance with either
o U.S. Department of Transportation (DOT),
o Transport Canada (TC) Transportation of Dangerous Goods Regulations, or
o ASME Boiler & Pressure Vessel Code Rules for the Construction of Unfired Pressure Vessels Section VIII
(also referenced by NFPA 55 Section 7.1.5.1)
 Labeling & Signage
[NFPA 2-2011 7.1.6]
o containers, cylinders, and tanks marked in accordance with NFPA 704 Standard for the Identification of
Hazards of Materials for Emergency Response (also reference by NFPA 55 Section 7.1.8.3.1)
o piping systems marked in accordance with ASME A13.1 Scheme for the Identification of Piping Systems
or applicable approved codes and standards (also referenced by NFPA 55 Section 7.1.7.4.1);
 marking includes name of gas and direction-of-flow arrow;
 at each critical process control valve,
 at wall, floor, or ceiling penetrations
 at a minimum of every 20ft (6.1m) or fraction thereof throughout the piping run.
NFPA 55 Compressed Gases and Cryogenic Fluids Code - 2013 edition
Note: NFPA 55 uses "scf" (standard cubic feet) for volumetric limits, and a conversion rate of 1 scf = 0.02832 "Nm 3"
(Normal cubic meter). A "standard" cubic foot is measured at 60°F, while a "normal" cubic meter is measured at 0°C;
both are measured relative to 1 atmosphere of pressure.
NFPA 55 addresses flammable hydrogen gas storage requirements by location and quantity stored.
 Definitions
Definitions (Chapter 3) - Important definitions:
o Control Areas - A building or portion of a building within which hazardous materials are allowed to be
stored, dispensed, used, or handled in quantities not exceeding the maximum allowable quantities (MAQ).
[NFPA55-2013 3.3.6.1]
o Maximum Allowable Quantity per Control Area (MAQ) - A threshold quantity of hazardous material in a
specific hazard class that once exceeded requires the application of additional administrative procedures,
construction features, or engineering controls. [NFPA55-2013 3.3.66]
o Bulk Hydrogen Compressed Gas System. - An assembly of equipment that consists of, but is not limited
to, storage containers, pressure regulators, pressure relief devices, compressors, manifolds, and piping,
with a storage capacity of more than 5000 scf (141.6 Nm3) of compressed hydrogen gas and that
terminates at the source valve. [NFPA55-2013 3.3.93.2]
o Bulk Liquefied Hydrogen System. - An assembly of equipment that consists of, but is not limited to,
storage containers, pressure regulators, pressure relief devices, vaporizers, liquid pumps, compressors,
manifolds, and piping, with a storage capacity of more than 39.7 gal (150 L) of liquefied hydrogen that
terminates at the source valve. [NFPA55-2013 3.3.93.4]
Hazardous Materials - General Provisions
o Emergency plan required when exceeding MAQ (max allowable quantity), or when required by AHJ.
[NFPA55-2013 4.2.1.1]
o Emergency plan details (MSDS, emergency procedures, emergency contact info, hazard identification
labeling, etc.) [NFPA55-2013 4.2.1.2]
o Potential electrical ignition sources shall be listed or approved for use with the hazardous material (NRTL
listed, and class) [NFPA55-2013 4.9.3]
Chapter 6 Building-Related Controls - defines Control Areas inside a building, defines the construction of gas rooms
Chapter 7 Compressed Gases - Non-Bulk Storage: <5000 scf (standard cubic feet) stored
Chapter 8 Cryogenic Fluids - Non-Bulk Liquified Hydrogen <39.7 gal (150 L) stored
Page 24 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
Chapter 10 Bulk Hydrogen Compressed Gas Storage: ≥5000 scf, or exceeding MAQ per control area.
Chapter 11 Bulk Liquified Hydrogen Systems
≥39.7 gal (150 L) stored
Chapter 12 Gas Generation Systems - includes electrolyzers and catalytic reforming hydrogen generators
o
o
Table 6.2.1 defines the MAQ derating for control areas for floor levels above grade plane, limits number of
control areas per floor based on the Fire Resistance Rating for Fire Barriers
Table 6.5 requires a detached building for bulk hydrogen compressed gas systems that exceed 15,000 scf
(425Nm3)

Piping, Valves, Regulators, Fuel Controls
Non-Bulk Storage:
o Piping per ANSI/ASME B31.3, Process Piping, or other approved standard [NFPA55-2013 7.3.1.3]
Bulk Storage:
o Piping, tubing, valves, and fittings shall be designed and installed in accordance with ASME B31.12,
Hydrogen Piping and Pipelines, NFPA 55 Section 7.3.1.3, and IFC Sections 704.1.2.3, 704.1.2.4, and
704.1.2.5.
o Cast-iron pipe, valves, and fittings shall not be used. [NFPA55-2013 10.2.2]
o Prior to initial operation, all piping inspected & pressure tested per ASME B31.12, Hydrogen Piping and
Pipelines, and IFC Section 705. [NFPA55-2013 10.2.2.1]

Labeling & Signage
Non-Bulk Storage:
o No Smoking with 25ft (7.6m) of outdoor storage areas, dispensing areas, or open use areas [NFPA552013 4.9.1];
o No Smoking signs required [NFPA55-2013 4.10.3] .
Bulk Storage:
o Permanent placard for area: [NFPA55-2013 10.2.1.2]
"HYDROGEN - FLAMMABLE GAS - NO SMOKING - NO OPEN FLAMES"
o cylinders, containers, & tanks marked per NFPA 704
[NPFA55-2013 7.1.8.3.1]
NPFA 704 - hydrogen gas
NFPA 704 - methane gas
Page 25 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
NFPA 55 Compressed Gases and Cryogenic Fluids Code - additional requirements for
hydrogen-generating and refueling operations




Definitions
o applies to systems rated from greater than 0.08 lbs/hr (36 g/hr) to less than 55 lbs/hr (25 kg/hr). [NFPA552013 12.3.2.2]
Components & Systems Certifications
o Fuel processing equipment integrated into a listed fuel cell power system are installed per NFPA 853.
[NFPA55-2013 12.3.2.3]
o Safety related controls per NFPA79 Electrical Standard for Industrial Machinery. [NFPA55-2013
12.3.2.4.(8)]
o Electrolyzers tested and approved to ISO/DIS 22734 Hydrogen Generators Using Water Electrolysis
Process. [NFPA55-2013 12.3.2.7.1]
Location, Capacity, Siting, & Setbacks
o footing per ASCE/SEI 7 Minimum Design Loads for Buildings and Other Structures. [NFPA55-2013
12.3.2.4.(1)]
o protected from environment & unauthorized access (Fire Dept. access required).
o setbacks per Table 10.3.2.1(a), Table 10.3.2.1(b), or Table 10.3.2.1(c). [NFPA55-2013 12.3.2.4.(2) & (6)]
- Rooftop & penthouse installation:
o Hydrogen reformers or gasifiers are prohibited from rooftop or penthouse installation of occupied
structures, unless listing or approval is specific for rooftop installations. [NPFA55-2013 12.3.2.5.1.1 &
12.3.2.5.1.2]
o roofing material under and within 12 inches (305 mm) horizontally of a fuel cell power components or
system shall be Class A rating or noncombustible per building code. [NFPA55-2013 12.3.2.5.3]
- Outdoor installation:
o see ventilation requirements…
- Indoor installation:
o room separated from remainder of building by 1-hour fire resistance rated floor, wall, and ceiling per ASTM
E119 Standard Test Methods for Fire Tests of Building Construction and Materials. or UL 263 Fire Tests of
Building Construction & Materials. [NFPA55-2013 12.3.2.8.3.3]
o Openings between indoor use and other occupied spaces require protection by fire doors & dampers per
NFPA90A Standard for Installation of Air-Conditioning and Ventilation Systems, installed per NFPA80
Standard for Fire Doors and Other Opening Protectives, and require egress per NFPA101 Life Safety
Code. [NFPA55-2013 12.3.2.8.3.5. through 12.3.2.8.3.8]
o fire-rated separation is not required if hydrogen generating & storage does not exceed 400 scf (11.33 Nm 3)
[NFPA55-2013 12.3.2.4.(7)]
o Clearances from other combustible materials per NFPA31 Standard for the Installation of Oil-Burning
Equipment, NFPA54 National Fuel Gas Code, or NFPA58 Liquified Petroleum Gas Code. [NFPA55-2013
12.3.2.8.7.3]
Piping, Valves, Regulators, Fuel Controls
o Installed per ANSI/ASME B31.3 Process Piping. [NFPA55-2013 12.3.2.8.4.2]
o accessible shutoff valve in the reformer fuel piping, located within 6 ft (1.8 m) of the fuel storage, [NFPA552013 12.3.2.8.4.3]
o unless the power system is installed in a room with a 1-hour fire resistance rating; else a second
accessible shutoff valve located within 6 ft (1.8 m) of the power system is required, [NFPA55-2013
12.3.2.8.4.4]
o unless the power system is installed in a room with a 1-hour fire resistance rating; then the valve shall be
located outside of the room. [NFPA55-2013 12.3.2.8.4.5]
o Reformer systems using flammable liquid fuel, installed indoors, must: [NFPA55-2013 12.3.2.8.7.3]
 contain less than 5 gal (0.019m3) liquid fuel during all modes of operation, standby, and
shutdown,
 store bulk quantities of fuel outside,
 indoor fuel piping requires solid tubing or piping, all-welded, soldered, or brazed up through the
reformer enclosure,
 leak detection and automatic isolation of the indoor fuel piping to the outdoor bulk fuel supply,
 outdoor bulk supplies require an automatic isolation valve at the tank if located at a higher
elevation than the reformer.
Page 26 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers



requires an automatic shutoff valve outside the building using a gas detection system that will
close the valve above 25% LFL concentration. [NFPA55-2013 12.3.2.8.4.6]
 combustible gas detector installed per NFPA853 8.1.5.4 through 8.1.5.8 (unless fuel is odorized
and fuel gas system is listed for indoor use). [NFPA55-2013 12.3.2.8.8.1]
Vents & Ventilation
o prevent building air from being exposed to hazardous & toxic atmosphere in excess of OSHA limits
[NFPA55-2013 12.3.2.8.2.1, 12.3.2.8.3.2]
- Outdoor installation:
o exhaust outlets from reformer fuel-bearing components located at least 50 ft (15 m) from HVAC air
intakes, windows, doors, and other building openings, and not directed onto walkways or other pedestrian
paths. [NFPA55-2013 12.3.2.8.2.2]
- Indoor installation:
o ventilation & exhaust must be negative or neutral pressure (with respect to the surrounding building) in the
room where a reformer is use. [NFPA55-2013 12.3.2.8.5.3]
o Natural ventilation may be use if verified safe. [NFPA55-2013 12.3.2.8.5.5] Mechanical ventilation, if used,
requires a control interlock to shut down the system safely if ventilation fails. [NFPA55-2013 12.3.2.8.5.4]
Fire & Emergency Response
o Fire protection requirements per NFPA 853,
o Carbon Monoxide detector installed in the reformer enclosure, the reformer exhaust, or the room it's in.
[NFPA55-2013 12.3.2.8.6]
o For indoor installations if used without ventilation air from the outside, a limit control or method is required
to prevent ambient oxygen levels from dropping below 18% by volume. [NFPA55-2013 12.3.2.8.7.3]
Page 27 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
Fuel: Flammable Liquids - Methanol
OSHA (29CFR1910): Subpart H - Hazardous Materials
Methanol
29CFR1910.106 Flammable Liquids



Definitions
o Flammable Liquid - flashpoint at or below 199.4°F (93°C) [29CFR1910.106(a)(19)]
Methanol (from MSDS): flashpoint = 51.8°F (11°C), boiling point = 148.5°F (64.7°C)
o Methanol is defined as Category 2 Flammable Liquid: Packing Group II: flashpoint below 73.4°F (23°C),
and having a boiling point above 95°F (35°C), Hazard Class 3 flammable liquid, UN1230 identification
number, [per 49CFR173.121]
o "Atmospheric tank…operate at pressures for atmospheric through 0.5 psi." [29CFR1910.106(a)(2)]
Flammable liquid (fuel storage) for methanol reformers is stored in an atmospheric tank.
Location, Capacity, Siting, & Setbacks
- Outdoor storage, aboveground
o "The distance between any two flammable liquid storage tanks shall not be less than 3 feet."
[29CFR1910.106(b)(2)(ii)(a)]
o "…the distance between any two adjacent tanks shall not be less than one-sixth the sum of their
diameters. When the diameter of one tank is less than one-half the diameter of the adjacent tank, the
distance between the two tanks shall not be less than one-half the diameter of the smaller tank."
[29CFR1910.106(b)(2)(ii)(b)]
o See 29CFR1910.106(b)(2)(ii)(f) for further requirements when locating flammable liquid near liquefied
petroleum gas (e.g.; LNG, butane fluid, etc.).
o See 29CFR1910.106(b)(2)(vii) for further requirements for drainage, dikes, & walls for fluid containment of
aboveground tanks. Drainage, dikes, or walls are required to contain the full capacity of the storage tank,
prevent a leak from causing damage if the spilled fluid ignites.
o "No aboveground vertical storage tank containing a flammable liquid shall be located so that the allowable
liquid level within the tank is below the established maximum flood stage, unless the tank is
provided with a guiding structure such as described in (m), (n), and (o) of this subdivision."
[29CFR1910.106(b)(5)(vi)(a)]
o Flood Areas: see all sections under 29CFR1910.106(b)(5)(vi) for location requirements & restrictions for
storage in flood areas.
- Outdoor storage, underground
o See all sections under 29CFR1910.106(b)(3) for location requirements & restrictions for underground
tanks.
o "…The distance from any part of a tank storing Category… 2 flammable liquids…to the nearest wall of any
basement or pit shall be not less than 1 foot, and to any property line that may be built upon, not less than
3 feet." [29CFR1910.106(b)(3)(i)]
- Indoor storage
o "Location." Tanks shall not be permitted inside of buildings except as provided in paragraphs (e), (g),
(h), or (i) of this section."
i.e.; restricted except for (e) Industrial Plants, (g) Service Stations, (h)
Processing Plants, (i) Refineries, Chemical Plants, Distilleries. [29CFR1910.106(b)(4)(i)]
o See all sections under 29CFR1910.106(b)(4) for venting indoor tank locations that are allowed.
Container types & design & storage construction
- Storage:
o "flammable liquids shall be stored in a tank or in a container that complies with paragraph (d)(2) of this
section." [29CFR1910.106(a)(32)]
- Construction:
o "Only approved containers and portable tanks shall be used. Metal containers and portable tanks meeting
the requirements of and containing products authorized by chapter I, title 49 of the Code of Federal
Regulations (regulations issued by the Hazardous Materials Regulations Board, Department of
Transportation), shall be deemed to be acceptable." [29CFR1910.106(d)(2)(i)]
o Tanks may be built of materials other than steel for installation underground or if required by the properties
of the liquid stored. Tanks located above ground or inside buildings shall be of noncombustible
construction. [29CFR1910.106(b)(1)(i)]
o Tanks at atmospheric pressure must follow good standards of design; steel tanks may use these
standards: [29CFR1910.106(b)(1)(iii)]
Page 28 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers


Underwriters' Laboratories, Inc., (UL) Subject No. 142, Standard for Steel Aboveground Tanks for
Flammable and Combustible Liquids, 1968; or
 UL Subject No. 58, Standard for Steel Underground Tanks for Flammable and Combustible
Liquids, Fifth Edition, December 1961; or
 UL Subject No. 80, Standard for Steel Inside Tanks for Oil-Burner Fuel, September 1963.
 American Petroleum Institute Standards No. 650, Welded Steel Tanks for Oil Storage, Third
Edition, 1966.
o Tanks at low pressure (0.5 to 15 psig) may be used as tanks at atmospheric pressure, must follow good
standards of design, and low pressure tanks may use these standards: [29CFR1910.106(b)(1)(iv)]
 American Petroleum Institute Standard No. 620. Recommended Rules for the Design and
Construction of Large, Welded, Low-Pressure Storage Tanks, Third Edition, 1966.
 The principles of the Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler and
Pressure Vessels Code, 1968.
o Pressure vessels may be used as tanks at atmospheric pressure. Pressure vessels shall be built in
accordance with: [29CFR1910.106(b)(1)(v)]
 The Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler and Pressure Vessel
Code 1968.
o "Tank supports shall be installed on firm foundations. Tank supports shall be of concrete, masonry, or
protected steel. Single wood timber supports (not cribbing) laid horizontally may be used for outside
aboveground tanks if not more than 12 inches high at their lowest point." [29CFR1910.106(b)(5)(i)]
o "Fire resistance. Steel supports or exposed piling shall be protected by materials having a fire resistance
rating of not less than 2 hours, except that steel saddles need not be protected if less than 12 inches high
at their lowest point. Water spray protection or its equivalent may be used in lieu of fire-resistive materials
to protect supports." [29CFR1910.106(b)(5)(ii)]
Vents & Ventilation
o "Atmospheric storage tanks shall be adequately vented to prevent the development of vacuum or pressure
sufficient to distort the roof of a cone roof tank or exceeding the design pressure in the case of other
atmospheric tanks, as a result of filling or emptying, and atmospheric temperature changes."
[29CFR1910.106(b)(2)(iv)]
o Normal vents shall be sized either in accordance with:
 The American Petroleum Institute Standard 2000 (1968), Venting Atmospheric and Low-Pressure
Storage Tanks…[29CFR1910.106(b)(2)(iv)(b)(1)] or
 other accepted standard [29CFR1910.106(b)(2)(iv)(b)(2)]; or
 shall be at least as large as the filling or withdrawal connection, whichever is larger but in no case
less than 1 1/4 inch nominal inside diameter." [29CFR1910.106(b)(2)(iv)(b)(3)]
o "…Tanks and pressure vessels storing Category 2 flammable …shall be equipped with venting devices
which shall be normally closed except when venting under pressure or vacuum conditions, or with
approved flame arresters." [29CFR1910.106(b)(2)(iv)(f)(1)]
o "Exemption: …outside aboveground atmospheric tanks under 1,000 gallons capacity containing other
than Category 1 flammable liquids may have open vents. (See paragraph (b)(2)(vi)(b) of this section."
[29CFR1910.106(b)(2)(iv)(f)(2)]
o "Flame arresters or venting devices required in paragraph (b)(2)(iv)(f) of this section may be omitted
for Category 2 flammable liquids… where conditions are such that their use may, in case of obstruction,
result in tank damage. [29CFR1910.106(b)(2)(iv)(g)]
o "Where vent pipe outlets for tanks storing Category 1 or 2 flammable liquids…are adjacent to buildings
or public ways, they shall be located so that the vapors are released at a safe point outside of buildings
and not less than 12 feet above the adjacent ground level. In order to aid their dispersion, vapors shall
be discharged upward or horizontally away from closely adjacent walls. Vent outlets shall be located so
that flammable vapors will not be trapped by eaves or other obstructions and shall be at least 5 feet from
building openings." [29CFR1910.106(b)(2)(vi)(b)]
Page 29 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
29CFR1926.152 Flammable Liquids (Safety & Health Regulations for Construction)

Container types & design & storage construction
- Indoor Storage:
o "No more than 25 gallons of flammable liquids shall be stored in a room outside of an approved storage
cabinet." [29CFR1926.152(b)(1)]
o "Quantities of flammable liquid in excess of 25 gallons shall be stored in an acceptable or approved
cabinet…" [29CFR1926.152(b)(2)]
 Requirements for "approved cabinet" under 29CFR1926.152(b)(2) subsections.
o "Not more than 60 gallons of Category 1, 2 and/or 3 flammable liquids…shall be stored in any one
storage cabinet. Not more than three such cabinets may be located in a single storage area…"
[29CFR1926.152(b)(3)]
o Additional storage is allowed in an "inside storage room" under 29CFR1926.152(b)(4) subsections
Safe Transportation of Methanol - Identified by 49CFR172.101 Hazardous Materials Table
(2)
(8)
Hazardous
Packaging
(3)
(7)
(1)
materials
(4)
(6)
(§173.***)
Hazard
(5)
Special
Sym descriptions
Identification
Label
class or
PG
provisions
bols and proper
Numbers
Codes
Division
(§172.102) Exceptions Nonshipping
bulk
names
+I
Methanol
3 UN1230
II 3, 6.1
IB2, T7,
TP2
150
202
(9)
Quantity limitations
(see §§173.27 and 175.75)
Bulk
Passenger
aircraft/rail
Cargo aircraft
only
242
1 Liter
60 Liters
(1) Symbol "+ " :
the material is known to pose a risk to humans
(1) Symbol "I" : The letter “I” identifies proper shipping names which are appropriate for describing materials in
international transportation. An alternate proper shipping name may be selected when only domestic transportation is
involved (i.e.; must call it "Methanol", not "Methyl Alcohol")
(2) "Methanol" proper shipping name
(3) Hazard class or Division "3" : flammable liquid per 49CFR173.120(a) definitions
(4) Identification Numbers :
United Nations (international) material designation for shipping identification number
(5) PG : Packing Group II flashpoint below 73.4°F (23°C), and having a boiling point above 95°F (35°C) per
49CFR173.121(a)(1).
(6) Label Codes :
Flammable Liquid [see 49CFR172.419 for labeling], Poison [see 49CFR172.430 for labeling]
(7) Special provisions :
IB2 = special provision for Intermediate Bulk Container (IBC);
T7 = special provision for UN or IM Specification portable tanks;
TP2 = special provision for UN or IM Specification portable tanks.
(8) Packaging :
Exceptions [49CFR173.150] = inner packaging not over 1.0 Liter (0.3 gallons) net capacity each…
Non-bulk [49CFR173.202] = Non-bulk packagings for liquid hazardous materials in Packing Group II.
Non-bulk packaging: liquid capacity does not exceed 119 gallons (450L) [49CFR171.8]
Bulk [49CFR173.242] = Bulk packagings for certain medium hazard liquids and solids, including solids with dual
hazards. Defines requirements for (a) Rail cars (see specification for details), (b) Cargo tanks (see specification for
details), and
(c) Portable tanks.
DOT Specification 51, 56, 57 and 60 portable tanks;
Specification IM 101, IM 102, and UN portable tanks;
and marine portable tanks conforming to 46 CFR part 64 are authorized.
(9) Quantity limitations : limit of 1 Liter for passenger aircraft or passenger rail, limit of 60 Liters for cargo aircraft.

Label specifications: [49CFR172.407]
o "Durability.
 Each label, whether printed on or affixed to a package, must be durable and weather resistant. A
label on a package must be able to withstand, without deterioration or a substantial change in
color, a 30-day exposure to conditions incident to transportation that reasonably could be
expected to be encountered by the labeled package."
Page 30 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
o


"Design.
 Except for size and color, the printing, inner border, and symbol on each label must be as shown
in §§172.411 through 172.448 of this subpart, as appropriate." "The dotted line border shown on
each label is not part of the label specification, except when used as an alternative for the solid
line outer border to meet the requirements of §172.406(d) of this subpart."
o "Size.
 Each diamond (square-on-point) label …must be at least 100 mm (3.9 inches) on each side with
each side having a solid line inner border 5.0 to 6.3 mm (0.2 to 0.25 inches) from the edge."
 "…the hazard class number, or division number, as appropriate, must be at least 6.3 mm (0.25
inches) and not greater than 12.7 mm (0.5 inches)."
 "When text indicating a hazard is displayed on a label, the label name must be shown in letters
measuring at least 7.6 mm (0.3 inches) in height."
o "Color.
 …(2) The symbol, text, numbers, and border must be shown in black on a label except that—
 White may be used on a label with a one color background of green, red or blue."
Fuel Transportation & Site Refueling
o "Areas in which flammable liquids are transferred at one time, in quantities greater than 5 gallons from one
tank or container to another tank or container, shall be separated from other operations by 25-feet
distance or by construction having a fire resistance of at least 1 hour. Drainage or other means shall be
provided to control spills. Adequate natural or mechanical ventilation shall be provided to maintain the
concentration of flammable vapor at or below 10 percent of the lower flammable limit."
[29CFR1926.152(e)(1)]
o "Transfer of Category 1, 2, or 3 flammable liquids from one container to another shall be done only when
containers are electrically interconnected (bonded)." [29CFR1926.152(e)(2)]
o " Dispensing devices and nozzles for Category 1, 2, or 3 flammable liquids shall be of an approved type.
[29CFR1926.152(e)(5)]
o "Category 1, 2, or 3 flammable liquids shall be kept in closed containers when not actually in use."
[29CFR1926.152(f)(1)]
o "The tank trucks shall comply with the requirements covered in the Standard for Tank Vehicles for
Flammable and Combustible Liquids, NFPA No. 385-1966." [29CFR1926.152(g)(2)]
o "The dispensing hose shall be an approved type." [29CFR1926.152(g)(3)]
o "The dispensing nozzle shall be an approved automatic-closing type without a latch-open device."
[29CFR1926.152(g)(4)]
Fire & Emergency Response
- Indoor:
o "At least one portable fire extinguisher, having a rating of not less than 20-B units, shall be located outside
of, but not more than 10 feet from, the door opening into any room used for storage of more than 60
gallons of flammable liquids." [29CFR1926.152(d)(1)]
- Outdoor:
o "At least one portable fire extinguisher having a rating of not less than 20-B units shall be located not less
than 25 feet, nor more than 75 feet, from any flammable liquid storage area located outside."
[29CFR1926.152(d)(2)]
Hazardous Substances - Reportable Quantity (RQ) - Methanol
Table 1 to Appendix A
Methanol = 5000lbs (2270kg) [49CFR172.101].
See also Table 302.4 List of Hazardous Substances and Reportable Quantities. [40CFR302.4]
At a specific gravity of 0.8822 for 70% methanol & 30% water, this is ~680 gallons (2573 Liters) at 68°F (20°C)
At a specific gravity of 0.792 for 100% methanol, this is ~758 gallons (2866 Liters) at 68°F (20°C)
Page 31 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
For Flammable Liquids:
International Fire Code (IFC)- methanol & other flammable liquids:
referenced sections:
IFC:
2012: Chapter 50 - Hazardous Materials - General Provisions
o Section 5001.2 Material classification
o Section 5001.3 Performance-based design alternative, specifically,
o Section 5001.3.3 Performance requirements
o Section 5001.5.1 Hazardous Materials Management Plan (HMMP)
o Section 5001.5.2 Hazardous Materials Inventory Statement (HMIS)
o Section 5003.1.1 Maximum Allowable Quantity (MAQ) per Control Area
Chapter 57 - Flammable and Combustible Liquids
 Definitions
IFC(all editions) [Section 202]:
o Flammable Liquid - Class IB: (e.g.; methanol): flashpoint below 73°F (23°C), and having a boiling point
at or above 1--°F (30°C); does not include cryogenic fluids (like liquefied hydrogen)
o Combustible Liquid: "A liquid having a closed cup flash point at or above 100°F (38°C)."
o Explosive: "The term "Explosive" includes any material determined to be within the scope of USC Title 18:
Chapter 40 and also includes any material classified as an explosive other than consumer fireworks, 1.4G
by the hazardous materials regulations of DOTn 49 CFR Parts 100-185."
Methanol is a Class IB flammable liquid; it is not a combustible liquid , it is not an explosive.
Note: Methanol is defined as a Class I Group D flammable vapor per National Electric Code [NFPA70-2014 500.6]
for relevance, see Table 5703.1.1 Class I Electrical Equipment Locations
o Toxic: "A chemical falling within any of the following categories:
1. median lethal dose (LD50) > 50 milligrams per kilogram, < 500 milligrams per kilogram of body weight when
administered orally to albino rats weighing between 200 and 300 grams each.
2. median lethal dose (LD50) > 200 milligrams per kilogram & < 1,000 milligrams per kilogram of body weight when
administered by continuous contact for 24 hours (or less if death occurs within 24 hours) with the bare skin of albino
rabbits weighing between 2 and 3 kilograms each.
3. median lethal concentration (LC50) in air > 200 parts per million & < 2,000 parts per million by volume of gas or
vapor, or > 2 milligrams per liter & < 20 milligrams per liter of mist, fume or dust, when administered by continuous
inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats weighing between 200 and 300 grams each."
Methanol (from MSDS);
100% concentration; diluted concentrations with water have higher median lethal dose & concentrations:
1. LD50/oral/rat: >1100 mg/kg
2. LD50/dermal/rabbit: >17000 mg/kg
3. LC50/inhalation/4hr/rat: >128 mg/liter/4hr
Methanol (including methanol-water mixtures) is not classified as Toxic
o Container: "A vessel of 60 gallons (227 L) or less in capacity used for transporting or storing hazardous
materials. Pipes, piping systems, engines and engine fuel tanks are not considered to be containers."
o Tank: "A vessel containing more than 60 gallons (227 L)."
Capacity of 60 gallons or less is a 'container', over 60 gallons is a 'tank'.
o Control Area: "Spaces within a building where quantities of hazardous materials not exceeding the
maximum allowable quantities per control area are stored, dispensed, used or handled…"
o Outdoor control area. "An outdoor area that contains hazardous materials in amounts not exceeding the
maximum allowable quantities of Table 5003.1.1(3) or Table 5003.1.1(4)."
Per Table 5003.1.1(3) & Table 5003.1.1(4), methanol does not have a MAQ for outdoor control areas (no 'flammable
liquid' listed under 'MATERIAL').
o Closed System: "The use of a solid or liquid hazardous material involving a closed vessel or system that
remains closed during normal operations where vapors emitted by the product are not liberated outside of
the vessel or system and the product is not exposed to the atmosphere during normal operations; and all
uses of compressed gases. Examples of closed systems for solids and liquids include product conveyed
through a piping system into a closed vessel, system or piece of equipment."
Page 32 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
o
Open System: "The use of a solid or liquid hazardous material involving a vessel or system that is
continuously open to the atmosphere during normal operations and where vapors are liberated, or the
product is exposed to the atmosphere during normal operations. Examples of open systems for solids and
liquids include dispensing from or into open beakers or containers, dip tank and plating tank operations."
A methanol tank vented to the atmosphere through a flame arrestor may be classified as a Closed System.




Components & Systems Certifications
o "An operational permit is required:
2. To store, handle or use Class I liquids in excess of 5 gallons (19 L) in a building or in excess of 10
gallons (37.9 L) outside of a building…" [IFC2012 105.6.16]
o Electrical equipment must be Class I Division 1 or 2 depending on proximity to indoor or outdoor storage
per Table 5703.1.1 Class I Electrical Equipment Locations unless amended by AHJ. [IFC2012 5703.1]
Location, Capacity, Siting, & Setbacks
o Spill control: If MAQ is exceeded, or if individual capacity storage of more than 55 gallons (208 L), or
multiple storage vessels exceeding 1000 gallons (3785 L): [IFC2012 5703.4]
"1. Liquid-tight sloped or recessed floors in indoor locations or similar areas in outdoor locations.
2. Liquid-tight floors in indoor locations or similar areas in outdoor locations provided with liquid-tight raised or
recessed sills or dikes.
3. Sumps and collection systems.
4. Other approved engineered systems."
[IFC2012 5004.2.1]
- Fuel Storage:
o See IFC2012 5704.2.9.1 through 5704.2.9.7.10 for above-ground tank storage detailed requirements.
o See IFC2012 5704.2.11.1 through 5704.2.11.5.2 for underground tank storage detailed requirements.
o Vaults are approved for above or below grade; shall be listed in accordance with UL 2245 NRTL certified
or approved for liquid tightness, drain to a sump, wind & seismic resistant per IBC, resistant to hydrostatic
& soil loads for below grade. Floor and walls of the vault shall be reinforced concrete at least 6 inches (152
mm) thick, roof made of noncombustible material weaker than the walls of the vault (to allow a pressure
burst upward). [IFC2012 5704.2.8]
o Storage inside buildings for containers & portable tanks (not exceeding 60 gallons) per IFC2012
5704.3.3 - Exception: liquid in fuel tanks of portable or stationary engines.
Indoor MAQ:
Maximum Allowable Quantity [MAQ] per Control Area of Hazardous Materials Posing a Physical Hazard
[IFC2012 Table 5003.1.1(1)]
o Storage & Use-Closed Systems - restricts MAQ of Flammable Liquid (Class IB) to 120 gallons per
control area, Use-Open Systems - restricts MAQ to 30 gallons per control area, or control area is
classified as Occupancy Group H-2 or H-3 (fire suppression required).
o Maximum quantities increased by 100% if an approved sprinkler system is in place.
 resulting limit: Flammable Liquid (Class IB) to 240 gallons per control area. [note d]
o Maximum quantities increased by 100% if stored in approved gas cabinet or storage cabinet.
 resulting limit: Flammable Liquid (Class IB) to 240 gallons per control area. [note e]
o If both an approved gas cabinet and approved sprinkler system are used, the 100% increase in MAQ is
applied accumulatively.
 resulting limit: Flammable Liquid (Class IB) to 480 gallons per control area. [note d & e].
Outdoor MAQ:
o not defined (no limit criteria)
Container types & design & storage construction
o "The design, fabrication and construction of tanks shall comply with NFPA 30. Each tank shall bear a
permanent nameplate or marking indicating the standard used as the basis of design." [IFC2012 5704.2.7]
Storage Cabinet (may be used for containers & portable tanks under 60 gallons; total storage of 120 gallons
maximum per cabinet):
o see IFC2012 5704.3.2 for construction of storage cabinet for liquid fuel.
Piping, Valves, Regulators, Fuel Controls (including pressure relief devices)
o Piping designed and fabricated per ASME B31.1 (power), B31.3 (process), B31.4 (pipeline transport),
B31.9 (building services), and per NFPA 30 Chapter 27. [IFC2012 5703.6]
o Piping pressure tested (unless tested per ASME B31.9) hydrostatically to 150% or pneumatically at 110%
of maximum anticipated pressure, but not less than 5 psig (34.47kPa) at the highest point of the system;
for 10 minutes minimum; allow sufficient duration to inspect all tubing & joints. [IFC2012 5703.6.3]
Page 33 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
o


Piping must be mechanically supported and protected from damage, including corrosion and galvanic
action; supports protected against exposure to fire. [IFC2012 5703.6.5 & IFC2012 5703.6.5] Piping,
valves, and fittings must be protected from vehicular damage. [IFC2012 5703.6.4]
o Flexible joints required for underground piping where piping connects to underground tanks, termination at
pump islands & vent risers, and at points of differential movement. [IFC2012 5703.6.9]
o Pipe Joints:
[IFC2012 5703.10]
 "Joints shall be liquid tight and shall be welded, flanged or threaded except that listed flexible
connectors are allowed in accordance with Section 5703.6.9. Threaded or flanged joints shall
fit tightly by using approved methods and materials for the type of joint. Joints in piping
systems used for Class I liquids shall be welded when located in concealed spaces within
buildings."
 Nonmetallic joints shall be approved and shall be installed in accordance with the
manufacturer’s instructions.
 Pipe joints that are dependent on the friction characteristics or resiliency of combustible
materials for liquid tightness of piping shall not be used in buildings. Piping shall be secured to
prevent disengagement at the fitting."
o Pipe and tube bending per ASME B31.9. [IFC2012 5703.6.11]
o "Vaults shall be provided with approved vapor and liquid detection systems and equipped with on-site
audible and visual warning devices with battery backup. Vapor detection systems shall sound an alarm
when the system detects vapors that reach or exceed 25 percent of the lower explosive limit (LEL) of the
liquid stored. Vapor detectors shall be located no higher than 12 inches (305 mm) above the lowest point
in the vault. Liquid detection systems shall sound an alarm upon detection of any liquid, including water.
Liquid detectors shall be located in accordance with the manufacturer’s instructions. Activation of either
vapor or liquid detection systems shall cause a signal to be sounded at an approved, constantly attended
location within the facility serving the tanks or at an approved location. Activation of vapor detection
systems shall also shut off dispenser pumps." [IFC2012 5704.2.8.11]
Vents & Ventilation
o "Listed or approved flame arresters or pressure-vacuum (PV) vents that remain closed unless venting
under pressure or vacuum conditions - shall be installed in normal vents of tanks containing Class
IB…liquids." [IFC2012 5703.6.9]
o "Tanks and pressure vessels storing Class IB or IC liquids shall be equipped with venting devices which
shall be normally closed except when venting under pressure or vacuum conditions, or with listed flame
arresters. The vents shall be installed and maintained in accordance with Section 21.4.3 of NFPA 30 or
API 2000." [IFC2012 5704.2.7.3.6]
o "Vent pipe outlets for tanks storing Class I, II or IIIA liquids shall be located such that the vapors are
released at a safe point outside of buildings and not less than 12 feet (3658 mm) above the finished
ground level. Vapors shall be discharged upward or horizontally away from adjacent walls to assist in
vapor dispersion. Vent outlets shall be located such that flammable vapors will not be trapped by eaves or
other obstructions and shall be at least 5 feet (1524 mm) from building openings or lot lines of
properties that can be built upon..." [IFC2012 5704.2.7.3.3]
o "Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive
internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not
discharge inside buildings. The venting shall be installed and maintained in accordance with Section 22.7
of NFPA 30." [IFC2012 5704.2.7.4]
o "Vaults that contain tanks of Class I liquids shall be provided with an exhaust ventilation system installed
in accordance with IFC2012 5004.3. The ventilation system shall operate continuously or be designed to
operate upon activation of the vapor or liquid detection system. The system shall provide ventilation at a
rate of not less than 1 cubic foot per minute (cfm) per square foot of floor area [0.00508 m 3/(s · m2)], but
not less than 150 cfm (4 m 3/min). The exhaust system shall be designed to provide air movement across
all parts of the vault floor. Supply and exhaust ducts shall extend to within 3 inches (76 mm), but not more
than 12 inches (305 mm), of the floor. The exhaust system shall be installed in accordance with the
International Mechanical Code." [IFC2012 5704.2.8.9]
Labeling & Signage
o Hazard identification signs. "Unless otherwise exempted by the fire code official, visible hazard
identification signs as specified in NFPA 704 for the specific material contained shall be placed on
stationary containers and above-ground tanks and at entrances to locations where hazardous materials
are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and
locations designated by the fire code official." [IFC2012 5003.5]
Page 34 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
o
Tanks more than 100 gallons (379 L) permanently installed or mounted and used for Class I…liquid
require identification and warning placard per NFPA 704 (underground tanks exempted). [IFC2012
5704.2.3]
NPFA 704 - Methanol
o
No Smoking signs: "Smoking shall be prohibited and "No Smoking” signs provided as follows…"
"2. Within 25 feet (7620 mm) of outdoor storage, dispensing or open use areas…"
"4. In rooms or areas where flammable or combustible hazardous materials are stored, dispensed or
used." [IFC2012 5003.7.1]
o
"Warning signs shall be of a durable material. Signs warning of the hazard of flammable liquids shall have
white lettering on a red background and shall read: DANGER—FLAMMABLE LIQUIDS. Letters shall not
be less than 3 inches (76 mm) in height and 1/2 inch (12.7 mm) in stroke. [IFC2012 5703.5.1]
Page 35 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
o
o
Piping labeled per ASME A13.1; locations as required by fire code official. [IFC2012 5703.5.2]
"A permanent sign shall be provided at the fill point for the tank, documenting the filling procedure and the
tank calibration chart.
Exception: Where climatic conditions are such that the sign may be obscured by ice or snow, or weathered
beyond readability or otherwise impaired, said procedures and chart shall be located in the office window,
lock box or other area accessible to the person filling the tank." IFC2012 5704.2.9.7.6.1]

Fuel Transportation & Site Refueling
o "Filling, emptying and vapor recovery connections to tanks containing Class I, II or IIIA liquids shall be
located outside of buildings in accordance with Section 5704.2.7.5.6 at a location free from sources of
ignition and not less than 5 feet (1524 mm) away from building openings or lot lines of property that can be
built upon. Such openings shall be properly identified and provided with a liquid-tight cap which shall be
closed when not in use."
[IFC2012 5704.2.7.5.2]
o "Filling, withdrawal and vapor-recovery connections for Class I, II and IIIA liquids which are made and
broken shall be located outside of buildings, not more than 5 feet (1524 mm) above the finished ground
level, in an approved location in close proximity to the parked delivery vehicle…." [IFC2012 5704.2.7.5.6]
o "An approved means or method in accordance with Section 5704.2.9.7.6 shall be provided to prevent the
overfill of all Class I, II and IIIA liquid storage tanks." [IFC2012 5704.2.7.5.8]
o "Protected above-ground tanks shall not be filled in excess of 95 percent of their capacity. An overfill
prevention system shall be provided for each tank. During tank-filling operations, the system shall comply
with one of the following:
1. The system shall:
1.1. Provide an independent means of notifying the person filling the tank that the fluid level has
reached 90 percent of tank capacity by providing an audible or visual alarm signal, providing a tank level
gauge marked at 90 percent of tank capacity, or other approved means; and
1.2. Automatically shut off the flow of fuel to the tank when the quantity of liquid in the tank reaches 95
percent of tank capacity. For rigid hose fuel-delivery systems, an approved means shall be provided to
empty the fill hose into the tank after the automatic shutoff device is activated.
2. The system shall reduce the flow rate to not more than 15 gallons per minute (0.95 L/s) so that at
the reduced flow rate, the tank will not overfill for 30 minutes, and automatically shut off flow into the tank
so that none of the fittings on the top of the tank are exposed to product because of overfilling." [IFC2012
5704.2.9.7.6]

Fire & Emergency Response
o Performance requirements (for Performance-based design alternative) - if chosen by mfg. [IFC2012
5001.3.3]
o Hazardous Materials Management Plan (HMMP) - if required by AHJ [IFC2012 5001.5.1]
o Hazardous Materials Inventory Statement (HMIS) - if required by AHJ
[IFC2012 5001.5.2]
o Fire Suppression - if required: [IFC2012 5705.3.7.3] Group H-2 or H-3 areas for flammable & combustible
liquids
o Fire protection for the storage, use, dispensing, mixing, handling, and on-site transportation of flammable
liquids per IFC Chapters 9 & 57.
Page 36 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
o
o
o
"When required by the fire code official, foam fire protection shall be provided for above-ground tanks,
other than pressure tanks operating at or above 1 pound per square inch gauge (psig) (6.89 kPa)
 when such tank, or group of tanks spaced less than 50 feet (15 240 mm) apart measured shell to
shell,
 has a liquid surface area in excess of 1,500 square feet (139 m2),
 and is in accordance with one of the following:
1. Used for the storage of Class I or II liquids. …
4. Considered by the fire code official as posing an unusual exposure hazard because of
topographical conditions; nature of occupancy, proximity on the same or adjoining property, and height
and character of liquids to be stored; degree of private fire protection to be provided; and facilities of
the fire department to cope with flammable liquid fires." [IFC2012 5704.2.9.2.1]
"Where foam fire protection is required, it shall be installed in accordance with NFPA 11." [IFC2012
5704.2.9.2.1]
"Where foam fire protection is required, foam-producing materials shall be stored on the premises.
Exception: Storage of foam-producing materials off the premises is allowed as follows:
1. Such materials stored off the premises shall be of the proper type suitable for use with the
equipment at the installation where required.
2. Such materials shall be readily available at the storage location at all times.
3. Adequate loading and transportation facilities shall be provided.
4. The time required to deliver such materials to the required location in the event of fire shall be
consistent with the hazards and fire scenarios for which the foam supply is intended.
5. At the time of a fire, these off-premises supplies shall be accumulated in sufficient quantities before
placing the equipment in operation to ensure foam production at an adequate rate without interruption
until extinguishment is accomplished." [IFC2012 5704.2.9.2.2.1]
International Fuel Gas Code (IFGC) - Liquid Fuel
 Components & Systems Certifications
Liquid-fueled fuel cell power systems, including methanol & LP are outside the scope of IFGC:
"This code shall not apply to the following:…
7. Integrated chemical plants or portions of such plants where flammable or combustible liquids or gases are produced
by, or used in, chemical reactions….
8. LP-gas installations at utility gas plants…
9. Liquefied natural gas (LNG) installations…" [IFGC2012.101.2.4]
NFPA 30 Flammable & Combustible Liquids Code - 2012 edition
NFPA 30 addresses flammable methanol/water mixture storage requirements by location and quantity stored.
NFPA 30 has different requirements & capacity limits for use in a process, i.e.; reformation (Chapter 17) vs. for bulk
storage (Chapters 10-16).
reformer fuel mix: Methanol/water blend, 60-70% (by weight) methanol to water, and has a flash point under 70°F.
Pure methanol and methanol/water blend as described above are Flammable Class IB liquids per Section 4.3.1

Definitions
o Flammable Liquid: Any liquid that has a closed-cup flash point below 100°F (37.8°C)…and a Reid vapor
pressure <40psi (276kPa) at 100°F (37.8°C). [NPFA30-2012 3.3.33.2]
o Classification of Liquids (Chapter 4):
Page 37 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers


(1) Class IB Liquid - Any liquid that has a flash point below 73°F (22.8°C) and a boiling point at or above 100°F
(37.8°C).. [NPFA30-2012 4.3.1]
o Containers & Tanks:
 Containers: vessel for use or storage not to exceed 119 gallons (450 L). [NPFA30-2012 Section
3.3.12]
 Intermediate Bulk Containers (IBC): closed vessel, not to exceed 793 gallons (3000 L),
intended for storage or transport per CFR49 Parts 100-199 (DOT) or Part 6 UN Recommendations
on the Transport of Dangerous Goods. [NPFA30-2012 3.3.12.4]
 Rigid nonmetallic intermediate bulk containers & composite IBCs:
 have a plastic vessel that serves as the primary liquid-holding component, enclosed in or
encased by an outer structure of steel cage, a single-wall metal or plastic enclosure, a
double wall of foamed or solid plastic, or a paperboard enclosure; also denotes an allplastic single-wall IBC that might or might not have a separate plastic base and for which
the containment vessel also serves as the support structure. U.S. Department of
Transportation (DOT) describes these as "composite IBCs".
 IBCs that have an outer liquid-tight metal structure are considered to be metal IBCs or
metal portable tanks by DOT. [NPFA30-2012 A.9.4.1(5)]
 Atmospheric Tank: storage tank designed for atmospheric to 1.0 psi (6.9 kPa) gauge pressure
measure at the top of the tank. [NPFA30-2012 3.3.51.2]
 Low-Pressure Tank: storage tank designed for pressures from 1.0 psi (6.9 kPa) to 15 psi (103
kPa) gauge pressure measured at the top of the tank. [NPFA30-2012 3.3.51.3]
 Pressure Vessel: tank designed to operate above 15 psi (100kPa). [NPFA30-2012 21.4.2.3.1]
 Portable Tank: storage tank over 60 gallons (230 L), not intended for fixed installations. [NPFA302012 3.3.51.4]
 Storage Tank: vessel for fixed installation, not used for processing, exceeds 60 gallons (230 L)
capacity. [NPFA30-2012 3.3.51.6]
 Secondary Containment Tank: tank with inner and outer walls with a means of leak detection in
the space between. [NPFA30-2012 3.3.51.5]
o Vault: an enclosure with a floor, 4 walls, and a top used only for containing a liquid Storage Tank.
[NPFA30-2012 3.3.59]
o Process or Processing: an integrated sequence of operations, including physical and or chemical
operations, involving (but not limited to) preparation, separation, purification, or change in state, energy
content, or composition. [NFPA30-2012 3.3.45 & A.3.3.45]
Components & Systems Certifications
o Electrical equipment must be Class I Division 1 or 2, Zone 1 or 2 depending on proximity to indoor or
outdoor storage per Table 7.3.3 Electrical Area Classifications unless amended by AHJ. [NFPA30-2012
7.3.3 - 7.3.6]
o Electrical equipment for Class I Division 1 or 2, or Zone 1 or 2 locations (classified area) may allow
ordinary electrical equipment in a room or enclosure if maintained at a positive pressure relative to the
classified area. [NFPA30-2012 7.3.7]
- Pressure Testing requirement:
 test per ASME B31, Code for Pressure Piping, all piping shall be tested before being covered,
enclosed, or placed in use. [NFPA30-2012 27.7.1]
 hydrostatic testing to 150 percent of the maximum anticipated pressure of the system or
pneumatically to 110 percent of the maximum anticipated pressure of the system; maintain test
pressure while a complete visual inspection of all joints and connections is conducted. [NFPA302012 27.7.1.1]
 test pressure no less than a gauge pressure of 5 psi (35 kPa) measured at the highest point of the
system, and the test pressure be maintained not less than 10 minutes duration. [NFPA30-2012
27.7.1.2]
Location, Capacity, Siting, & Setbacks
o basement storage for Class I liquids prohibited. [NFPA30-2012 9.3.6]
o for stable liquid, not over 2.5psi emergency relief pressure:
o Table 17.4.3 Location of Process Vessels with Respect to Property Lines, Public Ways, and the
Nearest Important Building on the Same Property….&
 275 gallons or less
5 ft (1.5 m) from Property Line (present & future)
Page 38 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers

 276-750 gallons
10 ft (3 m)
 751-12,000 gallons
15 ft (4.5 m)
 12,0001-30,000 gal
20 ft (6 m)
 30,001-50,000 gal
30 ft (9 m)
 50,001-100,000 gal
50 ft (15 m)
 over 100,000 gal
80 ft (24 m)
o Table 22.4.1.1.(a) Location of Aboveground Storage Tanks….
o Table 22.4.1.1.(b) Reference Table (for minimum distance from Property Line…)
o Storing near LP-Gas:
o 20 ft (6 m) minimum horizontal separation between LP-Gas containers and Class 1 Liquid storage.
[NFPA30-2012 22.4.2.4];
o including means to prevent Class 1 liquid from accumulating under LP-Gas containers [NFPA302012 22.4.2.4.1]
o LP-Gas outside of diked areas (if used), and at least 3 ft (0.9 m) from centerline of wall of diked
areas. [NFPA30-2012 22.4.2.4.2]
Indoor MAQ:
Maximum Allowable Quantity [MAQ] of Flammable Liquids per Control Area
[NFPA30-2012 Table 9.6.1]
o - restricts MAQ of Flammable Liquid (Class IB) to 120 gallons per control area,
o Maximum quantities increased by 100% if stored in approved flammable liquid storage cabinet or safety
cans;
 resulting limit: Flammable Liquid (Class IB) to 240 gallons per control area. [Note 1]
o Maximum quantities increased by 100% if an approved sprinkler system is in place;
 resulting limit: Flammable Liquid (Class IB) to 240 gallons per control area. [Note 2]
o If both an approved gas cabinet and approved sprinkler system are used, the 100% increase in MAQ is
applied accumulatively;
 resulting limit: Flammable Liquid (Class IB) to 480 gallons per control area. [Notes 1 & 2].
o No limit if building has an automatic fire sprinkler system throughout installed per NFPA 13 Standard for
the Installation of Sprinkler Systems, and designed per NFPA30-2012 Chapter 16. [Note 4]
Outdoor MAQ:
o not defined (no limit criteria)
o Storage is limited per Table 15.3 Storage Limitations for Outside Storage (per Pile):
 Containers: 2200 gallons
 Portable Tanks & Metal IBCs: 4400 gallons
 Rigid Plastic & Composite IBCs: Not Permitted
o Outdoor storage adjacent to a building - for containers, IBCs, or portable tanks: [NFPA30-2012 15.4.1]
 limited to 1100 gallons (4160 L) per pile
 the adjacent building wall has an exterior fire resistance rating of 2 hours,
 no openings at or above grade on the adjacent building wall that are within 10 ft (3 m) horizontally
of the storage, and
 no openings below grade on the adjacent building wall that are within 50 ft (15 m) horizontally of
the storage,
 may be waived by AHJ if the building is one story, is of noncombustible or fire-resistive
construction, and devoted principally to liquid storage. [NFPA30-2012 15.4.2]
 may exceed 1100 gallons (4160 L) if stored at least 5 ft between piles, 50 ft from property lines,
and 10 ft from Street, Alley, or Public Way. [NFPA30-2012 15.4.4]
Container types & design & storage construction
o For fixed tanks that exceed 60 gallons (230 L), or portable tanks that exceed 660 gallons (2500 L),
or IBC that exceed 793 gallons (3000 L) capacity: [NFPA30-2012 21.1]
 of any shape, size, or type consistent with recognized engineering standards, [NFPA30-2012
21.3.2]
 made of steel or other noncombustible material, [NFPA30-2012 21.4.1]
 made of compatible materials to what's being stored, [NFPA30-2012 21.4.1.1]
 tanks may have combustible linings, [NFPA30-2012 21.4.1.4]
 designed and constructed per recognized engineering standards, including the following (design
standards for atmospheric tanks): [NFPA30-2012 21.4.2.1.1]
o API Specification 12B, Bolted Tanks for Storage of Production Liquids
Page 39 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
o
o
o
o
o
o


API Specification 12D, FieldWelded Tanks for Storage of Production Liquids
API Specification 12F, Shop Welded Tanks for Storage of Production Liquids
API Standard 650, Welded Steel Tanks for Oil Storage
UL 58, Standard for Steel Underground Tanks for Flammable and Combustible Liquids
ANSI/UL 80, Standard for Steel Tanks for Oil-Burner Fuels and Other Combustible Liquids
ANSI/UL 142, Standard for Steel Aboveground Tanks for Flammable and Combustible
Liquids
o UL 1316, Standard for Glass-Fiber Reinforced Plastic Underground Storage Tanks for
Petroleum Products, Alcohols, and Alcohol-Gasoline Mixtures
o ANSI/UL 1746, Standard for External Corrosion Protection Systems for Steel
Underground Storage Tanks
o UL2080, Standard for Fire Resistant Tanks for Flammable and Combustible Liquids
o ANSI/UL 2085, Standard for Protected Aboveground Tanks for Flammable and
Combustible Liquids
 low-pressure tanks (1.0 - 15 psi)
o API 620, Recommended Rules for the Design and Construction of Large, Welded, LowPressure Storage Tanks
o ASME Code for Unfired Pressure Vessels, Section VIII, Division 1
o For drums or other containers not exceeding 119 gallons (450 L), or portable tanks not exceeding
660 gallons (2500 L), or IBC not exceeding 793 gallons (3000L) capacity: [NFPA30-2012 9.1.1]
Approved containers, IBC, and portable tanks: [NFPA30-2012 9.4.1]
 Metal: US DOT Title 49CFR Parts 100-199 or Part 6 of UN Recommendations on the Transport of
Dangerous Goods.
 Plastic: US DOT Title 49CFR Parts 100-199 or Part 6 of UN Recommendations on the Transport
of Dangerous Goods.
 Fiber Drums: National Motor Freight Classification (NMFC) Items 294 & 296, or Uniform Freight
Classification (UFC) Rule 51 for types 2A, 3A, 3B-H, 3B-L, or 4A.
o For rigid nonmetallic intermediate bulk containers
 must be listed and labeled for fire performance. [NPFA30-2012 9.4.1.1]
 US DOT Title 49CFR Parts 100-199 or Part 6 of UN Recommendations on the Transport of
Dangerous Goods, for Classes 31H1, 31H2, and 31HZ1
 National Motor Freight Classification (NMFC), or the International Safe Transit Association for
liquids that are not classified as hazardous by the US DOT Title 49CFR Parts 100-199 or Part 6 of
UN Recommendations on the Transport of Dangerous Goods. [NPFA30-2012 9.4.1(5)]
o Maximum allowable size for Containers, IBCs, and Portable Tanks - for Class 1B per Table 9.4.3;
 Metal drums (e.g.; UN 1A1/1A2): 119 gallons (450 L)
 approved Metal Portable Tanks & IBCs: 793 gallons (3000 L)
 approved Plastic or Metal (other than drums): 5.3 gallons (20 L)
 Rigid Plastic, Composite IBCs, Fiber Drum: not permitted; except: Plastic Containers are permitted
up 60 gallons (230 L) capacity of Class 1B water-miscible liquids. [NPFA30-2012 9.4.3.1]
Piping, Valves, Regulators, Fuel Controls
per Chapter 27
o "Pipe, valves, faucets, couplings, flexible connectors, fittings, and other pressure-containing parts shall
meet the material specifications and pressure and temperature limitations of ASME B31, Code for
Pressure Piping…" [NFPA30-2012 27.4.1]
o "Nonmetallic piping shall be built and used within the scope of their approvals or within the scope of UL
971, Standard for Nonmetallic Underground Piping for Flammable Liquids." [NFPA30-2012 27.4.6.2]
Vents & Ventilation
o "When a process heats a liquid to a temperature at or above its flashpoint (e.g.; burner)…
(1) The process vessel shall be closed to the room in which it is located and vented to the outside of the
building….
(3) The process vessel shall be equipped with an excess temperature control set to limit excessive heating
of the liquid and the subsequent release of vapors." [NPFA30-2012 17.3.7]
o Portable Tank & IBC vents:
 portable tanks or IBCs require emergency venting devices installed on top to limit internal
pressure under fire exposure to 10 psi (70 kPa) gauge or 30% portable tank bursting pressure.
[NFPA30-2012 9.4.2]
Page 40 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers

total venting capacity not less than specified in NFPA30-2012 22.7.3.2 or 22.7.3.4. [NFPA302012 9.4.2.1]
 require at least 1 pressure-actuated vent, opening at not less than 5 psi (35 kPa) gauge pressure,
capable of 6000 ft3 (170 m3) of free air per hour at an absolute pressure of 14.7 psi (101 kPa) at
60F (15.6C). [NFPA30-2012 9.4.2.2]
 fusible vents if used must activate at or below 300°F (150°C); type that softens to failure at
300°F (150°C) maximum under fire conditions may be permitted for the entire emergency
venting requirement. [NFPA30-2012 9.4.2.3]
o Tanks vents:
 sized to either API Standard 2000, Venting Atmospheric and Low-Pressure Storage Tanks, or
another approved standard.
 The normal vent shall be at least as large as the largest filling or withdrawal connection, and not
less than 1.25 in. (32 mm) nominal inside diameter.
 "Tanks and pressure vessels that store Class IB…liquids shall be equipped with venting devices
or with listed flame arresters. When used, vent devices shall be closed, except when venting
under pressure or vacuum conditions." [NPFA30-2012 21.4.3.9]; waived if - when obstructed likely to cause damage to tank. [NPFA30-2012 21.4.3.11]
 vent not required for interstitial space between primary & secondary containment. [NPFA30-2012
A21.4.3.2]

Labeling & Signage
Labeling (Storage Cabinet):
o shall be marked - attached to upper portion of cabinet's front door or frame - as follows:
"WARNING:
FLAMMABLE
KEEP FIRE AWAY"
uppercase letters, contrasting color to the background, 2.0 inch (50mm) minimum height for
"FLAMMABLE", 1.0 inch (25mm) minimum height for "KEEP FIRE AWAY".
May use other languages and international symbols (flame in a triangle, burning match in "no" circle).
[NFPA30-2012 9.5.5]

Fuel Transportation & Site Refueling
o Class 1 liquids are kept in closed containers or tanks when not actually in use. [NFPA30-2012 18.4.1]
o Liquids transferred by inert gas pressure are permitted if all fluid storage & handling is designed for the
anticipated pressure, overpressure or pressure-relief devices are provided, and only inert gas is used.
[NFPA30-2012 18.4.4]
o Areas where liquids are transferred from one container or tank into another require:
 separation by distance or fire-resistance construction from other potential ignition sources,
 drainage or other spill control, and
 natural or mechanical ventilation per NFPA30-2012 17.11. [NFPA30-2012 18.5.6]
 mechanical ventilation required for Class 1 liquids dispensed inside a room. [NFPA30-2012
18.6];
 shall provide at least 1cfm exhaust air for each sq. ft. of floor area (0.3 m 3/min./m2),
but not less than 150 cfm (4 m 3/min.), [NFPA30-2012 18.6.5]
Page 41 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers


have an interlocked audible alarm that sounds if ventilation fails. [NFPA30-2012
18.6.5.1]
 exhaust air outlet on one side of a room within 12 inches (300 mm) of the floor, and
one or more inlets on the other side of the room within 12 inches (300 mm) of the
floor. [NFPA30-2012 18.6.1],
 and exhaust discharged outside the building unless recirculation is used; recirculation
requires continuous monitoring and provide full exhaust to the outside if vapor
exceeds 25% LFL. [NFPA30-2012 18.6.3 & 18.6.3.1]
Fire & Emergency Response
per Chapter 6
o Hazard analysis exempted: Exemption No. 1: Operations where liquids are used solely for on-site
consumption as fuels. [NFPA30-2012 6.4.1]
o Fire Protections and Fire Suppression Systems (general requirements) per NFPA30-2012 6.7.
o A written emergency action plans is required, including procedures for response to leaks or fire,
maintenance, inspections, shutdown and isolation, etc. [NFPA30-2012 6.8.1]
Page 42 of 43
version: 5May2014
Fuel Cell Power Electrical Generators - Implementation Guide For Telecom Providers
By application:
Telecom Use
Other compliance requirements:
Network Equipment Building Systems (NEBS) - Telcordia
Telcordia (formerly Bell Labs, now a part of Ericsson) has created a series of standards for telecom applications that
cover construction, performance, reliability, and additional safety requirements.
NEBS compliance criteria is defined by each particular telecom carrier (if required).
FR-2063 defines NEBS equipment. The fuel cell power system is a standby generator; when used at a cell site is
considered part of the Outside Plant equipment.
A guide to understanding NEBS criteria and document requirements entitled "Roadmap To NEBS Documents" is
provided by Telcordia at:
http://telecom-info.telcordia.com/ido/PDF/ROADMAP_TO_NEBS_1.i07.pdf

SR-3580
NEBS Criteria Levels: Level 1, Level 2, Level 3

GR-63-CORE
Physical Protection

GR-78-CORE
Generic Requirements for the Physical Design and Manufacture of Telecommunications
Products and Equipment

GR-487-CORE
Generic Requirements for Electronic Equipment Cabinets

GR-1089-CORE Electromagnetic Compatibility and Electrical Safety
Page 43 of 43