Qwest Communications

advertisement

Installation Quality Bulletin

Installation Quality Bulletin Number: 03-06 Issue 2

To: All Installation Suppliers / Central Office Operations

Representatives / Design Engineering Representatives / Quality

Representatives / Corporate Real Estate Representatives

Date: Wednesday, September 10, 2003

From: QWEST Installation Quality Assurance

Subject: Proper Procedures for Floor Anchor Installation and

Floor Anchor Hole Repair. Changes to TABLE A.

Action Required :

YES:  NO:

Description of Bulletin:

The purpose of this Bulletin is to provide all Qwest-approved installation Service Suppliers with the correct information regarding the proper floor anchor installation and floor hole repair procedures defined by the Qwest Corporate Real Estate organization for Qwest central office locations.

If there are any doubts about the quality or condition of the concrete flooring prior to, or during equipment removal or installation, Qwest Corporate Real Estate Design Construction or Property

Management should be consulted. New holes are normally drilled with floor tile in place but it is necessary to inspect the concrete for excessive surface and subsurface cracking as new anchors are installed. New holes should be drilled with a uniform diameter throughout the embedded anchor depth.

To assure the performance of new anchors, it is important to properly fill and repair old anchor holes with an approved filler material. This minimizes crack propagation and preserves the strength of the concrete where future anchors may be needed.

Service Supplier inquiries regarding floor anchor placement should be directed to Qwest

Technical Publication 77350 Issue M, Par. 3.21 - 3.23. Upon completion of the removal of equipment bays or other items anchored to the floor, the Service Supplier shall repair the vacated floor anchor holes in accordance with the procedures listed within this Bulletin.

Specific questions regarding floor hole repair or floor tile repair should be directed to the Qwest

Real Estate Work Environment Center (referrals will be made to the respective Real Estate

Project Management local office) at 1-800-201-7033.

Acknowledgments to Howard Cooper, CRE Senior Project Analyst, for his contribution to the technical content of this Bulletin via his source text, “Concrete Floor Post – Installed Anchor

Installation and Repair” dated Nov. 25, 2002.

Qwest Installation Quality Assurance

Jeff Bostow

612-798-2460 mailto: jbostow@qwest.com

METHODS & PROCEDURES FOR INSTALLING CONCRETE EXPANSION ANCHOR

2-1/2 INCH EMBEDMENT

Concrete Floor Drilling and Anchor Installation Procedure:

1.

Drill using 18-mm diameter masonry diamond drill to an embedment depth of 60-mm

(2-1/2 inches).

2.

Clean hole using a High Efficiency Particulate Arrestor (HEPA) vacuum to remove loose debris.

3.

Inspect the hole for uniform diameter top to bottom.

4.

If hole diameter is uniform, then install the anchor per Hilti Product Technical Guide

2002, Instructions for Heavy Duty Sleeve Anchor 4.3.2.4

. Refer also to Table

A.

5.

If hole diameter is not uniform, drill out a larger hole centered over the old hole using a minimum 44-mm (1-1/2 inches) diameter masonry diamond drill to a minimum embedment depth of 60-mm (2-1/2 inches).

6.

Clean hole using a High Efficiency Particulate Arrestor (HEPA) vacuum to remove loose debris.

7.

Wet surfaces and fill the hole flush with rapid setting high strength anchoring cement

(Quikrete 1245 or equal, with final set time 10 to 30 minutes per ASTM C191) and allow to set for 24 hours.

8.

Drill out a new 18-mm diameter hole and repeat this process starting at step 1 above.

REUSING EXISTING ANCHOR LOCATIONS:

NOTE: It is preferred to use a new anchor location if possible.

1.

Centered over the existing anchor location using a core drill with a minimum 44-mm (1-

1/2 inches) diameter, cut the new diameter to a minimum depth of 60-mm (2-1/2 inches).

2.

Inside the core carefully cut, break out, chip, and remove concrete debris and the old anchor insert.

2

3.

Clean hole using a High Efficiency Particulate Arrestor (HEPA) vacuum to remove loose debris.

4.

Wet surfaces and fill the hole flush with rapid setting high strength anchoring cement

(Quikrete 1245 or equal, with final set time 10 to 30 minutes per ASTM C191) and allow to set for 24 hours.

5.

Drill out a new 18-mm diameter hole centered on the new anchoring cement and install the new anchor using the above.

Concrete Floor Drilling and Anchor Installation Procedure

FILLING AND REPAIRING ANCHOR HOLES

1.

Remove stud bolt, or if necessary cut, grind flush with floor using HEPA vacuum.

2.

Fill the hole flush with rapid setting high strength anchoring cement (Quikrete 1245 or equal, with final set time 10 to 30 minutes per ASTM C191).

3.

Do not cover with tile.

MATERIAL SPECIFICATION FOR ANCHOR HOLE REPAIR

When removing equipment frames and repairing anchor holes use a designated “Repair Mortar” formulated for high strength to make structural repairs to concrete and masonry surfaces.

Quikrete 1245 or equal, with a final set time 10 to 30 minutes, is approved by Qwest CRE for this application. The mortar must be designated for concrete repair. To later locate repaired holes, do not cover with floor tile.

APPLYING MORTAR

The repair mortar should be applied to a damp surface. Pour the mortar and fill anchor hole.

After initial set, finish flush with exiting floor. Final set time is about 40 minutes. Do not cover with tile.

ADDITIONAL ITEMS WITH RESPECT TO ANCHOR HOLE REPAIR

NOTE: If floor tile repair work is also required as a result of floor tile damage due to equipment removal, the Service Supplier will not attempt to repair or replace the damaged tile(s). The Service Supplier is instructed to contact Qwest Corporate Real Estate Property

Management through the Work Environment Center (WEC) at 1-800-201-7033.

The Service Supplier should use this same contact number above in the event that the subsequent equipment removal has created a “structural issue” with the floor integrity.

3

TABLE A

HILTI TELECOMMUNICATIONS ANCHOR SPECIFICATION FOR QWEST LNS

HLSB M 12/12.7 *60 – Used for battery stands (only) in DC Power Rooms

HLSG M 12/0 *60 – Used in Toll Rooms and DC Power Equipment

APPLICATION

ZON

E

HILTI

P/N

SIZE

BIT EMBEDMENT MIN BASE

DIA DEPTH THICK.

TELECOMMUNICATIONS

ANCHORS

ALLOW.

LOADS

HSLB M 12/12.7 *60

Concrete

Compressive Strength

HSLG M 12/0 *60

Torque Cap version for High Seismic

Risk Zones 2b thru 4 with up to ½ inch fastening thickness.

Stud anchor for High Seismic applications in shallow embedment

Torque nut shears off at 60 ft-lbs leaving

2b,3 97413007 12mm 18mm

4

2b,3

4

230712 12mm 18 mm

60 mm

2 1/2"

60 mm

2 1/2"

100 mm

4"

100 mm

4"

Tensile

2740 lbs

1965 lbs

Shear

5040 lbs

3330 lbs.

(3000 psi)

Tensile

2335 lbs

1965 lbs red seal for quality assurance and Shear installation integrity. 2375 lbs

Concrete

Compressive Strength

2 -2X2 " washers 2680 lbs.

(3000 psi)

Note: This information is available from Hilti only on request and is not part of the Hilti product catalog. Anchor performance specifications are not available on Hilti letter head documentation.

Download